+ All Categories
Home > Documents > Adverse Environment Rotor Test Stand Calibration and Shape ...

Adverse Environment Rotor Test Stand Calibration and Shape ...

Date post: 12-Feb-2017
Category:
Upload: dangdiep
View: 227 times
Download: 0 times
Share this document with a friend
15
ADVERSE ENVIRONMENT ADVERSE ENVIRONMENT ADVERSE ENVIRONMENT ADVERSE ENVIRONMENT ROTOR TEST STAND CAL ROTOR TEST STAND CAL ROTOR TEST STAND CAL ROTOR TEST STAND CALIBRATION IBRATION IBRATION IBRATION PROCEDURES PROCEDURES PROCEDURES PROCEDURES AND ICE SHAPE CORRE AND ICE SHAPE CORRE AND ICE SHAPE CORRE AND ICE SHAPE CORRELATION LATION LATION LATION Jose L. Palacios Research Associate Edward W. Brouwers Research Assistant Yiqiang Han Research Assistant Edward C. Smith Professor The Vertical Lift Research Center of Excellence Department of Aerospace Engineering The Pennsylvania State University, University Park, PA 16802 ABSTRACT ABSTRACT ABSTRACT ABSTRACT An Adverse Environment Rotor Test Stand (AERTS) has been designed, and constructed. The facility is able to reproduce natural icing conditions on a hovering rotor. The motor/hub configuration is designed to spin instrumented rotors of up to 9 ft. diameter and has the capability of providing tip speeds of up to 470 ft/sec. A Liquid Water Content (LWC) calculation methodology was developed and sensitivity studies to determine experimental LWC are presented in this paper. Correlation between experimental ice accretion shapes obtained in the AERTS facility and experimental results obtained by the NASA Icing Research Tunnel and the Air Force Arnold Engineering Development Center are presented. These experimental correlations are conducted to demonstrate the capability of producing an accurate realistic icing cloud of the new facility. All tests reported in this paper have been conducted on 1 in. diameter circular cross section rotors. The majority of the experimental ice shapes compared agree with results presented in literature with thickness errors as low as 2% and impingement limits discrepancies no greater than 15%. Nomenclature Nomenclature Nomenclature Nomenclature Ac Accumulation parameter, dimensionless b Relative heat factor, dimensionless cp,ws Specific heat of water at the surface temperature, cal/g Khc Convective heat-transfer coefficient, cal/s m 2 K hG Gas-phase mass-transfer coefficient, g/s m 2 K Inertia parameter, dimensionless K0 Modified inertia parameter, dimensionless ka Thermal conductivity of air, cal/s m K LWC Cloud liquid-water content, g/m 3 Ma Mach Number, dimensionless MVD Water droplet median volume diameter, μm Nu Nusselt number, dimensionless m & Mass Flux, Kg/m 2 sec Pr Prandtl Number Pst Static pressure, psi pw Vapor pressure of water in atmosphere, psi pww Vapor pressure of water at the icing surface, psi r Recovery factor, dimensionless Re Reynolds number of model, dimensionless Reδ Reynolds number of water droplet, dimensionless τ Accretion time, min t Temperature, °C tf Freezing temperature of water, °C ts Surface temperature, °C V Free-stream velocity of air, m/s β0 Collection efficiency at stagnation line, dimensionless δ Cylinder diameter, cm Δ Ice thickness at stagnation line, cm ηa Freezing fraction (Messinger analysis), dimensionless ηe Freezing fraction, experimental, dimensionless θ Air energy transfer parameter, °K λ Water droplet range, m Λf Latent heat of freezing of water, cal/g λstokes Water droplet range if Stokes Law applies, m Λv Latent heat of evaporation of water, cal/g μ Viscosity of air, g/m s ρa Air density, g/m 3 ρi Ice density, g/m 3 ρw Liquid water density, g/m 3 Ф Water droplet energy transfer parameter, °K Presented at the American Helicopter Society 66 th Annual Forum, Phoenix, AZ, May 11-13, 2010. Copyright © 2010 by the American Helicopter Society International, Inc. All rights reserved.
Transcript
Page 1: Adverse Environment Rotor Test Stand Calibration and Shape ...

ADVERSE ENVIRONMENT ADVERSE ENVIRONMENT ADVERSE ENVIRONMENT ADVERSE ENVIRONMENT ROTOR TEST STAND CALROTOR TEST STAND CALROTOR TEST STAND CALROTOR TEST STAND CALIBRATIONIBRATIONIBRATIONIBRATION PROCEDURES PROCEDURES PROCEDURES PROCEDURES

AND ICE SHAPE CORRE AND ICE SHAPE CORRE AND ICE SHAPE CORRE AND ICE SHAPE CORRELATIONLATIONLATIONLATION

Jose L. Palacios

Research Associate

Edward W. Brouwers

Research Assistant

Yiqiang Han

Research Assistant

Edward C. Smith

Professor

The Vertical Lift Research Center of Excellence Department of Aerospace Engineering

The Pennsylvania State University, University Park, PA 16802

ABSTRACTABSTRACTABSTRACTABSTRACT

An Adverse Environment Rotor Test Stand (AERTS) has been designed, and constructed. The facility

is able to reproduce natural icing conditions on a hovering rotor. The motor/hub configuration is

designed to spin instrumented rotors of up to 9 ft. diameter and has the capability of providing tip

speeds of up to 470 ft/sec. A Liquid Water Content (LWC) calculation methodology was developed and

sensitivity studies to determine experimental LWC are presented in this paper. Correlation between

experimental ice accretion shapes obtained in the AERTS facility and experimental results obtained by

the NASA Icing Research Tunnel and the Air Force Arnold Engineering Development Center are

presented. These experimental correlations are conducted to demonstrate the capability of producing

an accurate realistic icing cloud of the new facility. All tests reported in this paper have been

conducted on 1 in. diameter circular cross section rotors. The majority of the experimental ice shapes

compared agree with results presented in literature with thickness errors as low as 2% and impingement limits discrepancies no greater than 15%.

