    Indice / Revision D 16/04/08 36013-6006913 1 Type

    Fichier / File Notice N Page

    ALIMENTATION / CHARGEUR / PRECHAUFFAGE

    AACCPP33 1122--22,,55 mmDD 3311661133550055440022

    SOMMAIRE

    I - DESCRIPTION

    I-1 Application

    I-2 Fonctionnement

    I-3 Caractristiques

    II - GUIDE DE DIAGNOSTIC

  • 36013-6006913-ind D-notice ACP3 12-

    2,5mD fr

    Notice d'utilisation

    Indice / Revision D 16/04/08 36013-6006913 2 Type

    Fichier / File Notice N Page

    I DESCRIPTION

    I-1 Application Charge de batteries d'accumulateurs de types Pb ouvert et alimentation de circuits auxiliaires ainsi que fonction de prchauffage.

    Les alimentations / chargeurs srie ACP sont prrgles en tension et courant.

    I-2 Fonctionnement Entirement automatiques, les alimentations / chargeurs ACP sont rgules en tension et possdent une limitation d'intensit au calibre nominal. La fonction de prchauffage s'active par bornes extrieures.

    I-3 Caractristiques

    Tension d'entre nominale : 230Vac - 50Hz / 60Hz Plage de tension : 187Vac - 305Vac

    Sortie : 13,2Vdc ; 2,5A Environnement :

    - Temprature d'utilisation : - 20 + 60 C - Temprature de stockage : - 20 + 70 C - Humidit relative : 95% 20C ("tous climats")

    Stabilit rgulation : 1% en variations cumules - de la tension d'entre - du courant de sortie - de la temprature ambiante

    Rsiduelle de sortie : < 1% crte crte Tenue dilectrique : - 2500Vac entre entre et sortie

    - 2000Vac entre masse et entre / sortie - Transformateur conforme la norme EN 61 558-2-17

    Directive DBT n 73/23/CEE modifie par directive n 93/68/CEE Directive CEM n 89/336/CEE modifie par directive n 93/68/CEE Normes CEM : NF EN 55011 ; NF EN 61000-4-2 ; NF EN 61000-4-3 ; NF EN 61000-4-4

    NF EN 61000-4-5 ; NF EN 61000-4-6. Caractristiques circuit de prchauffage : 250Vac - 50Hz / 60Hz - 8A / AC1 max. Consommation : 75VA : chargeur seul ; 1560VA : chargeur + prchauffage FS : fusible secteur interne type 5 x 20 calibre 1A - T F2 : fusible sortie interne type 5 x 20 calibre 5A - T Poids : 0,5 kg Rendement : 0,8 C INV : faisceau d'alimentation chargeur / prchauffage C100 : connecteur de sortie prchauffage C28 : cosse faston 6,3 mm de report dalarme C 27 : connecteur de sortie batterie et tlcommande

    prchauffage

  • 36013-6006913-ind D-notice ACP3 12-

    2,5mD fr

    Notice d'utilisation

    Indice / Revision D 16/04/08 36013-6006913 3 Type

    Fichier / File Notice N Page

    II GUIDE DE DIAGNOSTIC

    Constat Cause probable Remde

    La led verte "ON" teinte, pas de tension en sortie

    Secteur 230Vac absent Disjoncteur ou fusible amont ouvert Fusible FS (interne) dfectueux

    Vrifier le secteur et ltat des protections. Vrifier le fusible interne FS (1A-T)

    Tension de sortie anormalement basse, chargeur en fonctionnement

    Batterie ayant subie une dcharge complte, le chargeur est en limitation dintensit

    Contrle de la tension du chargeur avec batterie dconnecte 13,2Vdc

    Attendre la recharge de la batterie (la tension doit remonter progressivement)

    Vrifier ltat de la batterie

    La batterie est dcharge - Secteur prsent - Chargeur en

    fonctionnement Fusible F2 dfectueux

    Vrifier le raccordement de la batterie (polarits + / -)

    Remplacer le fusible F2 (5A-T) Si le dfaut persiste, remplacer

    le chargeur.

    La commande "prchauffage" ne fonctionne pas (la led jaune "PRE" ne s'allume pas)

    Connecteur C27 mal connect Vrifier le potentiel de borne

    centrale du connecteur C27 : on doit avoir +12Vdc par rapport au moins.

    Le signal dfaut est actif

    Le fusible FS est HS

    Le fusible F2 est HS

    Le chargeur a provoqu une surtension

    Le chargeur est en sous-tension

    Dfaut de charge

    Lentre du chargeur est en court-circuit, remplacer le chargeur

    Vrifier le raccordement de la batterie (polarits + / -). Remplacer le fusible F2 (5A-T). Si le dfaut persiste, remplacer le chargeur.

