User's guide Manual de uso
Manuel dutilisation
AAEEEESS
BBaatttteerryy cchhaarrggeerr CCaarrggaaddoorr ddee bbaatteerraa CChhaarrggeeuurr ddee bbaatttteerriiee
AACCPP 33
ACP3 12-2,5mD (16/04/2008)
33502023301_1_1
36013-6006913-ind D-notice ACP3 12-
2,5mD fr
Notice d'utilisation
Indice / Revision D 16/04/08 36013-6006913 1 Type
Fichier / File Notice N Page
ALIMENTATION / CHARGEUR / PRECHAUFFAGE
AACCPP33 1122--22,,55 mmDD 3311661133550055440022
SOMMAIRE
I - DESCRIPTION
I-1 Application
I-2 Fonctionnement
I-3 Caractristiques
II - GUIDE DE DIAGNOSTIC
36013-6006913-ind D-notice ACP3 12-
2,5mD fr
Notice d'utilisation
Indice / Revision D 16/04/08 36013-6006913 2 Type
Fichier / File Notice N Page
I DESCRIPTION
I-1 Application Charge de batteries d'accumulateurs de types Pb ouvert et alimentation de circuits auxiliaires ainsi que fonction de prchauffage.
Les alimentations / chargeurs srie ACP sont prrgles en tension et courant.
I-2 Fonctionnement Entirement automatiques, les alimentations / chargeurs ACP sont rgules en tension et possdent une limitation d'intensit au calibre nominal. La fonction de prchauffage s'active par bornes extrieures.
I-3 Caractristiques
Tension d'entre nominale : 230Vac - 50Hz / 60Hz Plage de tension : 187Vac - 305Vac
Sortie : 13,2Vdc ; 2,5A Environnement :
- Temprature d'utilisation : - 20 + 60 C - Temprature de stockage : - 20 + 70 C - Humidit relative : 95% 20C ("tous climats")
Stabilit rgulation : 1% en variations cumules - de la tension d'entre - du courant de sortie - de la temprature ambiante
Rsiduelle de sortie : < 1% crte crte Tenue dilectrique : - 2500Vac entre entre et sortie
- 2000Vac entre masse et entre / sortie - Transformateur conforme la norme EN 61 558-2-17
Directive DBT n 73/23/CEE modifie par directive n 93/68/CEE Directive CEM n 89/336/CEE modifie par directive n 93/68/CEE Normes CEM : NF EN 55011 ; NF EN 61000-4-2 ; NF EN 61000-4-3 ; NF EN 61000-4-4
NF EN 61000-4-5 ; NF EN 61000-4-6. Caractristiques circuit de prchauffage : 250Vac - 50Hz / 60Hz - 8A / AC1 max. Consommation : 75VA : chargeur seul ; 1560VA : chargeur + prchauffage FS : fusible secteur interne type 5 x 20 calibre 1A - T F2 : fusible sortie interne type 5 x 20 calibre 5A - T Poids : 0,5 kg Rendement : 0,8 C INV : faisceau d'alimentation chargeur / prchauffage C100 : connecteur de sortie prchauffage C28 : cosse faston 6,3 mm de report dalarme C 27 : connecteur de sortie batterie et tlcommande
prchauffage
36013-6006913-ind D-notice ACP3 12-
2,5mD fr
Notice d'utilisation
Indice / Revision D 16/04/08 36013-6006913 3 Type
Fichier / File Notice N Page
II GUIDE DE DIAGNOSTIC
Constat Cause probable Remde
La led verte "ON" teinte, pas de tension en sortie
Secteur 230Vac absent Disjoncteur ou fusible amont ouvert Fusible FS (interne) dfectueux
Vrifier le secteur et ltat des protections. Vrifier le fusible interne FS (1A-T)
Tension de sortie anormalement basse, chargeur en fonctionnement
Batterie ayant subie une dcharge complte, le chargeur est en limitation dintensit
Contrle de la tension du chargeur avec batterie dconnecte 13,2Vdc
Attendre la recharge de la batterie (la tension doit remonter progressivement)
Vrifier ltat de la batterie
La batterie est dcharge - Secteur prsent - Chargeur en
fonctionnement Fusible F2 dfectueux
Vrifier le raccordement de la batterie (polarits + / -)
Remplacer le fusible F2 (5A-T) Si le dfaut persiste, remplacer
le chargeur.
La commande "prchauffage" ne fonctionne pas (la led jaune "PRE" ne s'allume pas)
Connecteur C27 mal connect Vrifier le potentiel de borne
centrale du connecteur C27 : on doit avoir +12Vdc par rapport au moins.