NomenclatureNomenclatureNomenclatureNomenclature

Ac Accumulation parameter, dimensionless

b Relative heat factor, dimensionless

cp,ws Specific heat of water at the surface temperature, cal/g Khc

Convective heat-transfer coefficient, cal/s m2 K

hG Gas-phase mass-transfer coefficient, g/s m2

K Inertia parameter, dimensionless

K0 Modified inertia parameter, dimensionless

ka Thermal conductivity of air, cal/s m K

LWC Cloud liquid-water content, g/m3

Ma Mach Number, dimensionless

MVD Water droplet median volume diameter, μm

Nu Nusselt number, dimensionless

m& Mass Flux, Kg/m2 sec

Pr Prandtl Number

Pst Static pressure, psi

pw Vapor pressure of water in atmosphere, psi

pww Vapor pressure of water at the icing surface, psi

r Recovery factor, dimensionless

Re Reynolds number of model, dimensionless

Reδ Reynolds number of water droplet, dimensionless

τ Accretion time, min

t Temperature, °C

tf Freezing temperature of water, °C

ts Surface temperature, °C

V Free-stream velocity of air, m/s

β0 Collection efficiency at stagnation line, dimensionless

δ Cylinder diameter, cm

∆ Ice thickness at stagnation line, cm

ηa Freezing fraction (Messinger analysis), dimensionless

ηe Freezing fraction, experimental, dimensionless

θ Air energy transfer parameter, °K

λ Water droplet range, m

Λf Latent heat of freezing of water, cal/g

λstokes Water droplet range if Stokes Law applies, m

Λv Latent heat of evaporation of water, cal/g

μ Viscosity of air, g/m s

ρa Air density, g/m3

ρi Ice density, g/m3

ρw Liquid water density, g/m3

Ф Water droplet energy transfer parameter, °K

Presented at the American Helicopter Society 66th Annual Forum, Phoenix, AZ, May 11-13, 2010.

Copyright © 2010 by the American Helicopter Society International, Inc. All rights reserved.

Page 2: Adverse Environment Rotor Test Stand Calibration and Shape ...

1111. . . . INTRODUCTIONINTRODUCTIONINTRODUCTIONINTRODUCTION

HERE are four main ways to perform rotor ice testing:

wind tunnel ice testing, ground spraying approaches,

in-flight spraying systems, and “chasing the weather.”

Wind tunnel testing considerably reduces cost comparing

with natural icing trials and it is ideal for ice shape model

validation and preliminary testing of fix wing ice

protection technologies. Wind tunnel icing facilities, such

as NASA Glenn (OH)[1], Cox Icing Research Facility[2]

(NY), or Goodrich Icing Tunnel (OH)[3] have limited test

sections restricting the size of the rotor blades that can be

spun. Ground icing facilities or in-flight water spraying

system [4] (such as the Helicopter Icing Spray System,

HISS) are expensive approaches to reproduce natural icing

on full scale rotors and are not suitable for proof-of-

concept testing of new deicing systems. These are testing

techniques used for certification of established ice

protection systems. Similarly, chasing the weather

involves high costs reserved for ice protection

certification of technologies in production.

A main obstacle on on-going efforts to model rotor ice

accretion is lack of open source validation ice shape data.

There are limited icing facilities focusing on rotorcraft

research. Rotor icing testing can be accomplished in

NASA Glenn’s Icing Research Tunnel (IRT), but model

rotor diameters are limited to 6 ft by the test section [1].

The Helicopter In-flight Spray System (HISS) allows for

full scale testing, but detailed icing shapes are difficult to

acquire as the vehicle must descent through layers of

warm air that may shed ice prior to landing.

Ice protection system and other components tests, such as

icing sensors or effects of icing on other probes, can be

conducted at above mentioned icing wind tunnels. These

tests are often limited by tunnel velocity and the fact that

the centrifugal forces inherent to rotor rotation are not

represented.

For this reason, a new Adverse Environment Rotor Test

Stand facility (AERTS) has been designed, fabricated and

calibrated. In this facility icing conditions can be

reproduced surrounding a 9 ft. diameter rotor. The main

mission of this facility is to provide a test bed for new ice

protection systems, such as ultrasonic deicing. Secondary

objectives involve measurement of ice adhesion strength

to different coatings and ice shape correlations with ice

accretion models.

To determine if natural icing conditions can be

reproduced, Liquid Water Concentration (LWC) must be

properly characterized in the facility. This is one of the

most important parameters used during ice accretion

experimental testing [5] and it is measured in g/m3. LWC

sensors are not applicable to the facility because they

require velocity over the active element. To provide these

devices with proper operational velocity conditions, the

LWC sensors would have to be spun. Due to size and cost

of these sensors, their rotation was not possible. For this

reason, in the AERTS facility, LWC is calculated using the

modified accumulation parameter of a body, which

involves the accurate determination of the freezing

fraction. The freezing fraction of a body, η, measures the percentage of water that freezes to the shape with respect

to all the water coming into contact with the body.

Freezing fraction is dependent on icing conditions

including LWC. Freezing fraction is therefore the most

important non-dimensional parameter used in ice

accretion modeling, scaling, and calibration as it

represents all the effects from LWC, droplet size,

temperature and other icing test parameters. The accurate

determination of the freezing fraction of a body is critical

to the calculation of LWC. This quantity is defined by

Messinger’s heat-balance analysis and it determines how

rapidly freezing takes place when super-cooled water

impacts a solid body.

In this paper, a description of the facility is provided, as

well as initial calibration procedures to determine LWC

and MVD in the laboratory. To demonstrate the facility

initial capabilities and to determine its application limits,

ice accretion shapes to a 1 in. diameter cylinder are

correlated to results presented in literature.

2. RESEARCH OBJECTIV2. RESEARCH OBJECTIV2. RESEARCH OBJECTIV2. RESEARCH OBJECTIVEEEE

The objectives of the research are to describe the

capabilities of the newly designed and constructed AERTS

facility, the purpose of which is future evaluation of

helicopter deicing systems. Analysis of LWC sensitivity

studies is presented. To validate the functionality and

capability to reproduce natural icing conditions on the rig,

ice shapes obtained in the facility are correlated with prior

testing conducted at the NASA Glenn Icing Research

Tunnel[6] and the Air Force Arnold Engineering

Development Center (AEDC)[11].

This paper is divided into three sections:

- Facility Description

- LWC Sensitivity Study

- Ice Shape Correlation to NASA Icing Research

Tunnel and AEDC Experimental Results on 1 in.

Diameter Cylinder

T

Page 3: Adverse Environment Rotor Test Stand Calibration and Shape ...

3. 3. 3. 3. AERTS FACILITY AERTS FACILITY AERTS FACILITY AERTS FACILITY

The AERTS facility is formed by an industrial 20 x 20 x 20

foot cold chamber where 4 in. thick insulated walls and a

water-cooled compressor form the cooling system.

Temperatures between -25° C and 0° C can be achieved in

the chamber. The chamber floor is waterproofed with

marine lumber covered by aluminum plating, and a

drainage system in the perimeter of the room, collects

melted ice during the post-test defrosting process. Inside

the chamber, and surrounding the rotor, there is a safety

ballistic wall in the shape of an octagon. The ballistic wall

is formed by 6 in. thick weather resistant lumber

reinforced with 0.25 in. thick steel, and covered by

aluminum plating for weather protection. A schematic

and photograph of the chamber, as seen from a top view,

is shown in Figure 1.

Figure 1: Schematic and Photograph of the AERTS Facility. The AERTS Hub is Collective and Lateral Cyclic Capable. Max RPM:

1000. Max. Rotor Diameter: 9 ft. MAX. Power: 120 HP.

3.1 3.1 3.1 3.1 Nozzle Nozzle Nozzle Nozzle Spray System Spray System Spray System Spray System ArrayArrayArrayArray

In the ceiling of the chamber there are 15 NASA standard

icing nozzles that generate the icing cloud to the room.

