Date post: | 15-Nov-2014 |
Category: |
Documents |
Upload: | jaime-r-fulguerinas |
View: | 213 times |
Download: | 4 times |
Condensing UnitsCX Series
CX030 thru CX3602.5 TR thru 30 TR9 kW thru 105 kW
MODELS :CX030 - CX060
Contents Page
Model decoding ........................................................................................................................................ 2
Unit features & options .......................................................................................................................... 2-3
Physical data ......................................................................................................................................... 4-6
Selection procedure ................................................................................................................................. 7
Performance characteristics ................................................................................................................ 7-10
Electrical data .................................................................................................................................... 11-13
Dimensions ........................................................................................................................................ 14-18
Typical schematic wiring diagram ...................................................................................................... 19-21
Typical unit installation ........................................................................................................................... 22
Electrical ................................................................................................................................................. 23
System design ........................................................................................................................................ 23
INDEX
CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
1
MODEL DECODING1& 2
BASIC3, 4 & 5
NOMINALCOOLINGCAPACITY
(MBH)
7REFRIGERA-
TION CIRCUIT
6ELECTRICAL
SUPPLY( V-Ph-Hz )
9MODE
11CONDENSER
COIL
CXCLASSIC
CONDENSINGUNIT
030036042048060
075090100120150180220240300360
S : SINGLEC : 208/230-1-60
H : 208/230-3-60
M : 380-3-60 (4 WIRE)
F : 460-3-60
C : COOL ONLY
H : HEATPUMP+
A : ALUMINUM FIN
B : COATEDALUMINUMFIN
C : COPPER FIN
8COMPRESSOR
TYPE
R : HERMETICRECIPRO-CATING
13OTHER OPTIONS
10CONDENSER
MOTOR
N : STANDARD
L : LOWAMBIENT
12ACCESSORIES
N : NO OPTION
U : UVM
V : VOLT FREECONTACTS*
C : U & V
S : SINGLE
D : DUAL
H : 208/230-3-60
M : 380-3-60 (4 WIRE)
F : 460-3-60
+ Applicable for CX030 to CX220 only.
* Not applicable for CX030 & CX036 single phase models.
** To match with KW series double skin units only.
D : DUAL
R : HERMETICRECIPRO-CATING
S : SCROLL
S : SCROLL
UNIT FEATURES & OPTIONSA. GENERALThe Classic Condensing units incorporate the latest innovative technology to provide quiet, reliable performance. Thewrap-around coil not only adds to the aesthetical appeal, it also gives optimum heat transfer efficiency. The access panelsprovide access to the compressor, fan motor and to the electrical control box.
These condensing units can be combined with a wide variety of evaporator coils and blower packages to provide quietand dependable comfort. These units can be installed on a roof or at ground level.
Heat pump feature is available as an option for added comfort during cold season (for models up to CX220 only).
B. UNIT ENCLOSUREAll panels are of heavy gauge (G-90) galvanized steel sheet and completely weatherized for outdoor installation. Steelsheet panels are zinc coated and galvanized by the hot dip process of lock-forming quality conforming to ASTM A 653commercial weight G-90, followed by baked on electrostatic polyester dry powder coat.
C. COMPRESSORHermetic reciprocating/scroll compressors are used as standard as shown in the physical data. They are provided withall the standard controls necessary for proper and safe operation. These compressors have a self-regulating crankcaseheater, improved internal pressure relief valve which provides high pressure protection to the refrigerant system andvibration isolators for quiet and efficient operation.
D. AIR COOLED CONDENSER1. The large wrap-around condenser coil is of corrugated fin & tube type, constructed of enhanced copper tubes and
mechanically bonded to aluminum fins. As an option to aluminum fins, coated aluminum fins or corrugated copper finsmay be provided. Tube support sheets are of galvanized steel, formed to provide structural strength. Tubes arecircuited to ensure minimum pressure drop and maximum heat transfer. Each coil is completely dehydrated, chargedand sealed at the factory upon completion of pressure tests.
2. The fans are propeller type and direct-driven, upward discharge provided with fan grille.
3. Units are equipped with totally enclosed fan motors for greater reliability and dependable performance for many years.Inherent thermal protection is automatic reset type.
N : NO OPTION
F : STD. UNIT WITHFILTER DRYER &SIGHT GLASS
K : CONDENSINGUNIT WITHSYSTEMIZER**
R : F & K
N : NO OPTIONF : STD. UNIT WITH
FILTER DRYER &SIGHT GLASS
K : CONDENSINGUNIT WITHSYSTEMIZER**
P : PDSR : F & K
S : F & PT : K & P
Q : F, K & P
2
E. SERVICE VALVESBoth suction and liquid service valves are back seating type. Valves are externally located so refrigerant tube connec-tions can be made quickly and easily. Each valve has a gauge pressure port for ease of checking refrigerant operatingpressures.
F. CONTROL PANELThe control panel design is equivalent to NEMA construction for easy access ensuring dust and weather proof construc-tion. Internal power and control wiring is neatly routed, properly anchored and all wires identified with cable markers asper NEC standard applicable to HVAC units. The electrical controls used in the control panel are UL approved, which arereliable in operation at high ambient conditions for a long period.
The electrical circuit has been carefully designed with all necessary protection and circuit elements for safe operation ofthe unit.
G. LOW PRESSURE SWITCHAuto reset SPST switch activated by refrigerant pressure - locks out the compressor, if the refrigerant pressure fallsbelow 25 PSIG. Also provides additional protection against evaporator freeze up due to loss of indoor airflow.
H. HIGH PRESSURE SWITCH (OPTIONAL)Auto reset SPST switch activated by refrigerant pressure - locks out the compressor, if the refrigerant pressure risesabove 450 PSIG. Also provides additional protection against compressor damage due to loss of outdoor airflow.
I. LOW AMBIENT (OPTIONAL)Low ambient operation down to 450F using fan cycling switch.
J. PUMP DOWN SOLENOID VALVE FOR COOL ONLY MODELS (OPTIONAL for CX075 & above)Pump down solenoid valve keeps the evaporator coil dry of liquid refrigerant.
3
MODEL NUMBER CX030 CX036 CX042 CX048 CX060
NOMINAL CAPACITY (TONS)* 2.5 3 3.5 4 5
COMPRESSOR Type Hermetic reciprocating
Quantity 1 1 1 1 1
Oil (oz) 32 40 40 45 70
Refrigerant R–22
Operating Charge (oz) 106 106 120 167 170
CONDENSER FAN Type Propeller
Qty. – Diameter (inch) 1–18 1–18 1–24 1–24 1–24
Nominal airflow, CFM (L/S) 2300 (1085) 2300 (1085) 3650 (1723) 3650 (1723) 3650 (1723)
Motor HP – RPM 1/4–1100 1/3–1100
CONDENSER COIL Type Corrugated fin & tube
Tube Dia.- Rows - Fins Per Inch 3/8-2-16 3/8-2-16 3/8-1-16 3/8-2-16 3/8-2-16
Total face area, Sq. ft. (Sq. m.) 10 (0.929) 10 (0.929) 16 (1.49) 16 (1.49) 16 (1.49)
HIGH PRESSURE SWITCH Open (PSIG) 450 ± 10 450 ± 10 450 ± 10 450 ± 10 450 ± 10
Close (PSIG) 360 ± 15 360 ± 15 360 ± 15 360 ± 15 360 ± 15
LOW PRESSURE SWITCH Open (PSIG) 25 ± 5 25 ± 5 25 ± 5 25 ± 5 25 ± 5
Close (PSIG) 50 ± 5 50 ± 5 50 ± 5 50 ± 5 50 ± 5
REFRIGERANT LINES** Suction line size (OD) - inch 3/4 3/4 7/8 7/8 7/8
Liquid line size (OD) - inch 3/8 3/8 3/8 3/8 1/2
SHIPPING WEIGHT Kg. 75 79 98 111 113
PHYSICAL DATA
* Refer to performance data for exact rating values.
** Pipe sizes are for runs up to 25 feet to indoor unit. For refrigerant lines longer than 25 feet, use next larger size.
(OPTIONAL)
4
5
MODEL NUMBER CX075 CX075 CX090 CX090 CX100 CX100 CX120 CX120
NUMBER OF REFRIGERATION CIRCUIT Single Dual Single Dual Single Dual Single Dual
NOMINAL CAPACITY (TONS)* 6 6 7 7 8 8 10 10
COMPRESSOR Type Scroll Recip. Scroll Recip. Scroll Recip. Scroll Recip.
Quantity 1 2 1 2 1 2 1 2
Oil (oz) 56 32x2 60 40x2 81 45x2 110 70x2
Refrigerant R–22
Operating Charge (oz) 200 105x2 301 140x2 314 151x2 330 158x2
CONDENSER FAN Type Propeller
Qty. – Diameter (inch) 2–24 2–24 2–24 2–24 2–24 2–24 2–24 2–24
Nominal airflow, CFM (L/S) 7150 (3374) 7150 (3374) 6500 (3068) 6500 (3068) 7150 (3374) 7150 (3374) 7150 (3374) 7150 (3374)
Motor HP – RPM 1/3–1100 (2)
CONDENSER COIL Type Corrugated fin & tube
Tube Dia.- Rows - Fins Per Inch 3/8-1-16 3/8-1-16 3/8-2-16 3/8-2-16 3/8-2-16 3/8-2-16 3/8-2-16 3/8-2-16
Total face area, Sq. ft. (Sq. m.) 24 (2.23) 24 (2.23) 21 (1.95) 21 (1.95) 24 (2.23) 24 (2.23) 24 (2.23) 24 (2.23)
HIGH PRESSURE SWITCH Open (PSIG) 450 ± 10 450 ± 10 450 ± 10 450 ± 10 450 ± 10 450 ± 10 450 ± 10 450 ± 10
Close (PSIG) 360 ± 15 360 ± 15 360 ± 15 360 ± 15 360 ± 15 360 ± 15 360 ± 15 360 ± 15
LOW PRESSURE SWITCH Open (PSIG) 25 ± 5 25 ± 5 25 ± 5 25 ± 5 25 ± 5 25 ± 5 25 ± 5 25 ± 5
Close (PSIG) 50 ± 5 50 ± 5 50 ± 5 50 ± 5 50 ± 5 50 ± 5 50 ± 5 50 ± 5
REFRIGERANT LINES** Suction line size (OD) - inch 1-1/8 7/8 (2) 1-1/8 7/8 (2) 1-3/8 7/8 (2) 1-3/8 7/8 (2)
Liquid line size (OD) - inch 5/8 1/2 (2) 5/8 1/2 (2) 5/8 1/2 (2) 5/8 1/2 (2)
SHIPPING WEIGHT Kg. 200 215 210 233 228 230 240 244
PHYSICAL DATA
* Refer to performance data for exact rating values.
