1
While every care is taken to ensure that the information contained in this publication is correct, no legal responsibility can be accepted for any inaccuracy. Nexans Network Solutions N.V. - Div. Euromold reserves the right to alter or modify the characteristics of its products described in this catalogue as standards and technology evolve.
EUROMOLDEuromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for medium voltage energy distribution. Euromold provides a complete range of accessories for underground cables: premoulded EPDM rubber connectors for cables and epoxy bushings for transformers and switchgear, as well as a large range of cold-shrinkable terminations and joints from 12 to 42 kV.Euromold is also the manufacturer of electrical components for the high voltage accessories of the Nexans group.
ISO 9001 CertificateSince 1992, Euromold’s commitment to quality is demonstrated by its ISO 9001 certification.
Laboratory accreditationSince June 2000, Euromold’s independent ELAB laboratory obtained the BELAC accreditation no.144-TEST conform with the European standards for laboratories ISO 17025 for electrical testing of low and medium voltage cable accessories according to the international standards HD 623 and HD 629.
International standardsAll our products meet the International standards like CENELEC HD 629.1, CENELEC EN 50180, IEC 60137, IEC 60502-4… or country speci-fications. Official certificates, CESI, KEMA, ATEX… prove the conformity of our products. Long duration tests of existing or new products are con-tinuously performed in our test fields.
Nexans Network SolutionsDiv. Euromold
COMPANY PRESENTATION
2
01/2
012
SEPARABLE CONNECTORSAND BUSHINGS
INTERFACE A
Table of contents158LR - elbow connector152SR - straight connector151SP - straight plug156SA - surge arrester 180AR-1 /-2 /-3 and 180AR-1-G /-3-G - equipment bushings250SFR-P - equipment bushing180A-24P-O - in-air bushingPITO-E - plug-in terminationAccessoriesBail restraints
Interface ADimensions according to European CENELEC EN 50180 and 50181 (in mm).
48 0-0.2
Dia. 48.5±0.2
Dia. 32.5±0.2
Dia. forpin 7.9+0.02
- 0.05
Dia. 31+0.1 - 0.3
9min
3
Connecting possibilities
PITO-EPlug-in termination
(K)150DRDead-end receptacle
(K)150DRDead-end receptacle
(K)151SPStraight plug
BUSHINGS / ACCESSORIES /CONNECTOR
CONNECTION CONNECTORS /ACCESSORIES
(K)400RTPAReducing tap plug
(K)151SOPStand-off plug
(K)150DPDead-end plug
cable isolation
in-line junction + 2 tap-offs
tap-off630/250 A
disconnectable joint
in-line junction+ 2 tap-offs
in-line junction+ tap-off
cableinsulation
tap-off1250/250 A
250GPEarthing plug
(K)250SFR-PEquipment bushing
(K)180AR-1(-G),-2 & -3(-G)Equipment bushing
Equipment interface
cableearthing
(K)200TTee connector
(K)200XCross connector
(K)200TTee connector
one cable toequipment
(K)200XCross connector
(K)200TTee connector
(K)200XCross connector
in-line junction + tap-off
dead-ending of equipment
two cables to equipment
one line to equipment
three cables to equipment
(K)676RTPAReducing tap plug
(K)152SR(/G)Straight connector
(K)158LR(/G)Elbow connector
(K)152SR(/G)Straight connector
180A-24P-OIn-air bushing
(K)158LR(/G)Elbow connector
01/2
012
4
01/2
012
Specifications and standardsThe separable connector 158LR meets the requirements of CENELEC HD 629.1.
Up to 24 kV - 250 A
DesignSeparable connector comprising:1. Conductive EPDM insert.2. Conductive EPDM jacket.3. Insulating EPDM layer moulded between the insert and the jacket.4. Type A - 250 A interface as described by CENELEC EN 50180 and 50181.5. Conductor connector.6. Voltage test point.7. Earthing lead (-/G version only).
