EXISTING CLADDING PANEL
THROUGH-WALL SILLFLASHING W/DRIP EDGE &END DAMS SET IN SEALANT;COLOR TO MATCH MTL PANEL
FACE OF STL BEYOND(SHOWN DASHED)
MIN 16 GA GALV STL ANGLE BYMTL PNL MFR, TYP FULLPERIMETER OF OPENING
TWO-PIECE HEAD EXTRUSIONCAP WITH GASKET, TYP
POSITVELY SLOPE FIBERDUCTS AWAY FROM BUILDINGSLIGHTLY TO SHED WATERAWAY FROM THE BUILDINGFACE, TYPDUCT FLANGE,TYP TOP ANDSIDES OF DUCT; ANCHOR TOTUBE STEEL
OVERHEAD FIBER DUCT (SEE TELECOM)
OVERHEAD FIBER (SEE TELECOM)
FILL GAP BETWEN TUBE STEELAND DUCT W/EXPANDINGSPRAY FOAM INSULATION, TYPFULL PERIMETER OF DUCT
SEALANT & BACKER ROD, TYP
TUBE STEEL FRAMING FULL PERIMETEROF OPENING (SEE STRUCTURAL)
EPDM PIPE SLEEVE; COORDINATESIZES MEP/TELECOM DRAWINGS
JOINT SEALANT, TYP
BACKER ROD AND SEALANT BOTH INTERIORAND EXTERIOR, FULL PERIMETER OFPENETRATION
PENETRATING PIPE
EXTERIOR CLADDINGPANEL
NOTE:PROVIDE SEALANT AS REQUIREDFOR WEATHER-TIGHT SYSTEM
SEAL EXT. PANEL AND BRAKE METALINFILL PER PANEL MANUFACTURERS
RECOMMENDATIONS
PIPE HANGER AND SUPPORT.REFER TO MECHANICAL
SET SLEEVE & COMPRESSIONRING IN SEALANT, TYP
SEE PLANS FOR INTERIOR FURRING &FINISH WHERE APPLICABLE, TYP
PROVIDE HORIZONTAL METALSTUDS TO MATCH GIRT DIMENSIONAT PENETRATION, BOTH SIDES(TYP)RIVET, TYP
METAL COMPRESSION RING,TYP
SEAL ENTIRE PERIMETER OFPENETRATION W/EXPANDING SPRAYFOAM INSULATION, TYP
WRAP PIPE W/INSULATION MIN 915mm IN TOTHE SPACE UNLESS NOTED OTHERWISE BYMECHANICAL DRAWINGS, TYPICAL
EXTERIOR CLADDING PANELINTERIOR WALL FINISH (WHERE
APPLICABLE - SEE PLANS)
TUBE STEEL OR METAL STUDFRAMING, TYP
SECTION
ELEVATION (EXTERIOR)
MANUFACTURER'SRECOMMENDED FASTENER,TYP
TRIM FLANGE; SET IN SEALANT FULLPERIMETER OF FRAME. BASIS OF DESIGN IS'ROXTEC GH FRAMES'. WWW.ROXTEC.COM
EXPANDING SPRAY FOAMINSULATION, TYP FULL
PERIMETER OF PENETRANTCAVITY
ON
NU
MB
ER
OF
PE
NE
TRA
NTS
SIZ
E A
S R
EQ
UIR
ED
BA
SE
D
ON NUMBER OF PENETRANTSSIZE AS REQUIRED BASED
BASIS OF DESIGN IS 'MULTI-DIAMETER'PENETRANT SEALS. WWW.ROXTEC.COM
CONDUIT/SMALL PIPE/CABLEPENETRANT (SEE ELECTRICAL ANDTELECOM DRAWINGS FORSIZES/QUANTITIES)
MANUFACTURER'SRECOMMENDED FASTENER,TYP
TRIM FLANGE; SET IN SEALANTFULL PERIMETER OF FRAME.BASIS OF DESIGN IS 'ROXTEC GHFRAMES'. WWW.ROXTEC.COM
BASIS OF DESIGN IS 'MULTI-DIAMETER' PENETRANT SEALS.WWW.ROXTEC.COM
CONDUIT/CABLE PENETRANT, TYP(SEE ELECTRICAL AND TELECOM
DRAWINGS)
LINER FLASHING, FULLPERIMETER OF PENETRANT;
SET IN SEALANT, TYP
NOTE: THIS DETAIL APPLIES FOR SITUATIONSWHERE MULTIPLE SMALL CONDUITS, SMALLPIPES, AND/OR CABLES PENETRATE THE SIDEOF A BUILDING. FOR INDIVIDUALPENETRATIONS, REFER TO ALTERNAE WALLPENETRATION DETAILS ON THIS SHEET.