The nozzles are arranged into two concentric circles

located 20 and 42 in. from the center of rotation...The

nozzles can be operated in sets of five, having the

capability to turn on five, ten or fifteen nozzles. The

number of nozzles operating and the Median Volume

Diameter (MVD) of the water droplets (provided by the

pressure differential between air and water) dictate the

Liquid Water Content (LWC) in the room.

Similar nozzles are used in the Icing Research Tunnel

(IRT) and Goodrich Icing Tunnel. A photograph of the

icing cloud start is shown in Figure 2.

Figure 2: Detail of Icing Cloud AERTS Facility

The nozzles operate by aerosolizing water droplets with a

precise combination of water and air as per nozzle

calibration curves[1]. The plots relating water and air

pressure differential to the MVD particle size created is

presented in Figure 3. The nozzles are installed in parallel,

such that equal air and water pressure is sent to every

nozzle. This is done because the pressures control the

water particle size provided by the nozzles

The air system was designed to provide accurate and

consistent air pressure to the icing nozzles. Each nozzle

requires up to 15 CFM to provide a stable icing cloud at 50

psi of input air pressure. A 21 HP air compressor provides

the nozzles the required pressure, with an upper limit

corresponding to constant 35 psi air pressure to all 15

nozzles, 55 psi to 10 nozzles, and 105 psi of air pressure to

5 nozzles. These upper limits dictate the airline pressures

that can be triggered.

15 Nozzles – Facility Ceiling View

9 ft

Slip Ring

Collective Actuator Bell Housing w/ 6 Axis Load Cell

Weather Station

125 HP Motor

Ballistic Wall

20’

20’

Cooling Fan

Page 4: Adverse Environment Rotor Test Stand Calibration and Shape ...

Figure 3: NASA Standard Icing Nozzle Operation Chart as

Described in Reference 1

The water system is generally similar to the air system,

with added complications in maintaining constant and

controllable water pressure in a close loop. For this

reason, a feedback control is in place to maintain the

water pressure at desired conditions. In addition, a water

reverse osmosis purification systems is required prior

pressurization in order to reproduce natural icing

conditions and to prevent nozzle clogging. The water

purity measured 1 ppm and a resistance of 2 KΩ between

two electrodes immersed in the water 6 in. from each

other. The water and air pressures are measured at the

input of the water and air lines to the nozzles, ensuring

precise readings of the pressure differential controlling the

particle size. A diagram of the air and water system is

shown in Figure 4.

3.2 3.2 3.2 3.2 Motor/HubMotor/HubMotor/HubMotor/Hub

In the center of the chamber a 125 HP, 160 ft-lb motor

rotates the lower hub of a QH-50D DASH UAV vehicle.

The motor is connected to a gear box with a 2.5:1

reduction ratio. The hub was retrofitted to fit the

transmission of the motor. The configuration provides

RPM values of up to 1500 RPM for 4.5 ft. radius blades,

reproducing full scale helicopter tip speeds. The test stand

has been successfully operated to date up to 1000 RPM.

The hub has collective and lateral cyclic capabilities, as

well as a six-axis load cell. A detail photo of the hub is

presented in Figure 5 and a summary of key facility

capabilities is listed in Table 1.

3.3 Controls and Measurements3.3 Controls and Measurements3.3 Controls and Measurements3.3 Controls and Measurements

The facility is operated from a control room where remote

controllers of all aspects of the facility are located.

Controls are separated on three main independent groups:

rotor, icing cloud and cooling.

The icing cloud can be turned on and off at desired

settings (MVD, airline) from the control room, where

remote electronic shut-off valves of the water and air

systems are located. Custom designed computer software

controls the water and air pressures to desired settings

using feedback control loops, maintaining the particle size

within 2 µm of desired parameters. The remote

capabilities of the cloud allow starting the icing once the

rotor has reached desired RPM. Suction pumps are in

place to stop the cloud instantaneously once the system is

shut down.

Figure 4: Diagram of Air and Water Conditioning Prior Atomization at Nozzle

Figure 5: Photo of QH-50D DASH UAV Hub

10

15

20

25

30

35

40

45

50

0 20 40 60 80 100

∆P =Delta Pressure Water - Air (Psi)

MV

D (

Mic

ron

s)

Air (Psi) � 10 15 20 25 30 35 40 45 50

QH-50 Bell Housing/HUB

Bell housing with Heated Load Cell

Page 5: Adverse Environment Rotor Test Stand Calibration and Shape ...

Table 1: AERTS Facility Capabilities

Rotor SystemRotor SystemRotor SystemRotor System

ParameterParameterParameterParameter ValueValueValueValue NotesNotesNotesNotes

84 max Unlimited run time Motor Power (HP)

120 max 3 minute run limit

696 max Unlimited run time Motor Torque (in-lbf)

995 max 3 minute run limit

RPM 400 to 1000 400 RPM for adequate cloud mixing; 1000 RPM test stand safety limit

Rotor Tip Radius (ft) 2 to 4.5 Minimum required to reduce effects of hub icing cloud; maximum dictated by

ballistic wall geometry

Blade Grip Radius (ft) 0.94

Blade Grip CF Load (lbf) 14,000 Based upon QH-50 hub design loads. Includes required facility FOS

Hub Precone (°) 3

Hub Flap (Teeter) Range (°) -12 to +12 Limited by teeter bumpers

Collective Pitch (°) -2 to +12 Controlled with linear actuator.

Lateral Cyclic Pitch (°) -5 to +5 Controlled with linear actuator. Longitudinal cyclic pitch is locked out.

Icing SystemIcing SystemIcing SystemIcing System

ParameterParameterParameterParameter ValueValueValueValue NotesNotesNotesNotes

Active Nozzles 1 to 15

Nozzles are arranged in 2 concentric rings in chamber ceiling, with 5 nozzles

in inner ring and 10 nozzles in outer ring. Any combination of nozzles can be

used for each test.

Temperature (°C) Ambient to -25

Chamber cooling system is shut down during each test to avoid disrupting

icing cloud. Temperature increases during each test due to kinetic friction of

the rotor and warm water inputs to the chamber.

MVD (µm) 10 to 50

Not directly measured. Droplet size based upon NASA Standard nozzle

calibration tables. Water and air pressure input control system maintains

droplet size input to the test chamber ± 2 µm. Larger particle sizes are

possible, but are outside the calibrated range of the nozzles.

LWC (g/ m3) 1 to 5

Not directly measured. Controlled by number of active nozzles and input

pressures and calculated after each test based upon accreted ice thickness. Not

all MVD/LWC points are possible based upon chamber limitations.

Icing Time (seconds) 30 to 240

Approximately 30 seconds is required for the nozzles to stabilize and for the

cloud properly to mix in the chamber. Icing duration limit is based on the

requirement to maintain static temperature in chamber ± 1 °C from desired

point.