158LRINTERFACE A
ELBOW CONNECTOR
ApplicationSeparable elbow connector designed to connect polymeric insulated cable to equipment (transformers, switchgear, motors...).Also connects cable to cable, using the appropriate mating part.
6/10 (12) kV6.35/11 (12) kV
8.7/15 (17.5) kV12/20 (24) kV
12.7/22 (24) kV
Technical characteristics •ThethickconductiveEPDM
jacket provides a total safe to touch screen which ensures safety for personnel.•Eachseparableconnectoris
tested for AC withstand and partial discharge prior to leaving the factory.
Separable connector
type
VoltageUm(kV)
CurrentIr
(A)
Conductor sizes (mm2)
min max158LR/G
158LR
K158LR/G
K158LR
12
12
24
24
250
250
250
250
16
70
16
25
95
95
70
95
6
1
3
2
7
221 mm
160 mm
4
5
5
For adaptedbail restraints:
see 'Bail restraints and typical applications'.
For outdoorapplications.
Order: +MWS.
Components can be ordered individually.
For use withcopper tape
screened cables. Order: Kit MT.
For use with Alupe orC 33-226 cables.
Please contact our representative.
For use withother cable types.
Please contact our representative.
The kit also comprises lubricant, wipers, installation instructions and crimp chart.
Ordering instructionsSelect the part number which gives the best centring to the cable core insulation diameter and substitute X using table X, according to the conductor size and type.Add a 'K' for use up to 24 kV.
Example:The copper wire screened cable is 24 kV, 50 mm2 stranded aluminium with a diameter over core insulation of 20.4 mm.Order a K158LR-FG-50(K)M-12-2+11TL elbow connector kit.
For an option with a bolted conductor contact,specify the ordering part number below.
Conductorsizes
(mm²)
Aluminium Copper
DIN hexagonal Deep indent DIN hexagonal
162535507095
- 25(K)M-12-2 35(K)M-12-2 50(K)M-12-2 70(K)M-12-2 95(K)M-12-2 *
-25KM-12-135KM-12-1
50(K)M-12-1*70(K)M-12-1*95(K)M-12-1*
16(K)M-11-225(K)M-11-235(K)M-11-250(K)M-11-270(K)M-11-295(K)M-11-2
Table X
Conductor
contact
164LRC-X
or
164LRMC-X
Pin contact
+ hex key
154LRF
Bail
restraint
150BA-B1
Connector housing
(K)158BLR-W
(K)158LR-W-X+11TL
connector kit for
larger sizesCable adaptor
11TL
Connector housing
(K)158BLR/G-WCable reducer
211CA
(K)158LR/G-W-Xconnector kit for
smaller sizes
Kit contentsThe complete (K)158LR or (K)158LR/G elbow connector kit comprises the following components:
* The 158LR-FB is not compatible with these conductor contacts.
Orderingpart number
Dia. over core insulation (mm)
min max
158LR/G-11-X158LR/G-13-X
158LR-FB-X+11TL158LR-FG-X+11TL158LR-GA-X+11TL158LR-GAB-X+11TL158LR-GH-X+11TL
12.614.617.518.419.721.023.2
16.118.720.221.222.523.826.4
Table W
Ordering part number Dia. over core insulation (mm) Conductor sizes (mm²)
158LR/G-13-25.95-14-5
158LR-GAS-50.95-14-5+11TL
14.6 - 22.7
19.7 - 25.4
35 - 70
25 - 95
Catalogue 2011
a Nexans company
1
02/2
011
While every care is taken to ensure that the information contained in this publication is correct, no legal responsibility can be accepted for any inaccuracy. Nexans Network Solutions N.V. - Div. Euromold reserves the right to alter or modify the characteristics of its products described in this catalogue as standards and technology evolve.
EUROMOLDEuromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for medium voltage energy distribution. Euromold provides a complete range of accessories for underground cables: premoulded EPDM rubber connectors for cables and epoxy bushings for transformers and switchgear, as well as a large range of cold-shrinkable terminations and joints from 12 to 42 kV.Euromold is also the manufacturer of electrical components for the high voltage accessories of the Nexans group.
