+ All Categories
Home > Documents > ACTIVE FILTER - Alpes Technologies

ACTIVE FILTER - Alpes Technologies

Date post: 28-Feb-2022
Category:
Upload: others
View: 8 times
Download: 0 times
Share this document with a friend
4
ACTIVE FILTER HARMONICS MITIGATION, COMPENSATION, LOAD BALANCING
Transcript

ACTIVE FILTERHARMONICS MITIGATION,COMPENSATION,LOAD BALANCING

I1150A100A50A

-50A-100A

-150A

0A

I4150A100A50A

-50A-100A

-150A

0A

I330A20A10A

-10A-20A

-30A

0A

Clean current waveform

Active filter response:harmonic components

Current waveform distoredby the loads

Non-linear loads

With Alpes Technologies you can be assured

of professional, rigorous solutions.

To have a positive impact on the environment by contributing to energy efficiency is one our company's driving forces. Through our diversified offer, we are committed to supporting you in your endeavours to improve power quality.

Our products (capacitor banks and harmonic filters) will help you improve the quality of your electricity supply. Our services (audit and maintenance) will help you improve production by limiting the detrimental factors.

The active filter continuously generates a compensating current for the harmonic mitigation. This eliminates harmonic distortions and re-establishes a linear current waveform. With a response time of less than 300μs, the active filter

improves the quality of the mains electricity supply in real time and thus limits potential damage in the production chain. An active filter significantly reduces current harmonics. It also rectifies and compensates the reactive power.

• Banks and data centers• Logistics platforms, warehouses• Theme parks • Road tunnels

• Supermarkets • Steel industry • Gas and oil exploration • Wastewater treatment

• Reduced wear, and consequently longer service life, due to its capacity to limit temperature rises and vibrations

• Optimum maintenance thanks to ease of servicing

• Fulfillment of contractual obligations with energy suppliers in terms of consumption

• Interference-free, rectified power supply

When connected in parallel on the mains supply, an active filter offers several advantages:

Applications

Active filter

This latest generation of active filters available from Alpes Technologies, as a result of the partnership with Schaffner Group, allows you to limit harmonics and so reduce maintenance costs and machine downtime.

The range of products

FN 3420 3-wire 30-480-3 50-480-3 ___ 100-480-3 120-480-3 200-480-3 250-2480-3 300-480-3

FN 3430 4-wire 30-400-4 ___ 60-400-4 100-400-4 120-400-4 200-400-4 250-400-4 300-400-4

Ratedcomp. current

3-wire 30A 50A ___ 100A 120A 200A 250A 300A

4-wire 30/90A ___ 60/180A 100/300A 120/360A 200/600A 250/750A 300/750A

Switching frequency 16kHz

Overload capability(1) 75A for 10ms 125A for 10ms 150A for 10ms 250A for 10ms 250A for 10ms 500A for 10ms 625A for 10ms 750A for 10ms

Cooling type Forced circulation air cooling Liquid cooling (closed circuit)

Ambient temperature 40°C(3) 30°C(2,3) 40°C(3) 30°C(3) 40°C(3)

Parallel operation Up to 5 units

Interfaces Modbus RTU (RS485), Modbus TCP/IP (Ethernet)

Power loss3-wire < 900W < 1300W ___ < 2200W < 2500W < 5000W < 6000W < 7500W

4-wire < 950W ___ < 1800W < 3000W < 3000W < 5500W < 6300W < 8500W

Air cooling requirements, speed-controlled fan

3-wire < 350m3/h < 550m3/h ___ < 1400m3/h < 1400m3/h < 2600m3/h < 3100m3/h < 3400m3/h

4-wire < 400m3/h ___ < 600m3/h < 1700m3/h < 1700m3/h < 2800m3/h < 3300m3/h < 3600m3/h

Noise level(1m)

3-wire 65dBA 65dBA ___ 68dBA 68dBA 70dBA 70dBA 70dBA

4-wire 63dBA ___ 63dBA 69dBA 69dBA 70dBA 70dBA 70dBA

Filter attenuation characteristics Up to 50 degrees (odd harmonics up to 49)

Altitude 1000m/derating up to 4000m, 1%/100m

Mains voltage(4)3-wire 380V (AC) ± 15% ... 480V (AC) ± 10% 50Hz: 380V (AC) ± 15% ... 415V (AC) ± 15

60Hz: 480V (AC) ± 10%

4-wire 380V (AC) ± 15% ... 415V (AC) ± 10% 50Hz: 380V (AC) ± 15% ... 415V (AC) ± 10%

Mains frequency 47 to 63Hz 50Hz or 60Hz ± 5%

Response time 300μs

Command topology Digital with FFT analysis

Current limitation Nominal current

Current transformer 100:5 to 50,000:5

Dimensions(l x h x d) (mm)

3-wire 360x590x290 360x590x290 ___ 468x970x412 468x970x412800x2000x600

Height plus socket (200mm standard)Depth including heat exchanger 760mm4-wire 415x840x300 ___ 415x840x300 468x1460x412 468x1460x412

Weight3-wire 47kg 47kg ___ 105kg 105kg 415kg 415kg 415kg

4-wire 70kg ___ 70kg 145kg 145kg 495kg 495kg 495kg

Protection class IP20 IP54

Approval CE, UL(5) CE, UL(5) (pending)

(1) Peak value (4) Other voltages available on request(2) Derating up to 40°C, 1.2%/K (5) UL for 3-wire versions only(3) Derating up to 55°C, 2%/K

Head officeP.A.E. Les Glaisins7, rue des BouvièresBP 33274943 Annecy-Le-VieuxCEDEX FRANCETel: (+33) 4 50 64 05 13 Fax: (+33) 4 50 64 04 37