+ All Categories
Home > Documents > 96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply · Uninterruptible Power Supply 96-01101 /...

96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply · Uninterruptible Power Supply 96-01101 /...

Date post: 23-Jan-2021
Category:
Upload: others
View: 11 times
Download: 0 times
Share this document with a friend
5
Uninterruptible Power Supply 96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply with Energy Saver design that is optimized to address the needs of A/V systems Pure Sine Wave technology with Automatic Voltage Regulation to improve the quality of power provided to the A/V system Surge suppression utilizes a clean line-to-neutral design that does not pass noise contamination to ground Models with bank control available Individual outlet control available Internet enabled models available, which include: Real time UPS monitoring via the Web Remote management and configuration of UPS via Web Browser or NMS (Network Management System) Auto-shutdown to protect servers/workstations from data loss due to power failure Schedule shutdown/start-up/reboot of the UPS Event logging to trace UPS operational history Data logging for analyzing power conditions Event notification via email and SNMP traps Supports TCP/IP, SNMP/HTTP, NTP, DNS, SMTP protocol MIB (Management Information Base) provided Quick installation and user friendly interface User upgradeable firmware via FTP Security management provided Control system integration via RS-232 and USB and analog I/O Load shedding allows extended run time for system-critical components by disconnecting power to less-critical components Line Interactive Technology Power Manager software allows extensive configuration and event notification capabilities Energy Saver design reduces power consumption by up to 75% when compared with traditional UPS designs 9’ SignalSafe power cord minimizes stray magnetic fields UL Listed in the US and Canada 96-01101 / rev. 2e / 2-2-12 / Uninterruptible Power Supply UPS-1000R UPS-EBPR EXCEPTIONAL SUPPORT & PROTECTION Features CUSTOMIZABLE SPECIFICATION CLIPS AVAILABLE AT MIDDLEATLANTIC . COM US: New Jersey • California • Illinois • Voice: 973-839-1011 Fax: 973-839-1976 • middleatlantic.com Canada: Ontario • British Columbia • Voice: 613-836-2501 Fax: 613-836-2690 • middleatlantic.ca
Transcript
Page 1: 96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply · Uninterruptible Power Supply 96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply with Energy Saver design that is

Uninterruptible Power Supply

96-01101 / rev. 2e / 2-2-12

Uninterruptible Power Supply with Energy Saver design that is optimized to address the needs of A/V systems

• PureSineWavetechnologywithAutomaticVoltageRegulation toimprovethequalityofpowerprovidedtotheA/Vsystem

• Surgesuppressionutilizesacleanline-to-neutraldesignthat doesnotpassnoisecontaminationtoground

• Modelswithbankcontrolavailable

• Individualoutletcontrolavailable

• Internetenabledmodelsavailable,whichinclude:

• RealtimeUPSmonitoringviatheWeb

• RemotemanagementandconfigurationofUPSviaWeb BrowserorNMS(NetworkManagementSystem)

• Auto-shutdowntoprotectservers/workstationsfromdata lossduetopowerfailure

• Scheduleshutdown/start-up/rebootoftheUPS

• EventloggingtotraceUPSoperationalhistory

• Dataloggingforanalyzingpowerconditions

• EventnotificationviaemailandSNMPtraps

• SupportsTCP/IP,SNMP/HTTP,NTP,DNS,SMTPprotocol

• MIB(ManagementInformationBase)provided

• Quickinstallationanduserfriendlyinterface

• UserupgradeablefirmwareviaFTP

• Securitymanagementprovided

• ControlsystemintegrationviaRS-232andUSBandanalogI/O

• Loadsheddingallowsextendedruntimeforsystem-critical componentsbydisconnectingpowertoless-criticalcomponents

• LineInteractiveTechnology

• PowerManagersoftwareallowsextensiveconfiguration andeventnotificationcapabilities

• EnergySaverdesignreducespowerconsumptionby upto75%whencomparedwithtraditionalUPSdesigns

• 9’SignalSafe™powercordminimizesstraymagneticfields

• ULListedintheUSandCanada

96-01101/rev.2e/2-2-12/UninterruptiblePowerSupply

UPS-1000R

UPS-EBPR

EXCEPTIONAL SUPPORT & PROTECTION™

Features

c u s t o m i z a b l e s p e c i f i c at i o n c l i p s a v a i l a b l e at m i d d l e at l a n t i c . c o m

US: New Jersey • California • Illinois • Voice: 973-839-1011 Fax: 973-839-1976 • middleatlantic.comCanada: Ontario • British Columbia • Voice: 613-836-2501 Fax: 613-836-2690 • middleatlantic.ca