** Pipe sizes are for runs up to 25 feet to indoor unit. For refrigerant lines longer than 25 feet, use next larger size.
(OPTIONAL)
6
MODEL NUMBER CX150 CX150 CX180 CX220 CX240 CX300 CX360
NUMBER OF REFRIGERATION CIRCUIT Single Dual Dual Dual Dual Dual Dual
NOMINAL CAPACITY (TONS)* 12 12 15 18 20 25 30
COMPRESSOR Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Quantity 1 2 2 2 2 2 2
Oil per system (oz) 110 56 81 11 0 110 135 223
Refrigerant R–22
Charge per system (oz)+ 313 160 245 250 360 450 540
CONDENSER FAN Type Propeller
Qty. – Diameter (inch) 2 – 26 2 – 26 2 – 26 2 – 26 2 – 30 2 – 30 3– 30
Nominal CFM (L/S) 10000 (4719) 10000 (4719) 12500 (5899) 12500 (5899) 15200 (7173) 15000 (7079) 22800(10760)
Motor HP – RPM 1/3 – 850 1/3 – 850 3/4 – 1140 3/4 – 1140 1.5 – 1100 1.5 – 1100 1.5 – 1100
CONDENSER COIL Type Corrugated fin & tube
Tube Dia.– Rows – Fins per inch 3/8–2–16 3/8–2–16 3/8–2–16 3/8–2–16 3/8–4–14 3/8–5–14 3/8–4–14
Total face area, Sq. ft. (Sq. m.) 38 (3.53) 38 (3.53) 38 (3.53) 38 (3.53) 28 (2.6) 28 (2.6) 46.66 (4.33)
HIGH PRESSURE SWITCH Open (PSIG) 450 ± 10 450 ± 10 450 ± 10 450 ± 10 450 ± 10 450 ± 10 450 ± 10
Close (PSIG) 360 ± 15 360 ± 15 360 ± 15 360 ± 15 360 ± 15 360 ± 15 360 ± 15
LOW PRESSURE SWITCH Open (PSIG) 25 ± 5 25 ± 5 25 ± 5 25 ± 5 25 ± 5 25 ± 5 25 ± 5
Close (PSIG) 50 ± 5 50 ± 5 50 ± 5 50 ± 5 50 ± 5 50 ± 5 50 ± 5
REFRIGERANT LINES** Suction line size (OD), inch 1-3/8 7/8 1-3/8 1-3/8 1-3/8 1-3/8 1-5/8
Liquid line size (OD), inch 5/8 1/2 5/8 5/8 5/8 5/8 7/8
SHIPPING WEIGHT Kg. 400 415 535 592 750 840 950
PHYSICAL DATA
* Refer to performance data for exact rating values.
** Pipe sizes are for runs up to 50 feet to indoor unit. For refrigerant lines longer than 50 feet, use next larger size.
+ Operating system charge is applicable when matched with BX series air handling units & connected by 25 feet of refrigerant piping.
(OPTIONAL)
ALTITUDE (FEET) 2000 4000 6000 8000 10000
Condensing Unit Cooling Capacity .99 .98 .96 .95 .94
Condensing Unit & Evaporator .98 .96 .93 .90 .88FACTOR
SELECTION PROCEDURE1. Enter performance tables at specified SST and desired ambient conditions.
2. HEAT REJECTION:Calculate condenser Total Heat Rejection Capacity as follows:HR = Unit cooling capacity + (3.41 x Total Unit Power Input, Watts).
3. HEAD PRESSURE:To determine head pressure (psig) use the following conversion table:
LEGEND: SST - Saturated Suction Temperature; TC - Total Capacity (1000 Btuh) Gross; CT - Condensing Temperature (0F); kW - Total unit power input
Condensing Temp. - 0F. 100 110 120 130 140 150 160
(R-22) Head Pressure - PSIG. 195.9 226.4 259.9 296.9 337.3 381.6 429.8
MODEL : CX030, HERMETIC RECIPROCATING (SINGLE) COMP.
MODEL : CX042, HERMETIC RECIPROCATING (SINGLE) COMP.
MODEL : CX036, HERMETIC RECIPROCATING (SINGLE) COMP.
MODEL : CX048, HERMETIC RECIPROCATING (SINGLE) COMP.
TC30 CT
kWTC
35 CTkWTC
40 CTkWTC
45 CTkWTC
50 CTkWTC
55 CTkW
75 85 95 105 115 12529.40 26.80 24.10 21.50 19.00 16.5099.00 108.00 118.00 127.00 135.00 142.50
2.7 2.8 2.9 3.0 3.1 3.1532.90 30.40 27.60 24.90 22.00 19.40
101.00 112.00 121.00 130.00 138.00 145.002.8 2.96 3.05 3.15 3.27 3.36
37.90 34.10 31.00 27.90 25.00 22.00103.00 115.00 124.00 133.00 141.00 148.00
2.93 3.12 3.27 3.37 3.52 3.6440.90 37.90 34.40 31.20 27.90 24.70
108.00 118.00 126.50 135.50 143.00 150.503.1 3.23 3.4 3.55 3.7 3.88
45.00 41.30 38.10 34.50 31.00 27.60110.00 120.00 128.00 137.00 145.00 152.00
3.2 3.4 3.58 3.75 3.98 4.1349.00 45.00 41.20 37.90 33.80 30.00
114.00 122.00 131.00 139.50 147.00 154.003.4 3.58 3.82 4.05 4.27 4.4
SST(0F)
AMBIENT TEMPERATURE - 0F
TC30 CT
kWTC
35 CTkWTC
40 CTkWTC
45 CTkWTC
50 CTkWTC
55 CTkW
SST(0F)
AMBIENT TEMPERATURE - 0F
TC30 CT
kWTC
35 CTkWTC
40 CTkWTC
45 CTkWTC
50 CTkWTC
55 CTkW
SST(0F)
AMBIENT TEMPERATURE - 0F
TC30 CT
kWTC
35 CTkWTC
40 CTkWTC
45 CTkWTC
50 CTkWTC
55 CTkW
SST(0F)
AMBIENT TEMPERATURE - 0F
75 85 95 105 115 12535.80 33.00 30.00 27.50 25.00 22.00
104.00 112.50 122.50 130.00 140.00 146.003.52 3.62 3.8 3.94 4.1 4.21
40.00 37.00 33.50 30.60 27.70 24.80107.00 116.00 125.00 133.00 142.00 150.00
3.68 3.83 4.0 4.17 4.33 4.4844.00 41.00 37.50 34.40 31.00 28.00
112.00 120.00 129.00 137.00 145.00 153.003.89 4.1 4.27 4.5 4.62 4.8
48.50 45.00 41.50 38.00 34.50 31.00115.00 123.00 131.00 140.00 147.50 156.00
4.12 4.31 4.52 4.73 4.94 5.1153.00 49.00 45.50 41.60 38.00 34.00
118.50 126.00 134.00 142.00 150.00 157.004.36 4.6 4.77 4.96 5.25 5.43
57.50 53.50 49.60 45.30 41.20 37.50120.00 128.00 136.00 144.00 152.00 159.00
4.56 4.83 5.1 5.3 5.54 5.8
75 85 95 105 115 12538.50 35.70 32.30 29.25 26.75 23.0099.00 107.00 115.00 123.00 132.00 141.00
3.68 3.81 4.0 4.1 4.38 4.543.40 40.30 36.50 33.00 29.65 26.40
102.00 110.00 119.00 127.00 136.00 144.003.86 4.0 4.2 4.33 4.5 4.66
48.10 45.00 41.00 37.30 33.60 30.00105.00 113.00 122.00 130.00 139.00 147.00
4.05 4.25 4.45 4.64 4.8 4.953.15 49.50 45.50 41.50 37.50 33.75
107.00 115.50 124.00 132.00 141.00 149.004.39 4.5 4.68 4.9 5.1 5.3
58.25 54.30 50.00 45.55 41.55 37.25109.00 117.00 126.00 134.00 143.00 150.50
4.53 4.77 4.94 5.12 5.43 5.6163.25 59.00 54.30 49.90 45.35 41.00
111.50 119.00 129.00 136.00 144.00 152.004.73 5.0 5.23 5.47 5.72 5.96
75 85 95 105 115 12543.00 39.80 36.00 32.50 30.00 25.50
100.00 108.00 116.00 124.00 133.00 141.503.90 3.97 4.06 4.12 4.22 4.30
48.80 45.00 41.00 37.00 33.10 29.50103.00 111.00 120.00 128.00 136.50 145.00
4.00 4.11 4.22 4.35 4.47 4.6354.20 50.50 46.00 41.75 37.70 33.50
105.00 113.00 123.00 130.50 139.50 147.504.12 4.30 4.45 4.61 4.78 4.97
59.80 55.50 51.00 46.50 42.00 38.00108.00 116.00 125.00 133.00 141.50 150.00
4.30 4.50 4.70 4.90 5.06 5.3165.00 61.00 56.00 51.00 46.60 42.00
110.00 118.00 127.00 135.00 144.00 151.004.50 4.70 4.97 5.17 5.45 5.65
70.50 66.00 60.50 56.00 51.00 46.00112.00 120.00 130.00 137.00 145.00 153.00
4.67 4.93 5.25 5.46 5.80 6.04
PERFORMANCE DATA
4. CORRECTION FACTORS FOR ALTITUDE:
7
PERFORMANCE DATAMODEL : CX060, HERMETIC RECIPROCATING (SINGLE) COMP.
MODEL : CX075, HERMETIC SCROLL (SINGLE) COMP.