ISO 9001 CertificateSince 1992, Euromold’s commitment to quality is demonstrated by its ISO 9001 certification.
Laboratory accreditationSince June 2000, Euromold’s independent ELAB laboratory obtained the BELAC accreditation no.144-TEST conform with the European standards for laboratories ISO 17025 for electrical testing of low and medium voltage cable accessories according to the international standards HD 623 and HD 629.
International standardsAll our products meet the International standards like CENELEC HD 629.1, CENELEC EN 50180, IEC 60137, IEC 60502-4… or country speci-fications. Official certificates, CESI, KEMA, ATEX… prove the conformity of our products. Long duration tests of existing or new products are con-tinuously performed in our test fields.
Nexans Network SolutionsDiv. Euromold
COMPANY PRESENTATION
2
02/2
011
SEPARABLE CONNECTORSAND BUSHINGS
INTERFACE B
Table of contents400LR - elbow connector400TE - tee connector400T1 - equipment bushing400AR-1 - equipment bushing400AR-2 - equipment bushing400AR-8 - equipment bushing400SFR-P - equipment bushingAccessoriesPossible arrangements
Interface BDimensions according to European CENELEC EN 50180 and 50181 (in mm).
90±0.2
Dia. 46±0.2
Dia. 56±0.2
Dia. 70±0.2
40min
Dia. forpin 14 0
-0.04
11min
3 02/2
011
Connecting possibilities
BUSHINGS / ACCESSORIES
CONNECTION CONNECTORS / ACCESSORIES
(K)(M)400DR Dead-end receptacle
(K)(M)400TE/GTee connector
(K)(M)400SOPStand-off plug
400GPEarthing plug
dead-ending of equipment
one cable toequipment
cableisolation
cableearthing
(K)400RTPAReducing tap plug
(K)(M)400CP-SC Connecting plug
two cables to equipment
tap-off630/250A
in-line junction
(K)(M)400LR/GElbow connector
(K)400SFR-PEquipment bushing
(K)(M)400AR-8Equipment bushing
Equipmentinterface
(K)(M)400AR-1Equipment bushing
(K)(M)400T1Equipment bushing
(K)(M)400AR-2Equipment bushing
4
02/2
011
Specifications and standardsThe separable connector 400LR meets the requirements of CENELEC HD 629.1.
Up to 36 kV - 400 A
DesignSeparable connector comprising:1. Conductive EPDM insert.2. Conductive EPDM jacket.3. Insulating EPDM layer moulded between the insert and the jacket.4. Type B - 400 A interface as described by CENELEC EN 50180 and 50181.5. Conductor connector.6. Cable reducer.7. Earthing lead.
The screen break design enables cable outer sheath testing without removing or dismantling the connector.
400LRINTERFACE B
ELBOW CONNECTOR
ApplicationSeparable elbow connector (plug-in type) designed to connect polymeric insulated cable to equipment (transformers, switchgear, motors...).
6/10 (12) kV6.35/11 (12) kV
8.7/15 (17.5) kV12/20 (24) kV
12.7/22 (24) kV18/30 (36) kV
Technical characteristics •ThethickconductiveEPDM
jacket provides a total safe to touch screen which ensures safety for personnel.•Eachseparableconnectoris
tested for AC withstand and partial discharge prior to leaving the factory.
210 mm
365 mm
4
5
1
2
3
7
6
Separable connector
type
VoltageUm(kV)
CurrentIr
(A)
Conductor sizes (mm2)
min max400LR/G
K400LR/G
M400LR/G
12
24
36
400
400
400
50
25
35
240
240
185
5
Kit contentsThe complete (K)(M)400LR/G elbow connector kit comprises the following components:
The kit also comprises lubricant, wipers,
installation instructions and crimp chart.
