REVISION NO: 002 PRODUCT DATA SHEET REPORT NO: 021 PRODUCT CODE: AB300 ABSEIL ANCHORS 021
Transcript
  • REVISION NO: 002PRODUCT DATA SHEET REPORT NO: 021

    PRODUCT CODE: AB300

    ABSEIL ANCHORS

    021

  • For any technical queries please call our advice line on 0845 241 9102 3

    AVIATOR ABSEIL ANCHORS

    021

    PRODUCT DESCRIPTION:Abseil anchors are designed to be fixed to a structural substrate such as structural steel or concrete to provide suitable rope access connection points. It is essential when designing rope access to ensure at least 2 connection points are available to connect to at any one time. There are 2 types of abseil anchors available – abseil brackets and abseil eyebolts. Brackets are supplied in galvanised steel with stainless steel components. Neoprene washers ensure no galvanic reaction can take place. Abseil eyebolts are supplied in stainless steel . Brackets and eyebolts are secured to concrete with resin anchors and to steelwork with stainless steel bolts, washers and vibration proof nuts. When fixing to metal deck or timber deck it may be necessary to provide a backing plate to ensure compliance.

    The brackets are designed for 1 user at any one time and 2 users in the event of emergency access requirements. Brackets need to be positioned so any rope connections do not exceed a 120 degree angle when in use – an angle of 90 degrees is recommended. This will be determined by the design layout and position of the anchors. Involving our specialist design teams as early as possible will ensure the most cost effective system is used without compromising any safety or access requirements. Our designers will consider the welfare and safety of both rope access and non-rope access personal during the construction and future use.

    General arrangement

    Absolute maximum angle

    Recommended angle

    (the smaller the better)

    Angle to be avoided

    1 0.7kN

    1.0kN 2.0kN

    900

    1kN

    1kN 1kN

    0.7kN

    1.0kN 2.0kN

    2

  • For any technical queries please call our advice line on 0845 241 91024

    AVIATOR ABSEIL ANCHORS

    021

    Brackets can be supplied in varying heights from 150mm up to 750mm to accommodate different roof constructions. The brackets are manufactured with a strengthening gusset

    to ensure compliance with 15kN design load requirements. Eyebolts are supplied in 150mm or 100mm lengths for concrete and block/brick fixing. Shorter eyebolts of 50mm are used in structural steel. For timber of sufficient strength the 150mm eyebolt can be used with vibration resistant locking nuts and large washers either side. A minimum thickness of 125 mm treated timber is required. Both abseil anchors and eyebolts can be installed

    on the horizontal or vertical substrates of a building. Careful consideration must be taken when designing the abseil positions to ensure abseil ropes will not foul with any roof plant or roof penetrations. If ropes are required to lie over any parapet walls or edge protection such as balustrading it will be necessary to ensure that the parapet has been re-enforced. The use of a abseil rope spreader plate can reduce the point loading considerably.

    The main contractor is responsible for calculations regarding building loading capabilities and is responsible for the reinforcement of the parapet. As a rule a minimum force of 1.5 kN should be considered.

    Bracket heights

    150mm

    250mm

    350mm

    450mm

    550mm

    Concrete Block / Brickwork eyebolts

    Socket

    150mm

    100mm

    100mm

    Steel fix Timber fix

    50mm

    150mm

    Rope over parapet wall

    ULS15kN

  • For any technical queries please call our advice line on 0845 241 9102 5

    AVIATOR ABSEIL ANCHORS

    021

    Yield 275 N/mm² C 0.15 – 0.26; Si < 0.35; Mn < 1.5; P < 0.035;

    S < 0.040; Mo 0.4 – 0.6.

    Young’s Modulus of Elasticity 200 x 103 MPa at 20 °C

    Density 7.87 g/cm3 at 20 °C

    Coefficient of Thermal Expansion Low-Carbon/HSLAS: 12.4 μm/m/°C in 20 °C to 100 °C range

    I-F Steel: 12.9 μm/m/°C in 20 °C to 100 °C range

    Thermal Conductivity Low-Carbon/HSLAS: 89 W/m°C at 20°C I-F Steel: 93 W/m°C

    at 20°C

    Specific Heat 481 J/kg/°C in 50 °C to 100 °C range

    Electrical Resistivity 0.142 μΩ•m at 20 °C

    MATERIAL SPECIFICATION:Brackets - galvanised steel

    Component partsStainless Steel - Grade 304 (UNS S30400)Fe,

  • For any technical queries please call our advice line on 0845 241 91026

    AVIATOR ABSEIL ANCHORS

    021

    Maintenance to be in accordance with SIMS standards. (details available on request)

    Maintenance to be carried out at time of yearly inspection.

    Contact Sayfa Systems to arrange system maintenance.

    TRAINING REQUIREMENTS:All personnel who use the Aviator system should have attended a Sayfa Systems Ltd, Aviator users course.

    Courses are available from Sayfa Systems UK Ltd.

    Courses cover the use of all Aviator and Payload products, the legal and practical side of the Working at Height legislation - 2005 and how to use and carry out safety checks on harnesses and all necessary PPE equipment.

    INSPECTION/MAINTENANCE/TRAINING

    INSPECTION ROUTINE:All systems to be inspected at least every 12 months from date of installation.

    In harsh environments all systems to be inspected at least every 3 months.

    Inspections must be carried out by approved Aviator engineers.

    Inspections must be approved to SIMS (Safety Inspection and Maintenance Service) standards.

    All inspections to be carried out to EN795:2012 and BS 7883:2005 and WAHSA (inspection of eyebolts) requirements for safety line and anchor points.

    All inspections to be carried out to EN364 requirements for personal protective equipment.

    Contact Sayfa Systems to arrange inspections.

    MAINTENANCE SCHEDULE:All maintenance to be carried out by approved Aviator engineers. Maintenance to be in accordance with Sayfa Systems UK (manufacturer) guidelines and recommendations.

    In harsh environments all systems to be inspected at least every 3 months.

    12 Months

    From date of installation

    3Months

    in harsh environments

    d

    12 Months

    From date of installation

    6Months

    in harsh environments

    d

    CERTIFICATEOF

    OPERATIVE INSTRUCTIONAL TECHNIQUES AND

    WORKING AT HEIGHT SAFETY

    In recognition of successful completion of training for the installation and assembly, use, handling and safety checks of:-

    Aviator Safety Line Systems nAviator Mobile Anchors

    Payload Access Ladder Systems

    Payload Handrail Systems

    Aviator PPE n

    To:

    ........................................................................

