H i g h Q u a l i t y T e c h n i q u e Structure and features of the air handling unit Standard specification Model of the air handling unit and air volume selection table Table of external dimensions Horizontal type Horizontal type - built-in return fan Combination type Combination type - built-in return fan Vertical type Additional dimensions in longitudinal direction when applying optional items Model selection and calculation of pressure drop inside the unit Method and process of the air handling unit model selection Internal static pressure drop Calculation of static pressure drop resulting from coil Calculation of the internal static pressure drop of the air handling unit Calculation of pressure drop inside the cold and hot water coil Outline drawing and dimensions of the coil Outline drawing of the coil Standard table of the face area of the coil Dimension of the coil width Diameter of the tube Performance of the coil and selection method Calculation of the chilled water coil performance Calculation of hot water coil performance Calculation of steam coil performance Chilled water coil performance table Hot water coil performance table Steam coil performance table Selection of the hot water coil Selection of the steam coil Weight table by model Order specification sheet for the heat exchanger (Coil) Cold hot water coil Steam coil Order specification sheet for the air handling unit Air Handling Unit
Transcript
Page 1: AHU Catalouge-with design details

H i g h Q u a l i t y T e c h n i q u e

Structure and features of the air handling unit

Standard specification

Model of the air handling unit and air volume selection table

Table of external dimensionsHorizontal typeHorizontal type - built-in return fanCombination typeCombination type - built-in return fanVertical typeAdditional dimensions in longitudinal direction when applying optional items

Model selection and calculation of pressure drop inside the unit Method and process of the air handling unit model selectionInternal static pressure dropCalculation of static pressure drop resulting from coilCalculation of the internal static pressure drop of the air handling unit Calculation of pressure drop inside the cold and hot water coil

Outline drawing and dimensions of the coilOutline drawing of the coilStandard table of the face area of the coilDimension of the coil widthDiameter of the tube

Performance of the coil and selection methodCalculation of the chilled water coil performance Calculation of hot water coil performance Calculation of steam coil performance Chilled water coil performance tableHot water coil performance tableSteam coil performance tableSelection of the hot water coilSelection of the steam coil

Weight table by model

Order specification sheet for the heat exchanger (Coil)Cold hot water coilSteam coil

Order specification sheet for the air handling unit

Air Handling Unit

Page 2: AHU Catalouge-with design details

Standard specification

Note1. For specifications other than the standard air volume range, contact our sales department.2. Operating conditions

Cooling coil inlet air temperature : 27 DB, 21 WB Cold water inlet temperature: 7 , cold water temperature difference at the inlet and outlet: 5 , 6Row basisSteam coil inlet air temperature: 15 DB, steam pressure: 0.35 kg/ , 2Row basisHot water coil inlet air temperature: 15 , hot water inlet temperature: 60 , hot water temperature difference at the inlet and outlet: 5 , 4Row basis

3. The standard and specification may change without prior notice for improvement of the product.

m3/min

m3/h

m3/min

m3/h

#DS

kW

mmAq

#DS

kW

mmAq

kcal/h

kcal/h

kcal/h

m2

EA

EA

m2

Kg/h

A x

Quantity

Standard air volume

Air volume range

Air-Foil

Motor

Staticpressure

Sirocco

Motor

Dimensions

Face area

Arrangement

610 x 610

305 x 610

Face area

Steam inlet

Steam outlet

Steam

Coolingcapacity

Heatingcapacity

Supp

ly A

ir

Fan

Coil

Filte

rCo

nnec

tion d

iamete

rof

the pi

pes

Retu

rn A

ir

Standard humidity CAPA.

ModelCategory AA0045 AA0065 AA0085 AA0120 AA0160 AA0200 AA0240 AA0300 AA0370 AA0450 AA0500 AA0600

45 65 85 120 160 200 240 300 370 450 500 600

2,700 3,900 5,100 7,200 9,600 12,000 14,400 18,000 22,200 27,000 30,000 36,000

35~49 46~7980~ 101~ 140~ 180~ 200~ 284~ 340~ 411~ 481~ 557~

100 139 199 249 283 339 432 529 556 679

2,100~ 2,760~ 4,800~ 6,060~ 8,400~ 10,800~ 12,000~ 17,040~ 20,400~ 24,660~ 28,860~ 33,420~

2,940 4,740 6,000 8,340 11,940 14,940 16,980 20,340 25,920 31,740 33,360 40,740

1 3/4 2 2 1/2 3 3 3 3 1/2 4 4 4 1/2 5 5 1/2

1.5 2.2 2.2 3.7 3.7 5.5 7.5 7.5 11 15 15 18.5

60 75 75 80 80 80 85 85 85 90 90 90

1 3/4 1 3/4 2 2 2 1/2 2 1/2 3 3 1/2 4 4 4 4 1/2

0.75 1.5 1.5 2.2 2.2 3.7 3.7 5.5 5.5 7.5 7.5 11

35 35 40 40 40 45 45 45 45 45 45 45

19,000 29,000 38,000 54,000 71,000 90,000 105,000 135,000 165,000 200,000 225,000 270,000

27,000 39,000 51,000 73,000 97,000 121,000 145,000 181,000 224,000 272,000 302,000 363,000

22,000 32,000 42,000 60,000 80,000 100,000 120,000 150,000 185,000 225,000 250,000 300,000

18(689) 18(689) 20(765) 22(842) 22(842) 26(994) 30(1146) 30(1146) 34(1299) 38(1451) 40(1527) 46(1756)

x 440 x 1 x 640 x1 x 740 x1 x 940 x1 x 1240 x1 x 1340 x1 x 1440 x1 x 1740 x1 x 1840 x1 x 2140 x1 x 2140 x1 x 2340 x1

0.303 0.441 0.566 0.791 1.044 1.332 1.651 1.995 2.390 3.106 3.269 4.109

1 x 1 1 x 1.5 1 x 1.5 1.5 x 2 1.5 x 2 2 x 2 2 x 2.5 2 x 3 2 x 3.5 2.5 x 4 2.5 x 4 3 x 4

1 1 1 2 2 4 4 6 6 8 8 12

- 1 1 2 2 - 2 - 2 4 4 -

0.37 0.56 0.56 1.12 1.12 1.49 1.86 2.23 2.60 3.72 3.72 4.47

5 10 15 20 30 35 40 55 65 75 85 100

32 x 1 32 x 1 32 x 1 40 x 1 50 x 1 50 x 1 65 x 1 65 x 1 80 x 1 80 x 1 100 x 1 100 x 1

32 x 1 32 x 1 40 x 1 40 x 1 50 x 1 50 x 1 50 x 1 65 x 1 80 x 1 80 x 1 80 x 1 80 x 1

25 x 1 25 x 1 25 x 1 25 x 1 32 x 1 32 x 1 32 x 1 40 x 1 40 x 1 40 x 1 40 x 1 40 x 1

[table 1-1]

08 www.aceind.co.krAACCEE RR && AA

Air Handling Unit

Row x Column

Inlet and outlet of thecold and hot water

PASS(H)x L x

Quantity

Staticpressure

Coldwater

Hotwater

Page 3: AHU Catalouge-with design details

m3/min

m3/h

m3/min

m3/h

#DS

kW

mmAq

#DS

kW

mmAq

kcal/h

kcal/h

kcal/h

m2

EA

EA

m2

Kg/h

A x

Quantity

Standard air volume

Air volume range

Air-Foil

Motor

Staticpressure

Sirocco

Motor

Dimensions

Face area

Arrangement

610 x 610

305 x 610

Face area

Steam inlet

Steam outlet

Steam

Coolingcapacity

Heatingcapacity

Supp

ly A

ir

Fan

Coil

Filte

rCo

nnec

tion d

iamete

rof

the pi

pes

Retu

rn A

ir

Standard humidity CAPA.

Row x Column

Inlet and outlet of thecold and hot water

PASS(H)x L x

Quantity

Staticpressure

Coldwater

Hotwater

700 780 870 950 1,050 1,200 1,300 1,450 1,600 1,750 1,850 2,000

42,000 46,800 52,200 57,000 63,000 72,000 78,000 87,000 96,000 105,000 111,000 120,000

650~ 730~ 845~ 900~ 950~ 1,124~ 1,246~ 1,403~ 1,500~ 1,699~ 1,800~ 1,900~

755 844 982 1,043 1,123 1,245 1,402 1,584 1,698 1,924 2,045 2,105

39,000~ 43,800~ 50,700~ 54,000~ 57,000~ 67,440~ 74,760~ 84,180~ 90,000~ 101,940~ 108,000~ 114,000~

45,300 50,640 58,920 62,580 67,380 74,700 84,120 95,040 101,880 115,440 122,700 129,000

5 1/2 5 1/2 6 7 7 7 8 5 1/2 x 2 5 1/2 x 2 6 x 2 7 x 2 7 x 2

22 30 30 30 30 37 45 30 x 2 30 x 2 37 x 2 37 x 2 37 x 2

90 90 100 100 105 105 110 110 110 110 110 110

5 5 1/2 5 1/2 6 6 6 7 5 x 2 5 x 2 5 1/2 x 2 6 x 2 6 x 2

11 15 15 15 18.5 18.5 22 15 x 2 18.5 x 2 15 x 2 15 x 2 18.5 x 2

45 50 50 50 50 50 50 50 50 50 50 50

310,000 350,000 390,000 425,000 470,000 535,000 580,000 645,000 715,000 780,000 825,000 895,000

423,000 472,000 526,000 575,000 635,000 726,000 786,000 877,000 968,000 1,058,000 1,119,000 1,210,000

350,000 390,000 435,000 475,000 525,000 600,000 645,000 720,000 795,000 870,000 920,000 995,000

24(918) 24(918) 24(918) 26(994) 28(1070) 32(1223) 32(1223) 30(1146) 32(1223) 32(1223) 30(1146) 32(1223)

x 2540 x 2 x 2840 x 2 x 3040 x 2 x 3240 x 2 x 3240 x 2 x 3240 x 2 x 3540 x 2 x 2155 x 4 x 2155 x 4 x 2430 x 4 x 2755 x 4 x 2755 x 4

4.662 5.213 5.580 6.441 6.935 7.922 8.656 9.882 10.539 11.884 12.633 13.473

3 x 4.5 3 x 5 3.5 x 5 3.5 x 5 4 x 5 4 x 5.5 4 x 6 4 x 7 4 x 7.5 4 x 8 4 x 8.5 4 x 9

12 15 15 15 20 20 24 28 28 32 32 36

3 - 5 5 - 4 - - 4 - 4 -

5.02 5.58 6.51 6.51 7.44 8.19 8.93 10.42 11.16 11.91 12.65 13.40

120 130 150 160 180 210 225 251 277 303 320 346

65 x 2 80 x 2 80 x 2 100 x 2 100 x 2 100 x 2 100 x 2 80 x 4 80 x 4 80 x 4 80 x 4 100 x 4