    Dconnecter le secteur puis la batterie, reconnecter le secteur puis la batterie, si le dfaut persiste remplacer le chargeur

    La batterie et/ou lutilisation provoque une surcharge. Dbrancher lutilisation et la batterie, si le dfaut persiste vide, remplacer le chargeur.

    Le chargeur est dfectueux, remplacer le chargeur

  • 36013-6006914-ind D-notice ACP3 12-

    2,5mD ang

    User's Manual

    Indice / Revision D 16/04/08 36013-6006914 1 Type

    Fichier / File Notice N Page

    POWER SUPPLY / CHARGER / PRE-HEATING

    AACCPP33 1122--22,,55 mmDD 3311661133550055440022

    TABLE OF CONTENTS

    I - DESCRIPTION

    I-1 Application

    I-2 Operation

    I-3 Specifications

    II TROUBLE SHOOTING GUIDE

  • 36013-6006914-ind D-notice ACP3 12-

    2,5mD ang

    User's Manual

    Indice / Revision D 16/04/08 36013-6006914 2 Type

    Fichier / File Notice N Page

    I DESCRIPTION

    I-1 Application Designed to charge vented lead-acid batteries and to power auxiliary circuits with a pre-heating function.

    Power supply / chargers ACP series have voltage and current preset.

    I-2 Operation Entirely automatic, the ACP power supply / chargers are voltage regulated and have a current limitation at nominal rating. The pre-heat function is activated by external terminals.

    I-3 Specifications

    Nominal input voltage : 230Vac - 50Hz / 60Hz Voltage range: 187Vac - 305Vac

    Output : 13,2Vdc ; 2,5A Environment :

    - Operating temperature : - 20 to + 60 C - Storage temperature : - 20 to + 70 C - Relative humidity : 95% at 20C ("all climates")

    Control stability : 1% with cumulated variations of - Input voltage - Output current - Operating temperature

    Output ripple voltage : < 1% peak to peak Dielectric strength : - 2500V ac between input and output

    - 2000V ac between ground and input / output - Transformer in compliance with standard EN 61 558-2-17

    DBT Directive No. 73/23/CEE modified by Directive No. 93/68/CEE EMC Directive No. 89/336/CEE modified by Directive No. 93/68/CEE EMC standards : NF EN 55011 ; NF EN 61000-4-2 ; NF EN 61000-4-3 ; NF EN 61000-4-4

    NF EN 61000-4-5 ; NF EN 61000-4-6. Pre-heat relay characteristics : 250Vac - 50Hz / 60Hz - 8A / AC1 Consumption : 75VA : charger only ; 1560VA : charger + pre-heating FS : internal main fuse model 5 x 20 ; 1A - T F2 : internal output fuse model 5 x 20 ; 5A - T Weight : 0,5 kg Efficiency : 0,8 C INV : charger / pre-heating main cable C100 : pre-heating output terminal C28 : 6.3 mm terminal for alarm output C 27 : output terminal and pre-heating controls

  • 36013-6006914-ind D-notice ACP3 12-

    2,5mD ang

    User's Manual

    Indice / Revision D 16/04/08 36013-6006914 3 Type

    Fichier / File Notice N Page

    II TROUBLE SHOOTING GUIDE

    Report Probable cause Corrective action

    Green LED "ON" off, no output voltage

    Main 230Vac absent Upstream circuit breaker or fuse

    open FS fuse (internal) blown

    Check mains and protections status. Check internal fuse FS (1A-T)

    Abnormal low output voltage, charger in operation

    Battery went to a complete discharge, the charger is in current limit

    Check charger voltage disconnecting the battery

    13,2Vdc Wait the recharge of battery

    (the voltage should rise gradually)

    Check the battery status

    The battery is discharged - With mains on - Charger in

    operation F2 fuse blown

    check the battery connections (polarities +/-)

    Replace F2 fuse (5A-T) If the fault persists, replace the

    charger.

    The "pre-heating" control does not work (yellow LED "PRE" does not light on)

    C27 connector misconnected

    Check voltage on central terminal of C27 connector : You should see +12Vdc between this terminal and negative polarity.

    Alarm signal is active

    Fuse FS is blown

    Fuse F2 is blown

    Charger ran over voltage

    Under voltage limit hit

    Charging fault

    Charger input is shorted, please replace the charger

    Check the battery connections (polarities +/-). Replace F2 fuse (5A-T). If the fault persists, replace the charger.

    Disconnect Mains and then the battery, wait few seconds, reconnect Mains and the battery. If the fault persists, replace the charger.

    Output or battery circuit overloaded. Disconnect both, if the fault persists at no load, replace the charger.

    Charger is defective, replace the charger.

