All techniques for measuring earth resistance are made by way of
circulating a test current between the earth system under study and r
remote electrode, measuring at the same time the change of voltage of the
earth system relative to a potential reference electrode.
The most commonly used method for the measurement of earth-electrode
resistance and also one which has been found to be most reliable is the
so-called "fal1-of-potential" method. This method, Figure 8.10, requires
two reference earth rods, refer' J to as potential electrode P and
auxiliary current electrode C. A. alternating test current is circulated
between the electrode system E and C. The potential drop V is then
measured (usually using a null-balanced technique of potential
measurement), between E and P. By repeating these measurements for a
variety of distances 'd' of the electrode P, away from the earth system
E, it is possible tc derive a resistance curve of the form shown in Figure
8 .10 .
The above method encounters difficulties when the resistance of a large
area earth-electrode system, consisting of a number of rods, trenches,
etc., all connected in parallel, is required to be measured. A major
problem has been the need for large distances (about 1 km) between the
auxiliary current electrode C and the earth system E so as to validity
assumptions. This introduces such problems as finding a clear run for
the required length and also long leads which possess reactances and which
can cause difficulties vith measuring equipment. To solve these problems,
Tngg^10^ has devised the "intersection Method" which eliminates the use
of very long leads. It is concluded that a more accurate measurement of
resistance is achieved by placing the electrode P at a distance which is
62% of the total distance D between the earth system E and the auxiliary
current electrode C, as illustrated in Figure 8.10.
An additional guide to accurate measurement is the minimum requirement
that the distance D be five time the diagonal across the earth-electrode
system being measured. Furthermore, it has been sugge^ ed that tests in
iwo directions at right angles be made, both as a check and to enable the
electrical centre of the earth system to be determined more accurately.
However, both the above points may be difficult to meet in practice.
Th* Earth Electrode System251
FIGURE B. 10 FALL-OF-POTENTIAL EARTH
RESISTANCE MEASUREMENT
The Earth Electrode System 252
Field testing of large earthing systems, which include extended earths,
by the usual earth resistance meter (earth meggar) may fail to give
realistic values because of the inductive component in the earthing
impedance or the increase of ac resistance over dc resistance (normally
this happens when the earth resistance is less than 0.5 Q), and due to
inductive interference in the leads used for the measurement. In these
cases, it has been suggested^111 ̂that the heavy current injection method
be applied, at or close to, the power frequency. For a more complete
treatment of this method the reader is referred to this paper by Seljeseth
et al^11^ . Other methods which are variations of this method include
the 'synchronous power-frequency method', 'the beat-frequency method' and
'the interference compensation method', which are all described in the
same paper.
An interesting method described in a paper by Sarmiento et al^187 ̂ is the
frequency scanning method which falls in the class of low current
injection methods. This method uses digital techniques and allows for a
complete plot of impedance and phase angle over a wide frequency range.
Figure 8.11 illustrates the general lay-out for the frequency method.
The signal source consists of a pseudorandom noise generator, noise
conditioning filter and a power amplifier of about 1.5 kW. The bandwidth
of the noise source is set from 0 Hz to 400 Hz. An external filter is
used to limit the noise signal to a range of 10 to 400 Hz in order to
protect the power amplifier output transformer and the power transistors
from the effects of low frequency saturation. The digital signal analyser
has to be a dual channel instrument. With the instruments set up as shown
in the figure, the current and voltage signals are first filtered, then
digitised and transformed in the frequency domain through a FTT (fast
fourier transform) routine. Using the transfer function of the spectrum
analyser, the display (either CRT or X-Y plotter) will show the impedance
magnitude and phase over the selected frequency range.
The Earth Electrode System 253
Figure 8.11 Frequency Scanning Method
8.8 CORROSION AND BONDING CONSIDERATION
The problems of bonding and corrosion of earth systems require particular
consideration due to the harsh nature of the industrial plant environment.
To ensure the integrity of the earth system as well as the connections
made to it, such factors as electrode material, soil resistivity and
environment conditions should bo taken into account. The subject of
corrosion and corrosion prevention is a science unto itself and is beyond
the scope of this study. Salient points are noted below and should be
considered when engineering an earth system.
The causes of corrosion of both electrodes and bonds are manifold and
include the following^3 :
The Earth Electrode System 254
1. Differential aeraticn of the soil - arising during the backfilling
process and through uneven distribution of moisture in the vicinity
of the electrode.