65 x 2 80 x 2 80 x 2 80 x 2 80 x 2 80 x 2 80 x 2 80 x 4 80 x 4 80 x 4 80 x 4 80 x 4

40 x 2 40 x 2 40 x 2 40 x 2 40 x 2 40 x 2 40 x 2 40 x 4 40 x 4 40 x 4 40 x 4 40 x 4

AA0700 AA0780 AA0870 AA0950 AA1050 AA1200 AA1300 AA1450 AA1600 AA1750 AA1850 AA2000

[table 1-2]

Note1. For specifications other than the standard air volume range, contact our sales department.2. Operating conditions

Cooling coil inlet air temperature : 27 DB, 21 WB Cold water inlet temperature: 7 , cold water temperature difference at the inlet and outlet: 5 , 6Row basisSteam coil inlet air temperature: 15 DB, steam pressure: 0.35 kg/ , 2Row basisHot water coil inlet air temperature: 15 , hot water inlet temperature: 60 , hot water temperature difference at the inlet and outlet: 5 , 4Row basis

3. The standard and specification may change without prior notice for improvement of the product.

09 www.aceind.co.krAACCEE RR && AA

ACE Air Conditioning System

Air H

andl

ing

Unit

Ther

mo

- Hy

gros

tat

Heat

Rec

over

ySy

stem

Slim

Typ

e Ai

rHa

ndlin

g Un

itDi

rect

Exp

ansio

n Ty

peAi

r Han

dlin

g Un

itCe

iling

Typ

e Ai

rHa

ndlin

g Un

itFa

nBu

ilt-U

p Un

itFa

n Dr

y Co

il Un

it

ModelCategory

Page 4: AHU Catalouge-with design details

10 www.aceind.co.krAACCEE RR && AA

Air Handling Unit

Air handling unit

Model name display method

Simple model selection table by air volume

4 50 0 XHXA XA

H : Horizontal TypeHR : Horizontal Type, Built-in return fanC : Combination TypeCR : Combination Type, Built-in return fanV : Vertical Type

Type

Process air volume (CMM)

Air handling unit

ACE R&A Co., Ltd.

[table 2-1]

2,000

5,000

8,000

11,000

14,000

17,000

20,000

23,000

26,000

29,000

31,000

34,000

37,000

40,000

AA0045 AA0065 AA0085 AA0120 AA0160 AA0200 AA0240 AA0300 AA0370 AA0450 AA0500 AA0600#1 3/4 #2 #2 1/2 #3 #3 #3 #3 1/2 #4 #4 #4 1/2 #5 #5 1/2#1 3/4 #1 3/4 #2 #2 #2 1/2 #2 1/2 #3 #3 1/2 #4 #4 #4 #4 1/20.303 0.441 0.566 0.791 1.044 1.332 1.651 1.995 2.390 3.106 3.269 4.109

Model

Air v

olum

e(CM

H)

Coil area(m2)

Supply Air Return Air

Fan

Page 5: AHU Catalouge-with design details

11 www.aceind.co.krAACCEE RR && AA

ACE Air Conditioning System

[table 2-2]

32,000

38,000

44,000

50,000

56,000

62,000

68,000

74,000

80,000

86,000

92,000

98,000

104,000

110,000

116,000

122,000

128,000

134,000

140,000

146,000

152,000

158,000

AA0700 AA0780 AA0870 AA0950 AA1050 AA1200 AA1300 AA1450 AA1600 AA1750 AA1850 AA2000#5 1/2 #5 1/2 #6 #7 #7 #7 #8 #5 1/2X2 #5 1/2X2 #6X2 #7X2 #7X2

#5 #5 1/2 #5 1/2 #6 #6 #6 #7 #5X2 #5X2 #5 1/2x2 #6X2 #6X24.662 5.213 5.580 6.441 6.935 7.922 8.656 9.882 10.539 11.884 12.633 13.473

Model

Coil area(m2)

Supply Air Return Air

Fan

Air v

olum

e(CM

H)

Air H

andl

ing

Unit

Ther

mo

- Hy

gros

tat

Heat

Rec

over

ySy

stem

Slim

Typ

e Ai

rHa

ndlin

g Un

itDi

rect

Exp

ansio

n Ty

peAi

r Han

dlin

g Un

itCe

iling

Typ

e Ai

rHa

ndlin

g Un

itFa

nBu

ilt-U

p Un

itFa

n Dr

y Co

il Un

it

Page 6: AHU Catalouge-with design details

12 www.aceind.co.krAACCEE RR && AA

Air Handling Unit

External dimensions chart

[table 3]

Dimension (mm)

Model Size

Note1. The dimensions B above are based on the setup cold water coil + steam coil + humidifier . For models AA1450H

and above, the dimensions are taken with the coil piping on one side.2. When equipped with coil for both cold and hot water, the dimensions B of the model AA0045HR~AA1300HR can

be manufactured in 600mm, and AA1450H and above, in 750mm.3. When coil piping is done for both directions in models AA1450HR and above, dimensions B can be manufactured in 750mm.

AA0045H 500 750 1,100 2,350 940 1,020 850 100 270 385 170 790

AA0065H 600 750 1,150 2,500 1,140 1,120 950 100 315 440 170 990

AA0085H 600 750 1,300 2,650 1,240 1,170 1,000 100 397 550 300 1,090

AA0120H 600 750 1,450 2,800 1,440 1,270 1,100 100 480 660 300 1,290

AA0160H 600 750 1,450 2,800 1,740 1,370 1,200 100 480 660 300 1,590

AA0200H 600 750 1,450 2,800 1,840 1,470 1,300 100 480 660 300 1,690

AA0240H 600 750 1,600 2,950 1,940 1,570 1,400 100 560 745 320 1,790

AA0300H 600 750 1,450 2,800 2,240 1,670 1,500 100 642 865 320 2,090

AA0370H 750 750 1,450 2,950 2,340 1,770 1,600 100 642 865 430 2,190

AA0450H 750 750 1,600 3,100 2,640 1,870 1,700 100 723 970 430 2,490

AA0500H 750 750 1,650 3,150 2,640 1,970 1,800 100 745 1,070 450 2,490

AA0600H 900 750 1,900 3,550 2,840 2,170 2,000 100 886 1,185 560 2,690

AA0700H 900 750 1,900 3,550 3,040 2,270 2,100 100 886 1,185 600 2,890

AA0780H 900 750 1,900 3,550 3,340 2,270 2,100 100 886 1,185 600 3,190

AA0870H 900 750 2,000 3,650 3,540 2,420 2,250 100 967 1,290 620 3,390

AA0950H 1,050 750 2,350 4,150 3,740 2,420 2,250 100 1,130 1,500 620 3,590

AA1050H 1,050 750 2,350 4,150 3,740 2,670 2,500 100 1,130 1,500 700 3,590

AA1200H 1,150 750 2,350 4,250 3,740 2,870 2,700 100 1,130 1,500 830 3,590

AA1300H 1,150 750 2,600 4,500 4,040 2,870 2,700 100 1,293 1,715 830 3,890

AA1450H 1,200 1,200 2,200 4,600 4,840 2,795 2,600 125 886 x 2 1,185 x 2 830 x 2 2,145x 2

AA1600H 1,350 1,200 2,200 4,750 4,840 2,895 2,700 125 886 x 2 1,185 x 2 890 x 2 2,145 x 2

AA1750H 1,350 1,200 2,450 5,000 5,390 2,895 2,700 125 967 x 2 1,290 x 2 890 x 2 2,420 x 2

AA1850H 1,350 1,200 2,800 5,350 6,040 2,795 2,600 125 1,130 x 2 1,500 x 2 770 x 2 2,745 x 2

AA2000H 1,500 1,200 2,800 5,500 6,040 2,895 2,700 125 1,130 x 2 1,500 x 2 830 x 2 2,745 x 2

A B C L W H PH BH F G J K

[figure 1]

Horizontal Type AA H

Page 7: AHU Catalouge-with design details

13 www.aceind.co.krAACCEE RR && AA

ACE Air Conditioning System

[figure 2]

[table 4]

Dimension (mm)

Model Size

Note1. The dimensions B above are based on the setup “cold water coil + steam coil + humidifier”. For models AA1450HR

and above, the dimensions are taken with the piping on one side.2. When equipped with coil for both cold and hot water, the dimensions B of the model AA0045HR~AA1300HR can

be manufactured in 600mm, and AA1450HR and above, in 750mm.3. When coil piping is done for both directions in models AA1450HR and above, dimensions B can be manufactured in 750mm.

AA0045HR 500 750 1,100 1,150 500 4,000 940 1,020 850 100 270 385 170 790

AA0065HR 600 750 1,150 1,150 600 4,250 1,140 1,120 950 100 315 440 170 990

AA0085HR 600 750 1,300 1,250 600 4.500 1,240 1,170 1000 100 397 550 300 1,090

AA0120HR 600 750 1,450 1,250 600 4,650 1,440 1,270 1,100 100 480 660 300 1,290

AA0160HR 600 750 1,450 1,050 600 4,450 1,740 1,370 1,200 100 480 660 300 1,590

AA0200HR 600 750 1,450 1,050 600 4,450 1,840 1,470 1,300 100 480 660 300 1,690

AA0240HR 600 750 1,600 1,200 600 4,750 1,940 1,570 1,400 100 560 745 320 1,790

AA0300HR 600 750 1,450 1,300 600 4,700 2,240 1,670 1,500 100 642 865 320 2,090

AA0370HR 750 750 1,450 1,400 750 5,100 2,340 1,770 1,600 100 642 865 430 2,190

AA0450HR 750 750 1,600 1,400 750 5,250 2,640 1,870 1,700 100 723 970 430 2,490

AA0500HR 750 750 1,650 1,400 750 5,300 2,640 1,970 1,800 100 745 1070 450 2,490

AA0600HR 900 750 1,900 1,500 900 5,950 2,840 2,170 2,000 100 886 1,185 560 2,690

AA0700HR 900 750 1,900 1,600 900 6,050 3,040 2,270 2,100 100 886 1,185 600 2,890

AA0780HR 900 750 1,900 1,800 900 6,250 3,340 2,270 2,100 100 886 1,185 600 3,190

AA0870HR 900 750 2,000 1,800 900 6,350 3,540 2,420 2,250 100 967 1,290 620 3,390

AA0950HR 1,050 750 2,350 2,000 1,050 7,200 3,740 2,420 2,250 100 1,130 1,500 620 3,590

AA1050HR 1,050 750 2,350 2,000 1,050 7,200 3,740 2,670 2,500 100 1,130 1,500 700 3,590

AA1200HR 1,150 750 2,350 2,000 1,150 7,400 3,740 2,870 2,700 100 1,130 1,500 830 3,590

AA1300HR 1,150 750 2,600 2,300 1,150 7,950 4,040 2,870 2,700 100 1,293 1,715 830 3,890

AA1450HR 1,200 1,200 2,200 2,000 1,200 7,800 4,840 2,795 2,600 125 886 x 2 1,185 x 2 830 x 2 2,145 x 2

