APOGEE Firmware Revision 3.4
Release Notes
545-975-3p4 Building Technologies 2015-12-18
Copyright Notice
2 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
Copyright Notice
Notice
Document information is subject to change without notice by Siemens Industry, Inc. Companies, names, and various data used in examples are fictitious unless otherwise noted. No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written permission of Siemens Industry, Inc.
All software described in this document is furnished under a license agreement and may be used or copied only in accordance with license terms.
For further information, contact your nearest Siemens Industry, Inc. representative.
Copyright 2015 by Siemens Industry, Inc.
To the Reader
Your feedback is important to us. If you have comments about this manual, please submit them to: [email protected]
Credits
APOGEE, APOGEE GO, InfoCenter Administrator, InfoCenter Report Manager, InfoCenter Server, InfoCenter Suite, and Insight are registered trademarks of Siemens Industry, Inc.
Other product or company names mentioned herein may be the trademarks of their respective owners.
Printed in the USA.
3 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
Table of Contents
Section 1 - New Features and Enhancements ............................................................ 5
Totalization for Analog and Multistate Points .................................................................. 5
Totalized Point Report ..................................................................................................... 5
Additional Trend Interval Rates for Time-based Trends ................................................. 6
Deleting Multiple Points or PPCL Programs.................................................................... 6
FLN Network Types ......................................................................................................... 6
Two MS/TP FLN Connections Supported ............................................................. 7
New FLN Device Support ...................................................................................... 7
Integration Driver Support on Field Panel Web UI .......................................................... 7
Slope/Intercept Calculator ............................................................................................... 7
Greenleaf Component ..................................................................................................... 7
Enhancements to Application MC ................................................................................... 8
Field Panel Editor Enhancements ................................................................................... 8
Section 2 - Fixed Issues ............................................................................................. 9
Section 3 - Installation .............................................................................................. 10
Section 4 - System Requirements and Compatibility ................................................. 11
User Interface and Firmware Compatibility ................................................................... 11
BACnet Firmware Compatibility with Desigo CC™ Software........................................ 12
BACnet Firmware Compatibility with Insight Software and Commissioning Tool ......... 14
P2 Firmware Compatibility with Desigo CC™ ............................................................... 17
P2 Firmware Compatibility with Insight Software and Commissioning Tool ................. 20
Firmware Compatibility with Insight Software and Commissioning Tool—68302
Processor Field Panels ....................................................................................... 29
Addendum, Revision 3.4 Build 12.65.0040 ................................................................ 33
Section 1 - New Features and Enhancements
Totalization for Analog and Multistate Points
5 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
Section 1 - New Features and Enhancements
Totalization for Analog and Multistate Points The Point Commander and Point Editor now support totalization for analog and multistate points. The following point types may now be totalized:
● LAO
● LAI
● LDO
● LDI
● L2SL
● L2SP
● LOOAL
● LOOAP
● LFSSL
● LFSSP
The totalization function accumulates the runtime value of a point. Examples for using this feature include:
● Accumulating runtime for fans and pumps.
● Accumulating total volume from a flow rate sensor.
● Calculating degree days.
NOTE: Using the PPCL TOTAL function to access the totalized value of a BACnet Multistate Output point is currently not supported.
Totalized Point Report
The BACnet Field Panel Web Server (FPWeb) now offers a Totalized Point report,
which displays the panel name, point name, totalized value, reset date and time, and
reset value. To open the report, click the Totalized Point Report icon under the
Reporting bar.
Section 1 - New Features and Enhancements
Additional Trend Interval Rates for Time-based Trends
6 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
Figure 1: Totalized Point Report Example.
Additional Trend Interval Rates for Time-based
Trends The Trend Editor has been enhanced to support additional trend interval rates for time-based trends. The trend interval options for time-based trends are now hours, minutes, and seconds.
Deleting Multiple Points or PPCL Programs ● The BACnet Field Panel Web Client Point Editor now allows you to delete multiple
points.
● The BACnet Field Panel Web Client PPCL Editor now allows you to delete multiple PPCL programs without having to open them one-by-one.
FLN Network Types MS/TP Routed and Ethernet/IP FLNs are now supported for BACnet devices.
● BACnet MS/TP routed FLN is supported for Programmable TECs (PTECs), Unitary Equipment Controllers (UECs), and third-party BACnet devices.
– FIN Builder supports MS/TP routed FLNs and IP FLNs.
– PPCL and Point Editing are currently not available on routed FLNs.
● The Ethernet/IP FLN is used with the new DXR-E FLN device.
● Auto-discovery is supported for all BACnet FLN network types.
An Integration FLN is now available. For Integration Drivers that support FPWeb, Integration FLNs can be viewed and modified from the FPWeb UI and in Kiosk mode.
The following products support the MS/TP Routed, Ethernet/IP, and Integration FLNs:
● Application Monitoring and Control System Tool (AppMC)
● FPWeb UI
● FIN Builder
Section 1 - New Features and Enhancements
Integration Driver Support on Field Panel Web UI
7 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
● FINlite
● Launch Pad
When a new FLN device is created, the field panel is queried to determine which FLN device types it supports. The Web Client displays the appropriate FLN Device Editor window.
With Firmware Revision 3.4 and later, each controller can support one of the following FLN network types:
● A combination of BACnet MS/TP, routed MS/TP, secondary MS/TP, or Ethernet/IP used simultaneously.
● Integration
● P1
Two MS/TP FLN Connections Supported For improved cost-effectiveness and flexibility of BACnet MS/TP FLN installations, two physical MS/TP FLN connections are supported on PXC Modular and PXC-36 field panels
● For PXC Modular, the PXX-485.3 FLN 1 port is the primary FLN port, and the RS-485 ALN is the secondary FLN port.
● For PXC-36, the A port is the primary FLN port, and the B port is the secondary FLN port.
To use the secondary FLN port, the primary FLN must be configured as MS/TP and the MS/TP ALN must be enabled.
New FLN Device Support Firmware Revision 3.4 allows users to view and command points in DXR controllers. Supervision and support of DXR controllers is supported on both MS/TP and IP networks.
Integration Driver Support on Field Panel Web UI Integration Drivers running Firmware Revision 3.4 are now fully integrated into the FPWeb editors. Support for the following is included with Firmware Revision 3.4:
● BACnet Driver
● Johnson Controls N2 Master Driver
● Modbus or Modbus 250/500/1000 Drivers
Slope/Intercept Calculator The Point Editor now includes a Slope/Intercept Calculator which allows you to enter or calculate scaling factors (slope and intercept) to achieve accurate results.
Greenleaf Component A graphic component called Greenleaf is now available for FINlite (in the components list) and FIN Builder (as a FIN Builder Model). This component allows you to display the current value of the DXR application Greenleaf energy efficiency indicator in your FINlite or FIN Builder graphic.
Section 1 - New Features and Enhancements
Enhancements to Application MC
8 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
Enhancements to Application MC ● Additional TEC applications in the 66xx range are now available for use in
Application MC.
● You can now select which applications to deploy with Application MC.
● MS/TP routed and Ethernet/IP FLNs are now supported for BACnet devices.
● The new BACnet FLN network types—MS/TP routed and BACnet IP—as well as the use of the secondary FLN port are supported.
● The mapping file provided with the Launch Pad deployment can be used to create custom applications in graphics.
Field Panel Editor Enhancements ● Field panels with Firmware Revision 3.4 no longer require a coldstart when the
following settings are changed:
– Site Name
– Device Location
– Device Description
– Telnet Enabled/disabled
– Auto Backup to Flash Enabled/disabled
– Auto Restore from Flash Enabled/disabled
– MS/TP Max Master
– Baud rates
● BACnet Field Panel Web Server (FPWeb) editors for Desigo™ CC have been improved.
APOGEE Editors were first introduced with Firmware Revision 3.2.4 and Desigo™ CC Version 1.0.0.17. With Firmware Revision 3.4, the code base that is used for FPWeb is also used for Desigo CC (the same file is deployed from Launch Pad).
For specific information on FPWeb compatibility with Desigo™ CC, see the BACnet Firmware Compatibility with Desigo CC™ Software [➙ 11] topic in this document.
– Desigo CC now uses the most current FPWeb UI.
– Desigo CC users are now able to edit UEC and PTEC devices.
– Desigo CC supports both FPWeb UI and APOGEE Editors for editing APOGEE objects in APOGEE field panels.
APOGEE Editors are special FPWeb UI pages that are used with Desigo CC Versions 1.0, 1.1, and 2.0 for viewing and editing points, PPCL, field panels, and TEC subpoints.