Ordering instructionsSelect the part numberwhich gives the best centring to the cable core insulation diameter and substitute X using table X, according to the conductor size and type.Add a 'K' for use up to 24 kV and add an 'M' for use up to 36 kV.
Conductor
contact
400LRC-X
Pin contact
+ hex. key
400LRF
Bail
restraint
400BA
Connector housing
(K)(M)400BLR/G
Cable reducer
411CA-W
Orderingpart number
Dia. over core insulation (mm)
min max
400LR/G-11-X400LR/G-15-X400LR/G-19-X
400LR/G-22-X400LR/G-25-X400LR/G-27-X
12.0
16.0
20.0
23.5
26.5
28.5
17.5
22.0
26.5
31.0
32.5
37.5
Example:The copper wire screened cable is 12 kV, 150 mm2 stranded copper with a diameter over core insulation of 23.5 mm.Order a 400LR/G-19-150(K)M-11-2 elbow connector kit.
(K)(M)400LR/G-W-Xconnector kit
Table X
Table W
Conductorsizes
(mm²)
Aluminium Copper
DIN hexagonal Deep indent DIN hexagonal
25
35
50
70
95
120
150
185
240
-
35(K)M-12-2
50(K)M-12-2
70(K)M-12-2
95(K)M-12-2
120(K)M-12-2
150(K)M-12-2
185(K)M-12-2
240(K)M-12-2
-
35KM-12-1
50(K)M-12-1
70(K)M-12-1
95(K)M-12-1
120(K)M-12-1
150(K)M-12-1
185(K)M-12-1
240(K)M-12-1
25(K)M-11-2
35(K)M-11-2
50(K)M-11-2
70(K)M-11-2
95(K)M-11-2
120(K)M-11-2
150(K)M-11-2
185(K)M-11-2
240(K)M-11-2
For applicationsoutdoors and in humid climate.
Order: +MWS.
Components can be ordered individually.
For use withcopper tape
screened cables. Order: Kit MT.
For use with Alupe orC 33-226 cables.
Please contact our representative.
For use with fabric tape (graphite) screened cables.
Order additionalsemi-conductive tape
(type TSC).
For use withother cable types.
Please contact our representative.
Catalogue 2011
a Nexans company
1
08/2
011
While every care is taken to ensure that the information contained in this publication is correct, no legal responsibility can be accepted for any inaccuracy. Nexans Network Solutions N.V. - Div. Euromold reserves the right to alter or modify the characteristics of its products described in this catalogue as standards and technology evolve.
EUROMOLDEuromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for medium voltage energy distribution. Euromold provides a complete range of accessories for underground cables: premoulded EPDM rubber connectors for cables and epoxy bushings for transformers and switchgear, as well as a large range of cold-shrinkable terminations and joints from 12 to 42 kV.Euromold is also the manufacturer of electrical components for the high voltage accessories of the Nexans group.
ISO 9001 CertificateSince 1992, Euromold’s commitment to quality is demonstrated by its ISO 9001 certification.
Laboratory accreditationSince June 2000, Euromold’s independent ELAB laboratory obtained the BELAC accreditation no.144-TEST conform with the European standards for laboratories ISO 17025 for electrical testing of low and medium voltage cable accessories according to the international standards EN 50393, IEC 60502-4, IEC 61442 and HD 629.
International standardsAll our products meet the International standards like CENELEC HD 629.1, CENELEC EN 50180, IEC 60137, IEC 60502-4… or country speci-fications. Official certificates, CESI, KEMA, ATEX… prove the conformity of our products. Long duration tests of existing or new products are con-tinuously performed in our test fields.
Nexans Network SolutionsDiv. Euromold
COMPANY PRESENTATION
2
08/2
011
SEPARABLE CONNECTORSINTERFACE C
Interface C1 & C2Dimensions according to European CENELEC EN 50180 and 50181 (in mm).