AA1600HR 1,350 1,200 2,200 2,000 1,350 8,100 4,840 2,895 2,700 125 886 x 2 1,185 x 2 890 x 2 2,145 x 2

AA1750HR 1,350 1,200 2,450 2,300 1,350 8,650 5,390 2,895 2,700 125 967 x 2 1,290 x 2 890 x 2 2,420 x 2

AA1850HR 1,350 1,200 2,800 2,000 1,350 8,700 6,040 2,795 2,600 125 1,130 x 2 1,500 x 2 770 x 2 2,745 x 2

AA2000HR 1,500 1,200 2,800 2,000 1,500 9,000 6,040 2,895 2,700 125 1,130 x 2 1,500 x 2 830 x 2 2,745 x 2

A B C D E L W H PH BH F G J K

AA HRHorizontal type - built-in return fan

Air H

andl

ing

Unit

Ther

mo

- Hy

gros

tat

Heat

Rec

over

ySy

stem

Slim

Typ

e Ai

rHa

ndlin

g Un

itDi

rect

Exp

ansio

n Ty

peAi

r Han

dlin

g Un

itCe

iling

Typ

e Ai

rHa

ndlin

g Un

itFa

nBu

ilt-U

p Un

itFa

n Dr

y Co

il Un

it

Page 8: AHU Catalouge-with design details

14 www.aceind.co.krAACCEE RR && AA

Air Handling Unit

[figure 3]

[table 5]

Dimension (mm)

Model Size

AA0045C 500 1,200 1,700 940 1,970 900 900 100 270 385 170 790

AA0065C 600 1,300 1,900 1,140 2,120 1,000 950 100 315 440 170 990

AA0085C 700 1,400 2,100 1,240 2,320 1,050 1,100 100 397 550 300 1,090

AA0120C 700 1,550 2,250 1,440 2,520 1,150 1,200 100 480 660 300 1,290

AA0160C 700 1,550 2,250 1,740 2,570 1,200 1,200 100 480 660 300 1,590

AA0200C 700 1,550 2,250 1,840 2,720 1,350 1,200 100 480 660 300 1,690

AA0240C 800 1,700 2,500 1,940 3,020 1,450 1,400 100 560 745 320 1,790

AA0300C 800 1,500 2,300 2,240 3,170 1,500 1,500 100 642 865 320 2,090

AA0370C 900 1,500 2,400 2,340 3,320 1,650 1,500 100 642 865 430 2,190

AA0450C 900 1,650 2,550 2,640 3,570 1,750 1,650 100 723 970 430 2,490

AA0500C 900 1,700 2,600 2,640 3,720 1,800 1,750 100 745 1,070 450 2,490

AA0600C 1000 1,900 2,900 2,840 4,220 2,050 2,000 100 886 1,185 560 2,690

AA0700C 1,050 1,900 2,950 3,040 4,320 2,150 2,000 100 886 1,185 600 2,890

AA0780C 1,050 1,900 2,950 3,340 4,320 2,150 2,000 100 886 1,185 600 3,190

AA0870C 1,050 2,050 3,100 3,540 4,570 2,300 2,100 100 967 1,290 620 3,390

AA0950C 1,050 2,400 3,450 3,740 4,870 2,300 2,400 100 1,130 1,500 620 3,590

AA1050C 1,150 2,400 3,550 3,740 5,170 2,600 2,400 100 1,130 1,500 700 3,590

AA1200C 1,300 2,400 3,700 3,740 5,320 2,750 2,400 100 1,130 1,500 830 3,590

AA1300C 1,300 2,700 4,000 4,040 5,620 2,750 2,700 100 1,293 1,715 830 3,890

AA1450C 1,300 2,300 3,600 4,840 4,795 2,600 2,000 125 886 x 2 1,185 x 2 830 x 2 2,145 x 2

A C L W H PH1 PH2 BH F G J K

AA CCombination Type

Page 9: AHU Catalouge-with design details

15 www.aceind.co.krAACCEE RR && AA

ACE Air Conditioning System

[figure 4]

[table 6]

Dimension (mm)

Model Size

AA0045CR 500 1,150 1,200 2,850 940 2,110 970 1,040 900 900 100 270 385 170 790

AA0065CR 600 1,150 1,300 3,050 1,140 2,210 1,070 1,040 1,000 900 100 315 440 170 990

AA0085CR 700 1,250 1,400 3,350 1,240 2,210 1,070 1,040 1,000 900 100 397 550 300 1,090

AA0120CR 700 1,250 1,550 3,500 1,440 2,310 1,170 1,040 1,100 900 100 480 660 300 1,290

AA0160CR 700 1,050 1,550 3,300 1,740 2,560 1,270 1,190 1,200 1,050 100 480 660 300 1,590

AA0200CR 700 1,050 1,550 3,300 1,840 2,660 1,370 1,190 1,300 1,050 100 480 660 300 1,690

AA0240CR 800 1,200 1,700 3,700 1,940 2,910 1,470 1,340 1,400 1,200 100 560 745 320 1,790

AA0300CR 800 1,300 1,500 3,600 2,240 3,110 1,570 1,440 1,500 1,300 100 642 865 320 2,090

AA0370CR 900 1,400 1,500 3,800 2,340 3,210 1,670 1,440 1,600 1,300 100 642 865 430 2,190

AA0450CR 900 1,400 1,650 3,950 2,640 3,510 1,770 1,640 1,700 1,500 100 723 970 430 2,490

AA0500CR 900 1,400 1,700 4,000 2,640 3,610 1,870 1,640 1,800 1,500 100 745 1,070 450 2,490

AA0600CR 1,000 1,500 1,900 4,400 2,840 3,910 2,070 1,740 2,000 1,600 100 886 1,185 560 2,690

AA0700CR 1,050 1,600 1,900 4,550 3,040 4,110 2,170 1,840 2,100 1,700 100 886 1,185 600 2,890

AA0780CR 1,050 1,800 1,900 4,750 3,340 4,310 2,170 2,040 2,100 1,900 100 886 1,185 600 3,190

AA0870CR 1,050 1,800 2,050 4,900 3,540 4,460 2,320 2,040 2,250 1,900 100 967 1,290 620 3,390

AA0950CR 1,050 2,000 2,400 5,450 3,740 4,610 2,320 2,190 2,250 2,050 100 1,130 1,500 620 3,590

AA1050CR 1,150 2,000 2,400 5,550 3,740 4,860 2,570 2,190 2,500 2,050 100 1,130 1,500 700 3,590

AA1200CR 1,300 2,000 2,400 5,700 3,740 5,060 2,770 2,190 2,700 2,050 100 1,130 1,500 830 3,590

AA1300CR 1,300 2,300 2,700 6,300 4,040 5,360 2,770 2,490 2,700 2,350 100 1,293 1,715 830 3,890

AA1450CR 1,300 2,000 2,300 5,600 4,840 4,585 2,670 1,790 2,600 1,650 125 886x2 1,185x2 830x2 2,145x2

A B C L W H H1 H2 PH1 PH2 BH F G J K

Combination type - built-in return fan AA CR

Air H

andl

ing

Unit

Ther

mo

- Hy

gros

tat

Heat

Rec

over

ySy

stem

Slim

Typ

e Ai

rHa

ndlin

g Un

itDi

rect

Exp

ansio

n Ty

peAi

r Han

dlin

g Un

itCe

iling

Typ

e Ai

rHa

ndlin

g Un

itFa

nBu

ilt-U

p Un

itFa

n Dr

y Co

il Un

it

Page 10: AHU Catalouge-with design details

16 www.aceind.co.krAACCEE RR && AA

Air Handling Unit

[figure 5]

[table 7]

Dimension (mm)

Model Size

AA0045V 1,200 940 2,520 700 750 900 100 270 385 170 790

AA0065V 1,300 1,140 2,570 700 750 950 100 315 440 170 990

AA0085V 1,400 1,240 2,720 700 750 1,100 100 397 550 300 1,090

AA0120V 1,550 1,440 2,820 700 750 1,200 100 480 660 300 1,290

AA0160V 1,550 1,740 2,820 700 750 1,200 100 480 660 300 1,590

AA0200V 1,550 1,840 2,870 750 750 1,200 100 480 660 300 1,690

AA0240V 1,700 1,940 3,070 750 750 1,400 100 560 745 320 1,790

AA0300V 1,700 2,240 3,170 750 750 1,500 100 642 865 320 2,090

AA0370V 1,850 2,340 3,420 1,000 750 1,500 100 642 865 430 2,190

AA0450V 1,950 2,640 3,570 1,000 750 1,650 100 723 970 430 2,490

AA0500V 2,000 2,640 3,670 1,000 750 1,750 100 745 1,070 450 2,490

AA0600V 2,200 2,840 3,920 1,000 750 2,000 100 886 1,185 560 2,690

AA0700V 2,300 3,040 3,920 1,000 750 2,000 100 886 1,185 600 2,890

AA0780V 2,300 3,340 3,920 1,000 750 2,000 100 886 1,185 600 3,190

L W H PH1 PH2 PH3 BH F G J K

Note1. The dimensions PH2 above are based on the setup cold water coil + steam coil + humidifier .2. When equipped with coil for both cold and hot water, the dimensions PH2 can be manufactured in 600mm

with humidifier, and 500mm without humidifier.

Vertical Type AA V

Page 11: AHU Catalouge-with design details

17 www.aceind.co.krAACCEE RR && AA

ACE Air Conditioning System

Charged corpuscle neutralization device Self cleaning electric dust collector

Standard L115 450

22 650

30 850

32 900

36 1,000

Auto Filter

(mm)

Roll Type Cell Type Bag TypeTwo-stage

electrostatic type

Air filter assembly method-Roll Filter + Service Door(430mm) + Medium Filter(Cell or Bag Type)-Pre + Medium Filter( Mini Pleat 3 or Cell or Bag Type) + Service Door(430mm) +Charged corpuscle neutralization device

/C : Cooling Coil H/C : Heating Coil S/D : Service Door1. Additional dimensions are on the basis of C/C-6Rows and H/C-2Rows when the above coil option is added.2. 33mm will be added for increment of each row of coil.

