EXISTING CLADDING PANEL THROUGH-WALL SILL FLASHING W/DRIP EDGE & END DAMS SET IN SEALANT; COLOR TO MATCH MTL PANEL FACE OF STL BEYOND (SHOWN DASHED) MIN 16 GA GALV STL ANGLE BY MTL PNL MFR, TYP FULL PERIMETER OF OPENING TWO-PIECE HEAD EXTRUSION CAP WITH GASKET, TYP POSITVELY SLOPE FIBER DUCTS AWAY FROM BUILDING SLIGHTLY TO SHED WATER AWAY FROM THE BUILDING FACE, TYP DUCT FLANGE,TYP TOP AND SIDES OF DUCT; ANCHOR TO TUBE STEEL OVERHEAD FIBER DUCT (SEE TELECOM) OVERHEAD FIBER (SEE TELECOM) FILL GAP BETWEN TUBE STEEL AND DUCT W/EXPANDING SPRAY FOAM INSULATION, TYP FULL PERIMETER OF DUCT SEALANT & BACKER ROD, TYP TUBE STEEL FRAMING FULL PERIMETER OF OPENING (SEE STRUCTURAL) EPDM PIPE SLEEVE; COORDINATE SIZES MEP/TELECOM DRAWINGS JOINT SEALANT, TYP BACKER ROD AND SEALANT BOTH INTERIOR AND EXTERIOR, FULL PERIMETER OF PENETRATION PENETRATING PIPE EXTERIOR CLADDING PANEL NOTE: PROVIDE SEALANT AS REQUIRED FOR WEATHER-TIGHT SYSTEM SEAL EXT. PANEL AND BRAKE METAL INFILL PER PANEL MANUFACTURERS RECOMMENDATIONS PIPE HANGER AND SUPPORT. REFER TO MECHANICAL SET SLEEVE & COMPRESSION RING IN SEALANT, TYP SEE PLANS FOR INTERIOR FURRING & FINISH WHERE APPLICABLE, TYP PROVIDE HORIZONTAL METAL STUDS TO MATCH GIRT DIMENSION AT PENETRATION, BOTH SIDES (TYP) RIVET, TYP METAL COMPRESSION RING, TYP SEAL ENTIRE PERIMETER OF PENETRATION W/EXPANDING SPRAY FOAM INSULATION, TYP WRAP PIPE W/INSULATION MIN 915mm IN TO THE SPACE UNLESS NOTED OTHERWISE BY MECHANICAL DRAWINGS, TYPICAL EXTERIOR CLADDING PANEL INTERIOR WALL FINISH (WHERE APPLICABLE - SEE PLANS) TUBE STEEL OR METAL STUD FRAMING, TYP SECTION ELEVATION (EXTERIOR) MANUFACTURER'S RECOMMENDED FASTENER, TYP TRIM FLANGE; SET IN SEALANT FULL PERIMETER OF FRAME. BASIS OF DESIGN IS 'ROXTEC GH FRAMES'. WWW.ROXTEC.COM EXPANDING SPRAY FOAM INSULATION, TYP FULL PERIMETER OF PENETRANT CAVITY O N N U M B E R O F P E N E T R A N T S SIZE AS REQUIRED BASED ON NUMBER OF PENETRANTS SIZE AS REQUIRED BASED BASIS OF DESIGN IS 'MULTI-DIAMETER' PENETRANT SEALS. WWW.ROXTEC.COM CONDUIT/SMALL PIPE/CABLE PENETRANT (SEE ELECTRICAL AND TELECOM DRAWINGS FOR SIZES/QUANTITIES) MANUFACTURER'S RECOMMENDED FASTENER, TYP TRIM FLANGE; SET IN SEALANT FULL PERIMETER OF FRAME. BASIS OF DESIGN IS 'ROXTEC GH FRAMES'. WWW.ROXTEC.COM BASIS OF DESIGN IS 'MULTI- DIAMETER' PENETRANT SEALS. WWW.ROXTEC.COM CONDUIT/CABLE PENETRANT, TYP (SEE ELECTRICAL AND TELECOM DRAWINGS) LINER FLASHING, FULL PERIMETER OF PENETRANT; SET IN SEALANT, TYP NOTE: THIS DETAIL APPLIES FOR SITUATIONS WHERE MULTIPLE SMALL CONDUITS, SMALL PIPES, AND/OR CABLES PENETRATE THE SIDE OF A BUILDING. FOR INDIVIDUAL PENETRATIONS, REFER TO ALTERNAE WALL PENETRATION DETAILS ON THIS SHEET. 'WEDGE BLOCK' (PRESSURES THE SEALANT BLOCKS TO SEAL THE PENETRANTS) 'STAY-PLATE' BETWEEN ROWS, TYP LARGE PENETRATION ROUGH OPENING W/MULTIPLE ROUND PENETRANTS, TYPICAL. BASIS- OF-DESIGN ROXTEC. COORDINATE WITH SPECIFIED PRODUCT. REFER TO TELECOM DRAWINGS, MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS. PROVIDE DOUBLE METAL FRAMING STUDS TYPICAL AT ALL LARGE PENETRATION ROUGH OPENINGS. COORDINATE WITH SPECIFIED PRODUCTS. LARGE PENETRANT (DUCT, TELECOM FIBER, LARGE PIPES, ETC) NOTE: 1. THIS DETAIL IS SHOWN TO DEMONSTRATE THE NEED FOR SUPPLEMENTAL METAL STUD FRAMING AT LOCATIONS WHERE MECHANICAL, PLUMBING, ELECTRICAL, AND/OR TELECOM ITEMS PENETRATE THE EXTERIOR WALL OF THE BUILDING & THERE IS NO TUBE STEEL. 2. CONTRACTOR SHALL COORDINATE PENETRATION ROUGH OPENINGS WITH STRUCTURAL STEEL CONTRACTOR, METAL FRAMING CONTRACTOR AND EXTERIOR METAL PANEL CONTRACTOR, TYPICAL. 3. CONTRACTOR SHALL COORDINATE BACKUP REQUIREMENTS WITH THE SELECTED METAL PANEL SUPPLIER. 