Table of contents430TB - tee connector484TB - tee connector300PBM - coupling connector430TBM-P2/P3 - dual/triple cable arrangement804PB - coupling connector300SA - surge arrester800SA - surge arrester400TR and 800TR - test rod400TK and 400SW installation toolsAccessoriesPossible arrangements
90±0.2
0-0.51.5
Dia. 22 min for C1Dia. 32 nominal for C2
Dia. 46±0.2
Dia. 56±0.2
Dia. 70±0.2
M16 x 2 - 6H
29min.
11min.
3 08/2
011
Connecting possibilities
CONNECTIONBUSHINGS /ACCESSORIES
CONNECTORS /ACCESSORIES
(K)(M)300PBM/GCoupling connector
300SASurge arrester
dead-endingof equipment (K)(M)400DR-B
Dead-end receptacle
cableearthing
tap-off630/250A
in-linejunction
(K)(M)430TB/GTee connector
Equipmentinterface
(K)(M)400AR-3Equipment bushing
400A-24BIn-air bushing
(K)(M)400SOP-BStand-off plug
400GP-BEarthing plug
(K)400RTPAReducing tap plug
(K)(M)400CP-SCConnecting plug
(K)(M)400SFR-BEquipment bushing
(K)(M)400AR-6Equipment bushing
(K)(M)400AR-4Equipment bushing
(K)(M)400AR-5Equipment bushing
cable toequipment
cableisolation
(K)(M)484TB/GTee connector
(K)(M)804PB/GCoupling connector
800SASurge arrester
For information on our bushings please refer to our bushing catalogue.
4
08/2
011
ApplicationSeparable tee shape connector (bolted type) designed to connect polymeric insulated cable to equipment (transformers, switchgear, motors, ...).Also connects cable to cable when using the appropriate mating parts.
Technical characteristics•AthickconductiveEPDM
jacket provides a total safe to touch screen.
•Eachseparableconnectoristested for AC withstand and partial discharge prior to leaving the factory.
Specifications and standardsThe 430TB separable connector meets the requirements of CENELEC HD 629.1.
Up to 36 kV630 A (800 A)
430TBINTERFACE C
TEE CONNECTOR
6/10 (12) kV6.35/11 (12) kV
8.7/15 (17.5) kV12/20 (24) kV
12.7/22 (24) kV18/30 (36) kV19/33 (36) kV
DesignSeparable connector comprising: 1. Conductive EPDM insert. 2. Conductive EPDM jacket. 3. Insulating EPDM layer moulded between the insert and the jacket. 4. Type C interface as described by CENELEC EN 50180 and 50181. 5. Conductor connector. 6. Basic insulating plug (with VD point). 7. Cable reducer. 8. Conductive rubber cap. 9. Clamping screw. 10. Earthing lead.
The screen break designenables cable outer sheathtesting without removing ordismantling the connector.
185 mm
290 mm
(350 mmfor 36 kV)
4 9
6
1
2
3
10
7
5
8
Separable connector
type
VoltageUm(kV)
CurrentIr
(A)
Current Ir (A)Conductor sizes (mm2)
When installed on an appropriate equipment bushing and when using a copper (-11-2) or a
bolted (-12-5 or -14-5) conductor contact min max
430TB/GK430TB/GM430TB/G
122436
630630630
800800800
353550
300300240
5
3 x (K)(M)430TB/G-W-X connector kit
When installed on an appropriate equipment
bushing: 800 A continuously
Kit contentsThe complete (K)(M)430TB/G tee connector kit comprises 3 x the following components:
The kit also comprises silicone grease, field control mastic, installation rod, installation instructions and crimp chart.
Table W
Table X
Connector housing(K)(M)430BT/G
Cable reducer430CA-W
(411CA-Wfor 36 kV)
Clamping screw
430TCS
For use withcopper tape
screened cables. Order: Kit MT.
