ABB Power Products - Medium & High Voltage Transformers Cast Resin Trasformers ABB Power Products ABB TDC voltage transformer for medium voltage systems has all parts of its primary winding, including terminals, insulated from the earth at a level corresponding to its rated insulation level . Indoor dry type, cast resin insulated medium voltage (MV) transformer for measuring and protection with up to 2 secondary windings. Cast Resin Transformers are constructed with their HV high voltage windings encapsulated in resin and are an excellent alternative to traditional oil immersed transformers. Cast resin transformers encase the windings in epoxy resin : these HV high voltage cast resin transformers simplify installation since they are dry, without cooling oil, and so require no fire-proof vault for indoor installations. The epoxy resin protects the high voltage transformer windings from dust and corrosive atmospheres. ABB TDC Voltage Transformer ABB MV Medium Voltage Transformers - Voltage Transformer Features Indoor dry type, cast resin insulated transformers for medium voltages (MV). ABB transformers are suitable for measuring and protection of MV medium voltages with up to 2 secondary windings. ABB offers a full range of medium voltage (MV) and high voltage (HV) transformer products and solutions for ANSI, IEC and other local standards. ABB is a major transformer manufacturer throughout the world and offers both liquid-filled and dry-type transfomers for medium and high voltage power distribution, measurement and protection. T&D distribute ABB fuses, vacuum contactors, surge arresters, capacitors, plugs and sockets for LV, MV and HV electrical distribution and cable systems.
Popular Tags:
12
Description The TDC 4 voltage, double-pole insulated transformers are cast in epox resin and designed mostly for insulation voltages of 3.6 kV to 12 kV. If no other value is required the transformers are manufactured with a voltage factor of 1.2 x Un. All the parts of the primary winding of the transformer are insulated from the earth, including the terminals, to an insulation level identical with the rated insulation level. When operating in a three-phase system the primary inlets of the transformer are connected across the respective lines, to the phase-to-phase voltage, mostly in the „V“ type of connection. The majority of the transformers is equipped with one secondary winding, intended to be used for either the measurement or protection purposes. One of the terminals of each secondary winding has to be earthed during the transformer operation. If not required otherwise, the secondary winding is lead out into a cast secondary terminal board. The transformer may be mounted in any position. The transformers are fixed by four screws, The M8 bolted earthing clamp is located on the transformer base plate. The secondary, sealable terminal board is covered with a transparent cover made of plastic material. Rated primary voltages ... 3 kV; 3.3 kV; 6 kV; 6.6 kV; 10 kV; 11 kV Other primary voltages based on customer‘s request may be delivered, too. Rated secondary voltages... 100 V; 110 V – 0.2; 0.5; and 1 accuracy classes (measuring winding), or 3P; 6P (protection winding) Other secondary voltages based on customer‘s request may be delivered, too. Rated frequency ... 50 Hz; 60 Hz Design for two primary voltages is also possible, based on a consultancy to be conducted with the manufacturer (change over secondary side). The transformers are manufactured and delivered conformably to the requirements and recommendations of the following standards and regulations: IEC, VDE, ANSI, BS, GOST and CSN. Highest voltage for equipment [kV] 3.6 - 12 Power frequency test voltage, 1 min. [kV] 10 - Lightning impulse test voltage [kV] 40 - 75 Max. rated burden, classes [VA/cl] 25/0.2 - 75/0.5 - 150/1 TDC 4 Indoor voltage transformers Medium Voltage Product
Transcript
Page 1: ABB TDC Voltage Transformer - ABB MV Medium Voltage Transformer - Indoor Cast Resin Voltage Transformer Double Pole ABB TDC

DescriptionThe TDC 4 voltage, double-pole insulated transformers are cast in epox resin and designed mostly for insulation voltages of 3.6 kV to 12 kV.If no other value is required the transformers are manufactured with a voltage factor of 1.2 x Un. All the parts of the primary winding of the transformer are insulated from the earth, including the terminals, to an insulation level identical with the rated insulation level. When operating in a three-phase system the primary inlets of the transformer are connected across the respective lines, to the phase-to-phase voltage, mostly in the „V“ type of connection. The majority of the transformers is equipped with one secondary winding, intended to be used for either the measurement or protection purposes. One of the terminals of each secondary winding has to be earthed during the transformer operation.If not required otherwise, the secondary winding is lead out into a cast secondary terminal board.The transformer may be mounted in any position. The transformers are fixed by four screws, The M8 bolted earthing clamp is located on the transformer base plate. The secondary, sealable terminal board is covered with a transparent cover made of plastic material.

