+ All Categories
Home > Documents > Air & Flue Gases System

Air & Flue Gases System

Date post: 05-Apr-2018
Category:
Upload: vijay-raj
View: 221 times
Download: 0 times
Share this document with a friend

of 38

Transcript
  • 7/31/2019 Air & Flue Gases System

    1/38

    1.0 MODULATING CONTROL

    1.1 FORCED DRAFT FANS PRESSURE CONTROL

    The F.D. fans pressure control loop is designed to maintain the pressure

    downstream regenerative air heaters at the proper value feeding the combustion airheader in order to match primary (tempering to mill resuction duct), secondary (to

    coal burners) and tertiary (additional air firing to AAF nozzles) air flow demand.

    The combustion air pressure set point (bases on boiler demand) is compared via

    high/low selecting logic to minimum and maximum pressure limits, then the

    resulting valve is compared to header pressure value and through the controller sets

    the demand for F.D. fans inlet control damper.

    The operator has a biasing capability to shift the combustion air pressure set point

    curve up or down of the established curve based on boiler test.

    The F.D. fans damper position demand is actually the average demand for each of

    the two fans; the operator can settle a bias in order to balance the incidental

    mismatch between the two fans.

    If one fan is on manual or forced, the fan on automatic compensates for the fan not

    participating in the control.

    Thus, the bias is continuously calculated when on or more fans are on hand.

    When the last is released to control (auto mode and no for cement), the bias is

    released to the operator at the value, if any, that is actually between the fans.

    To determine the error between demand and the individual fan, the fan control vane

    pitch position is compared to the individual fan biased demand; during normal

    operation, the two are kept equal through a high reset proportional plus integral

    controller.

    In case a F.D. fan motor is off and the other F.D. fan is in service, the control

    damper related to the fan not in service automatically closes.

    Proper firing action are performed according to the request from Burners

    Management System and Air & Flue Gases functional groups that force F.D. fans

    control dampers at proper position, that are:

    Fully open/closed to perform fan start/stop sequence

    Fully open for natural draft requirement

    1.2 REGENERATIVE AIR HEATER COLD END TEMPERATURE CONTROL

    The regenerative air heater cold end temperature control is designed to maintain a

    good relation between the combustion air and flue gases temperature to avoid the

    last one falls below the dew point temperature, thus the acids in the flue gases

    cannot be condensed and the extensive corrosion effect on heating surfaces of the

    regenerative air heater will be reduced.

    The above control loop is simple feedback control loop, based on the method to

    raise the raise the air temperature at regenerative air heater inlet by means of steam

  • 7/31/2019 Air & Flue Gases System

    2/38

    coil air heater (S.C.A.P.H.) and consequently the flue gases temperature will

    approximately increase of the same amount.

    Set point is function of boiler load (i.e. SH steam flow) corrected evaluating fuel

    (i.e. oil and/or coal) partition.

    The operator has a biasing capability to shift the combustion air temperature set

    point curve up or down of the established curve based on boiler test.

    One of the above control loop for each regenerative air heater is provided.

    1.3 S.C.A.P.H. CONDENSATE TANL LEVEL CONTROL

    The furnace draft pressure control is designed to provide the proper exhausting

    force for flue gases through the boiler, acting on I.D. fans control dampers.

    When I.D. fans are properly balanced with F.D. fans, the furnace pressure will be at

    the desired operating pressure.

    The I.D. fans are controlled by a feedforward plus feedback control which is thencorrected by any deviation of furnace pressure from set point.

    The furnace pressure signal is compared to the desired to the desired furnace

    pressure set point to develop the furnace pressure error.

    The feedforward for I.D. fans dampers position demand is developed from a

    program based on the air flow demand (i.e. F.D. fans dampers position demand,

    taking into account F.D, fan motors), by using this signal the I.D. fans can respond

    to load changes at the same time that F.D. fans do.

    This feedforward program is trimmed by integral and proportional action resulting

    from any furnace purser error.

    The integral and proportional action are separated so that when furnace pressure

    effort exceeds a certain deadband, proportional action becomes significant to

    rapidly adjust program, to return furnace pressure to the desired value.

    Then this corrected program becomes the I.D. fans load demand (i.e. I.D. fans

    dampers position).

    The I.D. fans damper position demand is actually the average demand for each of

    the two fans; the operator can settle a bias in order to balance the incidental

    mismatch between the two fans. If one fan is on manual or forced, the fan on

    automatic compensates for the fan not participating in the control.

    Thus, the bias is continuously calculated when one or more fans are on hand.

    When the last is released to control (auto mode and no forcement), the bias isreleased to the operator at the value, if any that is actually between the fans.

    To determine the error between demand and the individual fan, the control vane

    pitch position is compared to the individual fan biased demand; during normal

    operation, the two are kept equal through a high reset proportional plus integral

    controller.

    In case a I.D. fan motor is off and the other I.D, fan is in service, the control damper

    related to the fan not in service automatically closes.

    Proper firing action are performed according to the requires from Burners

    Management System and Air & Flue Gases functional groups that force I.D, fan

    dampers at proper position, that are: Fully open/closed to perform fans start/stop requence

  • 7/31/2019 Air & Flue Gases System

    3/38

    Fully open for natural draft requirement, if both I.D. fan motors are off

    Because of mater fuel trip and/or loss of flames and/or rapid loss of forced draft, the

    negative pressure in the furnace and in flue gases ducts may result in a large

    increase, due to:

    Sudden reduction of flue gases temperature in the first two cases In large increase of negative pressure at the I.D. fan suction in the last one

    This action may occur mach faster than the regular on line furnace draft control,

    therefore a separate high speed subsystem for implosion protection, based on the

    characterized furnace pressure signal evaluated by three separated wide range

    furnace pressure transmitters is p[provided downstream the A/M control stations so

    that it cannot be overridden by the operator.

    1.5 RECIRCULATING GASES FANS PRESSURE CONTROL

    The R.G. fans pressure control is designed to maintain the pressure at the proper

    value feeding the cold gases header in order to match cold gases tempering to mills

    resuction duct and C.G.R. nozzles flue gases flow demand.

    The cold gases pressure set point (based on boiler demand) is compared via

    high/low selecting logic to minimum and maximum, pressure limits, then the

    resulting value is compared to header pressure value and through the controller sets

    the demand for R.G. fans inlet control damper.

    The operator has a biasing capability to shift the cold flue gases pressure set point

    curve up or down of the established curve based on boiler test.

    The R.G. fans damper position demand is actually the average demand for each of

    the two fans; the operator can settler a bias in order to balance the incidentalmismatch between the two fans.

    If one fan is on manual or forced, the fan on automatic compensates for the fan not

    participating in the control.

    Thus, the bias is continuously calculated when one or more fns are on had.

    When the last is released to control (auto mode and no forcement), the bias is

    released to the operator at the value, if any, that is actually between the fans.

    To determine the error between demand and the individual fan, the fan inlet control

    damper position is compared to the individual fan biased demand; during normal

    operation, the two are kept equal through a high reset proportional plus integral

    controller.

    In case R.G. fan motor is off, the related control damper automatically closed.Both R.G. fans control dampers automatically close in case of boiler purge.

    Proper firing action are performed according to the request from Burners

    Management System and Air & Flue Gases functional groups that force R.G. fans

    control dampers at proper position that are:

    Fully open/closed to perform fan start/stop sequence

    Fully closed for natural draft.

    1.6 AFTER BURNING GRATE AIR FLOW CONTROL

    The A.B.G. air flow control is designed to maintain the air at the proper value in

    order to match the flow demand.

  • 7/31/2019 Air & Flue Gases System

    4/38

    The air flow set point (based on boiler load, i.e. SH steam flow) is compared to the

    related air flow value and through the controller sets the demand for the related

    A.B.G. air control damper.

    The operator has a biasing capability to shift the air flow set point curve up or down

    of the established curve based on boiler test.

    Two of the above control loop are provided, one for each section of the A.B.G.

    Proper firing action are performed according to the request from Burners

    Management System that force the A.B.G. control dampers at proper position, that

    are:

    Partially open (approx. 30% -to be defined-) too perform furnace purge

    sequence

    Last position for five minutes if the combustion air flow is below the purge

    rate at the time of the trip, waiting time for purge

    Fully open for natural draft requirement

    2.0 BINARY CONTROL

    2.0.00 FORWORD

    The air & flue gases system is structure as follows:

    Functional group: The operator puts in or out of service a complete lime of

    air and flue gases circuit consisting of the related Regenerative Air Heater (in

    the hereinafter paragraphs will be called as R.A.H.), I.D. fan, F.D. fan and

    relevant automatic dampers with a single command, if the functional group is in

    auto mode.Facilities to put in service each line separately or both lines in sequence are

    provided according to line selection.

    Functional subgroup: the operator puts in or out of service an eequipment

    and its associated items (dampers..). Each sequence is simplified, i.e.

    interruption facility is not available and the sequence is forced to manual in case

    of step failure (see typical command logic description). The following

    functional subgroups are provided, one for each line:

    Regenerative air heater functional subgroups: the operator puts in or out of

    service the selected R.A.H. and relevant automatic dampers with a single

    command if the functional subgroup is in auto mode. I.D. fan functional subgroup: the operator puts in or out of service the

    selected I.D. fan and relevant automatic dampers with a single command

    if the functional subgroup is in auto mode.

    F.D. fan functional subgroup: the operator puts in or out of service the

    selected F.D. fan and relevant automatic dampers with a single with a

    single command if the functional subgroup is in auto mode.

