ADR244B Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 1 of 43 Introduction: ASHIDA has designed economical & reliable Multifunction ADR244B Protection & Control System. The simple and compact construction of ADITYA series ADR244B relay provides integrated Protection, Control and Monitoring functions integrated Protection, Control and Monitoring functions for Electric Motors. The ADR244B relay provides the options for three versions: basic, extended and modular versions. For hardware features of individual models refer the ordering information. Functional Overview: Key Protection & Control Functions: Four Independent Settings Groups. Non Directional Phase & Ground Over Current Function (50/51/51N/51). Four Independent Stages for Non Directional Phase Over Current Protection. Three Stages of Non Directional Ground Over Current Protection. Internally Derived (3I0>) / Externally measured Ground Over Current Protection. Inverse time Over Current Protection (IEC curves according to IEC60255). High Impedance Restricted Earth Fault Protection (64R). Inverse & Definite time Negative Phase Sequence Over Current Protection (46). Broken Conductor Protection (46BC) Negative Phase Sequence Over Voltage Protection (47). Under and Over Voltage Protections (27 /59).
Transcript
Page 1: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 1 of 43

Introduction:

ASHIDA has designed economical & reliable

Multifunction ADR244B Protection & Control

System. The simple and compact

construction of ADITYA series ADR244B

relay provides integrated Protection,

Control and Monitoring functions integrated

Protection, Control and Monitoring

functions for Electric Motors.

The ADR244B relay provides the options

for three versions: basic, extended and

modular versions. For hardware features of

individual models refer the ordering

information.

Functional Overview:

Key Protection & Control Functions:

• Four Independent Settings Groups.

• Non Directional Phase & Ground Over

Current Function (50/51/51N/51).

• Four Independent Stages for Non

Directional Phase Over Current

Protection.

• Three Stages of Non Directional

Ground Over Current Protection.

• Internally Derived (3I0>) / Externally

measured Ground Over Current

Protection.

• Inverse time Over Current Protection

(IEC curves according to IEC60255).

• High Impedance Restricted Earth

Fault Protection (64R).

• Inverse & Definite time Negative

Phase Sequence Over Current

Protection (46).

• Broken Conductor Protection (46BC)

• Negative Phase Sequence Over

Voltage Protection (47).

• Under and Over Voltage Protections

(27 /59).

Page 2: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 2 of 43

• Externally measured / Internally

calculated Residual Over Voltage

Protection (59N).

• Rate of change of Frequency (81R)

(Optional)

• Locked rotor / Motor stall Protection

(50LR)

• Prolong start Protection (66)

• Too many starts / Number starts

function

• Phase reversal Protection (47)

• Under current Protection (37)

• Under/Over Power Protection (32P)

• Reverse Power Protection (32R)

• Power factor Protection (55)

• Under and Over Frequency

Protection (81U/O)

• SOTF (Optional)

• Breaker Failure detection (50BF)

• Out of Step (68)

• VT and CT supervision function

• Trip circuit supervision function

• Programmable Inputs & Outputs

• CB Close / Trip from HMI

• Programmable & Target LEDs for

indication with dual colours

• Self Supervision of relay

• Metering function

• Disturbance Recording (10 nos.)

• Event Recording

• Fault Recording on HMI display

(10nos.)

• Non-Volatile memory

• Fully communicable with IEC standard

open protocol IEC60870-5-103,

MODBUS & IEC 61850.

• SCADA communication

• Single / Dual Ethernet ports (RJ45),

RS485/RS422 port

• PC front port communication for

convenient relay settings

• Conformal coating of PCB

• User friendly local operation with key

pad

• Large Liquid crystal display (20X4)

with backlight

• Password Protection

Software Support:

• Setting Editor.

• Programmable scheme logic Editor.

• Settings upload / download.

• Offline Settings Editor.

• Online Measurement.

• Disturbance analysis.

• Relay assistant for testing relay at site Applications:

ADR244B numerical multifunction relay

designed for electric motor protection

applications. Relay designed with fast

and selective tripping ensures the stability

and availability of electrical power system.

ADR244B relay apply for protection

of motor feeder to achieve sensitivity

and selectivity on phase & ground faults as

well as on abnormal conditions.