4. INTERIOR FURRING AND SHEATHING IS NOT SHOWN FOR CLARITY. 5. FOR LOCATIONS W/ TUBE STEEL AROUND THE PERIMETER OF THE OPENING, NO SUPPLEMENTAL STUD FRAMING IS REQUIRED. STRUCTURAL STEEL, TYP (SEE STRU) CONC CURB OR STRUCTURAL STEEL (SEE STRUCTURAL) METAL ROOF DECK CONT METAL ROOF DECK CLOSURE. CONFORM TO DECK PROFILE. SET IN MASTIC AND SEAL AIR-TIGHT VAPOUR RETARDER RIGID ROOF INSULATION PROTECTION BOARD ROOFING MEMBRANE ROOFING SEALANT / HEAT WELD EXTEND ROOFING MEMBRANE AND VAPOUR RETARDER HIGH-DOMED GASKETED FASTENER MECHANICAL UNIT OR FAN SET UNIT IN MASTIC SEALANT TAPE PROVIDED BY CURB MANUFACTURER INSULATED PRE- MANUFACTURED CURB, FASTEN TO ROOF DECK SUPPORTING FRAMING, SEE STRUCT DWGS 600mm MIN MECH UNIT T/CURB - LEVEL EL. 300mm MIN ABOVE FINISHED ROOF HIGH-DOMED GASKETED SHEET METAL FASTENER COUNTER FLASHING, SET IN SEALANT TERMINATION BAR, FASTEN TO DUCT 150mm OC SEALANT INSULATED DUCT, SEE MECH DRAWINGS ROOFING MEMBRANE FLASHING FULLY ADHERED CONT SHEET VAPOR RETARDER AROUND ALL SIDES OF DUCT CURB. TAPE AND SEAL TO DUCT AND CURB. TAPE AND SEAL ALL EDGES AND SEAMS FILL VOIDS WITH CONT BATT INSULATION INTERIOR OF DUCT VAPOR RETARDER (SHOWN DASHED) PROTECTION BOARD, TYP METAL ROOF DECK STEEL FRAMING AT DUCT PENETRATION, REFER TO STRUCTURAL DRAWINGS ROOFING MEMBRANE CURB FLASHING. EXTEND OVER TOP OF CURB SINGLE-PLY ROOFING MEMBRANE ADHERE CONTINUOUS VAPOR RETARDER OVER CURB FLANGE. SEAL TO CURB AND ROOF VAPOR RETARDER ROOF CURB FLANGE, SET IN CONTINUOUS ROOFING SEALANT AND FASTENED RIGID ROOF INSULATION ROOFING MEMBRANE FLASHING FULLY ADHERED OVER BACKER ROD BACKER ROD EXPANSION JOINT 40mm PT WOOD NAILER PRE-MANUFACTURED INSULATED ROOF CURB W/ PT WOOD NAILER SEALANT 22 GA MTL FLASHING W/HEMMED EDGE, TYP; FINISH TO MATCH MTL PANELS FACE OF MTL PANEL RIVET CLOSED END OR CHERRY MAXIBOLT; PAINT EXPOSED HEAD TO MATCH MTL SIDING COLOR CONT BUTYL SEALANT BEAD IN BULGE COMPRESSION SEAL; FASTEN W/POP RIVET. EXPOSED HEAD TO MATCH MTL SIDING COLOR CONT TERMINATION BAR SEALANT 5" 115 mm MIN 3" 75 6" 140 ROOF MEMBRANE; TURN UP FACE OF METAL PANEL MIN 450mm AND FULLY ADHERE. AIR SEAL - CONTINUOUS 20 x 6mm PVC FOAM TAPE. INTERNAL FINISH TO ARCHITECTS DETAILS AND SPECIFICATION. VOID FILLED WITH 25mm THICK RIGID INSULATION BOARD. LOUVRE SYSTEM & SEALS BY LOUVRE SPECIALIST. POLYESTER POWDER COATED ALUMINIUM SOFFIT FLASHING. AIR SEAL - POLYESTER POWDER COATED ALUMINIUM SOFFIT FLASHING TO BE FULLY SEALED TO SUPPORT WITH VAPOUR SEAL TAPE. AIR SEAL - CONTINUOUS 20 x 6mm PVC FOAM TAPE. INTERNAL FINISH TO ARCHITECTS DETAILS AND SPECIFICATION. AIR SEAL - POLYESTER POWDER COATED ALUMINIUM SOFFIT FLASHING TO BE FULLY SEALED TO SUPPORT WITH VAPOUR SEAL TAPE. LOUVRE SYSTEM & SEALS BY LOUVRE SPECIALIST. HORIZONTAL SUPPORT TO STRUCTURAL ENGINEER'S DETAILS AND SPECIFICATION. MIN 60mm BEARING. POLYESTER POWDER COATED ALUMINIUM DRIP FLASHING. HORIZONTAL SUPPORT TO STRUCTURAL ENGINEER'S DETAILS AND SPECIFICATION. MIN 60mm BEARING. TOP OF PANEL TO BE TRIMMED TO SUIT. POLYESTER POWDER COATED ALUMINIUM CILL FLASHING. FLASHING TO BE FIXED AND SEALED TO PANEL WITH 9mmx3mm BUTYL RUBBER SEALANT. LOW PROFILE STAINLESS STEEL STITCHING SCREWS WITH 14mm DIAMETER NON-FERROUS EPDM BACKED WASHER FITTED AT 450mm CENTRES . KS1100AB LPCB CERTIFIED INSULATED WALL PANEL, HORIZONTALLY LAID. SELF-DRILLING, SELF-TAPPING LOW PROFILE STAINLESS STEEL PRIMARY FIXINGS WITH 16mm DIAMETER NON-FERROUS EPDM BACKED WASHER . AT 1000mm CENTRES. SELF-DRILLING, SELF-TAPPING LOW PROFILE STAINLESS STEEL PRIMARY FIXINGS WITH 16mm DIAMETER NON-FERROUS EPDM BACKED WASHER AT 1000mm CENTRES. KS1100 