Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 1 von 52
ARCAPRO 827A.E/X∗ - ∗∗∗ - ∗∗∗ - ∗ Electropneumatic Positioner for Linear and Quarter-turn Actuators Version without / with HART-Communication Operating Instructions
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 2 von 52
Legal information Warning notice system This documentation notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown be-low are graded according to the degree of danger.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel
The device may only be set up and used in conjunction with this documentation. Commissioning and operation of a device may only be performed by qualified personnel. Within the context of the safety notes in this documentation qualified persons are defined as persons who are authorized to commission, ground and label devices, systems and circuits in accordance with established safety practices and standards. Prescribed Usage
Note the following:
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software de-scribed. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the in-formation in this publication is reviewed regularly and any necessary corrections are included in subsequent editions.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
Indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
With a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.
CAUTION
Without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.
NOTICE
Indicates that an unintended result or situation can occur if the corresponding information is not taken into account.
WARNING
ARCA-positioner may only be used for the applications described in the relevant technical documentation. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be adhered to. The information in the relevant documentation must be observed.
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 3 von 52
Table of Contents
1 Introduction 4 2 General safety notes 6 3 Description 8 3.1 Function 8 3.2 Structure 8 3.3 Device Components 9 3.3.1 Motherboard 9 3.3.2 Electric Connections 10 3.3.3 Pneumatic Connections 10 3.3.4 Purging Air Switch 10 3.3.5 Restrictors 10 4 Mounting 12 4.1 Safety notes for mounting 12 4.2 Mounting Linear Actuator 13 4.2.1 Mounting Kit for "Integrated Fitting Linear Actuator" 13 4.2.2 Mounting Kit for "Linear Actuator IEC534" 15 4.3 Mounting Kit for "Quarter-turn Actuator VDI/VDE 3845" 17 4.4 Note on the Use of Positioners in Wet Environments 19 4.5 Positioners exposed to strong acceleration forces or vibrations 20 4.5.1 Slip clutch 21 4.5.2 Leverage ratio switch 21 5 Electric Connection 22 5.1 Electric Connection, not intrinsically safe 24 5.1.1 Basic device 24 5.1.2 Options 25 5.2 Connecting device with type of protection intrinsic safety 28 5.2.1 Basic device 28 5.2.2 Options 30 6 Pneumatic Connections 32 7 Commissioning 33 7.1 Preparations for Linear Actuators 35 7.1.1 Automatic Initialization of Linear Actuators 35 7.1.2 Manual Initialization of Linear Actuators 36 7.2 Preparations for Quarter-turn Actuators 38 7.2.1 Automatic Initialization of Quarter-turn Actuators 38 7.2.2 Manual Initialization of Quarter-turn Actuators 39 7.3 Copying Initialization Data (Positioner Exchange) 39 8 Overview of Parameters 40 8.1 Parameters 1 to 5 40 8.2 Parameters 6 to 51 41 8.3 Parameters A to P 42 9 Fault removal 43 10 Service and Maintenance 46 11 Technical Data 47
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 4 von 52
1 Introduction This operating instructions contains all information that will be required to connect and to commission the de-vice. It is aimed at persons who install the device mechanically, connect it electrically and commission it. Information and tips for projecting, parameterization and service contains the manual that can ordered by us. This operating instruction is valid for devises from firmware 4.00.00 in not intrinsically safe and intrinsically safe version. The content reflects the technical status at the time of printing. We reserve the right to make technical changes in the course of further development. Checking the consignment
Design of the nameplate
II 2 G Ex ia IIC T6/T4 Gb Ta = -30 …50/80°C TÜV 12 ATEX 085253 X
1
3 2
9
6 4
11
10
5 8 7
Stellungsregler 827A.X4-0BH-M10-G
Mat-Nr. XXXXXXX F-Nr. X XXXXXX
1 - Manufacturer 2 – Device name 3 - Type 4 - Consult operating instructions 5 - Safety class 6 - Auxiliary power (air supply) 7 - Approval 8 - ATEX marking for hazardous area 9 - Rated signal range 10 - Auxiliary power (voltage) 11 - Manufacturer serial number
WARNING
Using a damaged or incomplete device Danger of explosion − Do not use any damaged or incomplete devices.
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 5 von 52
Type key 827A.∗ ∗ – ∗ ∗ ∗ – ∗ ∗ ∗ – ∗
Connection thread G M20x1,5 / G 1/4 electric / N 1/2“ NPT / 1/4“ NPT pneumatic M M20x1,5 / 1/4“ NPT P 1/2“ NPT / G 1/4
mechanical 0 Standard actuator 2 without (for external potentiometer) pneumatic 1 single-acting
2 double-acting ( only stainless housing )
body M aluminium E stainless housing
communication 0 without communication H HART
binary output 0 without binary outputs B binary module S slot initiator module K contact module
analog - output 0 without analog - output A analog module connection 2 2 - wire
basic device 4 2 / 3 / 4 - wire
Ex - certificate E not explosion protected X II 2 G Ex ia IIC T6/T4 Gb (Type 827A.X∗-A∗∗-∗∗∗-∗ only II2G Ex ia IIC T4 Gb)
series Transportation and storage
Environmental protection Devices described in this programming manual can be recycled owing to the low content of noxious sub-stances in their version. Please contact a certified waste disposal company for eco-friendly recycling and to dispose of your old devices.
CAUTION
Insufficient protection during storage The packaging only provides limited protection against moisture and infiltration. − Provide additional packaging as necessary.
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 6 von 52
2 General safety notes Requirement for safe use This device left the factory in good working condition. In order to maintain this status and to ensure safe opera-tion of the device, observe these instructions and all the specifications relevant to safety. Observe the information and symbols on the device. Do not remove any information or symbols from the de-vice. Always keep the information and symbols in a completely legible state. Warning symbols on the device
Symbol Explanation of the warning symbols on the device
Consult operating instructions
Protect the device from shocks (otherwise the degree of protection is not guaranteed)
Laws and directives Observe the test certification, provisions and laws applicable in your country during connection, assembly and operation: − IEC 60079-14 (international) − EN 60079-14 (EG) − The working reliability regulation (Germany) Conformity with European directives The CE marking on the device shows conformity with the regulations of the following European guidelines: EMC 2004/108/EG Directive of the European Parliament and of the Council on the approximation of the
laws of the Member States relating to electromagnetic compatibility and repealing Direc-tive 89/336/EEC.
ATEX 94/9/EG Directive of the European Parliament and the Council on the approximation of the laws
of the Member States concerning equipment and protective systems intended for use in potentially explosive atmospheres. .
LVD 2006/95/EC Directive of the European Parliament and the Council on the approximation of the laws
of the Member States relating to electrical equipment designed for use within certain voltage limits.
The applied standards can be found in the EC conformity declaration of the device. Improver device modifications
WARNING
Improver device modifications Danger to personnel, system and environment can result from modifications to the device, particularly in hazardous areas. − Only carry out modifications that are described in the instructions for the device. Failure to observe this
requirement cancels the manufacturer's warranty and the product approvals.
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 7 von 52
Use in areas subject to explosion hazard
WARNING
Unsuitable device for the hazardous area Danger of explosion − Only use equipment that is approved for use in hazardous area and labelled accordingly.
− Make sure that the device is suitable for the area of use.
WARNING
Loss of the safety of the device with type of protection "Intrinsic safety Ex i" If the device has already been operated in non-intrinsically safe circuits or with a higher voltage, the safety of the device is no longer ensured for use in hazardous areas. There is a danger of explosion. − Connect the device in "intrinsic safety" type of protection solely to an intrinsically safe circuit. − Observe the specifications for the electrical data in the certificate
WARNING
Impermissible accessories and spare parts Danger of explosion in areas subject to explosion hazard. − Only use original accessories or original spare parts. − Observe all relevant installation and safety instructions described in the instructions for the device or en-
closed with the accessory or spare part.
WARNING
Open cable inlet or incorrect cable gland Danger of explosion in areas subject to explosion hazard. − Close the cable inlets for the electrical connections. Only use cable glands or plugs which are approved
for the relevant type of protection.
WARNING
Exceeded maximum ambient or process media temperature Danger of explosion in areas subject to explosion hazard. If the maximum permissible ambient and process media temperatures are exceeded, the temperature class of the device is no longer valid. − Make sure that the maximum permissible ambient and process media temperatures of the device are not
exceeded.
CAUTION
Electrostatic Sensitive Devices This device contains electrostatic sensitive devices. Electrostatic sensitive devices may be destroyed by voltages that are undetectable to a human. Voltages of this kind occur as soon as a component or an as-sembly is touched by a person who is not grounded against static electricity. The damage to a module as a result of overvoltage cannot usually be detected immediately. It may only become apparent after a long period of operation. Therefore, avoid electrostatic charge.
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 8 von 52
Qualified Personnel Qualified personnel are people who are familiar with the installation, mounting, commissioning, and operation of the product. These people have the following qualifications: − They are authorized, trained or instructed in operating and maintaining devices and systems according to
the safety regulations for electrical circuits, high pressures and aggressive as well as hazardous media. − For explosion-proof devices: They are authorized, trained, or instructed in carrying out work on electrical
circuits for hazardous systems. − Hey are trained or instructed in maintenance and use of appropriate safety equipment according to the
safety regulations. 3 Description 3.1 Function − The electro-pneumatic positioner, in combination with the drive, forms a regulation system. The current
position of the drive is detected using a servo potentiometer and is sent back as actual value x. The actual and target values are simultaneously displayed on the digital display.
− The setpoint w forms a current applied to the positioner, which in two-wire mode is also used to power the positioner. In 3- and 4-wire mode, power is supplied through a 24-V power input.
− The positioner works as a predictive five-point positioner, through whose output value ±∆y the integrated valves can be controlled by pulse length modulation.
− These positioning signals cause pressure changes in the drive chamber(s) and thus a repositioning of the drive until the regulation deviation returns to zero.
− Using three buttons and a digital display with the housing cover removed, operation (manual mode) and configuration (structuring, initialization, and parameterization) can be performed.
− Normally the basic device has one binary input (BE1). This can be individually configured, and is particu-larly provided for blocking the operating levels.
− To be able to use the positioner in a variety of mechanically different rotational and linear actuators, it has a friction clutch and a switchable gear.
3.2 Structure
The following chapters describe the mechanical and electrical structure, components, and principle functional-ity of the positioner. The positioner is used to adjust and regulate pneumatic drives. The positioner works electropneumatically, using compressed air as auxiliary power The positioner can e.g. regulate valves with: - Linear actuator (Figure 3-1) or - Quarter turn actuator VDI/VDE 3845 (Figure 3-2) For linear actuators, there are various add-on extensions available - NAMUR or. IEC 534 - integrated addition (ARCA, SAMSON) - integrated addition according to VDI/VDE 3847 You can mount the positioner on the usual drives and operate it with the usual drives.