Page 3: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 3 of 43

Motor Protection Application

Motor Protection Application

ANSI Code

Description

27/59 Under/Over Voltage Protection 32 Directional Power Protection 37 Under current Protection 40 Loss of Excitation 46

Negative Phase Sequence Protection

46BC Broken Conductor Protection 47

Negative Phase Sequence Over Voltage Protection

48 Motor Prolong Start Protection 49 Thermal Overload Protection 50

Instantaneous/Definite Time Phase Over current Protection

50N

Instantaneous/Definite Time Ground Over current Protection

50BC Broken Conductor Protection 50BF Breaker Failure Detection

50LR Locked rotor Protection 51

Inverse Time Phase Over current Protection

51N

Inverse Time Ground Over current Protection

55 Power factor Protection 59N Residual Over Voltage Protection

62 Time Delay Stopping or Opening Relay

64R

High Impedance Restricted Earth Fault Protection

60/VTS VT Supervision Detection CTS CT Supervision Detection 66 Number of starts 68 Out of Step/Power Swing Blocking 74 Trip Circuit Supervision

81O/U Frequency Protection 81R Rate of change of frequency 86 Lockout (Trip command)

SOTF Switch On To Fault

The functional overview of ADR244B for Enhanced & Modular Version:

Protection functions Overview of Basic

Version

52

52

M

52

5252 52

M

M M

Page 4: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 4 of 43

Protection functions Overview of Enhanced

& Modular Version

The core functionality of ADR244B relay

is equipped with Motor protection &

Control functions.

Motor Prolong start Protection (48):

For an induction motor to stall during

normal operation (during motor starting

conditions), load torque may exceeds very

high and above the breakdown torque,

may cause damages of stator winding and

rotor bars. Stator draws heavy current

due to the heavy current flows in rotor

bars.

The ADR244B relay detects motor prolong

start conditions effectively and provides

protections to motor.

Number of Starts (66):

Induction motor can be start

frequently/periodically based on their rotor

bar thermal capacity design. ADR244B

provides number of start protection for

motor against too many / frequent starts

(cold or hot starts per hour) per hour. The

rotor temperature rise drastically high if

the motor starts frequently (beyond duty

cycle mentioned in motor datasheet). The

rotor temperature can be calculated from

stator current. The number of starts only

permits, if the rotor can have sufficient

thermal reserves for complete start up.

The cooling time between starts allowed to

restart motor, when the calculated rotor

temperature falls down to safe level.

ADR244B allows user to program number

of cold / hot starts per hour as per the

information available from motor

datasheet. Users can set the number of

starts protection (number of starts and

Page 5: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 5 of 43

time between starts) according to motor

start data available from motor datasheet.

Non Directional Over Current Protection (50/50N/51/51N/51V): The core functionality of ADR244B relay is

equipped with multi function Motor

protection. The relay provides Non

Directional phase and ground over current

protection with multiple settings (four

stages for phase over current and three

stages for ground over current) for various

power system applications and wide range

of protection settings. The function is

equipped with digital filter algorithms,

providing the rejection of higher harmonics

& DC offset. Selectable IEC/IEEE inverse

time curves with directional/non directional

over current protection will be providing

greater selectivity, flexibility and sensitivity

to users for better relay co-ordinations.

ADR244B relay provides inverse time over

current characteristic for phase and ground

over current elements. Each stages of

phase and ground over current elements

are independently settable with inverse

time or definite time characteristic. The

following tripping characteristics are

available;

• IEC Normal Inverse Curve (C1) for 3s

• IEC Normal Inverse Curve (C2) for 1.3s

• IEC Very Inverse Curve (C3)

• IEC Extremely Inverse Curve (C4)

• Long time Inverse Curve (C5)

• Definite time Over current (C6)

Curve Type

Description a B

C1 Standard Inverse_1

0.14 0.02

C2 Standard Inverse_2

0.06 0.02

C3 Very Inverse 13.5 1

C4 Extremely inverse

80 2

C5 Long Time Inverse

120 1

C6 Define Time - -

ADR244B relay provides three stages of

definite time/inverse time internally

derived zero sequence over current (3I0>)

protection to detects asymmetrical faults in

electrical network. It can apply to over

head transmission line, underground cable,

and feeder. The ground current (3I0>)

calculated from three line currents.

t = K* a

IIref

b

– 1

Page 6: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 6 of 43

Derived Zero sequence over current from three phases

ADR244B relay provides three stages of

externally ground over current protection.