Water Input Temp. (°C) 20 to 71 Water input temperature can be varied to properly supercool droplets at all

temperatures.

Water Purity

(ppm impurities) 1 to 3

Reverse Osmosis Purification System generates water with 2 MΩ resistance

(6" probe separation)

InstrumentationInstrumentationInstrumentationInstrumentation

ParameterParameterParameterParameter ValueValueValueValue NotesNotesNotesNotes

CCD Cameras 3 Two cameras monitor entire test chamber; third camera focused on rotor tip.

Static Temperature Sensors 5

Thermistors are positioned around test chamber to monitor internal

temperature. A commercial weather station measures temperature as well as

pressure, humidity and rain fall rates.

Slip Ring Power Channels 24 max Each channel is rated up to 15A, 800V

Slip Ring Signal Channels 24 max Each channel is rated up to 2A, 100V

Page 6: Adverse Environment Rotor Test Stand Calibration and Shape ...

Thrust: 875 6 Axis Load Cell Forces (lbf)

Lat/Long: 300

6 Axis Load Cell Moments

(in-lbf) Pitch/Roll/Yaw:

1800

Measurement range. Sensor can safely handle 8x reported loads.

Shaft Torque Sensor (in-lbf) 1500 Measurement range.

Available Output Channels 8 Each channel is rated at 0 - 10V, 10 ksps. Current is based upon DAQ module

usages, but typically ~ 10 mA. Used for triggering relays etc.

Available Generic Input

Channels 38 (+4)

Each channel is rated at 250 ksps. Four channels are reserved for temperature

(thermocouple) measurements.

Available Strain Gauge

Modules 3 Used only for fixed frame measurements

Strain Gauge Amplifiers 2

Strain gauge amplifiers are used for on blade measurements. The full bridge

completion units are mounted at the blade roots and amplify signals prior to

them entering the rotor hub to improve overall S/N ratio.

Accelerometer

Conditioning Circuits 2

Accelerometer signals are conditioned and amplified prior to being read by

Labview

The rotor system has ramping capabilities, currently

set-up to reach 1000 RPM in 5 seconds. Emergency stop

of the rotor allows for complete stop in 2 seconds.

The walk-in freezer is cooled by convection of cooling

lines and a fan located inside the chamber. To prevent

the fan from accreting ice and distorting the icing

cloud, the fan is turned off during exposure to super-

cooled water droplets. This currently limits the

capability to maintain a desired temperature within 1°C

to 3.5 minutes, as warm air and water and kinetic

friction of the rotor increase the temperature in the

chamber.

A six axis load cell is installed in the rotor stand. It

measures lift, side forces and related moments. This

load cell does not only provide physical loads on the

system, but also monitors for potential rotor unbalance

due to ice shedding. To monitor ice accretion

performance degradation, a torque sensor placed in line

with the shaft measures torque on the system with a

maximum reading capability of 95 ft-lbs.

Accelerometers are placed in the bell-housing and mast

as redundant measures to monitor potential vibration

due to rotor unbalance. Inside the bell-housing and

monitoring the rotation of the main shaft, there is an

RPM sensor that provides information on the rotor

status.

Temperature in the chamber is monitored by weather

stations inside of the ballistic wall and under the rotor

plane. Additional thermocouples are placed on the

room, also for redundancy.

All electric systems and signal conditioners are

insulated and heated to 29°C to limit temperature

compensation errors on the readings.

4. LWC SENSITIVITY S4. LWC SENSITIVITY S4. LWC SENSITIVITY S4. LWC SENSITIVITY STUDYTUDYTUDYTUDY

Static temperature is measured in the facility during

icing testing, as it can be read from thermocouples

located in the chamber. MVD is calculated from NASA

calibration tables and experimental readings of pressure

differentials between the water and the air inputs to the

nozzles. Even though MVD is not currently directly or

indirectly measured in the facility, however, nozzle

calibration is assumed to be accurate and constant

monitoring of the water and air pressure allows for the

calculation of MVD. The only icing parameter that is

unknown and could not be directly measured during

testing is the LWC in the room.

LWC sensors, in addition to their high cost, require

velocity components that are not available in the

facility. These sensors are designed for wind tunnel and

in-flight LWC measurements and require a minimum

velocity component of 15 m/s. To subject the LWC

sensors to these velocities, they could be placed in the

rotating frame, but due to the size of these sensors and

centrifugal effects, their rotation is not possible.

For this reason, LWC must be determined

experimentally by investigating the ice accretion

thicknesses to a known body. These calibration efforts

must be performed prior attempting ice shape

correlations with literature or ice accretion model

validation. A computer code that calculates LWC from

ice accretion thickness during a given time interval was

created. One of the most important non-dimensional

Page 7: Adverse Environment Rotor Test Stand Calibration and Shape ...

parameters used to calculate LWC modeling is the

freezing fraction, η, defined by the heat-balance analysis of Messinger. The code was validated versus

experimental and analytical results presented by

Anderson and Tsao[7] on their paper “Evaluation and

Validation of the Messinger Freezing Fraction.”

To determine the LWC in the facility, a computer code

that calculates LWC from ice accretion thickness

during a given time interval was created. The principle

of this code traces back LWC from the experimental

result of ice accretion thickness. The code correlates

thickness and freezing fraction to determine the

experimental LWC. The freezing fraction is defined by

Messinger[8] as the fraction of water flux entering a

control volume that freezes within the control volume.

It illustrates the ice accretion rate when super-cooled

water impinges on a solid body, on which the ice

thickness is depended. In this way, the LWC can be

calculated from the experimental ice thickness. This

code was validated versus experimental and analytical

results from reference 7. The calculation scheme is

represented in the following sections.

4.1 4.1 4.1 4.1 LWC Experimental CalculationLWC Experimental CalculationLWC Experimental CalculationLWC Experimental Calculation

The developed code estimates the LWC from the

stagnation point ice thickness for a given accretion

time. The estimated LWC, together with other icing

conditions, is then compared with analytical results

presented in literature[7] to validate the procedure. The

input parameters to the code include: chord (for airfoil)

or diameter (for cylinder), MVD, temperature, local

velocity, icing time and thickness. To calculate the

physical LWC condition during testing with this

analytical method, several parameters are introduced in

the analysis and are described in the following sections.

4.1.1. Droplet Trajectory Analysis Prior Impingement

The objective for this section of the analytical

calculations is to find the collection efficiency, which

can be interpreted into how much water droplets are

going to hit on the model (i.e. the mass flux used in the

following equations). This is the basis of both analytical

and experimental expression of freezing fraction.

This analysis aims to find an expression for super-

cooled water drop distribution. The stagnation line

collection efficiency, βo, illustrates the impinging water

drop trajectory by considering the projection of a

stream tube from the far-field inflow at stagnation line.

The problem is simplified at the stagnation line, as it is

assumed that at this line there is no incoming

interference from other controlled volumes. The

analysis following are all based on this assumption[7,8].