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 9 von 52
The device is available for single-acting and double-acting actuators and for potentially explosive applications and applications that are not potentially explosive.
1 Actuator 2 Positioner, single-acting in metal-housing 3 Lantern 4 Manometer block, single-acting 5 Valve
Figure 3-1 Positioner fitted to a linear actuator Figure 3-2 Positioner fitted to a quarter-turn actuator (single-acting) (double-acting) 3.3 Device Components
Figure 3-3 Structure 3.3.1 Motherboard The motherboard contains: - CPU - Memory - A/D-converter - Display - Operating buttons - Terminal strips to connect the optional module to the motherboard
1. Input: supply air 2. Output: Actuating pressure Y1 3. Display 4. Output: Actuating pressure Y2 1) 5. Control buttons 6. Restrictor 7. Restrictor Y1 1) 8. Restrictor Y2 1)
9. Silencer 10. leverage ratio switch 11. Slip clutch adjusting wheel 12. Connection terminals motherboard 13. Connection terminals for optional module 14. Blinding plug 15. Cable gland 16. Terminal plate on cover 17. Purging air selector 1) for double-acting drives
1
2
3
4
5
1
2
3
1 Positioner, double-acting in plastic housing 2 Quarter-turn actuator 3 Manometer block, double-acting
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 10 von 52
3.3.2 Electric Connections
The connecting terminals for the base device, the optional analog, binary and slot initiator modules are ar-ranged at the front left-hand edge, and are displaced with respect to one another in a stepped pattern.
An assembly cover secures the components against being pulled out, and prevents incorrect assembly. 3.3.3 Pneumatic Connections
The pneumatic connections (G1/4) are located on the right-hand side of the positioner
Exhaust air outlet E with silencer on the bottom of the device
Actuating pressure Y1 in single-acting and double-acting actuators
Feedback shaft Air supply Pz
Actuating pressure Y2 on double-acting actuators
Figure 3-4 Pneumatic connections Connection versions
In addition, the rear of the positioner has pneumatic connections for integrated fitting of single-acting linear actuators: - actuating pressure Y1 - exhaust air outlet E
Except in cases of integrated ARCA fitting, these connections are closed by screws. The exhaust air outlet E can be used to supply the sensing area and the spring chamber with dry, instrumentation-quality air to prevent corrosion.
Figure 3-6 illustrates the versions of the pneumatic connections for the various types of actuator, the position-ing effect and the safety position after failure of the auxiliary power supply.
3.3.4 Purging Air Switch The purging air switch is accessible when the housing is open above the pneumatic connection strip on the valve block. − In the IN position the interior of the housing is flushed by very small quantities of clean, dry instrumentation-
quality air. − In the OUT position, the purging air is fed directly outside.
Figure 3-5 Purging air switch on the valve block
CAUTION
Before working on the control valve Note that before working on the control valve, you must first move it to the safety position. Make sure that the control valve has reached the safety position. If you only interrupt the pneumatic auxiliary power supply to the positioner, the safety position may in some cases only be attained after a certain delay period.
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 11 von 52
On rotary actuators,it is usual to define theanti-clockwise direction ofrotation – seen looking atthe valve's operatingshaft – as "OPEN".
Open
Closed
up down
OpenClosed
Open
ActuatingpressureConnection
Y1
Y1
Y2
Open
ClosedClosed
Y1
Y1
Y2
Y1
Closed
Y2
Open
Open
Open
Closed
Open
Closed
Closed
Y1
Last position(before failure ofauxiliary power)
Last position(before failure ofauxiliary power)
Y1
Y1
Y2
up
downdown down
down
up
up
upup
down
up
down
up
down
Safety position following failure of the auxiliary powerelectrical pneumatic
Actuator type
Figure 3-6 Pneumatic connection positioning effect
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 12 von 52
3.3.5 Restrictors Note The exhaust air valve is always open in the de-energized state. − In order to achieve floating times of > 1.5 s on small actuators, it is possible to reduce the air power by
means of the restrictors Y1 and Y2. − By turning to the right, the air power is reduced until it is completely blocked − In order to adjust the restrictors, it is recommended that they are closed and then slowly opened (see ini-
tialization RUN3). − In case of double-acting valves, ensure that both restrictors have approximately the same setting.
Y 1 Y 2 Figure 3-7 Restrictors 4 Mounting 4.1 Safety notes for mounting
CAUTION
Incorrect mounting The device can be damaged, destroyed or its functionality impaired through improper mounting. . − Before installing ensure there is no visible damage present on the device. − Make sure that process connectors are clean, and suitable gaskets and glands are used. − Mount the device using suitable tools.
CAUTION
Mechanical impact effect It is essential that the following sequence is observed during assembly in order to avoid injury or mechanical damage to the positioner/mounting kit: 1. Mechanically mount the positioner 2. Connect the auxiliary electrical power supply 3. Connect the pneumatic auxiliary power 4. Carry out the commissioning procedure
NOTICE
Loss of degree of protection Damage to device if the enclosure is open or not properly closed. The degree of protection specified on the nameplate is no longer guaranteed.
hexagon socket 2,5 mm
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 13 von 52
4.2 Mounting Linear Actuator 4.2.1 Mounting Kit for "Integrated Fitting Linear Actuator"
Included with the "integrated fitting linear actuator" are (see Figure 4-1 for identifying numbers):
Serial no.
No. of items
Name Note
1 1 Driver pin cpl. with roller mounted on lever (2) 2 1 Lever 3 2 Washer B6.4 - DIN 125 - A2 4 1 Spring washer A6 – DIN 137A- A2 5 1 Lock washer A6 – DIN 127- A2 6 1 Cylinder head bolt M6 x 25 DIN 7984 - A2 7 1 Hexagonal nut M6 - DIN 934 - A4 8 1 Square nut M6 - DIN 557 - A4 9 2 Cylinder head bolt M8 x 65 - DIN 912 - A2
10 2 Lock washer A8 - DIN 127 - A2 11 2 Screw plug 12 1 O-ring 13 x 2.5
Mounting procedure (see Figure 4-1) 1. Adjust the pin (1) on the previously assembled lever to the value of the stroke range given on the actuator
or, if this is not available as a scale value, at the next largest scale value. In case of uncertainty with regard to the real actuator stroke (pneumatic actuators often have a travel resource) you always have to choose the next large scale value. The centre of the pin must be positioned at the scale value. The same value can later be set during the commissioning under the parameter 3.YWAY, in order to display the displacement in mm after the initialization.
2. Push the lever to the stop on the controller axis, and fix it with cylinder head screw (6). 3. Open the rear actuating pressure outlet by removing the screw (13) and the O-ring (14). 4. When fitting with spring chamber exhaust air supply open the exhaust air outlet by removing the screw (15)
and the O-ring (16). 5. Seal the actuating pressure outlet with screw plug (11). When fitting with exhaust air supply remove ex-
haust air silencer and seal. 6. Insert the O-ring (12) in the intermediate bracket recess. 7. Locate the positioner on the actuator in such a way that the roller passes between the pins (17). 8. Align the controller horizontally at the intermediate bracket, and assemble it with the screws (9) and lock
washers (10).
CAUTION
Humid environment/dry compressed air Install the positioner in a humid environment such that the positioner shaft does not freeze at low ambient temperatures. Ensure that water does not seep through an open enclosure or an open gland. Water may seep through if the positioner is not installed and connected on-site immediately and finally. As a general rule, the positioner must be operated only with dry compressed air. Therefore, use the custom-ary water separator. An additional dryer is required in extreme cases. The use of dryers is especially impor-tant when you operate the positioner at low ambient temperatures. Set the Purge air switch to the "OUT" position when installing on the pneumatic block, above the pneumatic connections.
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 14 von 52
1) 2)
3)
14
13
17
1211
9
10
8
1 1
6
5
3
2
3 4
7
15
16
Figure 4-1 Mounting procedure for integrated fitting
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 15 von 52
4.2.2 " Mounting Kit for "Linear Actuator IEC534
The "linear actuator IEC 534" mounting kit, stroke 3 … 35 mm, includes (see Figure 4-3 for identifying num-bers): Serial no.
No. of items
Name Note
1 1 NAMUR fitting angle IEC 534 Standardised connecting location for fitting bracket with rib, column or flat surface
2 1 Sensing hoop Guides the roller with the driver pin and turns the lever arm 3 2 Clamping piece Assembly of the sensing hoop to the actuator's spindle 4 1 Driver pin cpl. with roller Mounted on lever (5) 5 1 NAMUR lever For stroke range 3 … 35 mm or (stroke range > 35 … 130 mm,
order separately, see figure 4-2) 6 2 U-bolts Only far actuators with columns 7 4 Hexagonal screw M8 x 20 DIN 933–A2 8 2 Hexagonal screw M8 x 16 DIN 933–A2 9 6 Lock washer A8 - DIN 127–A2
10 6 Washer B 8.4 - DIN 125–A2 11 2 Washer B 6.4 - DIN 125–A2 12 1 Spring washer A6 - DIN 137A–A2 13 3 Lock washer A6 - DIN 127–A2 14 3 Cylinder head bolt M6 x 25 DIN 7984–A2 15 1 Hexagonal nut M6 - DIN 934–A4 16 1 Square nut M6 - DIN 557–A4 17 4 Hexagonal nut M8 - DIN 934–A4
Assembly procedure (see Figure 4-3) 1. Assemble the clamping pieces (3) using the hexagonal screws (14) and lock washers (13) to the actuator
spindle. 2. Push the sensing hoop (2) into the cut-outs in the clamping piece. Adjust to the required length, and tight-
ened the screws so that it is still just possible to push the sensing handle. 3. Adjust the pin (4) on the previously assembled lever to the value of the stroke range given on the actuator
or, if this is not available as a scale value, at the next largest scale value. In case of uncertainty with regard to the real actuator stroke (pneumatic actuators often have a travel resource) you always have to choose the next large scale value. The centre of the pin must be positioned at the scale value. The same value can later be set during the commissioning under the parameter 3.YWAY, in order to display the displacement in mm after the initialization.
4. Push the lever to the stop on the controller axis, and fix it with cylinder head screw (14). 5. Assemble the fitting angle (1) with two hexagonal screws (8), lock washer (9) and washers (10) to the rear
of the positioner. The choice of the hole row depends on the width of the actuator's intermediate bracket width. The roller should engage in the sensing hoop (2) as close to the spindle as possible, but must not touch the clamping piece.