Page 2: 96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply · Uninterruptible Power Supply 96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply with Energy Saver design that is

RackmountUninterruptiblePowerSupply(UPS)shallbeMiddleAtlanticProductsmodel#UPS-__R__(refertochart).UPSshallbelineinteractivewithAVR.Unitshallmeasure19.00”Wx3.50”Hx19.00”Dandoccupy2rackspaces.UPSshallhavearearmountingrangeof19”to32”andnotrequiremorethanonepersontomount.Unitshalloperateon120VAC/60Hzcurrent.Unitshallhaveanominaloutputof120V.Unitshallhaveacapacityof__VAand__W(refertochart).Unitshallhave(8)NEMA5-__receptaclesontherearoftheunit(refertochart).Unitshallhaveapriorityoutletbankconsistingof4outletsdedicatedtoensuremaximumruntimeofcriticalcomponents.Unitshallhaveanon-criticaloutletbankconsistingof4outletsdedicatedtoloadshedding,orindividualoutletcontrol,dependingonmodel.UnitshallbeIPenabled,dependingonmodel,orwhenusedwithoptionIPExpansioncard,model#UPS-IPCARD.RackmountUPSshallincludea9’__(refertochart)SignalSafe™powercordwithNEMA__(refertochart)plug.UPSshallhavesurgesuppressionthatutilizesacleanline-to-neutraldesignthatdoesnotpassnoisecontaminationtoground.RackmountUPSshallhaveahotswappablebatterythatallowsfora__minuteruntimeathalfloadanda__(refertochart)minuteruntimeatfullload.Rearofunitshallhaveinputsthatallowfortheinstallationofupto10additionalhotswappablebatteries.RackmountUPSshallbeRoHSEUDirective2002/95/ECcompliant.RackmountUPSshallutilizeMiddleAtlanticPowerManager™software.RackmountUPSshallbewarrantiedtobefreefromdefectsinmaterialsandworkmanshipundernormaluseandconditionsforaperiodof3years;batteryshallbewarrantiedforaperiodof2years.RackmountUPSshallbeULlistedinUSandCanada.

UPS-IPCARDWebbasedcontrolshallbeenabledonnon-internetenabledMiddleAtlanticProductsUPSbyUPS-IPCARD,whichshallbeinstalledintotheExpansionPortontherearoftheUPS.ThisshallbecompatiblewithUPSfirmwarev1.65orgreater,andprovidefullfunctionalitywhenusedonmodelswithfirmwarev1.75orgreater.

ExpansionBatteryRackmountexpansionbatterypackshallbeMiddleAtlanticProductsmodel#UPS-EBPR.ExpansionbatterypackshallbesuitableforusewithbothUPS-1000RandUPS-2200R.UPS-EBPRshallmeasure19.00”Wx3.50”Hx19.29”Dandoccupy2rackspaces.UPS-EBPRshallrequire22.66”useabledepth.With__hotswappablebatteriesconnected totheunit,thereisa__minuteruntimeathalfloadanda__minuteruntimeatfullload(refertochart).Rackmountexpansionbatterypackshallbewarrantiedfora periodof2years.

ReplacementBatteryReplacementBatteryPackfortheUPSshallbeMiddleAtlanticProductsmodel#UPS-RBP.ReplacementbatterypackshallbesuitableforusewithbothUPS-1000R__and UPS-2200R__.Replacementbatteryshallbewarrantiedtobefreefromdefectsinmaterialsandworkmanshipundernormaluseandconditionsforaperiodof2years.

Architects and Engineers’ Specifications

US: New Jersey • California • Illinois • Voice: 973-839-1011 Fax: 973-839-1976 • middleatlantic.comCanada: Ontario • British Columbia • Voice: 613-836-2501 Fax: 613-836-2690 • middleatlantic.ca

UPS-1000 SERIESUtility Voltage (AC) ≤80 81-105 106-133 133-147 >147

Fans Engaged Front&Rear Rearonly None RearOnly Front&Rear

dBA above Ambient 22dBA 11dBA 0 11dBA 22dBA

UPS-2200 SERIESUtility Voltage (AC) ≤80 81-105 106-133 133-147 >147

Fans Engaged Front&Rear Rearonly None RearOnly Front&Rear

dBA above Ambient 27dBA 14dBA 0 14dBA 27dBA

Page 3: 96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply · Uninterruptible Power Supply 96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply with Energy Saver design that is

TOP VIEW BOTTOM VIEW

FRONT VIEW (UPS-EBPR)

REAR VIEW (UPS-EBPR)