    Drive level: at this level the operator commands each device individually.

    Interlocks among different devices will always be guaranteed.

    2.1.00 AIR 7 FLUE GASES SYSTEM FUNCTIONAL GROUP

  • 7/31/2019 Air & Flue Gases System

    5/38

    This functional group commands the start-up and shut-down of the air & flue gases

    system in sequential mode, provided the functional group is selected in auto mode.

    The functional group is put in auto mode by the operator, via the auto/manual

    selection command; it is forced to manual in the following cases:

    Natural draft (after natural draft the functional group is released to

    automatic mode) After start-up or shut-down sequence end, if the functional group status

    changes

    At line selection (pulse-type command).

    2.1.01 AIR FLUE GASES SYSTEM SELECTION

    The operator chooses among following possibilities which line has to be put in or

    out of service:

    Only line 1 in or out of service

    Only line 2 in or out of service Both lines in or out of service; line 1as first, followed by line 2

    Both lines in or out of service; line 2 as first, followed by line 1

    The above mentioned selections are commanded form keyboard by depressing the

    selection push-button.

    The initial selected sequence cannot be changed until sequence itself has been

    completed or has failed.

    2.1.02 AIR 7 FULE GASES SYSTEM START-UP SEQUENCE

    The operator starts the sequence from keyboard by issuing the start command or

    from conventional control panel interface by depressing the start push-button,provided the functional group has been selected on auto mode and line selected.

    When the operator selects both lines to be put in service, the start-up sequence of

    the second line automatically starts when the first line start-up is complete.

    Each sequence step takes place if the following permissive is satisfied:

    Waiting time for purge not present

    a. The 1st step commands the air and flue gases system amperes opening. It is takes

    place if the following permissives are satisfied:

    R.A.H. 1(2) start permissives present (i.e. guide and support bearings

    cooling water flow adequate)

    All the related devices are available

    At least one of the following conditions present:

    air & flue gases line 1(2) selected

    air & flue gases line 1and 2 (2 and 1) selected

    air & flue gases line 2and 1 (1 and 2) selected and line 2 start-up

    sequence end;

    In this case the step is performed but the command is skipped.

    The relevant commands are set to fans and

    R.,A.H.s shut-off dampers individual drive levels, to fans control amperes and

    to secondary and tertiary air control dampers

  • 7/31/2019 Air & Flue Gases System

    6/38

    b. The 2nd step commands the R.A.H. start-up. It takes place after checking the

    completion of the 1st step within the proper che3ck time, that is:

    At least one air flow path open OR the other air and gases line in service

    The relevant command is sent to the functional subgroup R.A.H. start-up

    sequence.

    c. The 3rd step commands the related I.D. fan start-up. It takes place after checking

    the completion of the 2nd step within the proper check time, that is :

    R.A.H. in service

    The relevant command is sent to the functional subgroup I.D. fan start-up

    sequence.

    d. The 4th step commands the related F.D. fan start-up. It takes place after checking

    the completion of the 3rd step within the proper check time, that is:

    I.D. fan in service

    The relevant command is sent to the functional subgroup F.D. fan start-up

    sequence.

    e. After completion of the 4th step the air and flue gases line start-up sequence is

    complete. If air & flue gases lines 2 and 1 (1 and 2) are selected, line 2(1) start-

    up permissive mist be satisfied, in order to start the second sequence as soon as

    the first one ends.

    Therefore, at time 1(2) start-up sequence end, the alarm start up line 2(1)

    require and on permissives will be issued in any of the following cases: Line 2(1) start-up permissives not present

    Waiting time for purge

    Functional group selected on manual mode

    2.1.03 AIR & FLUE GASES SYSTEM SHUT-DOWN SEQUENCE

    The operator starts the sequence from the keyboard by issuing the stop command or

    from conventional control panel interface by depressing the stop push-button,

    provided the functional group has been selects on auto mode and line selected.

    Then the operator selects both lines to be stopped, the shut-down sequence of the

    second line automatically starts when the first line shut-down is complete.Each sequence step talks place if the following permissive is satisfied:

    Waiting time for purge not present

    a. The 1st commands the F.D. fan shut-down. It takes place if the following

    permissives are satisfied:

    All functional subgroups relevant to line 1 (2) in automatic mode

    At least one of the following conditions present:

    air & flue gases line 1(2) selected

    air & flue gases line 1and 2 (2 and 1) selected

    air & flue gases line 2and 1 (1 and 2) selected and line 2 shut-downsequence end.

  • 7/31/2019 Air & Flue Gases System

    7/38

    The relevant command is sent to the functional subgroup F.D. fan shut-down

    sequence.

    b. The 2nd step commands the I.D. fan start- down. It takes place after checking the

    completion of the 1st step within the proper check time, that is:

    F.D. fan motor off

    The relevant command is sent to the functional subgroup I.D. fan start-down

    sequence.

    c. The 3rd step commands the related R.A.H start-down. It takes place after

    checking the completion of the 2nd step within the proper check time, that is:

    I.D. fan motor off.

    The relevant command is sent to the functional subgroup R.A.H. start-down

    sequence.

    d. After completion of the 3rdh step the air and flue gases system start-down

    sequence is complete.

    If air & flue gases lines 2 and 1 (1 and 2) are selected, line 2(1) start-up

    permissive mist be satisfied, in order to start the second sequence as soon as the

    first one ends.

    Therefore, at line 1(2) start-down sequence end, the alarm start down line

    2(1) require and on permissives will be issued in any of the following cases:

    Line 2(1) start-up permissives not present

    Waiting time for purge

    Functional group selected on manual mode

    2.1.04 AIR & GASES SYSTEM COUNTING

    To satisfy at least one air path open permissive, required by first air and flue

    gases equipment start-up, command provided to perform all shut-off and control

    dampers opening as follows:

    From air and flue gases functional group: if no air and flue gases line is in

    service both R.A.H.s inlet and outlet air and flue gases dampers, both F.D.

    fans dampers, all secondary and tertiary air dampers are required to open.

    From I.D. fan functional subgroup: if the other I.D. fan is not in service bothF.D. fans dampers, secondary and tertiary air dampers are required to open.

    From F.D. fan, functional subgroup: if the other F.D. fan is not in service

    the dampers of other F.D. fan, secondary and tertiary air dampers are

    required to open

    After least one air path open permissive is satisfied when all the hereinafter

    conditions occurs:

    All shut-off dampers of one R.A.H. are fully open

    Shut-off damper of one F.D. fan fully open and related control damper not

    closed

    At least 3 mill air paths open

  • 7/31/2019 Air & Flue Gases System

    8/38

    2.2.00 REGENERATIVE AIR HEATER SYSATEM FUNCTIONAL SUBGROUP

    This functional subgroup commands the start-up and shut-down of the R.A.H. and

    the automatic dampers in sequential mode, provided the functional subgroup is

    selected in auto mode.

    The functional subgroup is put in auto mode by the operator, via the auto/manualselection command; it is forced to manual in any of the following cases:

    R.A.H. trip

    After start-up or shut-down sequence end if the functional subgroup status

    changes

    Natural draft (after natural draft the functional group is released to auto)

    Two of the above mentioned functional subgroups are provided, one for each

    R.A.H.

    2.2.01 REGEENERATIVE AIR HEATER 1 START-UP SEQUENCE

    The operator starts the sequence from keyboard by issuing the start command or

    from conventional control panel interface by depressing the start push-button, or the

    sequence is also automatically started by a logic signal generated at higher

    hierarchical level.

    Each sequence step takes place if the following permissive is satisfied:

    Waiting time for purge not present

    a. The 1st step commands the selected R.A.H. 1 bearings oil pumps motor start

    and shut-off dampers opening; it takes place if the following permissives are

    satisfied: All the related devices are available

    R.A.H. 1 start permissives present (i.e. guide and support bearings

    cooling water flow adequate

    The relevant commands are sent to the individual drive levels R.A.H. 1 guide

    bearing oil pump, R.A.H. 1 support bearing oil pump, R.A>H. 1 damper

    upstream S.C.A. P.H. 1, Air damper at R.A.H. 1 outlet, Flue gases damper

    at R.A.H. 1 inlet and R.A.H. 1 damper downstream ESP 1

    b. 2nd step commands the selected R.A.H. 1 motor starting; it takes place after

    checking the completion of the 1st step within the proper check time, that is: R.A.H. 1 damper upstream S.C.A.P.H, 1 open

    Air damper at R.A.H. 1 outlet open

    Flue gases damper at R.A.H. 1 inlet open

    R.A.H. 1 damper downstream ESP 1 open

    R.A.H. 1 guide bearing lubricating oil temperature adequate OR related

    pump in service

    R.A.H. 1 support bearing lubricating oil temperature adequate OR related

    pump in service

    The relevant command is sent to the individual drive level R.A.H. 1 motor.

  • 7/31/2019 Air & Flue Gases System

    9/38

    c. After completion of the 2nd step, the R.A.H. 1 sequence is complete.

    The signal of the R.A.H. 1 in service is generated when all the following

    conditions are satisfied:

    At least one R.A.H. 1 motor running

    R.A.H. 1 damper upstream S.C.A.P.H. 1 open

    Air damper at R.A.H. 1 outlet open

    Flue gases damper at R.A.H. 1 inlet open

    R.A.H. 1 damper downstream ESP 1 open

    2.2.02 REGENERATIVE AIR HEATER SHUT-DOWN SEQUENCE

    The operator stats the sequence from keyboard by issuing the stop command or

    from conventional control panel interface by depressing the stop push-button, or the

    sequence is also automatically started by a logic signal generated at higher

    hierarchical level.