Air f

ilter

Hum

idifi

erCo

il

Elim

inat

or

Medium Filter L2Mini Pleat 3 800

Cell Type 12 1,000

Application typeSteam GridSteam InjectionElectrode typeWater evaporationtype

H/C C/C C/C+H/C H/C+C/C+H/C C/C+S/D+H/C H/C+S/D+C/C+H/C

Application typeWater Spray + Eliminator

Additional dimensions in longitudinal direction when applying optional items

Air H

andl

ing

Unit

Ther

mo

- Hy

gros

tat

Heat

Rec

over

ySy

stem

Slim

Typ

e Ai

rHa

ndlin

g Un

itDi

rect

Exp

ansio

n Ty

peAi

r Han

dlin

g Un

itCe

iling

Typ

e Ai

rHa

ndlin

g Un

itFa

nBu

ilt-U

p Un

itFa

n Dr

y Co

il Un

it

Page 12: AHU Catalouge-with design details

18 www.aceind.co.krAACCEE RR && AA

Air Handling Unit

Model selection and calculation of the pressure drop inside the unit

Method and process of the air handling unit model selection

Page 13: AHU Catalouge-with design details

19 www.aceind.co.krAACCEE RR && AA

ACE Air Conditioning System

Static pressure drop = coil + air filter + eliminator +mixing box, casing + damper + other additional components

H = H1 + H2 + H3 + H4 + H5 + H6

H Internal static pressure drop

H1 Static pressure drop caused by the coil - [table8] [table9] [table15]

H2 Static pressure drop caused by the air filter - [table12]

H3 Static pressure drop caused by the eliminator [If eliminator is installed] - [table13]

H4 Static pressure drop caused by the mixing box and casing - [table14]

H5 Static pressure drop caused by the damper - [table 16]

H6 Addition of other components

Number offins(per inch) 14 12 10 8 6 4 2

1.81 2.12 2.54 3.18 4.23 6.35 12.7

1.95 1.60 1.35 1.00 0.72 0.43 0.26

Fin pitch(mm)

Correctionfactor

[table 8] [table 9]

[table 11][table 10]

Internal static pressure drop

Static pressure drop curve caused by the chilled water coil

Static pressure drop correction factor by fin pitch

Static pressure drop correction factor for coil fin pitch

Static pressure drop correction factor by temperature

Temperature correction factor forpressure drop at the air side

Static pressure drop curve causedby the hot water(steam) coil

Air H

andl

ing

Unit

Ther

mo

- Hy

gros

tat

Heat

Rec

over

ySy

stem

Slim

Typ

e Ai

rHa

ndlin

g Un

itDi

rect

Exp

ansio

n Ty

peAi

r Han

dlin

g Un

itCe

iling

Typ

e Ai

rHa

ndlin

g Un

itFa

nBu

ilt-U

p Un

itFa

n Dr

y Co

il Un

it

Page 14: AHU Catalouge-with design details

20 www.aceind.co.krAACCEE RR && AA

Air Handling Unit

Static pressure drop curve by air filter Static pressure drop curve by mixing box & casing

[table12]

[table13]

Note 1. Air pressure drop by the air filter may be different by the actual media used.2. Additional calculation for the pressure drop is required depending on the category, type and specification of the air filter.

[table14]

[table15]

[table 16]

Static pressure drop caused by the air filter Static pressure drop caused by the mixing box and casing

Static pressure drop curve by air damperStatic pressure drop caused by the damper

Static pressure drop curve by eliminatorStatic pressure drop caused by the eliminator

Static pressure drop curve by Vertical type coil

Static pressure drop caused by the coil in case of vertical air handling unit

Page 15: AHU Catalouge-with design details

21 www.aceind.co.krAACCEE RR && AA

ACE Air Conditioning System

Sample specification - chilled water coil- Coil : 8 Row, 10Fin/Inch - Coil inlet air temperature(DB1) : 28- Pass-through wind speed : 2.5m/s - Coil outlet air temperature(DB2) : 18

Sample specification- Chilled water coil: 8 Row, 10Fin/Inch - Air Filter: Glass Fiber material- Pass-through wind speed: 2.5m/s - Eliminator: Installed

Basic specification1. Model: AA0300H2. Cooling caloric value : 135,000 kcal/h3. Specification of coil : 6Row 30 Pass 1,740mm4. Inlet and outlet temperature difference : 5

When cold and hot water coil is used, the pressure drop on thewater side is calculated from the flow rate per tube Pass bundleand the length (effective length) of tube.

Note Recommended water speed inside the coil is 0.5~2.3m/s.

Air side static pressure drop

Fin pitch static pressuredrop correction factor

Through the above process 1,2,3

Correction factor on theaverage dry bulb airtemperature at the coil inletand outlet

Using the static pressure drop curve at the air side of the chilled water coil,intersection between pass-through wind speed(2.5m/s) and number of coilrows (8Row) is taken

Air side static pressure drop x fin pitch static pressure drop correction factorx correction factor on the average dry bulb temperature of the coil inlet andoutlet air =15.8mmAq x 1.35 x1.02

Check on the temperature correction factor for the air side pressure drop

= 23Coil inlet air temperature + Coil outlet air temperature

15.8 mmAq table 8

table 10

table 11

1.35

1.02

21.76 mmAq

1

2

3

4

Check on the fin pitch static pressure drop correction factor table

Air filter static pressuredrop

1

2

3

4

450 /min

15 /min

0.76mAq

4.56 mAq

Measured pressure drop atthe chilled water coil

Through the above process1,2,3

Flow rate

As the length of the tube is1,740mm, check the curve onthe right

Total pressure drop = 0.76 6Row

450 30 (Single Circuit)

135,000 (60 5)Flow rate pertube

Water pressure drop

Through theprocess 1,2,3

Eliminator, mixing box,casing static pressure drop

From each curve, read the value at the pass-through windspeed 2.5m/s

According to the above calculation of static pressure dropcaused by the coil

Summation of item 1,2,37.6 3.7 0.5 2.8 21.76

7.6 mmAq

21.76 mmAq

36.36 mmAq

table 12

table 13table 14

Eliminator-3.7mmAqMixing box-0.5mmAq

Casing-2.8mmAq

1

2

3

4

[table 17]

Calculation of static pressure drop caused by the coil

Calculation of internal static pressure drop of the air handling unit

Calculation of pressure drop inside theCold and hot water coil

Sequence Item Method Result Reference

table

Sequence Item

Sequence Item Calculation formula

and method Values

Method Result Referencetable

Air H

andl

ing

Unit

Ther

mo

- Hy

gros

tat

Heat

Rec

over

ySy

stem

Slim

Typ

e Ai

rHa

ndlin

g Un

itDi

rect

Exp

ansio

n Ty

peAi

r Han

dlin

g Un

itCe

iling

Typ

e Ai

rHa

ndlin

g Un

itFa

nBu

ilt-U

p Un

itFa

n Dr

y Co

il Un

it

Average air temperature at the inlet and outlet =

Page 16: AHU Catalouge-with design details

22 www.aceind.co.krAACCEE RR && AA

Air Handling Unit

Outline drawing and dimensions of the coil

10 384

12 461

14 537

16 613

18 689

20 765

22 842

24 918

26 994

28 1070

30 1146

32 1223

34 1299

36 1375

38 1451

40 1527

42 1604

44 1680

46 1756

0.15 0.23 0.31 0.38 0.46 0.54 0.61 0.69 0.77 0.84 0.92 1.00 1.08 1.15 1.23 1.31 1.38

0.18 0.28 0.37 0.46 0.55 0.65 0.74 0.83 0.92 1.01 1.11 1.20 1.29 1.38 1.48 1.57 1.66

0.21 0.32 0.43 0.54 0.64 0.75 0.86 0.97 1.07 1.18 1.29 1.40 1.50 1.61 1.72 1.83 1.93

0.25 0.37 0.49 0.61 0.74 0.86 0.98 1.10 1.23 1.35 1.47 1.59 1.72 1.84 1.96 2.08 2.21

0.28 0.41 0.55 0.69 0.83 0.96 1.10 1.24 1.38 1.52 1.65 1.79 1.93 2.07 2.20 2.34 2.48

0.31 0.46 0.61 0.77 0.92 1.07 1.22 1.38 1.53 1.68 1.84 1.99 2.14 2.30 2.45 2.60 2.75

0.34 0.51 0.67 0.84 1.01 1.18 1.35 1.52 1.68 1.85 2.02 2.19 2.36 2.53 2.69 2.86 3.03

0.37 0.55 0.73 0.92 1.10 1.29 1.47 1.65 1.84 2.02 2.20 2.39 2.57 2.75 2.94 3.12 3.30

0.40 0.60 0.80 0.99 1.19 1.39 1.59 1.79 1.99 2.19 2.39 2.58 2.78 2.98 3.18 3.38 3.58

0.43 0.64 0.86 1.07 1.28 1.50 1.71 1.93 2.14 2.35 2.57 2.78 3.00 3.21 3.42 3.64 3.85

0.46 0.69 0.92 1.15 1.38 1.60 1.83 2.06 2.29 2.52 2.75 2.98 3.21 3.44 3.67 3.90 4.13

0.49 0.73 0.98 1.22 1.47 1.71 1.96 2.20 2.45 2.69 2.94 3.18 3.42 3.67 3.91 4.16 4.40

0.52 0.78 1.04 1.30 1.56 1.82 2.08 2.34 2.60 2.86 3.12 3.38 3.64 3.90 4.16 4.42 4.68

0.55 0.83 1.10 1.38 1.65 1.93 2.20 2.48 2.75 3.03 3.30 3.58 3.85 4.13 4.40 4.68 4.95

0.58 0.87 1.16 1.45 1.74 2.03 2.32 2.61 2.90 3.19 3.48 3.77 4.06 4.35 4.64 4.93 5.22

0.61 0.92 1.22 1.53 1.83 2.14 2.44 2.75 3.05 3.36 3.66 3.97 4.28 4.58 4.89 5.19 5.50

0.64 0.96 1.28 1.60 1.92 2.25 2.57 2.89 3.21 3.53 3.85 4.17 4.49 4.81 5.13 5.45 5.77

0.67 1.01 1.34 1.68 2.02 2.35 2.69 3.02 3.36 3.70 4.03 4.37 4.70 5.04 5.38 5.71 6.05

0.70 1.05 1.40 1.76 2.11 2.46 2.81 3.16 3.51 3.86 4.21 4.57 4.92 5.27 5.62 5.97 6.32

400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200 3400 3600Pass H(mm)

Height

1-2 125

3-4 192

5-6 258

7-8 324

9-10 390

11-12 456

0 ~ 150 32A

151 ~ 203 40A

204 ~ 329 50A

330 ~ 542 65A

543 ~ 767 80A

768 ~ 1306 100A

1. Cu-Tube : OD5 / 8 (15.88mm)2. Fin: 4~12 sheets / Inch

[table 18]

[table 19]

[table 20]

L(mm)

[figure 6]

Outline drawing of the coil

Standard face area table for the coil (Coil Face Area: m2) Coil width dimension

Tube diameter

Number of rows C(mm)

Flow rate( /min) Tube diameter

Page 17: AHU Catalouge-with design details

23 www.aceind.co.krAACCEE RR && AA

ACE Air Conditioning System

Operating condition1. Chilled water inlet temperature : 7 4. Coil specification : 6 Row (8Fins/Inch)

2. Chilled water inlet and outlet temperature difference : 5 5. Air volume : 45 CMM

3. Chilled water coil inlet air temperature : 27 DB, 21 WB 6. Coil pass-through wind speed : 2.5m/s

The following coil performance tables (table25, table26, table27) are based on the standard operation condition, which need to be corrected depending on the conditions of use.