AB LPCB CERTIFIED INSULATED WALL PANEL , HORIZONTALLY LAID. BOTTOM OF PANEL TO BE TRIMMED TO SUIT. PANEL THICKNESS PANEL THICKNESS 60 30 60 Internal. External. Gap between panel ends to be filled using FR canister insulation and cut flush prior to butyl tape application. Self-drill, self-tapping fastener complete with convex washer. Minimum 3 No. per panel per support . Drill ends removed. Panel sealed along its full length using two runs of 12 x 6mm foam tape - Premier Sealants ref: SBV25 . Kingspan KS1 1 00 CS EcoSafe insulated wall panel horizontally laid. Continuous 6mm bead of FR silicone sealant Nullifire M703 or similar , in female joint on internal and externa face prior to panel installation. 4mm diameter butyl rubber sealant (site applied) . Top Hat Flashing (RWH1) . Top-hat support cleats at 500mm centres fixed using rivets . Flush 'Snap-in' insert with clip . Internal. External. Kingspan KS1 1 00AB EcoSafe insulated wall panel horizontally laid. Blind rivets. 4mm diameter butyl rubber sealant (site applied) . Top Hat Flashing (RWH1) . Flush 'Snap-in' insert with clip . Top Hat fixed to top hat support cleats using stitching screws complete with clip . Continuous 6mm bead of FR silicone sealant Nullifire M703 or similar , to male joint prior to panel installation . face 75mm 40mm Min. Steel bearing face 75mm Min. Steel bearing To be read in conjunction with specification NOTE - THIS IS A STANDARD KINGSPAN DETAIL: SYSTEM- Boundary Wall - Hz Wall Vt Joint Detail Hz SFS 001 Drawing Nº.: KCE 5035 _2 NOTE - THIS IS A STANDARD KINGSPAN DETAIL: SYSTEM- Boundary Wall - Hz Wall Vt Joint Detail Drawing Nº.: KCE 5035_1 INSULATED METAL WALL PANEL METAL TRIM FLASHING, TYP 150mm METAL FRAMING FILL CAVITY WITH SPRAY FOAM SEALANT. TYPICAL. INSULATION ON MECHANICAL DUCT (SEE MECHANICAL DRAWINGS) DUCT WRAP (SEE MECHANICAL DRAWINGS) CONTINUOUS VAPOR BARRIER; SEAL TO STRUCTURE SEE PLANS FOR INTERIOR FURRING AND FINISH (WHERE APPLICABLE), TYP STL TUBE FRAMING, TYP (SEE STRUCTURAL DRAWINGS) ( S E E M E C H F O R S I Z E ) MECHANICAL DUCT 10mm SEALANT JOINT WITH COMPRESSIBLE BACKER ROD (FULL PERIMETER, BOTH SIDES) NOTE: SLOPE EXTERIOR PORTION OF DUCT AWAY FROM BLDG FACE SLIGHTLY TO SHED WATER ALUMINUM THERMAL SILL RECEPTOR BY WINDOW MANUFACTURER SEALANT AND BACKER ROD (FULL PERIMETER OF FRAME, BOTH SIDES) SEALANT AND BACKER ROD, TYP. GASKETED ALUMINUM SILL FLASHING WITH END DAMS PREFINISHED INSULATED METAL WALL PANEL TUBE STEEL BACKUP (SEE STRUCTURAL DRAWINGS) 13mm FRMT PLYWOOD INFILL BETWEEN STEEL TUBING W/ MTL STUDS @ 40mm O.C., TYP (WHERE APPLICABLE) 3" 75 MIN 40mm GA STL ANGLE, FULL PERIMETER OF OPENING (BY MTL PNL MFR), TYP SCHEDULED GLAZING TERMINATE GYP BD W/TEAR-AWAY BEAD SOLID SURFACE SILL; EASE EDGES W/ 3mm ROUND OVER 8" 200 4" 100 PREFINISHED INSULATED METAL WALL PANEL TWO-PIECE HEAD EXTRUSION CAP WITH GASKET FIELD DRILL 10mm DIA. WEEP HOLES IN EXTRUSION CAP SEALANT AND BACKER ROD, FULL PERIMETER OF FRAME (BOTH SIDES) DEFLECTION HEAD RECEPTOR ALUMINUM STOREFRONT WINDOW SYSTEM TUBE STEEL BACK-UP (SEE STRUCTURAL DRAWINGS) MOLD RESISTANT GYP. BOARD OR PLYWOOD (WHERE SCHEDULED; REFER TO FINISH SCHEDULE) SEALANT AND BACKER ROD, FULL PERIMETER OF FRAME 12mm FRMT PLYWOOD METAL STUD @ 400mm O.C. HEAD FLASHING W/END DAMS SCHEDULED CEILING 90 5" 115 8" 200 4" 100 PREFINISHED INSULATED METAL WALL PANEL SEALANT AND BACKER ROD, FULL PERIMETER OF FRAME BOTH SIDES ALUMINUM STOREFRONT WINDOW SYSTEM TUBE STEEL BACK-UP (SEE STRUCTURAL DRAWINGS) MOLD RESISTANT GYP BD OR FIRE-TREATED PLYWOOD (WHERE SCHEDULED; REFER TO FINISH SCHEDULE) SEALANT AND BACKER ROD METAL STUD INFILL @ 