    Each sequence step takes place if the following permissive is satisfied: Waiting time for purge not present

    a. The 1st step commands the R.A.H. 1 dampers closing; it takes place if at least

    one of the following permissives is satisfied

    The other R.A.H. in service

    Both I.D. fans motor off

    The relevant commands are sent to the individual drive levels R.A.H. 1 damper

    atS.C.A. P.H. 1 inlet, Air damper at R.A.H. 1 outlet, Flue gases damper at

    R.A.H. 1 inlet and R.A.H. 1 damper downstream ESP 1

    The relevant requirements are set to R.A.H. 1 dampers, and it will be effective

    only if the R.A.H. 1 is not the last in service; that means, according to NFPA

    rules, the last R.A.H, will be stopped with open dampers.

    b. The 2nd step commands the selected R.A.H. 1 motor starting; it takes place after

    checking the completion of the 1st step within the proper check time, i.e. the

    following permissive is satisfied:

    R.A.H. 1 damper (i.e. upsteream S.C.A.PH. 1, outlet air, inlet flue gases

    and downstream ESP) closed

    Both I.D. fans motor off AND R.A.H. 2 not in service

    The relevant command is sent to the individual drive level R.A.H. 1 motor.

    The R.A.H. 1 shut-down command is memorized to allow the completion of the

    R.A.H. 1 shut-down sequence without expecting the R.A.H, 1 motor off signal,

    which will be available after several hours (up to 20 hours), when the R.A.H. 1

    has been cooled.

    The R.A.H. shut-down memory (running for cooling) is set in the following

    cases:

    The stopping request comes from logic and at least one of the two

    R.A.H. 1 motors is running;

  • 7/31/2019 Air & Flue Gases System

    10/38

    The operator tries to stop the R.A. H. 1 motor A and all the following

    conditions are present:

    R.A.H. 1 motor A is running;

    R.A.H. 1 gas outlet temperature is not lower than minimum;

    the above mentioned R.A.H. 1 motor shut-down permissive is satisfied.

    Once the running for cooling signal is active, the motor will be automatically

    stopped as soon as R.A.H. 1 gas outlet temperature becomes lower than

    minimum (or cooling time has been expired).

    The R.A.H. running for cooling memory is reset (and the running for cooling

    signal deleted) in the following cases:

    When the R.A.H. 1 start is required again;

    When R.A.H. 1 motor shut-down permissive disappears (the running for

    cooling memory can be set only if such permissive is present);

    If during cooling time, both R.A.H. motors are stopped for 30 s (e.g. in

    case of R.A.H. trip).After cooling time has expired the running for cooling signal disappears, in

    order to have the permissive to start the R.A.H. motors again.

    c. The 3rd step commands the R.A.H, 1 bearings oil pumps motors stopping; it

    takes place after checking the completion of the 2 nd step within the proper check

    time, that is:

    R.A.H. 1 running for cooling OR both R.A.H. 1 motors off

    The relevant commands are sent to the individual drive levels R.A.H. 1 guide

    bearing oil pump and R.A.H., 1 support bearing oil pump.

    d. After comp0letion of the 3rd step, the R.A.H. 1 shut-down sequence is complete

    2.2.03 R.A.H. 1 MOTOR SELECTION

    The choice of the R.A.H. 1 motor as operating or as stand-by duty ius selected by

    the operator through the keyboard.

    The operator can select one R.A.H. 1 motor running and the other one as stand-by

    or can choose manual selection and in this case both pumps can be remotely started

    by the operator. Motor selection cannot be changed during functional subgroup

    start-up.

    2.2.04 R.A.H. 1 MOTOR

    a. Start

    The operator starts R.A.H. 1 motor issuing the related command from keyboard;

    it also automatically starts by a logic signal generated at higher hierarchical

    level, if selected.

    If selected as stands-by, the R.A.H. 1 motor is also started automatically in case

    of failure of the other motor.

    The motor starts if the following permissives are present:

    The other motor is nor selected OR the other motor is in failure

  • 7/31/2019 Air & Flue Gases System

    11/38

    The other motor has been off for 15 s (to be defined), in order to allow

    centrifugal clutch disengaging

    R.A.H. 1 guide bearing lubricating oil temperature adequate (OR at least

    one guide bearing lubricating oil pump in service)

    R.A.H. 1 guide bearing cooling water flow greater than minimum

    R.A.H. 1 support bearing lubricating oil temperature adequate (OR at leastone support bearing lubricating oil pump in service)

    R.A.H. 1 support bearing cooling water flow greater than minimum

    Natural draft not required.

    b. Stop

    The operator stops the R.A.H. 1 motor by issuing the related command from

    keyboard; the R.A.H. 1 motor also automatically stops by a logic signal

    generated at higher hierarchical level. If the R.A.H. 1 gas outlet temperature is

    lower than minimum, the motor is stopped at once, other wise the stoppingrequest is stored in the running for cooling memory, described at functional

    group shut-down sequence (2nd step).

    The motor stops if the following stop permissive is present:

    R.A.H. 1 motor shut down permiossive, described at functional group

    shut-down sequence (2nd step)

    c. Protection stop

    The R.A.H. 1 motor A is forced to stop in any of the following cases:

    When R.A.H. 1 motor A failure signal occurs;

    When R.A.H. 1 trip signal occurs.

    Two of the above the drive (motor A and motor B) are provided for each R.A.H.

    2.2.05 R.A.H. 1 MOTOR FAILURE AND TRIP

    The R.A.H. 1 Motor failure signal is generated when R.A.H. 1 is service and any

    of the following conditions occurs:

    R.A.H. 1 rotation loss (see the following 2.2.06)

    R.A.H. 1 motor start failure

    This signal will provide to start the R.A.H. 1 stand-by motor; if within 30 secondthe trip conditions (i.e. rotation loss or motor trip) are not deleted by the start-up of

    the stand-by motor the R.A.H. 1 trip signal occurs.

    The conditions causing the trip are memorized and alarmed. After the condition

    causing the trip returns to a non trip status, the memories are reset by the operator

    depressing the appropriate reset push-button via keyboard.

    2.2.06 R.A.H. 1 ROTATION LOSS DETECTION

    R.A.H. 1 rotation switches monitoring is active when at least one R.A.H. 1 motor is

    running. When rotation loss is detected, the running motor(s) is (are) declared infailure, as described in the previous 2.2.05

  • 7/31/2019 Air & Flue Gases System

    12/38

    Rotation loss detection is performed as follows:

    1. If a rotation switch has been closed for at least 5 s (to be

    defined):

    At once, an alarm is given to the operator (switch closed too long);

    If the other rotation switch is nor detected within one revolution time (sincethe last detection it), rotation loss is detected;

    2. If a rotation switch is nor detected with one revolution (since

    the last detection of it):

    At once, an alarm is given to the operator (switch closed too long);

    If the other rotation switch is not detected within one revolution time (since

    the last detection of it), rotation loss is detected;

    So, in the first case rotation loss is detected not later than half a revolution time

    after R.A.H. stopping, while in the second case rotation loss is detected not later

    than one revolution time after R.A.H. stopping. In any case, if only one limit switchis out of order, an alarm is given to the operator, but the rotation loss is not

    declared.

    2.2.07 R.A.H. 1 SUPPORT BEARING LUBRICSAYTING OIL PUMP MOTOR

    SELECTION

    The choice of the R.A.H. 1 support bearing lubricating oil pump as operating or as

    stand-by duty is selected by the operator through the keyboard.

    The operator can select one R.A.H. 1 support bearing lubricating oil pump running

    and the other one as stand-by or can choose manual selection and in this case both

    pumps can be remotely started by the operator.

    2.2.08 R.A.H. 1 SUPPORT BEARING LUBRICATING OIL PUMP MOTOR

    a. Start

    The operator starts R.A.H. 1 support bearing lubricating oil pump motor by

    issuing the related command from keyboard; it also automatically starts, if

    R.A.H. 1 support bearing lubricating oil temperature is high, in any of the

    following cases:

    If the pump is selected, by a logic signal generated at higher hierarchicallevel:

    If the pump is selected, when R.A.H. 1 is running;

    If the pump is selected as stand-by, in case of failure of the other pump.

    The pump starts if any of the following permissives is satisfied:

    The other pump is nor selected;

    The other pump is in failure.

    b. Stop

  • 7/31/2019 Air & Flue Gases System

    13/38

    The operator stops the R.A.H. 1 support bearing lubricating oil pump motor by

    issuing command from keyboard; it also automatically stops if any of the

    following cases:

    When R.A.H. 1 support bearing oil temperature is lower than minimum

    for 60 s;

    By a logic signal generated at higher hierarchical level

    The motor stops if at least one of the following strop permissives is present:

    Lubricating oil temperature lower than minimum for 60 s;

    Other pump in service;

    Both R.A.H. 1 motors off.

    c. Protection stop

    For each pump, the related R.A.H. 1 support bearing lubricating oil pump

    failure signal is generated when any of the following conditions occurs: Pump motor start failure (e.g. electrical overload);

    Low delivery pressure for 3 s with pump motor running for 5 s.

    The conditions causing the failure are memorized and alarmed. After the

    condition causing the failure returns to a non failure status, the memories are

    reset by the operator depressing the appropriate reset push-button via keyboard.

    Each R.A.H. 1 support bearing lubricating oil pump motor is forced to stop

    when the following condition arises:

    Pump failure

    Two of the above drive are provided

    2.2.09 R.A.H. 1 GUIDE BEARING LUBRICATING OIL PUMP MOTOR SELECTION

    The choice of the R.A.H. 1 guide bearing lubricating oil pump as operating or as

    stand-by duty is selected by the operator through the keyboard.

