ADVERSE ENVIRONMENT ADVERSE ENVIRONMENT ADVERSE ENVIRONMENT ADVERSE ENVIRONMENT ROTOR TEST STAND CALROTOR TEST STAND CALROTOR TEST STAND CALROTOR TEST STAND CALIBRATIONIBRATIONIBRATIONIBRATION PROCEDURES PROCEDURES PROCEDURES PROCEDURES
AND ICE SHAPE CORRE AND ICE SHAPE CORRE AND ICE SHAPE CORRE AND ICE SHAPE CORRELATIONLATIONLATIONLATION
Jose L. Palacios
Research Associate
Edward W. Brouwers
Research Assistant
Yiqiang Han
Research Assistant
Edward C. Smith
Professor
The Vertical Lift Research Center of Excellence Department of Aerospace Engineering
The Pennsylvania State University, University Park, PA 16802
ABSTRACTABSTRACTABSTRACTABSTRACT
An Adverse Environment Rotor Test Stand (AERTS) has been designed, and constructed. The facility
is able to reproduce natural icing conditions on a hovering rotor. The motor/hub configuration is
designed to spin instrumented rotors of up to 9 ft. diameter and has the capability of providing tip
speeds of up to 470 ft/sec. A Liquid Water Content (LWC) calculation methodology was developed and
sensitivity studies to determine experimental LWC are presented in this paper. Correlation between
experimental ice accretion shapes obtained in the AERTS facility and experimental results obtained by
the NASA Icing Research Tunnel and the Air Force Arnold Engineering Development Center are
presented. These experimental correlations are conducted to demonstrate the capability of producing
an accurate realistic icing cloud of the new facility. All tests reported in this paper have been
conducted on 1 in. diameter circular cross section rotors. The majority of the experimental ice shapes
compared agree with results presented in literature with thickness errors as low as 2% and impingement limits discrepancies no greater than 15%.
NomenclatureNomenclatureNomenclatureNomenclature
Ac Accumulation parameter, dimensionless
b Relative heat factor, dimensionless
cp,ws Specific heat of water at the surface temperature, cal/g Khc
Convective heat-transfer coefficient, cal/s m2 K
hG Gas-phase mass-transfer coefficient, g/s m2
K Inertia parameter, dimensionless
K0 Modified inertia parameter, dimensionless
ka Thermal conductivity of air, cal/s m K
LWC Cloud liquid-water content, g/m3
Ma Mach Number, dimensionless
MVD Water droplet median volume diameter, μm
Nu Nusselt number, dimensionless
m& Mass Flux, Kg/m2 sec
Pr Prandtl Number
Pst Static pressure, psi
pw Vapor pressure of water in atmosphere, psi
pww Vapor pressure of water at the icing surface, psi
r Recovery factor, dimensionless
Re Reynolds number of model, dimensionless
Reδ Reynolds number of water droplet, dimensionless
τ Accretion time, min
t Temperature, °C
tf Freezing temperature of water, °C
ts Surface temperature, °C
V Free-stream velocity of air, m/s
β0 Collection efficiency at stagnation line, dimensionless
δ Cylinder diameter, cm
∆ Ice thickness at stagnation line, cm
ηa Freezing fraction (Messinger analysis), dimensionless
ηe Freezing fraction, experimental, dimensionless
θ Air energy transfer parameter, °K
λ Water droplet range, m
Λf Latent heat of freezing of water, cal/g
λstokes Water droplet range if Stokes Law applies, m
Λv Latent heat of evaporation of water, cal/g
μ Viscosity of air, g/m s
ρa Air density, g/m3
ρi Ice density, g/m3
ρw Liquid water density, g/m3
Ф Water droplet energy transfer parameter, °K
Presented at the American Helicopter Society 66th Annual Forum, Phoenix, AZ, May 11-13, 2010.
Copyright © 2010 by the American Helicopter Society International, Inc. All rights reserved.
1111. . . . INTRODUCTIONINTRODUCTIONINTRODUCTIONINTRODUCTION
HERE are four main ways to perform rotor ice testing:
wind tunnel ice testing, ground spraying approaches,
in-flight spraying systems, and “chasing the weather.”
Wind tunnel testing considerably reduces cost comparing
with natural icing trials and it is ideal for ice shape model
validation and preliminary testing of fix wing ice
protection technologies. Wind tunnel icing facilities, such
as NASA Glenn (OH)[1], Cox Icing Research Facility[2]
(NY), or Goodrich Icing Tunnel (OH)[3] have limited test
sections restricting the size of the rotor blades that can be
spun. Ground icing facilities or in-flight water spraying
system [4] (such as the Helicopter Icing Spray System,
HISS) are expensive approaches to reproduce natural icing
on full scale rotors and are not suitable for proof-of-
concept testing of new deicing systems. These are testing
techniques used for certification of established ice
protection systems. Similarly, chasing the weather
involves high costs reserved for ice protection
certification of technologies in production.
A main obstacle on on-going efforts to model rotor ice
accretion is lack of open source validation ice shape data.
There are limited icing facilities focusing on rotorcraft
research. Rotor icing testing can be accomplished in
NASA Glenn’s Icing Research Tunnel (IRT), but model
rotor diameters are limited to 6 ft by the test section [1].
The Helicopter In-flight Spray System (HISS) allows for
full scale testing, but detailed icing shapes are difficult to
acquire as the vehicle must descent through layers of
warm air that may shed ice prior to landing.
Ice protection system and other components tests, such as
icing sensors or effects of icing on other probes, can be
conducted at above mentioned icing wind tunnels. These
tests are often limited by tunnel velocity and the fact that
the centrifugal forces inherent to rotor rotation are not
represented.
For this reason, a new Adverse Environment Rotor Test
Stand facility (AERTS) has been designed, fabricated and
calibrated. In this facility icing conditions can be
reproduced surrounding a 9 ft. diameter rotor. The main
mission of this facility is to provide a test bed for new ice
protection systems, such as ultrasonic deicing. Secondary
objectives involve measurement of ice adhesion strength
to different coatings and ice shape correlations with ice
accretion models.