40mm O.C. WHERE GYP BD OR PLYWOOD IS SPECIFIED. SEE WALL SECTIONS FOR ADDTIONAL INFORMATION. TERMINATE GYP BD W/MTL J- BEAD FACE OF SILL BELOW MIN 40mm GA STL ANGLE BY MTL PNL MFR; FULL PERIMETER OF OPENING, TYP 4" 100 8" 200 TWO-PIECE EXTRUSION CAP WITH GASKET STEEL PROFILE REFER TO STRUCTURAL DRAWINGS EXISTING STRUCTURE NEW INSULATED WALL SITE APPLIED FIRE RATED INSULATION INTERNAL CLOSURE FLASHING WITH 100mm OVERALP SEALED WITH FILM BACKED BUTYL TAPE OR GUN GRADE SEALANT AIR SEAL 6mm BEAD OF GUN GRADE SEALANT OR COMPRESSIBLE FOAM TAPE AIR SEAL GUN GRADE SEAL TO MALE JOINT INLINE WITH INTERNAL AIR SEAL INSULATED CLADDING PANEL FINISH TO MATCH EXISTING POLYETHYLENE BACKING ROD AND SILICONE SEALANT AWP JOINT FILLER LOW PROFILE STICHING SCREWS WITH MIN. Ø14mm NON FERROUS EPDM BACKED WASHER FITTED MAX.@ 450mm c/c Ø4mm BUTYL RUBBER SEALANT EXTERNAL ENCLOUSRE FLASHING WITH 100mm SEALED BUTT STRAPS 4" 100 4" 100 NEW INSULATED WALL INSULATED CLADDING PANEL FINISH TO MATCH EXISTING AIR SEAL 6mm BEAD OF GUN GRADE AIR SEAL GUN GRADE TO MALE JOINT INLINE WITH INTERNAL SEAL STEEL PROFILE REFER TO STRUCTURAL DRAWINGS FOR DETAIL AIR SEAL CONTINOUS BEAD OF GUN GRADE SEALANT DRIP FLASHING WITH 100mm SEALED BUTT STRAPS EXISTING STRUCTURE SITE APPLIED PIR INSULATION BOARD ANY GAPS FILLED WITH FIRE RATED CANNISTER INSULATION EXISTING STRUCTURE NEW INSULATED WALL STEEL PROFILE REFER TO STRUCTURAL DRAWINGS FOR DETAIL SILICONE SEALANT DRIP FLASHING WITH 100mm SEALED BUTT STRAPS AIR SEAL GUN GRADE TO MALE JOINT INLINE WITH INTERNAL SEAL AIR SEAL 6mm BEAD OF GUN GRADE SEALANT SITE APPLIED PIR INSULATION BOARD ANY GAPS FILLED WITH FIRE RATED CANNISTER INSULATION INSULATED CLADDING PANEL FINISH TO MATCH EXISTING 4" 100 N ENGINEERING EXCELLENCE NOTE: EVERY SHEET NOTE MAY NOT APPEAR ON THIS PAGE KEY PLAN GENSLER 2017 All rights reserved, including but not limited to The Copyright, Design and Patents Act 1988 Do not scale from drawings. All discrepancies to be reported to Gensler architect immediately. All dimensions to be verified by contractor on site prior to any works C Thomas More Square London E1W 1YW England, UK Tel (0)20 7073 9600 Fax (0)20 7539 1917 WOOLVERSTONE HOUSE 61 BERNERS STREET LONDON W1T 3NJ Tel: 0207 0433410 Scale: DRAWN: REVIEW: PROJECT NO.: SHEET TITLE SEAL/SIGNATURE SHEET NO: ISSUES & REVISIONS 10400 Rodgers Road Houston, Texas 77070 Phone: 281-374-8644 Fax: 281-374-8992 RED ENGINEERING DESIGN LTD WOOLVERSTONE HOUSE 61 BERNERS STREET LONDON W1T 3NJ Tel: 0207 2998260 PERMIT ITEM NUMBER SUBJECT TO LOCAL ARCHITECT REVIEW FOR STATUTORY CODE COMPLIANCE As indicated @ A0 A9.051 Cessnalaan 32, 1119 NL Schiphol-Rijk, Netherlands 08.7142.101 Project Number: 08.7142.101 DETAILS - EXTERIOR SCALE: 1 : 5 TYP OVERHEAD FIBER DUCT ENTRANCE DETAIL 03 SCALE: 1 : 10 TYP WALL PENETRATION - SINGLE PIPE/CONDUIT 02 SCALE: 1 : 5 TYP EXT WALL CABLE PENETRATION DETAIL 07 SCALE: 1 : 20 WALL PENETRATION ELEVATION 01 SCALE: 1 : 5 TYPICAL MECHANICAL CURB DETAIL 10 SCALE: 1 : 5 TYP AHU DUCT ROOF PENETRATION DETAIL 11 SCALE: 1 : 2 TYP MTL COUNTER FLASHING DETAIL 06 Issue # Rev # Issue Date Issue Description 3 1 20.01.17 90% - ISSUE FOR REVIEW 4 2 17.02.17 TENDER ISSUE 7 3 xx.xx.xx REVISION xx SCALE: 1 : 5 KINGSPAN STANDARD LOUVRE DETAIL 15 SCALE: 1 : 5 TYP INSULATED DUCT WALL PENETRATION 04 SCALE: 1 : 5 TYP EXTERIOR WINDOW SILL DETAIL 13 SCALE: 1 : 5 TYP EXTERIOR WINDOW HEAD DETAIL 14 3 SCALE: 1 : 5 TYP EXTERIOR WINDOW JAMB DETAIL 12 3 SCALE: 1 : 5 WINDOW OPENING INFILL JAMB DETAIL 05 SCALE: 1 : 5 WINDOW OPENING INFILL SILL DETAIL 08 SCALE: 1 : 5 WINDOW OPENING INFILL HEAD DETAIL 09 3
Transcript