In case the operation condition is the same with the standard operation condition: Refer to the chilled water coil performance table, hot water coil performance table and the steam coil performance tableIn case the operation condition is different from the standard operation condition: coil performance= coil performance table (table25, table26, table27) X heat transfer correction factor of the fin (table21) X coil performance correction factor (table22, table23, table24)

14

1.81

1.35

1

2

3

4

12

2.12

1.25

10

2.54

1.12

8

3.18

1.0

7

3.63

0.92

6

4.23

0.81

Number of fins / inch

Fin pitch(mm)

Correction factor[table 21]

[table 22]

Performance of the coil and selection method

Note In case the coil pass-through wind speed is 2.3m/s, interpolate with the values of 2.0m/s and 2.5m/s.

Performance of the coil

Heat transfer correction factor of the fin

Chilled water coil performance correction factor

Calculation of the chilled water coil performance

Sequence Item Method Result Reference table

19,000Kcal/h

1.0

1.0

19,000Kcal/h

Table 25

Table 21

Table 22

Chilled water coil performance

Heat transfer correctionfactor of the finChilled water coil performancecorrection factor

According to the items 1,2,3

Check on the chilled water coil performance table

Check on the heat transfer correction factor table of the fin

Check on the chilled water coil performance correction factor chart Chilled water coil performance table X heat transfer correctionfactor of the fin X coil performance correction factor

Air H

andl

ing

Unit

Ther

mo

- Hy

gros

tat

Heat

Rec

over

ySy

stem

Slim

Typ

e Ai

rHa

ndlin

g Un

itDi

rect

Exp

ansio

n Ty

peAi

r Han

dlin

g Un

itCe

iling

Typ

e Ai

rHa

ndlin

g Un

itFa

nBu

ilt-U

p Un

itFa

n Dr

y Co

il Un

it

Page 18: AHU Catalouge-with design details

Operating condition1. Steam coil inlet air temperature : 11 DB2. Steam pressure : 1Kg/cm2

3. Coil specification : 2 Row (8Fins/Inch)4. Air volume : 65CMM5. Coil pass-through wind speed : 2.5m/s

Operating condition1. Hot water inlet temperature: 702. Hot water inlet and outlet temperature difference : 53. Hot water coil inlet air temperature : 15 DB4. Coil specification : 4 Row (8Fins/Inch)5. Air volume : 65CMM6. Coil pass-through wind speed : 2.5m/s

24 www.aceind.co.krAACCEE RR && AA

Air Handling Unit

[[table 23]

[[table 24]

Note In case the coil pass-through wind speed is 2.3m/s, interpolate with the values of 2.0m/s and 2.5m/s.

Note In case the coil pass-through wind speed is 2.3m/s, interpolate with thevalues of 2.0m/s and 2.5m/s.

Hot water coil performance correction factor

Steam coil performance correction factor

Calculation of the hot water coil performance

Calculation of the steam coil performance

Sequence Item Method Result

Reference table

1

2

3

4

Hot water coil performance

Heat transfercorrection factorof the fin

Hot water coilperformancecorrection factor

According to theitems 1,2,3

Hot water coil performance table XHeat transfer correction factor of the fin XCoil performance correction factor X

Check on the hot water coilperformance correctionfactor chart

Check on the heat transfercorrection factor table ofthe fin

Check on the hot water coilperformance table

table 26

table 21

table 23

32,000Kcal/h

1.0

1.23

39,400Kcal/h

Sequence Item Method Result

Reference table

1

2

3

4

Steam coilperformance

Heat transfercorrection factor of the fin

Steam coilperformancecorrection factor

According to theitems 1,2,3

Steam coil performance table X Heat transfer correction factor of the fin XCoil performance correction factor

Check on the performancecorrection factor Chart ofthe steam coil

Check on the heat transfercorrection factor Table ofthe fin

Check on the steam coilperformance table

Table 27

Table 21

Table 24

39,000Kcal/h

1.0

1.179

45,981Kcal/h

Page 19: AHU Catalouge-with design details

25 www.aceind.co.krAACCEE RR && AA

ACE Air Conditioning System

Performance table of cold water coil

5

7

Inletwater

temperature

Model

AA0045AA0065AA0085AA0120AA0160AA0200AA0240AA0300AA0370AA0450AA0500AA0600AA0700AA0780AA0870AA0950AA1050AA1200AA1300AA1450AA1600AA1750AA1850AA2000AA0045AA0065AA0085AA0120AA0160AA0200AA0240AA0300AA0370AA0450AA0500AA0600AA0700AA0780AA0870AA0950AA1050AA1200AA1300AA1450AA1600AA1750AA1850AA2000

4 ROW 6 ROW 8 ROW 4 ROW 6 ROW 8 ROW 4 ROW 6 ROW 8 ROW13.7 18.2 21.7 16.0 21.7 26.2 18.2 25.1 29.6 20.5 27.4 33.1 23.9 33.1 38.8 27.4 37.6 44.5 27.4 36.5 43.3 31.9 43.3 51.3 36.5 49.0 58.1 37.6 51.3 61.6 44.5 61.6 73.0 50.2 70.7 83.2 50.2 68.4 80.9 59.3 80.9 95.8 67.3 92.3 109.4 62.7 86.6 102.6 75.2 102.6 122.0 85.5 117.4 139.1 74.1 100.3 118.6 87.8 119.7 141.4 100.3 136.8 160.7 94.6 128.8 152.8 112.9 153.9 182.4 128.8 175.6 207.5

115.1 158.5 188.1 136.8 188.1 223.4 156.2 214.3 255.4 140.2 191.5 226.9 166.4 228.0 270.2 190.4 259.9 307.8157.3 215.5 255.4 187.0 256.5 304.4 213.2 293.0 347.7 188.1 258.8 306.7 224.6 307.8 364.8 256.5 351.1 416.1 216.6 296.4 351.1 257.6 353.4 418.4 294.1 403.6 477.7 245.1 335.2 397.9 291.8 399.0 473.1 332.9 454.9 539.2 272.5 373.9 442.3 324.9 444.6 526.7 370.5 507.3 600.8 296.4 407.0 482.2 353.4 484.5 574.6 403.6 552.9 655.5 328.3 450.3 533.5 391.0 535.8 635.0 445.7 611.0 723.9 373.9 511.9 607.6 445.7 609.9 722.8 508.4 695.4 824.2 404.7 555.2 657.8 482.2 661.2 783.2 549.5 753.5 892.6 451.4 617.9 731.9 536.9 735.3 871.0 612.2 839.0 992.9 499.3 685.1 810.5 595.1 815.1 965.6 678.3 929.1 1,101.2 544.9 746.7 884.6 648.7 889.2 1,053.4 739.9 1,014.6 1,201.6 576.8 790.0 937.1 686.3 940.5 1,114.9 783.2 1,072.7 1,271.1 625.9 857.3 1,015.7 744.4 1,020.3 1,209.5 849.3 1,163.9 1,379.4

12.0 16.0 19.0 14.0 19.0 23.0 16.0 22.0 26.0 18.0 24.0 29.0 21.0 29.0 34.0 24.0 33.0 39.0 24.0 32.0 38.0 28.0 38.0 45.0 32.0 43.0 51.0 33.0 45.0 54.0 39.0 54.0 64.0 44.0 62.0 73.0 44.0 60.0 71.0 52.0 71.0 84.0 59.0 81.0 96.0 55.0 76.0 90.0 66.0 90.0 107.0 75.0 103.0 122.0 65.0 88.0 104.0 77.0 105.0 124.0 88.0 120.0 141.0 83.0 113.0 134.0 99.0 135.0 160.0 113.0 154.0 182.0

101.0 139.0 165.0 120.0 165.0 196.0 137.0 188.0 224.0 123.0 168.0 199.0 146.0 200.0 237.0 167.0 228.0 270.0 138.0 189.0 224.0 164.0 225.0 267.0 187.0 257.0 305.0 165.0 227.0 269.0 197.0 270.0 320.0 225.0 308.0 365.0 190.0 260.0 308.0 226.0 310.0 367.0 258.0 354.0 419.0 215.0 294.0 349.0 256.0 350.0 415.0 292.0 399.0 473.0 239.0 328.0 388.0 285.0 390.0 462.0 325.0 445.0 527.0 260.0 357.0 423.0 310.0 425.0 504.0 354.0 485.0 575.0 288.0 395.0 468.0 343.0 470.0 557.0 391.0 536.0 635.0 328.0 449.0 533.0 391.0 535.0 634.0 446.0 610.0 723.0 355.0 487.0 577.0 423.0 580.0 687.0 482.0 661.0 783.0 396.0 542.0 642.0 471.0 645.0 764.0 537.0 736.0 871.0 438.0 601.0 711.0 522.0 715.0 847.0 595.0 815.0 966.0 478.0 655.0 776.0 569.0 780.0 924.0 649.0 890.0 1,054.0 506.0 693.0 822.0 602.0 825.0 978.0 687.0 941.0 1,115.0 549.0 752.0 891.0 653.0 895.0 1,061.0 745.0 1,021.0 1,210.0

Cooling performance ( 1,000 kcal/h)

Air velocity through the coil Va = 2.0m/s Air velocity through the coil Va = 2.5m/s Air velocity through the coil Va = 3.0m/s

Note1. Operating condition - Air temperature at the inlet of the coil: 27 DB, 21 WB

- Cold water temperature difference at the inlet and outlet: 52. Coil specification : OD. 5/8 Copper Tube + Al Plate Fin 8Fins/lnch 3. Same heat transfer area condition

[table 25]

Air H

andl

ing

Unit

Ther

mo

- Hy

gros

tat

Heat

Rec

over

ySy

stem

Slim

Typ

e Ai

rHa

ndlin

g Un

itDi

rect

Exp

ansio

n Ty

peAi

r Han

dlin

g Un

itCe

iling

Typ

e Ai

rHa

ndlin

g Un

itFa

nBu

ilt-U

p Un

itFa

n Dr

y Co

il Un

it

Page 20: AHU Catalouge-with design details

26 www.aceind.co.krAACCEE RR && AA

Air Handling Unit

Performance table of hot water coil

60

70

Inletwater

temperature

Model

AA0045AA0065AA0085AA0120AA0160AA0200AA0240AA0300AA0370AA0450AA0500AA0600AA0700AA0780AA0870AA0950AA1050AA1200AA1300AA1450AA1600AA1750AA1850AA2000AA0045AA0065AA0085AA0120AA0160AA0200AA0240AA0300AA0370AA0450AA0500AA0600AA0700AA0780AA0870AA0950AA1050AA1200AA1300AA1450AA1600AA1750AA1850AA2000