  • 36013-6006915-ind D-notice ACP3 12-

    2,5mD esp

    Manual de uso

    Indice / Revision D 16/04/08 36013-6006915 1 Type

    Fichier / File Notice N Page

    ALIMENTACIN / CARGADOR / PRECALENTAMIENTO

    AACCPP33 1122--22,,55 mmDD 3311661133550055440022

    NDICE

    I - DESCRIPCIN

    I-1 Aplicacin

    I-2 Funcionamiento

    I-3 Caractersticas

    II - GUA DE DIAGNSTICO

  • 36013-6006915-ind D-notice ACP3 12-

    2,5mD esp

    Manual de uso

    Indice / Revision D 16/04/08 36013-6006915 2 Type

    Fichier / File Notice N Page

    I DESCRIPCIN

    I-1 Aplicacin Carga de bateras de acumuladores de tipo Plomo abierta y alimentacin de circuitos auxiliares as que una funcin de precalentamiento.

    Las fuentes / cargadores serie ACP estn preajustadas en tensin y corriente.

    I-2 Funcionamiento Totalmente automticos, las fuentes / cargadores ACP estn regulados en tensin y disponen de limitacin de intensidad al calibre nominal. La funcin de precalentamiento se activa por bornes exteriores.

    I-3 Caractersticas

    Tensin de entrada nominal: 230Vac - 50Hz / 60Hz Amplio margen de tensin: 187Vac - 305Vac

    Salida : 13,2Vdc ; 2,5A Entorno :

    - Temperatura de uso: - 20 + 60 C - Temperatura de almacenamiento : - 20 + 70 C - Humedad relativa : 95% 20C ("todo clima")

    Estabilidad regulacin : 1% en variaciones acumuladas - de la tensin de entrada - de la corriente de salida - de la temperatura ambiente

    Residual de salida : < 1% cresta a cresta Resistencia dielctrica : - 2500V AC entre entrada y salida

    - 2000V AC entre masa y entrada / salida - Transformador conforme a la norma EN 61 558-2-17

    Directriz DBT n 73/23/CEE modificada por directri z n 93/68/CEE Directriz CEM n 89/336/CEE modificada por directr iz n 93/68/CEE Normas CEM : NF EN 55011 ; NF EN 61000-4-2 ; NF EN 61000-4-3 ; NF EN 61000-4-4

    NF EN 61000-4-5 ; NF EN 61000-4-6. Caractersticas rel de precalentamiento : 250Vac - 50Hz / 60Hz - 8A / AC1 Consumo : 75VA : cargador solo ; 1560VA : cargador + precalentamiento FS : fusible red interna tipo 5 x 20 calibre 1A - T F2 : fusible salida interna tipo 5 x 20 calibre 5A - T Peso : 0,5 kg Rendimiento : 0,8 C INV : haz de fuente cargador / precalentamiento C100 : conectador de salida de precalentamiento C 28 : 6.3 mm conectador de alarma C 27 : conectador de salida batera et telemando

    precalentamiento

  • 36013-6006915-ind D-notice ACP3 12-

    2,5mD esp

    Manual de uso

    Indice / Revision D 16/04/08 36013-6006915 3 Type

    Fichier / File Notice N Page

    II GUA DE DIAGNSTICO

    Constatacin Causa probable Solucin

    La led verde "ON" apagada, No hay tensin en salida

    Red 230Vac ausente Disyuntor o fusible anterior abierto Fusible FS (interno) defectuoso

    Verificar la red y el estado de las protecciones. Verificar el fusible interno FS (1A-T)

    Tensin de salida anormalmente baja, cargador en funcionamiento

    Batera que sufre una descarga completa, el cargador est en limitacin de intensidad

    Control de la tensin del cargador con batera desconectada 13,2Vdc

    Esperar la descarga de la batera (la tensin debe subir progresivamente)

    Verificar el estado de la batera

    La batera esta descargada - Red presente - Cargador en

    funcionamiento Fusible F2 defectuoso

    Verificar la conexin de la batera (polaridad + / - )

    Sustituir el fusible F2 (5A-T) Si el defecto persista, sustituir

    el cargador.

    El mando "precalentamiento" no funciona (la led amarilla "PRE" no se enciende)

    Conectador C27 mal conectado

    Verificar el potencial de la borna central del conectador C27 : Se debe tener +12Vdc con relacin al menos.

    Alarma apagada

    Fusible FS defectuoso

    Fusible F2 defectuoso

    El cargador toca la limitacin de voltaje

    Voltaje mnima detectado

    Defecto de carga

    La entrada del cargador esta en corte circuito, sustituir el cargador.

    Verificar la conexin de la batera (polaridad + / - ) Sustituir el fusible F2 (5A-T). Si el defecto persista, sustituir el cargador.

    Desconectar la red pues la batera, esperar algunas secundas, reconectar la red y la batera. Si el defecto persista, sustituir el cargador.

    Hay una sobrecarga sobre la salida o la batera. Desconectar la salida y la batera, si el defecto persista sin carga, sustituir el cargador.

    El cargador es defectuoso, sustituir el cargador