EXISTING CLADDING PANEL

THROUGH-WALL SILLFLASHING W/DRIP EDGE &END DAMS SET IN SEALANT;COLOR TO MATCH MTL PANEL

FACE OF STL BEYOND(SHOWN DASHED)

MIN 16 GA GALV STL ANGLE BYMTL PNL MFR, TYP FULLPERIMETER OF OPENING

TWO-PIECE HEAD EXTRUSIONCAP WITH GASKET, TYP

POSITVELY SLOPE FIBERDUCTS AWAY FROM BUILDINGSLIGHTLY TO SHED WATERAWAY FROM THE BUILDINGFACE, TYPDUCT FLANGE,TYP TOP ANDSIDES OF DUCT; ANCHOR TOTUBE STEEL

OVERHEAD FIBER DUCT (SEE TELECOM)

OVERHEAD FIBER (SEE TELECOM)

FILL GAP BETWEN TUBE STEELAND DUCT W/EXPANDINGSPRAY FOAM INSULATION, TYPFULL PERIMETER OF DUCT

SEALANT & BACKER ROD, TYP

TUBE STEEL FRAMING FULL PERIMETEROF OPENING (SEE STRUCTURAL)

EPDM PIPE SLEEVE; COORDINATESIZES MEP/TELECOM DRAWINGS

JOINT SEALANT, TYP

BACKER ROD AND SEALANT BOTH INTERIORAND EXTERIOR, FULL PERIMETER OFPENETRATION

PENETRATING PIPE

EXTERIOR CLADDINGPANEL

NOTE:PROVIDE SEALANT AS REQUIREDFOR WEATHER-TIGHT SYSTEM

SEAL EXT. PANEL AND BRAKE METALINFILL PER PANEL MANUFACTURERS

RECOMMENDATIONS

PIPE HANGER AND SUPPORT.REFER TO MECHANICAL

SET SLEEVE & COMPRESSIONRING IN SEALANT, TYP

SEE PLANS FOR INTERIOR FURRING &FINISH WHERE APPLICABLE, TYP

PROVIDE HORIZONTAL METALSTUDS TO MATCH GIRT DIMENSIONAT PENETRATION, BOTH SIDES(TYP)RIVET, TYP

METAL COMPRESSION RING,TYP

SEAL ENTIRE PERIMETER OFPENETRATION W/EXPANDING SPRAYFOAM INSULATION, TYP

WRAP PIPE W/INSULATION MIN 915mm IN TOTHE SPACE UNLESS NOTED OTHERWISE BYMECHANICAL DRAWINGS, TYPICAL

EXTERIOR CLADDING PANELINTERIOR WALL FINISH (WHERE

APPLICABLE - SEE PLANS)

TUBE STEEL OR METAL STUDFRAMING, TYP

SECTION

ELEVATION (EXTERIOR)

MANUFACTURER'SRECOMMENDED FASTENER,TYP

TRIM FLANGE; SET IN SEALANT FULLPERIMETER OF FRAME. BASIS OF DESIGN IS'ROXTEC GH FRAMES'. WWW.ROXTEC.COM

EXPANDING SPRAY FOAMINSULATION, TYP FULL

PERIMETER OF PENETRANTCAVITY

ON

NU

MB

ER

OF

PE

NE

TRA

NTS

SIZ

E A

S R

EQ

UIR

ED

BA

SE

D

ON NUMBER OF PENETRANTSSIZE AS REQUIRED BASED

BASIS OF DESIGN IS 'MULTI-DIAMETER'PENETRANT SEALS. WWW.ROXTEC.COM

CONDUIT/SMALL PIPE/CABLEPENETRANT (SEE ELECTRICAL ANDTELECOM DRAWINGS FORSIZES/QUANTITIES)

MANUFACTURER'SRECOMMENDED FASTENER,TYP

TRIM FLANGE; SET IN SEALANTFULL PERIMETER OF FRAME.BASIS OF DESIGN IS 'ROXTEC GHFRAMES'. WWW.ROXTEC.COM

BASIS OF DESIGN IS 'MULTI-DIAMETER' PENETRANT SEALS.WWW.ROXTEC.COM

CONDUIT/CABLE PENETRANT, TYP(SEE ELECTRICAL AND TELECOM

DRAWINGS)

LINER FLASHING, FULLPERIMETER OF PENETRANT;

SET IN SEALANT, TYP

NOTE: THIS DETAIL APPLIES FOR SITUATIONSWHERE MULTIPLE SMALL CONDUITS, SMALLPIPES, AND/OR CABLES PENETRATE THE SIDEOF A BUILDING. FOR INDIVIDUALPENETRATIONS, REFER TO ALTERNAE WALLPENETRATION DETAILS ON THIS SHEET.

'WEDGE BLOCK' (PRESSURESTHE SEALANT BLOCKS TOSEAL THE PENETRANTS)

'STAY-PLATE' BETWEEN ROWS, TYP

LARGE PENETRATION ROUGH OPENINGW/MULTIPLE ROUND PENETRANTS, TYPICAL. BASIS-OF-DESIGN ROXTEC. COORDINATE WITHSPECIFIED PRODUCT. REFER TO TELECOMDRAWINGS, MECHANICAL, PLUMBING, ANDELECTRICAL DRAWINGS.

PROVIDE DOUBLE METAL FRAMING STUDSTYPICAL AT ALL LARGE PENETRATION ROUGHOPENINGS. COORDINATE WITH SPECIFIEDPRODUCTS.

LARGE PENETRANT (DUCT, TELECOMFIBER, LARGE PIPES, ETC)NOTE:

1. THIS DETAIL IS SHOWN TO DEMONSTRATE THE NEED FOR SUPPLEMENTAL METAL STUD FRAMING AT LOCATIONSWHERE MECHANICAL, PLUMBING, ELECTRICAL, AND/OR TELECOM ITEMS PENETRATE THE EXTERIOR WALL OF THEBUILDING & THERE IS NO TUBE STEEL.

2. CONTRACTOR SHALL COORDINATE PENETRATION ROUGH OPENINGS WITH STRUCTURAL STEEL CONTRACTOR, METALFRAMING CONTRACTOR AND EXTERIOR METAL PANEL CONTRACTOR, TYPICAL.