See also
BACnet Firmware Compatibility with Desigo CC™ Software [➙ 11]
Section 2 - Fixed Issues
9 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
Section 2 - Fixed Issues Solutions to the following issues have been implemented in APOGEE Firmware Revision 3.4 and the related APOGEE user interface:
● PPCL now correctly sets the value of a LOCAL or virtual LAO point equal to a LENUM point instead of subtracting 1 from the value.
● Field panels on a BACnet network no longer fail when they are connected to third-party MS/TP devices that broadcast confirmed requests.
● BBMD fix for broadcast storms: If a field panel that is configured as a BBMD receives a broadcast message from another BBMD, and both BBMDs are on the same subnet, the field panel that received the broadcast message will no longer rebroadcast the message, thus preventing a broadcast storm.
NOTE: This is part of the BACnet specification; however, some third-party vendors may not have implemented this yet.
● Copy paste functions are fully functioning in the PPCL editor.
● An intermittent issue was found in Firmware 3.3.1 that affected the accuracy of TX-I/O digital inputs after a warmstart. This issue has been fixed.
● Multi-state input objects are now supported for MS/TP FLN device integration.
● BACnet value types (AV, BV, MSV) that do not have a priority array are now supported.
● PXC-36 no longer coldstarts when onboard points enter a timeout period due to high COV activity.
Section 3 - Installation
10 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
Section 3 - Installation Existing compatible field panel hardware can be upgraded by flashing the new firmware. The following table outlines the available upgrade options.
Flash upgrades are installed using Firmware Loading Tool (FLT) Revision 3.12 and later.
Upgrade Information
From Firmware
Revision
ALN Protocol To Firmware
Revision
ALN Protocol Method Cost
2.x P2/Ethernet 3.4 BACnet Flash with file from
StdApps
Yes
Pre-3.2 BACnet 3.4 BACnet Flash with file from
StdApps
Yes
3.2.5 and earlier BACnet 3.4 BACnet Flash with file from
StdApps
Yes
3.3 or 3.3.1 BACnet 3.4 BACnet Flash with file from
StdApps
Yes
Section 4 - System Requirements and Compatibility
User Interface and Firmware Compatibility
11 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
Section 4 - System Requirements and
Compatibility
User Interface and Firmware Compatibility This section outlines which user interface revisions are compatible with certain firmware revisions.
For proper functionality and access of the new features, you must upgrade the user interface (UI) at the field panel as well as upgrade the firmware. The UI upgrade is free and provides you with the latest defect resolutions.
See the following compatibility chart for the minimum firmware revision required to fully support each revision of FINlite, the FPWeb UI, and APOGEE Editor.
BACnet Field Panel Web Server
Firmware Revision a)
FINlite Revision
UI/Launch Pad Revision b)
FP Web UI for Desigo CC™
APOGEE Editor Revision c)
FIN Builder Revision/ Connector
3.4 1.4.35 1.4.35 1.4.35 1.0.0.17 3.0.235
3.3.1 1.3.102 1.3.102 N/A 1.0.0.17 3.0.003
3.3 1.3.40 1.3.40 N/A 1.0.0.17 N/A
3.2.5 1.2.35 1.2.35 N/A 1.0.0.17 N/A
3.2.4 1.1.0.2638 1.1.0.143 N/A 1.0.0.17 N/A
3.2.3 1.1.0.2638 1.1.0.130 N/A N/A N/A
a) It is recommended that you change the default passwords for the HIGH and MED accounts before upgrading to Firmware Revision
3.3 or later.
b) Support for editing points and PPCL programs on FLN devices is provided in Firmware Revisions 3.3 and later.
c) Used in conjunction with the Desigo™ CC management station.
Section 4 - System Requirements and Compatibility
BACnet Firmware Compatibility with Desigo CC™ Software
12 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
BACnet Firmware Compatibility with Desigo CC™
Software This section outlines which APOGEE firmware revisions are compatible with Desigo™ CC and the field panels that support those revisions.
BACnet Firmware Compatibility with Desigo™ CC Software.
Desigo™ CC Revision
Field Panel (Firmware Revision String)
Model (Product Number)
2.1 using FPWeb
Editors
2.1 using native
BACnet only
2.0 using native
BACnet only
PXC Modular Series (PXME)
PXC00-E96.A, PXC100-E96.A
3.4 3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
3.0.1
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
3.0.1
PXC Compact Series (EX36)
PXC36-E.A, PXC36-EF.A
3.4 3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
PXC Compact Series (PAAC)
PXC24.2-UCM.A a)
3.4 3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
PXC Compact Series (PAAC)
PXC16.3-UCM.A
PXC24.3-UCM.A
3.4 3.3.1
3.3
3.2.5
3.4
3.3.1
3.3
3.2.5
PXC Compact Series (PXCE)
PXC16.2-E.A, PXC16.2-ER.A a)
PXC24.2-E.A, PXC24.2-ER.A
3.4 3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
PXC Compact Series (PXCP)
PXC16.2-M.A, PXC16.2-MR.A a)
PXC24.2-M.A, PXC24.2-MR.A
3.4 3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
Section 4 - System Requirements and Compatibility
BACnet Firmware Compatibility with Desigo CC™ Software
13 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
BACnet Firmware Compatibility with Desigo™ CC Software.
Desigo™ CC Revision
Field Panel (Firmware Revision String)
Model (Product Number)
2.1 using FPWeb
Editors
2.1 using native
BACnet only
2.0 using native
BACnet only
PXC Compact Series (EPXC)
PXC24.2-EF.A, PXC24.2-ERF.A
3.4 3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
PXC Compact Series (PXCE)
PXC16-E.A a), PXC16-ER.A a)
PXC24-E.A a), PXC24-ER.A a)
PXC16.2-EF.A, PXC16.2-ERF.A a)
PXC16.2-EF32.A
PXC24.2-EF32.A
3.4 3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
3.0
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
3.0
Power Open Processor
BACnet/IP ALN a) (562-040)
– 3.2
3.1
3.0
3.2
3.1
3.0
Power MEC (MCNE)
1200EB (549-632)
1100EB/1110EB a) (549-630, 549-631)
1210EB a) (549-633)
– 3.2
3.1
3.0
3.2
3.1
3.0
Power MEC (MEFE)
1200EFB (549-634)
1210EFB a) (549-635)
– 3.2
3.1
3.0
3.2
3.1
3.0
Power MEC
1200ELB (549-636)
1210ELB a) (549-637)
– 3.1
3.0
3.1
3.0
a) This model is discontinued.
Section 4 - System Requirements and Compatibility
BACnet Firmware Compatibility with Insight Software and Commissioning Tool
14 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
BACnet Firmware Compatibility with Insight Software
and Commissioning Tool This section outlines which APOGEE firmware revisions are compatible with Insight software and Commissioning Tool (CT) (online mode), and the field panels that support those revisions.
It is strongly encouraged that you update the user interface (UI), regardless of whether you update to the latest firmware revision. The UI upgrade is free and provides you with the latest defect resolutions.