'WEDGE BLOCK' (PRESSURESTHE SEALANT BLOCKS TOSEAL THE PENETRANTS)
'STAY-PLATE' BETWEEN ROWS, TYP
LARGE PENETRATION ROUGH OPENINGW/MULTIPLE ROUND PENETRANTS, TYPICAL. BASIS-OF-DESIGN ROXTEC. COORDINATE WITHSPECIFIED PRODUCT. REFER TO TELECOMDRAWINGS, MECHANICAL, PLUMBING, ANDELECTRICAL DRAWINGS.
PROVIDE DOUBLE METAL FRAMING STUDSTYPICAL AT ALL LARGE PENETRATION ROUGHOPENINGS. COORDINATE WITH SPECIFIEDPRODUCTS.
LARGE PENETRANT (DUCT, TELECOMFIBER, LARGE PIPES, ETC)NOTE:
1. THIS DETAIL IS SHOWN TO DEMONSTRATE THE NEED FOR SUPPLEMENTAL METAL STUD FRAMING AT LOCATIONSWHERE MECHANICAL, PLUMBING, ELECTRICAL, AND/OR TELECOM ITEMS PENETRATE THE EXTERIOR WALL OF THEBUILDING & THERE IS NO TUBE STEEL.
2. CONTRACTOR SHALL COORDINATE PENETRATION ROUGH OPENINGS WITH STRUCTURAL STEEL CONTRACTOR, METALFRAMING CONTRACTOR AND EXTERIOR METAL PANEL CONTRACTOR, TYPICAL.
3. CONTRACTOR SHALL COORDINATE BACKUP REQUIREMENTS WITH THE SELECTED METAL PANEL SUPPLIER.4. INTERIOR FURRING AND SHEATHING IS NOT SHOWN FOR CLARITY.5. FOR LOCATIONS W/ TUBE STEEL AROUND THE PERIMETER OF THE OPENING, NO SUPPLEMENTAL STUD FRAMING IS
REQUIRED.
STRUCTURAL STEEL, TYP (SEE STRU)
CONC CURB OR STRUCTURAL STEEL(SEE STRUCTURAL)
METAL ROOF DECK
CONT METAL ROOF DECK CLOSURE.CONFORM TO DECK PROFILE. SET INMASTIC AND SEAL AIR-TIGHT
VAPOUR RETARDER
RIGID ROOF INSULATION
PROTECTION BOARD
ROOFING MEMBRANE
ROOFING SEALANT / HEAT WELD
EXTEND ROOFING MEMBRANEAND VAPOUR RETARDER
HIGH-DOMED GASKETED FASTENER
MECHANICAL UNIT OR FANSET UNIT IN MASTICSEALANT TAPE PROVIDEDBY CURB MANUFACTURER
INSULATED PRE-MANUFACTURED CURB,FASTEN TO ROOF DECK
SUPPORTING FRAMING, SEESTRUCT DWGS
600m
m M
IN
MECH UNIT
T/CURB - LEVEL
EL. 300mm MIN ABOVEFINISHED ROOF
HIGH-DOMED GASKETED SHEETMETAL FASTENER
COUNTER FLASHING, SET INSEALANT
TERMINATION BAR, FASTEN TO DUCT 150mm OC
SEALANT
INSULATED DUCT,SEE MECHDRAWINGS
ROOFING MEMBRANEFLASHING FULLY ADHERED
CONT SHEET VAPOR RETARDERAROUND ALL SIDES OF DUCT CURB.TAPE AND SEAL TO DUCT AND CURB.TAPE AND SEAL ALL EDGES ANDSEAMS
FILL VOIDS WITH CONTBATT INSULATION