3. CONTRACTOR SHALL COORDINATE BACKUP REQUIREMENTS WITH THE SELECTED METAL PANEL SUPPLIER.4. INTERIOR FURRING AND SHEATHING IS NOT SHOWN FOR CLARITY.5. FOR LOCATIONS W/ TUBE STEEL AROUND THE PERIMETER OF THE OPENING, NO SUPPLEMENTAL STUD FRAMING IS

REQUIRED.

STRUCTURAL STEEL, TYP (SEE STRU)

CONC CURB OR STRUCTURAL STEEL(SEE STRUCTURAL)

METAL ROOF DECK

CONT METAL ROOF DECK CLOSURE.CONFORM TO DECK PROFILE. SET INMASTIC AND SEAL AIR-TIGHT

VAPOUR RETARDER

RIGID ROOF INSULATION

PROTECTION BOARD

ROOFING MEMBRANE

ROOFING SEALANT / HEAT WELD

EXTEND ROOFING MEMBRANEAND VAPOUR RETARDER

HIGH-DOMED GASKETED FASTENER

MECHANICAL UNIT OR FANSET UNIT IN MASTICSEALANT TAPE PROVIDEDBY CURB MANUFACTURER

INSULATED PRE-MANUFACTURED CURB,FASTEN TO ROOF DECK

SUPPORTING FRAMING, SEESTRUCT DWGS

600m

m M

IN

MECH UNIT

T/CURB - LEVEL

EL. 300mm MIN ABOVEFINISHED ROOF

HIGH-DOMED GASKETED SHEETMETAL FASTENER

COUNTER FLASHING, SET INSEALANT

TERMINATION BAR, FASTEN TO DUCT 150mm OC

SEALANT

INSULATED DUCT,SEE MECHDRAWINGS

ROOFING MEMBRANEFLASHING FULLY ADHERED

CONT SHEET VAPOR RETARDERAROUND ALL SIDES OF DUCT CURB.TAPE AND SEAL TO DUCT AND CURB.TAPE AND SEAL ALL EDGES ANDSEAMS

FILL VOIDS WITH CONTBATT INSULATION

INTERIOROF DUCT

VAPOR RETARDER (SHOWN DASHED)

PROTECTION BOARD, TYP

METAL ROOF DECK

STEEL FRAMING AT DUCTPENETRATION, REFER TOSTRUCTURAL DRAWINGS

ROOFING MEMBRANE CURB FLASHING.EXTEND OVER TOP OF CURB

SINGLE-PLY ROOFING MEMBRANE

ADHERE CONTINUOUS VAPOR RETARDER OVERCURB FLANGE. SEAL TO CURB AND ROOF VAPOR

RETARDERROOF CURB FLANGE, SET IN CONTINUOUS

ROOFING SEALANT AND FASTENED

RIGID ROOF INSULATION

ROOFING MEMBRANE FLASHING FULLYADHERED OVER BACKER ROD

BACKER ROD EXPANSION JOINT40mm

PT WOOD NAILER

PRE-MANUFACTURED INSULATEDROOF CURB W/ PT WOOD NAILER

SEALANT

22 GA MTL FLASHINGW/HEMMED EDGE, TYP; FINISHTO MATCH MTL PANELS

FACE OF MTL PANEL

RIVET CLOSED END OR CHERRYMAXIBOLT; PAINT EXPOSED HEADTO MATCH MTL SIDING COLOR

CONT BUTYL SEALANT BEAD INBULGE

COMPRESSION SEAL; FASTENW/POP RIVET. EXPOSED HEADTO MATCH MTL SIDING COLOR

CONT TERMINATION BAR

SEALANT

5"

115

mm

MIN

3"75

6"140

ROOF MEMBRANE; TURNUP FACE OF METAL PANELMIN 450mm AND FULLYADHERE.

AIR SEAL - CONTINUOUS 20 x 6mmPVC FOAM TAPE.

INTERNAL FINISH TO ARCHITECTSDETAILS AND SPECIFICATION.

VOID FILLED WITH 25mm THICKRIGID INSULATION BOARD.

LOUVRE SYSTEM & SEALS BYLOUVRE SPECIALIST.

POLYESTER POWDER COATEDALUMINIUM SOFFIT FLASHING.

AIR SEAL - POLYESTER POWDERCOATED ALUMINIUM SOFFIT

FLASHING TO BE FULLY SEALED TOSUPPORT WITH VAPOUR SEAL TAPE.

AIR SEAL - CONTINUOUS 20 x 6mmPVC FOAM TAPE.

INTERNAL FINISH TO ARCHITECTSDETAILS AND SPECIFICATION.

AIR SEAL - POLYESTER POWDERCOATED ALUMINIUM SOFFIT FLASHING

TO BE FULLY SEALED TO SUPPORTWITH VAPOUR SEAL TAPE.

LOUVRE SYSTEM & SEALS BYLOUVRE SPECIALIST.

HORIZONTAL SUPPORT TO STRUCTURALENGINEER'S DETAILS AND SPECIFICATION.

MIN 60mm BEARING.POLYESTER POWDER COATEDALUMINIUM DRIP FLASHING.

HORIZONTAL SUPPORT TO STRUCTURALENGINEER'S DETAILS AND SPECIFICATION.

MIN 60mm BEARING.

TOP OF PANEL TO BE TRIMMED TO SUIT.

POLYESTER POWDER COATED ALUMINIUM CILLFLASHING. FLASHING TO BE FIXED AND SEALED TO PANELWITH 9mmx3mm BUTYL RUBBER SEALANT.

LOW PROFILE STAINLESS STEEL STITCHING SCREWS WITH

14mm DIAMETER NON-FERROUS EPDM BACKED WASHER

FITTED AT 450mm CENTRES .

KS1100AB LPCB CERTIFIED INSULATED

WALL PANEL, HORIZONTALLY LAID.

SELF-DRILLING, SELF-TAPPING LOW

PROFILE STAINLESS STEEL PRIMARY

FIXINGS WITH 16mm DIAMETER

NON-FERROUS EPDM BACKED WASHER .