To determine if natural icing conditions can be
reproduced, Liquid Water Concentration (LWC) must be
properly characterized in the facility. This is one of the
most important parameters used during ice accretion
experimental testing [5] and it is measured in g/m3. LWC
sensors are not applicable to the facility because they
require velocity over the active element. To provide these
devices with proper operational velocity conditions, the
LWC sensors would have to be spun. Due to size and cost
of these sensors, their rotation was not possible. For this
reason, in the AERTS facility, LWC is calculated using the
modified accumulation parameter of a body, which
involves the accurate determination of the freezing
fraction. The freezing fraction of a body, η, measures the percentage of water that freezes to the shape with respect
to all the water coming into contact with the body.
Freezing fraction is dependent on icing conditions
including LWC. Freezing fraction is therefore the most
important non-dimensional parameter used in ice
accretion modeling, scaling, and calibration as it
represents all the effects from LWC, droplet size,
temperature and other icing test parameters. The accurate
determination of the freezing fraction of a body is critical
to the calculation of LWC. This quantity is defined by
Messinger’s heat-balance analysis and it determines how
rapidly freezing takes place when super-cooled water
impacts a solid body.
In this paper, a description of the facility is provided, as
well as initial calibration procedures to determine LWC
and MVD in the laboratory. To demonstrate the facility
initial capabilities and to determine its application limits,
ice accretion shapes to a 1 in. diameter cylinder are
correlated to results presented in literature.
2. RESEARCH OBJECTIV2. RESEARCH OBJECTIV2. RESEARCH OBJECTIV2. RESEARCH OBJECTIVEEEE
The objectives of the research are to describe the
capabilities of the newly designed and constructed AERTS
facility, the purpose of which is future evaluation of
helicopter deicing systems. Analysis of LWC sensitivity
studies is presented. To validate the functionality and
capability to reproduce natural icing conditions on the rig,
ice shapes obtained in the facility are correlated with prior
testing conducted at the NASA Glenn Icing Research
Tunnel[6] and the Air Force Arnold Engineering
Development Center (AEDC)[11].
This paper is divided into three sections:
- Facility Description
- LWC Sensitivity Study
- Ice Shape Correlation to NASA Icing Research
Tunnel and AEDC Experimental Results on 1 in.
Diameter Cylinder
T
3. 3. 3. 3. AERTS FACILITY AERTS FACILITY AERTS FACILITY AERTS FACILITY
The AERTS facility is formed by an industrial 20 x 20 x 20
foot cold chamber where 4 in. thick insulated walls and a
water-cooled compressor form the cooling system.
Temperatures between -25° C and 0° C can be achieved in
the chamber. The chamber floor is waterproofed with
marine lumber covered by aluminum plating, and a
drainage system in the perimeter of the room, collects
melted ice during the post-test defrosting process. Inside
the chamber, and surrounding the rotor, there is a safety
ballistic wall in the shape of an octagon. The ballistic wall
is formed by 6 in. thick weather resistant lumber
reinforced with 0.25 in. thick steel, and covered by
aluminum plating for weather protection. A schematic
and photograph of the chamber, as seen from a top view,
is shown in Figure 1.
Figure 1: Schematic and Photograph of the AERTS Facility. The AERTS Hub is Collective and Lateral Cyclic Capable. Max RPM:
1000. Max. Rotor Diameter: 9 ft. MAX. Power: 120 HP.
3.1 3.1 3.1 3.1 Nozzle Nozzle Nozzle Nozzle Spray System Spray System Spray System Spray System ArrayArrayArrayArray
In the ceiling of the chamber there are 15 NASA standard
icing nozzles that generate the icing cloud to the room.
The nozzles are arranged into two concentric circles
located 20 and 42 in. from the center of rotation...The
nozzles can be operated in sets of five, having the
capability to turn on five, ten or fifteen nozzles. The
number of nozzles operating and the Median Volume
Diameter (MVD) of the water droplets (provided by the
pressure differential between air and water) dictate the
Liquid Water Content (LWC) in the room.
Similar nozzles are used in the Icing Research Tunnel
(IRT) and Goodrich Icing Tunnel. A photograph of the
icing cloud start is shown in Figure 2.
Figure 2: Detail of Icing Cloud AERTS Facility
The nozzles operate by aerosolizing water droplets with a
precise combination of water and air as per nozzle
calibration curves[1]. The plots relating water and air
pressure differential to the MVD particle size created is
presented in Figure 3. The nozzles are installed in parallel,
such that equal air and water pressure is sent to every
nozzle. This is done because the pressures control the
water particle size provided by the nozzles
The air system was designed to provide accurate and
consistent air pressure to the icing nozzles. Each nozzle
requires up to 15 CFM to provide a stable icing cloud at 50
psi of input air pressure. A 21 HP air compressor provides
the nozzles the required pressure, with an upper limit
corresponding to constant 35 psi air pressure to all 15
nozzles, 55 psi to 10 nozzles, and 105 psi of air pressure to
5 nozzles. These upper limits dictate the airline pressures
that can be triggered.
15 Nozzles – Facility Ceiling View
9 ft
Slip Ring
Collective Actuator Bell Housing w/ 6 Axis Load Cell
Weather Station
125 HP Motor
Ballistic Wall
20’
20’
Cooling Fan
Figure 3: NASA Standard Icing Nozzle Operation Chart as
Described in Reference 1
The water system is generally similar to the air system,
with added complications in maintaining constant and
controllable water pressure in a close loop. For this
reason, a feedback control is in place to maintain the
water pressure at desired conditions. In addition, a water
reverse osmosis purification systems is required prior
pressurization in order to reproduce natural icing
conditions and to prevent nozzle clogging. The water
purity measured 1 ppm and a resistance of 2 KΩ between
two electrodes immersed in the water 6 in. from each
other. The water and air pressures are measured at the
input of the water and air lines to the nozzles, ensuring
precise readings of the pressure differential controlling the
particle size. A diagram of the air and water system is
shown in Figure 4.
3.2 3.2 3.2 3.2 Motor/HubMotor/HubMotor/HubMotor/Hub
In the center of the chamber a 125 HP, 160 ft-lb motor
rotates the lower hub of a QH-50D DASH UAV vehicle.
The motor is connected to a gear box with a 2.5:1
reduction ratio. The hub was retrofitted to fit the
transmission of the motor. The configuration provides
RPM values of up to 1500 RPM for 4.5 ft. radius blades,
reproducing full scale helicopter tip speeds. The test stand
has been successfully operated to date up to 1000 RPM.