TC30 CT
kWTC
35 CTkWTC
40 CTkWTC
45 CTkWTC
50 CTkWTC
55 CTkW
SST(0F)
AMBIENT TEMPERATURE - 0F
TC30 CT
kWTC
35 CTkWTC
40 CTkWTC
45 CTkWTC
50 CTkWTC
55 CTkW
SST(0F)
AMBIENT TEMPERATURE - 0F
75 85 95 105 115 12554.00 50.50 46.50 42.80 39.00 35.30
102.00 109.00 118.50 126.00 135.00 144.004.65 4.70 4.85 5.00 5.15 5.35
60.00 56.00 52.00 47.50 43.50 39.50103.00 111.50 120.00 129.50 138.50 146.50
4.67 4.85 5.05 5.30 5.50 5.7066.00 61.50 57.40 52.70 48.50 44.20
106.00 115.00 123.00 132.00 141.00 149.504.80 5.10 5.30 5.60 5.80 6.05
72.00 67.00 62.50 58.00 53.50 48.50109.00 118.50 126.00 134.50 142.50 151.00
5.02 5.37 5.60 5.90 6.10 6.4577.50 72.50 67.60 63.00 58.00 53.50
111.00 120.00 128.50 137.00 145.00 154.005.20 5.55 5.90 6.20 6.55 6.95
83.50 78.40 73.40 68.20 63.00 58.00114.00 122.00 130.00 138.50 147.00 155.00
5.50 5.85 6.15 6.45 6.95 7.30
75 85 95 105 115 12567.00 62.50 59.00 54.50 50.50 47.0096.00 105.00 114.00 123.00 132.00 140.005.90 6.15 6.25 6.65 7.10 7.30
75.00 70.10 66.00 61.50 57.50 54.0099.00 108.00 117.00 126.00 135.00 143.006.10 6.40 6.70 7.05 7.40 7.70
82.50 78.00 73.00 68.50 64.50 60.70102.00 111.00 120.50 130.00 138.00 145.00
6.40 6.70 7.00 7.50 7.80 8.1090.20 85.50 80.50 75.50 71.20 67.00
104.00 112.00 121.00 131.00 140.00 147.006.60 6.90 7.30 7.75 8.15 8.50
98.00 93.00 87.50 83.00 76.50 73.50106.00 114.00 123.00 132.50 141.00 149.00
6.85 7.20 7.60 8.10 8.45 9.00106.00 100.00 94.50 89.00 84.00 80.00108.00 116.00 125.00 134.00 142.50 150.00
7.10 7.45 7.90 8.20 8.50 9.35
MODEL : CX090, HERMETIC SCROLL (SINGLE) COMP.
TC30 CT
kWTC
35 CTkWTC
40 CTkWTC
45 CTkWTC
50 CTkWTC
55 CTkW
75 85 95 105 115 12575.00 70.00 66.00 61.00 56.50 51.50
100.00 110.00 118.00 127.00 136.00 145.006.90 7.30 7.70 8.10 8.50 8.90
83.50 78.00 73.00 68.00 63.00 57.50103.00 112.00 120.00 130.00 139.00 148.00
7.20 7.70 8.10 8.50 9.00 9.5092.00 86.50 81.00 75.00 69.50 63.50
106.00 114.00 123.00 133.00 142.00 150.007.60 8.00 8.50 9.10 9.50 10.00
101.00 94.50 88.50 82.00 76.50 70.00108.00 116.00 125.00 135.00 144.00 152.00
7.90 8.40 8.95 9.50 10.00 10.50109.00 103.00 96.00 89.00 83.00 76.00110.00 118.00 127.00 137.00 145.00 153.00
8.30 8.75 9.30 9.90 10.40 11.00109.00 103.00 96.00 89.00 83.00 76.00112.00 119.00 128.00 138.00 146.00 154.00
8.60 9.10 9.65 10.30 10.90 11.40
SST(0F)
AMBIENT TEMPERATURE - 0F
LEGEND:
SST - Saturated Suction Temperature
TC - Total Capacity (1000 Btuh) Gross
CT - Condensing Temperature (0F)
kW - Total unit power input
MODEL : CX075, HERMETIC RECIPROCATING (DUAL) COMP.
TC30 CT
kWTC
35 CTkWTC
40 CTkWTC
45 CTkWTC
50 CTkWTC
55 CTkW
SST(0F)
AMBIENT TEMPERATURE - 0F
75 85 95 105 115 12568.00 62.50 57.50 52.50 48.00 43.0088.00 100.00 112.00 123.00 132.00 141.00
5.62 5.94 6.16 6.40 6.60 6.8076.50 70.50 65.00 59.50 54.50 49.0092.00 105.00 116.00 126.00 134.00 143.00
5.72 6.16 6.40 6.70 7.0 7.2485.00 78.00 73.00 66.50 61.00 55.0096.00 109.00 120.00 128.00 136.00 145.00
5.94 6.40 6.75 7.0 7.45 7.6793.00 86.00 80.00 73.50 66.50 61.00
100.00 112.00 122.00 130.00 138.00 147.006.10 6.60 7.0 7.40 7.78 8.15
101.50 93.50 87.00 80.50 74.00 67.00103.00 115.00 124.00 132.00 140.00 149.00
6.26 6.96 7.50 7.76 8.15 8.64109.00 101.00 94.00 87.00 80.00 73.00105.00 116.00 125.00 133.00 142.00 150.00
6.48 7.13 7.67 8.10 8.59 9.20
MODEL : CX090, HERMETIC RECIPROCATING (DUAL) COMP.
TC30 CT
kWTC
35 CTkWTC
40 CTkWTC
45 CTkWTC
50 CTkWTC
55 CTkW
SST(0F)
AMBIENT TEMPERATURE - 0F
75 85 95 105 115 12582.00 75.00 69.00 63.00 56.00 50.00
100.00 109.00 118.00 127.00 135.00 144.007.12 7.45 7.76 8.10 8.31 8.64
91.50 85.00 79.00 71.00 65.00 57.00104.00 112.00 120.00 129.00 138.00 146.00
7.45 7.90 8.20 8.53 8.86 9.20101.00 94.00 87.00 80.00 72.50 65.50106.00 115.00 124.00 132.00 140.00 148.00
7.90 8.31 8.75 9.10 9.40 9.72111.00 103.00 95.50 88.50 81.00 73.00109.00 117.00 126.00 134.00 142.00 150.00
8.31 8.64 9.20 9.61 10.0 10.26121.00 113.00 105.00 97.00 89.00 81.00111.00 120.00 129.00 136.00 145.00 152.00
8.75 9.23 9.72 10.15 10.55 10.90131.00 122.00 113.00 105.00 97.00 89.00113.00 122.00 131.00 138.00 146.00 154.00
9.10 9.72 10.26 10.60 11.12 11.45
8
PERFORMANCE DATA
MODEL : CX120, HERMETIC SCROLL (SINGLE) COMP.
MODEL : CX100, HERMETIC SCROLL (SINGLE) COMP.
TC30 CT
kWTC
35 CTkWTC
40 CTkWTC
45 CTkWTC
50 CTkWTC
55 CTkW
SST(0F)
AMBIENT TEMPERATURE - 0F
TC30 CT
kWTC
35 CTkWTC
40 CTkWTC
45 CTkWTC
50 CTkWTC
55 CTkW
SST(0F)
AMBIENT TEMPERATURE - 0F
75 85 95 105 115 12588.00 81.00 74.00 67.50 60.00 53.50
103.00 112.00 119.00 128.00 136.00 144.008.16 8.37 8.51 8.67 8.82 8.98
98.00 90.00 83.50 76.00 69.00 61.50105.00 114.00 122.00 130.00 138.00 147.00
8.47 8.67 8.98 9.18 9.38 9.59109.00 99.00 92.50 87.50 77.50 69.00108.00 117.00 124.00 133.00 142.00 150.00
8.87 9.18 9.38 9.80 10.1 10.15120.00 111.00 102.50 94.00 86.00 77.50112.00 120.00 127.00 136.00 144.00 152.00
9.33 9.70 10.0 10.35 10.71 11.02130.00 122.00 112.00 104.00 94.00 83.50114.00 122.00 130.00 138.00 146.00 154.00
9.75 10.15 10.61 11.07 11.37 11.73140.00 132.00 122.00 114.00 100.00 93.50116.00 124.00 133.00 140.00 148.00 156.00
10.2 10.61 11.22 1163 12.04 12.44
75 85 95 105 115 125100.00 92.00 85.00 77.50 70.00 63.00104.00 113.00 121.00 130.00 138.00 146.00
8.95 9.20 9.45 9.75 9.90 10.20110.00 102.50 95.50 87.50 79.50 71.50107.00 116.00 123.00 133.00 140.00 149.00
9.35 9.65 9.90 10.30 10.60 10.90123.00 114.00 106.00 97.00 88.50 80.00111.00 120.00 127.00 136.00 144.00 152.00
9.85 10.20 10.55 10.95 11.30 11.65134.50 125.00 116.00 107.00 97.50 88.00113.00 122.00 130.00 138.00 146.00 154.0010.30 10.75 11.20 11.60 12.00 12.35
146.00 136.00 126.00 116.00 106.50 96.50116.00 124.00 132.00 140.00 148.00 156.0010.80 11.30 11.80 12.25 12.70 13.05
158.00 146.00 136.00 125.00 115.00 104.50118.00 126.00 134.00 142.00 150.00 158.0011.30 11.60 12.40 12.95 13.55 13.80
MODEL : CX100, HERMETIC RECIPROCATING (DUAL) COMP.
TC30 CT
kWTC
35 CTkWTC
40 CTkWTC
45 CTkWTC
50 CTkWTC
55 CTkW
SST(0F)
AMBIENT TEMPERATURE - 0F
75 85 95 105 115 12588.50 81.00 74.00 66.00 59.00 51.50
102.00 110.00 116.00 126.00 135.00 144.008.34 8.50 8.67 8.90 9.10 9.25
99.00 91.00 83.50 76.00 68.00 60.00105.00 113.00 119.00 128.00 138.00 147.00
8.60 8.90 9.16 9.43 9.70 10.0110.50 102.00 93.50 84.50 76.50 68.50108.00 116.00 122.00 131.00 141.00 150.00
8.94 9.32 9.65 10.0 10.36 10.74121.50 112.00 103.50 94.50 86.00 76.50111.00 119.00 125.00 134.00 143.00 152.00
9.37 9.81 10.2 10.63 11.10 11.45132.00 122.50 113.50 104.00 95.00 85.00113.00 122.00 128.00 136.00 146.00 154.00
9.81 10.36 10.87 11.37 11.82 12.20142.50 133.00 122.50 113.00 103.00 93.00115.00 124.00 130.00 138.00 147.00 156.0010.25 10.90 11.45 12.00 12.54 12.97
MODEL : CX120, HERMETIC RECIPROCATING (DUAL) COMP.