The expression of collection efficiency at the stagnation

line is given by Equation 1:

( )( )

−+

−=

84.

0

84.

0

0

8/1*40.11

8/1*40.1

K

Kβ (1)

where, K0 is the Langmuir and Blodgett’s[9] expression for modified inertia parameter (Equation 2). This

equation was initially published for cylinders, but was

then validated for airfoils in the reference 9.

−+=

8

1

8

10

KKStokes

λ

λ, for

8

1>K (2)

The inertia parameter, K, in Equation 2 can be expressed as:

a

w

d

VK

µ

δρ

18

2

= (3)

And Stokes

λλ / is defined as the dimensionless droplet

range parameter,

δδλ

λ

Re1847.0Re001483.08388.0

1

++=

Stokes

(4)

where

a

aV

µ

δρδ =Re (5)

4.1.2. Energy Balance Analysis during Impingement

As mentioned, one of the most important variables

during icing testing is the freezing fraction, which

denotes the fraction of water droplets that freezes at the

surface of a body, thus indicating the heat balance at

the ice surface.

Analytical freezing fraction can be found by the

following Equation:

+

Λ=

b

Cn

f

wsp

a

θφ

,

,0 (6)

where, ф and θ , are defined as droplet energy transfer and air energy transfer coefficients respectively:

wsp

stfc

Vtt

,

2

2−−=φ (7)

v

st

www

c

G

ap

stsp

pp

h

h

c

Vtt Λ

−+

−−=

,

2

2θ (8)

The relative heat factor, b, is introduced by Tribus[9] as:

Page 8: Adverse Environment Rotor Test Stand Calibration and Shape ...

c

wsp

h

cmb

,&

= (9)

The convective heat-transfer coefficient, hc, can be calculated from Equation 11.

a

c

k

dhNu = (10)

The numerical expression of Nu in this code is chosen according to different Re numbers: for Re > 105, as per reference 9:

472.0Re10.1=Nu (11)

and for Re < 105, as per reference 9: 5.040

Re141.

rP.Nu = (12)

Based on the trajectory analysis at stagnation line in the

last section and assuming βo and ρi remain the same while the ice shape changes during the test, the mass

flux can be expressed as:

0β⋅⋅= VLWCm& (13)

Here, it can be seen that LWC can be determined from

the analytical freezing fraction. by introducing a

correlation between freezing fraction and ice thickness

in next section, the LWC can be finally determined.

4.1.3 Ice Accretion Analysis

Based on the previous analysis, a time-span analysis

during ice accretion can be performed. Total ice

thickness at stagnation line, ∆, can be expressed as:

0n

m

i

⋅=∆ρ

τ& (14)

By Substituting Equation 10 into Equation 14 and

introducing an accumulation parameter Ac, Equation 15 is found.

d

VLWCA

i

τ⋅⋅= (15)

The non-dimensional total ice thickness is defined in

Equation 16.

0,0β

ceAn

d=

∆ (16)

The experimental freezing fraction, η0,e, can be related to the analytical freezing fraction, η0,a, by using a linear curve fitting as it is suggested by Anderson and Tsao[7]:

aenn

,0,0107.10184.0 += (18)

The relationship between total thickness and LWC can

be shown to be monotonic. Thus, an exhaust algorithm

can be implemented to find experimental LWC from

total ice thickness per time. The scheme of the code is

summarized in Figure 6.

4.1.4. Evaluation of LWC Calculation Code

The calculated LWCs based on the total ice thickness

per time are compared with the analytic LWCs

presented in literature for both cylinders [10] and airfoils [7]. The correlation between calculated LWC and results

presented in literature are shown in Figure 7 and Figure

8. It can be concluded that this code calculates

acceptable LWC from total ice thickness per time

(within ±15% error) for nearly 90% of all the cases

presented in literature. Taking into account the

uncertainties related to experimental test data, these

results can be assumed to be useful and reliable to

support the LWC calibration of the facility.

4.1.6. Uncertainty Analysis

From Figure 7, and Figure 8, it is shown that

experiment-derived LWCs generally result in a good

agreement with literature data, presenting correlation

discrepancies of less than 15% for the majority of the

cases compared. Several cases deviate between

calculations and experimental results presented by the

referenced documents. The two main contributions of

this kind of error come from uncertainty of

measurement; and error transmitted between

calculation equations.

Firstly, for most experiments performed at NASA IRT

to which this paper is comparing, the uncertainty

related to LWC calibration at IRT is claimed to be

about ±12%[7] . Also there is ±12% uncertainty in MVD. ]In addition, in most icing tests, hand-tracing

measurement methods are prevalently used, and for

this reason, the thickness record has its own inherent

uncertainty. For similar shapes, it can be shown that

the experimental ice thicknesses can differ by up to

18.8% [7] between the centerline of a test section and

some small distance above centerline. Given the limited

data set, these uncertainties cannot be effectively

resolved.

Page 9: Adverse Environment Rotor Test Stand Calibration and Shape ...

Figure 6: Scheme of Experimental LWC Calculation Code

Figure 7: Cylinder LWC Calculations from Total Thickness and Correlation with Results Presented in Reference 10

Figure 8: NACA 0012 LWC Calculations Compared to

Experimental Results Presented in Reference 7

Page 10: Adverse Environment Rotor Test Stand Calibration and Shape ...

Secondly, due to the small size of the ice thickness itself, a

slight error in tracing the ice thickness will then be

transmitted and amplified through equations and

computing loops of the presented code, resulting in a

relatively big error between analytic LWC and thickness-

based or experimental LWC.

It can be seen from presented equations, that the change

in thickness has large effects on the calculated LWC. As

stated before, there is a linear relationship between

thickness, freezing fraction and eventually the LWC.

Small changes in ice thickness (> 0.5 mm) will produce

deviations of LWC of up to 50%.

In the reference [7], although with a different analysis

method and ignoring the difference between analytical

and experimental LWC, Anderson and Tsao also did some

comparisons between analytical freezing fraction and

experimental freezing fraction based on the ice thickness.

In two test groups (test case number 8 – 14 and 32 – 35

with regard to Figure 8 in this article), large discrepancies

between ηa and ηa can be found in these two groups. The greatest one is found in case 3-12-02/1(test case number

32 in Figure 8, with regard to this article), where ηa = 0.275 and ηe = 0.190; i.e., the error can be as high as 45% (error with respect to ηe, from which the experimental LWC is determined), much bigger than ±12% as they

expected for most cases. These errors are also reflected in

the LWC calculation code in Figure 8. The same

phenomena are also found in Figure 7, test case number 9

and 10.

Anderson and Tsao believe this is because there can be

significant uncertainty in the ice thickness values found

from tracings at low freezing fractions. This is true as

already mentioned above. Also, the relatively large

discrepancies between the analytical LWCs and the ones

calculated from the measured thickness can also be

explained by the slope of the relationship between ice

thickness and LWC (Equation 19). The slope, S, of the equation could be very small (≈0.025), greatly affecting

the LWC value for errors introduced in the measurement

of the ice thickness.

rLWCS +⋅=∆ (19)

For example, in some cases, a change in thickness of 0.005

in. results in a change on the calculated LWC of 0.43 g/m3.

