Date post: | 26-Jul-2018 |
Category: |
Documents |
Upload: | vuongnguyet |
View: | 257 times |
Download: | 2 times |
EN
EMH meteringGmbH & Co. KG
Neu-Galliner Weg 119258 GallinGERMANYTel. +49 38851 326-0Fax +49 38851 326-1129
E-mail [email protected] www.emh-metering.com
EN
EMH metering GmbH & Co. KG • Neu-Galliner Weg 1 • 19258 Gallin • GERMANY • Tel. +49 38851 326-0 • [email protected] • www.emh-metering.com
Edition: 07.05.2012LZQJXC-DAB-E-3.10
Designacc.toVDEW-Specifications2.1
Plugablecommunicationmodule
Exchangeablebufferbattery
Networkanalysis
OptionalwithDLMS
LZQJ-XCAdditional features of the LZQJ-XC:
Measuringofinstantaneous P,Q,S(perphaseandsum),U,I,powerfactor,linefrequency, valuesphasefailuresInstallationcheck viainstantaneousvalues(servicedata)possibleOpticalfibreinterface forconnectionofupto4opticalfibreseparationboxesBufferbattery exchangeablebufferbatteryforreadingoutthemeterviatheopticalinterface andreadingthedisplaywithoutpowerTamperdetection openingofmeterandterminalcoverandmagneticfieldsNetworkanalysis monitoringofU,I,THD,f,flicker,harmonicsacc.toDINEN50160
The LZQJ-XC fulfils the following standards:
DIN43857-2 Watthourmetersinmouldedinsulationcasewithoutinstrumenttransformers, upto60Aratedmaximumcurrent;principaldimensionsforpoly-phasemetersEN50470-1 Electricitymeteringequipment(a.c.)-Part1:Generalrequirements, estsandtestconditions-Meteringequipment(classindexesA,BandC)EN50470-3 Electricitymeteringequipment(a.c.)-Part3:Particularrequirements- Staticmetersforactiveenergy(classindexesA,BandC)IEC61000-... Electromagneticcompatibility(EMC)IEC60529 Degreesofprotectionprovidedbyenclosures(IPcode)IEC61038 TimeswitchesfortariffandloadcontrolIEC62052-11 Electricitymeteringequipment(AC)-Generalrequirements, testsandtestconditions-Part11:MeteringequipmentIEC62053-21 Electricitymeteringequipment(a.c.)-ParticularRequirements -Part21:Staticmetersforactiveenergy(classes1and2)IEC62053-22 Electricitymeteringequipment(a.c.)-Particularrequirements -Part22:Staticmetersforactiveenergy(classes0,2Sand0,5S)IEC62053-23 Electricitymeteringequipment(a.c.)-Particularrequirements -Part23:Staticmetersforreactiveenergy(classes2and3)IEC62056-21 Electricitymetering-Dataexchangeformeterreading,tariffandloadcontrol -Part21:DirectlocaldataexchangeIEC62056-46 Electricitymetering-Dataexchangeformeterreading,tariffandloadcontrol -Part46:DatalinklayerusingHDLCprotocolIEC62056-53 Electricitymetering-Dataexchangeformeterreading,tariffandloadcontrol -Part53:COSEMapplicationlayerIEC62056-61 Electricitymetering-Dataexchangeformeterreading,tariffandloadcontrol -Part61:Objectidentificationsystem(OBIS)IEC62056-62 Electricitymetering-Dataexchangeformeterreading,tariffandloadcontrol -Part62:InterfaceclassesDIN66348-1 Interfacesandbasicdatalinkcontrolproceduresforserialmeasurement datacommunication;start-stop-transmission,point-to-pointconnectionITU-TV.11 Electricalcharacteristicsforbalanceddouble-currentinterchangecircuits operatingatdatasignallingratesupto10Mbit/sTIA/EIA-485 Electricalcharacteristicsofgenerators&receiversforuseinbalanceddigital multipointsystemsITU-TV.24 Listofdefinitionsforinterchangecircuitsbetweendataterminalequipment(DTE) anddatacircuit-terminatingequipment(DCE)ITU-TV.28 Electricalcharacteristicsforunbalanceddouble-currentinterchangecircuits