BACnet Firmware Compatibility with Insight Software or Commissioning Tool Revisions 3.10 through 3.14
Insight Software or Online Commissioning Tool Revision
(With Optional Registry/XML Update)
Field Panel (Firmware Revision String)
Model (Product Number)
3.14 3.13c) 3.12c) 3.11c) 3.10b),c)
PXC Modular Series (PXME)
PXC00-E96.A, PXC100-E96.A
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
3.0.1
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
3.0.1
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
3.0.1
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
3.0.1
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
3.0.1
PXC Compact Series (PXCE)
PXC36-E.A, PXC36-EF.A
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
PXC Compact Series (PAAC)
PXC16.2-UCM.A
3.4
3.3.1
3.3
3.2.5
3.4
3.3.1
3.3
3.2.5
3.4
3.3.1
3.3
3.2.5
3.4
3.3.1
3.3
3.2.5
3.4
3.3.1
3.3
3.2.5
PXC Compact Series (PAAC)
PXC24.2-UCM.A
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
PXC Compact Series (PAAC)
PXC16.3-UCMR.A
PXC24.3-UCMR.A
3.4
3.3.1
3.2.5
3.4
3.3.1
3.2.5
3.4
3.3.1
3.2.5
3.4
3.3.1
3.2.5
–
PXC Compact Series (PAAC)
PXC16.3-UCM.A
PXC24.3-UCM.A
3.4
3.3.1
3.3
3.2.5
3.4
3.3.1
3.3
3.2.5
3.4
3.3.1
3.3
3.2.5
3.4
3.3.1
3.3
3.2.5
3.4
3.3.1
3.3
3.2.5
Section 4 - System Requirements and Compatibility
BACnet Firmware Compatibility with Insight Software and Commissioning Tool
15 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
Insight Software or Online Commissioning Tool Revision
(With Optional Registry/XML Update)
Field Panel (Firmware Revision String)
Model (Product Number)
3.14 3.13c) 3.12c) 3.11c) 3.10b),c)
PXC Compact Series (PXCE)
PXC16.2-E.A, PXC16.2-ER.A a)
PXC24.2-E.A, PXC24.2-ER.A
PXC16.2-M.A, PXC16.2-MR.A a)
PXC24.2-M.A, PXC24.2-MR.A
PXC16.2-EF.A, PXC16.2-ERF.A a)
PXC16.2-EF32.A
PXC24.2-EF.A, PXC24.2-ERF.A
PXC24.2-EF32.A
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
PXC Compact Series (PXCE)
PXC16-E.A a), PXC16-ER.A a)
PXC24-E.A a), PXC24-ER.A a)
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
3.0
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
3.0
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
3.0
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
3.0
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2
3.1
3.0
Power Open Processor
BACnet/IP ALN a) (562-040)
3.2
3.1
3.0
3.2
3.1
3.0
3.2
3.1
3.0
3.2
3.1
3.0
3.2
3.1
3.0
Power MEC (MCNE)
1200EB (549-632)
1100EB/1110EB a) (549-630, 549-631)
1210EB a) (549-633)
3.2
3.1
3.0
3.2
3.1
3.0
3.2
3.1
3.0
3.2
3.1
3.0
3.2
3.1
3.0
Power MEC (MEFE)
1200EFB (549-634)
1210EFB a) (549-635)
3.2
3.1
3.0
3.2
3.1
3.0
3.2
3.1
3.0
3.2
3.1
3.0
3.2
3.1
3.0
Power MEC
1200ELB (549-636)
1210ELB a) (549-637)
3.2
3.1
3.0
3.2
3.1
3.0
3.2
3.1
3.0
3.2
3.1
3.0
3.2
3.1
3.0
a) This model is discontinued.
b) Insight and Commissioning Tool (CT) Revision 3.10 and earlier do not recognize the PXMT/S, UEC (in FLNmode) or MS/TP PPM.
c) Revisions in bold are supported with the latest firmware.rev.xml.
Section 4 - System Requirements and Compatibility
BACnet Firmware Compatibility with Insight Software and Commissioning Tool
16 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
BACnet Firmware Compatibility with Insight Software or Commissioning Tool Revisions 3.7 through 3.9.1
Insight Software or Online Commissioning Tool Revision
(With Optional Registry/XML Update)
Field Panel (Firmware Revision String)
Model (Product Number)
3.9e)
or 3.9.1e)
3.9.1 3.9 3.8.1 3.8 3.7
PXC Modular Series (PXME)
PXC00-E96.A, PXC100-E96.A
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2d)
3.2 b)
3.1
3.0.1
3.1
3.0.1
3.0.1a) 3.0.1 - -
PXC Compact Series (PXCE)
PXC36-E.A, PXC36-EF.A
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2b)
- - - - -
PXC Compact Series (PAAC)
PXC24.2-UCM.A
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
- - - - -
PXC Compact Series (PAAC)
PXC16.3-UCM.A
PXC24.3-UCM.A
3.4
3.3.1
3.3
3.2.5
- - - - -
PXC Compact Series (PXCE)
PXC16.2-E.A, PXC16.2-ER.A a)
PXC24.2-E.A, PXC24.2-ER.A
PXC16.2-M.A, PXC16.2-MR.A a)
PXC24.2-M.A, PXC24.2-MR.A
PXC16.2-EF.A, PXC16.2-ERF.A a)
PXC24.2-EF.A, PXC24.2-ERF.A
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2b)
3.1
3.1 - - - -
PXC Compact Series (PXCE)
PXC16-E.A a), PXC16-ER.A a)
PXC24-E.A a), PXC24-ER.A a)
3.4
3.3.1
3.3
3.2.5
3.2.4
3.2.3
3.2.2
3.2 b)
3.1
3.0
3.1
3.0
3.0 a) 3.0 3.0 3.0
Section 4 - System Requirements and Compatibility
P2 Firmware Compatibility with Desigo CC™
17 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
Insight Software or Online Commissioning Tool Revision
(With Optional Registry/XML Update)
Field Panel (Firmware Revision String)
Model (Product Number)
3.9e)
or 3.9.1e)
3.9.1 3.9 3.8.1 3.8 3.7
Power Open Processor
BACnet/IP ALN a) (562-040)
3.2b)
3.1
3.0
3.1
3.0
3.0a) 3.0 3.0 3.0
Power MEC (MCNE)
1200EB (549-632)
1100EB/1110EB a) (549-630, 549-631)
1210EB a) (549-633)
3.2b)
3.1
3.0
3.1
3.0
3.0a) 3.0 3.0 3.0
Power MEC (MEFE)
1200EFB (549-634)
1210EFB a) (549-635)
3.2b)
3.1
3.0
3.1
3.0
3.0a) 3.0 3.0 3.0
Power MEC
1200ELB (549-636)
1210ELB a) (549-637)
3.2b)
3.1
3.1 - - - -
a) Insight Revision 3.9 does not support MS/TP FLN, routing, and external trend.
b) Insight and Commissioning Tool (CT) Revisions 3.9.1 and earlier do not recognize the HOA Upgrade Kit or algorithmic alarming.
c) This model is discontinued.
d) Insight and Commissioning Tool (CT) Revisions 3.10 and earlier do not recognize the PXMT/S, UEC (in FLNmode) or MS/TP PPM.
e) With latest firmware.rev.xml.
P2 Firmware Compatibility with Desigo CC™ This section outlines which APOGEE firmware revisions are compatible with Desigo™ CC and the field panels that support those revisions.
P2 Firmware Compatibility with Desigo™ CC Software.
Desigo™ CC Revision
Field Panel (Firmware Revision String)
Model (Product Number)
2.1 2.0
PXC Modular Series (PME)
PXC00-PE96.A, PXC100-PE96.A
2.8.10
2.8.6
2.8.2
2.8.1
–
PXC Compact Series (EX36)
PXC36-PE.A, PXC36-PEF.A
2.8.10
2.8.6
2.8.5
–
PXC Compact Series (PXCP)
PXC16.2-P.A, PXC16.2-PR.Aa)
PXC24.2-P.A, PXC24.2-PR.A
2.8.10
2.8.6
2.8.5
2.8.4
2.8
–
PXC Compact Series (PXCE)
PXC16.2-PE.A, PXC16.2-PER.Aa)
PXC24.2-PE.A, PXC24.2-PER.A
2.8.10
2.8.6
2.8.5
2.8.4
2.8.3
–
Section 4 - System Requirements and Compatibility
P2 Firmware Compatibility with Desigo CC™
18 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
P2 Firmware Compatibility with Desigo™ CC Software.
Desigo™ CC Revision
Field Panel (Firmware Revision String)
Model (Product Number)
2.1 2.0
PXC Compact Series (EPXC)
PXC24.2-PEF.A, PXC24.2-PERF.A
PXC24.2-PEF32.A
2.8.10
2.8.6
–
PXC-16 and PXC-24
(Ethernet = PXCE, RS-485 = PXCP)
PXC16-PE.Aa), PXC16-PER.Aa)
PXC24-PE.Aa), PXC24-PER.Aa)
PXC16-P.Aa), PXC16-PR.Aa)
PXC24-P.Aa), PXC24-PR.Aa)
2.8.10
2.8.6
2.8.5
2.8.4
2.8.3
2.8
2.7.1
–
Power Open Processor
Ethernet TCP/IP ALNa) (562-002) (MBCE)
2.8.10
2.8
2.7
2.6.5
2.6.3
2.6
–
Power Open Processor
RS-485 ALNa) (562-001) (MBCP)
2.8
2.7
2.6.5
2.6
2.5.2
–
Power MEC (MCNE)
1100E (549-624)
1110E (549-625)
1200E (549-626)
1210E (549-627)
2.8.10
2.8
2.7
2.6.3
2.6
–
Power MEC (MEFE)
1200EF (549-628)
1210EF (549-629)
2.8.10
2.8
2.7
2.6.5
2.6.3
2.6
–
Power MEC (MCLE)
1200EL (549-644)
1210EL (549-645)
2.8
2.7
2.6.3
2.6
–
Power MEC (MECP)
1100 (549-610)
1101 (549-611)
1110 (549-612)
1200 (549-613)
1201 (549-614)
1210 (549-615)
1300 (549-616)
1310 (549-617)
2.8
2.7
2.6
–
Power MEC (MCFP)
1200F (549-620)
1210F (549-621)
1300F (549-622)
1310F (549-623)
2.8
2.7
2.6.5
2.6
–
Section 4 - System Requirements and Compatibility
P2 Firmware Compatibility with Desigo CC™
19 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
P2 Firmware Compatibility with Desigo™ CC Software.