2. The acidity and chemical content of the soil as well as the presence
of foreign materials including cinders, »crap metal, or organic
material.
3. The presence of stray electric currents - particularly dc - perhaps
originating from nearby traction systems.
4. The interconnection of dissimilar metals in the soil or in the open,
where moisture is present.
Three basic techniques can be used to lessen the corrosion rate of buried
metals. The obvious method is to insulate the metals from the soil. This
method is however not a acceptable corrosion preventive for earth
electrodes.
The '.e^ond technique, and one which should be considered at the design
stage after a site survey, is avoiding the use of dissimilar metals to
reduce galvanic corrosion. For example, if all metals in contact with
the soil are of one type (such as iron or lead or copper), galvanic
corrosion is minimised. Copper is a desirable material for the earth
electrode system; apart from its high conductivity, the oxidation
potential of copper is such that it is relatively corrosion resistant.
Since copper is cathodic relative to the more common structural metals,
its corrosion resistance is at the expense of other metals, such ac iron
and aluminium. As an alternative to copper, steel rods may be used,
especially if the earth electrode system is installed in an area where
there are known to be many buried galvanised steel pipes, buried
structural steel, etc.
The third technique, for combating corrosion caused by strong direct
currents and dissimilar metal unions is commonly called cathodic
protection. Cathodic protection may be implemented through the use cf
sacrificial anodes or the use of an external current supply to counteract
The Earth Elertrode System255
the voltage developed by oxidation. Discussion of cathodic protection
is beyond the scope of this study. For detailed information refer to the
(1891
relevant texts and the paper by Nelson et al
Another approach which offers advantages in corrosive soils is the use
of concrete encased galvanised steel electrode systems. In addition to
all of this, surface connections should also be protected from moisture
and made accessible for inspection. Bonds are best brazed or welded and
a number of specialised techniques are available for this purpose (See
Chapter 9 on bonding).
8.9 DESIGN AND INSTALLATION GUIDELINES
1. Establish the design objectives in terms of required value of earth
system resistance. As discussed in Section 8.1 the earth electrode
system for a facility should exhibit a resistance to earth of 5 ohms
or less. However, it should be noted that the final value obtained
weald be dictated by such factors as soil resistivity, moisture
content, rock formation and landscape features, as well as r cost
analysis which would take account of the costs of various alternative
design approaches.
2. Considering the relative advantages and disadvantages given in Table
8.6, select and configure a type of earth system most appropriate for
meeting the functional requirements of the facility at the site under
construction. In addition, cognizance should also be taken of such
factors as the final leakage resistance, the geometric disposition
which influences surge impedance, the resistivity depth profile and
the personnel safety considerations as well as the need to minimise
surface potential gradients, particularly during lightning
conditions.
The Earth Electrode System 256
Advantages Disadvantages
Vertical Rods
Horizontal Grid
Plates
Horizontal Wires
(Radials)
Incidental
Electrodes
(Utility pipes,
building founda
tions, burled
tanks)
TABLE 8.6 OF THE
Straightforward design.
Easiest to instaH (parti
cularly around an existing
facility.) Hardware read
ily available. Can be ex
tended to reach water
table.
Minimum surface potential
gradient. Straightforward
Installation if done before
construction. Can achieve
low resistance contact in
areas where rock formations
prevent use of vertical rods.
Can be combined with verti
cal rods to stabilize resis
tance fluctuations.
Can achieve low resistance
contact in limited area.
Can achieve low resistance
where rock formations pre
vent use of vertical rods.
Low impulse impedance.
Good RF counterpoise when
laid in star pattern.
Can exhibit very low resis
tance (if electrically con
tinuous. Generally lowest
initial cost (borne by
others).
RELATIVE ADVANTAGES AND PRINCIPLE TYPES OF EARTH
(SOURCE: DENNY*3))
High impulse impedance.
Not useful where large
rock formations are
near surface. Step
voltage on earth sur
face can be excessive
under high fault cur
rents or during direct
lightning strike.
Subject to resistance
fluctuation with soil
drying if vertical rods
not used.
Most difficult to
install.
Subject to resistance
fluctuations with soil
drying.
Little or no control
over future alterations.
