    Current and voltage transformers

    for

    Low Voltage

    Edition 05 07

  • 8/22/2019 AG akm gerilim trf

    2/12

    Operation manual

    1. Mounting siteInstrument transformers of ALCE shall be mounted in

    accordance with following conditions;

    a) Ambient temperature: -20C~40C (Avarage temp.:

    lower than 35C)

    b) Altitude: lower than 1000 meters.

    c) At the places not exposed to sea - breeze, rain,

    snow and sunlight and kept under 90% humidity.

    d) At places where the exceeded vapor, oil-vapor,

    explosive flammable gas shall not occur.

    e) At places not subject to exceeded dust & foreing

    particles.

    f) At places where exceeded oscillation and impact shall

    not occur.

    2. How to mount

    a) Cable and busbar shall not be directly loaded onto

    CT&PT.

    b) Enough distance shall be taken that primary lead

    wires and busbars do not approach the surface of

    transformers except the connection terminals. Besides,

    please draw your attention for corona and partial

    discharge not to occur.

    c) Secondary lead wires shall be correctly connected to

    the terminals and shall not be approached to the surface

    of transformers.

    d) The connection shall be correctly done as per the

    terminals marks and connection diagram on the name

    plate.

    e) The earthing terminal on primary side of grounding

    type of instrument transformers shall be absolutely

    grounded.

    f) The earthing terminal on secondary side and the

    mounted base (flame) on the body shall be absolutely

    grounded.

    g) Bolts & Nuts for the connection of cables, busbars

    and lead wires shall be firmly fastened.

    3.Maintenance and inspection

    a) Please check instrument transformers once a month

    and pay your attention for noise, over - heat, corrosion

    and exceeded polluting. It is recommended to put the

    thermo-labels on surface of transformers and terminals

    portion.

    b) The operation shall be stopped at least once a year

    and the dust & foreing particles shall be wiped off with

    dry cloth. At that time, please check the appearance,

    the iron-core and looseness of bolts & nuts.

  • 8/22/2019 AG akm gerilim trf

    3/12

    General information

    Current transformers for low voltage

    Location : indoor

    Standard, insulation level : IEC - 60044-1, DIN VDE 0414 edition 01/1994, Um: 0,72 kV

    Frequency : 50 - 60 Hz

    Insulation : thermoplastic casing, insulation class E

    Rated continious thermal current : 1,2 In

    Secondary rated current : 5A or 1A

    Security factor : for class 0.5, at primary current

  • 8/22/2019 AG akm gerilim trf

    4/12

    General information

    Current transformers for low voltage

    -all types are sealed or pivoted from inside, not openable

    Types according to bar dimensions

    120

    mm

    Types Descriptions

    Plug-in current transformers. For bars or round conductor.

    Wound current transformers (primary cable)

    Wound current transformers (primary busbar 25x3 mm x mm)

    ADS 20, A 20, ADS 30, ADB 30

    ADS 40, ADB 40, A 50, A 61,

    ADS 62, ADB 80, ADB 81, A 101,

    ADB 111, ADB 120

    ASS, ASK

    ASB

    Current transformer for differential protection.TDR

    ARS-1, ARS-2

    ARK-1, ARK-2

    Bar or cable type. Protection current transformer for relays.ARD-2, ARD-3

    Types and descriptions

    Primary cable protection current transformer for relays.

    Bar-type cast resin.A125

    Summation current transformers with up to 6 separate independent primary input circuits.TA-2, TA-3, TA-4, TA-5, TA6

    Bar-type. Protection current transformer for relays.