For this reason, careful measurement of the ice shapes

must be performed.

In addition, the empirical equations used in this code

(such as relationships between ηe and ηa, or the numerical expression of Nu.) will add error into the calculation as

icing conditions diverge from those used during the

definition of these empirical equations.

With these assumptions of uncertainty, each analytic

LWC is plotted in Figure 7 and Figure 8 with an error bar

of ±15%. Calculated LWC results correlate with values

presented in literature, validating the usage of the code to

determine the LWC in the facility.

4.2 Experimental 4.2 Experimental 4.2 Experimental 4.2 Experimental ResultsResultsResultsResults

A rotor formed by a 1 in. diameter cylinder (50 in. radius)

was spun at different icing conditions. A total of 18 runs

were conducted to calibrate the chamber at -5°C, -10°C,

and -15°C. A 1 in. diameter rotor of 50 in. radius was used.

For each temperature, variations of RPM (500, and 600),

air lines (20, 25, and 30 Psi) and MVD (20, 25, and 30 µm)

were conducted. LWC were calculated for all conditions

along the span of the rotor, as ice thickness. All tests were

run for 3 minutes, with a maximum temperature deviation

of 1°C. Five nozzles located in the outer ring were used

during testing. LWC calibration matrices allow for the

selection of conditions (MVD, airline, temperature) to

trigger a desired experimental LWC during a test. A

photograph of the 1 in. diameter rotor as seen from one of

the monitoring cameras during ice testing is presented in

Figure 9.

Figure 9: Photograph 1 in. Diameter Rotor during Icing Testing

As it can be observed on Figure 10, the ice thickness at the

stagnation point increased as temperature decreased from

-5°C to -15°C. These tests were conducted at ceteris

paribus conditions (25 MVD, 500 RPM, 25 Psi air line, 3

minutes of ice exposure). It is counterintuitive that the ice

thickness would increase as temperature drops, as the

LWC should decrease. This does not happen in the AERTS

facility for all conditions, as temperatures below -10°C are

allowing more droplets to become super-cooled. For this

1 in. Diameter 1 in. Diameter 1 in. Diameter 1 in. Diameter

50 in.50 in.50 in.50 in.

Bottom View Rotor Bottom View Rotor Bottom View Rotor Bottom View Rotor

with Accreted Icewith Accreted Icewith Accreted Icewith Accreted Ice

Page 11: Adverse Environment Rotor Test Stand Calibration and Shape ...

reason, each temperature condition at the facility must be

calibrated for LWC. A detail of the ice thickness increase

is depicted in Figure 11, where the calculated LWC is

shown.

Figure 10: Variation on Ice Thickness with Rotor Span: -5º, -10º

and -15º Deg. C Static Temperature

RPM increases correspond to ice increases, as it is shown

in Figure 12. This was expected, given the reduced tip

speeds (about 65 m/sec), in where kinetic heating of the

blade is not a major factor affecting ice accretion. Also, as

particle size was increased between 20 and 30 MVD, ice

accretion thickness increased.

Figure 11: Detail of Ice Shapes Obtained at -15°C, -10°C, and -5°C (500 RPM, 25 MVD, 25 PSI Air Line, 3 min. Exposure)

For this reason, the facility is limited to the 30 Psi air line

if 25 MVD are sought and 5 nozzles are in operation. This

airline limitation will vary depending on the MVD

sought, as this is controlled by the pressure differential

between water and air. Lower MVD will allow for an

increase in the airline, while larger MVD will further

decrease the maximum air pressure line to be used. To

allow for the use of higher airlines, a decrease in

operational nozzles could be implemented.

Figure 12: Effect of RPM Increase on Ice Thickness and LWC

One important issue encountered during testing was the

appearance of ice crystals when air lines exceeding 23 Psi

(see Figure 3) were triggered. Due to the small facility

size, super-cooled liquid droplets re-circulate around the

ballistic wall after they pass through the rotor plane if

they do not accrete to the walls or floor of the facility.

Since no particle removal process is used in the facility

(other than ice collection screens located under the rotor

plane) the droplets can freeze into solid crystals when

they re-circulate.

Figure 13: Effect of MVD Increase on Ice Thickness and LWC

Figure 14: Effect of Airline Increase (-10°C). Notice Ice shape Erosion, as Facility is Saturated by Ice Crystals – 30 Psi

25 Psi Air, 25 MVD, 500 RPM25 Psi Air, 25 MVD, 500 RPM25 Psi Air, 25 MVD, 500 RPM25 Psi Air, 25 MVD, 500 RPM 30303030 Psi Air, 25 MVD, 500 RPM Psi Air, 25 MVD, 500 RPM Psi Air, 25 MVD, 500 RPM Psi Air, 25 MVD, 500 RPM

500 RPM, 25 Psi Air, -15 Deg. C

1

1.05

1.1

1.15

1.2

1.25

1.3

1.35

0.5 0.55 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1

Rotor Span (r/R)

Ice T

hic

kn

ess (

in.)

20 MVD

30 MVD

Linear (30 MVD)

Linear (20 MVD)

LWC = 2.4 g/m3

LWC = 2.2 g/m3

25 Air line, 25 MVD, -5 Deg C.

0.8

0.9

1

1.1

1.2

1.3

1.4

0.5 0.6 0.7 0.8 0.9 1

Span Location (r/R)

Ice T

hic

kn

ess (

in.)

500 RPM 600 RPM

LWC 2.4 g/m3

LWC 3 g/m3

500 RPM, 25 Psi Air, 25 MVD, 3 min.

0.8

0.9

1

1.1

1.2

1.3

1.4

0.5 0.6 0.7 0.8 0.9 1

Rotor Span (r/R)

Ice T

hic

kn

ess

(in

.)

-15°C

-10° C

-5°C

-150C

-50C -100C

-150C, LWC, 2.55 g/m3

-100C, LWC 2.35 g/m3

-50C, LWC 2.29 g/m3

Ice shape ErosionIce shape ErosionIce shape ErosionIce shape Erosion

Page 12: Adverse Environment Rotor Test Stand Calibration and Shape ...

When liquid droplets impact a crystal, the droplet is

immediately crystallized, which creates a chain reaction[5].

Larger numbers of particles in the chamber increase this

effect due to saturation and are generated when using

higher air pressure inputs to the nozzle. To maintain a

desired MVD at higher air pressures, water pressures need

to be increased to maintain the proper pressure

differential, as detailed in Figure 3 and explained in

Reference 1. Since the water flow rate is dependent on

this pressure differential, the mass of water added to the

chamber increases, creating a large number of droplets. If

the droplets crystallize, they erode ice shapes, providing

“spear” shaped ice accretion, as shown in Figure 14. The

maximum pressure differential to avoid crystallization

problems was experimentally determined to be 23 psi.