ADR244B relay measures ground fault

current through neutral CT input.

Externally ground CT input can also apply

for high impedance restricted earth fault

protection or sensitive ground fault

protection through CBCT.

Externally measured ground over current

through neutral CT

Externally measured ground over current

through CBCT

Voltage controlled over current (51V)

protection can be apply for distributed

generator against phase faults. Protection

function can be selectable in over current

menu.

Negative Phase Sequence Protection (46): ADR244B provides sequence over current

against unbalance faults/condition or high

impedance faults over transmission

line/under ground cable or over load

condition. Sequence over current function

provided in two modes; Positive sequence

and Negative sequence over current

function. User can select the mode based

on their application and requirement.

The negative phase sequence over current

element can be programmed as IDMT or

definite time characteristic. ADR244B relay

provides five selectable IEC inverse curves

for each stage.

Protection can also apply in condition when

there is a very high resistive ground fault

and ground element may not sense the

fault current.

Page 7: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 7 of 43

Broken Conductor Protection

(46BC):

ADR244B equipped with Broken conductor

detection protection. Broken conductor

condition can be detected by ratio of

Negative sequence current to Positive

sequence current (I2/I1). Protection

provides higher sensitivity on High resistive

fault.

Broken Conductor Protection (50BC):

ADR244B provide independent I0/I1

function for sensitive ground fault

detection. Relay measure the ratio of zero

to positive sequence current precisely.

Thermal Overload Protection (49):

The thermal withstand capability of the

power system equipment is affected by

overheating prior to a fault. The

temperature should not exceed the thermal

withstands capability of power system

equipment. The RMS currents are

measured and analyzed to monitor the

thermal state

Under & Over Voltage Protections

(27/59):

ADR244B relay provides independent phase

over and under voltage protections with

definite time delay range. Relay also

provides the positive sequence over

voltage protection with definite time

characteristic option. Protection functions

can be programmed for alarm signal or trip

signal through programmable logic.

Under & Over voltage detection through

3-phase VT connection

Residual Over Voltage Protections

(59N):

ADR244B relay provides zero sequence /

residual over voltage protection with

definite time delay range. Protection can be

achieved by externally measured residual

voltage through open delta VT or the zero

sequence voltage internally calculated from

three phases.

Page 8: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 8 of 43

Zero sequence Over voltage / Externally measured residual Over Voltage detection through 3-phase VT &

Open delta VT connections

Negative Phase Sequence Over Voltage Protections (47): ADR244B relay provides positive/negative

sequence over voltage protections with

definite time delay range. It provides

protection against high resistive faults and

unbalance loading condition.

Figure16: Positive/Negative Phase Sequence Over voltage detection through 3-phase VT connection

Directional Power Protection (32)

available in Enhance/Modular

version:

The directional power protection designed

for protection against reverse power mode

and over / under load protection in forward

power mode. It can also be settable as a

active / reactive power mode. ADR244B

provides four elements for power

protection with independent definite time

delay characteristic.

Frequency Protection (81O/U) available in Enhance/Modular version: Frequency protection function provides

either under or over frequency protection

of line/feeder/machine. ADR244B relay

provides six independent stages with

definite time delay characteristic. Stages

can be settable in a under or over

frequency mode. Protection function can

also be use for load shedding scheme.

Rate of change of frequency - 81R (df/dt) available in Enhance/ Modular version: This Protection function is used for fast

disconnection of a generator or load

shedding control. Based on the calculation

of the frequency variation, it is insensitive

to transient voltage disturbances and

therefore more stable than a phase-shift

protection function.

Time-delay stopping or opening Relay (62): Time delay function in ADR244B can be

derived from software RTV2. Number of

timers, gates and flip-flops are available in

each module which can be assigned to any

of the contact output to achieve the

desired delay for stopping or opening

operation.