Desigo™ CC Revision
Field Panel (Firmware Revision String)
Model (Product Number)
2.1 2.0
Power MEC (MCLP)
1200L (549-640)
1210L (549-641)
1300L (549-642)
1310L (549-643)
2.8
2.7
2.6
–
Power MEC (MECE)
100Ea) (549-016)
110Ea) (549-017)
200Ea) (549-018)
210Ea) (549-019)
2.8
2.7
2.6.3
2.6
2.5.3
–
Power MEC (MCFE)
200EFa) (549-011)
210EFa) (549-012)
2.8
2.7
2.6.5
2.6.3
2.6
2.5.3
–
Power MEC (MECF)
200Fa) (549-007)
210Fa) (549-008)
300Fa) (549-009)
310Fa) (549-010)
2.8
2.7
2.6
2.5.2
2.5
–
Power MEC (MECL)
200La) (549-407)
210La) (549-408)
300La) (549-409)
310La) (549-410)
2.8
2.7
2.6
2.5.1
–
a) This model is discontinued.
Section 4 - System Requirements and Compatibility
P2 Firmware Compatibility with Insight Software and Commissioning Tool
20 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
P2 Firmware Compatibility with Insight Software and
Commissioning Tool This section outlines which APOGEE firmware revisions are compatible with Insight software and Commissioning Tool (CT) (online mode), and the field panels that support those revisions.
NOTE: The Firmware.rev.xml update released with the current firmware revision includes all previous XML updates.
The Firmware.rev.xml and INS_3p3C.reg updates released with Firmware Revision 2.8 include all previous XML/registry updates.
APOGEE P2 Firmware Compatibility with Insight or Commissioning Tool Revisions 3.11 and Later
Field Panel (Firmware Revision String)
Model (Product Number)
Insight or Commissioning Tool Revision
3.14 3.13 3.12 3.11
PXC Modular Series (PME)
PXC00-PE96.A, PXC100-PE96.A
2.8.10b)
2.8.6
2.8.2
2.8.1
2.8.10b)
2.8.6
2.8.2
2.8.1
2.8.10b)
2.8.6
2.8.2
2.8.1
2.8.10b)
2.8.6b)
2.8.2
2.8.1
PXC Compact Series (EX36)
PXC36-PE.A, PXC36-PEF.A
2.8.10b)
2.8.6
2.8.5
2.8.10b)
2.8.6
2.8.5
2.8.10b)
2.8.6
2.8.5
2.8.10b)
2.8.6b)
2.8.5
PXC Compact Series (PXCP)
PXC16.2-P.A, PXC16.2-PR.Aa)
PXC24.2-P.A, PXC24.2-PR.A
2.8.10b)
2.8.6
2.8.5
2.8.4
2.8
2.8.10b)
2.8.6
2.8.5
2.8.4
2.8
2.8.10b)
2.8.6
2.8.5
2.8.4
2.8
2.8.10b)
2.8.6b)
2.8.5
2.8.4
2.8
PXC Compact Series (PXCE)
PXC16.2-PE.A, PXC16.2-PER.Aa)
PXC24.2-PE.A, PXC24.2-PER.A
2.8.10b)
2.8.6
2.8.5
2.8.4
2.8.3
2.8.10b)
2.8.6
2.8.5
2.8.4
2.8.3
2.8.10b)
2.8.6
2.8.5
2.8.4
2.8.3
2.8.10b)
2.8.6b)
2.8.5
2.8.4
2.8.3
PXC Compact Series (EPXC)
PXC24.2-PEF.A, PXC24.2-PERF.A
PXC24.2-PEF32.A
2.8.10b)
2.8.6
2.8.10b)
2.8.6
2.8.10b)
2.8.6
2.8.10b)
2.8.6b)
PXC-16 and PXC-24
(Ethernet = PXCE, RS-485 = PXCP)
PXC16-PE.Aa), PXC16-PER.Aa)
PXC24-PE.Aa), PXC24-PER.Aa)
PXC16-P.Aa), PXC16-PR.Aa)
PXC24-P.Aa), PXC24-PR.Aa)
2.8.10b)
2.8.6
2.8.5
2.8.4
2.8.3
2.8
2.7.1
2.8.10b)
2.8.6
2.8.5
2.8.4
2.8.3
2.8
2.7.1
2.8.10b)
2.8.6
2.8.5
2.8.4
2.8.3
2.8
2.7.1
2.8.10b)
2.8.6b)
2.8.5
2.8.4
2.8.3
2.8
2.7.1
Power Open Processor
Ethernet TCP/IP ALNc) (562-002) (MBCE)
2.8.10d)
2.8
2.7
2.6.5
2.6.3
2.6
2.8.10d)
2.8
2.7
2.6.5
2.6.3
2.6
2.8.10d)
2.8
2.7
2.6.5
2.6.3
2.6
2.8.10d)
2.8
2.7
2.6.5
2.6.3
2.6
Section 4 - System Requirements and Compatibility
P2 Firmware Compatibility with Insight Software and Commissioning Tool
21 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
Field Panel (Firmware Revision String)
Model (Product Number)
Insight or Commissioning Tool Revision
3.14 3.13 3.12 3.11
Power Open Processor
RS-485 ALNc) (562-001) (MBCP)
2.8
2.7
2.6.5
2.6
2.5.2
2.8
2.7
2.6.5
2.6
2.5.2
2.8
2.7
2.6.5
2.6
2.5.2
2.8
2.7
2.6.5
2.6
2.5.2
Power MEC (MCNE)
1100E (549-624)
1110E (549-625)
1200E (549-626)
1210E (549-627)
2.8.10b)
2.8
2.7
2.6.3
2.6
2.8.10b)
2.8
2.7
2.6.3
2.6
2.8.10d)
2.8
2.7
2.6.3
2.6
2.8.10d)
2.8
2.7
2.6.3
2.6
Power MEC (MEFE)
1200EF (549-628)
1210EF (549-629)
2.8.10b)
2.8
2.7
2.6.5
2.6.3
2.6
2.8.10b)
2.8
2.7
2.6.5
2.6.3
2.6
2.8.10d)
2.8
2.7
2.6.5
2.6.3
2.6
2.8.10d)
2.8
2.7
2.6.3
2.6.5
2.6
Power MEC (MCLE)
1200EL (549-644)
1210EL (549-645)
2.8
2.7
2.6.3
2.6
2.8
2.7
2.6.3
2.6
2.8
2.7
2.6.3
2.6
2.8
2.7
2.6.3
2.6
Power MEC (MECP)
1100 (549-610)
1101 (549-611)
1110 (549-612)
1200 (549-613)
1201 (549-614)
1210 (549-615)
1300 (549-616)
1310 (549-617)
2.8
2.7
2.6
2.8
2.7
2.6
2.8
2.7
2.6
2.8
2.7
2.6
Power MEC (MCFP)
1200F (549-620)
1210F (549-621)
1300F (549-622)
1310F (549-623)
2.8
2.7
2.6.5
2.6
2.8
2.7
2.6.5
2.6
2.8
2.7
2.6.5
2.6
2.8
2.7
2.6.5
2.6
Power MEC (MCLP)
1200L (549-640)
1210L (549-641)
1300L (549-642)
1310L (549-643)
2.8
2.7
2.6
2.8
2.7
2.6
2.8
2.7
2.6
2.8
2.7
2.6
Section 4 - System Requirements and Compatibility
P2 Firmware Compatibility with Insight Software and Commissioning Tool
22 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
Field Panel (Firmware Revision String)
Model (Product Number)
Insight or Commissioning Tool Revision
3.14 3.13 3.12 3.11
Power MEC (MECE)
100Ec) (549-016)
110Ec) (549-017)
200Ec) (549-018)
210Ec) (549-019)
2.8
2.7
2.6.3
2.6
2.5.3
2.8
2.7
2.6.3
2.6
2.5.3
2.8
2.7
2.6.3
2.6
2.5.3
2.8
2.7
2.6.3
2.6
2.5.3
Power MEC (MCFE)
200EFc) (549-011)
210EFc) (549-012)
2.8
2.7
2.6.5
2.6.3
2.6
2.5.3
2.8
2.7
2.6.5
2.6.3
2.6
2.5.3
2.8
2.7
2.6.5
2.6.3
2.6
2.5.3
2.8
2.7
2.6.5
2.6.3
2.6
2.5.3
Power MEC (MECF)
200Fc) (549-007)
210Fc) (549-008)
300Fc) (549-009)
310Fc) (549-010)
2.8
2.7
2.6
2.5.2
2.5
2.8
2.7
2.6
2.5.2
2.5
2.8
2.7
2.6
2.5.2
2.5
2.8
2.7
2.6
2.5.2
2.5
Power MEC (MECL)
200Lc) (549-407)
210Lc) (549-408)
300Lc) (549-409)
310Lc) (549-410)
2.8
2.7
2.6
2.5.1
2.8
2.7
2.6
2.5.1
2.8
2.7
2.6
2.5.1
2.8
2.7
2.6
2.5.1
a) This model is discontinued.
b) With latest firmware.rev.xml and System Profile patch.