UPS basic dimensionsAll dimensions in inches unless otherwise noted [All dimensions in brackets are in millimeters]

SIDE VIEW SIDE VIEW

FRONT VIEW REAR VIEW

EXPANSION BATTERY CONNECTOR

SERIALCONTROL PORTS

15/20A CIRCUIT BREAKER

ETHERNET SURGEPROTECTION

15/20ASIGNALSAFE™CORD

CATV SURGE PROTECTION8X NEMA 5-20R (UPS-2200R SERIES)8X NEMA 5-15R (UPS-1000R SERIES)

POWER SWITCH

19.00 [483]

17.283 [439]

19.00 [483]

CONNECTING CABLE

22.66[575.5]17.829

[452.85]

4.83[122.68]

FUNCTION SELECT

LCD DISPLAY

3.465[88]

AC INPUT

19.29 [490]

REAR MOUNTING

RANGE19” [483]

TO 32” [813]

17.829[452.9]

19.00 [483]

19.00 [483]

17.047 [433]

48V DC BATTERY OUTPUT

48V DC BATTERY INPUT

POWER SWITCH

AC OUTPUT NEMA5-15R

US: New Jersey • California • Illinois • Voice: 973-839-1011 Fax: 973-839-1976 • middleatlantic.comCanada: Ontario • British Columbia • Voice: 613-836-2501 Fax: 613-836-2690 • middleatlantic.ca

Model# Capacity Outlet Control Internet enabled

UPS-1000R 1000VA Critical/Non-CriticalBank WithoptionalUPS-IPCARD

UPS-1000R-IP 1000VA Critical/Non-CriticalBank Yes

UPS-1000R-8 1000VA IndividualOutlet WithoptionalUPS-IPCARD

UPS-1000R-8IP 1000VA IndividualOutlet Yes

UPS-2200R 2150VA Critical/Non-CriticalBank WithoptionalUPS-IPCARD

UPS-2200R-IP 2150VA Critical/Non-CriticalBank Yes

UPS-2200R-8 2150VA IndividualOutlet WithoptionalUPS-IPCARD

UPS-2200R-8IP 2150VA IndividualOutlet Yes

Page 4: 96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply · Uninterruptible Power Supply 96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply with Energy Saver design that is

GeneralInformation

ModelNo. UPS-1000RSeries UPS-2200RSeries

Input

NominalInputVoltage 120V 120V

InputVoltageRange 80VAC–145VAC 80VAC–145VAC

InputFrequency 60Hz+/-3Hz(autosensing) 60Hz+/-3Hz(autosensing)

InputProtectionType Resettablethermalfuse Resettablethermalfuse

CordLength/CordType/PlugType 9ft./14/3/NEMA5-15P 9ft./12/3/NEMA5-20P

Output

GreenModeConsumption Lessthan9Watfullbatterycapacity Lessthan9Watfullbatterycapacity

NominalOutputVoltage 120V 120V

Capacity(VA) 1000VA 2150VA

Capacity(Watts) 750W 1650W

Waveform PureSineWave PureSineWave

OnLineOutputFrequency 57-63Hzfor60Hznominal 57-63Hzfor60Hznominal

OnBatteryOutputFrequency 60Hz+/-.1Hz 60Hz+/-.1Hz

TransferTime(Typical) 4mstypicallinetobattery/batterytoline 4mstypicallinetobattery/batterytoline

OverloadProtection(onlinemode) 100%≤Load<110%warning,120secshutdown110%≤Load<125%warning,40secshutdown125%≤Loadwarning,10secshutdown

100%≤Load<110%warning,120secshutdown110%≤Load<125%warning,40secshutdown125%≤Loadwarning,10secshutdown

OverloadProtection(onbatterymode) 100%≤Load<110%warning,30secshutdown110%≤Load<125%warning,10secshutdown125%≤Loadwarning,3secshutdown

100%≤Load<110%warning,30secshutdown110%≤Load<125%warning,10secshutdown125%≤Loadwarning,3secshutdown

SurgeProtectionandFiltering UPS-1000RSeries UPS-2200RSeries

Lightning/SurgeProtection L-N=>381J(127Jx3)Clampvoltage270V (Maxenergy10/1000µs)

L-N=>381J(127Jx3)Clampvoltage270V (Maxenergy10/1000µs)

RJ11/RJ45Protection Sidactorx1ClampVoltage275VFuse(.75A/250V)x2

Sidactorx1ClampVoltage275VFuse(.75A/250V)x2

Physical

OutputReceptacles (8)NEMA5-15R (8)NEMA5-20R

Dimensions(in.) 19.00”[423]Wx3.50”[89]Hx19.29”[490]D 19.00”[423]Wx3.50”[89]Hx19.29”[490]D

Weight(lb.) 68lbs. 77lbs.