2 ROW 4 ROW 6 ROW 2 ROW 4 ROW 6 ROW 2 ROW 4 ROW 6 ROW11.0 19.0 23.5 12.0 22.0 28.0 13.5 25.0 32.514.1 26.6 32.7 16.6 32.0 39.4 19.3 36.5 46.018.5 34.9 42.9 21.8 42.0 51.7 25.4 47.9 60.326.4 49.8 61.3 31.2 60.0 73.8 36.3 68.4 86.235.2 66.4 81.7 41.6 80.0 98.4 48.3 91.2 114.944.0 83.0 102.1 52.0 100.0 123.0 60.4 114.0 143.652.8 99.6 122.5 62.4 120.0 147.6 72.5 136.8 172.466.0 124.5 153.1 78.0 150.0 184.5 90.6 171.0 215.581.4 153.6 188.9 96.2 185.0 227.6 111.8 210.9 265.799.0 186.8 229.7 117.0 225.0 276.8 135.9 256.5 323.2

110.0 207.5 255.2 130.0 250.0 307.5 151.1 285.0 359.1132.0 249.0 306.3 156.0 300.0 369.0 181.3 342.0 430.9188.8 304.5 386.7 220.5 350.0 444.5 245.2 395.5 502.3210.4 339.3 430.9 245.7 390.0 495.3 273.2 440.7 559.7234.6 378.5 480.6 274.1 435.0 552.5 304.8 491.6 624.3256.2 413.3 524.8 299.3 475.0 603.3 332.8 536.8 681.7283.2 456.8 580.1 330.8 525.0 666.8 367.8 593.3 753.4323.6 522.0 662.9 378.0 600.0 762.0 420.4 678.0 861.1347.9 561.2 712.7 406.4 645.0 819.2 451.9 728.9 925.6388.4 626.4 795.5 453.6 720.0 914.4 504.4 813.6 1,033.3428.8 691.7 878.4 500.9 795.0 1,009.7 557.0 898.4 1,140.9469.3 756.9 961.3 548.1 870.0 1,104.9 609.5 983.1 1,248.5496.2 800.4 1,016.5 579.6 920.0 1,168.4 644.6 1,039.6 1,320.3536.7 865.7 1,099.4 626.9 995.0 1,263.7 697.1 1,124.4 1,427.9

13.0 23.8 29.0 15.0 28.0 35.0 17.0 32.0 40.517.6 32.7 39.5 20.9 39.4 48.0 23.3 44.9 55.223.2 42.9 51.9 27.4 51.7 63.0 30.6 58.9 72.433.1 61.3 74.1 39.1 73.8 90.0 43.7 84.1 103.544.1 81.7 98.8 52.2 98.4 120.0 58.3 112.2 138.055.1 102.1 123.5 65.2 123.0 150.1 72.9 140.2 172.566.2 122.5 148.2 78.2 147.6 180.1 87.5 168.3 207.082.7 153.1 185.3 97.8 184.5 225.1 109.4 210.3 258.7

102.0 188.9 228.5 120.6 227.6 277.6 134.9 259.4 319.1124.0 229.7 277.9 146.7 276.8 337.6 164.1 315.5 388.1137.8 255.2 308.8 163.0 307.5 375.2 182.3 350.6 431.2165.4 306.3 370.6 195.6 369.0 450.2 218.7 420.7 517.4236.9 370.2 451.7 258.3 430.5 538.1 296.7 486.5 622.7264.0 412.5 503.3 287.8 479.7 599.6 330.7 542.1 693.8294.5 460.1 561.4 321.0 535.1 668.8 368.8 604.6 773.9321.6 502.5 613.0 350.6 584.3 730.3 402.7 660.2 845.1355.4 555.3 677.5 387.5 645.8 807.2 445.1 729.7 934.0406.2 634.7 774.3 442.8 738.0 922.5 508.7 833.9 1,067.4436.7 682.3 832.4 476.0 793.4 991.7 546.9 896.5 1,147.5487.4 761.6 929.2 531.4 885.6 1,107.0 610.4 1,000.7 1,280.9538.2 841.0 1,026.0 586.7 977.9 1,222.3 674.0 1,105.0 1,414.4589.0 920.3 1,122.7 642.1 1,070.1 1,337.6 737.6 1,209.2 1,547.8622.8 973.2 1,187.3 679.0 1,131.6 1,414.5 780.0 1,278.7 1,636.7673.6 1,052.5 1,284.1 734.3 1,223.9 1,529.8 843.6 1,383.0 1,770.2

Heating performance ( 1,000 kcal/h)

Air velocity through the coil Va = 2.0m/s Air velocity through the coil Va = 2.5m/s Air velocity through the coil Va = 3.0m/s

Note1. Operating condition - Air temperature at the inlet of the coil: 15 DB,

- Hot water temperature difference at the inlet and outlet: 52. Coil specification : OD. 5/8 Copper Tube + Al Plate Fin 8Fins/lnch 3. Same heat transfer area condition

[table 26]

Page 21: AHU Catalouge-with design details

27 www.aceind.co.krAACCEE RR && AA

ACE Air Conditioning System

Model

AA0045AA0065AA0085AA0120AA0160AA0200AA0240AA0300AA0370AA0450AA0500AA0600AA0700AA0780AA0870AA0950AA1050AA1200AA1350AA1450AA1600AA1750AA1850AA2000AA0045AA0065AA0085AA0120AA0160AA0200AA0240AA0350AA0370AA0450AA0500AA0600AA0700AA0780AA0870AA0950AA1050AA1200AA1300AA1450AA1600AA1750AA1850AA2000

Va=1.5m/s Va=2.0m/s Va=2.5m/s Va=3.0m/s Va=3.5m/s Va=4.0m/s18.8 22.5 27.0 32.4 38.9 46.7 27.1 32.5 39.0 46.8 56.2 67.4 35.4 42.5 51.0 61.2 73.4 88.1 50.7 60.8 73.0 87.6 105.1 126.1 67.4 80.8 97.0 116.4 139.7 167.6 84.0 100.8 121.0 145.2 174.2 209.1

100.7 120.8 145.0 174.0 208.8 250.6 125.7 150.8 181.0 217.2 260.6 312.8 155.6 186.7 224.0 268.8 322.6 387.1 188.9 226.7 272.0 326.4 391.7 470.0 209.7 251.7 302.0 362.4 434.9 521.9 252.1 302.5 363.0 435.6 522.7 627.3 293.8 352.5 423.0 507.6 609.1 730.9 327.8 393.3 472.0 566.4 679.7 815.6 365.3 438.3 526.0 631.2 757.4 908.9 399.3 479.2 575.0 690.0 828.0 993.6 441.0 529.2 635.0 762.0 914.4 1,097.3 504.2 605.0 726.0 871.2 1,045.4 1,254.5 545.8 655.0 786.0 943.2 1,131.8 1,358.2 609.0 730.8 877.0 1,052.4 1,262.9 1,515.5 672.2 806.7 968.0 1,161.6 1,393.9 1,672.7 734.7 881.7 1,058.0 1,269.6 1,523.5 1,828.2 777.1 932.5 1,119.0 1,342.8 1,611.4 1,933.6 840.3 1,008.3 1,210.0 1,452.0 1,742.4 2,090.9

24.3 29.2 35.0 42.0 50.4 60.5 34.7 41.7 50.0 60.0 72.0 86.4 45.8 55.0 66.0 79.2 95.0 114.0 65.3 78.3 94.0 112.8 135.4 162.4 86.8 104.2 125.0 150.0 180.0 216.0

107.6 129.2 155.0 186.0 223.2 267.8 129.2 155.0 186.0 223.2 267.8 321.4 161.8 194.2 233.0 279.6 335.5 402.6 200.0 240.0 288.0 345.6 414.7 497.7 243.1 291.7 350.0 420.0 504.0 604.8 269.4 323.3 388.0 465.6 558.7 670.5 323.6 388.3 466.0 559.2 671.0 805.2 377.8 453.3 544.0 652.8 783.4 940.0 421.5 505.8 607.0 728.4 874.1 1,048.9 469.4 563.3 676.0 811.2 973.4 1,168.1 513.2 615.8 739.0 886.8 1,064.2 1,277.0 566.7 680.0 816.0 979.2 1,175.0 1,410.0 647.9 777.5 933.0 1,119.6 1,343.5 1,612.2 701.4 841.7 1,010.0 1,212.0 1,454.4 1,745.3 782.6 939.2 1,127.0 1,352.4 1,622.9 1,947.5 863.9 1,036.7 1,244.0 1,492.8 1,791.4 2,149.6 944.4 1,133.3 1,360.0 1,632.0 1,958.4 2,350.1 998.6 1,198.3 1,438.0 1,725.6 2,070.7 2,484.9

1,079.9 1,295.8 1,555.0 1,866.0 2,239.2 2,687.0

Heating performance ( 1,000 kcal/h)

Air velocity through the coil

Note1. Operating condition - Steam pressure: 0.35kg/ G - Air temperature at the inlet of the coil: 15 DB

- Steam pressure: 2.0kg/ G - Air temperature at the inlet of the coil: 11 DB2. Coil specification : OD. 5/8 Copper Tube + Al Plate Fin 8Fins/lnch 3. Same heat transfer area condition and two row basis.