Page 9: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 9 of 43

Out of Step/Power Swing Blocking

(68):

Power swings or Out of step can be

classified as either stable or unstable.

Basically, ADR244B will not pick up on a

swing (either stable or unstable). When a

power swing is a consequence of stable

disturbance, unwanted line tripping can

aggravate disturbance and lead to

instability. Thus ADR244B gives a blocking

signal to the further tripping for certain

amount of time.

Breaker Failure detection (50BF):

If the fault current is not interrupted after

a time delay expired, circuit breaker

failures detected, and execute trip

command to upstream circuit breaker.

ADR244B relay incorporates circuit breaker

failure protection to detect failure of

tripping command execution due to

mechanical or electrical problems in circuit

breaker.

SOTF

The ADR244B provides SOTF function to

protection feeder against switch on to fault

condition during feeder/transformer

energization.

Trip circuit supervision (74):

Any two binary inputs for circuit breaker

poles can be used for monitoring the circuit

breaker trip coils including connecting

cables. Relay initiate alarm whenever the

circuit breaker control/DC circuitry gets

interrupted.

Relay monitor Trip coil healthiness through

CB NO during close condition and through

CB NC during Trip condition. If any

discontinuity observed it generate Alarm

signal.

VT supervision Function (60/VTS): ADR244B relay provides VT supervision

function to detecting a loss of phase

voltage input such as that caused by failure

of fuses (figure) or molded case/miniature

circuit breaker (MCB). Relay declares the

VT supervision when the below logic shall

be stratified.

1

62

B+

B-

TC

CB NO

CB NC

Fig.4 Trip Circuit Logic

1

62

To Relay CPU

To Relay CPU

TCCOM

T1

T2

1

62

B+

B-

TC

CB NO

CB NC

Fig.4 Trip Circuit Logic

1

62

To Relay CPU

To Relay CPU1

62

B+

B-

TC

CB NO

CB NC

Fig.4 Trip Circuit Logic

1

62

To Relay CPU

To Relay CPU

TCCOM

T1

T2

Page 10: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 10 of 43

CT supervision function(CTS):

ADR244B relay provides CT supervision

function to detecting a loss of phase

current due to the failure of ct secondary

wiring.

If the power system currents are healthy,

negligible negative & zero sequence

voltage could be derived. If, however, one

or more of the AC current inputs are

missing, a negative & zero sequence

currents would be derived, even if the

actual power system phase currents are

healthy. CTS works by using these criteria;

that is by detecting a ratio of derived

negative to positive sequence currents &

ratio of derived zero sequence to positive

sequence currents in the absence of a

corresponding derived negative & zero

sequence voltage from VT.

Programmable Inputs, Outputs & Logic: The Basic version of ADR244B relay

provides 11 nos. of programmable digital

outputs and 12 nos. of optically isolated

digital inputs. Two nos. of digital inputs

shall be configured for trip circuit

supervision monitoring and remaining 10

Page 11: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 11 of 43

nos. are the programmable digital inputs to

be configured for desired applications.

Back side terminals Basic Version (Plugin)

Back side terminals Basic Version (Non-

Drawout)

The enhance version of ADR244B provides

upto 16 nos. of digital output and 10 nos.

of digital inputs. (ref. ordering option)

Back side terminals Enhanced version

The modular version of ADR244B provides

62 nos. of programmable inputs and

outputs in modular cabinet. Modular

version shall be available in 19” or 14” rack

mount size.

Back side terminals Modular version (19”)

Back side terminals Modular version (14”)

Cabinet size depends on the ordering

information. Maximum standard 19” rack

mounted cabinet size available for this

model

Programmable LEDs and

Pushbuttons:

The Basic version of ADR244B relay

provides total 8 nos. of target &

programmable LEDs with dual colors

indication. The enhanced and modular

Page 12: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 12 of 43

version of ADR244B relay provides total 16

nos. of target and programmable LEDs with

dual colors indication. The LEDs can be

programmed either through HMI or

through PC software (RTV2 software).

The ADR244B also provides the

programmable pushbuttons for circuit

breaker close and open from HMI of relay.

Pushbuttons can be programmed through

HMI or through RTV2 software.