Similar ice shape erosion is documented by Tsao et al. in

reference 12. During tests conducted at the IRT, there was

evidence indicating that ice erosion occurred for rime ice

shapes obtained at 250 knots. Erosion was identified by

shapes lacking expected small-scale feathers and increased

stagnation ice thickness, as seen in Figure 15[12].

Figure 15: Example of Eroded Rime Ice Tracing at the IRT,

Reference 12

5. AERTS ICE SHAPE C5. AERTS ICE SHAPE C5. AERTS ICE SHAPE C5. AERTS ICE SHAPE CORRELATION TO NASA AORRELATION TO NASA AORRELATION TO NASA AORRELATION TO NASA AND ND ND ND

AIRFORCE EXPERIMENTAAIRFORCE EXPERIMENTAAIRFORCE EXPERIMENTAAIRFORCE EXPERIMENTAL RESULTSL RESULTSL RESULTSL RESULTS

To validate the capability of the facility to reproduce

natural icing conditions, accretion shapes found in

literature for 1 in. diameter cylinders were compared to

experimental results obtained in the AERTS facility.

Currently, the main challenges operating the facility are

due to lack of temperature control and complete LWC

calibration. Radiation cooling systems capable of

maintaining the facility at temperature without

convection fans are not installed yet. The temperature in

the facility can only be maintained for 3.5 minutes with a

deviation of 1°C, since all cooling fans must be shut down

during icing to avoid ice accretion and cloud perturbation.

A second issue is that LWC calibrations matrices are not

fully populated yet, as this is the first attempt to

understand and calibrate the facility. For this reason,

specific conditions identified in literature are cumbersome

to match perfectly in terms of LWC.

Despite these temporary limitations, agreement between

ice shapes presented in literature and experimental results

are observed. Correlations between AERTS experimental

results and experimental results presented in literature

(Reference 6) are shown in Figure 16 and Figure 17.

As it can be seen in Figure 16 and Figure 17, the

stagnation ice thickness correlates with experimental

results obtained at the IRT. The overall shape of the

accreted ice also agrees. Increases in the impingement

limits can be observed, which could imply an increase in

particle size or decrease in temperature during testing.

Figure 16: Test 1 - Correlation of Experimental Results from AERTS (25 MVD, 58 m/sec. -11.7

0C, 5 min., 2 gr/m

3) to Reference

Results (Ref. 6: 23 MVD, 58 m/sec, -11.70C, 5 min., 1.6 gr/m

3)

The discrepancy between impingement limits of the two

experimental results was calculated to be less than 16% of

the total ice thickness for both Tests.

Figure 17: Test 2 - Correlation of Experimental Results from AERTS (27 MVD, 59.2 m/sec. -12

0C, 6.3 min., 1.91 gr/m

3) to

Reference Results (Ref. 6: 27 MVD, 58 m/sec, -12.670C, 6.3 min.,

and 1.3 gr/m3)

AERTS Exp. Reference

AERTS – EXP.

1 in Tube

AERTS – EXP.

27 MVD

490 RPM

0.91 r/R

59.2 m/sec

-120C

AERTS Exp. Reference

25 MVD

510 RPM

0.875 r/R

58 m/sec

-11.70C

Tsao, J., Kreeger, R., Reference 12

Ice shape ErosionIce shape ErosionIce shape ErosionIce shape Erosion

Page 13: Adverse Environment Rotor Test Stand Calibration and Shape ...

Correlations were also performed against experimental ice

shapes obtained by Ruff et al. at the Air Force Arnold

Engineering Development Center (AEDC) [15]. These tests

were performed at lower LWC values than the minimum

provided by the facility when 5 NASA standard nozzles

are in operation. For this reason, and to reduce the LWC

in the chamber, a controlled system of nozzles was

introduced, such that each nozzle can be operated

individually. This allowed for combinations of 3 and 4

nozzles to be used, thus allowing for a reduction of LWC.

As it can be observed on Figure 18 to Figure 22, ice shape

agreement is obtained between all tests.

Figure 18: Test 3 - Correlation of Experimental Results from

AERTS to Reference Results Presented in Literature (Ref. 11)

The maximum discrepancy between ice thicknesses is

calculated to be 11.8% for test 4 (Figure 19). Tests 1, 2, 5,

and 6 have an ice thickness discrepancy between facilities

of less than 2%. Deviations between targeted temperature

and experimental temperature, in addition to other

experimental uncertainty during tests, might introduce

errors observed between shapes. In general, ice shape

trends agree between experimental results presented in

literature and results obtained at the AERTS facility,

validating its capabilities to reproduce icing conditions.

Figure 19: Test 4 - Correlation of Experimental Results from AERTS to Reference Results Presented in Literature (Ref. 11)

Figure 20: Test 5 - Correlation of Experimental Results from

AERTS to Reference Results Presented in Literature (Ref. 11)

Figure 21: Test 6 - Correlation of Experimental Results from

AERTS to Reference Results Presented in Literature (Ref. 11)

In the first test presented in Figure 16, the experimental

MVD was 25 μm, 2 μm larger than what is presented in

the result presented in literature. In the second test

(Figure 17), the MVD was maintained at exactly 27 μm,

matching the MVD presented in literature results.

Discrepancies in MVD between the experimental tests

compared are not believed to be the main cause of ice

shape deviation.

As mentioned on section 3, the MVD in the facility is

maintained with a feedback control loop that ensures

desired air and water pressure to the NASA standard

nozzles. According to NASA nozzle calibration tables

(Figure 3), the particle size is maintained within 2 μm. For

this reason, MVD deviation is assumed not to be the main

cause presenting the slight differences between both tests.

It is believed that the main reason making the ice shape

correlation deviate is that the temperature in the chamber

can only be maintained for 3.5 minutes, before

temperature increases exceed 1°C. Those tests run for

longer than 3.5 minutes show increased discrepancies

between experimental results. Tests 1 and 2 (Figure 16 and

Figure 17) were run for 5 and 6.3 minutes respectively,

having temperature increases of up to 2°C with respect to

the desired starting temperature. From those tests

MVD = 20 µm

TRef = -15°C

TExp = -15°C

Vel = 60.9 m/sec

LWCref = 1.2 gr/m3

LWCExp = 1.3 gr/m3

r/R = 0.91

AERTS Exp. Reference

MVD = 20 µm

TRef = -15°C

TExp = -13.75°C

Vel = 60.9 m/sec

LWCref = 1.2 gr/m3

LWCExp = 1.2 gr/m3

r/R = 0.91

AERTS Exp. Reference

MVD = 20 µm

TRef = -11.4°C

TExp = -12°C

Vel = 60.9 m/sec

LWCref = 0.9 gr/m3

LWCExp = 0.8 gr/m3

r/R = 0.91

AERTS Exp. Reference

Time: 2.5 Min

Time: 5 Min

Time: 3.75 Min

MVD = 20 µm

TRef = -5°C

TExp = -5.5°C

Vel = 60.9 m/sec

LWCref = 1.2 gr/m3

LWCExp = 1.3 gr/m3

r/R = 0.91

AERTS Exp. Reference

Time: 2.5 Min

Page 14: Adverse Environment Rotor Test Stand Calibration and Shape ...

compared to AEDC results, tests 4, 5 and 7 were also run

for more than 3.5 minutes, presenting larger shape

deviations than tests 3 and 6 (run for 2.5 minutes).