[table 27]

Performance table of steam coil

0.35

2.0

Steampressure(kg/cm2 G)

Air H

andl

ing

Unit

Ther

mo

- Hy

gros

tat

Heat

Rec

over

ySy

stem

Slim

Typ

e Ai

rHa

ndlin

g Un

itDi

rect

Exp

ansio

n Ty

peAi

r Han

dlin

g Un

itCe

iling

Typ

e Ai

rHa

ndlin

g Un

itFa

nBu

ilt-U

p Un

itFa

n Dr

y Co

il Un

it

Page 22: AHU Catalouge-with design details

Basic specification1. Model : AA0300 6. Fresh air dry bulb temperature : Tf = 322. Air volume : Qa = 18,000m3/h 7. Fresh air relative humidity : RHf = 65%3. Cooling capacity : Ht = 135,000Kcal/hr 8. Circulation air dry bulb temperature : Tr = 264. Flow rate : Qw = 450 /min 9. Circulation air relative humidity : RHr = 50%5. Inflow water temperature : tw1 = 7 10. Ratio between fresh air quantity and the circulation air quantity : ( 30% , 70% )

28 www.aceind.co.krAACCEE RR && AA

Air Handling Unit

Selection of the chilled flow rate

Sequence

Fresh air wet bulb temperature

Circulation air wet bulb temperature

Dry bulb temperature

Wet bulb temperature

Dew point temperature

Inlet air heat transfer quantity

Outlet air heat transfer quantity

Wet bulb temperature

Coil surface temperature

Coil pass-through wind speed

Sensible heat ratio

Flow rate per tube

Outlet water temperature

Number of rows

Large temperature difference

Small temperature difference

Logarithmic Mean Temperature

Heat transfer coefficient

Air inlet dry bulb temperature - inlet water temperature

Air inlet dew point temperature- inlet water temperature

Coefficient on the surface of the coil

Coil outlet dry bulbtemperature

Coil face area

Coil dimension

Coil

inle

tCo

il ou

tlet

SymbolItem Calculation formula Calculation Reference

table

Psychrometric

chart

Tf l When Tf = 32 , RHf = 65% 26.5

Tr l When Tr = 26 , RHr = 50% 18.7

1 DB1 Tf 0.3 + Tr 0.7 32 0.3 + 26 0.7 = 27.8

WB1 Tf l 0.3 + Tr l 0.7 26.5 0.3 + 18.7 0.7 = 21

DP When DB1 = 27.8 , WB1 = 21. 17.7

h1 When WB1 = 21 14.7kcal/kg

2 h2 h1 -Ht

14.5 -135,000

= 8.3kcal/kgQa 1.2 18,000 1.2

WB2 When h2 = 8.3kcal/kg 12.2

3 tc 1/2 (tw1 + WB2)1/2 (7+12.2) = 9.6

hc = 6.8kcal/kg

4 R0.24(DB1-tc)

=0.24(DB1-DB2) 0.24(27.8-9.6)

= 0.57h1-hc h1-h2 14.5-6.8

5 DB2 DB1-(h1-h2)R

= DB1-(h1-h2)

(DB1-tc) 27.8 -(14.5-8.3) 0.57

= 13.10.24 (h1-hC) 0.24

FA l Qa (2.5 3,600) 18,000 (2.5 3,600)=2.0m2

6 FA Modified by the Coil, Table 1.995m2 Table 18

Coil Pass X effective length 30 Pass 1740L

7 Va Qa (FA 3,600) 18,000 (1.995 3,600) = 2.51m/s

Coil Circuit

H.C.= 0.5

8 Vq Qw (Pass Circuit) 450 (30 1)=15 /min S.C.= 1

O.H.C.= 1.5

D.C.= 2

9 tw2 tw1 +Ht

7 + 135,000

= 12Qw 60 Cw 450 60 1

10 KVq = 15 /min

K = 885kcal/h m2 Row Table 31When Va = 2.51 m/s

tc1 DB1 - tw1 27.8 - 7 = 20.8

11 tc2 DP - tw1 17.7 - 7 = 10.7 Table 29

Cws tc1 = 20.8 When tc2 = 10.7 Cws = 1.38

t1 DB1 - tw2 27.8 - 12 = 15.8

12 t2 DB2 - tw1 13.1 - 7 = 6.1 Table 30

Mtd t1 = 15.8 When t2 = 6.1 10.2

Ht135,000

= 5.4Row13 N

FA K Cws MTD1.995 885 1.38 10.2 Table 28

N = 6Row

Page 23: AHU Catalouge-with design details

29 www.aceind.co.krAACCEE RR && AA

ACE Air Conditioning System

Basic specification1. Model: AA0300 5. Fresh air dry bulb temperature : Tf = -112. Air volume : Qa = 18,000m3/h 6. Circulation air dry bulb temperature : Tr = 213. Heating capacity : Ht = 150,000Kcal/h 7. Inlet water temperature : Tw1= 604. Flow rate : Qw = 500 /min 8. Ratio between fresh air quantity and the circulation air quantity : ( 20% , 80% )

Selection of the hot flow rate

Conversion table for number of rows that are actually used

0~2.00 2.01~4.00 4.01~6.00 6.01~8.00 8.01~10.00 10.01~12.00

2 4 6 8 10 12

<table 28>

Sequence

SymbolItem Calculation formula Calculation Reference

table

1 DB1 Tf 0.2 + Tr 0.8 (-11) 0.2 + 21 0.8 = 14.6

2 DB2 DB1 +Ht

14.6+150,000

= 43.54a Cp Qa 1.2 0.24 18,000

FA l Qa (2.5 3600) 18,000 (2.5 3,600) = 2.0m2

3 FA Modified by the Coil, Table 1.995m2 Table 18

Coil Pass X effective length 30 Pass 1,740L

4 Va Qa (FA 3,600) 18,000 (1.995 3,600) = 2.51m/s

COIL Circuit

H.C. = 0.5

5 Vq 500 (30 1 1) = 16.67 /min S.C. = 1

O.H.C. = 1.5

D.C. = 2

6 tw2 tw1 -Ht

60 -150,000

= 55Qw 60 Cw 500 60 1

7 KVq = 16.67 /min K = 910kcal/h .m2.Row

Table 31Va = 2.51 m/s

t1 tw2 - DB1 55 - 14.6 = 40.4

8 t2 tw1 - DB2 60 - 43.5 = 16.5 Table 30

Mtd t1 = 40.2 When t2 = 16.5 26.69

Ht150,000

= 3.1Row9 N

FA K MTD1.995 910 26.69 Table 28

N=4Row

Coil inlet dry bulb temperature

Coil pass-through wind speed

Flow rate per tube

Outlet water temperature

Heat transfer coefficient

Number of rows

Large temperature difference

Small temperature difference

Logarithmic Mean Temperature

Coil face area

Coil dimension

Coil outlet dry bulb temperature

Calculated numberof rows

Number of rows that are

actually used(Row)

Qw (number of pass X

Circuit X number of stack)

Air H

andl

ing

Unit

Ther

mo

- Hy

gros

tat

Heat

Rec

over

ySy

stem

Slim

Typ

e Ai

rHa

ndlin

g Un

itDi

rect

Exp

ansio

n Ty

peAi

r Han

dlin

g Un

itCe

iling

Typ

e Ai

rHa

ndlin

g Un

itFa

nBu

ilt-U

p Un

itFa

n Dr

y Co

il Un

it

Page 24: AHU Catalouge-with design details

t1- t22.3log ( t1/ t2)

MTD=

45 42.5 40 37.5

(Wet coil coefficient of the coil surface)1 1.1 1.2 1.3 1.4 1.5 1.6 1.7

Flow rate per tube ( /min)

35

30

25

20

15

10

5

0

35.032.530.027.525.022.520.017.515.012.510.07.55.0

1t( ) Mtd( ) t2( )

30

25

20

15

109876(60)5(50)4(40)3(30)2(20)1(10)

30

25

20

15

109876(60)5(50)4(40)3(30)2(20)1(10)

30

25

20

15

109876(60)5(50)4(40)3(30)2(20)1(10)

Heat

tran

sfer

coe

ffici

ent

k(k

cal/h

m2 Ro

w)

Inle

t air

dew

poi

nt te

mpe

ratu

re

-Inle

t wat

er te

mpe

ratu

re(

)

Inle

t air

dry

bulb

tem

pera

ture

-

Inle

t wat

er te

mpe

ratu

re(

)

Ht

K Cws FA MTDN=

5.0

4.5

4.0

3.5

3.0

2.5

2.0

Wind speed1.5m/s

[table 29]

[table 30]

[table 31]

30 www.aceind.co.krAACCEE RR && AA

Air Handling Unit

Wet coil coefficient of the coil surface (Cws)

Chilled water, hot flow rate heat transfer coefficient

Logarithmic Mean Temperature difference Mtd

(Example of chilledwater coil selection)

(Example of hot watercoil selection)

Page 25: AHU Catalouge-with design details

[table 33][table 32]

31 www.aceind.co.krAACCEE RR && AA

ACE Air Conditioning System

Basic specification1. Model : AA0300 5. Latent heat of vaporization : rs = 517Kcal/Kg2. Air volume : Qa = 18,000m3/h 6. Fresh air dry bulb temperature : Tf = -11.33. Heating capacity : Ht =181,000 Kcal/h 7. Circulation air dry bulb temperature : Tr = 224. Steam pressure : Ps = 2Kg/cm2G 8. Ratio between fresh air quantity and the circulation air quantity : ( 33% , 67% )

Selection of the steam coil

Steam saturation temperature by pressure and table of vaporization latent heat

Temperature increase of the steam coil ( )

1 DB1 Tf 0.33+Tr 0.67 (-11.3) 0.33+22 0.67 = 11

2 DB2 DB1 +Ht

11+181,000

= 45.92a Cp Qa 1.2 0.24 18,000

3 t DB2 - DB1 45.92 - 11 = 34.92

FA l Qa (2.5 3,600) 18,000 (2.5 3,6000) = 2.0m2

4 FA Modified by the Coil, Table 1.995m2 Table 18

Coil Pass X effective length 30 Pass 1,740L

5 Va Qa (FA 3,600) 18,000 (1.995 3,600) = 2.51m/s

6 ts When Ps = 2kg/cm2 G 133 Table 32

7 f When Ps = 2kg/cm2 G, ta1 = 11 1.285 Table 24

8 tdWhen N = 2, Va = 2.51 DTB = 44.3

Table 33DTB f + ta1 44.3 1.285+11= 67.9

9 t l (td-DB1)- t (67.9-11)-34.92=21.98 t l > 0

Ht1 = a Cp Qa (td - DB1) 1.2 0.24 18,000 (67.9-11)

10 N= 294,970kcal/h

181,000 < 294,970

N = 2Row

0 100 5390.2 104 536

0.35 107 5340.6 113 5310.8 116 5281.0 120 5261.5 127 5212 133 5173 143 5104 151 5045 158 4996 164 4947 170 4908 175 48610 183 479

Sequence

SymbolItem

Gage pressure(kg/ G)

Temperature( )

Latent heat( kcal/kg )

Calculation formula Calculation Referencetable

Coil inlet dry bulb temperature

Coil outlet dry bulb temperature

Required temperature difference

Coil pass-through wind speed

Saturated steam temperature

Coil correction factor

Final outlet temperature

Number of rows Compare Ht and Ht1,

and then decide if they appropriate

(Actual coil air temperature difference)-

(Theoretical coil air temperature difference)

Coil face area

Coil dimension

Air H

andl

ing

Unit

Ther

mo

- Hy

gros

tat

Heat

Rec

over

ySy

stem

Slim

Typ

e Ai

rHa

ndlin

g Un

itDi

rect

Exp

ansio

n Ty

peAi

r Han

dlin

g Un

itCe

iling

Typ

e Ai

rHa

ndlin

g Un

itFa

nBu

ilt-U

p Un

itFa

n Dr

y Co

il Un

it

Page 26: AHU Catalouge-with design details

[figure 7]

(kg)

Weight table by model

Airvolume(CMH)

Mixing & Filter Part Coil Part Fan Part Total

WeightReturn Fan

PartMixing(EA)

PartMixing(OA)& Filter Part

Coil Part Supply Fan Part

TotalWeight

H Type HR Type

Model

Type/Part

[table 34]

Basis of the weight calculation 1. Glass Wool insulation, AL Model Frame basis2. Weight below is machine weight