    The operator can select one R.A.H. 1 guide bearing lubricating oil pump running

    and the other one as stand-by or can choose manual selection and in this case both

    pumps can be remotely started by the operator.

    2.2.10 R.A.H. 1 GUIDE BEARING LUBRICATING OIL PUMP MOTOR

    a. Start

    The operator starts R.A.H. 1 guide bearing lubricating oil pump motor by

    issuing the related command from keyboard; it also automatically starts, if

    R.A.H. 1 guide bearing lubricating oil temperature is high, in any of the

    following cases:

    If the pump is selected, by a logic signal generated at higher hierarchical

    level:

    If the pump is selected, when R.A.H. 1 is running;

    If the pump is selected as stand-by, in case of failure of the other pump.

  • 7/31/2019 Air & Flue Gases System

    14/38

    The pump starts if any of the following permissives is satisfied:

    The other pump is nor selected;

    The other pump is in failure.

    b. Stop

    The operator stops the R.A.H. 1 guide bearing lubricating oil pump motor by

    issuing command from keyboard; it also automatically stops if any of the

    following cases:

    When R.A.H. 1 guide bearing oil temperature is lower than minimum

    for 60 s;

    By a logic signal generated at higher hierarchical level

    The motor stops if at least one of the following strop permissives is present: Lubricating oil temperature lower than minimum for 60 s;

    Other pump in service;

    Both R.A.H. 1 motors off.

    c. Protection stop

    For each pump, the related R.A.H. 1 guide bearing lubricating oil pump

    failure signal is generated when any of the following conditions occurs:

    Pump motor start failure (e.g. electrical overload);

    Low delivery pressure for 3 s with pump motor running for 5 s.

    The conditions causing the failure are memorized and alarmed. After thecondition causing the failure returns to a non failure status, the memories are

    reset by the operator depressing the appropriate reset push-button via keyboard.

    Each R.A.H. 1 support bearing lubricating oil pump motor is forced to stop

    when the following condition arises:

    Pump failure

    Two of the above drive are provided

    2.2.11 R.A.H. 1 DAMPER UPSTREAM S.C.A.P.H.

    a. Open

    The operator opens the damper by issuing the related command from keyboard,

    it also automatically opens by a logic signal generated at higher hierarchical

    level.

    No permissive is required.

    b. Protection open

    The damper is forced to the position when the following condition occurs:

    Natural draft required

  • 7/31/2019 Air & Flue Gases System

    15/38

    c. Close

    The operator closes the damper by issuing the related command from keyboard,

    it also automatically closes by a logic signal generated at higher hierarchical

    level. The damper closes if at least one of the following permissive is present:

    R.A.H. 2 in service Both I.D. fans motor off

    If R.A.H. 1 is not in service, the damper also closes (pulse command) when it

    has been opened in order to provided the open flow path.

    Any of the above permissives and additional stop condition shall be enabled by

    Waiting time for purge nor required.

    d. Protection close

    The damper is forced to the closed position when the R.A.H. 1 trip signal occurs

    enabled by Closing permissive satisfied AND Natural draft not required.

    2.2.12 AIR DAMPERAT R.A.H. 1 OUTLET

    a. Open

    The operator opens the damper by issuing the related command from keyboard,

    it also automatically opens by a logic signal generated at higher hierarchical

    level.No permissive is required.

    b. Protection open

    The damper is forced to the position when the following condition occurs:

    Natural draft required

    c. Close

    The operator closes the damper by issuing the related command from keyboard,

    it also automatically closes by a logic signal generated at higher hierarchical

    level. The damper closes if at least one of the following permissive is present: R.A.H. 2 in service

    Both I.D. fans motor off

    If R.A.H. 1 is not in service, the damper also closes (pulse command) when it

    has been opened in order to provided the open flow path.

    Any of the above permissives and additional stop condition shall be enabled by

    Waiting time for purge nor required.

    d. Protection close

  • 7/31/2019 Air & Flue Gases System

    16/38

    The damper is forced to the closed position when the R.A.H. 1 trip signal occurs

    enabled by Closing permissive satisfied AND Natural draft not required.

    2.2.13 FLUE GASES DAMPER AT R.A.H. 1 INLET

    a. Open

    The operator opens the damper by issuing the related command from keyboard,

    it also automatically opens by a logic signal generated at higher hierarchical

    level.

    No permissive is required.

    b. Protection open

    The damper is forced to the position when the following condition occurs:

    Natural draft required

    c. Close

    The operator closes the damper by issuing the related command from keyboard,

    it also automatically closes by a logic signal generated at higher hierarchical

    level. The damper closes if at least one of the following permissive is present:

    R.A.H. 2 in service

    Both I.D. fans motor off

    If R.A.H. 1 is not in service, the damper also closes (pulse command) when it

    has been opened in order to provided the open flow path.

    Any of the above permissives and additional stop condition shall be enabled by

    Waiting time for purge nor required.

    d. Protection close

    The damper is forced to the closed position when the R.A.H. 1 trip signal occurs

    enabled by Closing permissive satisfied AND Natural draft not required.

    2.2.14 R.A.H.1 DAMPER DOWNSTREAM ESP

    a. Open

    The operator opens the damper by issuing the related command from keyboard,

    it also automatically opens by a logic signal generated at higher hierarchical

    level.

    No permissive is required.

    b. Protection open

    The damper is forced to the position when the following condition occurs:

    Natural draft required

    c. Close

  • 7/31/2019 Air & Flue Gases System

    17/38

    The operator closes the damper by issuing the related command from keyboard,

    it also automatically closes by a logic signal generated at higher hierarchical

    level. The damper closes if at least one of the following permissive is present:

    R.A.H. 2 in service

    Both I.D. fans motor off

    If R.A.H. 1 is not in service, the damper also closes (pulse command) when it

    has been opened in order to provided the open flow path.

    Any of the above permissives and additional stop condition shall be enabled by

    Waiting time for purge nor required.

    d. Protection close

    The damper is forced to the closed position when the R.A.H. 1 trip signal occurs

    enabled by Closing permissive satisfied AND Natural draft not required.

    2.3.00 I.D. FAN SYSTEM FUNCTIONAL SUBGROUP

    This functional subgroup commands the start-up and shut-down of the related I.D.

    fan and the automatic dampers in sequential mode, provided the functional

    subgroup is selected in auto mode.

    The functional subgroup is put in auto mode by the operator, via the auto/manual

    selection command; it is forced to manual in any of the following cases:

    Related I.D. fan trip After start-up or shut-down sequence end, if the functional subgroup status

    changes

    Natural draft (after natural draft the functional group is released to auto)

    Two of the above mentioned functional subgroup are provided, one for each I.D.

    fan.

    2.3.01 I.D. FAN START-UP SEQUENCE

    The operator starts the sequence from keyboard by issuing the start command or

    from conventional control panel interface by depressing the start push-button, thesequence is also automatically started by a logic signal generated at higher

    hierarchical level.

    Each sequence step takes place if the following permissive is satisfied:

    Waiting time for purge not present

    a. The 1st step commands the I.D. fan 1 control oil system and cooling air

    fan system start-up; it takes place if the following permissives are

    satisfied:

    All the related devices are available

    At least one R.A.H. in service

  • 7/31/2019 Air & Flue Gases System

    18/38

    The relevant commands are sent to the individual drive levels I.D. fan 1 control

    and lubricating oil pump and I.D. fan 1 cooling and sealing air fan.

    b. The 2nd step commands all the dampers opening; it tasks place after checking

    the completion of the 1st step within the proper check time, that is:

    I.D. fan 1 start-up permisives satisfied (i.e. I.D. fan 12 lubricating oil and

    cooling air auxiliary subsystem in service with oil pressure adequate for

    start), or fan motor already running

    At least one R.A.H. in service

    The relevant commands are sent to fans and R.A.H.s shut-off dampers

    individual drive levels and to fans control dampers and secondary and tertiary

    air control dampers

    c. The 3rd step commands the I.D. fan 1 dampers closing; it takes place after

    checking the completion of the 2nd step within the proper check time, that is:

    At least one air flow path open

    I.D. fan 2 dampers open

    In order to avoid control damper opening at 3rd step end, the related command is

    saved in a dedicated memory, that is reset incase of sequence manual selection

    or at the end of the sequenced, when the control damper is released to auto.

    The relevant commands are sent to the individual drive levels I.D. fan 1

    suction damper, I.D. fan 1 discharge damper and to I.D. fan 1 controldamper, they are effective only if fan motor is not running.

    d. The 4th commands the I.D. fan 1 motor start; it takes place after checking the

    completion of the 3rd step within the proper check time, that is:

    I.D fan 1 start-up permissives satisfied (i.e. I.D. fan 1 lubricating oil and

    cooling air auxiliary subsystems in service with oil pressure adequate for

    start.

    I.D. 1 fan control damper closed

    I.D. 1 fan suction damper closed

    I.D. 1 fan discharge l damper closed

    If the fan motor is already running, no permissive is required.

    The relevant command is sent to the individual drive level I.D. fan 1 motor.

    e. The 5th step commands the I.D. fan 1 suction and discharge dampers opening; it

    takes place after checking the completion of the 4 th within the proper check

    time, that is:

    I.D. fan 1 motor has been running for 30 s.

    The relevant commands are sent to the individual drive level I.D. fan 1 suction

    damper and I.D. fan 1 discharge damper.