INTERIOROF DUCT
VAPOR RETARDER (SHOWN DASHED)
PROTECTION BOARD, TYP
METAL ROOF DECK
STEEL FRAMING AT DUCTPENETRATION, REFER TOSTRUCTURAL DRAWINGS
ROOFING MEMBRANE CURB FLASHING.EXTEND OVER TOP OF CURB
SINGLE-PLY ROOFING MEMBRANE
ADHERE CONTINUOUS VAPOR RETARDER OVERCURB FLANGE. SEAL TO CURB AND ROOF VAPOR
RETARDERROOF CURB FLANGE, SET IN CONTINUOUS
ROOFING SEALANT AND FASTENED
RIGID ROOF INSULATION
ROOFING MEMBRANE FLASHING FULLYADHERED OVER BACKER ROD
BACKER ROD EXPANSION JOINT40mm
PT WOOD NAILER
PRE-MANUFACTURED INSULATEDROOF CURB W/ PT WOOD NAILER
SEALANT
22 GA MTL FLASHINGW/HEMMED EDGE, TYP; FINISHTO MATCH MTL PANELS
FACE OF MTL PANEL
RIVET CLOSED END OR CHERRYMAXIBOLT; PAINT EXPOSED HEADTO MATCH MTL SIDING COLOR
CONT BUTYL SEALANT BEAD INBULGE
COMPRESSION SEAL; FASTENW/POP RIVET. EXPOSED HEADTO MATCH MTL SIDING COLOR
CONT TERMINATION BAR
SEALANT
5"
115
mm
MIN
3"75
6"140
ROOF MEMBRANE; TURNUP FACE OF METAL PANELMIN 450mm AND FULLYADHERE.
AIR SEAL - CONTINUOUS 20 x 6mmPVC FOAM TAPE.
INTERNAL FINISH TO ARCHITECTSDETAILS AND SPECIFICATION.
VOID FILLED WITH 25mm THICKRIGID INSULATION BOARD.
LOUVRE SYSTEM & SEALS BYLOUVRE SPECIALIST.
POLYESTER POWDER COATEDALUMINIUM SOFFIT FLASHING.
AIR SEAL - POLYESTER POWDERCOATED ALUMINIUM SOFFIT
FLASHING TO BE FULLY SEALED TOSUPPORT WITH VAPOUR SEAL TAPE.
AIR SEAL - CONTINUOUS 20 x 6mmPVC FOAM TAPE.
INTERNAL FINISH TO ARCHITECTSDETAILS AND SPECIFICATION.
AIR SEAL - POLYESTER POWDERCOATED ALUMINIUM SOFFIT FLASHING
TO BE FULLY SEALED TO SUPPORTWITH VAPOUR SEAL TAPE.
LOUVRE SYSTEM & SEALS BYLOUVRE SPECIALIST.
HORIZONTAL SUPPORT TO STRUCTURALENGINEER'S DETAILS AND SPECIFICATION.
MIN 60mm BEARING.POLYESTER POWDER COATEDALUMINIUM DRIP FLASHING.
HORIZONTAL SUPPORT TO STRUCTURALENGINEER'S DETAILS AND SPECIFICATION.
MIN 60mm BEARING.
TOP OF PANEL TO BE TRIMMED TO SUIT.
POLYESTER POWDER COATED ALUMINIUM CILLFLASHING. FLASHING TO BE FIXED AND SEALED TO PANELWITH 9mmx3mm BUTYL RUBBER SEALANT.
LOW PROFILE STAINLESS STEEL STITCHING SCREWS WITH
14mm DIAMETER NON-FERROUS EPDM BACKED WASHER
FITTED AT 450mm CENTRES .