Rated primary voltages ... 3 kV; 3.3 kV; 6 kV; 6.6 kV; 10 kV; 11 kVOther primary voltages based on customer‘s request may be delivered, too.Rated secondary voltages... 100 V; 110 V – 0.2; 0.5; and 1 accuracy classes (measuring winding), or 3P; 6P (protection winding)Other secondary voltages based on customer‘s request may be delivered, too.Rated frequency ... 50 Hz; 60 HzDesign for two primary voltages is also possible, based on a consultancy to be conducted with the manufacturer (change over secondary side).The transformers are manufactured and delivered conformably to the requirements and recommendations of the following standards and regulations: IEC, VDE, ANSI, BS, GOST and CSN.

Highest voltage for equipment [kV] 3.6 - 12

Power frequency test voltage, 1 min. [kV] 10 -

Lightning impulse test voltage [kV] 40 - 75

Max. rated burden, classes [VA/cl] 25/0.2 - 75/0.5 - 150/1

TDC 4Indoor voltage transformers

Medium Voltage Product

Page 2: ABB TDC Voltage Transformer - ABB MV Medium Voltage Transformer - Indoor Cast Resin Voltage Transformer Double Pole ABB TDC

2

Dimensions

100

220

20

116139

22

9

4

M10x15

M8

Pg1

6 14

(125

)

2x 11

148

27010

1196

30

82 188

110

338

Marking of the voltage transformer outlets

a) Single-pole insulated transformer | b) Single-pole insulated transformer with a tap | c) Double-pole insulated transformer | d) Double-pole insulated transformer with a tap | e) Single-pole insulated transformer with two secondary windings | f) Single-pole insulated transformer with two secondary windings, with one of which being the auxiliary (residual) winding | g) Single-pole insulated transformer with two secondary, tapped windings, with one which being the auxiliary (residual) winding.

Page 3: ABB TDC Voltage Transformer - ABB MV Medium Voltage Transformer - Indoor Cast Resin Voltage Transformer Double Pole ABB TDC

3

Standartized transformers

Primary

voltage,V

Secondary voltage

voltage,V accuracy burden, VA

3000 100 0,2 10,15,25

3000 100 0,5 15,25,50

3000 100 1 50,75,100

3300 110 0,2 10,15,25

3300 110 0,5 15,25,50

3300 110 1 50,75,100

6000 100 0,5 15,25,50

6000 100 0,5 15,25,50

6000 100 1 50,75,100

6600 110 0,2 10,15,25

6600 110 0,5 15,25,50

6600 110 1 50,75,100

10000 100 0,2 10,15,25

10000 110 0,2 10,15,25

10000 100 0,5 15,25,50

10000 110 0,5 15,25,50

10000 100 1 50,75,100

10000 110 1 50,75,100

11000 100 0,2 10,15,25

11000 110 0,2 10,15,25

11000 100 0,5 15,25,50

11000 110 0,5 15,25,50

11000 100 1 50,75,100

11000 110 1 50,75,100

Page 4: ABB TDC Voltage Transformer - ABB MV Medium Voltage Transformer - Indoor Cast Resin Voltage Transformer Double Pole ABB TDC

1VLC

0005

22 -

Rev

1, e

n 20

10.x

x.xxABB s.r.o.

PPMV Brno

Videnska 117

619 00 Brno, Czech Republic

Tel.: +420 547 152 602

+420 547 152 614

Fax: +420 547 152 626

E-mail: [email protected]

www.abb.com

The data and ilustrations in this catalogue are not binding. We reserve the right to make changes of the content, in the course of technical development of the product.