    Location of Training:

    ............................................................................0......................................................................

    Certificate Number:

    ........................................................................

    Name of trainee: ...................................................... Signed by trainee: .............................................

    Inductor’s name: Adrian Stutterheim .................. Signed: Adrian Stutterheim ................................

    Date of Training: 00 January 1900 .......................

  • For any technical queries please call our advice line on 0845 241 9102 7

    AVIATOR ABSEIL ANCHORS

    021

    OPERATING AND DESIGN STANDARDS:Eurocodes are designated by EN

    British standards are designated by BS

    • Steel – EN10 113 and EN 10 025

    • BS 7985: 2013 Code of Practice for Rope Access Methods for industrial purposes

    • The lifting operations and lifting equipment regulations 1998

    • LOLER REG. 5(1) (a and b) for design

    • LOLER REG. 7(a, d and e) for marking

    • LOLER REG. 9 (1, 2 , 3 a and b) for examination

    • ISO 9001:2008, ISO14001:2004, BS OHSAS 18001:2007

    • Management of health and safety at work regulations 1999 (MHSWR) ref.2

    • Work at height regulations 2005 (Ref 7)

    • Work at height (amended) regulations 2007 (Ref. 8) WAHR

    • BS ISO 22846-2:2012 Personal Equipment for the protection against falls -Code of Practice

    • BS ISO 22846 - 1 :2003 Personal Equipment for the protection against falls - Fundamental Principles for a system of work

    • Provision and use of work equipment regulations 1999 PUWER 98 (Ref.5)

    • The work at height safety association WAHSA- guidance on inspecting eyebolts for personal fall protection purposes

    Ultimate factored load on bracket base Bracket moment

    15.0kN

    Note: For guidelines only to be checked by Chief Engineer.

    BS ENISO

    Standards

    Typical connection loads (bracket height up to 150mm)

    The company operates to the following standards

    8.25kN/m

  • For any technical queries please call our advice line on 0845 241 91028

    AVIATOR ABSEIL ANCHORS

    021

    COMPONENT PART DETAILS:Abseil brackets AB300 BIM No: SpecEquip_RfSftySymAbslBkt_SayfaSystems_AB300_

    M3_G2

    Resin fix Abseil eyebolts EBRF370 BIM No: SpecEquip_RfSftySymAbsEye BltCon_SayfaSystems_

    EBRF370_M3_G2

    Steelwork abseil eyebolts EBSF365 BIM No: SpecEquip_RfSftySymAbsEye BltStl_SayfaSystems_

    EBRF365_M3_G2

    Timber abseil eyebolt EBRF390 BIM No: SpecEquip_RfSftySymAbsEye BltTimb_SayfaSystems_

    EBRF390_M3_G2

  • For any technical queries please call our advice line on 0845 241 9102 9

    AVIATOR ABSEIL ANCHORS

    021

    Aviator™ Abseil Anchor Fixed To Steelwork (Clamp Detail)

    AB300GALVANISED STEEL ABSEIL POST150-750mm

    4NR M12 (M16 IF POST OVER250mm) STAINLESS STEELTHREADED BAR FIXED TO STEELBACKING PLATE, SECURED WITHM12/M16 WASHER AND NYLOCKNUT

    NOTE:

    EACH PROJECT MUST BE LOOKED ATINDIVIDUALLY BY SAYFA SYSTEMS DESIGNDEPARTMENT BEFORE INSTALLATION.(CALCULATIONS MAY BE REQUIRED).

    PVC315PVC RAIN CAP

    SSEN320M16 STAINLESS STEEL EYENUT

    NW16NEOPRENE WASHER

    SYSTEM LABEL

    PW16SSSTAINLESS STEEL WASHER

    STEE

    LWO

    RK

    TO C

    LIEN

    T SP

    ECIF

    ICAT

    ION

    BACKING PLATE MAY VARYDEPENDING ON POST HEIGHT &STEELWORK

    · Line to be located as indicated on theroof plan.

    · Line primarily used to gain access toexposed roof edges.

    · Incorporates Aviator™ units and allSayfa Systems components required.

    · Fixing details for Aviator™ units asindicated within layout.

    · System to be used in conjunction with2m restraining lanyard unless statedotherwise.

    · Structural Engineer to confirmsubstructure can wistand LSD12-15kN. SLD 4-6kN of post/davit.

    · Enables two users simultaneously atany one time.

    System Details

    Jubilee House

    ShepshedLeicestershireLE12 9NHT:01509 502 155F:0845 130 4520www.sayfasystems.com

    Unit 3, Gelders Hall Road

    UNDER THE CDM REGULATIONS 2015, IF ANY ALTERATIONS ARE MADE TO THIS DRAWING THEN THE PERSON UNDERTAKING THESE CHANGES ASSUME THE ROLE OF THE DESIGNER, THEREFORE TAKING FULL CDM RESPONSIBILITY.

    Drawing Symbols

    THIS DRAWING IS PROTECTED BY COPYRIGHT AND THE INFORMATION HEREIN IS CONFIDENTIAL. THE DRAWING MAY NOT BE COPIED AND THE INFORMATION HEREIN MAY NOT BE USED OR DISCLOSED EXCEPT WITH THE WRITTEN PERMISSION OF SAYFA SYSTEMS ©

    THIS DRAWING WAS CREATED INCONJUNCTION WITH N/A

    DRAWING NO. N/A

    DRAWING REVISIONS

    REV BY DATE COMMENTS

    A C.S 19/06/2018 Issued for design

    Client:

    Contract:

    Project Title:

    SAYFA SYSTEMS UKLIMITED

    FIXING DETAILS

    AVIATOR™ ABSEIL ANCHORFIXED TO STEELWORK(CLAMP DETAIL)

    Revision:

    Drawn By:

    Scale:

    Date:

    Checked By:

    Job No:

    DWG No:

    Status:

    Released By:

    N/A

    N/A

    A

    C.S

    FOR DESIGN

    1:3 @ A3

    19/06/2018

    M.S

  • For any technical queries please call our advice line on 0845 241 910210

    AVIATOR ABSEIL ANCHORS

    021

    Aviator™ Abseil Anchor Fixed To Timber (Clamp Detail)

    AB300GALVANISED STEEL ABSEIL POST150-750mm

    4NR M12 (M16 IF POST OVER250mm) STAINLESS STEELTHREADED BAR FIXED TO STEELBACKING PLATE, SECURED WITHM12/M16 WASHER AND NYLOCKNUT

    NOTE:

    EACH PROJECT MUST BE LOOKED ATINDIVIDUALLY BY SAYFA SYSTEMS DESIGNDEPARTMENT BEFORE INSTALLATION.(CALCULATIONS MAY BE REQUIRED).