6. Hold the positioner with the fixing angle to the actuator in such a way that the pin (4) passes inside the sensing hoop (2).
7. Tighten the sensing hoop. 8. Prepare the assembly parts in accordance with the actuator type:
- Actuator with a rib: hexagonal bolt (7), washer (10) and lock washer (9). - Actuator with a flat surface: four hexagonal bolts (7) with washer (10) and lock washer (9). - Actuator with columns: two U-bolts (6), four hexagonal nuts (17) with washer (10) and lock washer (9).
9. Attach the positioner with the previously prepared assembly parts to the intermediate bracket. Adjust the height of the positioner so that the horizontal position of the lever is achieved as close as possible to the centre of the stroke. The actuator's lever scale provides orientation here. It is essential that the horizontal lever position is passed through within the range of the stroke.
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 16 von 52
33°5 10 15 20
25 30 3590°
90° 110 1309070605040
1
2
Figure 4-2 NAMUR lever 3 ... 35 mm (1), NAMUR lever > 35 … 130 mm (2)
2
13
14
3
1 )
3 )
4 )
1
8 9
10
8 9
10
1
7
9
10
7
9
10
17
9
10
6
F itting to lantern w ith colum ns
F itting to lantern w ith fla t surface
16
14
14
13
11
5
11 12
15
2 )
Figure 4-3 Mounting procedure for IEC 534 inear actuator
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 17 von 52
4.3 Mounting Kit for “Quarter-turn Actuator VDI/VDE 3845"
Included with the "VDI/VDE 3845 quarter-turn actuator" mounting kit are (see Figure 4-4 for identifying num-bers): Serial no. No. of
items Name Note
2 1 Coupling wheel Fitted to the position feedback shaft of the positioner 3 1 Driver pin Fitted to the actuator's shaft stub 4 1 Labels Display of the actuator position, consisting of: 4.1 and 4.2
4.1 8 Scale Various divisions 4.2 1 Pointer Reference point for scale 14 4 Hexagonal screw DIN 933 - M6 x 12 15 4 Retaining washer S6 16 1 Cylinder head bolt DIN 84 - M6 x 12 17 1 Washer DIN 125 – 6.4 18 1 Hexagonal socket bolt Pre-assembled with coupling wheel 19 1 Hexagon key For item 18
Assembly procedure (see Figure 4-4) 1. Attach the VDI/VDE 3845 fitting bracket ((9), actuator-specific, supplied by actuator manufacturer, see Fig-
ure 3-8) to the rear of the positioner, and fix it in place with the hexagonal screws (14) and retaining wash-ers (15).
2. Stick the pointer (4.2) on the fitting bracket at the middle of the centring hole. 3. Push the coupling wheel (2) as far as it will go on the positioner axis, pull it back about 1 mm, and tighten
the hexagonal socket bolt (18) with the supplied hexagonal key. 4. Place the driver pin (3) on the actuator's shaft stub and tighten it with cylinder head bolt (16) and washer
(17). 5. Carefully place the positioner with the fitting bracket on the actuator so that the pin of the coupling wheel
engages with the driver pin. 6. Align the positioner / fitting bracket centrally on the actuator, and screw tight (screws are not included with
the supply, but are part of the actuator's fitting bracket!). 7. When commissioning according to chapter 7 has been completed, take the actuator to its end position and
stick the scale (4.1) on to the coupling wheel (2) according to the direction of rotation and the turning range. The scale is self-adhesive!
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 18 von 52
3
2
2
9
9
1415
2 )1 )
3 )
4 .2
18
4 )
17
16
4.1
0 % 2 0 4 0 60 8 0 10 0%
5 )
2
3
Figure 4-4 Mounting procedure for VDI/VDE 3845 quarter-turn actuator
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 19 von 52
18
Positioner
Quarter-turn actuator
Section A - B
Figure 4-5 Mounted positioner for quarter-turn actuator
a = 4 (0,16) b = 12 (0,47) Figure 4-6 Fitting bracket (supplied by actuator manufacturer), dimensions 4.4 Note on the Use of Positioners in Wet Environments
This information provides you with important notes on assembling the positioner in wet environments (frequent heavy rain and/or persistent tropical condensation) in which protection class IP66 is no longer sufficient, in particular when there is a risk that the water might freeze. Avoid the unfavourable mounting positions: − To prevent fluids seeping through during normal operation of the device, e.g. through exhaust air openings. − Otherwise the digital display becomes poorly legible.
CAUTION
Never clean the positioner with a high pressure cleaner. Protection class IP66 is inadequate for this.
Quarter-turn actuator
Positioner fixing plane
2 Coupling wheel 3 Driver pin 4 Labels 4.1 Scale 4.2 Pointer 9 VDI/VDE 3845-fitting bracket 10 Feedback shaft 14 Hexagonal screw M6 x 12 15 Retaining washer S6 16 Cylinder head boltM6 x 12 17 Washer 18 Hexagon key
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 20 von 52
Figure 4-7 Favourable and unfavourable installation positions
If local conditions force you to operate the positioner in an unfavourable installation position, you can prevent the entry of water through additional measures. Additional measures
The steps necessary to prevent the entry of water depends on the installation position chosen. In certain cases you may need: - Threaded joint with sealing rings (e. g. FESTO: CK -¼ -PK-6) - Plastic hose, approx. 20 to 30 cm (e. g. FESTO: PUN- 8x1,25 SW) - Cable ties (number and length depend on the local conditions)
Procedure 1. Arrange the pipes in such a way that rainwater or condensation that runs along the length of the pipes can
drop off before reaching the positioner's connection strip. 2. Check that the seals for the electrical connections are correctly seated. 3. Check that the seal of the housing cover is not damaged or soiled. Clean or replace it if necessary. 4. If possible, mount the positioner in such a way that the sintered bronze silencer on the underneath of the
housing is pointing downwards (vertical installation position). If this is not possible, the silencer should be replaced by a plastic hose using a suitable threaded joint.
Assembling the Threaded Joint with Plastic Hose 1. Unscrew the sintered bronze silencer from the exhaust air opening on the underside of the housing. 2. Screw the threaded joint mentioned above into the outlet opening. 3. Fit the plastic hose mentioned above to the threaded joint and check that it is tightly seated. 4. Use a cable tie to fasten the plastic hose to the fittings in such a way that the opening is pointing down-
wards. 5. Check that the hose is not kinked, and that the exhaust air can flow out easily. 4.5 Positioners exposed to strong acceleration forces or vibrations High acceleration forces occur on fittings that are heavily mechanically stressed, such as breakaway flaps, heavily shaking or vibrating valves or "steam hammer". These forces can be well outside the range specified in the technical data. In extreme cases this can result in displacement of the slip clutch or the leverage ratio switch. In these cases the positioner is fitted as standard with a locking device for the slip clutch with which displace-ment as a result of the above-mentioned influences is inhibited. The adjustment function is accessible beneath the black adjusting wheel of the slip clutch and recognisable on the yellow wheel with slots. The null point setting and slip clutch adjustment functions are marked with symbols on an auxiliary plate The clamping piece for the transmission leverage ratio switch is located under the terminals and is also fitted with a yellow adjusting wheel with slots.
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 21 von 52
4.5.1 Slip clutch
Procedure After the positioner has been fitted and fully set into operation, the slip clutch can be locked as follows: 1. Place a commercial screwdriver of about 4 mm wide in a slot in the yellow wheel. 2. Turn the yellow wheel anti-clockwise with the screwdriver until it latches detectably. The slip clutch is
thereby locked. 3. A locked slip clutch is to be recognised by an approximately 1 mm wide gap between the yellow and black
wheel. 4. If a null point setting is necessary, e.g. after a drive change, the locking is released by a clockwise rotation
up to the stop of the yellow wheel. After the null point setting the slip clutch can be fixed again as described above.
4.5.2 Leverage ratio switch
Starting from the neutral position (as-delivered condition) the leverage ratio switch can be adjusted as follows: 1. Plug a conventional 4 mm wide screwdriver into a slot in the yellow wheel. 2. Then turn the adjustment wheel in accordance to the chosen gearing position (33° or 90°) clockwise or anti-
clockwise until it snaps in audibly. 3. An adjusted fixed leverage ratio switch is recognizable from the asymmetric position of the adjustment
wheel. 4. If you have to switch over the gearing, the adjustment has to be loosen by turning the adjustment wheel into
neutral position first.
Figure 4-8 Locking the slip clutch and leverage ratio switch
slip clutch and leverage ratio switch
Figure 4-9 Arrester device External Travel Acquisition
External travel acquisition is a possibility for those cases in which the measures described above are not suffi-cient, such as when vibration is heavy and persistent, at particularly high or low ambient temperatures, or in the presence of nuclear radiation. In this case the special positioner (see Type Code) is used at a distance from the fitting.
More information contains the appendix to the manual 827.EDP.
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 22 von 52
5 Electric connection Basic safety instructions
WARNING
Improper power supply Danger of explosion in hazardous areas as result of incorrect power supply, e.g. using alternating current instead of direct current. − Connect the device in accordance with the specified power supply and signal circuits. The relevant speci-
fications can be found in the certificates or on the nameplate.
WARNING
Unsafe extra-low voltage Danger of explosion in areas subject to explosion hazard due to voltage flashover − Connect the device to an extra-low voltage with safe isolation
WARNING
Connecting device in energized state Danger of explosion in areas subject to explosion hazard. − Connect devices in hazardous areas only in a de-energized state. Exception: Circuits of limited energy may also be connected in the energized state in hazardous areas.
WARNING
Lack of equipotential bonding Danger of explosion through compensating currents or ignition currents through lack of equipotential bond-ing. − Ensure that the device is potentially equalized. Exception: It may be permissible to omit connection of the equipotential bonding for devices with type of protection "In-trinsic safety Ex i".
WARNING
Unprotected cable ends Danger of explosion through unprotected cable ends in hazardous areas. − Protect unused cable ends in accordance with IEC/EN 60079-14
WARNING
Improper laying of shielded cables Danger of explosion through compensating currents between hazardous area and the non-hazardous area. − Only ground shielded cables that run into the hazardous area at one end. − If grounding is required at both ends, use an equipotential bonding conductor.
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 23 von 52
Owing the reasons pertaining to tightness (IP enclosure rating) and the required tensile strength, only use the cables having a diameter ≥ 8 mm for standard M20x1.5 cable gland, or use a suitable seal insert in case of smaller diameters.