    120

    mm

    Bar widths

    20

    mm

    30

    mm

    40

    mm

    50

    mm

    60

    mm

    80

    mm

    100

    mm

    150

    mm

    ADS 20, A 20

    ADS 30, ADB 30

    ADS 40, ADB 40

    A50

    A61

    ADS 62

    ADB 80

    ADB 81

    A101

    ADS 100, ADB 111

    ADB120

    Types

    ADB120

    A 125

    (*)

    200

    mm

    (*) (*)

    (*) Upon request

  • 8/22/2019 AG akm gerilim trf

    5/12

    Tables and dimensions

    Current transformers for low voltage

    ASS, ADS20, ADS30, ADS40, ADS62, ADS100

    Types ASS ADS20 ADS30 ADS40 ADS62 ADS100

    Primarycurrent

    A

    For secondary 5A or 1A

    0,5 1,0 0,5 1,0 0,5 1,0 0,5 1,0 0,5 1,0 0,5 1,0

    2,55

    10

    15

    20

    25

    30

    40

    50

    60

    75

    80

    100

    125

    150

    200

    250

    300

    400

    500

    600

    750

    800

    1000

    1200

    1250

    1500

    1600

    1800

    2000

    2500

    Cablemm

    Windowmm x mm

    Barmm x mm

    1 2,5 2,5

    2,5 2,55 5

    5 5

    5 5

    () ()

    () ()

    () ()

    () ()

    () ()

    () ()

    - 2,5

    - 2,5

    2,5 5

    3,75 5

    30 30

    30 30

    15 15

    15 15

    30 30

    30 30

    10 10

    10 10

    10 10

    10 10

    2,5 5

    3,75 5

    5 5

    5 5

    5 10

    -

    -

    -

    15

    21 x 5,5

    20 x 5

    23

    31 x10,5

    30 x 10

    28

    41 x 15

    40 x 10

    30

    61 x 31

    2(60 x 10)

    52

    101 x 53

    3(100 x 10)

    Class

    ) Penetration winding current transformers All types are protected against contact.

    Rated power VA

    5 5

    () 2,5

    () 2,5

    10

    10

    10 15

    10 15

    10 15

    30 30

    30 30

    30 30

    15 15

    15 15

    15 15

    30 30

    30 30

    30 30

    5 5

    3000

    3200

    30 30

    30 30

    ASS

    ADS 20

    ADS 30

    ADS 40

    ADS 62

    ADS 100

  • 8/22/2019 AG akm gerilim trf

    6/12

    Tables and dimensions

    Current transformers low voltage

    ASK, ASB, A20, ADB30, ADB40, A50, A61

    ASK

    ASB

    A20

    ADB30

    ADB40

    A50

    A61

    Types ASK ASB A20 ADB30 ADB40 A50

    1

    Primarycurrent

    A

    Rated power VA

    0,5 1,0 0,5 1,0 0,5 1,0 0,5 1,0 0,5 1,0 0,5 1,0

    2,5

    5

    10

    15

    20

    25

    30

    40

    50

    60

    75

    80

    100

    125

    150

    200

    250

    300

    400

    500

    600

    750

    800

    1000

    1200

    A61

    0,5 1,0

    Barmm x mm

    Windowmm x mm

    Cable

    mm

    10 10

    10 10

    15 15

    15 15

    15 15

    15 15

    15 15

    15 15

    15 15

    15 15

    15 15

    15 15

    15 15

    15 15

    15 15

    15 15

    15 15

    5 10

    10 15

    15 15

    15 15

    10 10

    10 15

    15 15

    15 15

    10 10

    15 15

    15 15

    15 15

    15 15

    15 15

    15 15

    15 15

    15 15

    15 15

    15 15

    15 15

    15 15

    15 15

    15 15

    Class

    -

    -

    -

    -

    -

    -

    16

    21 x 11

    20 x 10

    31 x 11

    30 x 10

    41 x 11

    40 x 10

    51 x 11

    50 x 10

    -

    62 x 12

    60 x 10

    26 30 40

    For secondary 5A or 1A

    15 15

    5 5 (*) 5

    (*) 10

    15 15

    15 15

    (*) 10

    10 10

    15 15

    15 15

    15 15

    10 15

    10 10

    5 10

    10 10

    10 15

    1250 15 15

    All types are protected against contact

  • 8/22/2019 AG akm gerilim trf

    7/12

    Tables and dimensions

    Current transformers for low voltage

    ADB80, ADB81, A101, ADB111, ADB120

    ADB111

    ADB120

    * For primary currents >4000 A , only 5A secondary current is possible.All types are protected against contact