    PVC315PVC RAIN CAP

    SSEN320M16 STAINLESS STEEL EYENUT

    NW16NEOPRENE WASHER

    SYSTEM LABEL

    PW16SSSTAINLESS STEEL WASHER

    TIM

    BER

    TO

    CLI

    ENT

    SPEC

    IFIC

    ATIO

    N

    BACKING PLATE MAY VARYDEPENDING ON POST HEIGHT &STEELWORK

    · Line to be located as indicated on theroof plan.

    · Line primarily used to gain access toexposed roof edges.

    · Incorporates Aviator™ units and allSayfa Systems components required.

    · Fixing details for Aviator™ units asindicated within layout.

    · System to be used in conjunction with2m restraining lanyard unless statedotherwise.

    · Structural Engineer to confirmsubstructure can wistand LSD12-15kN. SLD 4-6kN of post/davit.

    · Enables two users simultaneously atany one time.

    System Details

    Jubilee House

    ShepshedLeicestershireLE12 9NHT:01509 502 155F:0845 130 4520www.sayfasystems.com

    Unit 3, Gelders Hall Road

    UNDER THE CDM REGULATIONS 2015, IF ANY ALTERATIONS ARE MADE TO THIS DRAWING THEN THE PERSON UNDERTAKING THESE CHANGES ASSUME THE ROLE OF THE DESIGNER, THEREFORE TAKING FULL CDM RESPONSIBILITY.

    Drawing Symbols

    THIS DRAWING IS PROTECTED BY COPYRIGHT AND THE INFORMATION HEREIN IS CONFIDENTIAL. THE DRAWING MAY NOT BE COPIED AND THE INFORMATION HEREIN MAY NOT BE USED OR DISCLOSED EXCEPT WITH THE WRITTEN PERMISSION OF SAYFA SYSTEMS ©

    THIS DRAWING WAS CREATED INCONJUNCTION WITH N/A

    DRAWING NO. N/A

    DRAWING REVISIONS

    REV BY DATE COMMENTS

    A C.S 19/06/2018 Issued for design

    Client:

    Contract:

    Project Title:

    SAYFA SYSTEMS UKLIMITED

    FIXING DETAILS

    AVIATOR™ ABSEIL ANCHORFIXED TO TIMBER(CLAMP DETAIL)

    Revision:

    Drawn By:

    Scale:

    Date:

    Checked By:

    Job No:

    DWG No:

    Status:

    Released By:

    N/A

    N/A

    A

    C.S

    FOR DESIGN

    1:3 @ A3

    19/06/2018

    M.S

  • For any technical queries please call our advice line on 0845 241 9102 11

    AVIATOR ABSEIL ANCHORS

    021

    Aviator™ Abseil Anchor System Fixed In To Cast Concrete Slab On Metal Deck

    INSU

    LATI

    ON

    TO

    CLI

    ENTS

    SPE

    CG

    RO

    WIN

    G M

    EDIU

    M &

    PLA

    NTI

    NG

    100m

    m M

    IN C

    LEAR

    ANC

    E16

    0mm

    MIN

    IMU

    M

    4nr M12 (M16 IF POST OVER 250mm)RESIN ANCHOR SET 110mm INTOCONCRETE

    MET

    AL D

    ECK

    TO C

    LIEN

    TSP

    EC

    PITCH POCKET SEALING DETAIL(RECOMMENDED) BY ROOFINGCONTRACTOR

    AB300GALVANISED STEEL ABSEIL POST150-750mm

    PVC315PVC RAIN CAP

    SSEN320M16 STAINLESS STEEL EYENUT

    NW16NEOPRENE WASHER

    SYSTEM LABEL

    PW16SSSTAINLESS STEEL WASHER

    4NR M12 (M16 IF POST OVER250mm) STAINLESS STEEL RESINFIX ANCHORS SET 110mm INCONCRETE

    · Line to be located as indicated on theroof plan.

    · Line primarily used to gain access toexposed roof edges.

    · Incorporates Aviator™ units and allSayfa Systems components required.

    · Fixing details for Aviator™ units asindicated within layout.

    · System to be used in conjunction with2m restraining lanyard unless statedotherwise.

    · Structural Engineer to confirmsubstructure can wistand LSD12-15kN. SLD 4-6kN of post/davit.

    · Enables two users simultaneously atany one time.

    System Details

    Jubilee House

    ShepshedLeicestershireLE12 9NHT:01509 502 155F:0845 130 4520www.sayfasystems.com

    Unit 3, Gelders Hall Road

    UNDER THE CDM REGULATIONS 2015, IF ANY ALTERATIONS ARE MADE TO THIS DRAWING THEN THE PERSON UNDERTAKING THESE CHANGES ASSUME THE ROLE OF THE DESIGNER, THEREFORE TAKING FULL CDM RESPONSIBILITY.

    Drawing Symbols

    THIS DRAWING IS PROTECTED BY COPYRIGHT AND THE INFORMATION HEREIN IS CONFIDENTIAL. THE DRAWING MAY NOT BE COPIED AND THE INFORMATION HEREIN MAY NOT BE USED OR DISCLOSED EXCEPT WITH THE WRITTEN PERMISSION OF SAYFA SYSTEMS ©

    THIS DRAWING WAS CREATED INCONJUNCTION WITH N/A

    DRAWING NO. N/A

    DRAWING REVISIONS

    REV BY DATE COMMENTS

    B C.S 22/06/2018 Part No.s added

    Client:

    Contract:

    Project Title:

    SAYFA SYSTEMS UKLIMITED

    FIXING DETAILS

    AVIATOR™ ABSEIL ANCHOR SYSTEM FIXED IN TO CASTCONCRETE SLAB ON METALDECK

    Revision:

    Drawn By:

    Scale:

    Date:

    Checked By:

    Job No:

    DWG No:

    Status:

    Released By:

    N/A

    N/A

    B

    C.S

    FOR DESIGN

    1:4 @ A3

    22/06/2018

    M.S

  • For any technical queries please call our advice line on 0845 241 910212

    AVIATOR ABSEIL ANCHORS

    021

    Aviator™ Abseil Anchor Fixed To Hollowcore Concrete Slab Slab

    PRE

    CAS

    T TO

    CLI

    ENTS

    SPE

    CIN

    SULA

    TIO

    N T

    O C

    LIEN

    TS S

    PEC

    GR

    OW

    ING

    MED

    IUM

    & P

    LAN

    TIN

    G10

    0mm

    MIN

    CLE

    ARAN

    CE

    4NR M12 (M16 IF OVER 250mm) STAINLESS STEELTHREADED BAR FIXED THROUGH HOLLOWCOREAND BACKING PLATE, SECURED WITH M16 WASHER& NYLOCK NUT.