DISADVANTAGES ELECTRODES
The Earth Electrode System 257
3. The general electrode arrangement should broadly conform to the
perimeter of associated structures on the site - as shown in Figure
8.12. The minimum spacings between rods should exceed twice the
individual rod lengths. The rods should preferably be copper-clad
steel ("Copperweld") or stainless steel. For horizontal conductor
(trench earth), preferred material is electrical grade copper and the
minimum cross-sectional area should not be less than 50 mm1 or
diameter not less than 9.5 mm. Rectangular conductors should
preferably be about 30mm x 3mm or 50mm x 3mm.
A. Where two or more structures or facilities are located in the sane
general area and are electrically interconnected with signal,
control, and monitor cables, a common earth electrode system may be
provided, or in the case of extended inter-connections, separate
earth electrode systems should be bonded with low-impedance buried
horizontal trench earth systems. Examples of the two approaches are
shown in Figure 8.13. Note, however, that the screens of data, signal
or control cables should not be used as the only interconnecting
conductors between two structures, at least one dedicated
interconnecting conductor should be connected in parallel between the
sa*ne points.
5. Access to the -«arth electrode system for the purpose of periodic
measurements should be provided at certain strategically chosen
positions in the system.
6. All joints in the earth electrode system should preferably be brazed
or welded and proprietary methods are available for this purpose
("Cadweld", for example). Bolted connections should be used where
these are accessible for regular inspection and testing and where such
connections will not be subjected to a corrosive environment.
The Earth Electrode System 258
The Earth Electrode System
259
\ r — r----BDNDED IF
-I I2SJ ]------•
AUXILIARY STRUCTURE- NECESSARY
RADIALS —---- DRIVEN ROD
LOOP TRENCH EmRTH
a) ADJACENT STRUCTURES
\\
A\
\
b) INTERCONNECTED SYSTEMS
FIGURE 8.13 ELECTRODE CONFIGURATIONS FOR ADJACENT AND INTERCONNECTED STRUCTURES
The Earth Electrode System 260
CHAPTER 9
Chapter 9
261
9.0 GROUNDING OF CONTROL SYSTEMS
9.1 INTRODUCTION
This chapter is essentially concerned with the aspects of implementing
the concepts, tachniques and guidelines developed in earlier chapters.
To ease understanding, electronic systems are classified as either
isolated or clustered systems. The grounding of typical process '•.ontrol
system configurations - i.e. centralised, decentralised and distributed
systems * are analysed in terms of these two systems. It is shown that
most system grounding requirements can be viewed as an exercise in the
grounding of a majot clustered system. This leads to the presentation
of grounding guidelines for clustered system, which include signal
grounding networks, computer grounding, I/O rack grounding and facility
grounding. Bonding is then examined and practical guidelines suggested.
9.2 SYSTEM GROUNDING REQUIREMENTS
The term system is wadely used to mean many things and generally
encompasses what the user wishes. It could, for example, represent
electrical circuitry totally within the confines of a case, cabinet, or
rack, or it could refer to an extended collection of equipment racks or
consoles distributed over a wide geographical area. In the process
control sense the term system would represent the full collection of items
named in Chapter 2, and would include sensors, actuators, signal
conditioners, process control units and data processing units. These
items can be configured in many different ways. It can be centralised,
decentralised or distributed (hierarchical), as illustrated in Figure
9.1. These configurations refer to both functions and to location.
Grounding of Control Systems 262
Grounding of Control Systems
263
FIG
URE
9.1
- DIF
FERENT
SYSTEM
ST
RU
CT
UR
ES
In any process area the sensing and actuation is always done locally.
The ellipsoids in Figure 9.1 refer to the different control system
functions which can be functionally and/or geographically distributed.
Of importance is the aspect of geographical distribution since this would
determine the earthing and grounding requirements. Jn general, these
requirements will depend upon the type of system configuration.
One way of distinguishing between different types of systems is to examine
the manner by which power is obtained and how the equipment elements are
interconnected with each other and with other systems. These two
considerations form the basis for the rationalisation of the earthing end
grounding requirements of the different types of systems. To ease
analysis of systems, two distinct types of systems are identified; namely
isolated and clustered systems. These two systems form the building
blocks upon which rationalisations of the earthing and grounding
requirements of complex system configurations can be accomplished. The
properties of these two systems and the associated grounding issues are
presented below.