Event recording: ADR244B relay is providing feature to

record and store 512/1024 nos. Of events

in non-volatile memory through internally

by protection and control functions and

externally by triggering of digital inputs,

and can be extracted using communication

port or viewed on front of LCD display. The

event shall be trigger on time stamp

through time synchronization or internal

clock setting.

Disturbance recording:

ADR244B relay is provides built in

disturbance recording facility for recoding

of analogue and digital channels. Relay

records 10 nos. of disturbances and store

in to non-volatile memory. Disturbance

records can be saved in IEEE COMTRADE

format and same can be analyzed in

disturbance analysis software.

Fault recording:

ADR244B relay is providing fault record

facility. The fault records can be display

either on HMI display or in RTV2 software.

The relay can records 10 nos. of fault

records in non-volatile memory.

Metering:

Online metering feature of ADR244B relay

is providing metering of parameters (i.e

voltage/current magnitude, power, power

factor measurement etc.) on HMI display

or in RTV2 software.

Page 13: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 13 of 43

Relay Assistant:

RTV2 software provides relay assistant tool

for testing and commissioning of relay at

site/field area.

Independent Protection settings

groups:

ADR244B relay provides multiple

independent settings groups to allow

operate relay on different power system

operating conditions. Basic version

provides two independent settings groups.

The extended and modular versions

provides four independent settings groups.

IEC 60870-5-103 Protocol:

ADR244B relay provides internationally

standardized protocol for communication

via RS485 port of protection relays. IEC

60870-5-103 protocol used worldwide and

supported by relay manufacturers.

IEC 61850 Protocol:

ADR244B relay provides internationally

standardized protocol IEC61850 for

substation automation via Ethernet port of

protection relays.

Page 14: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 14 of 43

Typical Tests Information: The Relay Confirm to following standard Electromagnetic Compatibility Type Test: Sr. No. Standard Test

1. High Frequency Disturbance Test

IEC60255-22-1 : Frequency : 1MHz Damped Oscillatory : Longitudinal :2.5 KV Common Mode, 1 KV

Differential Mode : Duration: sec duration 2 sec. : On Mains Port.

2. Electrostatic Discharge Test- Direct Application

IEC60255-22-2 : IEC 61000-4-2 class III. : Contact discharge: 2, 4, 6 & 8kV, : Air discharge: 2, 4 8 & 15KV : Polarity: both +ve and –Ve polarities.

3. Fast Transient Disturbance Test

IEC60255-22-4 : Class A : 4KV; 5/50ns; 5KHz & 100KHz: Repetition rate

300ms; Both polarities; Ri = 50Ω; duration 1 min.

4.

Surge Immunity Test

IEC60255-22-5 : Differential Mode = 1kV : Common Mode = 2kV : 1.2/50µs, 8/20µs 5 surges of each polarity : On Mains Port and I/O Port

5. Power Frequency Immunity Test

IEC60255-22-7 : Class-A

6. Power Frequency Magnetic Field Immunity Test

IEC61000-4-8 : 1000A/m FOR 3s, 300A/m for 1minute.

7. Pulse Magnetic Field Immunity Test

IEC61000-4-9 : TEST LEVEL 5, TEST specifications = 1000A/m field applied in all planes

8. Radiated Electromagnetic Field Disturbance Test

IEC60255-22-3 : 10V/m, Performance Class-A : 10V/m, freq = 80MHz to 1GHz and 1.4GHz to

2.7GHz. 80% AM at 1kHz.

9. Conducted Disturbance Induced By Radio Frequency Field

IEC60255-22-6

: Freq. 150kHz – 80MHz, Amplitude 10 V, Modulation 80% AM @ 1 KHz.

10. Power Supply Immunity Test

IEC60255-11 & IEC61000-4-11

: DC voltage dip: 40% dip 200ms and 70% for 500ms for DC 10 & 20ms without loss of protection for DC 30ms, 50ms, 100ms, 200ms, 300ms, 0.5s, 1s and 5s with temporary loss of protection for DC

: AC voltage dip: 10, 20ms without loss of protection for AC 50ms, 100ms, 200ms, 0.5s, 5s with temporary loss

of protection

Page 15: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 15 of 43

11.