Figure 22: Test 7 - Correlation of Experimental Results from AERTS to Reference Results Presented in Literature (Ref. 11)

This warming effect is believed to be the main source of

any discrepancy that might be found between the two

experimental results. Other uncertainties would be

introduced due to the fact that the AERTS facility

introduces centrifugal forces not seen in the IRT.

6. CONCLUSION6. CONCLUSION6. CONCLUSION6. CONCLUSION

A new Adverse Environment Rotor Test Stand facility in

were icing clouds surrounding a hovering rotor can be

reproduced, was designed, and built to investigate ice

accretion phenomenon and solutions. The AERTS facility

is capable of reproducing natural icing conditions as long

as saturation of the chamber is prevented. LWC sensitivity

study of the facility for particle sizes between 20 and 30

MVD was accomplished. These efforts demonstrated that

representative LWC values encountered in natural icing

conditions (1.7 to 2.6 g/m3) can be reproduced. From these

initial calibration efforts, the saturation limit of the

chamber was determined. This condition is identified

when pressure differentials in the facility exceeded 23 Psi

for a five nozzle configuration. During LWC sensitivity

tests, it was also noted that the facility is limited to icing

tests of less than 3.5 minutes due to temperature increases

in the chamber. This temperature increases are due to lack

of cooling systems during operation since they must be

shut down to avoid ice accretion to cooling fans. This

issue could be mitigated with additional radiation cooling

lines in the facility that would allow for temperature

control for longer periods of time.

Ice shape correlations between the facility and

experimental results presented in literature by NASA and

Airforce, indicate the capability of the AERTS facility to

reproduce icing shapes obtained in the IRT and the

Arnold Engineering Development Center (AEDC).

Correlations between IRT and AERTS stagnation ice

thicknesses are excellent, with less than 2% discrepancy

between tests. Impingement limits and overall ice mass

was overachieved at the AERTS facility by up to 16%, due

to experimental uncertainties, but it is believed that

increases of temperature during testing beyond the

desired comparison value are the main cause. These errors

were calculated as percentage of thickness at the

stagnation line. The maximum ice thickness errors with

respect to the AEDC was calculated to be 11.8%, but the

majority of tests provided correlations between ice

thickness with discrepancies of less than 2%.

Ice shapes obtained at the AERTS facility agree with

experimental results presented in literature, validating the

capability of the facility to reproduce natural icing

conditions on hovering rotors with zero thrust.

ACKNOWLEDGEMENTS ACKNOWLEDGEMENTS ACKNOWLEDGEMENTS ACKNOWLEDGEMENTS

The authors would like to thank Eric Kreeger and Paul

Tsao of the NASA Glenn Research Center for their

donation of the critical icing nozzles and their advice in

calibrating the AERTS Facility. The authors would also

like to acknowledge Peter Papadakos of the Gyrodyne

Historical Foundation for the donation of the QH-50D

lower rotor head and upper controls. The authors would

also like to thank the US Army for sponsoring this

research by funding a program to investigate the potential

of the facility to generate representative ice shapes, and

the installation of the icing system. This research is

partially funded by the Government under Agreement

No. W911W6-06-2-0008. The U.S. Government is

authorized to reproduce and distribute reprints

notwithstanding any copyright notation thereon. The

views and conclusions contained in this document are

those of the authors and should not be interpreted as

representing the official policies, either expressed or

implied, of the U.S. Government.

REFERENCESREFERENCESREFERENCESREFERENCES

1. Ide, R., Oldenburg, J., “Icing Cloud Calibration of the

NASA Glenn Icing Research Tunnel,” AIAA-2001-0234,

March 2001

2. Al-Khalil, K., Salamon, L., Tenison, G., “Development

of the Cox Icing Research Facility,” 36th Aerospace

Sciences Meeting & Exhibit, AIAA 98-0097, January 12-

15, 1998, Reno, NV

MVD = 20 µm

TRef = -5°C

TExp = -6.7°C

Vel = 60.9 m/sec

LWCref = 1.2 gr/m3

LWCExp = 1.32 gr/m3

r/R = 0.91

AERTS Exp. Reference

Time: 5 Min

Page 15: Adverse Environment Rotor Test Stand Calibration and Shape ...

3. Herman, E., “Goodrich Icing Wind Tunnel Overview,

Improvements and Capabilities,” AIAA 2006-862, 44th

AIAA Aerospace Sciences Meeting and Exhibit, 9 - 12

January 2006, Reno, Nevada

4. Peterson, A., Oldenburg, J., “Spray Nozzle Investigation

for the Improved Helicopter Icing Spray system

(IHISS),” 28th Aerospace Sciences Meeting, , January 8-

11, 1990, Reno, NV

5. Gent, R.W., Dart, N.P and Candsdale, J.T. Aircraft

Icing. Philosophical Transactions of the Royal Society of

London SeriesA. 2000, Vol. 358

6. Anderson, D., “Rime-, Mixed-, and Glaze-Ice

Evaluations of Three Scaling Laws,” NASA Technical

Memorandum 106461, AIAA-94-07-18, AIAA 32nd

Aerospace Sciences Meeting and Exhibit, Reno, Nevada

January 10-13, 1994.

7. Anderson D., and Tsao, J., “Evaluation and Validation of

the Messinger Freezing Fraction,” NASA/CR—2005-

213852, AIAA–2003–1218, 41st Aerospace Sciences

Meeting and Exhibit, Reno, Nevada, January 6–9, 2003.

8. Messinger, B.L., “Equilibrium Temperature of an

Unheated Icing Surface as a Function of Airspeed,” J.

Aeron. Sci. vol. 20 no. 1, January 1953, pp 29-42.

9. Anderson, David N., “Manual of Scaling Methods”,

NASA CR – 2004-212875

10. Anderson, David N., “Evaluation of Constant-

Weber-Number Scaling for Icing Tests,” AIAA-96-0636

and NASA TM 107141, January 1996.

11. Ruff, G., “Analysis and Verification of the Icing

Scaling Equations,” Air force Technical Report AEDC-

TR-85-30, November 1985

12. Tsao. J., Kreeger, R., “Experimental Evaluation of

Stagnation Point Collection Efficiency of the NACA

0012 Swept Wing Tip,” AIAA 2009-4125, 1st AIAA

Atmospheric and Space Environments Conference, 22 -

25 June 2009, San Antonio, Texas


Recommended