In the NPT version, the positioner is delivered with a coupling. When inserting a counter piece in the coupling, ensure that the maximum permissible torque of 10 Nm is not exceeded. Two-wire mode Note To maintain the auxiliary power, the current iy must be ≥ 3.6 mA
WARNING
Unsuitable cables and/or cable glands Danger of explosion in areas subject to explosion hazard if cables and/or cable glands are connected which do not match one another or comply with the technical requirements. Before taking the device into operation let the device adapt for several hours in the new environment. − Tighten the cable glands in accordance with the torques specified − When replacing cable glands use only cable glands of the same type. − After installations check that the cables are seated firmly.
CAUTION
Condensation in the device Damage to device through formation of condensation if the temperature difference between transportation or storage and the mounting location exceeds 20 °C − Before taking the device into operation let the device adapt for several hours in the new environment.
CAUTION
Ambient temperature too high Damage to cable sheath − At an ambient temperature ≥ 60 °C, use heat-resistant cables suitable for an ambient temperature at
least 20 °C higher.
CAUTION
Connection of voltage source to current input Device damage if a voltage source is connected to the current input Iw (terminals 6 and 7). − Never connect the current input Iw to a voltage source, otherwise the positioner may be destroyed. − Always use a voltage source with a maximum output current of I = 20 mA.
WARNING
Version „Ex i“ As auxiliary power, control, and signal circuits, only certified intrinsically safe circuits may be connected.
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 24 von 52
5.1 Electric connection, not intrinsically safe 5.1.1 Basic device
+
J
4 … 20 mAPositioner
Binary input 1
6 7 8 9 10
+3 V
HART-Communicator
AE
Figure 5-1 2- wire connection, not for explosive regions Type 827A.E2
+ 4 … 20 mA
Binary input 1
HART-Communicator
5 4 3
+3 V
6
7 8 9
10
A
2
E
Positioner
J
Figure 5-2 2-wire connection, not for explosive regions Type 827A.E4
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 25 von 52
+
4 … 20 m A
2 3
B inaryinpu t 1
J
*) only for 3-wire co nne ct ion
+
18 … 30 V
HART-Comm unicator
6
10 9 8 7
EA
U 4 5
*)
* )
Positione r
Figure 5-3 3/4-wire connection not for explosive regions Type 827A.E4 5.1.2 Options Analog module
UH 61
62 JE
Analog module
+
+
≤ 35 V
Figure 5-4 Analog module not for explosive regions Binary module
BE2
Fault signal
Limit value A1
Limit value A2
Binary module
+
12
+13 V
+4,5 V ≥ 1
2122
+
+ 3 V
3132
4142
5152
+
+
1K
1K
1K
11≤ 30 V
≤ 35 V
≤ 35 V
≤ 35 V
Figure 5-5 Binary module not for explosive regions
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 26 von 52
Slot initiator module
Fault signal
Limit value A1
Limit value A2
Slot initiator module
3132
4142
51
52
+
+
+
2K1
10K
8,2 V
8,2 V
8,2 V
Figure 5-6 Slot initiator module not for explosive regions Contact module
DANGER
Low-voltage supply -Version not intrinsically safe When you supply the module in the non-intrinsically safe version with low voltage, you must be sure to ob-serve the following safety rules before starting work on the device: 1. Isolate the device from power. Use a circuit breaker positioned near the device to do this. 2. Make sure that the device cannot be switched back on inadvertently. 3. Make sure the device is truly isolated from power.
WARNING
Protection against mechanical influences In order to guarantee the degree of protection IP66, you must protect the module against mechanical influ-ences. This is achieved by selecting a suitable installation location or by installing a suitable protection de-vice. This required protection applies to the operation of the module with the following voltages: - > AC 16 V - > DC 35 V, low voltage
NOTICE
Maximal values for terminals 41/42 und 51/52 The following maximum values concern only terminals 41, 42, 51, and 52: - Maximum voltage: AC 250 V or DC 24 V - Maximum current: AC/DC 4 A No safe separation between the terminals can be guaranteed.
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 27 von 52
f ault s ign al
C onta ct m od ule
l limit valu e A 1
l im it value A 2
313 2
41
5 15 2
+
+
+ 1K 21
10K
D C 24V
< 35 V
4142
A C/DC 4 A
DC 2 4V
AC /DC 4 A
∼
∼
m ax. A C 250 V
m ax . A C 250 V
Figure 5-7 Contact module not for explosive Connecting the contact module (Figure 5-8)
1. Loosen the screw (18) on the transparent cover (19). 2. Pull the transparent cover (19) up to the front end stop. 3. Tighten every cable in the corresponding terminal. 4. Slide the transparent cover (19) up to the end stop of the motherboard. 5. Tighten the screw (18) on the transparent cover (19). 6. Connect the cables of each switch to the lug of the printed circuit board in pairs. Use the provided cable tie
(20) for this purpose.
Figure 5-8 Connection the cables
NOTICE
To observe before connecting − Only qualified personnel is permitted to install and connect the contact module. − Isolate all wires from power and make sure the device is truly isolated from power. − Construct the cross-sectional area of the connection cables in such a way that it is appropriate for the
permitted current load. − Selected the wires on the basis of the following rule: The temperature at which the wires are permitted to
be used must be 25°C above the maximum ambient temperature.
18 Screw 19 Cover 20 Cable tie
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 28 von 52
5.2 Connecting device with type of protection intrinsic safety 5.2.1 Basic device
+
J
4 … 20 mA Positioner
Binary input 1
6 7 8 9
10 +3 V
AE
Region of no explosive hazard
Intrinsically safe power source
EEx
Region of explosive hazard, Zone 1 or Zone 2
Figure 5-9 2- wire connection, for explosive regions, Type 827A.X2
+ 4 … 20 mA
Region of explosive hazard, Zone 1 or Zone 2
Intrinsically safe power source
J
Binary input 1
HART-Communicator
EEx
5 4 3
+3 V
6
7 8 9
10
A
2
E Positioner
Region of no explosive hazard
Figure 5-10 2- wire connection, for explosive regions Ex Type 827A.X4
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 29 von 52
+
4 … 20 mA
Region of explosive hazard, Zone 1 or Zone 2
2 3
Binary input 1
J
*) only for 3-wire connection
+
18 … 30 V
HART-Communicator
Intrinsically safe power sources
6
10 9 8 7
EA
EEx
+3 V
U 4 5
Region of no explosive hazard
*) *)
EEx
Positioner
Figure 5-11 3/4- wire connection, for explosive regions Ex Type 827A.X4 Split-Range
Figure 5-12 Series connection of two positioners, e.g. split range (auxiliary power supplied separately
Intri
nsic
ally
saf
e fe
ed s
ourc
es
L +
Iy
M
M
Posit ion ing range 2
Positio nin g rang e 1
+3V
+3V
BE 1
BE 1
8
10
9
5
7
6
8
4
10
9
3
2
7
6
5
4
3
2
I
EEx
U
EEx
Region of no hazard
Region of e xplosive hazard, Zo ne 1 or Zone 2
#
#
+ 0 /4 … 20 m A
+ 18 … 30 V Device 1
Device 2
E
A
E
A
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 30 von 52
5.2.2 Options Analog module
UH 62
61
J E
Ana log module
+
+
Region of explosive hazard, Zone 1 or Zone 2
Intrinsically safe power sources
J
EEx
U
+
≤ 30 V
Region of no explosive hazard
Figure 5-13 Analog module for explosive regions Binary module
BE2
Fault signal
Lim it value A1
Lim it value A2
Binary m odule
ntrinsically safe switching amplifier m eeting DIN EN 60947-5-6 (old DIN 19234)
Region of explosive hazard, Zone 1 or Zone 2 Region of no explosive hazard
+ 1112 ≥ 1
2122
+ 3132
4142
5152
EEx
EEx
EEx
EEx
+
+
+ 3 V
2K1
2K1
2K1
10K
10K
10K
≤ 25,2 V
8,2 V
8,2 V
8,2 V
Figure 5-14 Binary module for explosive regions
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 31 von 52
Slot initiator module
Intrinsically safeswitching amplifiermeetingDIN EN 60947-5-6(old DIN 19234)
Region of explosive hazard, Zone 1 or Zone 2Region of no explosive hazard
Fault signal
Slot initiator module
Limit value A1
Limit value A2
EEx
EEx
EEx
3132
4142
5152
+
+
+ 2K1
10K
2K1
10K
2K1
10K
8,2 V
8,2 V
8,2 V
Figure 5-15 Slot initiator module for explosive regions Contact module
Contact module connecting see Figure 5-8
NOTICE
Maximal values for terminals 41/42 und 51/52 The following maximum values concern only terminals 41, 42, 51, and 52: - Maximum voltage: DC 30 V - Maximum current: DC 100 mA - Maximum performance:750 mW
No safe separation between the terminals can be guaranteed.
NOTICE
To observe before connecting − Only qualified personnel is permitted to install and connect the contact module. − Isolate all wires from power and make sure the device is truly isolated from power. − Construct the cross-sectional area of the connection cables in such a way that it is appropriate for the
permitted current load. − Selected the wires on the basis of the following rule: The temperature at which the wires are permitted to
be used must be 25°C above the maximum ambient temperature. − Operate the Ex-version only in intrinsically safe circuits with approved switching amplifiers.
NOTICE
Preparing the cables or stranded wires - Version intrinsically safe 1. Insulate the cables in such a way that the insulation is flush with the terminal when plugging in the wires. 2. Fit ferrules to the ends of stranded wires.
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 32 von 52
Int rinsically safe switching am plifier meeting DIN EN 60947-5 -6 (old DIN 19234)
R egion o f explosive haza rd , Zone 1 o r Zone 2 Region of no explosive haza rd
Fault signa l
C ontact -m odu le
lim it value A1
lim it value A2
EEx
3132
41
5152
+
+
+ 1K21
10K
Umax DC 30V
DC 8,2V
4142
Imax 100 m A
Umax DC 30V
Imax 100 m A
Figure 5-16 Contact module for explosive regions 6 Pneumatic Connections
Procedure - If appropriate, connect manometer block for air supply and actuating pressure. - Connection via internal thread G 1/4 DIN 45141 PZ Air supply 1,4 to 7 bar Y1 Actuating pressure 1 for single-acting and double-acting actuators Y2 Actuating pressure 2 for double-acting actuators E Exhaust air output (remove silencer if necessary) - Safety position at failure of auxiliary electrical power: Single-acting: Y1 vented Double-acting: Y1 max. actuating pressure (supply pressure) Y2 vented - Connect actuating pressure Y1 or Y2 (only on double-acting actuators) according to the desired safety posi-
tion. - Connect air supply to PZ.
WARNING
For reasons of safety, the auxiliary pneumatic energy should only be connected after assembly when, in the presence of an electrical signal, the positioner is switched to the P-manual operating level (delivery status, see leaflet “Concise operating notes”).