Conducted & Radiated frequency Emission Test

IEC60255-25 : Conducted 0.15MHz - 0.5MHz, 79dB (microV) Q-Peak, 66dB

(microV) for average 0.5MHz - 30MHz, 73dB (microV) Q-Peak, 60dB

(microV) for average : Radiated (3mtr) 30MHz - 230MHz, 50dB (microV) Q-Peak, 230MHz - 1GHz, 57dB (microV) Q-Peak,

Insulation Tests: 12. High Voltage

Test

IEC60255-27 : At 2kV 50Hz between all terminal connected together and earth for 1 minutes

13. Impulse Voltage Test

IEC60255-27 : Test voltage: 5KV (peak) 1.2 / 50us, : Energy :0.5 J, : Polarity : + ve and – Ve : Nos. of impulses : 3 positive and 3 negative impulse : Duration between Impulses : 5 sec.

14. Insulation Resistance

IEC60255-27 : ≥ 100MΩ @ 500V DC

Environmental tests: 15. Cold test : IEC-60068-2-1 16. Dry heat test : IEC-60068-2-2

17. Damp heat test, steady state : IEC-60068-2-78

18. Change of Temperature : IEC-60068-2-14 19. Damp heat test, cyclic : IEC-60068-2-30

20. Enclosure Protection Test (IP54) : IEC 60529

CE compliance 21. Immunity : IEC-60255-26 22. Emissive Test : IEC- 60255-26 23. Low voltage directive : EN-50178 Mechanical tests

24. Vibration Endurance Test

: IEC 60255-21-1 class 2 : Frequency Range = 10Hz – 150Hz, acceleration. = 2gn : Sweep rate 1 octave/min; 20 cycle in 3 orthogonal axis.

25. Vibration Response Test

: IEC 60255-21-1 class 2 : Frequency Range = 10Hz – 150Hz, acceleration. = 1gn : Sweep rate 1 octave/min; Displacement =0.075mm, in 3

orthogonal axis. 26. Bump Test : IEC 60255-21-2 Class-1

: 1000 bumps / direction of 10gn peak acceleration and 16ms pulse duration in each of the two opposite direction per axis as per No. of axes. 3.

27. Shock Withstand Test : IEC 60255-21-2 Class-1 : 3 shocks of 15gn peak acceleration and 11ms pulse in

each of two opposite direction. No. of axis : 3

Page 16: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 16 of 43

28. Shock Response Test : IEC 60255-21-2 Class-2 : 3 shocks of 10gn peak acceleration and 11ms pulse in

each of two opposite direction. No. of axis : 3 29. Seismic Test : IEC 60255-21-3 Class-2

: Sweep 1/Axis (@a sweep rate of 1 octave/minute) vibration in the frequency range (5-35 Hz) at displacement X-axis: 7.5mm, Y-axis: 3.5mm amplitude of 3.5mm with acceleration of X-axis: 2gn, Y-axis: 1gn.

Drawings Information: I. Drawing References

Basic

: For Cabinet Type - MAC01302

: For Back Connections – Non-Drawout - ADV06101

: For Typical External Connections – Non-Drawout - ADV06201

: For Back Connections – Plugin - ADV09701

: For Typical External Connections – Plugin - ADV09801

Enhanced

: For Cabinet Type - MAC01964

: For Back Connections (16DO & 10DI) – Non-Drawout - ADV06301

: For Typical External Connections (16DO & 10DI) – Non-Drawout

- ADV06401

: For Back Connections (11DO & 10DI) – Non-Drawout - ADV09501

: For Typical External Connections (11DO & 10DI) – Non-Drawout

- ADV09601

: For Back Connections (16DO & 10DI) – Plugin - ADV10301

: For Typical External Connections (16DO & 10DI) – Plugin

- ADV10401

: For Back Connections (11DO & 10DI) – Plugin - ADV10501

: For Typical External Connections (11DO & 10DI) – Plugin

- ADV10601

Modular 14”

: For Cabinet Type - MAC01967

: For Back Connections - ADV06502

: For Typical External Connections - ADV06602

Modular 19”