Orderingpart number
Voltage(Um)(kV)
Dia. over core insulation (mm)
min max
3 x 430TB/G-11-X3 x 430TB/G-16-X3 x 430TB/G-18-X
3 x K430TB/G-11-X3 x K430TB/G-16-X3 x K430TB/G-18-X
3 x M430TB/G-11-X3 x M430TB/G-15-X3 x M430TB/G-19-X3 x M430TB/G-22-X3 x M430TB/G-25-X3 x M430TB/G-27-X
121212
242424
363636363636
12.017.019.0
12.017.019.0
12.016.020.023.526.528.5
17.523.532.6
17.523.532.6
17.522.026.531.032.537.5
Ordering instructionsTo order the tee connector, select the ordering part number which gives you the best centring of your core insula-tion diameter and substitute X using table X, according to your conductor size and type.
Example:The cable is 24 kV, 150 mm2 compact stranded copper with a diameter over core insulation of 27.5 mm.Order 3 x K430TB/G-18-95.240-14-5 tee connector kit.
Conductorcontact TMBC-X
Conductor contact TBC-X
For use with Alupe orC 33-226 cables.
Please contact our representative.
For use withother cable types.
Please contact our representative.
For applicationsoutdoors and in humid climate.
Order: +MWS.
For use witheasy strip semi-conductive screened cables. Order: Field control mastic
(type MFC).
Basic insulatingplug
(K)(M)300BIPA +rubber cap
Conductor sizes (mm2)
Aluminium conductorAluminium and
copper conductorCopper
conductor
DINhexagonal
Deepindent
BoltedDIN
hexagonal
35 35(K)M-10-2 35KM-10-1 35(K)M-11-250 50(K)M-10-2 50(K)M-10-1 50(K)M-11-270 70(K)M-10-2 70(K)M-10-1 70(K)M-11-295 95(K)M-10-2 95(K)M-10-1 95(K)M-11-2120 120(K)M-10-2 120(K)M-10-1 120(K)M-11-2150 150(K)M-10-2 150(K)M-10-1 150(K)M-11-2185 185(K)M-10-2 185(K)M-10-1 185(K)M-11-2240 240(K)M-10-2 240(K)M-10-1 240(K)M-11-2300 300(K)M-10-2 – 300(K)M-11-2
16.9
5-14
-5
50.1
50-1
4-5
95.2
40-1
4-5
120.
300-
12-5
6
08/2
011
Up to 42 kV630 A (1250 A)
484TBINTERFACE C
TEE CONNECTOR
Technical characteristics •ThethickconductiveEPDM
jacket provides a total safe to touch screen which ensures safety for personnel.•Eachseparableconnectoris
tested for AC withstand and partial discharge prior to leaving the factory.
ApplicationSeparable tee shape connector (bolted type) designed to connect polymeric insulated cable to equipment (transformers, switchgear, motors, ...).Also connects cable to cable when using the appropriate mating parts.
DesignSeparable connector comprising: 1. Conductive EPDM insert. 2. Conductive EPDM jacket. 3. Insulating EPDM layer moulded between the insert and the jacket. 4. Type C - interface as described by CENELEC EN 50180 and 50181. 5. Conductor connector. 6. Basic insulating plug (with VD point). 7. Cable reducer. 8. Conductive rubber cap. 9. Clamping screw. 10. Earthing lead.
The screen break designenables cable outer sheathtesting without removing ordismantling the connector.
Specifications and standardsThe 484TB separable connector meets the requirements of CENELEC HD 629.1.
Separable connector
type
VoltageUm(kV)
CurrentIr
(A)
CurrentIr (A)
When installed on anappropriate equipment bushing
Conductor sizes (mm2)
min max484TB/G
K484TB/GM484TB/GP484TB/G
12243642
630630630630
1250125012501250
50353535
630630630630
185 mm
4 9
1
2
3
10
7
360 mm
5
6
8
6/10 (12) kV6.35/11 (12) kV
8.7/15 (17.5) kV12/20 (24) kV
12.7/22 (24) kV18/30 (36) kV19/33 (36) kV
20.8/36 (42) kV
7
Ordering instructionsTo order the tee connector, select the ordering part number which gives you the best centring of your core insula-tion diameter and substitute X using table X, according to your conductor size and type.Add a 'K' for use up to 24 kV, add an 'M' for use up to 36 kV, add a 'P' for use up to 42 kV.