TC30 CT
kWTC
35 CTkWTC
40 CTkWTC
45 CTkWTC
50 CTkWTC
55 CTkW
SST(0F)
AMBIENT TEMPERATURE - 0F
75 85 95 105 115 125104.00 96.00 89.50 82.00 74.00 67.00105.00 114.00 120.00 128.00 139.00 148.00
9.81 10.20 10.52 10.70 11.40 11.61114.50 107.00 99.50 91.50 83.50 76.00108.00 117.00 123.00 131.00 142.00 151.0010.20 10.63 11.10 11.50 11.94 12.42
126.00 118.00 109.50 101.00 92.50 84.00111.00 120.00 125.00 134.00 145.00 153.0010.57 11.11 11.72 12.15 12.70 13.24
137.50 128.50 119.50 111.50 102.00 93.50113.00 122.00 128.00 137.00 147.00 154.0011.00 11.66 12.37 12.92 13.57 14.17
148.50 140.00 130.00 121.00 111.50 102.00116.00 124.00 130.00 139.00 149.00 156.0011.45 12.21 13.10 13.63 14.40 15.15
160.00 150.00 140.00 131.00 120.50 111.00118.00 126.00 132.00 141.00 150.00 158.0012.00 12.75 13.74 14.40 15.21 16.10
TC30 CT
kWTC
35 CTkWTC
40 CTkWTC
45 CTkWTC
50 CTkWTC
55 CTkW
75 85 95 105 115 125130.9 121.5 112.1 103.8 94.4 86.1
98 106 114 124 134.5 142.511.4 11.9 12.5 13.1 13.9 14.4
145.5 136.1 125.7 115.8 105.9 95.5101 110 117 127 137 14511.8 12.5 13 13.8 14.5 15.2
161.6 150.7 140.2 127.7 117.3 106.4104 112 121 130 139.5 14712.2 13 13.8 14.5 15.4 16.1176.7 165.2 152.7 141.3 127.7 116.3106 114 124 132.5 141 148.512.7 13.5 14.5 15.3 16.1 16.9191.3 178.8 165.8 152.7 140.2 126.2107 116 125 134 143 15013 14 15 16 16.8 17.7
205.9 192.3 177.7 163.2 150.7 136.6109 118 127 135 143.5 151.513.5 14.6 15.7 16.7 17.7 18.6
SST(0F)
AMBIENT TEMPERATURE - 0F
MODEL: CX150, HERMETIC SCROLL (SINGLE) COMP.
TC30 CT
kWTC
35 CTkWTC
40 CTkWTC
45 CTkWTC
50 CTkWTC
55 CTkW
75 85 95 105 115 125125.8 118.8 111.1 103.5 95.2 88.2
98 106 116 125 136 14511.1 11.8 12.5 13.2 14.1 14.8140 131.7 123.5 114.1 105.8 97.6101 108.5 117.5 127 137 14611.6 12.3 13.1 13.9 14.7 15.5
154.1 145.8 136.4 127 116.4 108.2102.5 111 120 130 140 14812.1 12.9 13.7 14.7 15.6 16.3169.4 160 149.4 138.8 128.2 118.8104 113 122 131 141 14912.5 13.5 14.4 15.3 16.2 17181.1 174.1 162.3 150.5 140 128.8105.5 114 124 133 142 15013.1 14 15 15.9 16.9 17.8198.8 188.2 175.2 163.5 150.5 138.8107 115 124.5 134.5 143 15113.7 14.7 15.7 16.8 17.7 18.5
SST(0F)
AMBIENT TEMPERATURE - 0F
MODEL: CX150, HERMETIC SCROLL (DUAL) COMP.
LEGEND: SST - Saturated Suction Temperature; TC - Total Capacity (1000 Btuh) Gross; CT - Condensing Temperature (0F); kW - Total unit power input
9
PERFORMANCE DATA
TC30 CT
kWTC
35 CTkWTC
40 CTkWTC
45 CTkWTC
50 CTkWTC
55 CTkW
75 85 95 105 115 125190 181.6 171.6 160.8 150 140100 110 120 130 140 15014.5 16.5 18.6 20.7 22.8 24.8207.5 197.5 187.5 176 165 155103 114 123 132 142.5 15115.2 17.4 19.2 21.2 23.2 25227 216 205 192.5 181.5 170107 116 125.5 135.5 143.5 15316 17.8 19.7 21.9 23.6 25.5245 232.5 222.5 210 197.5 185110 119.5 127.5 137.5 145 15516.6 18.6 20.3 22.5 24 26265 251 240 225 213 200112 122 130 140 147 156.516.9 19.1 20.8 23 24.4 26.3282.5 270 257 242 230 215115 124 131 141.5 148 15817.4 19.6 21 23.3 25.1 26.6
SST(0F)
AMBIENT TEMPERATURE - 0F
MODEL : CX220, HERMETIC SCROLL (DUAL) COMP.
TC30 CT
kWTC
35 CTkWTC
40 CTkWTC
45 CTkWTC
50 CTkWTC
55 CTkW
75 85 95 105 115 125224 212.8 201 191 180 166100 109 118 128 138 14817.8 19.53 21.6 23.2 25.8 27.6245.9 233.94 221.4 210.3 198.35 184.2102 111 120 130 140 15018.2 19.81 22 24 26.1 28267.8 255.08 241.8 229.6 216.7 202.4104 113 123 132 142 15218.6 20.27 22.6 24.35 26.5 28.4289.7 276.22 262.2 248.9 235.05 220.6106 115 125 133 143 15319 20.62 23 24.6 26.7 28.8
311.6 297.36 282.6 268.2 253.4 238.8107.5 117 127 135 145 15419.35 21.5 23.5 25 27.1 29333.5 318.5 303 287.5 271.75 257109 119 129 138 147 155
19.58 21.8 24 25.7 27.4 29.1
SST(0F)
AMBIENT TEMPERATURE - 0F
MODEL : CX240, HERMETIC SCROLL (DUAL) COMP.
MODEL : CX180, HERMETIC SCROLL (DUAL) COMP.
TC30 CT
kWTC
35 CTkWTC
40 CTkWTC
45 CTkWTC
50 CTkWTC
55 CTkW
75 85 95 105 115 125160.8 151.8 143.1 135.5 127.6 119
99 107 117 127 136 14612.4 12.7 13 13.4 13.8 14.1177 167.4 159.3 150.2 142 133101 110 119 129 138 14813.7 14.3 14.6 15 15.4 15.7193.6 183.8 173.2 164.6 154.8 145.7103 112 121 131 140 15015.5 15.7 16.1 16.4 16.8 17.2210.5 200.7 190.2 173.2 169.5 160.8105 114 123 133 142 15217.1 17.4 17.8 18.1 18.3 18.5230.1 218.1 206.4 195.5 185.3 172.5107 116 125 134 143 15318.6 19 19.3 19.5 19.7 20244.1 233.1 221.5 209.4 197.7 186108 118 127 135 145 15420.3 20.6 21 21.2 21.4 21.6
SST(0F)
AMBIENT TEMPERATURE - 0F
TC30 CT
kWTC
35 CTkWTC
40 CTkWTC
45 CTkWTC
50 CTkWTC
55 CTkW
75 85 95 105 115 125282 268 254 240 226 212100 112 122 133 144 15423.2 26.1 28.5 31.2 33.9 36.4309.6 294.66 279.68 264.72 249.76 234.8103 114 124 136 146 15624 26.8 29.2 32.1 34.6 37
337.2 321.32 305.36 289.44 273.52 257.6106 116 126 138 148 15824.8 27.4 29.8 32.8 35.2 37.5364.8 347.98 331.04 314.16 297.28 280.4108 118 129 140 150 16025.3 28 30.6 33.3 35.7 38.2392.4 374.64 356.72 338.88 321.04 303.2110 120 131 142 152 16226.1 28.5 31.4 33.7 36.2 38.7420 401.3 382.4 363.6 344.8 326112 122 133 143 154 16426.8 29.2 32 34.2 37 39.3
SST(0F)
AMBIENT TEMPERATURE - 0F
MODEL : CX300, HERMETIC SCROLL (DUAL) COMP.
MODEL : CX360, HERMETIC SCROLL (DUAL) COMP.