: For Cabinet Type - MAC01953

: For Back Connections - ADV06702

: For Typical External Connections - ADV06802

Page 17: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 17 of 43

Mounting Information:

Basic / Enhance – Flush mounting arrangement

19”/ 14” Modular – Rack mounting arrangement

Page 18: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 18 of 43

Mechanical Details – Basic Model

Page 19: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 19 of 43

Back Terminal Details – Basic Model (Non-Drawout)

Page 20: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 20 of 43

Electrical Connection Details – Basic Model (Non-Drawout)

Page 21: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 21 of 43

Back Terminal Details – Basic Model (Plugin)

Page 22: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 22 of 43

Electrical Connection Details – Basic Model (Plugin)

Page 23: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 23 of 43

Mechanical Details – Enhanced Model

Page 24: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 24 of 43

Back Terminal Details – Enhanced Model (16DO & 10DI) – Non Drawout

Page 25: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 25 of 43

Electrical Connection Details – Enhanced Model (16DO & 10DI) – Non Drawout

Page 26: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 26 of 43

Back Terminal Details – Enhanced Model (11DO & 10DI) – Non Drawout

Page 27: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 27 of 43

Electrical Connection Details – Enhanced Model (11DO & 10DI) – Non Drawout

Page 28: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 28 of 43

Back Terminal Details – Enhanced Model (16DO & 10DI) – Plugin

Page 29: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 29 of 43

Electrical Connection Details – Enhanced Model (16DO & 10DI) – Plugin

Page 30: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 30 of 43

Back Terminal Details – Enhanced Model (11DO & 10DI) – Plugin

Page 31: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 31 of 43

Electrical Connection Details – Enhanced Model (11DO & 10DI) – Plugin

Page 32: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 32 of 43

Mechanical Details – Modular 14” Model

Page 33: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 33 of 43

Back Terminal Details – Modular 14” Model

Page 34: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 34 of 43

Electrical Connection Details – Modular 14” Model

Page 35: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 35 of 43

Page 36: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 36 of 43

Mechanical Details – Modular 19” Model

Page 37: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 37 of 43

Back Terminal Details – Modular 19” Model

Page 38: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 38 of 43

Electrical Connection Details – Modular 19” Model

Page 39: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 39 of 43

Page 40: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 40 of 43

General Specifications: AC Current Inputs:

1A Nominal

5A Nominal

Continuous Thermal Rating:

250 X In for 1s

20 X In for 3s

4 X In for Continuous duty

Dynamic Thermal rating

1250 for 10ms dynamic timing

Burden Rating:

< 0.2VA for 1A Nominal

< 0.2VA for 5A Nominal

AC Voltage Inputs:

2 X Vn for Continuous duty

2.6 X Vn for 10s

Over Voltage Category III

Pollution Degree 2

Rated Insulation Voltage: 2.5kV

Burden: <0.2VA

System Frequency:

50Hz / 60Hz

Frequency Tracking: 45 – 55Hz for 50Hz and 55 – 65 for 60Hz

Power Supply:

Range: 24 to 230Vac/dc

Burden: < 10watts for DC

Digital Outputs:

Continuous carry: 5A

Make: 30A for 0.5s & 15A for 3s

Breaking capacity: 1250VA @ 250Vac, 100

watts @ 250Vdc resistive, 50 watts @

250Vdc inductive (L/R = 45ms)

Digital Inputs:

Operating range: 24 – 230Vac/dc

Communication Ports:

Front Port – RS232 / (AM220XX) / USB

(AM550XX)

Rear Ports – RJ45 (10-100/Base T Copper)

& RS485/422

IRIG Port – Demodulated (Optional)

Fiber Optic Port (Optional)

Operating Temperature:

-25OC to +65OC

Storage Temperature: -25OC to +70OC

Humidity: 95% RH

Weight: < 3.4kg Basic

< 3.5kg Enhanced

< 8.2kg Modular 19”

Refer respective Instruction Manual (Basic / Enhance/ Modular) for actual functionality