Example:The copper wire screened cable is 36 kV, 240 mm2 stranded aluminium with a diameter over core insulation of 37.0 mm.Order 3 x M484TB/G-32-240(K)M-12-2 tee connector kit.
Orderingpart number
Dia. over core insulation (mm)
min max
3 x 484TB/G-15-X3 x 484TB/G-19-X3 x 484TB/G-22-X3 x 484TB/G-27-X3 x 484TB/G-32-X3 x 484TB/G-37-X3 x 484TB/G-43-X
16.020.023.528.534.039.045.5
22.026.531.037.542.548.556.0
Table W
Kit contentsThe complete (K)(M)(P)484TB/G tee connector kit comprises 3x the following components:
The kit also comprises silicone grease, field control mastic, gloves, roll adhesive tape, installation instructions and crimp chart.
(K)(M)(P)484TB/G-W-Xconnector kit
Connector housing(K)(M)(P)484BT/G
Clampingscrew
430TCSCable reducer
611CA-W
Conductorcontact TMBC-X
Conductor contact TBC-X
Basic insulatingplug
(K)(M)(P)800BIPA+ rubber cap
When installed on an appropriate equipment
bushing: 1250 A continuously
Components can be ordered individually.
For use withcopper tape
screened cables. Order: Kit MT.
For use withother cable types.
Please contact our representative.
For applicationsoutdoors and in humid climate.
Order: +MWS.
For use with copperwire screened cables.
No earthingdevice is
necessary.
Table X
Conduc-tor sizes (mm2)
Aluminium conductorAluminium and
copper conductorCopper
conductor
DINhexagonal
Deepindent
BoltedDIN
hexagonal
35
50
70
95
120
150
185
240
300
400
500
630
35(K)M-12-2
50(K)M-12-2
70(K)M-12-2
95(K)M-12-2
120(K)M-12-2
150(K)M-12-2
185(K)M-12-2
240(K)M-12-2
300(K)M-12-2
400(K)M-12-2
500(K)M-12-2
–
35KM-12-1
50KM-12-1
70KM-12-1
95KM-12-1
120KM-12-1
150KM-12-1
185KM-12-1
240KM-12-1
300KM-12-1
400KM-12-1
500KM-12-1
630KM-12-1
35(K)M-11-2
50(K)M-11-2
70(K)M-11-2
95(K)M-11-2
120(K)M-11-2
150(K)M-11-2
185(K)M-11-2
240(K)M-11-2
300(K)M-11-2
400(K)M-11-2
500(K)M-11-2
630(K)M-11-2
16.9
5-14
-5
95.2
40-1
4-5
50.1
50-1
4-5
120.
300-
12-5
8
08/2
011
ApplicationSeparable coupling connector (bolted type) for dual cable arrangement. It has been designed to be used with 430TB separable Tee connector.
Technical characteristics•AthickconductiveEPDM
jacket provides a total safe to touch screen.
•Eachseparableconnectoristested for AC withstand and partial discharge prior to leaving the factory.
Up to 36 kV630 A (1250 A)
300PBMCOUPLING CONNECTOR
FOR 430TB/G
Specifications and standardsThe 300PBM coupling connector meets the requirements of CENELECHD 629.1.
Design 1. Interface designed to fit 430TB connector. 2. Bus for 300PBM. 3. Conductive EPDM insert. 4. Insulating EPDM layer moulded between the insert and the jacket. 5. Conductive EPDM jacket. 6. Conductive EPDM cap. 7. Basic insulating plug (with VD point). 8. Conductor connector (hexagonal crimping, deep indent crimping or bolted). 9. Cable reducer. 10. Earthing lead.