Le signal dfaut est actif
Le fusible FS est HS
Le fusible F2 est HS
Le chargeur a provoqu une surtension
Le chargeur est en sous-tension
Dfaut de charge
Lentre du chargeur est en court-circuit, remplacer le chargeur
Vrifier le raccordement de la batterie (polarits + / -). Remplacer le fusible F2 (5A-T). Si le dfaut persiste, remplacer le chargeur.
Dconnecter le secteur puis la batterie, reconnecter le secteur puis la batterie, si le dfaut persiste remplacer le chargeur
La batterie et/ou lutilisation provoque une surcharge. Dbrancher lutilisation et la batterie, si le dfaut persiste vide, remplacer le chargeur.
Le chargeur est dfectueux, remplacer le chargeur
36013-6006914-ind D-notice ACP3 12-
2,5mD ang
User's Manual
Indice / Revision D 16/04/08 36013-6006914 1 Type
Fichier / File Notice N Page
POWER SUPPLY / CHARGER / PRE-HEATING
AACCPP33 1122--22,,55 mmDD 3311661133550055440022
TABLE OF CONTENTS
I - DESCRIPTION
I-1 Application
I-2 Operation
I-3 Specifications
II TROUBLE SHOOTING GUIDE
36013-6006914-ind D-notice ACP3 12-
2,5mD ang
User's Manual
Indice / Revision D 16/04/08 36013-6006914 2 Type
Fichier / File Notice N Page
I DESCRIPTION
I-1 Application Designed to charge vented lead-acid batteries and to power auxiliary circuits with a pre-heating function.
Power supply / chargers ACP series have voltage and current preset.
I-2 Operation Entirely automatic, the ACP power supply / chargers are voltage regulated and have a current limitation at nominal rating. The pre-heat function is activated by external terminals.
I-3 Specifications
Nominal input voltage : 230Vac - 50Hz / 60Hz Voltage range: 187Vac - 305Vac
Output : 13,2Vdc ; 2,5A Environment :
- Operating temperature : - 20 to + 60 C - Storage temperature : - 20 to + 70 C - Relative humidity : 95% at 20C ("all climates")
Control stability : 1% with cumulated variations of - Input voltage - Output current - Operating temperature
Output ripple voltage : < 1% peak to peak Dielectric strength : - 2500V ac between input and output
- 2000V ac between ground and input / output - Transformer in compliance with standard EN 61 558-2-17
DBT Directive No. 73/23/CEE modified by Directive No. 93/68/CEE EMC Directive No. 89/336/CEE modified by Directive No. 93/68/CEE EMC standards : NF EN 55011 ; NF EN 61000-4-2 ; NF EN 61000-4-3 ; NF EN 61000-4-4
NF EN 61000-4-5 ; NF EN 61000-4-6. Pre-heat relay characteristics : 250Vac - 50Hz / 60Hz - 8A / AC1 Consumption : 75VA : charger only ; 1560VA : charger + pre-heating FS : internal main fuse model 5 x 20 ; 1A - T F2 : internal output fuse model 5 x 20 ; 5A - T Weight : 0,5 kg Efficiency : 0,8 C INV : charger / pre-heating main cable C100 : pre-heating output terminal C28 : 6.3 mm terminal for alarm output C 27 : output terminal and pre-heating controls
36013-6006914-ind D-notice ACP3 12-
2,5mD ang
User's Manual
Indice / Revision D 16/04/08 36013-6006914 3 Type
Fichier / File Notice N Page
II TROUBLE SHOOTING GUIDE
Report Probable cause Corrective action
Green LED "ON" off, no output voltage
Main 230Vac absent Upstream circuit breaker or fuse
open FS fuse (internal) blown
Check mains and protections status. Check internal fuse FS (1A-T)
Abnormal low output voltage, charger in operation
Battery went to a complete discharge, the charger is in current limit
Check charger voltage disconnecting the battery
13,2Vdc Wait the recharge of battery
(the voltage should rise gradually)
Check the battery status
The battery is discharged - With mains on - Charger in
operation F2 fuse blown
check the battery connections (polarities +/-)
Replace F2 fuse (5A-T) If the fault persists, replace the
charger.
The "pre-heating" control does not work (yellow LED "PRE" does not light on)
C27 connector misconnected
Check voltage on central terminal of C27 connector : You should see +12Vdc between this terminal and negative polarity.
Alarm signal is active
Fuse FS is blown
Fuse F2 is blown
Charger ran over voltage
Under voltage limit hit
Charging fault
Charger input is shorted, please replace the charger
Check the battery connections (polarities +/-). Replace F2 fuse (5A-T). If the fault persists, replace the charger.
Disconnect Mains and then the battery, wait few seconds, reconnect Mains and the battery. If the fault persists, replace the charger.
Output or battery circuit overloaded. Disconnect both, if the fault persists at no load, replace the charger.
Charger is defective, replace the charger.