The hub has collective and lateral cyclic capabilities, as
well as a six-axis load cell. A detail photo of the hub is
presented in Figure 5 and a summary of key facility
capabilities is listed in Table 1.
3.3 Controls and Measurements3.3 Controls and Measurements3.3 Controls and Measurements3.3 Controls and Measurements
The facility is operated from a control room where remote
controllers of all aspects of the facility are located.
Controls are separated on three main independent groups:
rotor, icing cloud and cooling.
The icing cloud can be turned on and off at desired
settings (MVD, airline) from the control room, where
remote electronic shut-off valves of the water and air
systems are located. Custom designed computer software
controls the water and air pressures to desired settings
using feedback control loops, maintaining the particle size
within 2 µm of desired parameters. The remote
capabilities of the cloud allow starting the icing once the
rotor has reached desired RPM. Suction pumps are in
place to stop the cloud instantaneously once the system is
shut down.
Figure 4: Diagram of Air and Water Conditioning Prior Atomization at Nozzle
Figure 5: Photo of QH-50D DASH UAV Hub
10
15
20
25
30
35
40
45
50
0 20 40 60 80 100
∆P =Delta Pressure Water - Air (Psi)
MV
D (
Mic
ron
s)
Air (Psi) � 10 15 20 25 30 35 40 45 50
QH-50 Bell Housing/HUB
Bell housing with Heated Load Cell
Table 1: AERTS Facility Capabilities
Rotor SystemRotor SystemRotor SystemRotor System
ParameterParameterParameterParameter ValueValueValueValue NotesNotesNotesNotes
84 max Unlimited run time Motor Power (HP)
120 max 3 minute run limit
696 max Unlimited run time Motor Torque (in-lbf)
995 max 3 minute run limit
RPM 400 to 1000 400 RPM for adequate cloud mixing; 1000 RPM test stand safety limit
Rotor Tip Radius (ft) 2 to 4.5 Minimum required to reduce effects of hub icing cloud; maximum dictated by
ballistic wall geometry
Blade Grip Radius (ft) 0.94
Blade Grip CF Load (lbf) 14,000 Based upon QH-50 hub design loads. Includes required facility FOS
Hub Precone (°) 3
Hub Flap (Teeter) Range (°) -12 to +12 Limited by teeter bumpers
Collective Pitch (°) -2 to +12 Controlled with linear actuator.
Lateral Cyclic Pitch (°) -5 to +5 Controlled with linear actuator. Longitudinal cyclic pitch is locked out.
Icing SystemIcing SystemIcing SystemIcing System
ParameterParameterParameterParameter ValueValueValueValue NotesNotesNotesNotes
Active Nozzles 1 to 15
Nozzles are arranged in 2 concentric rings in chamber ceiling, with 5 nozzles
in inner ring and 10 nozzles in outer ring. Any combination of nozzles can be
used for each test.
Temperature (°C) Ambient to -25
Chamber cooling system is shut down during each test to avoid disrupting
icing cloud. Temperature increases during each test due to kinetic friction of
the rotor and warm water inputs to the chamber.
MVD (µm) 10 to 50
Not directly measured. Droplet size based upon NASA Standard nozzle
calibration tables. Water and air pressure input control system maintains
droplet size input to the test chamber ± 2 µm. Larger particle sizes are
possible, but are outside the calibrated range of the nozzles.
LWC (g/ m3) 1 to 5
Not directly measured. Controlled by number of active nozzles and input
pressures and calculated after each test based upon accreted ice thickness. Not
all MVD/LWC points are possible based upon chamber limitations.
Icing Time (seconds) 30 to 240
Approximately 30 seconds is required for the nozzles to stabilize and for the
cloud properly to mix in the chamber. Icing duration limit is based on the
requirement to maintain static temperature in chamber ± 1 °C from desired
point.
Water Input Temp. (°C) 20 to 71 Water input temperature can be varied to properly supercool droplets at all
temperatures.
Water Purity
(ppm impurities) 1 to 3
Reverse Osmosis Purification System generates water with 2 MΩ resistance
(6" probe separation)
InstrumentationInstrumentationInstrumentationInstrumentation
ParameterParameterParameterParameter ValueValueValueValue NotesNotesNotesNotes
CCD Cameras 3 Two cameras monitor entire test chamber; third camera focused on rotor tip.
Static Temperature Sensors 5
Thermistors are positioned around test chamber to monitor internal
temperature. A commercial weather station measures temperature as well as
pressure, humidity and rain fall rates.
Slip Ring Power Channels 24 max Each channel is rated up to 15A, 800V
Slip Ring Signal Channels 24 max Each channel is rated up to 2A, 100V
Thrust: 875 6 Axis Load Cell Forces (lbf)
Lat/Long: 300
6 Axis Load Cell Moments
(in-lbf) Pitch/Roll/Yaw:
1800
Measurement range. Sensor can safely handle 8x reported loads.
Shaft Torque Sensor (in-lbf) 1500 Measurement range.
Available Output Channels 8 Each channel is rated at 0 - 10V, 10 ksps. Current is based upon DAQ module
usages, but typically ~ 10 mA. Used for triggering relays etc.
Available Generic Input
Channels 38 (+4)
Each channel is rated at 250 ksps. Four channels are reserved for temperature
(thermocouple) measurements.
Available Strain Gauge
Modules 3 Used only for fixed frame measurements
Strain Gauge Amplifiers 2
Strain gauge amplifiers are used for on blade measurements. The full bridge
completion units are mounted at the blade roots and amplify signals prior to
them entering the rotor hub to improve overall S/N ratio.
Accelerometer
Conditioning Circuits 2
Accelerometer signals are conditioned and amplified prior to being read by
Labview
The rotor system has ramping capabilities, currently
set-up to reach 1000 RPM in 5 seconds. Emergency stop
of the rotor allows for complete stop in 2 seconds.
The walk-in freezer is cooled by convection of cooling
lines and a fan located inside the chamber. To prevent
the fan from accreting ice and distorting the icing
cloud, the fan is turned off during exposure to super-
cooled water droplets. This currently limits the
capability to maintain a desired temperature within 1°C
to 3.5 minutes, as warm air and water and kinetic
friction of the rotor increase the temperature in the
chamber.