    ADB80

    ADB81

    A101

    Types ADB80 ADB81 A101 ADB111 ADB120

    Primarycurrent

    A

    Rated power VA

    0,5 1,0 0,5 1,0 0,5 1,0 0,5 1,0 0,5 1,0

    400

    500

    600

    750

    800

    1000

    1200

    1500

    10 10

    10 15

    15 15

    15 30

    15 30

    30 30

    15 30

    15 30

    15 30

    15 30

    15 30

    30 30 15 30 15 15

    30 45

    Barmm x mm

    Windowmm x mm

    Cablemm

    61

    82 x 32

    2(80 x 10)

    30

    81 x 31

    2(80 x 10)

    30

    102 x 32

    2(100 x 10)

    56

    102 x 58

    3(100 x 10)

    70

    121 x 72

    4(120 x 10)

    Class

    For secondary 5A or 1A *

    15 15

    1600

    1800

    2000

    2500

    3000

    4000

    30 30

    30 30

    30 30

    30 30

    30 30

    30 30

    30 30

    30 30

    30 30

    30 30 30 30 30 30

    30 45

    30 30

    30 30

    5000

    30 30

    30 30

    30 30

    10 15

    10 15

    10 10

    30 30

    30 30

    30 30

    30 30

    10 15

    15 15

    30 30

    30 30

    30 30

    30 30

    30 30

    30 30

    30 30

    30 45

    30 30

    30 30

    30 30

    30 30

    30 30

    30 4530 45

  • 8/22/2019 AG akm gerilim trf

    8/12

    Tables and dimensions

    Current transformers for low voltage

    ARS-1, ARS-2, ARK-1, ARK-2, ARD-2, ARD-3

    ARS-1

    ARS-2

    ARK-1

    ARK-2

    ARD-2

    ARD-3

    Primary bars (for type ARK)

    Primary currentA

    25 - 200 5

    Bar widthmm

    Types ARS - 1 ARS - 2 ARK - 1 ARK - 2

    Primarycurrent

    A

    For secondary 5A or 1A

    5P510P5

    5

    10

    15

    20

    25

    30

    40

    50

    60

    75

    80

    100

    125

    150

    200250

    300

    400

    500

    600

    750

    800

    1000

    1200

    1250

    1500

    1600

    1800

    2000

    2500

    3000

    4000

    ARD - 2 ARD - 3

    Barmm x mm

    Windowmm x mm

    Cable

    mm

    5P1010P10

    5P510P5

    5P1010P10

    5P510P5

    5P1010P10

    5P510P5

    5P1010P10

    5P510P5

    5P1010P10

    5P510P5

    5P1010P10

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    30

    82 - 32

    2(80 x 10)

    30

    102 - 32

    2(100 x 10)

    15

    15

    15

    15

    5

    5

    5

    5

    30

    30

    30

    30

    15

    15

    15

    15

    15 5

    15 5

    15 5

    15 5

    15 5

    15 5

    15 5

    15 5

    15 5

    15 5

    15 515 5

    15 5

    15 5

    30 15

    30 15

    30 15

    30 15

    30 15

    30 15

    30 15

    30 15

    30 15

    30 15

    30 1530 15

    30 15

    30 15

    15 5

    15 5

    15 5

    15 5

    30 15

    30 15

    30 15

    30 15

    30 30

    30 30

    30 30 30 30

    30 30

    30 30

    30 15

    30 15

    30 15

    30 15

    30 15

    30 15

    30 15

    30 15

    45 30

    45 30

    45 30

    Class

    Rated power VA

    All types are protected against contact

  • 8/22/2019 AG akm gerilim trf

    9/12

    Tables and dimensions

    Summation current transformers for low voltage

    TA-2, TA-3, TA-4, TA-5, TA-6

    Important : Summation current transformers are

    designed according to the ratios of the

    main current transformers for summation.