    GRB250-750mm GALVANISED STEEL BRACKET

    PVC315PVC RAIN CAP

    SSEN320M16 STAINLESS STEEL EYENUT

    NW16NEOPRENE WASHER

    HG125SYSTEM LABEL

    PW16SSSTAINLESS STEEL WASHER

    BOOT STYLESEALING DETAIL(RECOMMENDED)BY ROOFINGCONTRACTOR

    · Line to be located as indicated on theroof plan.

    · Line primarily used to gain access toexposed roof edges.

    · Incorporates Aviator™ units and allSayfa Systems components required.

    · Fixing details for Aviator™ units asindicated within layout.

    · System to be used in conjunction with2m restraining lanyard unless statedotherwise.

    · Structural Engineer to confirmsubstructure can wistand LSD12-15kN. SLD 4-6kN of post/davit.

    · Enables two users simultaneously atany one time.

    System Details

    Jubilee House

    ShepshedLeicestershireLE12 9NHT:01509 502 155F:0845 130 4520www.sayfasystems.com

    Unit 3, Gelders Hall Road

    UNDER THE CDM REGULATIONS 2015, IF ANY ALTERATIONS ARE MADE TO THIS DRAWING THEN THE PERSON UNDERTAKING THESE CHANGES ASSUME THE ROLE OF THE DESIGNER, THEREFORE TAKING FULL CDM RESPONSIBILITY.

    Drawing Symbols

    THIS DRAWING IS PROTECTED BY COPYRIGHT AND THE INFORMATION HEREIN IS CONFIDENTIAL. THE DRAWING MAY NOT BE COPIED AND THE INFORMATION HEREIN MAY NOT BE USED OR DISCLOSED EXCEPT WITH THE WRITTEN PERMISSION OF SAYFA SYSTEMS ©

    THIS DRAWING WAS CREATED INCONJUNCTION WITH N/A

    DRAWING NO. N/A

    DRAWING REVISIONS

    REV BY DATE COMMENTS

    A 22/12/2014 Issued for design

    B C.S 24/10/2018 Issued forinformation

    Client:

    Contract:

    Project Title:

    SAYFA SYSTEMS UKLIMITED

    FIXING DETAILS

    AVIATOR™ ABSEIL ANCHORFIXED TO HOLLOWCORECONCRETE SLABSLAB

    Revision:

    Drawn By:

    Scale:

    Date:

    Checked By:

    Job No:

    DWG No:

    Status:

    Released By:

    N/A

    N/A

    B

    C.S

    FOR DESIGN

    1:3 @ A3

    22/12/2014

    M.S

  • For any technical queries please call our advice line on 0845 241 9102 13

    AVIATOR ABSEIL ANCHORS

    021

    Aviator™ Permanent Eyebolt System Fixed To Concrete Slab

    M12 STAINLESS STEELEYE BOLT

    NW12NEOPRENE WASHER

    SYSTEM LABEL

    EBRF390/ST/STSTAINLESS STEELEYEBOLT M12 x 95mmRESIN ANCHORED INTO CONCRETE

    150

    NOTES:

    · CONCRETE TO BE MINIMUM 175mm THICK· 300mm MINIMUM SPACING BETWEEN ANCHORS· NO TRIAL TEST NEEDED IN CONCRETE UNLESS SUSPECT· 6kN PROOF TEST REQUIRED· EACH PROJECT TO BE ASSESSED BY SAYFA SYSTEMS

    DESIGN & OPERATIONS DEPARTMENTS FOR FEASIBILITY

    · Line to be located as indicated on theroof plan.

    · Line primarily used to gain access toexposed roof edges.

    · Incorporates Aviator™ units and allSayfa Systems components required.

    · Fixing details for Aviator™ units asindicated within layout.

    · System to be used in conjunction with2m restraining lanyard unless statedotherwise.

    · Structural Engineer to confirmsubstructure can wistand LSD12-15kN. SLD 4-6kN of post/davit.

    · Enables two users simultaneously atany one time.

    System Details

    Jubilee House

    ShepshedLeicestershireLE12 9NHT:01509 502 155F:0845 130 4520www.sayfasystems.com

    Unit 3, Gelders Hall Road

    UNDER THE CDM REGULATIONS 2015, IF ANY ALTERATIONS ARE MADE TO THIS DRAWING THEN THE PERSON UNDERTAKING THESE CHANGES ASSUME THE ROLE OF THE DESIGNER, THEREFORE TAKING FULL CDM RESPONSIBILITY.

    Drawing Symbols

    THIS DRAWING IS PROTECTED BY COPYRIGHT AND THE INFORMATION HEREIN IS CONFIDENTIAL. THE DRAWING MAY NOT BE COPIED AND THE INFORMATION HEREIN MAY NOT BE USED OR DISCLOSED EXCEPT WITH THE WRITTEN PERMISSION OF SAYFA SYSTEMS ©

    THIS DRAWING WAS CREATED INCONJUNCTION WITH N/A

    DRAWING NO. N/A

    DRAWING REVISIONS

    REV BY DATE COMMENTS

    B C.S 20/06/2018 Part No.s added

    Client:

    Contract:

    Project Title:

    SAYFA SYSTEMS UKLIMITED

    FIXING DETAILS

    AVIATOR™ PERMANENT EYEBOLT SYSTEM FIXED TOCONCRETE SLAB

    Revision:

    Drawn By:

    Scale:

    Date:

    Checked By:

    Job No:

    DWG No:

    Status:

    Released By:

    N/A

    N/A

    B

    C.S

    FOR DESIGN

    1:4 @ A3

    20/06/2018

    M.S

  • For any technical queries please call our advice line on 0845 241 910214

    AVIATOR ABSEIL ANCHORS

    021

    Aviator™ Permanent Eyebolt System Fixed To Solid Brickwork/Stonework

    M12 STAINLESS STEELEYE BOLT

    NW12NEOPRENE WASHER

    SYSTEM LABEL

    EBRF390ST/STSTAINLESS STEELM12 x 95mm EYEBOLTRESIN ANCHORED TOBRICKWORK

    · SOLID BRICKWORK/STONEWORK TO BE MINIMUM 215mm THICK· 350mm MINIMUM SPACING BETWEEN ANCHORS (UNRENDERED)· 500mm MINIMUM SPACING BETWEEN ANCHORS (RENDERED)· 12kN TRIAL TEST NEEDED· 6kN PROOF TEST REQUIRED· FIXING TO NON LOAD BEARING STRUCTURES SUBJECT TO

    STRUCTURAL CALCULATIONS

    280 MIN

    · Line to be located as indicated on theroof plan.