The screen break designenables cable outer sheathtesting without removing ordismantling the connector.
290 mm(350 mmfor 36 kV)
105 mm
300PBMcouplingconnector
290 mm
1
2
3
4
5
9
7
6
10
430TBconnector
8
6/10 (12) kV6.35/11 (12) kV
8.7/15 (17.5) kV12/20 (24) kV
12.7/22 (24) kV18/30 (36) kV19/33 (36) kV
Separable connector
type
VoltageUm(kV)
CurrentIr
(A)
Current Ir (A)Conductor sizes (mm2)
When installed on an appropriate equipment bushing and when using a copper (-11-2) or a
bolted (-12-5 or -14-5) conductor contact min max
300PBM/GK300PBM/GM300PBM/G
122436
630630630
125012501250
353550
300300240
9
Kit contentsThe complete (K)(M)300PBM/G coupling connector kit comprises 3 x the following components:
The kit also comprises silicone grease, field control mastic, installation rod, installation instructions and crimp chart.
For use withcopper tape
screened cables. Order: Kit MT.
For use witheasy strip semi-conductive screened cables. Order: Field control mastic
(type MFC).
For use with copperwire screened cables.
No earthingdevice is
necessary.
For use withother cable types.
Please contact our representative.
For outdoorapplications.
Order: +MWS.
Connector housing(K)(M)300BP/G
For use with fabric tape (graphite) screened cables.
Order additionalsemi-conductive tape
(type TSC).
Contact rod 300PB-CR
3 x (K)(M)300PBM/G-W-X coupling connector kit
Cable reducer430CA-W
(411CA-Wfor 36 kV)
Conductorcontact TMBC-X
Conductor contact TBC-X
Table W
Table X
Orderingpart number
Voltage(Um)(kV)
Dia. over core insulation (mm)
min max
3 x 300PBM/G-11-X3 x 300PBM/G-16-X3 x 300PBM/G-18-X
3 x K300PBM/G-11-X3 x K300PBM/G-16-X3 x K300PBM/G-18-X
3 x M300PBM/G-11-X3 x M300PBM/G-15-X3 x M300PBM/G-19-X3 x M300PBM/G-22-X3 x M300PBM/G-25-X3 x M300PBM/G-27-X
121212
242424
363636363636
12.017.019.0
12.017.019.0
12.016.020.023.526.528.5
17.523.532.6
17.523.532.6
17.522.026.531.032.537.5
Ordering instructionsTo order the coupling connector, select the ordering part number which gives you the best centring of your core insula-tion diameter and substitute X using table X, according to your conductor size and type.
Example:The cable is 24 kV, 150 mm2 compact stranded copper with a diameter over core insulation of 27.5 mm.Order 3 x K300PBM/G-18-95.240-14-5 coupling connector kit.
Conductor sizes (mm2)
Aluminium conductorAluminium and
copper conductorCopper
conductor
DINhexagonal
Deepindent
BoltedDIN
hexagonal
35 35(K)M-10-2 35KM-10-1 35(K)M-11-250 50(K)M-10-2 50(K)M-10-1 50(K)M-11-270 70(K)M-10-2 70(K)M-10-1 70(K)M-11-295 95(K)M-10-2 95(K)M-10-1 95(K)M-11-2120 120(K)M-10-2 120(K)M-10-1 120(K)M-11-2150 150(K)M-10-2 150(K)M-10-1 150(K)M-11-2185 185(K)M-10-2 185(K)M-10-1 185(K)M-11-2240 240(K)M-10-2 240(K)M-10-1 240(K)M-11-2300 300(K)M-10-2 – 300(K)M-11-2
16.9
5-14
-5
50.1
50-1
4-5
95.2
40-1
4-5
120.
300-
12-5
Zümrütevler Mh. Karayemiş Sk., REF PLAZA No:26 Kat:2 D:3 MALTEPE/İSTANBUL Telefon : 444 3 168E-Posta : [email protected]