H Type HR Type

32 www.aceind.co.krAACCEE RR && AA

Air Handling Unit

AA0045 2,700 90 162 252 505 252 59 61 162 244 779

AA0065 3,900 122 193 300 616 282 80 84 193 290 929

AA0085 5,100 138 218 361 717 320 90 93 218 347 1,068

AA0120 7,200 165 262 392 819 355 106 108 262 375 1,207

AA0160 9,600 207 319 504 1,030 392 126 132 319 479 1,448

AA0200 12,000 226 367 548 1,141 420 134 142 367 523 1,586

AA0240 14,400 253 430 645 1,328 515 149 157 430 616 1,867

AA0300 18,000 297 487 748 1,533 631 169 180 487 718 2,185

AA0370 22,200 357 554 802 1,713 761 214 220 554 772 2,521

AA0450 27,000 419 659 958 2,036 825 249 258 659 918 2,910

AA0500 30,000 442 707 973 2,123 843 262 270 707 935 3,018

AA0600 36,000 545 829 1,177 2,551 1,003 331 340 829 1,138 3,641

AA0700 42,000 604 1,101 1,386 3,091 1,187 364 372 1,101 1,333 4,537

AA0780 46,800 668 1,208 1,444 3,319 1,413 404 406 1,208 1,383 4,813

AA0870 52,200 728 1,276 1,666 3,670 1,471 429 438 1,276 1,599 5,213

AA0950 57,000 822 1,433 2,103 4,358 1,691 506 508 1,433 2,011 6,143

AA1050 63,000 897 1,506 2,153 4,555 1,779 548 554 1,506 2,069 6,454

AA1200 72,000 948 1,640 2,256 4,844 1,822 572 581 1,640 2,179 6,794

AA1300 78,000 1,045 1,751 2,798 5,595 2,284 639 640 1,751 2,696 8,010

AA1450 87,000 1,197 2,831 2,686 6,714 2,346 723 732 2,831 2,578 9,211

AA1600 96,000 1,291 2,939 2,707 6,938 2,445 801 807 2,939 2,604 9,596

AA1750 105,000 1,422 3,196 3,258 7,875 2,791 875 880 3,196 3,115 10,858

AA1850 111,000 1,527 3,373 4,107 9,006 3,010 935 942 3,373 3,903 12,163

AA2000 120,000 1,640 3,576 4,134 9,349 3,115 1,027 1,030 3,576 3,935 12,682

Page 27: AHU Catalouge-with design details

Order specification sheet for heat exchanger (Coil)

Cold and hot flow rate

Steam coil

33 www.aceind.co.krAACCEE RR && AA

ACE Air Conditioning System

Equipmentnumber

Airvolume(CMM)

Caloricvalue

(Kcal/h)

Flowrate Row Pass

FH(mm)

L(mm)

Header(A)

Inlet(A)

Nominaldiameter

Steel tube(mm)

Copper tube(mm)

Outlet(A)

Circuit Directionof tube

Remark

Stands for the standard specification of the company

Equi

pmen

t ord

er

and

Quan

tity

Optio

nal

spec

ifica

tion

Refe

renc

e dr

awin

g

Refe

renc

e di

men

sion

Spec

ial c

onsi

der-

atio

ns fo

r ord

erin

g

Nominaldiameter

Steel tube(mm)

Copper tube(mm)

Refe

renc

e di

men

sion

Spec

ial c

onsi

der

atio

ns fo

r ord

erin

g

Equipmentnumber

Airvolume(CMM)

Caloricvalue

(Kcal/h)

Flowrate Row Pass

FH(mm)

L(mm)

Header(A)

Inlet(A)

Outlet(A)

H1(mm)

Directionof tube Remark

Number of coil fins: 8FPI 10FPI 12FPI Header material: Black tube White tube Copper tube(K) Copper tube(L) Additional item: Flange Including the pairing flange Air Vent,Drain V/V

Coil category: Gradient coil(Non-freezing Coil) Flat coil Coil Fin material: General AL Fin Coated fin Copper fin Copper coated finCopper tube thickness: 0.7th 0.5th 0.6th 0.8th

Number of coil fins: 8FPI 10FPI 12FPI Header material: Black tube White tube Copper tube(K)

Copper tube(L)

Coil Fin material: General AL Fin Coated fin Copper fin Copper coated fin Thickness of the copper tube: 0.5th 0.6th 0.7th 0.8th Additional items: Flange Including the pairing flange Air Vent, Drain V/V

Stands for the standard specification of the company

Fill in the blanks (air volume, caloric value, etc. as many as possible). Check box for optional specifications must be marked with for the corresponding item.

25A 34.0 28.5832A 42.7 34.9240A 48.6 41.2850A 60.5 53.9865A 76.3 66.6880A 89.1 79.38100A 114.3 104.78

25A 34.0 28.5832A 42.7 34.9240A 48.6 41.2850A 60.5 53.9865A 76.3 66.6880A 89.1 79.38100A 114.3 104.78

Equi

pmen

t ord

eran

d Qu

antit

yOp

tiona

l sp

ecifi

catio

nRe

fere

nce

draw

ing

Air H

andl

ing

Unit

Ther

mo

- Hy

gros

tat

Heat

Rec

over

ySy

stem

Slim

Typ

e Ai

rHa

ndlin

g Un

itDi

rect

Exp

ansio

n Ty

peAi

r Han

dlin

g Un

itCe

iling

Typ

e Ai

rHa

ndlin

g Un

itFa

nBu

ilt-U

p Un

itFa

n Dr

y Co

il Un

it

Page 28: AHU Catalouge-with design details

Horizontal type(Al Mold)Indoor380V-60HzG/W-40K x 50T

Cold & painting (color : )SGCC 0.6T(perforation)

STS 1.5T+P.EF 15TH insulationCMH / CMMmmAQAir Foil(ACE Fan)

CMH / CMMmmAQSirocco(ACE Fan)

Built-in AHU

1"(housing type)Chilled water coil

kcal/hInlet DB : InletWB : Inlet : Outlet :

Common coil for cold and hot waterkcal/h

Inlet DB: Inlet : Outlet :

CU Tube 0.5TAl Fan 0.14T(Plate)Steel tube(black tube)AFI 82%(KPS-4000N,20TH)

NBS 85%(3")

Brand not specifiedBrand not specifiedBrand not specifiedBrand not specifiedBrand not specified

Steam Injectionkg/h

Air Tight(AL+AL)Electric Heater [ ]Kw, (single phase or three phase), (voltage : 220V, 380V, V)

Control Panel(based on integrated heater type) Control Panel(separate heater type)Wiring for each section Integrated wiring Controlled by the Heater Control BoxRound shape double window ( 250) Square (100 X 150TH) Squared double window(100 X 150TH)

Sensible heat heat transfer exchanger [air volume: ] 30% 100% Refer to other data selection requiredRotary heat transfer exchanger Plate type sensible heat exchanger Plate type heat transfer exchanger Heat pipeLadder installation U-Trap installation Common Base supply Silencer installationAir Mixer installation Air Blender installation Damper Actuator supplyOther additional comment:

1. Type of AHU2. Installation3. Power source specification

Insulator

External board

Internal board

Drain Pan

Motor location

Displacement

Fan Option

Option

Direction of tube

COIL materialand standard

Pre

Medium

Special

Advanced

TypeHumidification

quantity

Heat exchanger

Etc.

Anti-freezingheaterLamp

Sight Glass

4. Casing

5. Fan

6. Isolator

7. Coil

8. Filter

9. Humidifier

10. Damper

11. Option

Air volumeStatic pressure

TypeModel X Quantity

Air volumeStatic pressure

TypeModel X Quantity

TypeCooling capacityCondition of air

Condition of cold waterType

Heating capacityCondition of air

Condition of hot water

Vertical type Complex type Other (Frame, artilon)Outdoor Pinch Roof required (cold & painting STS)220V-60Hz 440V, 480V 50HzG/W-40KX25T Artilon-50T Polyurethane foam -50TG/W-[ ]K X [ ]T Other-[ ]SGCC 1.6T PCM color coated steel plate STS GalvalumeSGCC 0.6T(plain plate) SGCC 0.8T(plain plate) STS 0.6T(plain plate)Other-[ ] SGCC 0.8T(perforation) STS 0.6T(perforation)STS 1.5T+G/W insulation Cold & painting +G/W artilon insulation Other-[ ]

Specified domestic brand-[ ] Specified overseas brand-[ ] SiroccoOther model and quantity-[ X EA]

Specified domestic brand-[ ] Specified overseas brand-[ ] Air FoilOther model and quantity-[ X EA]External AHU Including isolator baseVariable pulley (motor side) Inlet Vane (Worm gear mounted not mounted)

Automatic grease injector (manual electronic)2" 3" Open type Specified brand[ ]D.X Coil Relife Coil

Separate hot water Steam coil Electric coil Anti-freezing damper coil(hot water steam)

Steam pressure in case of steam coil 2kg/cm2 1kg/cm2 0.35kg/cm2 Other[ ]kg/cm2

Pre-heating coil (steam hot water) Pre-cooling coil Supply of tube flangeEliminator-material SGCC+AL Eliminator-material STS Supply of pairing flangeLeft side Right side Both sides0.6T 0.7T 0.8T STSAL coated fin Copper fin Copper coated fin STS AeroCopper Header Steel tube(white tube)Header STS HeaderAFI 85%(25TH) NBS 30%(50TH) Unpowered electrostatic type 1"(AFI 85%)AFI 70%(DEMISTER) Auto Roll Filter [AFI %]Auto washing anti-fungus filter(AFI 80%) Auto Clean Filter[AFI %]NBS 60-65% 80-85% 90-95% (3" Mini Pleat thin type basis)NBS 60-65% 80-85% 90-95% (12" Cell Type basis)NBS 60-65% 80-85% 90-95% (12 18 22 30 36"Bag Type basis)Unpowered electrostatic type 2"(AFI 95%, NBS 40%) [Maker : ]Auto washing electric dust collector (NBS 85~90%) [Maker : ]Two-stage electrostatic type electric dust collector (NBS 85~90%) [Maker : ]Charged corpuscle neutralization device [Pre : ,Med : ] [Maker : ]Hepa[DOP %] Ulpa[ %] Bio-CleanUV Lamp Carbon(MAT TRAY) Chemical FilterSteam Grid [Maker: ] Including Control ValveElectrode type [Maker: ] Evaporation type(thickness of filter media:50 100TH)Water Spray Type Pan Type(electric type)General damper (SGCC+SGCC) Air Tight(AL+SGCC) Other

Item ACE standard Optional specification

Supp

ly

Cool

ing

Heat

ing

Retu

rn

* Inlet size : width [ ] X height [ ] * When brand is specified, write down the brand of the component you request.

Order specification sheet for air handling unit* For ordering, the corresponding items must be marked with or required specifications need to be written down. Contact our sales department for questions.