A six axis load cell is installed in the rotor stand. It
measures lift, side forces and related moments. This
load cell does not only provide physical loads on the
system, but also monitors for potential rotor unbalance
due to ice shedding. To monitor ice accretion
performance degradation, a torque sensor placed in line
with the shaft measures torque on the system with a
maximum reading capability of 95 ft-lbs.
Accelerometers are placed in the bell-housing and mast
as redundant measures to monitor potential vibration
due to rotor unbalance. Inside the bell-housing and
monitoring the rotation of the main shaft, there is an
RPM sensor that provides information on the rotor
status.
Temperature in the chamber is monitored by weather
stations inside of the ballistic wall and under the rotor
plane. Additional thermocouples are placed on the
room, also for redundancy.
All electric systems and signal conditioners are
insulated and heated to 29°C to limit temperature
compensation errors on the readings.
4. LWC SENSITIVITY S4. LWC SENSITIVITY S4. LWC SENSITIVITY S4. LWC SENSITIVITY STUDYTUDYTUDYTUDY
Static temperature is measured in the facility during
icing testing, as it can be read from thermocouples
located in the chamber. MVD is calculated from NASA
calibration tables and experimental readings of pressure
differentials between the water and the air inputs to the
nozzles. Even though MVD is not currently directly or
indirectly measured in the facility, however, nozzle
calibration is assumed to be accurate and constant
monitoring of the water and air pressure allows for the
calculation of MVD. The only icing parameter that is
unknown and could not be directly measured during
testing is the LWC in the room.
LWC sensors, in addition to their high cost, require
velocity components that are not available in the
facility. These sensors are designed for wind tunnel and
in-flight LWC measurements and require a minimum
velocity component of 15 m/s. To subject the LWC
sensors to these velocities, they could be placed in the
rotating frame, but due to the size of these sensors and
centrifugal effects, their rotation is not possible.
For this reason, LWC must be determined
experimentally by investigating the ice accretion
thicknesses to a known body. These calibration efforts
must be performed prior attempting ice shape
correlations with literature or ice accretion model
validation. A computer code that calculates LWC from
ice accretion thickness during a given time interval was
created. One of the most important non-dimensional
parameters used to calculate LWC modeling is the
freezing fraction, η, defined by the heat-balance analysis of Messinger. The code was validated versus
experimental and analytical results presented by
Anderson and Tsao[7] on their paper “Evaluation and
Validation of the Messinger Freezing Fraction.”
To determine the LWC in the facility, a computer code
that calculates LWC from ice accretion thickness
during a given time interval was created. The principle
of this code traces back LWC from the experimental
result of ice accretion thickness. The code correlates
thickness and freezing fraction to determine the
experimental LWC. The freezing fraction is defined by
Messinger[8] as the fraction of water flux entering a
control volume that freezes within the control volume.
It illustrates the ice accretion rate when super-cooled
water impinges on a solid body, on which the ice
thickness is depended. In this way, the LWC can be
calculated from the experimental ice thickness. This
code was validated versus experimental and analytical
results from reference 7. The calculation scheme is
represented in the following sections.
4.1 4.1 4.1 4.1 LWC Experimental CalculationLWC Experimental CalculationLWC Experimental CalculationLWC Experimental Calculation
The developed code estimates the LWC from the
stagnation point ice thickness for a given accretion
time. The estimated LWC, together with other icing
conditions, is then compared with analytical results
presented in literature[7] to validate the procedure. The
input parameters to the code include: chord (for airfoil)
or diameter (for cylinder), MVD, temperature, local
velocity, icing time and thickness. To calculate the
physical LWC condition during testing with this
analytical method, several parameters are introduced in
the analysis and are described in the following sections.
4.1.1. Droplet Trajectory Analysis Prior Impingement
The objective for this section of the analytical
calculations is to find the collection efficiency, which
can be interpreted into how much water droplets are
going to hit on the model (i.e. the mass flux used in the
following equations). This is the basis of both analytical
and experimental expression of freezing fraction.
This analysis aims to find an expression for super-
cooled water drop distribution. The stagnation line
collection efficiency, βo, illustrates the impinging water
drop trajectory by considering the projection of a
stream tube from the far-field inflow at stagnation line.
The problem is simplified at the stagnation line, as it is
assumed that at this line there is no incoming
interference from other controlled volumes. The
analysis following are all based on this assumption[7,8].
The expression of collection efficiency at the stagnation
line is given by Equation 1:
( )( )
−+
−=
84.
0
84.
0
0
8/1*40.11
8/1*40.1
K
Kβ (1)
where, K0 is the Langmuir and Blodgett’s[9] expression for modified inertia parameter (Equation 2). This
equation was initially published for cylinders, but was
then validated for airfoils in the reference 9.
−+=
8
1
8
10
KKStokes
λ
λ, for
8
1>K (2)
The inertia parameter, K, in Equation 2 can be expressed as:
a
w
d
VK
µ
δρ
18
2
= (3)
And Stokes
λλ / is defined as the dimensionless droplet
range parameter,
δδλ
λ
Re1847.0Re001483.08388.0
1
++=
Stokes
(4)
where
a
aV
µ
δρδ =Re (5)
4.1.2. Energy Balance Analysis during Impingement
As mentioned, one of the most important variables
during icing testing is the freezing fraction, which
denotes the fraction of water droplets that freezes at the
surface of a body, thus indicating the heat balance at
the ice surface.
Analytical freezing fraction can be found by the
following Equation:
+
Λ=
b
Cn
f
wsp
a
θφ
,
,0 (6)
where, ф and θ , are defined as droplet energy transfer and air energy transfer coefficients respectively:
wsp
stfc
Vtt
,
2
2−−=φ (7)
v
st
www
c
G
ap
stsp
pp
h
h
c
Vtt Λ
−+
−−=
,
2
2θ (8)
The relative heat factor, b, is introduced by Tribus[9] as:
c
wsp
h
cmb
,&
= (9)
The convective heat-transfer coefficient, hc, can be calculated from Equation 11.
a
c
k
dhNu = (10)
The numerical expression of Nu in this code is chosen according to different Re numbers: for Re > 105, as per reference 9:
472.0Re10.1=Nu (11)
and for Re < 105, as per reference 9: 5.040
Re141.
rP.Nu = (12)
Based on the trajectory analysis at stagnation line in the
last section and assuming βo and ρi remain the same while the ice shape changes during the test, the mass
flux can be expressed as:
0β⋅⋅= VLWCm& (13)
Here, it can be seen that LWC can be determined from
the analytical freezing fraction. by introducing a
correlation between freezing fraction and ice thickness
in next section, the LWC can be finally determined.