    · Line primarily used to gain access toexposed roof edges.

    · Incorporates Aviator™ units and allSayfa Systems components required.

    · Fixing details for Aviator™ units asindicated within layout.

    · System to be used in conjunction with2m restraining lanyard unless statedotherwise.

    · Structural Engineer to confirmsubstructure can wistand LSD12-15kN. SLD 4-6kN of post/davit.

    · Enables two users simultaneously atany one time.

    System Details

    Jubilee House

    ShepshedLeicestershireLE12 9NHT:01509 502 155F:0845 130 4520www.sayfasystems.com

    Unit 3, Gelders Hall Road

    UNDER THE CDM REGULATIONS 2015, IF ANY ALTERATIONS ARE MADE TO THIS DRAWING THEN THE PERSON UNDERTAKING THESE CHANGES ASSUME THE ROLE OF THE DESIGNER, THEREFORE TAKING FULL CDM RESPONSIBILITY.

    Drawing Symbols

    THIS DRAWING IS PROTECTED BY COPYRIGHT AND THE INFORMATION HEREIN IS CONFIDENTIAL. THE DRAWING MAY NOT BE COPIED AND THE INFORMATION HEREIN MAY NOT BE USED OR DISCLOSED EXCEPT WITH THE WRITTEN PERMISSION OF SAYFA SYSTEMS ©

    THIS DRAWING WAS CREATED INCONJUNCTION WITH N/A

    DRAWING NO. N/A

    DRAWING REVISIONS

    REV BY DATE COMMENTS

    B C.S 20/06/2018 Part No.s added

    Client:

    Contract:

    Project Title:

    SAYFA SYSTEMS UKLIMITED

    FIXING DETAILS

    AVIATOR™ PERMANENT EYEBOLT SYSTEM FIXED TOSOLID BRICKWORK/STONEWORK

    Revision:

    Drawn By:

    Scale:

    Date:

    Checked By:

    Job No:

    DWG No:

    Status:

    Released By:

    N/A

    N/A

    B

    C.S

    FOR DESIGN

    1:4 @ A3

    20/06/2018

    M.S

  • For any technical queries please call our advice line on 0845 241 9102 15

    AVIATOR ABSEIL ANCHORS

    021

    Aviator™ Permanent Eyebolt System Fixed To Brickwork With Cavity

    M12 STAINLESS STEELEYE BOLT

    NEOPRENE WASHER

    SYSTEM LABEL

    STAINLESS STEELM12 EYEBOLTTHROUGH FIXED TOBRICK/BLOCK WALL

    NOTES:

    · INSTALLATION ALLOWS FOR ANY THICKNESS OF WALL· 350mm MINIMUM SPACING BETWEEN ANCHORS (UNRENDERED)· 500mm MINIMUM SPACING BETWEEN ANCHORS (RENDERED)· MUST NOT BE LOAD TESTED AT ANY STAGE

    280

    MIN

    STAINLESS STEELBACK PLATE

    M12 STAINLESSSTEEL NUT

    BRICKWORK

    BLOCKWORK

    ANTI-COMPRESSION TUBE(ONLY REQUIRED IN CAVITYCONSTRUCTIONS)

    Client:

    Contract:

    Project Title:

    · Line to be located as indicated on theroof plan.

    · Line primarily used to gain access toexposed roof edges.

    · Incorporates Aviator™ units and allSayfa Systemscomponents required.

    · Fixing details for Aviator™ units asindicated within layout.

    · System to be used in conjunction with2m restraining lanyard unless statedotherwise.

    · Enables two users simultaneously atany one time.

    System Details

    SAYFA SYSTEMS UKLIMITED

    FIXING DETAIL

    AVIATOR™PERMANENT EYEBOLTSYSTEM FIXED TOBRICKWORK WITHCAVITY

    Revision:

    Drawn By: C.S

    Scale:

    Date:

    Checked By:

    Job No:

    DWG No:

    Jubilee House

    ShepshedLeicestershireLE12 9NHT: 01509 502 155F:0845 130 4520www.sayfasystems.com

    Unit 3, Gelders Hall Road

    Status:

    UNDER THE CDM REGULATIONS 2015, IF ANY ALTERATIONS ARE MADE TO THIS DRAWING THEN THE PERSON UNDERTAKING THESE CHANGES ASSUME THE ROLE OF THE DESIGNER, THEREFORE TAKING FULL CDM RESPONSIBILITY.

    Drawing Symbols

    THIS DRAWING IS PROTECTED BY COPYRIGHT AND THE INFORMATION HEREIN IS CONFIDENTIAL. THE DRAWING MAY NOT BE COPIED AND THE INFORMATION HEREIN MAY NOT BE USED OR DISCLOSED EXCEPT WITH THE WRITTEN PERMISSION OF SAYFA SYSTEMS ©

    DRAWING REVISIONSREV DATE COMMENT

    A 18/04/2018 Issued for internalreview

    THIS DRAWING WAS CREATED INCONJUNCTION WITH N/A

    DRAWING NO. N/A

    18/04/2018

    As Dimensioned

    For DesignN/A

    N/A

    A

    M.S

  • For any technical queries please call our advice line on 0845 241 910216

    AVIATOR ABSEIL ANCHORS

    021

    Aviator™ Permanent Eyebolt System Fixed To Hollowcore Concrete Slab

    M12 EN795STAINLESS STEELEYE BOLT

    NEO PRENE WASHER

    SYSTEM LABEL

    NOTES:

    · CONCRETE TO BE MINIMUM 176mm THICK· 300mm MINIMUM SPACING BETWEEN ANCHORS· NO TRIAL TEST NEEDED IN CONCRETE· 6kN PROOF TEST REQUIRED OR TIGHTEN TO REQUIRED TORQUE

    150 MIN

    STAINLESS STEELEYEBOLT M12 EXTENDEDWITH THREADED COUPLERTHROUGH FIXED TOCONCRETE

    STAINLESS STEELBACK PLATE

    M12 STAINLESSSTEEL NUT

    Client:

    Contract:

    Project Title:

    · Line to be located as indicated on theroof plan.