9.2.1 ISOLATED SYSTEMS
An isolated s y s t e m ^ is one in which all functions are accomplished with
one equipment enclosure. Typical examples are handheld calculators,
desktop computers (off line), radios and television receivers. A
characteristic feature is that only a single power supply housed within
the enclosure is associated with such systems. For personnel and/or
lightning protection, only one ground connection is required which could
be structure or earth ground. As the name suggests, no outside
interconnection (power or signal) with other equipment or devices, which
are grounded, are present or needed.
The grounding requirements for isolated systems are as illustrated in
Figure 9.2. This typically includes a three wire input where the third
wire (green or earth) provides the ground, if single-phasc j,owered.
Grounding of Control Systems 264
Figure 9.2 Grounding of AC Powered Isolated System
Refer to Figures 7.2 and 7.3 of Chapter 7 for the required earthing and
grounding configurations for single-phase and three-phase systems,
respectively. To prevent flashover or arcing, good practice dictates that
a safe distance between isolated systems and lightning-down conductors
should be maintained (See Chapter 6). Also, adequate screening and
separation must be provided in a very high RF field strength environment.
9 .2 .2 CLUSTERED SYSTEMS
A clustered system*' ̂ is characterised as having multiple elements, such
as equipment racks and consoles, in a localised area. Figure 9.3
illustrates a typical clustered system.
Grounding of Control Systems 265
U j
_Jo
z
□u
3:u
f-
</)
>-
(/)
n
0-
a:
□o
a
u
_ IA © j <
/ “
sW
E»
S2C/3
aEdOS
w
E-CO
D
i—J
o
CO
05w
OS
tD
U
»—<
fcl
Grounding of Control Systems
266
Examples of clustered systems Include minicomputers, medium scale data
processors, and multi-terminal processing systems.
A distinguishing feature of a clustered system is that each element is
powered from one common power source, i.e. a generator or a single ac
power connection. Multiple interconnecting cables (signal, power and
control) exist between the different units and equipment but not with any
other system, i.e. another system in another building. Thus, a clustered
system is a self-contained system that requires no interaction with any
other system other than between the members of the system itself.
Grounding for clustered ayeterns requires that only one connection be made
to facility (structure) ground to realise personnel safety and lightning
protection requirements. Again, the earthing and grounding arrangements
illustrated in Figures 7.2 and 7.3 for single-phase and three-phase
networks apply. The safety ground conductor connected to the equipment
case would provide the necessary structural connections, as illustrated
in Figure 9.4.
The signal ground referencing scheme us«d ' tween the elements of the
system would reflect the particular signal characteristics (frequency,
amplitude, etc) of the various pieces of equipment (See Chapters 3 and
5). This could be single-point, multiple-point or hybrid grounding. A
more detailed discussion of signal grounding of clustered systems is
presented from Section 9.6 onwards.
9.3 GROUNDING OF CENTRALISED SYSTEMS
A centralised system, as the name suggests, is functionally and/or
geographically centralised where all process measurements are biought
into a central-informat ion processing centre. This system is clearly
different from an isolated or clustered system in that integral elements
of the system such as transmitters, sensors and actuators extend out from
the central area, usually at long physical and electrical distances.
Grounding oi Control Systems 267
Grounding of Control Systems
268
FIGURE 9.4 POWER GROUNDING OF CLUSTERED SYSTEMS
The important point to note about this system is that it is powered by a
single power source and connections are not made any where except at the
main element. In addition, extended elements obtain their power from the
central element.
The grounding of a centralised system should be viewed as an exercise in
the grounding of a complex central or primary element and as such could
be thought of as a major clustered system. Hence, the grounding
philosophy set forth in Chapter 7 and the interference minimisation
techniques presented in Chapters 4 ana 5 should be applied. In addition,
the guidelines presented in Section 9.6 should be observed.
Depending upon the operating frequency ranges and signal levels of the
extension elements and the characteristics of the EM environment, either
a single-point (starpoint ground) configuration or a multiple-point
configuration may be required. Since >.he operating frequency range of
transducers and sensing elements are generally narrowband and
low-frequency, a single-point grounding system is desirable. However,
depending on the EM environment, multiple-point grounding may be
required. Though not good practice in general, such multiple-point
grounding can be effective in some high energy cases. Thus each situation
should be considered on its own merit and the best configuration
determined experimentally.