  • 7/31/2019 Air & Flue Gases System

    19/38

    f. The 6th step releases the I.D. 1 control damper in auto; it takes place after

    checking the completion of the 5th step within the proper check time, that is:

    I.D. fan 1 suction damper open

    I.D. fan 1 discharge damper open

    The relevant requirement is sent to I.D. fan 1 control damper

    g. After completion of the 6th step, the I.D. fan 1 start-up sequence is complete

    The signal of the I.D. fan 1 in service is generated when all the following conditions

    are satisfied:

    I.D. fan 1 motor running for 30 s

    I.D. fan 1 suction damper open

    I.D. fan 1 discharge damper open

    I.D. fan 1 start-up permissives satisfied (i.e. I.D. fan 1 lubricating oil and

    cooling air auxiliary subsystems inservice).

    2.3.02 I.D. FAN SHUT-DOWN SEQUENCE

    The operator starts the sequence from the keyboard by issuing the stop command or

    from conventional control panel interface by depressing the stop push-button, the

    sequence is also automatically started by a logic signal generated at higher

    hierarchical level.

    Each seque3nce step takes place if the following permissive is satisfied:

    Waiting time for purge nor present.

    a. The 1st step commands I.D. fan 1 control damper closing; it takes place if atleast one of the following permissives is satisfied:

    Both F.D. fans off

    The other I.D. fan in service

    In order to avoid control damper opening at 1st step end, the command is saved

    in a dedicated memory, that is reset incase of sequence manual selection or at

    the end of the sequenced, when the fan motor has been stopped for 30s (at this

    point, if the other I.D. fan is service, forcement in the analog control section

    keeps the control damper closed).

    The relevant requirement is sent to I.D. fan 1 control damper, and it will be

    effective only if the I.D. fan 1 is not the last inservice; that means, according to

    NFPA rules, the last I.D. fan will be stopped with dampers open.

    b. The 2nd step commands the I.D. fan 1 suction and discharge dampers closing; it

    takes place after checking the completion of the 1st step within the proper check

    time, that is:

    I.D. fan 1 control damper closed (or the other I.D. fan not in service).

    As per the above control damper this command will take place only if the other

    I.D. fan is still running.

  • 7/31/2019 Air & Flue Gases System

    20/38

    The relevant commands are sent to the individual drive level I.D. fan 1 suction

    damper and I.D. fan 1 discharge damper.

    c. The 3rd step commands the I.D. fan 1 motor stop; it takes place after checking

    the completion of the 2nd step within the proper check time, that is:

    I.D. fan 1 suction and discharge dampers closed (or the other I.D. fan notinservice).

    The relevant command is sent to the individual drive level IO.D. fan 1 motor.

    d. The 4th step commands the I.D. fan 1 control oil system and cooling air fan

    system stopping; it takes place after checking the completion of the 3 rd step

    within the proper check time, i.e. the following permissive is satisfied:

    I.D. fan 1 motor oil and cooling air stop permissive.

    Such permissive is issued when the following condition is verified:

    I.D. fan 1 motor off for 30 s

    The relevant commands are sent to the individual drive levels I.D. fan 1 control

    and lubricating oil pump and I.D. fan 1 cooling and sealing

    The oil pumps and air fans stop commands are memorized to allow the

    completion of the I.D. 1 shut-down sequence without expecting the pumps and

    fans motors off signals, which will be available after several minutes (up to 1

    hour), when the I.D. 1 bearing and hydraulic and bearing rooms have been

    cooled.

    The oil pumps shut-down memory (running for cooling) is set inset in thefollowing cases:

    The stopping request comes from logic (functional subgroup or I.D. fan

    trip) and at least one of the two I.D. fan 1 oil pump motors is running.

    The operator tries to stop the I.D. fan 1 oil pump A (B) motor and all the

    following conditions are present:

    I.D. fan 1 oil pump motor A (B) stop permissives satisfied; I.D. fan 1 bearing temperatures are not lower than minimum; I.D. fan 1 oil pump motor A (B) is running; I.D. fan 1 oil pump motor B (A) is not running (or it is in failure).

    Once the running for cooling signal is active, the pump motor will be

    automatically stopped as soon as I.D. fan 1 beating temperatures become lower

    than minimum (or cooling time has been expired).

    The oil pump shut-down memory (running for cooling) is reset (and the running

    for cooling signal deleted) in the following cases:

    When any oil pump start is required again;

    When I.D. fan 1 control oil and cooling air stop permissive disappears

    (the running for cooling memory can be set only if such permissive ispresent);

  • 7/31/2019 Air & Flue Gases System

    21/38

    In case of IU.D, fan control oil request (for natural draft the running

    for cooling memory can be set only if such request is not present);

    If, during cooling time, both oil pump motors are stopped for 30 s.

    The air fans shut-down memory (running for cooling) is set in the following

    cases: The stopping request comes from logic (functional subgroup or I.D. fan

    trip) and at least one of the two I.D. fan 1 air fan motors is running;

    The operator this to stop the I.D. fan 1 air A (B) motor and all the

    following conditions are present:

    I.D. fan 1 oil pump motor A (B) stop permissives satisfied; I.D. fan 1 Hydraulic and bearing rooms temperatures are not lower than

    minimum;

    I.D. air fan 1 motor A (B) is running;

    I.D. air fan 1 motor B (A) is not running (or it is in failure).

    Once the running for cooling signal is active; the fan motor will be

    automatically stopped as soon as I.D. fan 1 hydraulic and bearing rooms

    temperatures become lower than minimum (or cooling time has been expired).

    The air fans shut-down memory (running for cooling) is reset (and the running

    for cooling signal delet4d) in the following cases:

    When any air fan start is required again;

    When I.D fan 1 control oil and cooling air stop permissive disappears

    (the running for cooling memory can be set only if such permissive ispresent);

    If, during cooling time, both air fan motors are stopped for 30 s.

    e. After completion of the 4th step, the I.D.fan 1 shut-down sequence is complete

    Therefore, as above explained , if the I.D. fan 1 is the last one to be shut-down,

    it will be stopped with the suction and discharge shut-off dampers open and the

    control damper modulated to avoided excessive furnace pressure transients.

    2.3.03 I.D. FAN 1 MOTOR

    a. Te operator starts the I.D. fan 1 motor by issuing the command from the

    keyboard or from conventional control panel interface by depressing the

    start push-button, it also automatically starts by a logic signal generated

    at higher hierarchical level. The motor starts if the following permissives

    are present:

    I.D. fan 1 control oil permissives re present:

    I.D. fan 1 control oil flow adequate

    At least on I.D. fan 1 cooling air fan in service

    At least one R.A.H. in service I.D. fan 1 shut-off and control dampers closed

  • 7/31/2019 Air & Flue Gases System

    22/38

    Natural draft nor required

    Waiting time for purge not required

    At least one air flow path open

    b. Stop

    The operator stops the I.D. fan 1 motor by issuing the command from the

    keyboard or from conventional control panel interface by depressing the stop

    push-button, it also automatically stops by a logic. Signal generated at higher

    hierarchical level. The motor stops if the following permissives are presents;

    Waiting time for purge not required

    I.D. fan 1 shut-off and control dampers closed (if it is the first I.D. fan to

    be stopped) or both F.D. fans off (in that case because it is the last I.D. fan

    to be stopped, the dampers position will not be considered).

    c. Protection stop

    The I.D. fan 1 is forced to stop for I.D. fan 1 trip signal

    2.3.04 I.D. FAN 1 TRIP

    The I.D. 1 Trip signal is generated when any of the following conditions:

    I.D. fan 1 left or right motor bearing temperature very high

    I.D. fan 1 motor winding 1 or 2 or 3 temperature very high

    I.D. fan 1 motor left or right bearing vibration (displacement or average

    speed) very high

    I.D. fan 1 casing vibration (displacement or average speed) very high I.D. fan 1 local emergency

    Implosion protection enabled (i.e. all fuels of and furnace purge completed)

    and furnace pressure lower than175 mm w.c (to be defined)

    I.D. fan 1 left or middle or right bearing temperature very high

    I.D. fan 1 motor electrical overload.

    The conditions causing the trip are memorized and alarmed. After the condition

    causing the trip returns to a non trip status, the memories are reset by the operator

    depressing the appropriate reset push-button via keyboard.

    2.3.05 I.D. FAN 1 SUCTION DAMPER

    a. Open

    The operator opens the damper by issuing the command from keyboard, it also

    automatically opens by a logic signal generated at higher hierarchical level. The

    damper opens of one of the following permissives is present:

    I.D. fan 1 motor has been running for 30 s and at least one air flow path

    is open

    I.D. fan 1 motor off

    b. Protection open

  • 7/31/2019 Air & Flue Gases System

    23/38

    The damper is forced to the open position when the Natural draft condition

    occurs.

    c. Close

    The operator closed the damper by issuing the command from keyboard, it also

    automatically closes by a logic signal generated at high hierarchical level. The

    damper also closes when following condition occurs:

    I.D. fan 1 not in service and the other I.D. fan is in service (pulse).

    The damper closed if all the following permissives are satisfied:

    I.D. fan 1 off OR I.D. fan 1 control damper closed;

    Both F.D. fan motors off OR I.D. fan 2 in service;

    Waiting time for purge not required.