    · Line primarily used to gain access toexposed roof edges.

    · Incorporates Aviator™ units and allSayfa Systemscomponents required.

    · Fixing details for Aviator™ units asindicated within layout.

    · System to be used in conjunction with2m restraining lanyard unless statedotherwise.

    · Enables two users simultaneously atany one time.

    System Details

    SAYFA SYSTEMS

    FIXING DETAIL

    AVIATOR™PERMANENT EYEBOLTSYSTEM FIXED TOHOLLOWCORECONCRETE SLAB

    Revision:

    Drawn By: C.S

    Scale:

    Date:

    Checked By:

    Job No:

    DWG No:

    Jubilee House

    ShepshedLeicestershireLE12 9NHT: 01509 502 155F:0845 130 4520www.sayfasystems.com

    Unit 3, Gelders Hall Road

    Status:

    UNDER THE CDM REGULATIONS 2015, IF ANY ALTERATIONS ARE MADE TO THIS DRAWING THEN THE PERSON UNDERTAKING THESE CHANGES ASSUME THE ROLE OF THE DESIGNER, THEREFORE TAKING FULL CDM RESPONSIBILITY.

    Drawing Symbols

    THIS DRAWING IS PROTECTED BY COPYRIGHT AND THE INFORMATION HEREIN IS CONFIDENTIAL. THE DRAWING MAY NOT BE COPIED AND THE INFORMATION HEREIN MAY NOT BE USED OR DISCLOSED EXCEPT WITH THE WRITTEN PERMISSION OF SAYFA SYSTEMS ©

    DRAWING REVISIONSREV DATE COMMENT

    A 18/04/2018 Issued for internalreview

    THIS DRAWING WAS CREATED INCONJUNCTION WITH N/A

    DRAWING NO. N/A

    18/04/2018

    As Dimensioned

    For DesignN/A

    N/A

    A

    M.S

  • For any technical queries please call our advice line on 0845 241 9102 17

    AVIATOR ABSEIL ANCHORS

    021

    Aviator™ Permanent Eyebolt System Fixed To Thin Hollowcore Concrete Slab

    M12 EN795STAINLESS STEELEYE BOLT

    NEO PRENE WASHER

    SYSTEM LABEL

    NOTES:

    · CONCRETE TO BE 150-175mm THICK· 300mm MINIMUM SPACING BETWEEN ANCHORS· NO TRIAL TEST NEEDED IN CONCRETE· 6kN PROOF TEST REQUIRED

    150 MIN

    200

    STAINLESS STEELBACK PLATE

    M12 STAINLESSSTEEL NUT

    STAINLESS STEELEYEBOLT M12 x 200mmTHROUGH FIXEDTO CONCRETE

    Client:

    Contract:

    Project Title:

    · Line to be located as indicated on theroof plan.

    · Line primarily used to gain access toexposed roof edges.

    · Incorporates Aviator™ units and allSayfa Systemscomponents required.

    · Fixing details for Aviator™ units asindicated within layout.

    · System to be used in conjunction with2m restraining lanyard unless statedotherwise.

    · Enables two users simultaneously atany one time.

    System Details

    SAYFA SYSTEMS

    FIXING DETAIL

    AVIATOR™PERMANENT EYEBOLTSYSTEM FIXED TOTHIN HOLLOWCORECONCRETE SLAB

    Revision:

    Drawn By: C.S

    Scale:

    Date:

    Checked By:

    Job No:

    DWG No:

    Jubilee House

    ShepshedLeicestershireLE12 9NHT: 01509 502 155F:0845 130 4520www.sayfasystems.com

    Unit 3, Gelders Hall Road

    Status:

    UNDER THE CDM REGULATIONS 2015, IF ANY ALTERATIONS ARE MADE TO THIS DRAWING THEN THE PERSON UNDERTAKING THESE CHANGES ASSUME THE ROLE OF THE DESIGNER, THEREFORE TAKING FULL CDM RESPONSIBILITY.

    Drawing Symbols

    THIS DRAWING IS PROTECTED BY COPYRIGHT AND THE INFORMATION HEREIN IS CONFIDENTIAL. THE DRAWING MAY NOT BE COPIED AND THE INFORMATION HEREIN MAY NOT BE USED OR DISCLOSED EXCEPT WITH THE WRITTEN PERMISSION OF SAYFA SYSTEMS ©

    DRAWING REVISIONSREV DATE COMMENT

    A 18/04/2018 Issued for internalreview

    THIS DRAWING WAS CREATED INCONJUNCTION WITH N/A

    DRAWING NO. N/A

    18/04/2018

    As Dimensioned

    For DesignN/A

    N/A

    A

    M.S

    M12 EN795STAINLESS STEELEYE BOLT

    NEO PRENE WASHER

    SYSTEM LABEL

    NOTES:

    · CONCRETE TO BE 150-175mm THICK· 300mm MINIMUM SPACING BETWEEN ANCHORS· NO TRIAL TEST NEEDED IN CONCRETE· 6kN PROOF TEST REQUIRED

    150 MIN

    200

    STAINLESS STEELBACK PLATE

    M12 STAINLESSSTEEL NUT

    STAINLESS STEELEYEBOLT M12 x 200mmTHROUGH FIXEDTO CONCRETE

    Client:

    Contract:

    Project Title:

    · Line to be located as indicated on theroof plan.

    · Line primarily used to gain access toexposed roof edges.

    · Incorporates Aviator™ units and allSayfa Systemscomponents required.

    · Fixing details for Aviator™ units asindicated within layout.

    · System to be used in conjunction with2m restraining lanyard unless statedotherwise.

    · Enables two users simultaneously atany one time.

    System Details

    SAYFA SYSTEMS

    FIXING DETAIL

    AVIATOR™PERMANENT EYEBOLTSYSTEM FIXED TOTHIN HOLLOWCORECONCRETE SLAB

    Revision:

    Drawn By: C.S

    Scale:

    Date:

    Checked By:

    Job No:

    DWG No:

    Jubilee House

    ShepshedLeicestershireLE12 9NHT: 01509 502 155F:0845 130 4520www.sayfasystems.com

    Unit 3, Gelders Hall Road

    Status:

    UNDER THE CDM REGULATIONS 2015, IF ANY ALTERATIONS ARE MADE TO THIS DRAWING THEN THE PERSON UNDERTAKING THESE CHANGES ASSUME THE ROLE OF THE DESIGNER, THEREFORE TAKING FULL CDM RESPONSIBILITY.

