“ADCATROL” Intermittent Blowdown Valves VPA 26 S (cast steel) DESCRIPTION The VPA26S blowdown valve was specially designed for application on steam boilers removing the concentrations of solids avoiding boiler damages, unstable water level control and other typical problems. The valves are provided with a diaphragm actuator suitable for compressed air motive fluid. The opening signal is supplied by an automatic intermittent control unit or manually (optional). Connections are flanged . OPERATION The valve can be operated manually or using a pneumatic actuator. Valve aperture depends from the boiler manufacturer specification (example: once a day during five seconds). MAIN FEATURES High quality hardened valve and seat. Manual or automatic control. Can be locked in the open position if supplied with the manual operation lever. OPTIONS: Air filter regulator Solenoid valve with cycling timer . Mechanical limit switch Water powered actuator Stainless steel construction. USE: Intermittent blowdown of steam boilers. AVAILABLE MODELS: VPA 26S VALVE SIZES: DN20 to DN50 CONNECTIONS: Flanged EN 1092-1 ACTUATORS: PA-205; PA-280. ACTUATOR CONN: 1/4'’ NPT-F HOW TO SELECT: Never size the valve according to the pipe diameter in which it has to be fitted but according to the required actual flow of steam or water.Refer to valve calculation data sheet or consult the factory. MAX. AIR/WATER SUPPLY PRESS.: 3,5 bar AMBIENT TEMPERATURE: -20 C ...+70 C STEM SEALING: Graphite - up to 400 C PLUG TYPES: On-Off (PT) PORT: Full port
Transcript
  • “ADCATROL” Intermittent Blowdown Valves VPA 26 S (cast steel)

    DESCRIPTIONThe VPA26S blowdown valve was specially designed for applicationon steam boilers removing the concentrations of solids avoidingboiler damages, unstable water level control and other typicalproblems.The valves are provided with a diaphragm actuator suitable forcompressed air motive fluid.The opening signal is supplied by an automatic intermittent controlunit or manually (optional).Connections are flanged .

    OPERATIONThe valve can be operated manually or using a pneumatic actuator.Valve aperture depends from the boiler manufacturer specification(example: once a day during five seconds).

    MAIN FEATURESHigh quality hardened valve and seat.Manual or automatic control.Can be locked in the open position if suppliedwith the manual operation lever.

    OPTIONS: Air filter regulatorSolenoid valve with cycling timer .Mechanical limit switchWater powered actuatorStainless steel construction.

    USE: Intermittent blowdown of steamboilers.

    AVAILABLEMODELS: VPA 26SVALVE SIZES: DN20 to DN50CONNECTIONS: Flanged EN 1092-1ACTUATORS: PA-205; PA-280.ACTUATOR CONN: 1/4'’ NPT-F

    HOW TO SELECT:Never size the valve according to the pipe diameterin which it has to be fitted but according to therequired actual flow of steam or water.Refer to valvecalculation data sheet or consult the factory.

    MAX. AIR/WATERSUPPLY PRESS.: 3,5 barAMBIENTTEMPERATURE: -20�C ...+70�CSTEM SEALING: Graphite - up to 400�CPLUG TYPES: On-Off (PT)PORT: Full port

  • abcde ADCA

    VALSTEAM ADCA We reserve the right to change the design and material of this product without notice.

    IS VPA26S.10 E 04.07

    www.valsteam.com

    Press.bar

    Temp. C°+Temp.C°-

    Body

    FluidDN/PN

    www.valsteam.com

    Press.bar

    Temp. C°+Temp.C°-

    Body

    FluidDN/PN

    VPA26S– with pneumatic actuator and manual operation

    VPA26S– manual operation only

    20 150 53 80 175 380 15 1225 160 58 85 175 380 16 1332 180 70 90 175 380 20 1740 200 75 95 175 650 25 2250 230 83 105 175 650 34 31

    * Valve with pneumatic actuator** Valve with manual lever only

    D1 F * WGT. Kgs**WGT

    KgsDN A B C

    DIMENSIONS ( mm) - VALVE BODY

    POS. DESIGNATION MATERIAL

    1 Valve Body A216 WCB / 1.06192 Bonnet CF8 / 1.43083 * Actuator Steel Fe410.1/St.Steel

    3.1 * Spring Spring Steel4 * Diaphragm NBR 705 Yoke Carbon Steel/St.Steel6 * Valve Plug Hardened St. Steel

    6.1 * Valve Seat Hardened St. Steel7 Packing Graphite8 Valve Lever Stainless steel / 1.4301

    * Available spare parts.

    MATERIALS

    DN15-100 DA/RA DN125-200 DA

    PA-205 210 235 N/APA-280 275 240 N/A

    DIMENSIONS - ACTUATOR

    D (mm)Type ø E (mm)

    DN15 DN20 DN25 DN32 DN40 DN50

    Stroke - 12 12 12 12 12

    VALVE STROKE IN mm

    SIZES

    DN15 DN20 DN25 DN32 DN40 DN50

    Kvs - 6 7,5 11 24 30

    FLOW RATE COEFFICIENTS

    SIZES

  • abcde ADCA

    VALSTEAM ADCA We reserve the right to change the design and material of this product without notice.

    IS VPA26S.10 E 04.07

    ACTUATOR

    (Pressure) DN15 DN20 DN25 DN32 DN40 DN50

    PA-205

    (0 - 1 bar)

    PA-280

    (0 - 1 bar)

    3,5 bar

    MIN. AIR PRESSURE

    SIZES

    — 25 25 25 25 15

    MAX. PERMISSIBLE PRESS.DROP IN bar - Normally closed valve (fluid to close) - Reverse action actuator (air signal to open)

    — — — 253,5 bar — —

    Important: The pressure drop values are referred to closed valves. For valve sizes DN65 and above please consult. Special spring drops available on request. The pressure drop values must be used within the body rating limits.

    TYPICAL INSTALLATION

    1 VPA26S Blowdown Valve2 ADCA Digital Timer plus Connector3 ADCA Solenoid Valve 3/24 ADCA P10 Air Filter Regulator5 Ball Valve6 Limit Switch

    Pos. Designation

    www.valsteam.com

    Press.bar

    Temp. C°+Temp.C°-

    Body

    FluidDN/PN

    TESTVALVEPOWER

    10

    864

    2

    0 .2

    24 6

    8

    1 00 .2


Recommended