AT 1000mm CENTRES.

SELF-DRILLING, SELF-TAPPING LOW PROFILE STAINLESSSTEEL PRIMARY FIXINGS WITH 16mm DIAMETERNON-FERROUS EPDM BACKED WASHER AT 1000mm CENTRES.

KS1100 AB LPCB CERTIFIED INSULATED

WALL PANEL , HORIZONTALLY LAID.

BOTTOM OF PANEL TO BE TRIMMED TO SUIT.

PANEL THICKNESS

PANEL THICKNESS

60 30 60

Internal.

External.

Gap between panel ends to be filled using FR canisterinsulation and cut flush prior to butyl tape application.Self-drill, self-tapping fastener complete with convex

washer. Minimum 3 No. per panel per support . Drill endsremoved.

Panel sealed along its full length using two runs of 12 x 6mm foam tape - Premier Sealants ref: SBV25 .

Kingspan KS1 100 CS EcoSafe insulated wall panel horizontally laid.

Continuous 6mm bead of FR silicone sealantNullifire M703 or similar , in female joint on internaland externa face prior to panel installation.

4mm diameter butyl rubber sealant (site applied) .

Top Hat Flashing (RWH1) . Top-hat support cleats at 500mmcentres fixed using rivets.Flush 'Snap-in' insert with clip.

Internal.

External.

Kingspan KS1 1 00AB EcoSafe insulated wall panel horizontally laid.

Blind rivets.

4mm diameter butyl rubber sealant (site applied) .Top Hat Flashing (RWH1).

Flush 'Snap-in' insert with clip.

Top Hat fixed to top hat support cleats usingstitching screws complete with clip .

Continuous 6mm bead of FR silicone sealantNullifire M703 or similar , to male joint prior to panelinstallation.

face 75mm

40mmMin. Steelbearing

face 75mm

Min. Steelbearing

To be read in conjunctionwith specification

NOTE - THIS IS A STANDARD KINGSPAN DETAIL: SYSTEM- Boundary Wall - Hz Wall Vt Joint Detail Hz SFS 001 Drawing Nº.: KCE 5035_2

NOTE - THIS IS A STANDARD KINGSPAN DETAIL: SYSTEM- Boundary Wall - Hz Wall Vt Joint Detail Drawing Nº.: KCE 5035_1

INSULATED METAL WALL PANEL

METAL TRIM FLASHING, TYP

150mm METAL FRAMING

FILL CAVITY WITH SPRAY FOAM

SEALANT. TYPICAL.

INSULATION ON MECHANICAL DUCT(SEE MECHANICAL DRAWINGS)

DUCT WRAP (SEEMECHANICAL DRAWINGS)

CONTINUOUS VAPOR BARRIER;SEAL TO STRUCTURE

SEE PLANS FOR INTERIORFURRING AND FINISH (WHEREAPPLICABLE), TYP

STL TUBE FRAMING, TYP (SEESTRUCTURAL DRAWINGS)

(SE

E M

EC

H F

OR

SIZ

E)

ME

CH

AN

ICA

L D

UC

T

10mm SEALANT JOINT WITHCOMPRESSIBLE BACKER ROD (FULLPERIMETER, BOTH SIDES)

NOTE: SLOPE EXTERIORPORTION OF DUCT AWAYFROM BLDG FACESLIGHTLY TO SHEDWATER

ALUMINUM THERMAL SILLRECEPTOR BY WINDOWMANUFACTURER

SEALANT AND BACKERROD (FULL PERIMETEROF FRAME, BOTHSIDES)

SEALANT AND BACKERROD, TYP.

GASKETED ALUMINUM SILLFLASHING WITH END DAMS

PREFINISHED INSULATEDMETAL WALL PANEL

TUBE STEEL BACKUP (SEESTRUCTURAL DRAWINGS)

13mm FRMT PLYWOOD

INFILL BETWEEN STEELTUBING W/ MTL STUDS @40mm O.C., TYP (WHERE

APPLICABLE)

3"

75

MIN 40mm GA STL ANGLE, FULLPERIMETER OF OPENING (BYMTL PNL MFR), TYP

SCHEDULED GLAZING

TERMINATE GYP BDW/TEAR-AWAY BEAD

SOLID SURFACE SILL;EASE EDGES W/ 3mm

ROUND OVER

8"

200

4"

100

PREFINISHED INSULATEDMETAL WALL PANEL

TWO-PIECE HEAD EXTRUSIONCAP WITH GASKET

FIELD DRILL 10mm DIA. WEEPHOLES IN EXTRUSION CAP

SEALANT AND BACKER ROD, FULLPERIMETER OF FRAME (BOTHSIDES)

DEFLECTION HEADRECEPTOR

ALUMINUM STOREFRONTWINDOW SYSTEM

TUBE STEEL BACK-UP (SEESTRUCTURAL DRAWINGS)

MOLD RESISTANT GYP. BOARDOR PLYWOOD (WHERE

SCHEDULED; REFER TO FINISHSCHEDULE)

SEALANT AND BACKER ROD,FULL PERIMETER OF FRAME

12mm FRMT PLYWOOD

METAL STUD @ 400mm O.C.

HEAD FLASHING W/END DAMS

SCHEDULED CEILING

90

5"

115

8"

200

4"

100

PREFINISHED INSULATEDMETAL WALL PANEL

SEALANT AND BACKERROD, FULL PERIMETEROF FRAME BOTH SIDES

ALUMINUM STOREFRONTWINDOW SYSTEM

TUBE STEEL BACK-UP (SEESTRUCTURAL DRAWINGS)

MOLD RESISTANT GYP BD ORFIRE-TREATED PLYWOOD

(WHERE SCHEDULED; REFER TOFINISH SCHEDULE)

SEALANT AND BACKER ROD

METAL STUD INFILL @ 40mmO.C. WHERE GYP BD OR

PLYWOOD IS SPECIFIED. SEEWALL SECTIONS FOR

ADDTIONAL INFORMATION.