Direct connection version5(60) A, 10(60) A, 5(100) A, 10(100) A
Transformer connection versionCl. B (Cl. 1)
Precision MeterCl. C (Cl. 0,5 S)
Precision MeterCl. 0,2 S
Voltage 4-wiremeter
3-wiremeter
2-wiremeter(for16,7Hz)
3x127/220V...3x240/415V
---
---
3x58/100V...3x240/415V(optional3x57,7/100...3x277/480V)
orupto3x400/690V3x100V...3x415Vorupto3x690V100V...240V
3x58/100V...3x240/415V(optional3x57,7/100...3x277/480V)
orupto3x400/690V3x100V...3x415Vorupto3x690V100V...240V
Current 5(60)A,10(60)A,5(100)A,10(100)A 5||1A,1(6)A,1(10)A,5A,1A,5(20)A 5||1A,1(6)A,1(10)A,5A,1A,5(20)AFrequency 50Hz,60Hz 50Hz,60Hz,16,7Hz 50Hz,60Hz,16,7HzAccuracy activeenergy
reactiveenergyCl.A(Cl.2),optionalCl.B(Cl.1)
Cl.3,optionalCl.2Cl.B(Cl.1)
Cl.2Cl.C(Cl.0,5S)1%(Cl.2)
Cl.0,2S0,5%(Cl.2)
Measuring system designation compensatedcurrenttransformer compensatedcurrenttransformerMeasuring types activeenergy
reactiveenergyothers
+A,-A+R,-R,R1,R2,R3,R4
S,Ah,U2h,I2h
+A,-A+R,-R,R1,R2,R3,R4
S,Ah,U2h,I2hMeter constants LED(Imp./kWh[kvarh])
output(Imp./kWh[kvarh])
configurationability
500...100010000...100000(dependingonmetertype)(dependingonmetertype)
250...5005000...50000(dependingonmetertype)(dependingonmetertype)aftercertificationbymeansofthecertificationrelevantlogbook
10000...100000(dependingonmetertype)5000...50000(dependingonmetertype)
aftercertificationbymeansofthecertificationrelevantlogbook
Energy registers maximumnumber 32tariffregisters+16tarifflessregisters,eachwith15historicalvalues 32tariffregisters+16tarifflessregisters,eachwith15historicalvaluesMaximum registers maximumnumber
measuringperiod32tariffregisters,eachwith15historicalvalues
1,5,10,15,30,60min,adjustable32tariffregisters,eachwith15historicalvalues
1,5,10,15,30,60min,adjustableLoad profile maximumnumberofchannels
typicalmemorydepthat1channelregisteringperiodregisteringtype
32upto3yearswitharegisteringperiodlengthof15min
1,5,10,15,30,60min,adjustablepower,energy,energyfeed
32upto3yearswitharegisteringperiodlengthof15min
1,5,10,15,30,60min,adjustablepower,energy,energyfeed
Real Time Clock accuracysynchronisationrunningreservebattery/capacitor
within±5ppmviadatainterfaces,controlinputorDCF-module
>20years/approx.6days(150hours)
within±5ppmviadatainterfaces,controlinputorDCF-module
>20years/approx.6days(150hours)Ripple control receiver
numberofchannelstelegrams
6allcommontelegrams
6allcommontelegrams
Control inputs S0-input/systemvoltage max.1/max.5(intotalmax.5inputspossible)
max.2/max.9(intotalmax.10inputspossible)
max.2/max.9(intotalmax.10inputspossible)
Data retention time withoutvoltageintheEEPROM,atleast10years withoutvoltageintheEEPROM,atleast10yearsDisplay displayversion
heightofdigitsalternativedisplay
readingwithoutpowersupply
VDEW-display,84mmx24mm8mm
alphanumericaldisplay4x20characters;70,4mmx20,8mm;heightofdigits4mm
bybufferbattery(optional)
VDEW-display,84mmx24mm8mm
alphanumericaldisplay4x20characters;70,4mmx20,8mm;heightofdigits4mm
bybufferbattery(optional)Operation mechanicalbuttons
opticalsensorforoperationofdisplayandreset(sealableunderhingedmodulecover)
foroperationofdisplayforoperationofdisplayandreset(sealableunderhingedmodulecover)
foroperationofdisplayData interfaces opticaldatainterface
electricaldatainterfacedataprotocolsmaximumtransmissionrate
opticaldatainterfaceD0RS485,RS232orCL0IEC62056-21orDLMS