APOGEE P2 Firmware Compatibility with Insight or Commissioning Tool Revisions 3.9 to 3.10
Insight or Commissioning Tool Revision
(With Latest XML Update)
Field Panel (Firmware Revision String) 3.10 3.9 or 3.9.1 with
Firmware.rev.xml
PXC Modular Series (PME)
PXC00-PE96.A, PXC100-PE96.A
2.8.10 d
2.8.6 d
2.8.2
2.8.1
2.8.10 d
2.8.6 b
2.8.2
2.8.1
PXC-36 (EX36)
PXC36-PE.A, PXC36-PEF.A
2.8.10 d
2.8.6 d
2.8.5
2.8.10 d
2.8.6 a,b
2.8.5 a
PXC-16 and PXC-24 (PXCP)
PXC16.2-P.A, PXC16.2-PR.Ac)
PXC24.2-P.A, PXC24.2-PR.A
2.8.10 d
2.8.6 d
2.8.5
2.8.4
2.8
2.8.10 d
2.8.6 a,b
2.8.5 a
2.8.4 a,b
2.8 a)
PXC-16 and PXC-24 (PXCE)
PXC16.2-PE.A, PXC16.2-PER.Ac)
PXC24.2-PE.A, PXC24.2-PER.A
2.8.10 d
2.8.6 d
2.8.5
2.8.4
2.8.3
2.8.10 d
2.8.6 a,b
2.8.5 a
2.8.4 a,b
2.8.3 a
Section 4 - System Requirements and Compatibility
P2 Firmware Compatibility with Insight Software and Commissioning Tool
23 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
Insight or Commissioning Tool Revision
(With Latest XML Update)
Field Panel (Firmware Revision String) 3.10 3.9 or 3.9.1 with
Firmware.rev.xml
PXC-16 and PXC-24 (EPXC)
PXC24.2-PEF.A, PXC24.2-PERF.A
PXC24.2-PEF32.A
2.8.10 d
2.8.6 d
2.8.10 d
2.8.6
PXC-16 and PXC-24
(Ethernet = PXCE, RS-485 = PXCP)
PXC16-PE.A c), PXC16-PER.A c)
PXC24-PE.A c), PXC24-PER.A c)
PXC16-P.A c), PXC16-PR.A c)
PXC24-P.A c), PXC24-PR.A c)
2.8.10 d
2.8.6 d
2.8.5
2.8.4
2.8.3
2.8
2.7.1
2.8.10 d
2.8.6 a,b
2.8.5 a
2.8.4 a,b
2.8.3 a
2.8 a
2.7.1 a
Power Open Processor
Ethernet TCP/IP ALN c) (562-002) (MBCE)
2.8.10 d
2.8
2.7
2.6.5
2.6.3
2.6
2.8.10 d
2.8
2.7
2.6.5
2.6.3
2.6
Power Open Processor
RS-485 ALN c) (562-001) (MBCP)
2.8
2.7
2.6.5
2.6
2.5.2
2.8
2.7
2.6.5
2.6
2.5.2
Power MEC (MCNE)
1100E (549-624)
1110E (549-625)
1200E (549-626)
1210E (549-627)
2.8.10 b
2.8
2.7
2.6.3
2.6
2.8.10 d
2.8
2.7
2.6.3
2.6
Power MEC (MEFE)
1200EF (549-628)
1210EF (549-629)
2.8.10 b
2.8
2.7
2.6.5
2.6.3
2.6
2.8.10 d
2.8
2.7
2.6.5
2.6.3
2.6
Power MEC (MCLE)
1200EL (549-644)
1210EL (549-645)
2.8
2.7
2.6.3
2.6
2.8
2.7
2.6.3
2.6
Power MEC (MECP)
1100 (549-610)
1101 (549-611)
1110 (549-612)
1200 (549-613)
1201 (549-614)
1210 (549-615)
1300 (549-616)
1310 (549-617)
2.8
2.7
2.6
2.8
2.7
2.6
Power MEC (MCFP)
1200F (549-620)
1210F (549-621)
1300F (549-622)
1310F (549-623)
2.8
2.7
2.6.5
2.6
2.8
2.7
2.6.5
2.6
Section 4 - System Requirements and Compatibility
P2 Firmware Compatibility with Insight Software and Commissioning Tool
24 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
Insight or Commissioning Tool Revision
(With Latest XML Update)
Field Panel (Firmware Revision String) 3.10 3.9 or 3.9.1 with
Firmware.rev.xml
Power MEC (MCLP)
1200L (549-640)
1210L (549-641)
1300L (549-642)
1310L (549-643)
2.8
2.7
2.6
2.8
2.7
2.6
Power MEC (MECE)
100E c) (549-016)
110E c) (549-017)
200E c) (549-018)
210E c) (549-019)
2.8
2.7
2.6.3
2.6
2.5.3
2.8
2.7
2.6.3
2.6
2.5.3
Power MEC (MCFE)
200EF c) (549-011)
210EF c) (549-012)
2.8
2.7
2.6.5
2.6.3
2.6
2.5.3
2.8
2.7
2.6.5
2.6.3
2.6
2.5.3
Power MEC (MECF)
200F c) (549-007)
210F c) (549-008)
300F c) (549-009)
310F c) (549-010)
2.8
2.7
2.6
2.5.2
2.5
2.8
2.7
2.6
2.5.2
2.5
Power MEC (MECL)
200Lc) (549-407)
210L c) (549-408)
300L c) (549-409)
310L c) (549-410)
2.8
2.7
2.6
2.5.1
2.8
2.7
2.6
2.5.1
a) Insight software and Commissioning Tool Revision 3.9.1 and earlier do not recognize the HOA
Upgrade Kit.
b) Insight or Commissioning Tool Revision 3.10 or later is required to recognize the new sensor types.
c) This model is discontinued.
d) With latest firmware.rev.xml and System Profile patch.