TC30 CT
kWTC
35 CTkWTC
40 CTkWTC
45 CTkWTC
50 CTkWTC
55 CTkW
75 85 95 105 115 125334 317 300 284.5 267.5 25098 108 117 126 136 146
26.8 30.2 33 36.2 39.5 42.9369.2 350.8 332.4 315.2 296.6 277.8101 110 119 128 138 14827.5 30.8 33.8 37 40.5 43.9404.4 384.6 364.8 345.9 325.7 305.6103 112 121 130 140 15028.7 31.5 34.7 37.7 41.2 44.5439.6 418.4 397.2 376.6 354.8 333.4105 113 123 133 142 15229.3 32 35.3 38.7 41.8 45.2474.8 452.2 429.6 407.3 383.9 361.2106 115 125 134 144 15329.7 32.7 36 39.2 42.6 45.7510 486 462 438 413 389107 116 126 135 145 15430.3 33.3 36.7 39.7 43.2 46.3
SST(0F)
AMBIENT TEMPERATURE - 0F
LEGEND:
SST - Saturated Suction Temperature
TC - Total Capacity (1000 Btuh) Gross
CT - Condensing Temperature (0F)
kW - Total unit power input
10
11
ELECTRICAL DATA
MCA MOCPCOMPRESSOR *
FANMOTOR
FLA
VOLTAGERANGEPOWER
SUPPLY(V-Ph-Hz)
MODEL No.: CX036 (RECIPROCATING)
380-3-60(4 WIRE)
Single compressor units
MIN. MAX. RLA LRA
208/230-3-60 187 253 11.8 67 1.4 16.1 25
342 418 5.6 39 1.4 8.4 15
460-3-60 414 506 5.4 29.2 0.7 7.5 15
208/230-1-60 187 253 16.7 84 1.4 22.2 35
MCA MOCPCOMPRESSOR *
FANMOTOR
FLA
VOLTAGERANGEPOWER
SUPPLY(V-Ph-Hz)
MODEL No.: CX060 (RECIPROCATING)
380-3-60(4 WIRE)
MIN. MAX. RLA LRA
208/230-3-60 187 253 19.6 105 2.3 26.8 45
342 418 10.4 55 2.3 15.3 25
460-3-60 414 506 10.4 55 1.3 14.3 20
208/230-1-60 187 253 30.7 135 2.3 40.6 70
MCA MOCPCOMPRESSORVOLTAGE
RANGEPOWERSUPPLY
(V-Ph-Hz)
MODEL No.: CX090 (SCROLL)
380-3-60(4 WIRE)
MIN. MAX. RLA LRA
208/230-3-60 187 253 25 164 2.3 35.9 60
342 418 12 100 2.3 19.6 30
460-3-60 414 506 12 101 1.3 17.6 25
MOCP
MIN. MAX. RLA LRA
208/230-3-60 187 253 13.1 80 2.3 18.6 30
342 418 8.2 50 2.3 12.5 20
460-3-60 414 506 5.9 42 1.3 8.6 15
208/230-1-60 187 253 19.4 109.6 2.3 26.5 45
MOCP
MIN. MAX. RLA LRA
208/230-3-60 187 253 20.7 156 2.3 30.4 50
342 418 10.7 72 2.3 17.9 25
460-3-60 414 506 10 74 1.3 15.1 25
MOCP
MIN. MAX. RLA LRA
208/230-3-60 187 253 32.1 195 2.3 44.7 70
342 418 16.7 123 2.3 25.4 40
460-3-60 414 506 16.4 95 1.3 23.1 35
MCACOMPRESSOR *
FANMOTOR
FLA
VOLTAGERANGEPOWER
SUPPLY(V-Ph-Hz)
MODEL No.: CX042 (RECIPROCATING)
380-3-60(4 WIRE)
MCACOMPRESSORVOLTAGE
RANGEPOWERSUPPLY
(V-Ph-Hz)
MODEL No.: CX075 (SCROLL)
380-3-60(4 WIRE)
MCACOMPRESSOR *
FANMOTOR
FLA
VOLTAGERANGEPOWER
SUPPLY(V-Ph-Hz)
MODEL No.: CX100 (SCROLL)
380-3-60(4 WIRE)
MCA MOCPCOMPRESSOR *
FANMOTOR
FLA
VOLTAGERANGEPOWER
SUPPLY(V-Ph-Hz)
MODEL No.: CX030 (RECIPROCATING)
380-3-60(4 WIRE)
MIN. MAX. RLA LRA
208/230-3-60 187 253 11.8 67 1.4 16.2 25
342 418 5.6 39 1.4 8.4 15
460-3-60 414 506 5.4 29.2 0.7 7.5 15
208/230-1-60 187 253 15.6 90 1.4 20.9 35
NOTE: Refer to page 13 for legend & notes.
MOCP
MIN. MAX. RLA LRA
208/230-3-60 187 253 16 97 2.3 22.3 35
342 418 8.2 50 2.3 12.5 20
460-3-60 414 506 8.2 50 1.3 11.5 15
208/230-1-60 187 253 24.6 132 2.3 33 50
MCACOMPRESSOR *
FANMOTOR
FLA
VOLTAGERANGEPOWER
SUPPLY(V-Ph-Hz)
MODEL No.: CX048 (RECIPROCATING)
380-3-60(4 WIRE)
(each)
*FAN
MOTORFLA
(each)
*FAN
MOTORFLA
(each)
12
MCA MOCPCOMPRESSOR *
FANMOTOR
FLA
VOLTAGERANGEPOWER
SUPPLY(V-Ph-Hz)
MODEL No.: CX120 (SCROLL)
380-3-60(4 WIRE)
MIN. MAX. RLA LRA
208/230-3-60 187 253 33.6 225 2.3 46.6 80
342 418 18.6 140 2.3 27.8 45
460-3-60 414 506 17.3 114 1.3 24.2 40
ELECTRICAL DATA Single compressor units
Dual compressor units
MCA MOCP
COMPRESSOR *FAN
MOTORFLA
VOLTAGERANGEPOWER
SUPPLY(V-Ph-Hz)
MODEL No.: CX075 (RECIPROCATING)
380-3-60(4 WIRE)
MIN. MAX. RLA LRA
208/230-3-60 187 253 11.8 67 2.3 31.1 40
342 418 5.6 39 2.3 17.2 20
460-3-60 414 506 5.4 29.2 1.3 14.7 20
MCA MOCP
COMPRESSOR *FAN
MOTORFLA
VOLTAGERANGEPOWER
SUPPLY(V-Ph-Hz)
MODEL No.: CX090 (RECIPROCATING)
380-3-60(4 WIRE)
MIN. MAX. RLA LRA
208/230-3-60 187 253 13.1 80 2.3 34 45
342 418 8.2 50 2.3 23 30
460-3-60 414 506 5.9 42 1.3 15.8 20
MCA MOCP
COMPRESSOR *FAN
MOTORFLA
VOLTAGERANGEPOWER
SUPPLY(V-Ph-Hz)
MODEL No.: CX100 (RECIPROCATING)
380-3-60(4 WIRE)
MIN. MAX. RLA LRA
208/230-3-60 187 253 16 97 2.3 40.6 50
342 418 8.2 50 2.3 23 30
460-3-60 414 506 8.2 50 1.3 21 25
MCA MOCP
COMPRESSOR *FAN
MOTORFLA
VOLTAGERANGEPOWER
SUPPLY(V-Ph-Hz)
MODEL No.: CX120 (RECIPROCATING)
380-3-60(4 WIRE)
MIN. MAX. RLA LRA
208/230-3-60 187 253 19.6 105 2.3 48.7 60
342 418 10.4 55 2.3 28 35
460-3-60 414 506 10.4 55 1.3 26 35
MIN. MAX. RLA LRA
208/230-3-60 187 253 47.1 245 2.5 63.8 110
342 418 24.4 145 2.5 35.5 50
460-3-60 414 506 19.6 125 1.3 27.1 45
MCA MOCPCOMPRESSOR *
FANMOTOR
FLA
VOLTAGERANGEPOWER
SUPPLY(V-Ph-Hz)
MODEL No.: CX150 (SCROLL)
380-3-60(4 WIRE)
(each)
NOTE: Refer to page 13 for legend & notes.
MIN. MAX. RLA LRA
208/230-3-60 187 253 20.7 156 2.5 51.5 70
342 418 10.7 72 2.5 29 35
460-3-60 414 506 10 74 1.3 25.1 35
MCA MOCP
COMPRESSOR *FAN
MOTORFLA
VOLTAGERANGEPOWER
SUPPLY(V-Ph-Hz)
MODEL No.: CX150 (SCROLL)
380-3-60(4 WIRE)
(each)
(each)
(each)
(each)
(each)
(each)
(each)
(each)
(each)
(each)
(each)
MIN. MAX. RLA LRA
208/230-3-60 187 253 32.1 195 3.7 79.6 110
342 418 16.7 123 1.7 41 50
460-3-60 414 506 16.4 95 1.8 40.5 50
MCA MOCP
COMPRESSOR FANMOTOR
FLA
VOLTAGERANGEPOWER
SUPPLY(V-Ph-Hz)
MODEL No.: CX180 (SCROLL)
380-3-60(4 WIRE)
(each)
(each)
13
ELECTRICAL DATA Dual compressor units
MIN. MAX. RLA LRA
208/230-3-60 187 253 33.6 225 3.7 83 110
342 418 18.6 140 1.7 45.3 60
460-3-60 414 506 17.3 114 1.8 42.5 50
MCA MOCP
COMPRESSOR FANMOTOR
FLA
VOLTAGERANGEPOWER
SUPPLY(V-Ph-Hz)
MODEL No.: CX220 (SCROLL)
380-3-60(4 WIRE)
(each)
(each)MCA MOCP
COMPRESSOR FANMOTOR
FLA
VOLTAGERANGEPOWER
SUPPLY(V-Ph-Hz)
MODEL No.: CX240 (SCROLL)
380-3-60(4 WIRE)
MIN. MAX. RLA LRA
208/230-3-60 187 253 42 239 5 104.5 125
342 418 23.5 145 2.7 58.3 80
460-3-60 414 506 19.2 125 2.5 48.2 60
MCA MOCP
COMPRESSOR FANMOTOR
FLA
VOLTAGERANGEPOWER
SUPPLY(V-Ph-Hz)
MODEL No.: CX300 (SCROLL)
380-3-60(4 WIRE)
MIN. MAX. RLA LRA
208/230-3-60 187 253 47.1 245 5 116 150
342 418 24.4 145 2.7 60.3 80
460-3-60 414 506 19.6 125 2.5 49.1 60
(each)
(each)
(each)
(each)
MCA MOCP
COMPRESSOR FANMOTOR
FLA
VOLTAGERANGEPOWER
SUPPLY(V-Ph-Hz)
MODEL No.: CX360 (SCROLL)
380-3-60(4 WIRE)
MIN. MAX. RLA LRA
208/230-3-60 187 253 56.8 425 5 142.8 175
342 418 39 239 2.7 95.9 125
460-3-60 414 506 27.8 187 2.5 70.1 90
(each)
(each)
LEGEND:
* Single phase motors
FLA – Full Load Amps
LRA – Locked Rotor Amps
RLA – Rated Load Amps
MOCP – Maximum Over Current Protection
MCA – Minimum Circuit Amps
NOTE:If other than 900C copper wire is used, size can be determined from unit ampacity given in above table and applicable table of NEC.Wire size selected must have current capacity not less than that of copper wire specified and voltage drop should not exceed 2% ofrated voltage. Must use copper wire from disconnect switch to the unit.
DIMENSIONSCX030 - CX060
MODEL NUMBER A B C D E F G H
CX030 - CX036 711 610 708 596 440 175 86 57
CX042 - CX060 889 813 806 695 538 216 99 72
NOTES:1. All dimensions are in mm, (dimensions in brackets are in inches).2. Allow 32" (812mm) clearance to service end of the
unit, 12" (305mm) on remaining sides and 24"(610mm) between units for proper airflow.
14
NOTES:1. All dimensions are in mm, (dimensions in brackets are in inches).2. Allow 32" (812 mm) clearance to service end of the unit, 24" (610 mm) on remaining sides and 48" (1219 mm) between units for
proper airflow.