4.1.3 Ice Accretion Analysis
Based on the previous analysis, a time-span analysis
during ice accretion can be performed. Total ice
thickness at stagnation line, ∆, can be expressed as:
0n
m
i
⋅=∆ρ
τ& (14)
By Substituting Equation 10 into Equation 14 and
introducing an accumulation parameter Ac, Equation 15 is found.
d
VLWCA
i
cρ
τ⋅⋅= (15)
The non-dimensional total ice thickness is defined in
Equation 16.
0,0β
ceAn
d=
∆ (16)
The experimental freezing fraction, η0,e, can be related to the analytical freezing fraction, η0,a, by using a linear curve fitting as it is suggested by Anderson and Tsao[7]:
aenn
,0,0107.10184.0 += (18)
The relationship between total thickness and LWC can
be shown to be monotonic. Thus, an exhaust algorithm
can be implemented to find experimental LWC from
total ice thickness per time. The scheme of the code is
summarized in Figure 6.
4.1.4. Evaluation of LWC Calculation Code
The calculated LWCs based on the total ice thickness
per time are compared with the analytic LWCs
presented in literature for both cylinders [10] and airfoils [7]. The correlation between calculated LWC and results
presented in literature are shown in Figure 7 and Figure
8. It can be concluded that this code calculates
acceptable LWC from total ice thickness per time
(within ±15% error) for nearly 90% of all the cases
presented in literature. Taking into account the
uncertainties related to experimental test data, these
results can be assumed to be useful and reliable to
support the LWC calibration of the facility.
4.1.6. Uncertainty Analysis
From Figure 7, and Figure 8, it is shown that
experiment-derived LWCs generally result in a good
agreement with literature data, presenting correlation
discrepancies of less than 15% for the majority of the
cases compared. Several cases deviate between
calculations and experimental results presented by the
referenced documents. The two main contributions of
this kind of error come from uncertainty of
measurement; and error transmitted between
calculation equations.
Firstly, for most experiments performed at NASA IRT
to which this paper is comparing, the uncertainty
related to LWC calibration at IRT is claimed to be
about ±12%[7] . Also there is ±12% uncertainty in MVD. ]In addition, in most icing tests, hand-tracing
measurement methods are prevalently used, and for
this reason, the thickness record has its own inherent
uncertainty. For similar shapes, it can be shown that
the experimental ice thicknesses can differ by up to
18.8% [7] between the centerline of a test section and
some small distance above centerline. Given the limited
data set, these uncertainties cannot be effectively
resolved.
Figure 6: Scheme of Experimental LWC Calculation Code
Figure 7: Cylinder LWC Calculations from Total Thickness and Correlation with Results Presented in Reference 10
Figure 8: NACA 0012 LWC Calculations Compared to
Experimental Results Presented in Reference 7
Secondly, due to the small size of the ice thickness itself, a
slight error in tracing the ice thickness will then be
transmitted and amplified through equations and
computing loops of the presented code, resulting in a
relatively big error between analytic LWC and thickness-
based or experimental LWC.
It can be seen from presented equations, that the change
in thickness has large effects on the calculated LWC. As
stated before, there is a linear relationship between
thickness, freezing fraction and eventually the LWC.
Small changes in ice thickness (> 0.5 mm) will produce
deviations of LWC of up to 50%.
In the reference [7], although with a different analysis
method and ignoring the difference between analytical
and experimental LWC, Anderson and Tsao also did some
comparisons between analytical freezing fraction and
experimental freezing fraction based on the ice thickness.
In two test groups (test case number 8 – 14 and 32 – 35
with regard to Figure 8 in this article), large discrepancies
between ηa and ηa can be found in these two groups. The greatest one is found in case 3-12-02/1(test case number
32 in Figure 8, with regard to this article), where ηa = 0.275 and ηe = 0.190; i.e., the error can be as high as 45% (error with respect to ηe, from which the experimental LWC is determined), much bigger than ±12% as they
expected for most cases. These errors are also reflected in
the LWC calculation code in Figure 8. The same
phenomena are also found in Figure 7, test case number 9
and 10.
Anderson and Tsao believe this is because there can be
significant uncertainty in the ice thickness values found
from tracings at low freezing fractions. This is true as
already mentioned above. Also, the relatively large
discrepancies between the analytical LWCs and the ones
calculated from the measured thickness can also be
explained by the slope of the relationship between ice
thickness and LWC (Equation 19). The slope, S, of the equation could be very small (≈0.025), greatly affecting
the LWC value for errors introduced in the measurement
of the ice thickness.
rLWCS +⋅=∆ (19)
For example, in some cases, a change in thickness of 0.005
in. results in a change on the calculated LWC of 0.43 g/m3.
For this reason, careful measurement of the ice shapes
must be performed.
In addition, the empirical equations used in this code
(such as relationships between ηe and ηa, or the numerical expression of Nu.) will add error into the calculation as
icing conditions diverge from those used during the
definition of these empirical equations.
With these assumptions of uncertainty, each analytic
LWC is plotted in Figure 7 and Figure 8 with an error bar
of ±15%. Calculated LWC results correlate with values
presented in literature, validating the usage of the code to
determine the LWC in the facility.
4.2 Experimental 4.2 Experimental 4.2 Experimental 4.2 Experimental ResultsResultsResultsResults
A rotor formed by a 1 in. diameter cylinder (50 in. radius)
was spun at different icing conditions. A total of 18 runs
were conducted to calibrate the chamber at -5°C, -10°C,
and -15°C. A 1 in. diameter rotor of 50 in. radius was used.
For each temperature, variations of RPM (500, and 600),
air lines (20, 25, and 30 Psi) and MVD (20, 25, and 30 µm)
were conducted. LWC were calculated for all conditions
along the span of the rotor, as ice thickness. All tests were
run for 3 minutes, with a maximum temperature deviation
of 1°C. Five nozzles located in the outer ring were used
during testing. LWC calibration matrices allow for the
selection of conditions (MVD, airline, temperature) to
trigger a desired experimental LWC during a test. A
photograph of the 1 in. diameter rotor as seen from one of
the monitoring cameras during ice testing is presented in
Figure 9.