APOGEE P2 Firmware Compatibility with Insight or Commissioning Tool Revisions 3.6 to 3.8.1
Insight or Commissioning Tool Revision
(With Optional XML Update)
Field Panel (Firmware Revision String) 3.8.1 3.8 3.7 with
Firmware. rev.xml
3.7 3.6 with
Firmware. rev.xml
3.6
PXC Modular Series (PME)
PXC00-PE96.A, PXC100-PE96.A
2.8.2
2.8.1
- - - - -
PXC-16 and PXC-24 (PXCP)
PXC16.2-P.A, PXC16.2-PR.Ag)
PXC24.2-P.A, PXC24.2-PR.A
2.8 2.8 2.8 c,d) – 2.8 c,d) -
Section 4 - System Requirements and Compatibility
P2 Firmware Compatibility with Insight Software and Commissioning Tool
25 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
Insight or Commissioning Tool Revision
(With Optional XML Update)
Field Panel (Firmware Revision String) 3.8.1 3.8 3.7 with
Firmware. rev.xml
3.7 3.6 with
Firmware. rev.xml
3.6
PXC-16 and PXC-24
(Ethernet = PXCE, RS-485 = PXCP)
PXC16-PE.A g), PXC16-PER.A g)
PXC24-PE.A g), PXC24-PER.A g)
PXC16-P.A g), PXC16-PR.A g)
PXC24-P.A g), PXC24-PR.A g)
2.8
2.7.1
2.8
2.7.1
2.8 c,d)
2.7.1
2.7.1 2.8 c,d)
2.7.1 e)
-
Power Open Processor
Ethernet TCP/IP ALNg) (562-002) (MBCE)
2.8
2.7
2.6.5
2.6.3
2.6
2.8
2.7
2.6.5
2.6.3
2.6
2.8 c,d)
2.7
2.6.5
2.6.3
2.6
2.7
2.6.5
2.6.3
2.6
2.8 c,d)
2.7b)
2.6.5 a)
2.6.3 f)
2.6
2.6.5 a)
2.6.3f)
2.6
Power Open Processor
RS-485 ALN g) (562-001) (MBCP)
2.8
2.7
2.6.5
2.6
2.5.2
2.8
2.7
2.6.5
2.6
2.5.2
2.8 c,d)
2.7
2.6.5 a)
2.6
2.5.2
2.7
2.6.5 a)
2.6
2.5.2
2.8 c,d)
2.7b)
2.6.5 a)
2.6
2.5.2
2.6.5 a)
2.6
2.5.2
Power MEC (MCNE)
1100E (549-624)
1110E (549-625)
1200E (549-626)
1210E (549-627)
2.8
2.7
2.6.3
2.6
2.8
2.7
2.6.3
2.6
2.8c,d)
2.7
2.6.3
2.6
2.7
2.6.3
2.6
2.8c,d)
2.7b)
2.6.3f)
2.6
2.6.3f)
2.6
Power MEC (MEFE)
1200EF (549-628)
1210EF (549-629)
2.8
2.7
2.6.5
2.6.3
2.6
2.8
2.7
2.6.5
2.6.3
2.6
2.8c,d)
2.7
2.6.5a)
2.6.3
2.6
2.7
2.6.3
2.6.5a)
2.6
2.8c,d)
2.7b)
2.6.5a)
2.6.3f)
2.6
2.6.5a)
2.6.3f)
2.6
Power MEC (MCLE)
1200EL (549-644)
1210EL (549-645)
2.8
2.7
2.6.3
2.6
2.8
2.7
2.6.3
2.6
2.8c,d)
2.7
2.6.3
2.6
2.7
2.6.3
2.6
2.8c,d)
2.7b)
2.6.3f)
2.6
2.6.3f)
2.6
Power MEC (MECP)
1100 (549-610)
1101 (549-611)
1110 (549-612)
1200 (549-613)
1201 (549-614)
1210 (549-615)
1300 (549-616)
1310 (549-617)
2.8
2.7
2.6
2.8
2.7
2.6
2.8 c,d)
2.7
2.6
2.7
2.6
2.8 c,d)
2.7 b)
2.6
2.6
Power MEC (MCFP)
1200F (549-620)
1210F (549-621)
1300F (549-622)
1310F (549-623)
2.8
2.7
2.6.5
2.6
2.8
2.7
2.6.5
2.6
2.8 c,d)
2.7
2.6.5 a)
2.6
2.7
2.6.5 a)
2.6
2.8 c,d)
2.7 b)
2.6.5 a)
2.6
2.6.5 a)
2.6
Power MEC (MCLP)
1200L (549-640)
1210L (549-641)
1300L (549-642)
1310L (549-643)
2.8
2.7
2.6
2.8
2.7
2.6
2.8 c,d)
2.7
2.6
2.7
2.6
2.8 c,d)
2.7b)
2.6
2.6
Section 4 - System Requirements and Compatibility
P2 Firmware Compatibility with Insight Software and Commissioning Tool
26 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
Insight or Commissioning Tool Revision
(With Optional XML Update)
Field Panel (Firmware Revision String) 3.8.1 3.8 3.7 with
Firmware. rev.xml
3.7 3.6 with
Firmware. rev.xml
3.6
Power MEC (MECE)
100E g) (549-016)
110E g) (549-017)
200E g) (549-018)
210E g) (549-019)
2.8
2.7
2.6.3
2.6
2.5.3
2.8
2.7
2.6.3
2.6
2.5.3
2.8c,d)
2.7
2.6.3
2.6
2.5.3
2.7
2.6.3
2.6
2.5.3
2.8c,d)
2.7b)
2.6.3f)
2.6
2.5.3
2.6.3f)
2.6
2.5.3
Power MEC (MCFE)
200EF g) (549-011)
210EF g) (549-012)
2.8
2.7
2.6.5
2.6.3
2.6
2.5.3
2.8
2.7
2.6.5
2.6.3
2.6
2.5.3
2.8c,d)
2.7
2.6.5a)
2.6.3
2.6
2.5.3
2.7
2.6.3
2.6.5a)
2.6
2.5.3
2.8c,d)
2.7b)
2.6.5a)
2.6.3f)
2.6
2.5.3
2.6.5a)
2.6.3f)
2.6
2.5.3
Power MEC (MECF)
200F g) (549-007)
210F g) (549-008)
300F g) (549-009)
310F g) (549-010)
2.8
2.7
2.6
2.5.2
2.5
2.8
2.7
2.6
2.5.2
2.5
2.8 c,d)
2.7
2.6
2.5.2
2.5
2.7
2.6
2.5.2
2.5
2.8c,d)
2.7b)
2.6
2.5.2
2.5
2.6
2.5.2
2.5
Power MEC (MECL)
200L g) (549-407)
210L g) (549-408)
300L g) (549-409)
310L g) (549-410)
2.8
2.7
2.6
2.5.1
2.8
2.7
2.6
2.5.1
2.8 c,d)
2.7
2.6
2.5.1
2.7
2.6
2.5.1
2.8 c,d)
2.7 b)
2.6
2.5.1
2.6
2.5.1
a) Insight Revision 3.7 supports APOGEE Wireless FLN (Firmware Revision 2.6.5) without a registry/XML update.
b) ADAPTM and ADAPTS PPCL statements are incompatible with Insight and CT PPCL Editor.
c) Insight and Commissioning Tool Revision 3.7 and earlier cannot back up or restore AO-I type points (current outputs) for the PXC
Compact.
d) Insight and Commissioning Tool Revision 3.7 and earlier do not recognize TX-I/O modules or P1 BIMs.
e) Insight Revision 3.6 functionality is limited to backup and restore, the PXC Compact displays as an MEC, and new sensor types on
the PXC Compact are not supported. I/O configuration must be done through the HMI or Online CT 3.7.
f) Custom solution is required for Insight Revision 3.6 to support Field Panel GO graphics conversion.
g) This model is discontinued.
APOGEE P2 Firmware Compatibility with Insight or Commissioning Tool Revisions 3.4 to 3.5.1
Insight or Commissioning Tool Revision
(With Optional XML Update)
Field Panel (Firmware Revision String) 3.5.1 3.5 3.5.1 or 3.5 with
Firmware. Rev3.xml
3.4 3.4 with
Firmware.
Rev3.xml
Power Open Processor
Ethernet TCP/IP ALN d) (562-002) (MBCE)
2.6
2.5.3
2.6
2.5.3
2.8 b,c)
2.7a)
2.6
2.5.3
– –
Power Open Processor
RS-485 ALN d) (562-001) (MBCP)
2.6
2.5.2
2.6
2.5.2
2.8 b,c)
2.7a)
2.6
2.5.2
– 2.8 b,c)
2.6
2.5.2
Section 4 - System Requirements and Compatibility
P2 Firmware Compatibility with Insight Software and Commissioning Tool
27 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
Insight or Commissioning Tool Revision
(With Optional XML Update)
Field Panel (Firmware Revision String) 3.5.1 3.5 3.5.1 or 3.5 with
Firmware. Rev3.xml
3.4 3.4 with
Firmware.
Rev3.xml
Power MEC (MCNE)
1100E (549-624)
1110E (549-625)
1200E (549-626)
1210E (549-627)
2.6 2.6 2.8 b,c)
2.7a)
2.6
– –
Power MEC (MEFE)
1200EF (549-628)
1210EF (549-629)
2.6 2.6 2.8 b,c)
2.7a)
2.6
– –
Power MEC (MCLE)
1200EL (549-644)
1210EL (549-645)
2.6 2.6 2.8 b,c)
2.7a)
2.6
– –
Power MEC (MECP)
1100 (549-610)
1101 (549-611)
1110 (549-612)
1200 (549-613)
1201 (549-614)
1210 (549-615)
1300 (549-616)
1310 (549-617)
2.6 – 2.8 b,c)
2.7
2.6
– 2.8 b,c)
2.6
Power MEC (MCFP)
1200F (549-620)
1210F (549-621)
1300F (549-622)
1310F (549-623)
2.6 2.6 2.8 b,c)
2.7a)
2.6
– 2.8 b,c)
2.6
Power MEC (MCLP)
1200L (549-640)
1210L (549-641)
1300L (549-642)
1310L (549-643)
2.6 2.6 2.8 b,c)
2.7a)
2.6
– 2.8 b,c)
2.7 a)
2.6
Power MEC (MECE)
100E d) (549-016)
110E d) (549-017)
200E d) (549-018)
210E d) (549-019)
2.6
2.5.3
2.6
2.5.3
2.8 b,c)
2.7a)
2.6
2.5.3
– –
Power MEC (MCFE)
200EF d) (549-011)
210EF d) (549-012)
2.6
2.5.3
2.6
2.5.3
2.8 b,c)
2.7a)
2.6
2.5.3
– –
Power MEC (MECF)
200F d) (549-007)
210F d) (549-008)
300F d) (549-009)
310F d) (549-010)
2.6
2.5.2
2.5
2.6
2.5.2
2.5
2.8 b,c)
2.7a)
2.6
2.5.2
2.5
2.6
2.5.2
2.5
2.8b,c)
2.7 a)
2.6
2.5.2
2.5
Power MEC (MECL)
200L d) (549-407)
210L d) (549-408)
300L d) (549-409)
310L d) (549-410)
2.6
2.5.1
2.6
2.5.1
2.8 b,c)
2.7a)
2.6
2.5.1
2.6
2.5.1
2.8 b,c)
2.6
2.5.1
Section 4 - System Requirements and Compatibility
P2 Firmware Compatibility with Insight Software and Commissioning Tool
28 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
a) ADAPTM and ADAPTS PPCL statements are incompatible with Insight and CT PPCL Editor.