Sxnc« the central element forms the reference base, all the extended
elements should be floated or balanced. Also field wiring should be
twisted pair or balanced lines. Shield integrity should not be
compromised. The good practice techniques suggested in Chapters 4 and 5
should be applied. In more critical circuits, isolation, shielding,
filtering and mode conversion must be considered.
Grounding of Control Systems 2b9
9.4 GROUNDING OF DECENTRALISED SYSTEMS
In a functionally decentralised system, the information processing is
also done locally as the sensing and actuating for each control loop or
group of loops. Thus several local systems are contained and operating
in the same general process area. Typically, decentralised systems share
the primary power sources. The grounding guidelines presented for
centralised systems would apply to each localised system. However, these
systems may be located in an inherently noisy environment and thus run a
high risk of interfering with each other and being susceptible to
interference i,z& cility noise and the external environment. Thus, in
addition to having grounding requirements like those discussed for
distributed systems (See in Section 9.5), additional isolation, shielding
and filtering ars necessary to minimise system interference.
9.5 GROUNDING OF DISTRIBUTED SYSTEMS - HIERARCHICAL
Distributed systems, as already noted in Chapter 2, are systems which are
functir 'ally and geographically distributed on site. Typ'-.ally th-*s
means physical separation of major elements in a way that requires
equipment or cluster of equipment to be variously fed from different pow«.r
outlets, branch circuits, different phases of the line or even different
transformer banks. This could also mean distribution ol equipment in a
plant close to the process.
Distributed systems are characterised by multiple conductor (signal, data
and control) paths which typically leave a particular system element and
extend beyond the earth line area of such a system to connect to another
system element with its own earth system. In such cases conductor lengths
are likely to be greater than X/15 at frequencies where an interference
threat exists. Other examples besides the distributed process control
system include environmental monitoring and control, communications
switching and computer nets.
Grounding of Control Systems 270
Effective grounding of distributed systems to achieve the required safety
and lightning protection for equipment and personnel, while minimising
noise and EMI, requires cereful application of the principles set forth
in previous Chapters, particularly Chapters 4, 5 and 6. Due to the
variety and multiplicity of configurations available on site, it is not
considered prudent to describe a stereotyped network. However, some
general guidelines for proceeding are presented.
In any new installation planned for distributed control careful
consideration should be given to how control is tc be distributed. This
is essential because this will not only help resolve the earthing and
grounding issues but also result in cost savings through proper
installation, which is the real cost. Thus, it is recommended that I/O
clusters be assembled together to minimise wiring to sensors and actuators
while also maintaining closely interdependent I/O within the cluster.
Also one or more controllers should be specified at the centre of each
cluster for local control at that location. This then constitutes a major
element where the different types of equipment is essentially located at
a particular location. Major elements in the plant can then bo
interconnected via a network (serial hiway) to provide for interdependent
I/O between the elements. The earthing and grounding of a major element
should then proceed along the following lines.
Consider each major element as a clustered system where the grounding
practice should be applied along the lines discussed in Sections 9.2.2
and 9.6. In addition, each major element could be considered as a
centralized system and signal I/O grounding and shielding should observe
the guidelines suggested in Chapter 5.
In the case of inter-element I/O, each and every signal port on a
clustered subsystem that must interface with other portions of the total
system, i.e. other clustered subsystems, should be viewed as having tc
interface with a noisy "outside” world. As such, the techniques discussed
in Chapters 4 and 5 for separation, Isolation, and control of unwanted
coupling of radiated and conducted interference into the signal paths must
be fully employed. In addition, all cables are required to be shielded
and adequate protection applied to limit lightning induced surges into
Grounding of Control Systems 271
equipment (Refer to Chapter 6). Figure 9.5 illustrates protection of
low-level analog signals, which extend beyond the facility earth area,
against indirect lightning induced transients. The cable shield is
grounded directly at the signal termination point (equipment area) and
over a gas arrestor at the transducer end (to prevent hum during normal
operation). Obviously, discretion will be necessary and thus each signal
port should be considered on its own merit.
A particular case in point is *hat of clusters of equipment separated by
short distances, e.g. 200m. and concentrated in a localised general area,
as illustrated in Figure 8.14. The earthing requirements should follow
the general recommendations given in Chapter 8. Furthermore, where
practicable, the structures should share a common earth ground system to
minimise voltage differentials between structures. Grounding, bonding,
and protection (lightning) considerations for cables between structures
should folk.w the recommendations given in Chapter 6.