Figure 9: Photograph 1 in. Diameter Rotor during Icing Testing
As it can be observed on Figure 10, the ice thickness at the
stagnation point increased as temperature decreased from
-5°C to -15°C. These tests were conducted at ceteris
paribus conditions (25 MVD, 500 RPM, 25 Psi air line, 3
minutes of ice exposure). It is counterintuitive that the ice
thickness would increase as temperature drops, as the
LWC should decrease. This does not happen in the AERTS
facility for all conditions, as temperatures below -10°C are
allowing more droplets to become super-cooled. For this
1 in. Diameter 1 in. Diameter 1 in. Diameter 1 in. Diameter
50 in.50 in.50 in.50 in.
Bottom View Rotor Bottom View Rotor Bottom View Rotor Bottom View Rotor
with Accreted Icewith Accreted Icewith Accreted Icewith Accreted Ice
reason, each temperature condition at the facility must be
calibrated for LWC. A detail of the ice thickness increase
is depicted in Figure 11, where the calculated LWC is
shown.
Figure 10: Variation on Ice Thickness with Rotor Span: -5º, -10º
and -15º Deg. C Static Temperature
RPM increases correspond to ice increases, as it is shown
in Figure 12. This was expected, given the reduced tip
speeds (about 65 m/sec), in where kinetic heating of the
blade is not a major factor affecting ice accretion. Also, as
particle size was increased between 20 and 30 MVD, ice
accretion thickness increased.
Figure 11: Detail of Ice Shapes Obtained at -15°C, -10°C, and -5°C (500 RPM, 25 MVD, 25 PSI Air Line, 3 min. Exposure)
For this reason, the facility is limited to the 30 Psi air line
if 25 MVD are sought and 5 nozzles are in operation. This
airline limitation will vary depending on the MVD
sought, as this is controlled by the pressure differential
between water and air. Lower MVD will allow for an
increase in the airline, while larger MVD will further
decrease the maximum air pressure line to be used. To
allow for the use of higher airlines, a decrease in
operational nozzles could be implemented.
Figure 12: Effect of RPM Increase on Ice Thickness and LWC
One important issue encountered during testing was the
appearance of ice crystals when air lines exceeding 23 Psi
(see Figure 3) were triggered. Due to the small facility
size, super-cooled liquid droplets re-circulate around the
ballistic wall after they pass through the rotor plane if
they do not accrete to the walls or floor of the facility.
Since no particle removal process is used in the facility
(other than ice collection screens located under the rotor
plane) the droplets can freeze into solid crystals when
they re-circulate.
Figure 13: Effect of MVD Increase on Ice Thickness and LWC
Figure 14: Effect of Airline Increase (-10°C). Notice Ice shape Erosion, as Facility is Saturated by Ice Crystals – 30 Psi
25 Psi Air, 25 MVD, 500 RPM25 Psi Air, 25 MVD, 500 RPM25 Psi Air, 25 MVD, 500 RPM25 Psi Air, 25 MVD, 500 RPM 30303030 Psi Air, 25 MVD, 500 RPM Psi Air, 25 MVD, 500 RPM Psi Air, 25 MVD, 500 RPM Psi Air, 25 MVD, 500 RPM
500 RPM, 25 Psi Air, -15 Deg. C
1
1.05
1.1
1.15
1.2
1.25
1.3
1.35
0.5 0.55 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1
Rotor Span (r/R)
Ice T
hic
kn
ess (
in.)
20 MVD
30 MVD
Linear (30 MVD)
Linear (20 MVD)
LWC = 2.4 g/m3
LWC = 2.2 g/m3
25 Air line, 25 MVD, -5 Deg C.
0.8
0.9
1
1.1
1.2
1.3
1.4
0.5 0.6 0.7 0.8 0.9 1
Span Location (r/R)
Ice T
hic
kn
ess (
in.)
500 RPM 600 RPM
LWC 2.4 g/m3
LWC 3 g/m3
500 RPM, 25 Psi Air, 25 MVD, 3 min.
0.8
0.9
1
1.1
1.2
1.3
1.4
0.5 0.6 0.7 0.8 0.9 1
Rotor Span (r/R)
Ice T
hic
kn
ess
(in
.)
-15°C
-10° C
-5°C
-150C
-50C -100C
-150C, LWC, 2.55 g/m3
-100C, LWC 2.35 g/m3
-50C, LWC 2.29 g/m3
Ice shape ErosionIce shape ErosionIce shape ErosionIce shape Erosion
When liquid droplets impact a crystal, the droplet is
immediately crystallized, which creates a chain reaction[5].
Larger numbers of particles in the chamber increase this
effect due to saturation and are generated when using
higher air pressure inputs to the nozzle. To maintain a
desired MVD at higher air pressures, water pressures need
to be increased to maintain the proper pressure
differential, as detailed in Figure 3 and explained in
Reference 1. Since the water flow rate is dependent on
this pressure differential, the mass of water added to the
chamber increases, creating a large number of droplets. If
the droplets crystallize, they erode ice shapes, providing
“spear” shaped ice accretion, as shown in Figure 14. The
maximum pressure differential to avoid crystallization
problems was experimentally determined to be 23 psi.
Similar ice shape erosion is documented by Tsao et al. in
reference 12. During tests conducted at the IRT, there was
evidence indicating that ice erosion occurred for rime ice
shapes obtained at 250 knots. Erosion was identified by
shapes lacking expected small-scale feathers and increased
stagnation ice thickness, as seen in Figure 15[12].
Figure 15: Example of Eroded Rime Ice Tracing at the IRT,
Reference 12
5. AERTS ICE SHAPE C5. AERTS ICE SHAPE C5. AERTS ICE SHAPE C5. AERTS ICE SHAPE CORRELATION TO NASA AORRELATION TO NASA AORRELATION TO NASA AORRELATION TO NASA AND ND ND ND
AIRFORCE EXPERIMENTAAIRFORCE EXPERIMENTAAIRFORCE EXPERIMENTAAIRFORCE EXPERIMENTAL RESULTSL RESULTSL RESULTSL RESULTS
To validate the capability of the facility to reproduce
natural icing conditions, accretion shapes found in
literature for 1 in. diameter cylinders were compared to
experimental results obtained in the AERTS facility.