NOTICE
Ensure correct air-quality! Oil-free, instrument quality air with no water or dust, solid material content max. 1 mg/m3 (standard atmospheric conditions), max. particle size 1 µm, oil content max. 0.1 mg/m3 (standard atmospheric conditions), pressurised dew point 20 K below the lowest ambient temperature. When working on the compressed air system ensure that any contamination present such as water, oil, swarf, soldering material residues etc. are expelled by blowing out
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 33 von 52
Note So that spring-loaded pneumatic actuators can reliably exploit the maximum possible travel, it is necessary that the supply pressure exceeds the maximum required final pressure of the actuator by a sufficient margin. After installing the pneumatic connections, check the tightness of the entire control valve. Besides continuous air consumption, the positioner may try to compensate the position deviation due to leakage. This will lead to premature wear in the entire control unit. 7 Commissioning
(see leaflet "Concise operating notes") Basic safety instructions
WARNING
Improper commissioning in hazardous areas Device failure or danger of explosion in hazardous areas − Do not commission the device until it has been mounted completely and connected. − Before commissioning take the effect on other devices in the system into account.
WARNING
Loss of explosion protection Danger of explosion in hazardous areas if the device is open or not properly closed. .
WARNING
Opening device in energized state Danger of explosion in areas subject to explosion hazard. − Only open the device in a de-energized state. − Check prior to commissioning that the cover, cover locks, and cable inlets are assembled in accordance
with the directives. Exception: Devices having the type of protection "Intrinsic safety Ex i" may also be opened in energized state in hazardous areas.
WARNING
Water in compressed air line Device damage and possibly loss of type of protection. The factory setting for the purging air selector is "IN". In the "IN" position, water from the compressed air line may enter the device from the pneumatics during initial commissioning. − Before commissioning, make sure that no water is present in the compressed air line. If you cannot be sure that there is no water in the compressed air line: − Set the purging air selector to "OUT". In this way, you prevent water from the compressed air line from
penetrating the device. − Only set the purging air selector to "IN" again when all water has been discharged from the compressed
air line.
NOTICE
Loss of degree of protection Damage to device if the enclosure is open or not properly closed. The degree of protection specified on the nameplate is no longer guaranteed. − Make sure that the device is securely closed.
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 34 von 52
Safety notes for operation with natural gas
For operation with natural gases actuator medium an electric connection acc to explosion protection „ia“ cate-gory 2G is needed. More information and safety notes see for manual 827A-GHB-natural gas General Information After installing the positioner on a pneumatic actuator, you must supply electric and pneumatic auxiliary power to it. The positioner is in the "P manual mode" before initialization. At the same time, "NOINI" blinks in the lower line of the digital display. Adjust the positioner as per the respective actuator with the help of the initialization process and by setting the parameters. If required, use the "PRST" parameter to cancel the adjustment of the positioner on the actuator. The positioner is again in the "P manual mode" after this process. Types of initialization
- Automatic initialization The initialization takes place automatically. In this case, the positioner determines, one after another, the
effective working direction, the travel distance or rotation angle and the actuator's adjustment times and adjusts the control parameters to match the dynamic behaviour of the actuator.
- Manual initialization The travel distance or rotation angle of the actuator can be set manually. The other parameters are
automatically determined, just as in the case of automatic initialization. This function is useful on actua-tors with soft end stops
- Copying Initialization Data (Positioner Exchange) In devices with HART functionality, the initialization data of one positioner can be read and copied into
another positioner. This allows a faulty device to be exchanged, without having to interrupt a running process in order to carry out initialization.
You have to define a few parameters for the positioner before initialization. Owing to the preset values, you cannot adjust further parameters for initialization. You can use a suitably configured and activated binary input to protect the configured settings against acciden-tal adjustment.
WARNING
Commissioning and operation with pending error If an error message appears, correct operation in the process is no longer guaranteed. − Check the gravity of the error − Correct the error − If the device is faulty:
- Take the device out of operation. - Prevent renewed commissioning.
NOTICE
− During the initialization process, the operating pressure must be at least one bar more than that required to close or open the valve. However, the operating pressure should not be greater than the maximum permissible operating pressure for the actuator.
− The leverage ratio switch can be set only when the positioner is open. Therefore, check this setting before closing the enclosure.
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 35 von 52
7.1 Preparations for Linear Actuators
1. Assemble the positioner with the appropriate mounting kit The position of the leverage ratio switch in the positioner is particularly important here. Stroke lever Position leverage ratio switch 5 to 20 mm short 33° (i.e. down) 25 to 35 mm short 90° (i.e. up) 40 to 130 mm long 90° (i.e. up n)
2. Connect a suitable source of current or voltage 3. Connect the actuator and the positioner to the pneumatic lines, and activate the positioner's auxiliary
pneumatic power. 4. The positioner is now in the “P–manual" operating mode. The top line of the display now shows the current
potentiometer voltage (P) in percent, e.g.: “P37.5“, while "NOINI" flashes on the bottom line:
5. Check that the mechanics can move freely over the entire active range by moving the actuator with the
and buttons as far as the end positions. The value P5.0 may not be fallen below and P95.0 may not be exceeded. The difference of the two values must be greater than 25.0 You can move the actuator rapidly by pressing the button for the opposite direction as well while continuing to hold down the first direction button.
6. Now move the actuator so that the lever is horizontal. The display should show a value between P48.0 and P52.0. If this is not the case, make appropriate adjustments to the slip clutch. The closer you can get to the "P50.0" value, the more accurately the positioner can determine the travel.
7.1.1 Automatic Initialization of Linear Actuators When you can move the actuator correctly, leave it in a central position and start the automatic initialization: 1. Hold the button pressed for longer than 5 s. This will bring you to the configuration mode Display:
2. Switch to the second parameter by pressing the button briefly. Display: or
It is essential that this value matches the setting of the leverage ratio switch (33° or 90°))
3. Use the button to move on to the following display:
You only have to set this parameter if you want to have the total stroke determined displayed in mm at the end of the initialization phase. To do this, you select the value in the display at which you have set the driver pin on the scale at the lever.
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 36 von 52
4. Use the button to move on to the following display:
5. Start the initialization by pressing the button for longer than 5 s.
Display:
"RUN1" to "RUN5" appear in sequence in the lower display during the initialization process. Depending on the actuator, the initialization process can take up to 15 min and it is completed when the fol-lowing display appears:
The first line also contains the stroke that has been determined, in mm, if the lever length has been given with the 3.YWAY parameter. The following display appears after briefly pressing the button:
To leave the Configuration mode, press the button for longer than 5 s. The software status will be dis-played after about 5 s. When the button is released, the device will be in manual operation mode. You can interrupt an initialization that is in progress at any time by pressing the button. Your previous set-tings will be retained. The parameters will only be returned to the factory settings if you have carried out a "Preset". After successful initialization slipping clutch and leverage ratio switch can be adjusted if necessary (see chap-ter 4.1.2). 7.1.2 Manual Initialization of Linear Actuators With this function the positioner can be initialized without having to move the actuator hard against the end stops. The start and end positions of the travel are set manually. When you can move the actuator correctly, leave it in a central position and start the manual initialization. The other initialization steps (optimisation and control parameters) are carried out in the same way as under auto-matic initialization. 1. Hold the button pressed for longer than 5 s. This will bring you to the configuration mode
Display:
2. Switch to the second parameter by pressing the button briefly.
Display: or
It is essential that this value matches the setting of the leverage ratio switch (33° or 90°))
3. Use the button to move on to the following display:
You only have to set this parameter if you want to have the total stroke determined displayed in mm at the end of the initialization phase. To do this, you select the value in the display at which you have set the driver pin on the scale at the lever.
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 37 von 52
4. Press the button twice to move on to the following display:
5. Start the initialization by pressing the button for longer than 5 s.
Display:
6. After 5 s the display changes to:
(The potentiometer settings shown here and below are only illustrative examples.) Now use the and buttons to move the actuator to the position that you wish to define as the first of the two end positions. Then press the button. This will register the current position as end position 1, and will move on to the next step. If the message "RANGE" appears on the lower line, the selected end position is outside the permitted measurement range. There are a number of ways to correct this error: - adjust the slip clutch until "OK" appears, then press the button again, or - use the and buttons to move to a different end position, or - interrupt the initialization by pressing the button. You must then change to P-manual operation and
correct the travel and the displacement accession in accordance with chapter 7.1
7. When Step 6 has been successfully completed, the following display appears:
Now use the and buttons to move the actuator to the position that you wish to define as the second
end position. Then press the button. This will cause the current position to be registered as end position 2. If the message "RANGE" appears on the lower line, the selected end position is outside the permitted measurement range. There are a number of ways to correct this error: - adjust the slip clutch until "OK" appears, then press the operating mode switch again, or - use the and buttons to move to a different end position, or - interrupt the initialization by pressing the button. You must then change to P-manual operation and
correct the travel and the displacement accession in accordance with chapter 7.1 If the message "Set Middl" appears, the lever arm must be moved to a horizontal position with the aid of the
and buttons, and the button then pressed. This will set the reference point for the sine correction on linear actuators.
8. The rest of the initialization will now proceed automatically. "RUN1" to "RUN5" will appear in sequence on the lower line of the display. The following display appears when the initialization has been completed suc-cessfully:
The first line also contains the stroke that has been determined, in mm, if the lever length has been given with the 3.YWAY parameter. After briefly pressing the button the lower line will again show 5.INITM. You are then once more in the Configuration operating mode To leave the Configuration mode, press the button for longer than 5 s. The software status will be dis-played after about 5 s. When the button is released, the device will be in manual operation mode. After successful initialization slipping clutch and leverage ratio switch can be adjusted if necessary (see chapter 4.1.2).
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 38 von 52
7.2 Preparations for Quarter-turn Actuators In the positioner, place the leverage ratio switch in the 90° position (the usual adjustment angle for quarter-turn actuators). 1. Assemble the positioner with the appropriate mounting kit. 2. Connect a suitable source of current or voltage. 3. Connect the actuator and the positioner to the pneumatic lines, and activate the positioner's auxiliary
pneumatic power 4. The positioner is now in the “P-manual“ .The top line of the display now shows the current potentiometer
voltage (P) in percent, e. g.: “P37.5 “while “NOINI“ flashes on the bottom line
5. Check that the mechanics can move freely over the entire active range by moving the actuator with the
and buttons as far as the end positions. The value P5.0 may not be fallen below and P95.0 may not be exceeded. The difference of the two values must be greater than 25.0.
You can move the actuator rapidly by pressing the button for the opposite direction as well while continuing to hold down the first direction button. 7.2.1 Automatic Initialization of Quarter-turn Actuators When you can move the actuator correctly through its range, leave it in a central position and start the auto-matic initialization: 1. Hold the button pressed for longer than 5 s. This will bring you to the configuration mode.