Page 5: ABB TDC Voltage Transformer - ABB MV Medium Voltage Transformer - Indoor Cast Resin Voltage Transformer Double Pole ABB TDC

DescriptionThe TDC 6 voltage, double-pole insulated transformers are casted in epox resin and designed mostly for insulation voltages of 17,5 kV to 24 kV. Other insulation values are to be the subject of an agreement between the manufacturer and the customer. If no other value is required the transformers are manufactured with a voltage factor of 1.2 x Un. All the parts of the primary winding of the transformer are insulated from the earth, including the terminals, to an insulation level identical with the rated insulation level. When operating in a three-phase system the primary inlets of the transformer are connected across the respective lines, to the phase-to-phase voltage, mostly in the „V“ type of connections. The majority of transformers is equipped with one secondary winding, intended to be used for either the measurement or protection purposes. One of the terminals of each secondary winding has to be earthed during the transformer operation. If not required otherwise, the secondary winding is lead out into a casted secondary terminal board. The transformer may be mounted in any position. The transformers are fixed by four screws, The M8 bolted earthing clamp is located on the transformer base plate. The secondary, sealable terminal board is covered with a transparent cover made of plastic material.

Rated primary voltages ... 11 kV; 15 kV; 20 kV; 22 kVOther primary voltages based on customer‘s request may be delivered, too. Rated secondary voltages... 100 V; 110 V – 0.2; 0.5 and 1 accuracy classes (measuring winding), or 3P; 6P (protection winding)Other secondary voltages based on customer‘s request may be delivered, too. Rated frequency ... 50 Hz; 60 HzDesign for two primary voltages is also possible, based on a consultancy to be conducted with the manufacturer (change over secondary side).The transformers are manufactured and delivered conformably to the requirements and recommendations of the following standards and regulations: IEC, VDE, ANSI, BS, GOST and ČSN.

Highest voltage for equipment [kV] 17.5 - 24 (25)

Power frequency test voltage, 1 min. [kV] 38 - 50 (55)

Lightning impulse test voltage [kV] 95 - 125

V[ nedrub detar .xaM A/cl] 30/0.2 - 100/0.5 - 150/1

TDC 6Indoor voltage transformers

Medium Voltage Product

Page 6: ABB TDC Voltage Transformer - ABB MV Medium Voltage Transformer - Indoor Cast Resin Voltage Transformer Double Pole ABB TDC

2

Dimensions

Pg16 !14

M10x15

ZEM M8EARTH

165

30

130

178

150

!1420

280

9614

93

352

285

50

22

225

116

8

AU

VB

Marking of the voltage transformer outlets

a) Single-pole insulated transformer | b) Single-pole insulated transformer with a tap | c) Double-pole insulated transformer | d) Double-pole insulated transformer with a tap | e) Single-pole insulated transformer with two secondary windings | f) Single-pole insulated transformer with two secondary windings, with one of which being the auxiliary (residual) winding | g) Single-pole insulated transformer with two secondary, tapped windings, with one which being the auxiliary (residual) winding.

Page 7: ABB TDC Voltage Transformer - ABB MV Medium Voltage Transformer - Indoor Cast Resin Voltage Transformer Double Pole ABB TDC

3

Standartized transformers

Primary

voltage,V

Secondary voltage

voltage,V accuracy burden, VA

15000 100 0,2 10,15,25

15000 110 0,2 10,15,25

15000 100 0,5 15,25,50

15000 110 0,5 15,25,50

15000 100 1 50,75,100

15000 110 1 50,75,100

20000 100 0,2 10,15,25

20000 110 0,2 10,15,25

20000 100 0,5 15,25,50

20000 110 0,5 15,25,50

20000 100 1 50,75,100

20000 110 1 50,75,100

22000 100 0,2 10,15,25

22000 110 0,2 10,15,25

22000 100 0,5 15,25,50

22000 110 0,5 15,25,50

22000 100 1 50,75,100

22000 110 1 50,75,100

Page 8: ABB TDC Voltage Transformer - ABB MV Medium Voltage Transformer - Indoor Cast Resin Voltage Transformer Double Pole ABB TDC

1VLC

0005

23 -

Rev

. 2, e

n 20

11, 0

1.15

.

ABB s.r.o.