Page 41: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 41 of 43

Ordering Information

1-4 5 6 7 8 9 10 11 12 13 14 15

Model 244B X X X X X X X X X X X

Example 244B M 0 0 5 0 1 1 2 3 2 M

MOTOR PROTECTION

Sub Type

Basic Version B

Enhanced Version E

Modular Version M

Variant Standard 0 With SEF (Only for E and M) 1 Customer Specific C

Language

English 0

Protocol

IEC 103 0

IEC 103 & MODBUS RTU 1

IEC 103 & IEC 61850 2

IEC 103, IEC 61850 & MODBUS RTU 3

IEC 103 & MODBUS TCP 4

IEC 103, IEC 61850 & MODBUS TCP 5

Customer Specific C

CT / PT & RTD

Default: 4CT, CT Selection: 1A/5A, 4PT: 63.5V 0

Default + 5 RTD Protection 1

Default + 8 Analog Input (Only for Modular Versions) 2

4CT, CT Selection: 1A/5A, 3PT: 63.5V + 1PT: Sync Check 3

Digital Outputs

Default: (Basic - 11DO),(Enhanced - 16DO) 0

16 DO (only for Modular Version) * (Enhanced - 11DO) 1

24 DO (only for Modular Version) * 2

32 DO (only for Modular Version) * 3

40 DO (only for Modular Version)* 4

48 DO (only for Modular Version)* 5

Digital Inputs

(Basic - 12DI),(Enhanced - 10DI) 0

16 DI (only for Modular Version)* 1

24 DI (only for Modular Version)* 2

32 DI (only for Modular Version)* 3

40 DI (only for Modular Version)* 4

48 DI (only for Modular Version)* 5

Page 42: ADR244B - Armtek Elektrik

ADR244B

Doc ID: ADR244B/PC/01 Rev No.: 10 Page No.: 42 of 43

DI Setting Threshold

18VDC 0

35VDC 1

77VDC 2

154VDC 3

Auxiliary Supply

24VDC – 48VDC 1

24 – 230 VDC / VAC 2

110VDC – 250VDC 3

Customer Specific C

Cabinet Details

Non Draw Out (only for Basic Version & Enhanced Version) 0

Draw Out 1

Plug In (only for Basic Version & Enhanced Version) / Modular Version M-14 2

Modular Version M-19 3

Communication Ports

Disable / No Rear Port 0

RS-422 Rear Port A

RS-485 Rear Port B

10/100 Base-T Ethernet RJ45 Rear Port C

10/100 Base-T Ethernet RJ45 Rear Port & RS-422 Rear Port*** D

10/100 Base-T Ethernet RJ45 Rear Port & RS-485 Rear Port E

DUAL 10/100 Base-T Ethernet RJ45 Rear Port F

DUAL 10/100 Base-T Ethernet RJ45 Rear Port & RS-422 Rear Port*** G

DUAL 10/100 Base-T Ethernet RJ45 Rear Port & RS-485 Rear Port H

RS-485 Rear Port + IRIGB Port** I

10/100 Base-T Ethernet RJ45 Rear Port + IRIGB Port** J

10/100 Base-T Ethernet RJ45 Rear Port & RS-485 Rear Port + IRIGB Port** K

DUAL 10/100 Base-T Ethernet RJ45 Rear Port + IRIGB Port** L

DUAL 10/100 Base-T Ethernet RJ45 Rear Port & RS-485 Rear Port + IRIGB Port** M

*Note: For Modular Relay selection of DI & DO combinations are as follows: 16 DI & 16 DO (for Modular Version M-14 & M-19) 16 DI & 48 DO (only for Modular Version M-19) 24 DI & 24 DO (only for Modular Version M-19) 32 DI & 32 DO (only for Modular Version M-19) 48 DI & 16 DO (only for Modular Version M-19) 24 DI & 40 DO (only for Modular Version M-19) 40 DI & 24 DO (only for Modular Version M-19) ** Available only in E and M Version *** Available only in Basic Version

Page 43: ADR244B - Armtek Elektrik

ADR244B

ASHIDA ELECTRONICS PVT LTD. All rights reserved. All

brand or product names appearing in this document are the

trademark or registered trademark of their respective

holders. No ASHIDA trademarks may be used without

written permission.

The information in this document is provided for

informational use only and is subject to change without legal

notice. ASHIDA ELECTRONICS PVT LTD. has approved only

the English language document.