b) Insight and Commissioning Tool Revision 3.7 and earlier cannot back up or restore AO-I type points (current outputs) for the PXC
Compact.
c) Insight and Commissioning Tool Revision 3.7 and earlier do not recognize TX-I/O modules or P1 BIMs.
d) This model is discontinued.
APOGEE P2 Firmware Compatibility with Insight or Commissioning Tool Revisions 3.3
Insight or Commissioning Tool Revision
(With Registry Update)
Field Panel (Firmware Revision String) 3.3 with
Ins_3p3C.reg
3.3 with
Ins_3p3B.reg
3.3 with
Ins_3p3A.reg
3.3 with
Ins_3p3.reg
3.3 with
MBS_3p3A.reg
Power Open Processor
RS-485 ALN d) (562-001) (MBCP)
2.8c,d)
2.7a)
2.6
2.5.2
2.7a)
2.6
2.5.2
2.6
2.5.2
2.6
2.5.2
2.5.2
Power MEC (MECP)
1100 (549-610)
1101 (549-611)
1110 (549-612)
1200 (549-613)
1201 (549-614)
1210 (549-615)
1300 (549-616)
1310 (549-617)
2.8c,d)
2.7a)
2.6
2.7a)
2.6
2.6 2.6 –
Power MEC (MCFP)
1200F (549-620)
1210F (549-621)
1300F (549-622)
1310F (549-623)
2.8c,d)
2.7a)
2.6a)
2.7a)
2.6a)
2.6b) 2.6 b) –
Power MEC (MECF)
200F d) (549-007)
210F d) (549-008)
300F d) (549-009)
310F d) (549-010)
2.8c,d)
2.7a)
2.6a)
2.5.2b)
2.5 b)
2.7a)
2.6b)
2.5.2b)
2.5 b)
2.6b)
2.5.2b)
2.5 b)
2.5.2b)
2.5 b)
–
a) ADAPTM and ADAPTS PPCL statements are incompatible with Insight and CT PPCL Editor.
b) Adding FLN devices is not supported in System Profile.
b) Insight and Commissioning Tool Revision 3.7 and earlier cannot back up or restore AO-I type points (current outputs) for the PXC
Compact.
c) Insight and Commissioning Tool Revision 3.7 and earlier do not recognize TX-I/O modules or P1 BIMs.
d) This model is discontinued.
Section 4 - System Requirements and Compatibility
P2 Firmware Compatibility with Insight Software and Commissioning Tool
29 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
Firmware Compatibility with Insight Software and
Commissioning Tool—68302 Processor Field Panels This section outlines which APOGEE firmware revisions are compatible with Insight software and Commissioning Tool (CT) (online mode), and the field panels that support those revisions.
NOTE: The XML file or registry update provides the capability for some earlier revisions of Insight software or online Commissioning Tool to communicate with the field panel and to back up and restore the database. The XML file or registry update does not provide the new features or icons of the latest Insight software or online Commissioning Tool revision.
NOTE: The Firmware.rev.xml update released with the current firmware revision includes all previous XML updates.
The Firmware.rev.xml and INS_3p3C.reg updates released with Firmware Revision 2.8 include all previous XML/registry updates.
NOTE: All field panel controllers listed in this section have been discontinued. See the appropriate Configuration and Sizing Guidelines for availability of repaired parts.
APOGEE P2 Firmware Compatibility with Insight or Commissioning Tool Revisions 3.9 to 3.10
Insight or Commissioning Tool Revision
(With Optional XML Update)
Field Panel (Firmware Revision String) 3.10 3.9 or 3.9.1 with
Firmware.rev3.xml
3.9.1 3.9
Open Processor (OP)
(545-730, 545-726, 545-715, 545-701, 545-719,
545-716, 545-700, 545-818, 545-717, 545-705, 545-720)
2.8b)
2.6b)/2.6.1
2.1 to 2.5.2
2.8b)
2.6b)/2.6.1
2.1 to 2.5.2
2.8 b)
2.6 b)/2.6.1
2.1 to 2.5.2
2.8 b)
2.6 b)/2.6.1
2.1 to 2.5.2
MEC (68302) (MEC)
100 (549-001, 549-021)
101 (549-041)
110 (549-031)
200 (549-002, 545-022)
201 (549-042)
210 (549-032)
300 (549-003, 549-023)
310 (549-033)
2.6.1
2.5.2
2.1 to 2.5
2.6.1
2.5.2
2.1 to 2.5
2.6.1
2.5.2
2.1 to 2.5
2.6.1
2.5.2
2.1 to 2.5
FLN Controller (68302) (FLNC)
(545-796, 545-794, 545-489, 545-442, 545-793)
2.8b)
2.6b)/2.6.1
2.1 to 2.5.2
2.8b)
2.6b)/2.6.1
2.1 to 2.5.2
2.8 b)
2.6 b)/2.6.1
2.1 to 2.5.2
2.8 b)
2.6 b)/2.6.1
2.1 to 2.5.2
SCU V5 (68302) (SV5)
(545-887, 545-888, 545-884, 545-885, 545-831,
545-830, 545-488, 545-487, 545-765)
2.8b)
2.6b)/2.6.1
2.2 to 2.5.2
2.8b)
2.6b)/2.6.1
2.2 to 2.5.2
2.8 b)
2.6 b)/2.6.1
2.2 to 2.5.2
2.8 b)
2.6 b)/2.6.1
2.2 to 2.5.2
Section 4 - System Requirements and Compatibility
P2 Firmware Compatibility with Insight Software and Commissioning Tool
30 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
a) Wireless FLN is not supported in field panels with a 68302 processor (non-PowerPC).
b) Minimum of 6 MB of memory required.
APOGEE P2 Firmware Compatibility with Insight or Commissioning Tool Revisions 3.6 to 3.8.1
Insight or Commissioning Tool Revision
(With Optional XML Update)
Field Panel (Firmware Revision String) 3.8.1 3.8 3.7 with
Firmware. rev.xml
3.7 3.6 with
Firmware.
rev.xml
3.6
Open Processor (OP) (68302)
(545-730, 545-726, 545-715, 545-701,
545-719, 545-716, 545-700, 545-818,
545-717, 545-705, 545-720)
2.8b)
2.6b)/2.6.1
2.1 to 2.5.2
2.8b)
2.6b)/2.6.1
2.1 to 2.5.2
2.8b)
2.6b)/2.6.1
2.1 to 2.5.2
2.6b)/2.6.1
2.1 to 2.5.2
2.8b)
2.6b)/2.6.1
2.1 to 2.5.2
2.6b)/2.6.1
2.1 to 2.5.2
MEC (68302) (MEC)
100 (549-001, 549-021)
101 (549-041)
110 (549-031)
200 (549-002, 545-022)
201 (549-042)
210 (549-032)
300 (549-003, 549-023)
310 (549-033)
2.1 to 2.6.1 2.1 to 2.6.1 2.1 to 2.6.1 2.1 to 2.6.1 2.1 to 2.6.1 2.1 to 2.6.1
FLN Controller (68302) (FLNC)
(545-796, 545-794, 545-489, 545-442,
545-793)
2.8b)
2.7a, b)
2.6b)/2.6.1
2.1 to 2.5.2
2.8b)
2.7a, b)
2.6b)/2.6.1
2.1 to 2.5.2
2.8b, c, d, e)
2.7a, b)
2.6b)/2.6.1
2.1 to 2.5.2
2.7a, b)
2.6b)/2.6.1
2.1 to 2.5.2)
2.8 b, c, d, e)
2.7a, b)
2.6b)/2.6.1
2.1 to 2.5.2
2.7a, b)
2.6b)/2.6.1
2.1 to 2.5.2
SCU V5 (68302) (SV5)
(545-887, 545-888, 545-884, 545-885,
545-831, 545-830, 545-488, 545-487,
545-765)
2.8d)
2.7a)
2.6b)/2.6.1
2.2 to 2.5.2
2.8d)
2.7a)
2.6b)/2.6.1
2.2 to 2.5.2
2.8c,e,d)
2.7a)
2.6b)/2.6.1
2.2 to 2.5.2
2.7a)
2.6b)/2.6.1
2.2 to 2.5.2)
2.8c,e,d)
2.7a)
2.6b)/2.6.1
2.2 to 2.5.2
2.7a)
2.6b)/2.6.1
2.2 to 2.5.2
a) ADAPTM and ADAPTS PPCL statements are incompatible with Insight and CT PPCL Editor.
b) Minimum of 6 MB of memory required.
c) Insight and online Commissioning Tool Revision 3.7 and earlier cannot back up or restore AO-I type points (current outputs) for the
PXC Compact.
d) Wireless FLN is not supported in field panels with a 68302 processor (non-PowerPC).
e) Insight and online Commissioning Tool Revision 3.7 and earlier do not recognize TX-I/O modules or P1 BIMs.