PPMV Brno

Videnska 117

619 00 Brno, Czech Republic

Tel.: +420 547 152 602

+420 547 152 614

Fax: +420 547 152 626

E-mail: [email protected]

www.abb.com

The data and ilustrations in this catalogue are not binding. We reserve the right to make changes of the content, in the course of technical development of the product.

Page 9: ABB TDC Voltage Transformer - ABB MV Medium Voltage Transformer - Indoor Cast Resin Voltage Transformer Double Pole ABB TDC

DescriptionThe TDC 7 double-pole insulated voltage transformers are casted in epox resin and designed mostly for insulation voltage 36 kV. Insulation voltages different from the above are to be the subject of an agreement between the manufacturer and the customer. If no a different value is required the transformers are manufactured with a overvoltage factor of 1.2 x Un. Both outlets of the primary winding, including the respective terminal is insulated from the earth to a level which corresponds to the rated insulation value. Most of the transformers are equipped with one secondary windings. One terminal of each secondary winding has to be earthed during the transformer operation. The transformer can be mounted in any position. The transformer are fixed by four screws. The secondary terminal board is covered with sealable cover.

Secondary wiringThe terminal box is entirely metal and provided with two detachable threaded inserts, Pg 16. Degree of protection is IP 30. The terminals are provided with M5 screws for the termination of the secondary wiring and with throughgoing holes for direct earthing of the secondary circuit by M6 screws. The terminal cover is sealable.

Highest voltage for equipment [kV] 36

Power frequency test voltage, 1 min. [kV] 70

Lightning impulse test voltage [kV] 170

Max. rated burden, classes [VA/cl] 50/0.2 - 150/0.5 - 250/1

P6/002-05]lc/AV[ gnidniw laudiseR

TDC 7Indoor voltage transformers

Medium Voltage Product

Page 10: ABB TDC Voltage Transformer - ABB MV Medium Voltage Transformer - Indoor Cast Resin Voltage Transformer Double Pole ABB TDC

2

Marking of the voltage transformer outlets

Secondary terminals of TDC 7The double pole models can have max. 4 sec. terminals

Primary winding

Type Highest voltagekV

Alternating test voltagekV

Impulse testvoltage1.2/50 μs, kV

RatedfrequencyHz

TDC 7 36 70 170 50 (60)

The test voltage of secondary winding is 3 kV (1 min)

System and test voltages

StandardsThe transformers are manufactured according to the requirements and recommendations of the following standards and regulations : IEC, ANSI, VDE, BS, GOST and ČSN.

Double pole insulated voltage transformers

Type TDC 7

Primary voltage 25000...36000 V

Terminal marking A–B

Max. number of secondary windings 2

Secondary voltage 100 V110 V

Terminal marking a–b

Accuracy class 0.2 0.5 1 3 3P

Rated burden max. VA 1) 60 150 300 500 300

Secondary thermal limiting current U = 1.2 x Un max. 8 A

Mechanical strength of primary terminal 5 kN

Weight approx. 72 kg

1) Valid for single measuring winding only.Available outputs for double meas. wdgs are calculated on request.

Page 11: ABB TDC Voltage Transformer - ABB MV Medium Voltage Transformer - Indoor Cast Resin Voltage Transformer Double Pole ABB TDC

3

Dimensions

Sealable

M10

12

150

217 178421

19

14

225

1436

6

2 pcs Pg 16

2039

0

M8

250

5

A B

ba

320

AU

! 30

BV

150

Weight ca. 57 kg

Creepage distance 334 mmArcing distance 304 mm

Circuit diagram, standard

Page 12: ABB TDC Voltage Transformer - ABB MV Medium Voltage Transformer - Indoor Cast Resin Voltage Transformer Double Pole ABB TDC

1VLC

0005

36 -

Rev

. 1, e

n 20

11, 0

1.15

.

ABB s.r.o.

PPMV Brno

Videnska 117

619 00 Brno, Czech Republic

Tel.: +420 547 152 602

+420 547 152 614

Fax: +420 547 152 626

E-mail: [email protected]

www.abb.com

The data and ilustrations in this catalogue are not binding. We reserve the right to make changes of the content, in the course of technical development of the product.


Recommended