Display:
2. Hold the button pressed for longer than 5 s. This will bring you to the configuration mode.
Display:
3. Switch to the second parameter by pressing the button briefly. This has automatically been set to 90°.
Display:
It is essential that this value matches the setting of the leverage ratio switch (33° or 90°)
4. Use the button to move on to the following display:
5. Start the initialization by pressing the button for longer than 5 s.
Display:
"RUN1" to "RUN5" appear in sequence in the lower display during the initialization process. Depending on the actuator, the initialization process can take up to 15 min and it is completed when the fol-lowing display appears:
The upper value gives the actuator's full turning angle (e.g. 93.5°). The following display appears after briefly pressing the button:
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 39 von 52
To leave the Configuration mode, press the button for longer than 5 s. The software status will be dis-played after about 5 s. When the button is released, the device will be in manual operation mode. You can interrupt an initialization that is in progress at any time by pressing the button. Your previous set-tings will be retained. The parameters will only be returned to the factory settings if you have carried out a "Preset". After successful initialization slipping clutch and leverage ratio switch can be adjusted if necessary (see chap-ter 4.1.2). 7.2.2 Manual Initialization of Quarter-turn Actuators With this function the positioner can be initialized without having to move the actuator hard against the end stops. The start and end positions of the travel are set manually When you can move the actuator correctly, leave it in a central position and start the manual initialization. The other initialization steps (optimisation and control parameters) are carried out in the same way as under auto-matic initialization. 1. Hold the button pressed for longer than 5 s. This will bring you to the configuration mode.
Display:
2. Use the button to set the YFCT parameter to "turn"
Display:
3. Switch to the second parameter by pressing the button briefly.
Display:
Ensure that the leverage ratio switch is in the 90° position.
4. Press the button twice to move on to the following display:
The following steps are identical to steps 5) to 8) in the initialization of linear actuators. Following successful initialization, the pivoting range that has been determined is shown on the upper display in degrees After briefly pressing the button the lower line will again show 5.INITM. You are then once more in the Con-figuration operating mode. To leave the Configuration mode, press the button for longer than 5 s. The software status will be displayed after about 5 s. When the button is released, the device will be in manual operation mode. After successful initialization slipping clutch and leverage ratio switch can be adjusted if necessary (see chap-ter 4.1.2). 7.3 Copying Initialization Data (Positioner Exchange) − Electropneumatic positioners can be replaced in a running system without interrupting the process. − By copying and transferring the device and initialization data, it is possible to commission a replacement
positioner without needing to initialize it. − An electropneumatic positioner uses the communication interface to transfer data. The following steps are required to exchange a positioner: 1. The device parameters and initialization data (determined at initialization time) of the device needing re-
placement are read in and saved using SIMATIC PDM or HART Communicator. This step is not required if the device has been parameterised with SIMATIC PDM and the data already stored.
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 40 von 52
2. Fix the actuator in its current position (mechanically or pneumatically). 3. Read and note the current position value from the display of the positioner that is being replaced. If the
electronics are faulty, find the current position by measurement at the actuator or valve 4. Dismount the positioner. Fit the lever arm of the positioner to the replacement device. Mount the replace-
ment device to the fittings. Put the leverage ratio switch in the same position as on the faulty device. Download the device data and initialization data from the SIMATIC PDM or the handheld device
5. If the actual value displayed does not accord with the value noted from the faulty positioner, set the correct value with the slip clutch.
6. The positioner is now ready for operation. The accuracy and the dynamic behaviour may not be as good as they would be following a proper initialization. In particular the position of the hard end stops and the associated servicing data may be inaccurate. An initiali-zation must therefore be carried out at the next opportunity.
8 Overview of Parameters 8.1 Parameters 1 to 5 Parameters 1 to 5 are the same for all versions of positioner. These parameters are used to adjust the posi-tioner to the actuator. Normally the parameter setup is sufficient to be able to operate the positioner on an ac-tuator. If you want to get to know the positioner in detail, gradually try out the effects of the remaining parameters by systematic testing. Parameter Function Parameter values
(bold = factory setting) Unit
Type of position actuator turn (quarter-turn actuator)
WAY (linear actuator) LWAY (linear actuator without sine correction)
ncSt (quarter-turn actuator with NCS) -ncSt (quarter-turn actuator with NCS, inverse direction
of action ncSL (linear actuator with NCS)
1.YFCT
ncSLL (linear actuator with NCS and lever)
Nominal angle of rotation of the feedback message ( - Parameter does not appear if 1.YFCT = “turn”, “LWAY” or “ncS_” has been selected. - Set the leverage ratio switch accordingly)
33°
2.YAGL
90°
°
Range of stroke (optional setting) - The parameter only appears for "WAY" and for "ncSLL". - When used the value must correspond with the set range of stroke on the actuator. Carriers must be scaled to the
actuator's stroke value, or if this is not scaled they then must be set to the next largest scaled value.
OFF 5 | 10 | 15 | 20 (short lever 33°) 25 | 30 | 35 (short lever 90°)
3.YWAY
40 | 50 | 60 | 70 | 90 | 110 | 130 (long lever 90°)
mm
4.INITA Initialization (automatic) NOINI | no / ###.# | Strt 5.INITM Initialization (manual) NOINI | no / ###.# | Strt
NOTICE
Deferred initialization Initialize the replacement positioner as soon as possible. The following properties can be ensured only after initializing: − Optimum adjustment of the positioner as per the mechanical and dynamic properties of the actuator. − Unrestricted accuracy and dynamic behaviour of the positioner − Deviation-free position of the hard end stops − Correctness of the maintenance data
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 41 von 52
8.2 Parameters 6 to 51 These parameters are used to configure the following additional functions of the positioner: − Target value preparation − Actual value preparation − Binary signal processing − Tight closing function − Boundary value detection 6.SCUR Current range of setpoint 0 ... 20 mA 0 MA 4 ... 20 mA 4 MA
Setpoint setup Rising riSE
7.SDIR
Falling FALL 8.SPRA Setpoint split range start 0.0 ... 100.0 % 9.SPRE Setpoint split range end 0.0 ... 100.0 % 10.TSUP Setpoint ramp OPEN Auto / 0 ... 400 s 11.TSDO Setpoint ramp CLOSED 0 ... 400 s 12.SFCT Setpoint function
Linear Lin 1 : 25 1 - 25 1 : 33 1 - 33
Equal percentage
1 : 50 1 - 50 25 : 1 n1 - 25 33 : 1 n1 - 33
Inverse equal percentage
50 : 1 n1 - 50 Freely adjustable FrEE 13.SL0 ... 33.SL20 Setpoint turning point (Interpolation points appear only upon selection of 12.SFCT = "FrEE") 13.SL0 at 0 % 14.SL1 .... 5 % ... 0.0 ... 100.0 % 32.SL19 95 % 33.SL20 100 % 34.DEBA Dead zone of closed-loop controller Auto / 0.1 ... 10.0 % 35.YA Start of the manipulated variable limit 0.0 ... 100.0 % 36.YE End of the manipulated variable limit 0.0 ... 100.0 %
Manipulated variable scaling Mechanical MPOS
37.YNRM
On flow FLOW
Manipulated variable direction of action for display and position feedback Rising riSE
38.YDIR
Falling FALL Manipulated variable tight closing
None no Top only uP Bottom only do
39.YCLS
Top and bottom uP do
40.YCDO Lower value for tight closing 0.0 ... 0.5 ... 100 % 41.YCUP Upper value for tight closing 0.0 ... 99.5 ... 100 %
Function of BE1 Normally open (Action on switch closed or
High-Level)
Normally closed (Action on switch open or Low-
Level)
None OFF Message only on -on Block configuration bloc1 Block configuration and manual bloc2 Move valve to position YE uP -uP Move valve to position YA doWn -doWn Block movement StoP -StoP
42.BIN1
Partial-Stroke-Test PST -PST 43.BIN2 Function of BE2 Normally open
(Action on switch closed or High-Level)
Normally closed (Action on switch open or Low-
Level)
None OFF Message only on -on Move valve to position YE uP -uP Move valve to position YA doWn -doWn Block movement StoP -StoP
Partial-Stroke-Test PST -PST
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 42 von 52
Parameter Function Parameter values
(bold = factory setting) Unit
Alarm function Normal (High level without fault)
Inverted (Low level without fault)
without OFF A1 = Min, A2 = Max A1 = Min, A2 = Min
44.AFCT
A1 = Max, A2 = Max 45.A1 Trigger threshold, alarm 1 0.0 ... 10.0 ... 100 % 46.A2 Trigger threshold, alarm 2 0.0 ... 90.0 ... 100 % 47. FCT Function for fault message output
(„+“ means: Logical OR combination) Normal
(High level without fault) Inverted
(Low level without fault)
Fault Fault + not automatic Fault + not automatic + BE 48. TIM Monitoring time for setting of fault message
"regulation deviation" Auto / 0 ... 100 s
49. LIM Response threshold for fault message "regula-tion deviation"
Auto / 0 ... 100 %
Preset (factory setting) results in "NOINI"! no Nothing activated no Strt Start of factory setting Strt
50.PRST
oCAY Display after pushing button for 5 s oCAY Activation of extended diagnostics Parameters A up to P appears only if parameter 51.XDIAG is activated with On1, On2 or On3. The contents of the parameters A up to P appears also only if the selected parameter is activated with On.