Section 4 - System Requirements and Compatibility
P2 Firmware Compatibility with Insight Software and Commissioning Tool
31 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
APOGEE P2 Firmware Compatibility with Insight or Commissioning Tool Revisions 3.4 to 3.5.1
Insight or Commissioning Tool Revision
(With Optional XML Update)
Field Panel (Firmware Revision String) 3.5.1 3.5 3.5.1 or 3.5 with
Firmware. Rev3.xml
3.4 3.4 with
Firmware.
Rev3.xml
Open Processor (OP) (68302)
(545-730, 545-726, 545-715, 545-701, 545-
719, 545-716, 545-700, 545-818, 545-717,
545-705, 545-720)
2.6b)/2.6.1
2.1 to 2.5.2
2.6b)/2.6.1
2.1 to 2.5.2
2.8c,d,e)
2.6a,b)/2.6.1
2.1 to 2.5.2
2.6b)/2.6.1
2.1 to 2.5.2
2.8c,d,e)
2.6b)/2.6.1
2.1 to 2.5.2
MEC (68302) (MEC)
100 (549-001, 549-021)
101 (549-041)
110 (549-031)
200 (549-002, 545-022)
201 (549-042)
210 (549-032)
300 (549-003, 549-023)
310 (549-033)
2.1 to 2.6.1 2.1 to 2.6.1 2.1 to 2.6.1 2.1 to 2.6.1 2.1 to 2.6.1
FLN Controller (68302) (FLNC)
(545-796, 545-794, 545-489, 545-442, 545-
793)
2.6b)/2.6.1
2.1 to 2.5.2
2.6b)/2.6.1
2.1 to 2.5.2
2.8b, c, d, e)
2.7a,b)
2.6b)/2.6.1
2.1 to 2.5.2
2.6b)/2.6.1
2.1 to 2.5.2)
2.8 b, c, d, e)
2.7a,b)
2.6b)/2.6.1
2.1 to 2.5.2
SCU V5 (68302) (SV5)
(545-887, 545-888, 545-884, 545-885, 545-
831, 545-830, 545-488, 545-487, 545-765)
2.6b)/2.6.1
2.2 to 2.5.2
2.6b)/2.6.1
2.2 to 2.5.2
2.8 b, c, d, e)
2.7a,b)
2.6b)/2.6.1
2.2 to 2.5.2
2.6b)/2.6.1
2.2 to 2.5.2)
2.8 b, c, d, e)
2.7a,b)
2.6b)/2.6.1
2.2 to 2.5.2
a) ADAPTM and ADAPTS PPCL statements are incompatible with Insight and CT PPCL Editor.
b) Minimum of 6 MB of memory required.
c) Insight and online Commissioning Tool Revision 3.7 and earlier cannot back up or restore AO-I type points (current outputs) for the
PXC Compact.
d) Insight and online Commissioning Tool Revision 3.7 and earlier do not recognize TX-I/O modules or P1 BIMs.
e) Wireless FLN is not supported in field panels with a 68302 processor (non-PowerPC).
Section 4 - System Requirements and Compatibility
P2 Firmware Compatibility with Insight Software and Commissioning Tool
32 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
APOGEE P2 Firmware Compatibility with Insight or Commissioning Tool Revision 3.3
Insight or Commissioning Tool Revision
(With Optional Registry/XML Update)
Field Panel (Firmware
Revision String)
3.3 3.3 with
Ins_3p3C .reg
3.3 with
Ins_3p3B
.reg
3.3 with
Ins_3p3A
.reg
3.3 with
Ins_3p3. reg
3.3 with
MBS_3p3A .reg
3.3 with
MECF_3p3A.reg
or MECF_3p3.reg
Open Processor (OP)
(68302)
(545-730, 545-726, 545-
715, 545-701, 545-719,
545-716, 545-700, 545-
818, 545-717, 545-705,
545-720)
2.6b)/2.6.1
2.1 to 2.5.2
2.8b, c, d, e)
2.7a, b)
2.6b)/2.6.1
2.1 to 2.5.2
2.7a, b)
2.6a,b)/2.6.1
2.1 to 2.5.2
2.6b)/2.6.1
2.1 to 2.5.2
2.6b)/2.6.1
2.1 to 2.5.2
2.6b)/2.6.1
2.1 to 2.5.2
2.6b)/2.6.1
2.1 to 2.5.2
MEC (68302) (MEC)
100 (549-001, 549-021)
101 (549-041)
110 (549-031)
200 (549-002, 545-022)
201 (549-042)
210 (549-032)
300 (549-003, 549-023)
310 (549-033)
2.1 to 2.6.1 2.8b, c, d, e)
2.7a, b)
2.1 to 2.6.1
2.7a, b)
2.1 to 2.6.1
2.1 to 2.6.1 2.1 to 2.6.1 2.1 to 2.6.1 2.1 to 2.6.1
FLN Controller (68302)
(FLNC)
(545-796, 545-794,
545-489, 545-442,
545-793)
2.6b)/2.6.1
2.1 to 2.5.2
2.8b, c, d, e)
2.7a, b)
2.6b)/2.6.1
2.1 to 2.5.2
2.7a, b)
2.6b)/2.6.1
2.1 to 2.5.2
2.6b)/2.6.1
2.1 to 2.5.2)
2.6b)/2.6.1
2.1 to 2.5.2)
2.6b)/2.6.1
2.1 to 2.5.2)
2.6b)/2.6.1
2.1 to 2.5.2
SCU V5 (68302) (SV5)
(545-887, 545-888,
545-884, 545-885,
545-831, 545-830,
545-488, 545-487,
545-765)
2.6b)/2.6.1
2.2 to 2.5.2
2.8b, c, d, e)
2.7a, b)
2.6b)/2.6.1
2.2 to 2.5.2
2.7a, b)
2.6b)/2.6.1
2.2 to 2.5.2
2.6b)/2.6.1
2.2 to 2.5.2)
2.6b)/2.6.1
2.2 to 2.5.2)
2.6b)/2.6.1
2.2 to 2.5.2)
2.6b)/2.6.1
2.2 to 2.5.2
a) ADAPTM and ADAPTS PPCL statements are incompatible with Insight and CT PPCL Editor.
b) Minimum of 6 MB of memory required.
c) Insight and online Commissioning Tool Revision 3.7 and earlier cannot back up or restore AO-I type points (current outputs) for the
PXC Compact.
d) Insight and online Commissioning Tool Revision 3.7 and earlier do not recognize TX-I/O modules or P1 BIMs.
e) Wireless FLN is not supported in field panels with a 68302 processor (non-PowerPC).
Addendum, Revision 3.4 Build 12.65.0040
33 | 34
Siemens Industry, Inc. Release Notes 545-975-3p4
Building Technologies 2015-12-18
Addendum, Revision 3.4 Build 12.65.0040 ● An intermittent issue was found in Firmware 3.4 build 12.65 0039 that affected the
accuracy of TX-I/O digital inputs after a coldstart. This issue has been fixed.
Issued by Siemens Industry, Inc. Building Technologies Division 1000 Deerfield Pkwy Buffalo Grove IL 60089 +1 847-215-1000
© Siemens Industry, Inc., 2015
Technical specifications and availability subject to change without notice.
Document ID: 545-975-3p4 545-975-3p4(BA) Firmware Revision 3.4
Edition: 2015-12-18 Release Notes