    Type 1

    Type 2

    Primary

    A

    TA-2

    5+5 / 5

    Rated power VA

    Class 0,5

    TA-3

    5+5+5 / 5

    TA-4

    5+5+5+5 / 5

    TA-5

    5+5+5+5+5 / 5

    Class 1

    TA-6

    5+5+5+5+5+5 / 5

    Type1 Type 1 Type 2

    5

    10

    5

    10

    30

    30

    1015

    30

    30

    1530

    1530

    1530

    510

    1530

    1530

    1530

    Connection diagram of summation current transformer ( Type TA-3 )One phase (R) of the three- phase A, B, C groups is shown in the picture

    Type 2

    R S T

    R S T

    Burden for measuring

    K L

    k l

    K L

    k l

    K L

    k l

    AK AL BK BL CK CL

    k l

    R S T

    A

    B

    C

    Example :

    Main currenttransformers :

    Summation currenttranformers :

    Result :

    300A5

    100A1

    100A5

    , ,

    5 + 1 + 5

    5

    A

    300 + 100 + 1005

    : 100 Ratio

    Burden of summation current transformerSummation currenttransformers

    *

    *

    *

    *

    *

    *

    *

    *

    *

    * Main currenttransformers

  • 8/22/2019 AG akm gerilim trf

    10/12

    Table and dimensions

    Current transformer for low voltage

    A125

    A125

    A125

    0,5 1,0

    126 x 72

    4(120 x 10)

    30 45

    60 100

    30 45

    45 60

    Class

    For secondary 5A or 1A

    Rated power VA

    Tip

    Primarycurrent

    A

    5000

    60007500

    8000

    Barmm x mm

    Windowmm x mm

    Indoor current transformerType A125cast resin, for busbar fastening

  • 8/22/2019 AG akm gerilim trf

    11/12

    Table and dimensions

    Voltage transformersfor measuring and protection

    VM, 2VM

    - Insulation level 0,72 kV and 1,2 kV

    - Windings are cast resin.

    For secondary voltage 100 V or 110 V

    Secondary thermal burden current; Isth

    Secondary voltage = 100 V 3 , 110 V 3

    Rated voltage factor = 1.9 (30 sec.)

    Secondary thermal burden current; Isth

    Primary

    voltage

    0.72 kV, Isth=3A*

    100 : 3

    VA

    15

    110 : 3 30

    Class

    0.5

    1

    2

    Class

    1

    1

    1

    Class

    3

    1

    1

    200 : 3 45 - 2 1220 : 3 60 - 2 1380 : 3 Rated output and

    sizes as above.400 : 3500 : 3

    1.2 kV, Isth=2A*

    500 : 3 15600 : 3 30

    1

    -

    1

    1

    1

    1

    750 : 3 45 - 2 11000 : 3 60 - 2 2

    Type

    1

    2

    L1

    40

    50

    L2

    90

    100

    Weight (kg)

    6.6

    8.3

    2VMVM

    * Isth = 1A with earth-fault winding

    Earth-fault winding =100 V

    3,

    110 V

    3

    Primary

    voltage

    0.72 kV, Isth=2A

    100 V

    VA

    30

    110 V

    Class

    0.5

    2

    Class

    1

    1

    Class

    3

    1

    200 V

    220 V 60 - 1 1

    380 V Rated output and

    sizes as above.400 V

    500 V

    1.2 kV, Isth=1A

    500 V 15

    600 V 30

    1

    2

    1

    1

    1

    1

    750 V 45 - 2 1

    1000 V 60 - 2 1

    45 - 1 1