    Drawing Symbols

    THIS DRAWING IS PROTECTED BY COPYRIGHT AND THE INFORMATION HEREIN IS CONFIDENTIAL. THE DRAWING MAY NOT BE COPIED AND THE INFORMATION HEREIN MAY NOT BE USED OR DISCLOSED EXCEPT WITH THE WRITTEN PERMISSION OF SAYFA SYSTEMS ©

    DRAWING REVISIONSREV DATE COMMENT

    A 18/04/2018 Issued for internalreview

    THIS DRAWING WAS CREATED INCONJUNCTION WITH N/A

    DRAWING NO. N/A

    18/04/2018

    As Dimensioned

    For DesignN/A

    N/A

    A

    M.S

  • For any technical queries please call our advice line on 0845 241 910218

    AVIATOR ABSEIL ANCHORS

    021

    Aviator™ Permanent Eyebolt System Fixed To Thin Concrete Slab

    M12 EN795STAINLESS STEELEYE BOLT

    NEO PRENE WASHER

    SYSTEM LABEL

    STAINLESS STEELEYEBOLT M12 x 200mmTHROUGH FIXEDTO CONCRETE

    NOTES:

    · CONCRETE TO BE 150-175mm THICK· 300mm MINIMUM SPACING BETWEEN ANCHORS· NO TRIAL TEST NEEDED IN CONCRETE UNLESS SUSPECT· 6kN PROOF TEST REQUIRED· EACH PROJECT TO BE ASSESSED BY SAYFA SYSTEMS

    DESIGN & OPERATIONS DEPARTMENTS FOR SUITABILITY

    150 MIN

    200

    STAINLESS STEELBACK PLATE

    NSS12M12 STAINLESSSTEEL NUT

    · Line to be located as indicated on theroof plan.

    · Line primarily used to gain access toexposed roof edges.

    · Incorporates Aviator™ units and allSayfa Systems components required.

    · Fixing details for Aviator™ units asindicated within layout.

    · System to be used in conjunction with2m restraining lanyard unless statedotherwise.

    · Structural Engineer to confirmsubstructure can wistand LSD12-15kN. SLD 4-6kN of post/davit.

    · Enables two users simultaneously atany one time.

    System Details

    Jubilee House

    ShepshedLeicestershireLE12 9NHT:01509 502 155F:0845 130 4520www.sayfasystems.com

    Unit 3, Gelders Hall Road

    UNDER THE CDM REGULATIONS 2015, IF ANY ALTERATIONS ARE MADE TO THIS DRAWING THEN THE PERSON UNDERTAKING THESE CHANGES ASSUME THE ROLE OF THE DESIGNER, THEREFORE TAKING FULL CDM RESPONSIBILITY.

    Drawing Symbols

    THIS DRAWING IS PROTECTED BY COPYRIGHT AND THE INFORMATION HEREIN IS CONFIDENTIAL. THE DRAWING MAY NOT BE COPIED AND THE INFORMATION HEREIN MAY NOT BE USED OR DISCLOSED EXCEPT WITH THE WRITTEN PERMISSION OF SAYFA SYSTEMS ©

    THIS DRAWING WAS CREATED INCONJUNCTION WITH N/A

    DRAWING NO. N/A

    DRAWING REVISIONS

    REV BY DATE COMMENTS

    A C.S 22/06/2018 Issued forinternal review

    Client:

    Contract:

    Project Title:

    SAYFA SYSTEMS UKLIMITED

    FIXING DETAILS

    AVIATOR™ PERMANENTEYEBOLT SYSTEM FIXED TO THIN CONCRETE SLAB

    Revision:

    Drawn By:

    Scale:

    Date:

    Checked By:

    Job No:

    DWG No:

    Status:

    Released By:

    N/A

    N/A

    A

    C.S

    FOR DESIGN

    1:3 @ A3

    22/06/2018

    M.S

    M12 EN795STAINLESS STEELEYE BOLT

    NEO PRENE WASHER

    SYSTEM LABEL

    STAINLESS STEELEYEBOLT M12 x 200mmTHROUGH FIXEDTO CONCRETE

    NOTES:

    · CONCRETE TO BE 150-175mm THICK· 300mm MINIMUM SPACING BETWEEN ANCHORS· NO TRIAL TEST NEEDED IN CONCRETE UNLESS SUSPECT· 6kN PROOF TEST REQUIRED· EACH PROJECT TO BE ASSESSED BY SAYFA SYSTEMS

    DESIGN & OPERATIONS DEPARTMENTS FOR SUITABILITY

    150 MIN

    200

    STAINLESS STEELBACK PLATE

    NSS12M12 STAINLESSSTEEL NUT

    · Line to be located as indicated on theroof plan.

    · Line primarily used to gain access toexposed roof edges.

    · Incorporates Aviator™ units and allSayfa Systems components required.

    · Fixing details for Aviator™ units asindicated within layout.

    · System to be used in conjunction with2m restraining lanyard unless statedotherwise.

    · Structural Engineer to confirmsubstructure can wistand LSD12-15kN. SLD 4-6kN of post/davit.

    · Enables two users simultaneously atany one time.

    System Details

    Jubilee House

    ShepshedLeicestershireLE12 9NHT:01509 502 155F:0845 130 4520www.sayfasystems.com

    Unit 3, Gelders Hall Road

    UNDER THE CDM REGULATIONS 2015, IF ANY ALTERATIONS ARE MADE TO THIS DRAWING THEN THE PERSON UNDERTAKING THESE CHANGES ASSUME THE ROLE OF THE DESIGNER, THEREFORE TAKING FULL CDM RESPONSIBILITY.

    Drawing Symbols

    THIS DRAWING IS PROTECTED BY COPYRIGHT AND THE INFORMATION HEREIN IS CONFIDENTIAL. THE DRAWING MAY NOT BE COPIED AND THE INFORMATION HEREIN MAY NOT BE USED OR DISCLOSED EXCEPT WITH THE WRITTEN PERMISSION OF SAYFA SYSTEMS ©

    THIS DRAWING WAS CREATED INCONJUNCTION WITH N/A

    DRAWING NO. N/A

    DRAWING REVISIONS

    REV BY DATE COMMENTS

    A C.S 22/06/2018 Issued forinternal review

    Client:

    Contract:

    Project Title:

    SAYFA SYSTEMS UKLIMITED

    FIXING DETAILS

    AVIATOR™ PERMANENTEYEBOLT SYSTEM FIXED TO THIN CONCRETE SLAB

    Revision:

    Drawn By:

    Scale:

    Date:

    Checked By:

    Job No:

    DWG No:

    Status:

    Released By:

    N/A

    N/A

    A

    C.S

    FOR DESIGN

    1:3 @ A3

    22/06/2018

    M.S

  • For any technical queries please call our advice line on 0845 241 9102 19

    AVIATOR ABSEIL ANCHORS

    021

    Aviator™ Permanent Eyebolt System Fixed To Steelwork

    EBSF365ST/STM12 EN795 STAINLESS STEELEYE BOLT 52mm LONG

    NEOPRENE WASHER

    SYSTEM LABEL M12 STAINLESS STEELSOLID SWIVEL STEELWORKEYEBOLT BOLTED THROUGHSTEEL BEAM

    PVCW16M16 CLEAR PLASTIC WASHER

    STAINLESS STEELWASHER

    STAINLESS STEELWASHER

    M12 EN795 STAINLESS STEELEYE BOLT

    PVCW16M16 CLEAR PLASTIC WASHER

    SYSTEM LABELM12 KEE SAFETYSTEELWORK EYEBOLTBLIND FIXED TO STEEL

    STAINLESS STEELSPACER

    STAINLESS STEELWASHER

    NOTES:

    · SOLID SWIVEL EYEBOLT REQUIRES MINIMUM 10mm THICKNESS· MINIMUM 27mm EDGE DISTANCE· MINIMUM 50mm SPACING BETWEEN ANCHORS· NO TRIAL TEST REQUIRED· 6kN PROOF LOAD TEST REQUIRED· 14mm COUNTERSUNK HOLE

    NOTES:

    · SOLID SWIVEL EYEBOLT REQUIRES MINIMUM 12mm THICKNESS· MINIMUM 25mm EDGE DISTANCE· MINIMUM 50mm SPACING BETWEEN ANCHORS· NO TRIAL TEST REQUIRED· 6kN PROOF LOAD TEST REQUIRED· 10.2mm COUNTERSUNK & TAP M12

    · Line to be located as indicated on theroof plan.

    · Line primarily used to gain access toexposed roof edges.

    · Incorporates Aviator™ units and allSayfa Systems components required.

    · Fixing details for Aviator™ units asindicated within layout.

    · System to be used in conjunction with2m restraining lanyard unless statedotherwise.

    · Structural Engineer to confirmsubstructure can wistand LSD12-15kN. SLD 4-6kN of post/davit.

    · Enables two users simultaneously atany one time.

    System Details

    Jubilee House

    ShepshedLeicestershireLE12 9NHT:01509 502 155F:0845 130 4520www.sayfasystems.com

    Unit 3, Gelders Hall Road

    UNDER THE CDM REGULATIONS 2015, IF ANY ALTERATIONS ARE MADE TO THIS DRAWING THEN THE PERSON UNDERTAKING THESE CHANGES ASSUME THE ROLE OF THE DESIGNER, THEREFORE TAKING FULL CDM RESPONSIBILITY.

    Drawing Symbols

    THIS DRAWING IS PROTECTED BY COPYRIGHT AND THE INFORMATION HEREIN IS CONFIDENTIAL. THE DRAWING MAY NOT BE COPIED AND THE INFORMATION HEREIN MAY NOT BE USED OR DISCLOSED EXCEPT WITH THE WRITTEN PERMISSION OF SAYFA SYSTEMS ©

    THIS DRAWING WAS CREATED INCONJUNCTION WITH N/A

    DRAWING NO. N/A

    DRAWING REVISIONS

    REV BY DATE COMMENTS

    B C.S 20/06/2018 Part No.s added

    Client:

    Contract:

    Project Title:

    SAYFA SYSTEMS UKLIMITED

    FIXING DETAILS

    AVIATOR™ PERMANENT EYEBOLT SYSTEM FIXED TOSTEELWORK

    Revision:

    Drawn By:

    Scale:

    Date:

    Checked By:

    Job No:

    DWG No:

    Status:

    Released By:

    N/A

    N/A

    B

    C.S

    FOR DESIGN

    1:4 @ A3

    20/06/2018

    M.S

  • For any technical queries please call our advice line on 0845 241 910220

    AVIATOR ABSEIL ANCHORS

    021

    Aviator™ Eyebolt Components1

    1

    2

    2

    3

    3

    4

    4

    5

    5

    6

    6

    7

    7

    8

    8

    9

    9

    10

    10

    A A

    B B

    C C

    D D

    E E

    F F

    G G

    H H

    I I

    J J

    TITLE DRAWN BY

    CLIENTMATERIAL/FINISH/

    JUBILEE HOUSEUNIT3, GELDERS HALL ROADSHEPSHEDLEICESTERSHIRELE12 9NH

    SAYFA SYSTEMS UK LTD

    THIS DRAWING IS PROTECTED BY COPYRIGHT AND THE INFORMATION HEREIN IS CONFIDENTIAL.THE DRAWING MAY NOT BE COPIED AND THE INFORMATION HEREIN MAY NOT BE USED OR DISCLOSED EXCEPT WITH THE WRITTEN PERMISSIONS OF SAYFA SYSTEMS UK.

    WEIGHT0.19 kg

    FIRST ANGLEPROJECTION

    DIMENSIONS IN MM

    DO NOT SCALE

    IF IN DOUBT, ASKTOLERANCES ON THIS DRAWINGUNLESS OTHERWISE STATEDNO DECIMAL PLACE +/- 0.25ONE DECIMAL PLACE +/- 0.1TWO DECIMAL PLACES +/- 0.05ANGLES +/- 0.25°COMPARE PARTS WITH THIS DRAWING AND READALL INSTRUCTIONS BEFORE COMMENCING WORK.MAKE NO DEVIATION FROM THIS DRAWINGWITHOUT CONSULTING SAYFA SYSTEMS UK.

    SHEET No1 / 1

    CHECKED BYAviator™ Eyebolt Components

    Sayfa Systems UK Limited

    C.Scarle M.StuartDATE25/06/2018

    DRAWING NO.N/A

    A Issued for information 25/06/2018 C.Scarle M.Stuart

    REVISION HISTORY

    REV DESCRIPTION DATE DESIGNER CHECKEDBY

    EBSF365ST/ST - M12 EN795 STAINLESS STEEL EYEBOLT 52mm LONG

    EBRF370ST/ST-100 - ABSEIL EYEBOLT 100mm LONG

    EBRF370ST/ST-150 - ABSEIL EYEBOLT 150mm LONG

    RAS120 - EYEBOLT SOCKET 120mm

    55

    95

    150

    120

    16

    R18

    R18

    R18

    12

    12

    12