    2.3.06 I.D. FN 1 DISCHARGE DAMPER

    a. Open

    The operator opens the damper by issuing the command from keyboard, it also

    automatically opens by a logic signal generated at higher hierarchical level. The

    damper opens of one of the following permissives is present:

    I.D. fan 1 motor has been running for 30 s and at least one air flow path

    is open

    I.D. fan 1 motor off

    b. Protection open

    The damper is forced to the open position when the Natural draft condition

    occurs.

    c. Close

    The operator closed the damper by issuing the command from keyboard, it also

    automatically closes by a logic signal generated at high hierarchical level. The

    damper also closes when following condition occurs:

    I.D. fan 1 not in service and the other I.D. fan is in service (pulse).

    The damper closed if all the following permissives are satisfied:

    I.D. fan 1 off OR I.D. fan 1 control damper closed;

    Both F.D. fan motors off OR I.D. fan 2 in service;

    Waiting time for purge not required.

    2.3.07 I.D. FAN CONTROL AND LUBRICATING PUMP SELECTION

    The choice of the pump as operating or as stand-by duty is selected by the operator

    through the keyboard.

  • 7/31/2019 Air & Flue Gases System

    24/38

    The operator can select one pump running and the other one as stand-by or can

    choose manual selection and in this case both pumps can be remotely started by the

    operator.

    Pump selection cannot be changed during functional subgroup start-up

    2.3.08 I.D.FANCONTROL AND LUBRIUCATING PUMP A MOTOR

    a. Start

    The operator starts the I.D. fan 1 oil pump A motor by issuing the related

    command from keyboard. It also automatically starts in any of the following

    cases:

    If the pump is selected, by a logic signal generated at higher hierarchical

    level;

    If the pump is selected as stand-by, in case of failure of the other pump;

    In case of I.D. fan control oil request (for natural draft) and the other

    pump is not in service.

    The pump motor starts if all the following permissives are present:

    The other pump is not selected (OR the other pump is in failure);

    I.D. fan 1 lubricating oil tank level adequate.

    b. Stop

    The operator stops I.D fan 1 oil pump A motor by issuing the command from

    keyboard; it also automatically stops by a logic signal generated at higher

    hierarchical level or after I.D. fan 1 trip (time delayed). If the I.D. fn 1 bearingtemperatures are lower than minimum OR the other pump is in service (and not

    in failure), the motor is stopped at once, otherwise the stopping request is stored

    in the running for cooling memory, described at functional group shut-down

    sequence (4th step).

    The motor stops if at least one of the following permissives is present:

    Functional group is not in start-up AND I.D. fan 1 control oil and

    cooling air stop permissive (described at functional group shut-down

    sequence 4th step) is present AND I.D. fan control oil request (for natural

    draft) is not present;

    The other I.D. fan 1 oil pump is in service AND not in failure.

    c. Protection stop

    For each pump, the related I.D. fan 1 oil pump failure signal is generated

    when any of the following conditions occurs:

    Pump motor start failure (e.g. electrical overload):

    Low delivery pressure for 15 s with pump motor running for 5 s

    The conditions causing the failure are memorized and alarmed. After the

    condition causing the failure returns to a non failure status, the memories arereset by the operator depressing the appropriate reset push-button via keyboard.

  • 7/31/2019 Air & Flue Gases System

    25/38

    Each I.D. 1 oil pump motor is forced to stop when at least one of the following

    conditions arises:

    I.D. fan 1 lubricating oil tank very low level;

    Pump motor start failure (e.g. electrical overload);

    Low delivery pressure with pump motor running for 20 s.Therefore, in case of low delivery pressure with pump motor running:

    Low control oil pressure alarm is issued without time delay,

    The stand-by pump is switched-on additionally only 15 s after oil

    pressure drop (in order to avoid automatic actions for transient pressure

    loss);

    If delivery oil pressure is still low, 5 s after (i.e. 20 s after pressure

    drop), the previously running pump is automatically stopped;

    If delivery oil pressure is still low, 5 s after (i.e. 25 s after pressure

    drop), the stand-by pump is automatically stopped too.

    For each I.D. fan, two of the above drive are provided.

    2.3.09 I.D. FAN 1 AIR COOLING AND SEALING AIR FAN MOTOR SELECTION

    The choice of the I.D. fan 1 air cooling fan as operating or as stand-by duty is a

    selected by the operator through the keyboard.

    The operator can select one I.D. fan 1 air cooling fan running and the other one as

    stand-by or can choose manual selection and in this case both fans can be remotely

    started by the operator.

    Air fan selection cannot be changed during functional subgroup start-up.

    2.3.10 I.D. FAN 1 AIR COOLING AND SEALING FAN MOTOR

    a. Start

    The operator starts the I.D. fan 1 air cooling fan A motor by issuing the related

    command from keyboard. It also automatically starts in any of the following

    cases:

    If the air fan is selected, by a logic signal generated at higher

    hierarchical level;

    If the air fan is selected as stand-by, in case of failure of the other air

    fan.

    .

    The air fan motor starts if all the following permissives are present:

    The other air fan is not selected (OR the other pump is in failure);

    b. Stop

    The operator stops I.D fan 1 air cooling fan motor by issuing the command

    from keyboard; it also automatically stops by a logic signal generated at higher

    hierarchical level or after I.D. fan 1 trip (time delayed). If the I.D. fan 1

    hydraulic and bearing room temperatures are lower than minimum OR the otherair fan is in service (and not in failure), the motor is stopped at once, otherwise

  • 7/31/2019 Air & Flue Gases System

    26/38

    the stopping request is stored in the running for cooling memory, described at

    functional group shut-down sequence (4th step).

    The motor stops if at least one of the following permissives is present:

    Functional group is not in start-up AND I.D. fan 1 control oil and

    cooling air stop permissive (described at functional group shut-downsequence 4th step) is present

    The other I.D. fan 1 air fan is in service AND not in failure.

    d. Protection stop

    For each pump, the related I.D. fan 1 cooling air fan failure signal is

    generated when any of the following conditions occurs:

    Cooling air fan motor start failure (e.g. electrical overload);

    Low delivery pressure for 3 s with cooling air fan motor running for 5 s.

    The conditions causing the failure are memorized and alarmed. After thecondition causing the failure returns to a non failure status, the memories are

    reset by the operator depressing the appropriate reset push-button via keyboard.

    Each I.D. 1 Cooling air fan motor is forced to stop when the following

    conditions arises:

    Cooling air fan motor start failure (e.g. electrical overload);

    Therefore, in case of low delivery pressure with fan motor running:

    Low Cooling air pressure alarm is issued without time delay,

    The stand-by fan is switched-on additionally only 3s after air pressure

    drop (in order to avoid automatic actions for transient pressure loss);

    If delivery oil pressure is still low, 5 s after (i.e. 20 s after pressuredrop), the previously running pump is automatically stopped;

    No fan is automatically stopped.

    For each I.D. fan, two of the above drive are provided.

    2.4.00 F.D FAN SYSTEM FUNCTIONAL SUBGROUP

    This functional subgroup commands the start-up and shut-down of the related F.D.

    fan and the automatic dampers in sequential mode, prodded the functional subgroup

    is selected in auto mode.

    The functional subgroup is put in auto mode by the operator, via the auto/manual

    selection command; it is forced to manual in the following cases:

    Related F.D. fan trip

    After start-up or shut-down sequence end, if the functional subgroups status

    changes

    Natural draft (after natural draft the functional group is released to auto)

    Two of the above mentioned functional subgroup are provided, one for each F.D.

    fan.

    2.4.01 F.D.FAN START-UP SEQUENCE

  • 7/31/2019 Air & Flue Gases System

    27/38

    The operator starts the sequence from keyboard by issuing the start command or

    from conventional control panel interface by depressing the start push-button, the

    sequence is also automatically started by a logic signal generated at higher

    hierarchical level.

    Each sequence step takes place if the following permissive is satisfied:

    Waiting time for purge not present

    a. The 1st step commands the F.D. fan 1 control oil system start-up; it takes place if

    the following permissives are satisfied:

    All the related devices are available

    F.D. fan 2 not in start-up

    At least on E.A.H. in service

    At least one I.D. fan in service

    The relevant command is sent to the individual drive level F.D. fan 1 control

    oil pump.

    b. The 2nd commands all the dampers opening; it takes place after checking

    completion of the 1st within the proper check time, that is:

    F.D. fan 1 start-up permissives satisfied (i.e. control oil pressure adequate

    for start) or fan motor already running

    At least one R.A.H. in service

    At least one I.D. fan in service

    If the fan motor is already running, no permissive is required.

    The relevant commands are sent to fans and R.A.H.s shut-off dampers

    individual drive levels and to fans control dampers and secondary and tertiaryair control dampers.

    c. The 3rd step commands the F.D. fan 1 dampers closing ; it takes place after

    checking the completion of the 2nd step within the proper check time, that is:

    F.D. fan 2 air path open

    F.D. fan 1 start-up permissive satisfied (i.e. control oil pressure adequate)

    In order to avoid control damper opening at 3rd step end, the related command is

    saved in a dedicated memory, that is reset incase of sequence manual selection

    or at the end of the sequence, when the control damper is released to auto.

    The relevant commands are sent to the individual drive level F.D. fan 1

    discharge damper and to F.D. fan 1 control damper, they are effective only if

    fan motor is not running.

    d. The 4th step commands the F.D. fan 1 motor starting; it takes place after

    checking the completion of the 3rd step within the proper check time, that is:

    F.D fan 1 control damper closed

    F.D fan 1 discharge damper closed

    F.D fan 1 start-up permissives satisfied (i.e. control oil pressure adequate for

    start)

    If the fan motor is already running, no permissive is required.