Of particular concern in a distributed system is the need to maintain
electrical integrity of the network in an inherently noisy industrial
environment. The choice of a network media should primarily be dictated
by consideration of the level to which it is immune to electrical noise.
Twisted pair is the least noise-immune; it relies on the network
receivers' ability to reject noise that appears equally on both
conductors. Unfortunately, the conductors do not always pick up noise
equally, causing unbalanced signal distortion before the signal reaches
the network receiver. Adding a shield to the twisted pair provides
another reference for noist rejection (earth ground), and another
"antenna"; it still is susceptible to electrical noise generated by
starters, welders, relays, and similar equipment. As a result, twisted
pair is only recommended for the less-noisy office environment, where the
implications of a network failure are not as drastic as they are for
control.
A acceptable choice for a network medium is coaxial cable which has
significantly better noise rejection capability than twisted pair.
However, < ’imitation of coax is that it is single-ended, and requires
transmitter impedance matching to avoid signal reflection.
Grounding of Cowtrol Systems272
sr.*
Grounding of Control Systems273
FIG
URE
9.5
ANALO
G
SIGNAL
PROTECTIO
N
OUTSID
L
TH
EEARTHIN
G
AR
EA
Furthermore, since the shield is part of the signal path, noise currerts
may flow in the shield in a strong EM environment. The alternative is
to consider twinax cables which, however, are more costly and thus less
preferred.
The grounding of coax cables should conform to a single-point arrangement
as outlined in Chapter 5. However, a prime concern is that of protecting
the coax against lightning surges. Since the network cable must span the
entire plant area, making it vulnerable to lightning damage (which is
intolerable in a distributed control system), additional protection is
required. In particular, where the voltage between core and sheath of
the coaxial cable is likely to exceed the acceptable levels for the
connected equipment a voltage limiting device is required. The choice
of device should depend on the frequency, i.e. devices with appreciable
capacitance are not suitable at high frequencies. Thus low capacitance
devices, typically 3 - 100 pF, sho*.Id be applied for protection against
lightning surges. For protection details refer to Chapter 6.
Fiber optic cable as a network medium for harsh environments is the most
ideal since noise rejection is not an issue. Hence, baring such problems
as handling, termination and cost, fiber optic cables in highly
recommended.
9.6 GROUNDING OF CLUSTERED SYSTEMS
The following discussion make specific reference to process control
computer systems which is considered to make up the clustered system.
This is purely intended to clarify the earthing and grounding issues
relating to such systems which is the subject oi discussion in this study.
Of prime importance in any process control computer system is the power
source. Since the clustered system forms the "nerve centre" of the plant,
the electric power serving the process control computer system must be
as "clean", stable, and reliable as> possible. This means the system must
Grounding of Control Systems 274
be protected against power outages, voltage fluctuations, distortions,
transients, surges, and spikes. These problems can occur in a process
or manufacturing plant no matter if power is supplied by the utility or
by an on-site generator. Various methods exists to "clean" up line power,
eliminate noise and to provide backup power in emergencies. These include
isolation transformers, voltage regulators, line conditioners, motor
generators, and uninterruptible power sources. Figure 9.6 illustrates a
typical configuration for providing clean, reliable p^wer for a process
control computer system.
The power system shown in the figure has two separate feeders, an
uninterruptable power source (UPS) and an isolation transformer. To
protect tilt system from high-speed transients and high-frequency
common-mod* and differential-mode noise, a isolation transformer is
required. Such a transformer has physically separated primary and
secondary windings and an electrostatic (Faraday) shield between the
windings. Most modern shielding methods can achieve a common-mode
reject n ratio of 10 000 000:1 or 140 dB. Typical specification figures
when selecting isolation transformers include^7^^:
o Input-to-output, capacitance of 0.005 pF or less;
o Leakage resistance of 1000 MB or greater between the primary and
secondary windings or between either windings and ground.
In addition, the following rules should be followed when setting up a
power source for process control computer systems
1. Primary power should come from the most reliable source available.
2. A second power feed, completely separate as to source and
distribution, should be provided for backup.
3. The power line feeder to the computer and instrumen ition system
should originate at the plant substation or main service entrance.