Currently, the main challenges operating the facility are
due to lack of temperature control and complete LWC
calibration. Radiation cooling systems capable of
maintaining the facility at temperature without
convection fans are not installed yet. The temperature in
the facility can only be maintained for 3.5 minutes with a
deviation of 1°C, since all cooling fans must be shut down
during icing to avoid ice accretion and cloud perturbation.
A second issue is that LWC calibrations matrices are not
fully populated yet, as this is the first attempt to
understand and calibrate the facility. For this reason,
specific conditions identified in literature are cumbersome
to match perfectly in terms of LWC.
Despite these temporary limitations, agreement between
ice shapes presented in literature and experimental results
are observed. Correlations between AERTS experimental
results and experimental results presented in literature
(Reference 6) are shown in Figure 16 and Figure 17.
As it can be seen in Figure 16 and Figure 17, the
stagnation ice thickness correlates with experimental
results obtained at the IRT. The overall shape of the
accreted ice also agrees. Increases in the impingement
limits can be observed, which could imply an increase in
particle size or decrease in temperature during testing.
Figure 16: Test 1 - Correlation of Experimental Results from AERTS (25 MVD, 58 m/sec. -11.7
0C, 5 min., 2 gr/m
3) to Reference
Results (Ref. 6: 23 MVD, 58 m/sec, -11.70C, 5 min., 1.6 gr/m
3)
The discrepancy between impingement limits of the two
experimental results was calculated to be less than 16% of
the total ice thickness for both Tests.
Figure 17: Test 2 - Correlation of Experimental Results from AERTS (27 MVD, 59.2 m/sec. -12
0C, 6.3 min., 1.91 gr/m
3) to
Reference Results (Ref. 6: 27 MVD, 58 m/sec, -12.670C, 6.3 min.,
and 1.3 gr/m3)
AERTS Exp. Reference
AERTS – EXP.
1 in Tube
AERTS – EXP.
27 MVD
490 RPM
0.91 r/R
59.2 m/sec
-120C
AERTS Exp. Reference
25 MVD
510 RPM
0.875 r/R
58 m/sec
-11.70C
Tsao, J., Kreeger, R., Reference 12
Ice shape ErosionIce shape ErosionIce shape ErosionIce shape Erosion
Correlations were also performed against experimental ice
shapes obtained by Ruff et al. at the Air Force Arnold
Engineering Development Center (AEDC) [15]. These tests
were performed at lower LWC values than the minimum
provided by the facility when 5 NASA standard nozzles
are in operation. For this reason, and to reduce the LWC
in the chamber, a controlled system of nozzles was
introduced, such that each nozzle can be operated
individually. This allowed for combinations of 3 and 4
nozzles to be used, thus allowing for a reduction of LWC.
As it can be observed on Figure 18 to Figure 22, ice shape
agreement is obtained between all tests.
Figure 18: Test 3 - Correlation of Experimental Results from
AERTS to Reference Results Presented in Literature (Ref. 11)
The maximum discrepancy between ice thicknesses is
calculated to be 11.8% for test 4 (Figure 19). Tests 1, 2, 5,
and 6 have an ice thickness discrepancy between facilities
of less than 2%. Deviations between targeted temperature
and experimental temperature, in addition to other
experimental uncertainty during tests, might introduce
errors observed between shapes. In general, ice shape
trends agree between experimental results presented in
literature and results obtained at the AERTS facility,
validating its capabilities to reproduce icing conditions.
Figure 19: Test 4 - Correlation of Experimental Results from AERTS to Reference Results Presented in Literature (Ref. 11)
Figure 20: Test 5 - Correlation of Experimental Results from
AERTS to Reference Results Presented in Literature (Ref. 11)
Figure 21: Test 6 - Correlation of Experimental Results from
AERTS to Reference Results Presented in Literature (Ref. 11)
In the first test presented in Figure 16, the experimental
MVD was 25 μm, 2 μm larger than what is presented in
the result presented in literature. In the second test
(Figure 17), the MVD was maintained at exactly 27 μm,
matching the MVD presented in literature results.
Discrepancies in MVD between the experimental tests
compared are not believed to be the main cause of ice
shape deviation.
As mentioned on section 3, the MVD in the facility is
maintained with a feedback control loop that ensures
desired air and water pressure to the NASA standard
nozzles. According to NASA nozzle calibration tables
(Figure 3), the particle size is maintained within 2 μm. For
this reason, MVD deviation is assumed not to be the main
cause presenting the slight differences between both tests.
It is believed that the main reason making the ice shape
correlation deviate is that the temperature in the chamber
can only be maintained for 3.5 minutes, before
temperature increases exceed 1°C. Those tests run for
longer than 3.5 minutes show increased discrepancies
between experimental results. Tests 1 and 2 (Figure 16 and
Figure 17) were run for 5 and 6.3 minutes respectively,
having temperature increases of up to 2°C with respect to
the desired starting temperature. From those tests
MVD = 20 µm
TRef = -15°C
TExp = -15°C
Vel = 60.9 m/sec
LWCref = 1.2 gr/m3
LWCExp = 1.3 gr/m3
r/R = 0.91
AERTS Exp. Reference
MVD = 20 µm
TRef = -15°C
TExp = -13.75°C
Vel = 60.9 m/sec
LWCref = 1.2 gr/m3
LWCExp = 1.2 gr/m3
r/R = 0.91
AERTS Exp. Reference
MVD = 20 µm
TRef = -11.4°C
TExp = -12°C
Vel = 60.9 m/sec
LWCref = 0.9 gr/m3
LWCExp = 0.8 gr/m3
r/R = 0.91
AERTS Exp. Reference
Time: 2.5 Min
Time: 5 Min
Time: 3.75 Min
MVD = 20 µm
TRef = -5°C
TExp = -5.5°C
Vel = 60.9 m/sec
LWCref = 1.2 gr/m3
LWCExp = 1.3 gr/m3
r/R = 0.91
AERTS Exp. Reference
Time: 2.5 Min
compared to AEDC results, tests 4, 5 and 7 were also run
for more than 3.5 minutes, presenting larger shape
deviations than tests 3 and 6 (run for 2.5 minutes).