  • 7/31/2019 Air & Flue Gases System

    28/38

    The relevant command is sent to eh individual drive level F.D. fan 1 motor.

    e. The 5th step commands the F.D. fan 1 discharge damper opening; it takes place

    after checking the completion of the 4 th step within the proper check time, that

    is:

    F.D. fan 1 motor has been running for 30 s.

    The relevant command is sent to the individual drive level F.D. fan 1 discharge

    damper.

    f. The 6th step releases the F.D. fan 1 control damper in auto; it takes place after

    checking the completion of the 5th step within the proper check time, that is:

    F.D. fan 1 discharge damper open

    The relevant requirement is sent to F.D. fan 1 control damper.

    g. After completion of the 6th step, the F.D. fan 1 start-up sequence is complete.

    The signal of the F.D. fan 1 in service is generated when all the following

    conditions are satisfied:

    F.D. fan 1 motor running for 30 s

    F.D. fan 1 discharge damper open

    F.D. fan 1 at least one control oil pump in service.

    2.4.02 F.D. SHUT-DOWN SEQUENCE

    The operator starts the sequence from keyboard by issuing the stop command or

    from conventional control panel interface by depressing the start push-button, the

    sequence is also automatically started by a logic signal generated at higher

    hierarchical level.

    Each sequence step takes place if the following permissive is satisfied:

    Waiting time for purge not present

    a. The 1st step commands F.D. fan 1 control damper closing

    No specific permissive required.

    In order to avoid control damper opening at 1st step end, the command is savedin a dedicated memory, that is reset incase of sequence manual selection or at

    the end of the sequence, when the fan motor has been stopped for 30s (at this

    point, if the other F.D. fan is in service, a forcement in the analog control

    section keeps the control damper closed).

    The relevant requirement is sent to F.D. fan 1 control damper, and it will be

    effective only if the F.D. fan 1 is not the last in service; that means, according to

    NFPA rules, the last F.D. fan will be stopped with dampers open.

    b. The 2nd step commands the F.D. fan 1 discharge damper closing; it takes place

    after checking the completion of the 1st step within the proper check time, that

    is:

  • 7/31/2019 Air & Flue Gases System

    29/38

    F.D. fan 1 control damper closed (or the other F.D. fan not in service)

    As per the above control damper this command will take place only if the other

    F.D. fan is still running.

    The relevant command is sent to the individual drive level F.D. fan 1 discharge

    damper.

    c. The 3rd step commands the F.D. fan 1 motor stopping; it takes place after

    checking the completion of the 2nd step within the proper check time, that is:

    F.D. fan 1 discharge damper closed (or the other F.D. fan not inservice)

    The relevant command is sent to the individual drive level F.D. fan 1 motor.

    d. The 4th step commands the F.D. fan 1 control oil system stopping ; it takes place

    after checking the completion of the 3rd step within the proper check time, that

    is:

    F.D fan 1 motor off for 30 s

    The relevant command is sent to the individual drive level F.D. fan 1 control

    oil pump.

    After completion of the 4th step, the F.D. fan 1 shut-down sequence is

    complete

    Therefore, as above explained, in case the F.D. fan 1 is the last one to be shut-

    down, it will be stopped with the discharge damper open and the control damper

    modulated to avoid excessive air pressure transients.

    2.4.03 F.D. FAN 1 MOTOR

    a. Start

    The operator start the F.D. fan 1 motor by issuing the command from the

    keyboard or from conventional control panel interface by depressing the start

    push-button, it also automatically starts by a logic signal generated at higher

    hierarchical level. The motor starts if the following permissives are present:

    F.D. fan 1 shut-off and control dampers closed At least one R.A.H. in service

    At least one I.D. fan in service

    F.D. fan 1 control oil pressure adequate for fan start

    Waiting time for purge not required

    Natural draft not required

    F.D. fan 2 shut-off damper open

    F.D. fan 2 control damper not closed

    b. Stop

  • 7/31/2019 Air & Flue Gases System

    30/38

    The operator stops the F.,D fan 1 motor by issuing the command from the

    keyboard or from conventional control panel interface by depressing the stop

    push-button, it also automatically stops by a logic signal generated at higher

    hierarchical level. The motor stops if the following permissives are present:

    Wait time for purge not required

    F.D. fan 1 shut-off and control dampers closed (if it is the first F.D. fanto be stopped) or the other F.D. fan is already stopped (in the case because it

    is the last F.D. fan to be stopped, the dampers position will not be

    considered)

    c. Protection stop

    The F.D. fan 1 is forced to stop for F.D. fan 1 trip signal.

    F.D. fan 1 also forced to stop at least one of the following conditions arised:

    Both I.D. fans motor off

    2.4.04 F.D. FAN 1 TRIP

    The F.D. Fan 1 Trip signal is generated when any of the following conditions

    occurs.

    F.D. fan 1 left or right motor bearing temperature very high

    F.D. fan 1 motor winding 1 or 2 or 3 temperature very high

    F.D. fan 1 motor left or right bearing vibration (displacement or

    average speed) very high

    F.D. fan 1 casing vibration (displacement or average speed) very high

    F.D. fan 1 local emergency stop Implosion protection enabled (i.e. all fuels off and furnace purge

    completed) and furnace pressure higher that + 125 mm w.c.

    Furnace pressure higher that = 650 mm w.c. (to be defined)

    F.D. fan 1 left or middle or right bearing temperature very high

    F.D. fan 1 motor electrical overload.

    The conditions causing the trip are memorized and alarmed. After the condition

    causing the trip returns to a non trip status, the memories are reset by the operator

    depressing the appropriated reset push-button via keyboard.

    2.4.05 F.D. FAN 1 DISCHARGE DAMPER

    a. Open

    The operator opens the damper by issuing the command from keyboard, it also

    automatically opens by a logic signal generated at higher hierarchical level. The

    damper opens if any of the following permisives is present:

    F.D. fan 1 motor has been running for 30s

    F.D, fan 1 motor off

    b. Protection open

  • 7/31/2019 Air & Flue Gases System

    31/38

    The damper is forced to the position when Natural draft confection occurs.

    c. Close

    The operator closes the damper by issuing the command from the keyboard, it

    also automatically closes by a logic signal generated at higher hierarchical level.The damper also closes when the following condition occurs:

    F.D. fan 1 not in service and the other F.D. fan is in service (pulse)

    The damper closed if the following permissives are present:

    F.D. fan 1 off or F.D. fan 1 control damper closed;

    F.D. fan 2 dampers open OR both I.D. fan motors off;

    Waiting time for purge not required.

    2.4.06 F.D. FAN 1 CONTROL OIL PUMP SELECTION

    The choice of the pump as operating or as stand-by duty is selected by the operator

    through the keyboard.

    The operator can select one pump running and the other one as stand-by or can

    choose manual selection and in this case both pumps can be remotely start5ed by

    the operator.

    Pump selection cannot be changed during functional subgroup start-up.

    2.4.07 F.D. FAN 1 CONTROL OIL PUMP A MOTOR

    a. Start

    The operator starts the F.D. fan 1 oil pump A motor by issuing the related

    command from keyboard. It also automatically starts in any of the following

    cases:

    If the pump is selected, by a logic signal generated at higher hierarchical

    level;

    If the pump is selected as stand-by, in case of failure of the other pump;

    In case of F.D. fan control oil request (for natural draft or damper

    opening) and the other pump is not in service.

    The pump motor starts if all the following permissives are present:

    The other pump is not selected (OR the other pump is in failure);

    I.D. fan 1 lubricating oil tank level adequate.

    b. Stop

    The operator stops F.D. fan 1 oil pump A motor by issuing the command from

    keyboard; it also automatically stops by a logic signal generated at higher

    hierarchical level or after I.D. fan 1 trip (time delayed).

    The motor stops if at least one of the following permissives is present:

    F.D. fan 1 not running for 30 s (and no F.D. fan 1 control oil request)

    The other F.D. fan 1 oil pump is in service AND not in failure.

  • 7/31/2019 Air & Flue Gases System

    32/38

    c. Protection stop

    For each pump, the related F.D.. fan 1 oil pump failure signal is generated

    when any of the following conditions occurs:

    Pump motor start failure (e.g. electrical overload): Low delivery pressure for 15 s with pump motor running for 5 s

    The conditions causing the failure are memorized and alarmed. After the

    condition causing the failure returns to a non failure status, the memories are

    reset by the operator depressing the appropriate reset push-button via keyboard.

    Each F.D. 1 oil pump motor is forced to stop when at least one of the following

    conditions arises:

    F.D. fan 1 lubricating oil tank very low level;

    Pump motor start failure (e.g. electrical overload); Low delivery pressure with pump motor running for 20 s.

    Therefore, in case of low delivery pressure with pump motor running:

    Low control oil pressure alarm is issued without time delay,

    The stand-by pump is switched-on additionally only 15 s after oil

    pressure drop (in order to avoid automatic actions for transient pressure

    loss);

    If delivery oil pressure is still low, 5 s after (i.e. 20 s after pressure

    drop), the previously running pump is automatically stopped;

    If delivery oil pressure is still low, 5 s after (i.e. 25 s after pressuredrop), the stand-by pump is automatically stopped too.

    For each F.D. fan, two of the above drive are provided.

    2.5.00 R.G. FAN SYSTEM FUNCTIONAL SYBGROUP

    This functional subgroup commands the start-down of the R.G. fan and the

    automatic dampers in sequential mode, provided the functional subgroup is selected

    in auto mode.