Off OFF Single-level message On1 Two-level message On2
51.XDIAG
Three-level message On3
8.3 Parameters A to P These parameters are used to set the extended diagnostic functions of the positioner. Note Parameters A to P and their sub-parameters are only displayed when the extended diagnostics has been acti-vated using parameter "XDIAG" with parameter value "On1", "On2" or "On3". A. PST Partial-Stroke-Test with the following parameters: A1.STPOS Starting position 0.0 ... 100.0 % A2.STTOL Starting tolerance 0.1 ... 2.0 ... 10.0 % A3.STEP Step height 0.1 ... 10.0 ... 100.0 % A4.STEPD Step direction uP / do / uP do A5.INTRV Test interval OFF / 1 ... 365 d A6.PSTIN Partial-Stroke-Test reference step time NOINI / (C)##.# / Fdini / rEAL s A7.FACT1 Factor 1 0.1 ... 1.5 ... 100.0 A8.FACT2 Factor 2 0.1 ... 3.0 ... 100.0 A9.FACT3 Factor 3 0.1 ... 5.0 ... 100.0 b. DEVI General control valve fault with the following parameters: b1.TIM Time constant Auto / 1 ... 400 s b2.LIMIT Limit 0.1 ... 1.0 ... 100.0 % b3.FACT1 Factor 1 0.1 ... 5.0 ... 100.0 b4.FACT2 Factor 2 0.1 ... 10.0 ... 100.0 b5.FACT3 Factor 3 0.1 ... 15.0 ... 100.0 C. LEAK Pneumatic leakage with the following parameters: C1.LIMIT Limit 0.1 ... 30.0 ... 100.0 % C2.FACT1 Factor 1 0.1 ... 1.0 ... 100.0 C3.FACT2 Factor 2 0.1 ... 1.5 ... 100.0 C4.FACT3 Factor 3 0.1 ... 2.0 ... 100.0
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 43 von 52
Parameter Function Parameter values
(bold = factory setting) Unit
d. STIC Friction (slip-stick effect) with the following parameters: d1.LIMIT Limit 0.1 ... 1.0 ... 100.0 % d2.FACT1 Factor 1 0.1 ... 2.0 ... 100.0 d3.FACT2 Factor 2 0.1 ... 5.0 ... 100.0 d4.FACT3 Factor 3 0.1 ... 10.0 ... 100.0 E. DEBA Dead zone monitoring with the following parameters: E1.LEVEL3 Threshold 0.1 ... 2.0 ... 10.0 % F. ZERO Zero point monitoring with the following parameters: F1.LEVEL1 Threshold 1 0.1 ... 1.0 ... 10.0 % F2.LEVEL2 Threshold 2 0.1 ... 2.0 ... 10.0 % F3.LEVEL3 Threshold 3 0.1 ... 4.0 ... 10.0 % G. OPEN Displacement of the upper stop with the following parameters: G1.LEVEL1 Threshold 1 0.1 ... 1.0 ... 10.0 % G2.LEVEL2 Threshold 2 0.1 ... 2.0 ... 10.0 % G3.LEVEL3 Threshold 3 0.1 ... 4.0 ... 10.0 % H. TMIN Monitoring of the lower limit temperature with the following parameters: H1.TUNIT Temperature unit °C °F °C/°F H2.LEVEL1 Threshold 1 -40 ... -25 ... 90 -40 ... 194 H3.LEVEL2 Threshold 2 -40 ... -30 ... 90 -40 ... 194
H4.LEVEL3 Threshold 3 -40 ... 90 -40 ... 194 J. TMAX Monitoring of the upper limit temperature with the following parameters: J1.TUNIT Temperature unit °C °F J2.LEVEL1 Threshold 1 -40 ... 75 ... 90 -40 ... 194
°C/°F
J3.LEVEL2 Threshold 2 -40 ... 80 ... 90 -40 ... 194 J4.LEVEL3 Threshold 3 -40 ... 90 -40 ... 194 L. STRK Monitoring the path integral with the following parameters: L1. LIMIT Limit for the number of changes of direction 1 ... 1E6 ... 1E8 L2.FACT1 Factor 1 0.1 ... 1.0 ... 40.0 L3.FACT2 Factor 2 0.1 ... 2.0 ... 40.0 L4.FACT3 Factor 3 0.1 ... 5.0... 40.0
O. DCHG Monitoring the changes in direction with the following parameters:: O1.LIMIT Limit for the number of changes of direction 1 ... 1E6 ... 1E8 O2.FACT1 Factor 1 0.1 ... 1.0 ... 40.0 O3.FACT2 Factor 2 0.1 ... 2.0 ... 40.0 O4.FACT3 Factor 3 0.1 ... 5.0... 40.0
P. PAVG Position mean value calculation with the following parameters: P1.TBASE Time base of the mean value generation 0.5h / 8h / 5d / 60d / 2.5y P2.STATE State of the position mean value calculation IdLE / rEF / ###.# / Strt P3.LEVEL1 Threshold 1 0.1 ... 2.0 ... 100.0 % P4.LEVEL2 Threshold 2 0.1 ... 5.0 ... 100.0 % P5.LEVEL3 Threshold 3 0.1 ... 10.0 ... 100.0 % 9 Fault removal Diagnostic guide
See Table In which operating mode does the fault appear? - Initialization 1 - Manual operation and automatic operation 2 3 4 5 In what environment and under what boundary conditions does the fault appear?
- Wet environment (e.g. severe rain or constant condensation) 2 - Vibrating (oscillating) fittings 2 5 - Impact or shock loading (e.g. “steam hammer” or breakaway flaps) 5 - Damp (wet) compressed air 2 - Dirty compressed air (contaminated with solid particles) 2 3 When does the fault appear? - Regularly (reproducible) 1 2 3 4 - Sporadically (not reproducible) 5 - Mostly after a certain length of time of operation 2 3 5
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 44 von 52
Table 1 Fault symptoms Possible cause(s) Remedial measures Positioner remains in “RUN 1“ mode.
- Initialization from end position started and
- Failure to wait for reaction time of max. 1 min.
- Mains pressure not connected or too low.
- Up to 1 min waiting time is required - Do not start initialization from end
position - Check mains pressure
Positioner remains in “RUN 2“ mode.
- Leverage ratio switch and Parame-ter 2 (YAGL) and also actual stroke are not in agreement.
- Stroke on lever incorrectly adjusted. - Piezo valve(s) are not switching
(see Table 2)
- Check settings: Leverage ratio switch (10 in fig.1) and parameter 2
- Check stroke on lever - see Table 2
Positioner remains in “RUN 3“ mode.
- Actuator travel time too long - Open restrictor completely and/or set PZ pressure to highest permis-sible value.
- If necessary use booster Positioner remains in “RUN 5“ mode, does not get to “FINISH“ (waiting time > 5 min)
- “Slack” (play) in the positioner – actuator – fitting
- Quarter-turn actuator: Check that grub screw on the coupling wheel is tight
- Linear actuator: Check that lever on the positioner shaft is tight
- Remove any other play between actuator and fitting.
Table 2 Fault symptoms Possible cause(s) Remedial measures - “CPU test“ flashes in the display
(approx. every 2 s) - Piezo valve(s) are not switching.
- Water in the valve block (caused by wet compressed air)
- Actuator will not move at all or only in one direction in both manual and automatic operating modes.
- Dampness in the valve block
- In its early stages the fault can be removed by subsequent operation with dry air (if necessary in the dryer at 50 to 70°C).
- Otherwise repair
- Screw between cover and valve block not screwed tight or cover jammed.
- Tighten screw, if necessary remove cause of jam.
- Dirt (chips, particles) in valve block - Repair or new unit
- Piezo valve(s) are not switching (also no soft “clicking” audible if
or - button depressed in manual operating mode).
- Deposits on contacts between elec-tronics board and valve block; these can occur as a result of abrasion from long-term loading caused by severe vibration..
- Clean all contact surfaces with spirit, if necessary bend valve block contact springs a little.
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 45 von 52
Table 3 Fault symptoms Possible cause(s) Remedial measures - Actuator does not move - Compressed air < 1.4 bar - Set incoming air pressure to > 1.4
bar. - Restrictor valve(s) closed (screw(s)
at the right-hand stop) - Open restrictor screw(s) by turning to
the left - Piezo valve(s) are not switching
(however soft “clicking” audible if or button depressed in manual operating mode).
- Dirt in the valve block - Repair or new unit
- Pneumatic leakage in the posi-tioner – actuator system. Begin leakage test in “RUN 3“ (initiali-zation)
- Remove source of leakage in actua-tor and/or feed
- In the case where actuator is intact and feed is fully sealed: Repair or new unit
- In steady-state automatic oper-ating mode (constant setpoint) and in manual operating mode one Piezo valve is constantly switching.
- Dirt in the valve block (see above) - Repair or new unit Table 4 Fault symptoms Possible cause(s) Remedial measures
- Static friction in the stuffing box of fitting or actuator too large.
- Reduce static friction or increase dead zone (parameter DEBA) until the oscillating movement stops
- Slack (play) in the positioner - actua-tor - fitting system
- Quarter-turn actuator: Check that grub screw on the coupling wheel is tight
- Linear actuator: Check that lever on the positioner shaft is tight
- Remove any other play between actuator and fitting.
- In steady-state automatic oper-ating mode (constant setpoint) and in manual operating mode both Piezo valves are constantly switching alternately; actuator oscillates about a mean value.
- Actuator too fast - Increase travel times by means of restrictor screws.
- If fast travel time is necessary, in-crease dead zone (parameter DEBA) until the oscillating movement stops.
- Supply pressure too low - Increase supply pressure - Positioner does not drive fitting up to the stop (with a 100% in-put signal)
- Load voltage of the supply controller or system output is too low
- Interpose load transformer - Select 3/4-wire operation
Table 5 Fault symptoms Possible cause(s) Remedial measures - Null point moves about sporadi-
cally (> 3 %) - As a result of impact or shock loading
accelerations occur that are so high that the slip clutch is displaced (e.g. by “steam hammer” in steam pipe-work)
- Remove causes of shock loading. - Re-initialise positioner, lock slip
clutch (see chapter 4.1.2)
- Electrical auxiliary power source inadequate (< 3,6 mA)
- Control electrical auxiliary power source
- With very high long-term loading caused by vibration (oscillations)::
- Equipment functionality com-pletely fails: also no indication in the display
- Screws on the electrical con-necting terminals can work loose.
- Electrical connecting terminals and/or electronic components can be shaken loose
- Tighten screws and secure with sealant
- Repair - As a preventative measure mount
positioner on rubber-metal mounts
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 46 von 52
10 Service and maintenance Basic safety instructions
WARNING
Impermissible repair of the device − Repair must be carried out by Siemens authorized personnel only.
WARNING
Impermissible accessories and spare parts Danger of explosion in areas subject to explosion hazard. − Only use original accessories or original spare parts. − Observe all relevant installation and safety instructions described in the instructions for the device or en-
closed with the accessory or spare part.
WARNING
Improper connection after maintenance Danger of explosion in areas subject to explosion hazard. − Connect the device correctly after maintenance. − Close the device after maintenance work.
CAUTION
Penetration of moisture into the device Device damage − Make sure when carrying out cleaning and maintenance work that no moisture penetrates the inside of
the device.
CAUTION
Releasing key lock Improper modification of parameters could influence process safety. − Make sure that only authorized personnel may cancel the key locking of devices for safety-related appli-
cations.
WARNING
Electrostatic charge Danger of explosion in hazardous areas if electrostatic charges develop e.g. when cleaning plastic enclo-sures with a drycloth. − Prevent electrostatic charging in hazardous areas.