Figure 22: Test 7 - Correlation of Experimental Results from AERTS to Reference Results Presented in Literature (Ref. 11)
This warming effect is believed to be the main source of
any discrepancy that might be found between the two
experimental results. Other uncertainties would be
introduced due to the fact that the AERTS facility
introduces centrifugal forces not seen in the IRT.
6. CONCLUSION6. CONCLUSION6. CONCLUSION6. CONCLUSION
A new Adverse Environment Rotor Test Stand facility in
were icing clouds surrounding a hovering rotor can be
reproduced, was designed, and built to investigate ice
accretion phenomenon and solutions. The AERTS facility
is capable of reproducing natural icing conditions as long
as saturation of the chamber is prevented. LWC sensitivity
study of the facility for particle sizes between 20 and 30
MVD was accomplished. These efforts demonstrated that
representative LWC values encountered in natural icing
conditions (1.7 to 2.6 g/m3) can be reproduced. From these
initial calibration efforts, the saturation limit of the
chamber was determined. This condition is identified
when pressure differentials in the facility exceeded 23 Psi
for a five nozzle configuration. During LWC sensitivity
tests, it was also noted that the facility is limited to icing
tests of less than 3.5 minutes due to temperature increases
in the chamber. This temperature increases are due to lack
of cooling systems during operation since they must be
shut down to avoid ice accretion to cooling fans. This
issue could be mitigated with additional radiation cooling
lines in the facility that would allow for temperature
control for longer periods of time.
Ice shape correlations between the facility and
experimental results presented in literature by NASA and
Airforce, indicate the capability of the AERTS facility to
reproduce icing shapes obtained in the IRT and the
Arnold Engineering Development Center (AEDC).
Correlations between IRT and AERTS stagnation ice
thicknesses are excellent, with less than 2% discrepancy
between tests. Impingement limits and overall ice mass
was overachieved at the AERTS facility by up to 16%, due
to experimental uncertainties, but it is believed that
increases of temperature during testing beyond the
desired comparison value are the main cause. These errors
were calculated as percentage of thickness at the
stagnation line. The maximum ice thickness errors with
respect to the AEDC was calculated to be 11.8%, but the
majority of tests provided correlations between ice
thickness with discrepancies of less than 2%.
Ice shapes obtained at the AERTS facility agree with
experimental results presented in literature, validating the
capability of the facility to reproduce natural icing
conditions on hovering rotors with zero thrust.
ACKNOWLEDGEMENTS ACKNOWLEDGEMENTS ACKNOWLEDGEMENTS ACKNOWLEDGEMENTS
The authors would like to thank Eric Kreeger and Paul
Tsao of the NASA Glenn Research Center for their
donation of the critical icing nozzles and their advice in
calibrating the AERTS Facility. The authors would also
like to acknowledge Peter Papadakos of the Gyrodyne
Historical Foundation for the donation of the QH-50D
lower rotor head and upper controls. The authors would
also like to thank the US Army for sponsoring this
research by funding a program to investigate the potential
of the facility to generate representative ice shapes, and
the installation of the icing system. This research is
partially funded by the Government under Agreement
No. W911W6-06-2-0008. The U.S. Government is
authorized to reproduce and distribute reprints
notwithstanding any copyright notation thereon. The
views and conclusions contained in this document are
those of the authors and should not be interpreted as
representing the official policies, either expressed or
implied, of the U.S. Government.
REFERENCESREFERENCESREFERENCESREFERENCES
1. Ide, R., Oldenburg, J., “Icing Cloud Calibration of the
NASA Glenn Icing Research Tunnel,” AIAA-2001-0234,
March 2001
2. Al-Khalil, K., Salamon, L., Tenison, G., “Development
of the Cox Icing Research Facility,” 36th Aerospace
Sciences Meeting & Exhibit, AIAA 98-0097, January 12-
15, 1998, Reno, NV
MVD = 20 µm
TRef = -5°C
TExp = -6.7°C
Vel = 60.9 m/sec
LWCref = 1.2 gr/m3
LWCExp = 1.32 gr/m3
r/R = 0.91
AERTS Exp. Reference
Time: 5 Min
3. Herman, E., “Goodrich Icing Wind Tunnel Overview,
Improvements and Capabilities,” AIAA 2006-862, 44th
AIAA Aerospace Sciences Meeting and Exhibit, 9 - 12
January 2006, Reno, Nevada
4. Peterson, A., Oldenburg, J., “Spray Nozzle Investigation
for the Improved Helicopter Icing Spray system
(IHISS),” 28th Aerospace Sciences Meeting, , January 8-
11, 1990, Reno, NV
5. Gent, R.W., Dart, N.P and Candsdale, J.T. Aircraft
Icing. Philosophical Transactions of the Royal Society of
London SeriesA. 2000, Vol. 358
6. Anderson, D., “Rime-, Mixed-, and Glaze-Ice
Evaluations of Three Scaling Laws,” NASA Technical
Memorandum 106461, AIAA-94-07-18, AIAA 32nd
Aerospace Sciences Meeting and Exhibit, Reno, Nevada
January 10-13, 1994.
7. Anderson D., and Tsao, J., “Evaluation and Validation of
the Messinger Freezing Fraction,” NASA/CR—2005-
213852, AIAA–2003–1218, 41st Aerospace Sciences
Meeting and Exhibit, Reno, Nevada, January 6–9, 2003.
8. Messinger, B.L., “Equilibrium Temperature of an
Unheated Icing Surface as a Function of Airspeed,” J.
Aeron. Sci. vol. 20 no. 1, January 1953, pp 29-42.
9. Anderson, David N., “Manual of Scaling Methods”,
NASA CR – 2004-212875
10. Anderson, David N., “Evaluation of Constant-
Weber-Number Scaling for Icing Tests,” AIAA-96-0636
and NASA TM 107141, January 1996.
11. Ruff, G., “Analysis and Verification of the Icing
Scaling Equations,” Air force Technical Report AEDC-
TR-85-30, November 1985
12. Tsao. J., Kreeger, R., “Experimental Evaluation of
Stagnation Point Collection Efficiency of the NACA
0012 Swept Wing Tip,” AIAA 2009-4125, 1st AIAA
Atmospheric and Space Environments Conference, 22 -
25 June 2009, San Antonio, Texas