Battery

Rating 12V/9.0AHx4 12V/9.0AHx4

AutoCharger 1A 1A

HotSwappableExternalBattery Yes Yes

RunTimeatHalfLoad 26minutes 13minutes

RunTimeatFullLoad 13minutes 6.4minutes

WarningDiagnostics

ControlPanel LCDDisplayIndicators,PowerOn LCDDisplayIndicators,PowerOn

AudibleAlarms OnBattery,LowBattery OnBattery,LowBattery

Environmental

OperatingTemperature 32°Fto104°F(0°Cto40°C) 32°Fto104°F(0°Cto40°C)

OperatingRelativeHumidity 0to95%Non-Condensing 0to95%Non-Condensing

TotalHarmonicDistortion(THD)

TotalSystemLoad 0% 20% 60% 100%

UtilityMains*THD 2.0% 2.0% 2.0% 2.0%

BatteryBackupTHD 1.9% 1.3% 1.5% 5.2%*typical120Vpowerwith2%-4%THD

US: New Jersey • California • Illinois • Voice: 973-839-1011 Fax: 973-839-1976 • middleatlantic.comCanada: Ontario • British Columbia • Voice: 613-836-2501 Fax: 613-836-2690 • middleatlantic.ca

Page 5: 96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply · Uninterruptible Power Supply 96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply with Energy Saver design that is

Communication

Software MiddleAtlanticPowerManager™ MiddleAtlanticPowerManager™

Management

Self-Test ManualSelf-Testviafrontpanel ManualSelf-Testviafrontpanel

Auto-Charger/Auto-Restart Yes Yes

COMInterface Primary: -RS232Communication+Control -AnalogStatusNotification+Control

Secondary: -Analogstatusnotificationonly

Primary: -RS232Communication+Control -AnalogStatusNotification+Control

Secondary: -Analogstatusnotificationonly

Built-inUSBInterface Yes Yes

UPS-1000RSeries

Load(VA) 120 240 360 480 600 720 840 960

Load(W)* 84 168 252 336 420 504 588 672

Load(A) 1 2 3 4 5 6 7 8

Numberofexpansionbatteries

ESTIMATEDRUNTIME(Minutes)

UPSonly 102 51 34 26 20 17 15 13

1 561 283 190 143 114 94 80 69

2 1020 515 345 260 207 171 145 125

3 1479 747 501 377 300 249 211 181

4 1938 979 657 494 394 326 276 238

5 2397 1211 813 611 487 403 341 294

6 2856 1443 968 728 580 480 407 350

7 3315 1676 1124 845 674 557 472 406

8 3774 1908 1280 962 767 635 537 463

9 4233 2140 1435 1079 860 712 603 519

10 4692 2372 1591 1196 954 789 668 575

UPS-2200RSeries

Load(VA) 120 240 360 480 600 720 840 960 1080 1200 1320 1440 1560 1680 1800 1920

Load(W)* 90 180 270 360 450 540 630 720 810 900 990 1080 1170 1260 1350 1440

Load(A) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Numberofexpansionbatteries

ESTIMATEDRUNTIME(Minutes)

UPSonly 102 51 34 26 20 17 15 13 11 10 9 9 8 7 7 6

1 561 283 190 143 114 94 80 69 60 53 47 42 37 33 29 26

2 1020 515 345 260 207 171 145 125 109 96 84 75 66 58 51 45

3 1479 747 501 377 300 249 211 181 158 139 122 108 95 84 74 64

4 1938 979 657 494 394 326 276 238 207 181 160 141 124 109 96 84

5 2397 1211 813 611 487 403 341 294 256 224 197 174 153 135 118 103

6 2856 1443 968 728 580 480 407 350 305 267 235 207 182 161 141 122

7 3315 1676 1124 845 674 557 472 406 353 310 272 240 212 186 163 142

8 3774 1908 1280 962 767 635 537 463 402 352 310 273 241 212 185 161

9 4233 2140 1435 1079 860 712 603 519 451 395 348 306 270 237 208 181

10 4692 2372 1591 1196 954 789 668 575 500 438 385 339 299 263 230 200

Estimated Run Times

*AssumingaPowerFactorof.7

*AssumingaPowerFactorof.75

US: New Jersey • California • Illinois • Voice: 973-839-1011 Fax: 973-839-1976 • middleatlantic.comCanada: Ontario • British Columbia • Voice: 613-836-2501 Fax: 613-836-2690 • middleatlantic.ca


Recommended