DIMENSIONSCX075 - CX120
15
DIMENSIONSCX150 - CX220
NOTES:1. All dimensions are in mm, (dimensions in brackets are in inches).2. Allow 32" (812 mm) clearance to service end of the unit, 48" (1219 mm) on remaining sides for proper airflow.
16
DIMENSIONSCX 240 - CX 300
NOTES:1. All dimensions are in mm, (dimensions in brackets are in inches).2. Allow 48" (1219 mm) clearance on all sides for proper airflow.
17
DIMENSIONSCX 360
NOTES:1. All dimensions are in mm, (dimensions in brackets are in inches).2. Allow 48" (1219 mm) clearance on all sides for proper airflow.
18
943[37.13"]
943[37.13"]
2032[80.0"]
73 [2.88"]
2197[86.50"]
2121[83.50"]
1550
[61.
0"]
203
[8.0
"]
LEGEND
AHU AIR HANDLING UNIT
AI ANTI ICE THERMOSTAT
AR AUXILIARY RELAY
ATB AUXILIARY TERMINAL BLOCK
CAP CAPACITOR
CC COMPRESSOR CONTACTOR
CB CIRCUIT BREAKER
C. HTR CRANKCASE HEATER
COMP COMPRESSOR
FM FAN MOTOR (CONDENSER)
FMC FAN MOTOR CONTACTOR
FR FAULT RELAY
HPS HIGH PRESSURE SWITCH
HVTB HIGH VOLTAGE TERMINAL BLOCK
JP JUMPER
L1 LINE 1
L2 LINE 2
L3 LINE 3
LPS LOW PRESSURE SWITCH
LUG LUG GROUND
N NEUTRAL
NTB NEUTRAL TERMINAL BLOCK
SD SMOKE DETECTOR
TRANS TRANSFORMER
T'STAT THERMOSTAT
UVM UNDER VOLTAGE MONITOR
VFC VOLT FREE CONTACT
FIELD WIRING
DISCONNECT TAB - 1/4"
SPLICE-CLOSED END
TYPICAL SCHEMATIC WIRING DIAGRAM
_ _ _+
NOTES1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.
2. ANY WIRE REPLACEMENT SHOULD BE OF THE 900COR ITS EQUIVALENT.USE COPPER CONDUCTOR WIRES ONLY.
3. POWER MUST BE SUPPLIED TO CRANKCASEHEATER FOR MINIMUM OF 12 HOURS PRIOR TOSYSTEM START UP.
IF POWER IS OFF 6 HOURS OR MORE, CRANKCASEHEATER MUST BE ON FOR 12 HOURS BEFOREOPERATING THE SYSTEM.
FAILURE TO FOLLOW THESE INSTRUCTIONS MAYRESULT IN COMPRESSOR DAMAGE.
4. FUSED DISCONNECT SWITCH OR CIRCUITBREAKER TO BE PROVIDED BY END USER WITHRATING AS RECOMMENDED BY ZAMIL.
5. * ATB 3 IS APPLICABLE FOR PDS OPTION UNITSONLY.
6. REMOVE JUMPER FOR AI OPTION. ROUTE AIWIRES FROM AHU.
7. NEUTRAL LINE REQUIRED ON 380V-3Ph-60HzPOWER SUPPLY ONLY.
(Single compressor units - Cool only)
19
USE FOR OPTION-3B ONLY
UNITS 24V CIRCUITTO BX,FMX *
5
4
3
41A
22ALPS [AI]
SEE NOTE 6
*25A 26AJP12 CC
ATB1
2
11615 CB
TRANS
L1
[UVM] [SD] JP11JP124 VAC
1
L2
JP21A
17
1B 17
SEE HPS OPTION BELOW
HPS
NAME
LPS
SET POINTS
360 ± 15
CLOSE (PSIG)
50 ± 5
OPEN (PSIG)
450 ± 1025 ± 5
CRANKCASE HTR CONNECTION
LUG
36B
FM2
35A
COMP
T2A
T1A
CAP1
T3A
FM1
37A36A
CAP235B
CC
37B
COMP L1 C.HTR
HVTB
L2
L3
L1
L2
OF A.H.U ACCORDINGLY.
NOTE: ATB# 1,4 & 5 OF COND. UNIT TO BE CONNECTED TO ATB# 1,4 & 5
CONTROL & INTERCONN. DETAILS FOR FMX AHU W/O SYSTEMIZER
FCS 190 ± 15 290 ± 10
N (SEE NOTE -7)
REFER TO UNITNAMEPLATE FORPOWER SUPPLY
B. COMP ON/OFF & TRIP & [UNIT] TRIP INDICATION OPTION
1. UVM OPTION
A. UNIT ON & OFF INDICATION
3. VOLT FREE CONTACT OPTIONS
OPTIONS4. HPS OPTION
TOLPS
23A 25AHPS
2. SMOKE DETECTOR OPTION
1B
ATB2
1A
ATB2
REMOVE JP2
VFC-FROM CUSTOMER'SSMOKE DETECTOR
L3
UVM
L2L1
TO ATBTO ATB
(REMOVE JP1)
L3L2L1
FOR BX,FX & FMX AHU
AR1
46
UNIT ON
45 AR1-1
ATB115
UNIT OFF
AR1-1 47
ATB217
CC
A-2
B
COMP-TRIPCOMP-OFF
COMP-ON
55 56 57 58
FR-2
CC
A-2
A
FR-2
54
UNIT/COMP-TRIP
43 FR-15 41AATB1
FR44
ATB217
LEGEND
AHU AIR HANDLING UNIT
AI ANTI ICE THERMOSTAT
AR AUXILIARY RELAY
ATB AUXILIARY TERMINAL BLOCK
CAP CAPACITOR
CC COMPRESSOR CONTACTOR
CB CIRCUIT BREAKER
C. HTR CRANKCASE HEATER
COMP COMPRESSOR
FM FAN MOTOR (CONDENSER)
FMC FAN MOTOR CONTACTOR
FR FAULT RELAY
HPS HIGH PRESSURE SWITCH
HVTB HIGH VOLTAGE TERMINAL BLOCK
JP JUMPER
L1 LINE 1
L2 LINE 2
L3 LINE 3
LPS LOW PRESSURE SWITCH
LUG LUG GROUND
N NEUTRAL
NTB NEUTRAL TERMINAL BLOCK
RR RESET RELAY
SD SMOKE DETECTOR
TRANS TRANSFORMER
T'STAT THERMOSTAT
UVM UNDER VOLTAGE MONITOR
VFC VOLT FREE CONTACT
FIELD WIRING
DISCONNECT TAB - 1/4"
SPLICE-CLOSED END
TYPICAL SCHEMATIC WIRING DIAGRAM
_ _ _+
NOTES1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.
2. ANY WIRE REPLACEMENT SHOULD BE OF THE 900COR ITS EQUIVALENT.USE COPPER CONDUCTOR WIRES ONLY.
3. POWER MUST BE SUPPLIED TO CRANKCASEHEATER FOR MINIMUM OF 12 HOURS PRIOR TOSYSTEM START UP.
IF POWER IS OFF 6 HOURS OR MORE, CRANKCASEHEATER MUST BE ON FOR 12 HOURS BEFOREOPERATING THE SYSTEM.
FAILURE TO FOLLOW THESE INSTRUCTIONS MAYRESULT IN COMPRESSOR DAMAGE.
4. FUSED DISCONNECT SWITCH OR CIRCUITBREAKER TO BE PROVIDED BY END USER WITHRATING AS RECOMMENDED BY ZAMIL.
5. * ATB 3 & 5 IS APPLICABLE FOR PDS OPTION UNITSONLY.