    The functional subgroup is put in auto mode by the operator, via the auto/manual

    selection command; it is forced to manual in the following case:

    Related R.G. fan trip

    After start-up or shat-down sequence end, if the functional subgroup status

    changes

    Natural draft (after natural draft the functional group is released to auto)

    Two of the above mentioned functional subgroups are provided, one for each R.G.

    fan.

    2.5.01 R.G. FAN START-UP SEGQENCE

    The operator starts the sequence from keyboard by issuing the start command orfrom conventional control panel interface by depressing the start push-button.

  • 7/31/2019 Air & Flue Gases System

    33/38

    The R.G. fan also automatically starts from signal by higher hierarchical level, i.e.

    start-up required by B.M.S.; in this case the priority is given to R.G. fan A, if

    after 10 s no R.G. fan is in service or R.G. fan A start-up sequence is not in

    progress, it tries to start R.G. fan B.

    Each sequence step takes place if the following permissive is satisfied: Waiting time for purge not present

    a. The 1st step commands the R.G. fan 1 dampers closing; it takes place if the

    following permissives are satisfied

    All the related devices are available

    At least one air and flue gases line in service in service

    The relevant commands are sent to the individual drive levels R.G. fan 1

    suction damper, R.G. fan 1 discharge damper and to R.G. fan 1 control

    damper, they are effective only if fan motor is nor running.

    b. The 2nd step commands the R.G. fan 1 motor starting; it takes place after

    checking the completion of the 1st step within the proper check time, that is:

    R.G. fan 1 suction damper closed

    R.G. fan 1 discharge damper closed

    R.G. fan 1 control damper closed

    If the fan motor is already running, no permissive is required.

    The relevant command is sent to the individual drive level R.G. fan 1 motor.

    c. The 3rd step commands the R.G. fan 1 suction and discharge dampers opening; ittakes place after checking the completion of the 2 nd step within the proper check

    time, that is:

    R.G. fan 1 motor has been running for 30 s.

    The relevant commands are sent to the individual drive level R.G. fan 1 suction

    damper and R.G. fan 1 discharge damper.

    d. The 4th step releases the R.G. fan 1 control damper in auto; it takes place after

    checking the completion of the 3rd step within the proper check time, that is:

    R.G. fan 1 suction damper open

    R.G. fan 1 discharge damper open

    The relevant requirement is sent to R.G. fan 1 control damper.

    e. After completion of the 4th step, the I.D. fan 1 start-up sequence is complete.

    The signal of the R.G. fan 1 in service generated when all the following conditions

    arte satisfied:

    R.G. fan 1 motor running for 30 s

    R.G. fan 1 suction damper open

    R.G. fan 1 discharge damper open

  • 7/31/2019 Air & Flue Gases System

    34/38

    2.5.02 R.G. FAN SHUT-DOWN SEQUENCE

    The operator starts the sequence from the keyboard by issuing the stop command or

    from conventional control panel interface by depressing the stop push-button, the

    sequence is also automatically started by a logic generated at higher hierarchical

    level.

    Each sequence step takes place if the following permissive is satisfied:

    Waiting time for purge not present

    a. The 1st commands R.G. fan 1 control closing; it takes place if at least one of the

    following permissives is satisfied:

    No mills in service

    The other R.G. fan in service

    The relevant requirement is sent to R.G. fan 1 control damper.

    b. The 2nd step commands the R.G. fan 1 suction and discharge dampers closing; it

    takes place after checking the completion of the 1st step within the proper check

    time, that is:

    R.G. fan 1 control damper closed

    The relevant commands are sent to the individual drive levels R.G. fan 1

    suction damper and R.G. fan 1 discharge damper.

    c. The 3rd step commands the R.G. fan 1 motor stop; it takes place after checking

    the completion of the 2nd

    step within the proper check time, that is: R.G. fan 1 suction and discharge dampers closed

    The relevant command is sent to the individual level R.G. fan 1 motor.

    d. After completion of the 4th step, the R.G. fan 1 shut-down sequence is complete

    2.5.03 R.G. 1 MOTOR

    a. Start

    The operator start the R.G. fan 1 motor by issuing the command from thekeyboard or from conventional control panel interface by depressing the start

    push-button, it also automatically starts by a logic signal generated at higher

    hierarchical level. The motor starts if the following permissives are present:

    R.G. fan 1 shut-off and control dampers closed

    At least one air and flue gases line in service

    d. Stop

  • 7/31/2019 Air & Flue Gases System

    35/38

    The operator stops the R.G. fan 1 motor by issuing the command from the

    keyboard or from conventional control panel interface by depressing the stop

    push-button, it also automatically stops by a logic signal generated at higher

    hierarchical level. The motor stops if the following permissives are present:

    R.G. fan 1 shut-off and control dampers closed

    No mill in service (or the other R.G. fan in service)

    C. Protection stop

    The R.G. fan 1 Trip signal is generated when any of the following conditions

    occurs:

    2.5.04 R.G. FAN 1 TRIP

    The R.G. Fan 1 Trip signal is generated when any of the following conditions

    occurs:

    Both F.D. fans motor off

    R.G. fan 1 motor electrical overload

    The conditions causing the trip are memorized and alarmed. After the condition

    causing the trip returns to a non trip status, the memories are reset by the operator

    depressing the appropriate reset push-button via keyboard.

    2.5.05 R.G. FAN 1 SUCTION DAMPER

    a. Open

    The operator opens the damper by issuing the command from keyboard, it also

    automatically opens by a logic signal generated t higher hierarchical level. The

    damper opens if one of the following permissives is present:

    R.G. fan 1 motor has been running for 30 s

    R.G. fan 1 motor off

    b. The operator closes the damper by issuing the command from keyboard, it also

    automatically closes by a logic signal generated t higher hierarchical level.

    The damper R.G. fan motor is off OR if the following permissives are present:

    R.G. fan 1 control damper closed

    No mills in service (or the other R.G. fan in service)

    c. Protection close

    The damper is forced to closed for R.G. fan 1 trip.

    2.5.06 R.G. FAN 1 DISCHARGE DAMPER

    a. Open

  • 7/31/2019 Air & Flue Gases System

    36/38

    The operator opens the damper by issuing the command from keyboard, it also

    automatically opens by a logic signal generated t higher hierarchical level. The

    damper opens if one of the following permissives is present:

    R.G. fan 1 motor has been running for 30 s

    R.G. fan 1 motor off

    b. The operator closes the damper by issuing the command from keyboard, it also

    automatically closes by a logic signal generated t higher hierarchical level.

    The damper R.G. fan motor is off OR if the following permissives are present:

    R.G. fan 1 control damper closed

    No mills in service (or the other R.G. fan in service)

    c. Protection close

    The damper is forced to closed for R.G. fan 1 trip.

    2.6.00 AUXILIARY AIR FANS

    2.6.01 AUXILIARY AIR FAN SELECTION

    The choice of the auxiliary air fan as operating or as stand-by duty is selected by the

    operator through the keyboard.

    The operator can select one auxiliary air fan running and the other one as stand-by

    or can choose manual selection and in this case both auxiliary air fans can be

    remotely started by the operator.

    2.6.02 AUXILIARY AIR FAN 1 MOTOR

    a. Start

    The operator starts the auxiliary fan 1 motor by issuing the related command

    from keyboard; it also automatically starts if the other one fails and it had been

    selected as stand-by operation

    The fan motor starts if any of the following permissives is present:

    The other fan is not selected;

    The other fan is failure.

    b. Stop

    The operator stops the auxiliary fan motor by issuing the command from

    keyboard; it also automatically stops after 30 s that auxiliary air fan motor is

    running and the discharge damper is closed. The motor stops if at least one of

    the following permisives is present:

    The other auxiliary air fan is in service

    No burner in service.

    c. Protection stop

  • 7/31/2019 Air & Flue Gases System

    37/38

    For each fan, the related auxiliary air fan failure signal is generated when any

    of the following conditions occurs:

    fan motor start failure (e.g. electrical overload):

    Low delivery pressure for 3 s with fan motor running for 5 s

    The conditions causing the failure are memorized and alarmed. After the

    condition causing the failure returns to a non failure status, the memories are

    reset by the operator depressing the appropriate reset push-button via keyboard.

    Each auxiliary air fan motor is forced to stop when the following conditions

    arises:

    auxiliary air fan motor start failure (e.g. electrical overload).

    Low auxiliary air pressure alarm is issued without time delay,

    The stand-by fan is switched-on additionally only 3 s after air pressure

    drop (in order to avoid automatic actions for transient pressure loss); No fan is automatically stopped.

    Two of the above drive are provided.

    2.6.03 AUXILIARY AIR FAN 1 DISCHARGBE DAMPER

    a. Open

    The operator opens the damper by issuing the command from keyboard, it also

    automatically opens when is required the auxiliary air fan 1 starts.

    No permissive is required.

    b. Close

    The operator closes the damper by issuing the command from keyboard, it also

    automatically closes when auxiliary air fan 1 stops. The damper closed if the

    following permissive is present:

    Auxiliary air fan 1 motor off

    Two of the above drive are provided.

    2.6.04 AUXILIARY AIR FAN 1 BY-PASS DAMPER

    a. Open

    The operator opens the damper by issuing the command from keyboard and the

    following permissive is present:

    Both auxiliary air fan motor off

    b. Protection open

    If at least one burner is in service, the damper is forced to open in any of thefollowing cases:

  • 7/31/2019 Air & Flue Gases System

    38/38

    Auxiliary air pressure very low

    No auxiliary air fan in service (30 s delayed)

    c. Close

    The operator closes the damper by issuing the command from keyboard and atleast one of the following permissive is present:

    Bot


Recommended