WARNING
Enclosure open Danger of explosion in hazardous areas as a result of hot components and/or charged capacitors inside the device. Isolate the device from power, before open the device in a hazardous area. Exception Devices having the type of protection "Intrinsic safety Ex i" may also be opened in an energized state in hazardous areas.
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 47 von 52
The positioner requires almost no maintenance. Filters are fitted to the pneumatic connections to protect the positioner against large particles of dirt. Dirt present in the input air can collect on the filter and then adversely affect the operation of the positioner (increased travel time). In such a case, the filters can be cleaned as fol-lows: 1. Switch off the auxiliary pneumatic energy and disconnect the hose lines. 2. Carefully remove the metal filters from the holes and clean them (e.g. with compressed air). 3. Insert the filters 4. Connect the hose lines again and turn on the auxiliary pneumatic power. 11 Technical Data General data for the base device Degree of protection IP66 to EN60529 Climatic class in accordance with IEC 721 Storage 1K5 but -40 °C … + 80 °C 1)
Transport 2K4 but -40 °C … + 80 °C 1)
Operation without purging air 3K3 but -30 °C 3) … + 80 °C 2)
with purging air 3K4 but -30 °C 3) … + 80 °C 2)
Shock resistance 10 g to 100 Hz recommended continuous operating range of the entire fitting ≤ 30 m/s2
CE marking Applicable directives and standards see declaration of conformity
Fitting orientation Any, although in wet environments the pneumatic connections and exhaust opening must not face upwards
Connections electrical Screw terminals 2,5 AWG28-12 Cable feed through M 20x1.5 or
(cable feed through ½ –14 NPT on request) pneumatic Internal thread G 1/4 DIN 45141
(Internal thread 1/4 –18 NPT on request) 1) If commissioning at ≤ 0 °C it is important that the valves are flushed for long enough with a dry medium. 2 See the electrical data for devices protected against explosion hazard. 3) Reduced refresh rate in on the LCD display below -10 °C.
WARNING
Dust layers above 5 mm Danger of explosion in hazardous areas. Device may overheat due to dust build up. − Remove any dust layers in excess of 5 mm.
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 48 von 52
Pneumatic data for the base device
Auxiliary power (air supply) Medium Instrument quality air meeting DIN ISO 8573-1, class 2 Pressure 1,4 … 7 bar
Electrical data for the base device
Type 827A.E Type 827A.X Ignition protection type according to EN 50014 and EN 50020
- II2G Ex ia IIC T4/T6 Gb 1)
Ambient temperature - 30 … + 80 °C T4 - 30 … + 80 °C T6 - 30 … + 50 °C
1) Limited to T4 on type 827A.X∗-A∗∗-∗∗∗-∗ with analog module 2-wire connection without HART
Type 827A.E Type 827A.X
Current input IW 4 … 20 mA Current to maintain the auxiliary power
≥ 3,6 mA
Required load voltage UB typical
≥ 6,4 V (≈ 320 Ω) ≥ 7,8 V (≈ 390 Ω)
Static destruction limit ± 40 mA - Internal capacitance Ci - 22 nF Internal inductance Li - 0,12 mH For connection to circuits with the following peak values
- Ui = DC 30 V Ii = 100 mA Pi = 1 W
Binary input BE1 (electrically connected to the JW circuit)
Suitable for dry contact, max. contact load ≤ 5 µA at 3 V
2-wire connection with HART Type 827A.E Type 827A.X Current input JW 4 … 20 mA Current to maintain the auxiliary power
≥ 3,6 mA
Required load voltage UB typical
≥ 6,6 V (≈ 330 Ω) ≥ 8,4 V (≈ 420 Ω)
Static destruction limit ± 40 mA - Internal capacitance Ci - 7 nF Internal inductance Li - 0,24 mH For connection to circuits with the following peak values
- Ui = DC 30 V Ii = 100 mA Pi = 1 W
Binary input BE1 (electrically connected to the JW circuit)
Suitable for dry contact, max. contact load ≤ 5 µA at 3 V
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 49 von 52
3/4 wire connection with / without HART
Type 827A.E Type 827A.X
Auxiliary power UH DC … 35 V DC 18 … 30 V DC Current consumption IH IH [mA] = (UH [V] – 7,5 V) / 2,4 kΩ Static destruction limit ± 35 V - Internal capacitance Ci - 22 nF Internal inductance Li - 0,12 mH For connection to circuits with the following peak values
- Ui = DC 30 V Ii = 100 mA Pi = 1 W
Current input IW 0 …20 mA or 4 … 20 mA Required load voltage UB typical
≥ 0,2 V (≈ 10 Ω) ≥ 1,0 V (≈ 50 Ω)
Static destruction limit ± 40 mA - Internal capacitance Ci - 22 nF Internal inductance Li - 0,12 mH For connection to circuits with the following peak values
- Ui = DC 30 V Ii = 100 mA Pi = 1 W
Electrical isolation Between UH and JW Between UH and JW
(2 intrinsically safe circuits) Test voltage DC 840 V, 1 s Binary input BE1 (electrically connected to the JW circuit)
Suitable for dry contact, max. contact load ≤ 5 µA at 3 V
Electrical Data for the Options Ignition protection class As base device 1) Ambient temperature As base device 1) 1) If options with the same protection class as the base device are used. See also basic device electrical data. Analog module Type 827A.E Type 827A.X Nominal signal range IY 4 … 20 mA k short-circuit protected
dynamic range 3,6 … 20,5 mA
Auxiliary voltage UH DC 12 … 35 V DC 12 … 30 V External load RB RB [kΩ ] ≤ (UH [V] - 12 V) / JY [mA]
Conversion error ≤ 0,3 %
Temperature dependency ≤ 0,1 % / 10 K
Resolution ≤ 0,1 %
Residual ripple ≤ 1 %
Internal capacitance Ci - 11 nF Internal inductance Li - Negligible small For connection to circuits with the following peak values
-
Ui = DC 30 V Ii = 100 mA Pi = 1 W
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 50 von 52
Analog module (continuation) Type 827A.E Type 827A.X Electrical isolation To base device JY (tml. 61/62) and the base device
are individual, intrinsically safe elec-trical circuits
Test voltage DC 840 V, 1 s Binary module Type 827A.E Type 827A.X Binary outputs A1, A2, Signal status “High” (not responded) Conductive R = 1 kΩ
%1%3
−+ ≥ 2,1 mA 2)
Signal status “Low” (responded) 3)
Blocked IR < 60 µA ≤ 1,2 mA 2)
Internal capacitance Ci - 5,2 nF Internal inductance Li - Negligible small Auxiliary voltage UH ≤ DC 35 V - For connection to circuits with the following peak values
- Ui = DC 15,5 V Ii = 25 mA Pi = 64 mW
Binary input BE2 Terminal 21/22 (electrically con-nected to base device)
Suitable for dry contact, max. contact load ≤ 5 µA at 3 V
Terminal 11/12 (electrically iso-lated)
Signal status 0 ≤ DC 4,5 V or open Signal status 1 ≥ DC 13 V Input resistance ≥ 25 kΩ Static destruction limit ± 35 V - Internal capacitance Ci - Negligible small Internal inductance Li - Negligible small For connection to circuits with the following peak values
- Ui = DC 25,2 V
Electrical Isolation A1, A2, , BE2 (tml. 11/12) from one to another and to the base device
A1, A2, , BE2 (tml. 11/12) and the base device are individual, intrinsi-cally safe electrical circuits
Test voltage DC 840 V, 1 s 2) Switching thresholds when supplied in accordance with DIN EN 60947-5-6 (old DIN 19234): UH = 8.2 V; Ri = 1 kΩ. 3) Low is also the state adopted if the base device is damaged or has no auxiliary electrical power.
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 51 von 52
Slot initiator module Type 827A.E Type 827A.X Binary outputs A1, A2 Slot initiators Type SJ2-SN to EN 60947-5-6 (NAMUR) for connecting to switching am-
plifier, NC (normally closed) function
Connection to switching amplifier DIN EN 60947-5-6 (old DIN 19234)
Internal capacitance Ci - 41 nF Internal inductance Li - 100 µH For connection to circuits with the following peak values
UNenn = 8 V Ui = DC 15,5 V Ii = 25 mA Pi = 64 mW
Binary output Signal status “High” (not responded)
R = 1,1 kΏ ≥ 2,1 mA 1)
Signal status “Low” (responded) 2)
R = 10 kΏ ≤ 1,2 mA 1)
Internal capacitance Ci - 5,2 nF Internal inductance Li - Negligible small Auxiliary power UH ≤ DC 35 V - For connection to circuits with the following peak values
- Ui = DC 15,5 V Ii = 25 mA Pi = 64 mW
Electrical Isolation A1, A2, from one to another and to the base device
A1, A2, and the base device are individual, intrinsically safe electrical circuits
Test voltage DC 840 V, 1 s 1) Switching thresholds when supplied in accordance with DIN EN 60947-5-6 (old DIN 19234): UH = 8.2 V; Ri = 1 kΩ. 2) Low is also the state adopted if the base device is damaged or has no auxiliary electrical power. Contact module Type 827A.E Type 827A.X Binary outputs A1, A2 Limit transmitter mechanical dry contacts
max. switching voltage AC 250 V / DC 24 V- DC 30 V max. switching current 4 A - Internal capacitance Ci - Negligible small Internal inductance Li - Negligible small For connection to circuits with the following peak values
- Ui = DC 30 V Ii = 100 mA Pi = 750 mW
Binary output Signal status “High” (not responded)
R = 1,1 kΩ ≥ 2,1 mA 1)
Signal status “Low” (responded) 2)
R = 10 kΩ ≤ 1,2 mA 1)
Internal capacitance Ci - 5,2 nF Internal inductance Li - Negligible small Auxiliary voltage UH ≤ DC 35 V -
Reference no.: 827A-BA-03-12_gb ARCA-Regler GmbH D - 47918 Tönisvorst Page 52 von 52
Contact module (continuation) Type 827A.E Type 827A.X For connection to circuits with the following peak values
- Ui = DC 15,5 V Ii = 25 mA Pi = 64 mW
Electrical Isolation A1, A2, from one to another and to the base device
A1, A2, and the base device are individual, intrinsically safe electri-cal circuits
Test voltage DC 3150 V, 2 s 1) Switching thresholds when supplied in accordance with DIN EN 60947-5-6 (old DIN 19234): UH = 8.2 V; Ri = 1 kΩ. 2) Low is also the state adopted if the base device is damaged or has no auxiliary electrical power. The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights created by the granting of patents or registration of a design are reserved. Technical data subject to change without notice.
ARCA-REGLER GmbH D-47913 Tönisvorst Phone: +49-(0)2156/7709-0 Fax: +49-(0)2156/7709-50...55E-Mail [email protected]