upto19200baud(fixedorModeC/E)
opticaldatainterfaceD0RS485,RS232orCL0IEC62056-21orDLMS
upto19200baud(fixedorModeC/E)Communication module (plugable)
modeminterfacemoduledataprotocolsmaximumtransmissionrate
GSM/GPRS,Ethernet,PSTN(analog)RS485,RS232
IEC62056-21orDLMSupto19200baud(fixedorModeC/E)
GSM/GPRS,Ethernet,PSTN(analog)RS485,RS232
IEC62056-21orDLMSupto19200baud(fixedorModeC/E)
Outputs maximumnumberOpto-MOSFETS0-outputrelayshighloadrelay
8max.250VAC/DC,100mA(makecontact[NO]orbreakcontact[NC])
max.27VDC,27mAmax.250VAC/DC,100mA(max.2makecontacts[NO])max.250VAC/DC,10A(max.2makecontacts[NO])
8max.250VAC/DC,100mA(makecontact[NO]orbreakcontact[NC])
max.27VDC,27mAmax.250VAC/DC,100mA(max.2makecontacts[NO])max.250VAC/DC,10A(max.2makecontacts[NO])
Energy supply switched-modepowersupplymainsbufferingtime
3-phase>500ms
3-phase>500ms
Auxiliary voltage supply long-range --- 48...300VAC/DC(optional) 48...300VAC/DC(optional) 48...300VAC/DCPower consumption per phase (Basic meter)
voltagepathwithauxiliaryvoltagewithoutauxiliaryvoltagecurrentpathauxiliaryvoltage
---<1,2VA/<0,75W
<0,01VA---
<0,02VA/<0,01W(3x58/100V)<1,2VA/<0,75W
<0,004VA<4,2VA...<2,5VA
<0,02VA/<0,01W(3x58/100V)<1,2VA/<0,75W
<0,004VA<4,2VA...<2,5VA
EMC-characteristics isolationresistancesurgevoltage
resistanceagainstHF-fields
4kVAC,50Hz,1min8kV,impulse1,2/50µs,2Ω(measuringpaths,auxiliaryvoltage)
6kV,impulse1,2/50µs,500Ω(outputs:Opto-MOSFET,relays;inputs:systemvoltage)
10V/m(underload)
4kVAC,50Hz,1min8kV,impulse1,2/50µs,2Ω(measuringpaths,auxiliaryvoltage)
6kV,impulse1,2/50µs,500Ω(outputs:Opto-MOSFET,relays;inputs:systemvoltage)
10V/m(underload)Temperature range specifiedoperatingrange
limitrangeforoperation,storageandtransport
-25°C...+55°C
-40°C...+70°C
-25°C...+55°C
-40°C...+70°CRelative humidity max.95%,non-condensingacc.toIEC62052-11,EN50470-1and
IEC60068-2-30max.95%,non-condensingacc.toIEC62052-11,EN50470-1and
IEC60068-2-30Housing dimensions
classofprotectiondegreeofprotection:housingdegreeofprotection:terminalblockhousingmaterialfirecharacteristics
approx.180x285x80(WxHxD)mm,acc.toDIN43857II
IP51(optionalIP54)IP31
polycarbonateglass-fibrereinforced,withouthalogen,recyclableacc.toIEC62052-11
approx.180x285x80(WxHxD)mm,acc.toDIN43857II
IP51(optionalIP54)IP31
polycarbonateglass-fibrereinforced,withouthalogen,recyclableacc.toIEC62052-11
Environmental conditions
mechanicalelectromagneticintendedlocation
M1acc.toMeasuringInstrumentsDirective(2004/22/EC)E2acc.toMeasuringInstrumentsDirective(2004/22/EC)
indooracc.toEN50470-1
M1acc.toMeasuringInstrumentsDirective(2004/22/EC)E2acc.toMeasuringInstrumentsDirective(2004/22/EC)
indooracc.toEN50470-1Weight 1,4kg 1,2kg 1,2kg
Productspecificationsaresubjecttochangewithoutnotice!
Meters from the series LZQJ-XC are designed foruniversal applications according to VDEW-speci-fications 2.1. Due to the the application of a triedand tested measuring procedure the meter isdistinguishedby itshighreliability.Thehighperfor-mingprocessorsystemguaranteesasolidbasisforfurtherextensions.
TheLZQJ-XCfunctionscanbeextentedwiththefollowingaccessories:
MetermodemVARIOMOD-XC(GSM/GPRS,Ethernet,PSTN)
Interfacemodule(RS232,RS485)
DCF-AerialDCF77-TH2
OpticalfibreseparationboxLTR
Communicationandparameterisationsoftware
Networkanalysis(optional)