TERMINATE GYP BD W/MTL J-BEAD

FACE OF SILL BELOW

MIN 40mm GA STL ANGLE BYMTL PNL MFR; FULL

PERIMETER OF OPENING,TYP

4"100

8"200

TWO-PIECEEXTRUSION CAP WITHGASKET

STEEL PROFILE REFER TO STRUCTURALDRAWINGS

EXISTING STRUCTURE

NEW INSULATED WALL

SITE APPLIED FIRE RATED INSULATION

INTERNAL CLOSURE FLASHING WITH 100mmOVERALP SEALED WITH FILM BACKED BUTYLTAPE OR GUN GRADE SEALANT

AIR SEAL 6mm BEAD OF GUN GRADE SEALANTOR COMPRESSIBLE FOAM TAPE

AIR SEAL GUN GRADE SEAL TO MALE JOINTINLINE WITH INTERNAL AIR SEAL

INSULATED CLADDING PANEL FINISH TOMATCH EXISTING

POLYETHYLENE BACKING RODAND SILICONE SEALANT

AWP JOINT FILLER

LOW PROFILE STICHING SCREWS WITHMIN. Ø14mm NON FERROUS EPDM BACKEDWASHER FITTED MAX.@ 450mm c/c

Ø4mm BUTYL RUBBER SEALANT

EXTERNAL ENCLOUSRE FLASHING WITH 100mmSEALED BUTT STRAPS

4"100

4"

100

NEW INSULATED WALL

INSULATED CLADDING PANEL FINISH TOMATCH EXISTING

AIR SEAL 6mm BEAD OF GUN GRADE

AIR SEAL GUN GRADE TO MALE JOINTINLINE WITH INTERNAL SEAL

STEEL PROFILE REFER TO STRUCTURALDRAWINGS FOR DETAIL

AIR SEAL CONTINOUS BEAD OF GUN GRADESEALANT

DRIP FLASHING WITH 100mm SEALED BUTTSTRAPS

EXISTING STRUCTURE

SITE APPLIED PIR INSULATION BOARDANY GAPS FILLED WITH FIRE RATEDCANNISTER INSULATION

EXISTING STRUCTURE

NEW INSULATED WALLSTEEL PROFILE REFER TO STRUCTURALDRAWINGS FOR DETAIL

SILICONE SEALANT

DRIP FLASHING WITH 100mm SEALED BUTTSTRAPSAIR SEAL GUN GRADE TO MALE JOINTINLINE WITH INTERNAL SEAL

AIR SEAL 6mm BEAD OF GUN GRADESEALANTSITE APPLIED PIR INSULATION BOARDANY GAPS FILLED WITH FIRE RATEDCANNISTER INSULATION

INSULATED CLADDING PANEL FINISH TOMATCH EXISTING

4"

100

N

ENGINEERING EXCELLENCE

NOTE: EVERY SHEET NOTE MAY NOT APPEAR ON THIS PAGE

KEY PLAN

GENSLER 2017All rights reserved, including but not limited to The Copyright, Design and Patents Act 1988Do not scale from drawings. All discrepancies to be reported to Gensler architect immediately.All dimensions to be verified by contractor on site prior to any works

C

Thomas More SquareLondon

E1W 1YW

England, UK

Tel (0)20 7073 9600

Fax (0)20 7539 1917

WOOLVERSTONE HOUSE61 BERNERS STREETLONDONW1T 3NJ

Tel: 0207 0433410

Scale:

DRAWN:REVIEW:PROJECT NO.:

SHEET TITLE

SEAL/SIGNATURE

SHEET NO:

ISSUES & REVISIONS

10400 Rodgers RoadHouston, Texas 77070

Phone: 281-374-8644Fax: 281-374-8992

RED ENGINEERING DESIGN LTDWOOLVERSTONE HOUSE61 BERNERS STREETLONDONW1T 3NJ

Tel: 0207 2998260

PERMIT ITEM NUMBER

SUBJECT TO LOCALARCHITECT REVIEW FOR

STATUTORY CODECOMPLIANCE

As indicated @ A0

A9.051

Ces

snal

aan

32,

111

9 N

L S

chip

ho

l-R

ijk, N

eth

erla

nd

s

08.7142.101

Pro

ject

Nu

mb

er:

08.7

142.

101

DETAILS - EXTERIOR

SCALE: 1 : 5

TYP OVERHEAD FIBER DUCT ENTRANCE DETAIL03

SCALE: 1 : 10

TYP WALL PENETRATION - SINGLE PIPE/CONDUIT02

SCALE: 1 : 5

TYP EXT WALL CABLE PENETRATION DETAIL07

SCALE: 1 : 20

WALL PENETRATION ELEVATION01

SCALE: 1 : 5

TYPICAL MECHANICAL CURB DETAIL10

SCALE: 1 : 5

TYP AHU DUCT ROOF PENETRATION DETAIL11

SCALE: 1 : 2

TYP MTL COUNTER FLASHING DETAIL06

Issue # Rev # Issue Date Issue Description

3 1 20.01.17 90% - ISSUE FOR REVIEW

4 2 17.02.17 TENDER ISSUE

7 3 xx.xx.xx REVISION xx

SCALE: 1 : 5

KINGSPAN STANDARD LOUVRE DETAIL15

SCALE: 1 : 5

TYP INSULATED DUCT WALL PENETRATION04

SCALE: 1 : 5

TYP EXTERIOR WINDOW SILL DETAIL13

SCALE: 1 : 5

TYP EXTERIOR WINDOW HEAD DETAIL14

3

SCALE: 1 : 5

TYP EXTERIOR WINDOW JAMB DETAIL12

3

SCALE: 1 : 5

WINDOW OPENING INFILL JAMB DETAIL05SCALE: 1 : 5

WINDOW OPENING INFILL SILL DETAIL08

SCALE: 1 : 5

WINDOW OPENING INFILL HEAD DETAIL09

3