36013-6006915-ind D-notice ACP3 12-
2,5mD esp
Manual de uso
Indice / Revision D 16/04/08 36013-6006915 1 Type
Fichier / File Notice N Page
ALIMENTACIN / CARGADOR / PRECALENTAMIENTO
AACCPP33 1122--22,,55 mmDD 3311661133550055440022
NDICE
I - DESCRIPCIN
I-1 Aplicacin
I-2 Funcionamiento
I-3 Caractersticas
II - GUA DE DIAGNSTICO
36013-6006915-ind D-notice ACP3 12-
2,5mD esp
Manual de uso
Indice / Revision D 16/04/08 36013-6006915 2 Type
Fichier / File Notice N Page
I DESCRIPCIN
I-1 Aplicacin Carga de bateras de acumuladores de tipo Plomo abierta y alimentacin de circuitos auxiliares as que una funcin de precalentamiento.
Las fuentes / cargadores serie ACP estn preajustadas en tensin y corriente.
I-2 Funcionamiento Totalmente automticos, las fuentes / cargadores ACP estn regulados en tensin y disponen de limitacin de intensidad al calibre nominal. La funcin de precalentamiento se activa por bornes exteriores.
I-3 Caractersticas
Tensin de entrada nominal: 230Vac - 50Hz / 60Hz Amplio margen de tensin: 187Vac - 305Vac
Salida : 13,2Vdc ; 2,5A Entorno :
- Temperatura de uso: - 20 + 60 C - Temperatura de almacenamiento : - 20 + 70 C - Humedad relativa : 95% 20C ("todo clima")
Estabilidad regulacin : 1% en variaciones acumuladas - de la tensin de entrada - de la corriente de salida - de la temperatura ambiente
Residual de salida : < 1% cresta a cresta Resistencia dielctrica : - 2500V AC entre entrada y salida
- 2000V AC entre masa y entrada / salida - Transformador conforme a la norma EN 61 558-2-17
Directriz DBT n 73/23/CEE modificada por directri z n 93/68/CEE Directriz CEM n 89/336/CEE modificada por directr iz n 93/68/CEE Normas CEM : NF EN 55011 ; NF EN 61000-4-2 ; NF EN 61000-4-3 ; NF EN 61000-4-4
NF EN 61000-4-5 ; NF EN 61000-4-6. Caractersticas rel de precalentamiento : 250Vac - 50Hz / 60Hz - 8A / AC1 Consumo : 75VA : cargador solo ; 1560VA : cargador + precalentamiento FS : fusible red interna tipo 5 x 20 calibre 1A - T F2 : fusible salida interna tipo 5 x 20 calibre 5A - T Peso : 0,5 kg Rendimiento : 0,8 C INV : haz de fuente cargador / precalentamiento C100 : conectador de salida de precalentamiento C 28 : 6.3 mm conectador de alarma C 27 : conectador de salida batera et telemando
precalentamiento
36013-6006915-ind D-notice ACP3 12-
2,5mD esp
Manual de uso
Indice / Revision D 16/04/08 36013-6006915 3 Type
Fichier / File Notice N Page
II GUA DE DIAGNSTICO
Constatacin Causa probable Solucin
La led verde "ON" apagada, No hay tensin en salida
Red 230Vac ausente Disyuntor o fusible anterior abierto Fusible FS (interno) defectuoso
Verificar la red y el estado de las protecciones. Verificar el fusible interno FS (1A-T)
Tensin de salida anormalmente baja, cargador en funcionamiento
Batera que sufre una descarga completa, el cargador est en limitacin de intensidad
Control de la tensin del cargador con batera desconectada 13,2Vdc
Esperar la descarga de la batera (la tensin debe subir progresivamente)
Verificar el estado de la batera
La batera esta descargada - Red presente - Cargador en
funcionamiento Fusible F2 defectuoso
Verificar la conexin de la batera (polaridad + / - )
Sustituir el fusible F2 (5A-T) Si el defecto persista, sustituir
el cargador.
El mando "precalentamiento" no funciona (la led amarilla "PRE" no se enciende)
Conectador C27 mal conectado
Verificar el potencial de la borna central del conectador C27 : Se debe tener +12Vdc con relacin al menos.
Alarma apagada
Fusible FS defectuoso
Fusible F2 defectuoso
El cargador toca la limitacin de voltaje
Voltaje mnima detectado
Defecto de carga
La entrada del cargador esta en corte circuito, sustituir el cargador.
Verificar la conexin de la batera (polaridad + / - ) Sustituir el fusible F2 (5A-T). Si el defecto persista, sustituir el cargador.
Desconectar la red pues la batera, esperar algunas secundas, reconectar la red y la batera. Si el defecto persista, sustituir el cargador.
Hay una sobrecarga sobre la salida o la batera. Desconectar la salida y la batera, si el defecto persista sin carga, sustituir el cargador.
El cargador es defectuoso, sustituir el cargador