Grounding of Control Systems 275
w
H
sCO
02
fcu
E-
CL,S
o o
CO
CO
w
u
o05CL
05 O
k-
o
:z;I—I
C l5S
o05O
w
u
05D
O
CO
05
o a. u
<
I
CD05w
055o
>— i
Grounding of Control Systems
276
4. The computer system should be the only equipment that the feeder services.
5. Do not route the feeder close to other lines that supply noise-generating equipment.
6. The feeder should have enough capacity to accommodate future load increases.
The grounding of the clustered system, i.e. the cluster of process contra'1 computer equipment, should be in accordance with the recommendations given in Chapter 7, i.e. an isolated single point ground system is required. This means that the system's ground connects to earth ft only one point as illustrated in Figure 7.6 and Figure 9.6. This point may be facility earth ground or a dedicated earth rod.
As discussed in Chapter 7, two ground systems are desirable, namely, safety/equipment ground and signal ground. The signal ground referencing scheme used between the elements within the systems should reflect the particular signal characteristics (frequency, amplitude, etc) of the various pieces of equipment. This could be single-point or multiple-point grounding. However, since low frequency circuits and systems are particulaily susceptible to power line related noise and other low frequency interference, a single-point ground system should be provided.
9.6.1 LOW FREQUENCY SIGNAL GROUND NETWORK
The low frequency (below 1 MHz) grounding network for a facility should be configured as an isolated tree, like that shown in Figure 9.7. As shown, such a systec has grounding branches that serve various parts of the computer and instrumentation system.
Grounding of Control Systems 277
“ z z y u □X 2; »-HH- £ I- □ h C
ZD Oo a a( - Ul _J
<rorZDy- o o z ~Z> ZDa: □t— O'</) LD
a.
*cn£w2
ZD001o
3z0I—I1/5>“■u2 Ed t3 Of Ed OS
Et*
1sEhOCJ
E-<3Ed
ffiUCfi
I'-(~Ed
OE
Grounding of Control Systems 278
Major branches connect to the system ground plate, while minor branches connect to low frequency analog, digital or rack ground buses. Each
ground branch must be connected at one end only: the far ends of each ground branch must be disconnected from ground.
The system ground plate should be an isolated, 6.35mm (1/4 - in.) copper plate that is centrally located to provide a single point, and a low resistance interconnection between the signal ground network, the facility ground system, and the power system ground. The dimensions should be such that the plate will have enough tapped holes to accommodate all the ground cables or buses that need to be connected. An important point to note is that conduit, cable raceways, or build~.ig steel should not be used to distribute the single point ground from point to point in the system. The distribution should be through well insulated, dedicated cable of appropriate size - at least 25 mm*’ or more. Figure 9.8 shows the grounding of equipment racks in a single-point scheme with some typical mistakes. The routing of the conductor should be well planned to minimise conductor length as well as resistance. Long runs in parallel with unshielded power cables should be avoided and routed as far as possible from lightning down conductors.
After installation, but before interconnections with equipments t»re made,the isolation between the separate grounds networks should be checked.This is done by disconnecting one of the networks from the system groundplate end testing for continuity. At least 1 Mft should be registered
(3)between networks . The tests will detect and help eliminate unwanted ground loops. For further information on tests and measurement refer to Chapter 10.
9 .6 .2 GROUNDING COMPUTER COMPONENTS
Due to the fast rise time characteristics and high-frequency energies associated with computers, special care should be taken in creating a "interference-clean" signal/logic ground
Grounding of Control Systems 279
Author Ambelal Dependra
Name of thesis Earthing And Grounding For The Control Of Emi In Industrial Instrumentation And Control Systems. 1986
PUBLISHER: University of the Witwatersrand, Johannesburg
©2013
LEGAL NOTICES:
Copyright Notice: All materials on the Un i ve r s i t y o f the Wi twa te r s rand , Johannesbu rg L ib ra ry website are protected by South African copyright law and may not be distributed, transmitted, displayed, or otherwise published in any format, without the prior written permission of the copyright owner.
Disclaimer and Terms of Use: Provided that you maintain all copyright and other notices contained therein, you may download material (one machine readable copy and one print copy per page) for your personal and/or educational non-commercial use only.
The University of the Witwatersrand, Johannesburg, is not responsible for any errors or omissions and excludes any and all liability for any errors in or omissions from the information on the Library website.