6. USE DISCONNECT TAB OR SPLICE ONLY WHEREEVER REQUIRED FOR EXTENSION OF ORIGINALWIRE.
7. REMOVE JUMPER FOR AI OPTION. ROUTE AIWIRES FROM AHU.
8. NEUTRAL LINE REQUIRED ON 380V-3Ph-60HzPOWER SUPPLY ONLY.
(Dual compressor units - Cool only)
20
CC2
TO CC2
C1-CONTACTORCC1
1B JP11 17
FCSC
2
17FCSC1
FCSC213A
12A
FM1
HS
LS38
A37
A
T2A
FCS
C1
39A
FCS215
13B
FM2
12B
T2B
37B
LS38
B
T3B
FCSC4
FCSC317
FCSC
4
39B
FCS
C3
HS
CAP2
35B
36B
1PH FAN MOTOR ONLYCONNECTION APPLICABLE FOR
36A
CAP1
35A
HS
38B
FM2
LS37
B
FCS2
T3B
39B
37A
FM1
36A
TO CC1T2AT1A
37B
FM2
36B
TO CC2T3BT2B
CC1
TO CC1
39A
FM1
36A
CC2
35A
CAP1
T1A
36B
LS37
AH
S38
A
CAP2
FCS1
T2A
C2-CONTACTOR
SEE HPS OPTION BELOW
LPS1
CB 16
24VAC
TRANSL1
36A
T3A
T2A
T1A
35A
COMP2
COMP1
L2
L1
T1B
37A
T2B
T3B
JP1
[UVM]
SEE NOTE-7
[AI1]25A
L2
JP2
26A
1A
C.HTR1
C.HTR2
37B
35B
36B
35A
L3
L2
15
CAP1
36A
TO CC2T2B
35B
T1A
FCS1
TO CC1AMBIENT OPTION- 460VAC UNITS ONLYCONNECTION APPLICABLE FOR LOW -
AMBIENT OPTION 230VAC UNITS ONLYCONNECTION APPLICABLE FOR LOW
[SD]
5AHU
22B
7
8
6
USE FOR OPTION-3-B ONLY
LPS2
41A
41B
JP5
[AI2]25B 26B
22A
TO
1
3
4
2
ATB
15
380V/3PH/60HZ 460V/3PH/60HZ UNITS
230V/3PH/60HZ WIRG DGM SUITS
PLS. REFER UNIT NAME PLATEPOWER SUPPLY
HVTB
LUG
L2
L3
L1
CRANKCASE HTR CONNECTION
SEE HPS OPTION BELOW
N (SEE NOTE -8)
REFER TO UNITNAMEPLATE FORPOWER SUPPLY
(REMOVE JP1)
TO ATBTO ATB
L1 L2 L3
UVML1 L2 L3
A. UNIT ON & OFF INDICATION
UNIT ON
AR1-145
15 AR1 41A
UNIT OFF
AR1-146
55
47
17
OPTIONS3. VOLT FREE CONTACT OPTIONS
ATB(7)
C1-OFFC1-ON
B. COMP ON, OFF & TRIP [&] UNIT TRIP INDICATION OPTION
2. SMOKE DETECTOR OPTION
VFC-FROM CUSTOMER'S
REMOVE JP2
SMOKE DETECTOR
1A 1B
1. UVM OPTION
TOLPS2
LPS1TO
C2-ON
C1-TRIP C2-TRIP
C2-OFF
41B
FR2-1
ATB(8)
UNIT-TRIP
17
FR1-2
CC
1A-2
A
56
FR1-2
CC
1A-2
B
57
54
FR1
43
58 60
FR1-1 44A
COMP1
59
62
FR2-2
61
FR2-2
CC
2A-2
A
CC
2A-2
B
44
FR2
63
COMP2
23B HPS2 25B
23A
4. HPS OPTION
HPS1 25A
LEGEND
AHU AIR HANDLING UNIT
AI ANTI ICE THERMOSTAT
AR AUXILIARY RELAY
ATB AUXILIARY TERMINAL BLOCK
CAP CAPACITOR
CC COMPRESSOR CONTACTOR
CB CIRCUIT BREAKER
C. HTR CRANKCASE HEATER
COMP COMPRESSOR
FM FAN MOTOR (CONDENSER)
FMC FAN MOTOR CONTACTOR
FR FAULT RELAY
HPS HIGH PRESSURE SWITCH
HVTB HIGH VOLTAGE TERMINAL BLOCK
JP JUMPER
L1 LINE 1
L2 LINE 2
L3 LINE 3
LPS LOW PRESSURE SWITCH
LUG LUG GROUND
N NEUTRAL
NTB NEUTRAL TERMINAL BLOCK
RR RESET RELAY
SD SMOKE DETECTOR
TRANS TRANSFORMER
T'STAT THERMOSTAT
UVM UNDER VOLTAGE MONITOR
VFC VOLT FREE CONTACT
FIELD WIRING
DISCONNECT TAB - 1/4"
SPLICE-CLOSED END
TYPICAL SCHEMATIC WIRING DIAGRAM
_ _ _+
(Heat pump units)
21
JP12
"7"CONN. NOT REQ'D FOR CS/FMX (FCU)-AHU
SEE NOTE-5
HVTB
LUG
1
TO BX, FMXUNITS 24V CIRCUIT
7
8
9
5
6
380/3PH/60HZ460V/3PH/60HZ UNITS
PLS. REFER UNIT NAME PLATE
WIRG DGM SUITS208V/230V/3PH/60HZ
POWER SUPPLY
CAP1
SEE HPS OPTION BELOW
USE FOR OPTION-3B ONLY
1615
20
21
41A
22A LPS
T1A
ATB1
L1
CB
T3A
COMP
T2A
24 VAC
R-V
25A[AI]
CAP2
TRANS
FM1
36A
35A
37A
L2
1
36B
FM2
35B
37B
T3A
L2
L3
CC
L1
JP537A
CRANKCASE HTR CONNECTION
C.HTR
17
17
20
22
26A
JP1 JP2
JP3
JP4
JP11
CC
COMP
1A[UVM] [SD] 1B
L1
17
L2
T1ATO CC
37BT2A37ATO JP5 TO CC TO JP5
SET POINTS
190 ± 15
450 ± 10
OPEN (PSIG)NAME
HPS
FCS
LPS 25 ± 5360 ± 15
290 ± 10
CLOSE (PSIG)
50 ± 5
OF A.H.U ACCORDINGLY. PLS REMOVE JP5TO BE CONNECTED TO ATB# 1,6,8,9,T3A & 37A NOTE: ATB# 1,6,8,9,T3A & 37A OF COND. UNIT
CONTROL & INTERCONN. DETAILS FOR FMX AHU W/O SYSTEMIZER
REFER TO UNITNAMEPLATE FORPOWER SUPPLY
N (SEE NOTE -7)
NOTES1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.
2. ANY WIRE REPLACEMENT SHOULD BE OF THE 900COR ITS EQUIVALENT.USE COPPER CONDUCTOR WIRES ONLY.
3. POWER MUST BE SUPPLIED TO CRANKCASEHEATER FOR MINIMUM OF 12 HOURS PRIOR TOSYSTEM START UP.
IF POWER IS OFF 6 HOURS OR MORE, CRANKCASEHEATER MUST BE ON FOR 12 HOURS BEFOREOPERATING THE SYSTEM.
FAILURE TO FOLLOW THESE INSTRUCTIONS MAYRESULT IN COMPRESSOR DAMAGE.
4. FUSED DISCONNECT SWITCH OR CIRCUITBREAKER TO BE PROVIDED BY END USER WITHRATING AS RECOMMENDED BY ZAMIL.
5. REMOVE JUMPER FOR AI OPTION. ROUTE AIWIRES FROM AHU.
6. USE DISCONNECT TAB OR SPLICE ONLY WHEREEVER REQUIRED FOR EXTENSION OF ORIGINALWIRE.
7. NEUTRAL LINE REQUIRED ON 380V-3Ph-60HzPOWER SUPPLY ONLY.
L3L2L1
UVM
1ATO ATB
1TO ATB
(REMOVE JP1)
3. VOLT FREE CONTACT OPTIONS FOR BX & FMX AHUB. COMP ON, OFF & TRIP [&] UNIT TRIP INDICATION OPTION FOR BX,FMX AHU
REMOVE JP5
DEFROST CONTROL OPTION FOR BX AHU ONLY (NOT APPLICABLE FOR 460V)
UNIT/COMP-TRIP
DCT-1
FR-1
2.SMOKE DETECTOR OPTION
REMOVE JP2
1. UVM OPTION
VFC-FROM CUSTOMER'SSMOKE DETECTOR
1A
ATB2
1B
ATB2
A. UNIT ON & OFF INDICATION
45
L1 DCT
UNIT ON
AR1-1 46
15ATB1
AR1
L2/N
UNIT OFF
AR1-1 47
T3A
43
OPTIONS
ATB217 41A
9 ATB1
ATB2
REMOVE JP4
44
37A
ATB2
55
ATB217
FR FR-2
ATB2
CC
A-2
B
COMP-TRIP
57
54
DCT-2
CC
A-2A
56
COMP-OFF
COMP-ON
58
FR-2
REMOVE JP3
25ALPS
DCT-3 ATB2
4. HPS OPTION
TO 23A HPS
INSTALLATION & START-UP INSTRUCTIONSSAFETY CONSIDERATIONSImproper installation, service, maintenance or use can cause explosion, fire, electrical shock or other conditions whichmay cause personal injury or property damage. Check with your nearest Zamil dealer/sales office for information orassistance. For detailed instructions/informations, please refer to corresponding IOM manual.
WarningBefore installation or servicing the system, always turn off main power supply. Electrical shock can cause personal injuryor death.
INSTALLATIONSTEP-1:Check equipment and job siteUnpack unit and move to final location taking care not to damage the unit. Remove screws holding the unit to woodenpallet and after removing wooden pallet, refix the screws.
STEP- 2:Installation on a solid, level mounting padFor proper drainage, the condensing unit must be raised off the mounting pad. If conditions require the unit be attachedto the pad, tie down bolts should be used.
When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping and service. Double the serviceaccess when multiple units are installed at one location.
On rooftop applications, locate unit at least 6" (152 mm) above roof surface. Place unit above a load-bearing wall, isolateunit and piping set from structure.
Arrange supporting members to adequately support unit and minimize transmission of vibration to building.
STEP-3:Piping connectionsOutdoor units should be connected to indoor units using field-supplied piping of refrigerant grade and correct size. Theliquid and suction line diameters can be determined from the physical data table. For piping requirements beyond 25 ft(7.62m), obtain information from your nearest Zamil dealer/sales office.
If either refrigerant piping or indoor coil is exposed to atmospheric conditions, it must be dehydrated to 500 microns toeliminate moisture contamination in the system.
It is advisable to size piping according to recommended ASHRAE methods. Install piping according to refrigerationstandard practice. Run refrigerant pipes as directly as possible, avoiding unnecessary turns and bends. Install refrigerantpipes carefully to prevent damaging the suction pipe insulation and vibration transmission to the structure.
Outdoor unit connected to factory matched indoor unitOutdoor unit contains correct system refrigerant charge for operation with matched indoor unit as given on coolingcapacity table and when connected with up to 25 ft (7.62 m) of field-supplied piping. Check refrigerant charge for maxi-mum efficiency.
Sweat connectionUse refrigerant grade piping. Service valves are closed from factory when shipped and ready for brazing. After wrappingthe service valve with a wet cloth, the piping set can be brazed to service valve using either silver rod or silfos rod brazingmaterial. When brazing completed, refrigerant piping and indoor coil are now ready for leak testing. This check shouldalso include all field and factory brazed joints.
22
23
ELECTRICALSTEP 1: INSTALLATIONA) Please ensure power supply to the unit is as per unit nameplate (Volts/Ph/Hz) requirements.
Caution: Operation of the unit on improper power supply will result in damage to the unit.
Note: Use copper wires of proper rating for all field wiring.
Warning: Before servicing or installation of the unit, always TURN OFF all power to the unit. There may be more thanone disconnect switch. Ensure all of them are turned off. Electrical shock can cause personal injury or death.
B) Ground & power wiresConnect power wires to terminal block per wiring diagram.
Connect ground wire to the ground lug inside the control box.
C) Control wiring between outdoor & indoor unitUse 16 gauge color-coded wire between the indoor and outdoor units (control wiring).
STEP 2: START-UP1) Energize crankcase heater for a minimum of 12 hours prior to the system start-up. To energize crankcase heater only,
set thermostat to "off" position and close electrical disconnect switch to the outdoor unit.
2) Fully open liquid/suction service valves.
3) Close electrical disconnect switch to energize the system.
4) Set room thermostat to desired temperature.
SYSTEM DESIGNTHE CLASSIC CONDENSING UNIT SYSTEM HAS BEEN DESIGNED BASED ON THE FOLLOWING:
• Intended for outdoor installation with free air intake and discharge.
• Minimum outdoor operating air temperature during cooling without low ambient operation option is 550F.
• Maximum outdoor operating air temperature during cooling is 1300F.
• For reliable operation, unit should be level on horizontal plane.
• Maximum elevation of indoor unit above or below the outdoor unit is: indoor unit above = 50 feet, indoor unit below=150 feet.
• For interconnecting refrigerant pipe lengths greater than 25 feet, check with your local Zamil sales office.
• Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type ofconnector provided.
24
PARTS LIST(Single compressor units)
MODEL NUMBER CX048H CX048M CX048F CX060C CX060H CX060M CX060FCOMPRESSOR 800-684-06 800-684-09 800-684-09 800-672-59 800-672-51 800-672-52 800-672-52
FAN MOTOR 800-544-02 800-544-02 800-547-32 800-544-02 800-544-02 800-544-02 800-547-32
FAN MOTOR CAPACITOR 800-353-15 800-353-15 800-353-15 800-572-84 800-353-15 800-353-15 800-353-15
CONDENSER FAN 800-224-49 800-224-49 800-224-49 800-224-49 800-224-49 800-224-49 800-224-49
COMPRESSOR CONTACTOR 800-095-00 800-095-00 800-095-00 800-736-46 800-097-00 800-095-00 800-095-00
TRANSFORMER (24V) 800-012-30 800-012-30 800-012-31 800-012-30 800-012-30 800-012-30 800-012-31
LOW PRESSURE SWITCH 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00
MODEL NUMBER CX036F CX042C CX042H CX042M CX042F CX048CCOMPRESSOR 800-684-07 800-684-02 800-684-05 800-684-09 800-684-08 800-684-03
FAN MOTOR 800-545-71 800-544-02 800-544-02 800-544-02 800-547-32 800-544-02
FAN MOTOR CAPACITOR 800-353-15 800-572-82 800-353-15 800-353-15 800-353-15 800-572-84
CONDENSER FAN 800-224-26 800-224-49 800-224-49 800-224-49 800-224-49 800-224-49
COMPRESSOR CONTACTOR 800-095-00 800-097-00 800-095-00 800-095-00 800-095-00 800-097-00
TRANSFORMER (24V) 800-012-31 800-012-30 800-012-30 800-012-30 800-012-31 800-012-30
LOW PRESSURE SWITCH 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00
MODEL NUMBER CX030C CX030H CX030M CX030F CX036C CX036H CX036MCOMPRESSOR 800-675-35 800-684-04 800-684-14 800-684-07 800-684-01 800-684-04 800-684-14
FAN MOTOR 800-545-64 800-545-64 800-545-64 800-545-71 800-545-64 800-545-64 800-545-64
FAN MOTOR CAPACITOR 800-572-84 800-353-15 800-353-15 800-353-15 800-572-23 800-353-15 800-353-15
CONDENSER FAN 800-224-26 800-224-26 800-224-26 800-224-26 800-224-26 800-224-26 800-224-26
COMPRESSOR CONTACTOR 800-097-00 800-095-00 800-095-00 800-095-00 800-097-00 800-095-00 800-095-00
TRANSFORMER (24V) 800-012-30 800-012-30 800-012-30 800-012-31 800-012-30 800-012-30 800-012-30
LOW PRESSURE SWITCH 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00
MODEL NUMBER CX075H CX075M CX075F CX090H CX090M CX090FCOMPRESSOR 800-674-23 800-674-24 800-674-25 800-674-76 800-674-77 800-674-78
FAN MOTOR 800-544-02 800-544-02 800-547-32 800-544-02 800-544-02 800-547-32
FAN MOTOR CAPACITOR 800-353-15 800-353-15 800-353-15 800-353-15 800-353-15 800-353-15
CONDENSER FAN 800-224-49 800-224-49 800-224-49 800-224-49 800-224-49 800-224-49
COMPRESSOR CONTACTOR 800-097-00 800-095-00 800-095-00 800-097-00 800-095-00 800-095-00
TRANSFORMER (24V) 800-012-00 800-012-00 800-012-01 800-012-00 800-012-00 800-012-01
LOW PRESSURE SWITCH 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00
HIGH PRESSURE SWITCH (OPTIONAL) 800-558-00 800-558-00 800-558-00 800-558-00 800-558-00 800-558-00
MODEL NUMBER CX100H CX100M CX100F CX120H CX120M CX120FCOMPRESSOR 800-674-79 800-674-80 800-674-81 800-674-65 800-674-66 800-674-67
FAN MOTOR 800-544-02 800-544-02 800-547-32 800-544-02 800-544-02 800-547-32
FAN MOTOR CAPACITOR 800-353-15 800-353-15 800-353-15 800-353-15 800-353-15 800-353-15
CONDENSER FAN 800-224-49 800-224-49 800-224-49 800-224-49 800-224-49 800-224-49
COMPRESSOR CONTACTOR 800-736-46 800-095-00 800-095-00 800-736-23 800-097-00 800-097-00
TRANSFORMER (24V) 800-012-00 800-012-00 800-012-01 800-012-00 800-012-00 800-012-01
LOW PRESSURE SWITCH 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00
HIGH PRESSURE SWITCH (OPTIONAL) 800-558-00 800-558-00 800-558-00 800-558-00 800-558-00 800-558-00
25
PARTS LIST
MODEL NUMBER CX075H CX075M CX075F CX090H CX090M CX090FCOMPRESSOR 800-684-04 800-684-14 800-684-07 800-684-05 800-684-09 800-684-08
FAN MOTOR 800-544-02 800-544-02 800-547-32 800-544-02 800-544-02 800-547-32
FAN MOTOR CAPACITOR 800-353-15 800-353-15 800-353-15 800-353-15 800-353-15 800-353-15
CONDENSER FAN 800-224-49 800-224-49 800-224-49 800-224-49 800-224-49 800-224-49
COMPRESSOR CONTACTOR 800-095-00 800-095-00 800-095-00 800-095-00 800-095-00 800-095-00
TRANSFORMER (24V) 800-012-14 800-012-14 800-012-14 800-012-14 800-012-14 800-012-14
LOW PRESSURE SWITCH 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00
HIGH PRESSURE SWITCH (OPTIONAL) 800-558-00 800-558-00 800-558-00 800-558-00 800-558-00 800-558-00
(Dual compressor units)
MODEL NUMBER CX150H CX150M CX150F CX180H CX180M CX180FCOMPRESSOR (Single),Scroll 800-674-17 800-674-18 800-674-19 N.A. N.A. N.A. .
COMPRESSOR (Dual), Scroll 800-674-23 800-674-24 800-674-25 800-674-79 800-674-80 800-674-81
FAN MOTOR 800-545-58 800-545-58 800-545-63 800-545-68 800-545-68 800-545-68
FAN MOTOR CAPACITOR 800-572-20 800-572-20 800-572-20 N.A. N.A. N.A.
CONDENSER FAN 800-224-23 800-224-23 800-224-23 800-224-23 800-224-23 800-224-23
COMP. CONTACTOR (Single),Scroll 800-098-65 800-736-22 800-736-22 N.A. N.A. N.A.
COMP. CONTACTOR (Dual), Scroll 800-097-00 800-095-00 800-095-00 800-736-48 800-095-01 800-095-01
TRANSFORMER (24V) 800-012-14 800-012-14 800-012-14 800-012-14 800-012-14 800-012-14
LOW PRESSURE SWITCH 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00
HIGH PRESSURE SWITCH (OPTIONAL) 800-558-00 800-558-00 800-558-00 800-558-00 800-558-00 800-558-00
MODEL NUMBER CX220H CX220M CX220F CX240H CX240M CX240FCOMPRESSOR, Scroll 800-674-65 800-674-66 800-674-67 800-674-36 800-674-37 800-674-38
COMP. CONTACTOR, Scroll 800-736-48 800-736-22 800-095-01 800-098-65 800-098-61 800-098-61
FAN MOTOR 800-545-68 800-545-68 800-545-68 800-555-06 800-555-06 800-555-06
CONDENSER FAN 800-224-23 800-224-23 800-224-23 800-224-28 800-224-28 800-224-28
TRANSFORMER (24V) 800-012-14 800-012-14 800-012-14 - - -
LOW PRESSURE SWITCH 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00
HIGH PRESSURE SWITCH (OPTIONAL) 800-558-00 800-558-00 800-558-00 800-558-00 800-558-00 800-558-00
MODEL NUMBER CX300H CX300M CX300F CX360H CX360M CX360FCOMPRESSOR, Scroll 800-674-17 800-674-18 800-674-19 800-674-70 800-674-71 800-674-72
COMP. CONTACTOR, Scroll 800-098-65 800-098-61 800-098-61 800-098-67 800-098-63 800-098-61
FAN MOTOR 800-555-05 800-555-06 800-555-06 800-555-05 800-555-06 800-555-06
FAN MOTOR CONTACTOR 800-098-51 800-098-51 800-098-51 800-098-51 800-098-51 800-098-51
CONDENSER FAN 800-224-28 800-224-28 800-224-28 800-224-28 800-224-28 800-224-28
LOW PRESSURE SWITCH 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00
HIGH PRESSURE SWITCH (OPTIONAL) 800-558-00 800-558-00 800-558-00 800-558-00 800-558-00 800-558-00
MODEL NUMBER CX100H CX100M CX100F CX120H CX120M CX120FCOMPRESSOR 800-684-06 800-684-09 800-684-09 800-672-51 800-672-52 800-672-52
FAN MOTOR 800-544-02 800-544-02 800-547-32 800-544-02 800-544-02 800-547-32
FAN MOTOR CAPACITOR 800-353-15 800-353-15 800-353-15 800-353-15 800-353-15 800-353-15
CONDENSER FAN 800-224-49 800-224-49 800-224-49 800-224-49 800-224-49 800-224-49
COMPRESSOR CONTACTOR 800-097-00 800-095-00 800-095-00 800-097-00 800-095-00 800-095-00
TRANSFORMER (24V) 800-012-14 800-012-14 800-012-14 800-012-14 800-012-14 800-012-14
LOW PRESSURE SWITCH 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00 800-557-00
HIGH PRESSURE SWITCH (OPTIONAL) 800-558-00 800-558-00 800-558-00 800-558-00 800-558-00 800-558-00