KS1100AB LPCB CERTIFIED INSULATED
WALL PANEL, HORIZONTALLY LAID.
SELF-DRILLING, SELF-TAPPING LOW
PROFILE STAINLESS STEEL PRIMARY
FIXINGS WITH 16mm DIAMETER
NON-FERROUS EPDM BACKED WASHER .
AT 1000mm CENTRES.
SELF-DRILLING, SELF-TAPPING LOW PROFILE STAINLESSSTEEL PRIMARY FIXINGS WITH 16mm DIAMETERNON-FERROUS EPDM BACKED WASHER AT 1000mm CENTRES.
KS1100 AB LPCB CERTIFIED INSULATED
WALL PANEL , HORIZONTALLY LAID.
BOTTOM OF PANEL TO BE TRIMMED TO SUIT.
PANEL THICKNESS
PANEL THICKNESS
60 30 60
Internal.
External.
Gap between panel ends to be filled using FR canisterinsulation and cut flush prior to butyl tape application.Self-drill, self-tapping fastener complete with convex
washer. Minimum 3 No. per panel per support . Drill endsremoved.
Panel sealed along its full length using two runs of 12 x 6mm foam tape - Premier Sealants ref: SBV25 .
Kingspan KS1 100 CS EcoSafe insulated wall panel horizontally laid.
Continuous 6mm bead of FR silicone sealantNullifire M703 or similar , in female joint on internaland externa face prior to panel installation.
4mm diameter butyl rubber sealant (site applied) .
Top Hat Flashing (RWH1) . Top-hat support cleats at 500mmcentres fixed using rivets.Flush 'Snap-in' insert with clip.
Internal.
External.
Kingspan KS1 1 00AB EcoSafe insulated wall panel horizontally laid.
Blind rivets.
4mm diameter butyl rubber sealant (site applied) .Top Hat Flashing (RWH1).
Flush 'Snap-in' insert with clip.
Top Hat fixed to top hat support cleats usingstitching screws complete with clip .
Continuous 6mm bead of FR silicone sealantNullifire M703 or similar , to male joint prior to panelinstallation.
face 75mm
40mmMin. Steelbearing
face 75mm
Min. Steelbearing
To be read in conjunctionwith specification
NOTE - THIS IS A STANDARD KINGSPAN DETAIL: SYSTEM- Boundary Wall - Hz Wall Vt Joint Detail Hz SFS 001 Drawing Nº.: KCE 5035_2
NOTE - THIS IS A STANDARD KINGSPAN DETAIL: SYSTEM- Boundary Wall - Hz Wall Vt Joint Detail Drawing Nº.: KCE 5035_1
INSULATED METAL WALL PANEL
METAL TRIM FLASHING, TYP
150mm METAL FRAMING
FILL CAVITY WITH SPRAY FOAM
SEALANT. TYPICAL.
INSULATION ON MECHANICAL DUCT(SEE MECHANICAL DRAWINGS)
DUCT WRAP (SEEMECHANICAL DRAWINGS)
CONTINUOUS VAPOR BARRIER;SEAL TO STRUCTURE
SEE PLANS FOR INTERIORFURRING AND FINISH (WHEREAPPLICABLE), TYP
STL TUBE FRAMING, TYP (SEESTRUCTURAL DRAWINGS)
(SE
E M
EC
H F
OR
SIZ
E)
ME
CH
AN
ICA
L D
UC
T
10mm SEALANT JOINT WITHCOMPRESSIBLE BACKER ROD (FULLPERIMETER, BOTH SIDES)
NOTE: SLOPE EXTERIORPORTION OF DUCT AWAYFROM BLDG FACESLIGHTLY TO SHEDWATER
ALUMINUM THERMAL SILLRECEPTOR BY WINDOWMANUFACTURER
SEALANT AND BACKERROD (FULL PERIMETEROF FRAME, BOTHSIDES)
SEALANT AND BACKERROD, TYP.
GASKETED ALUMINUM SILLFLASHING WITH END DAMS
PREFINISHED INSULATEDMETAL WALL PANEL
TUBE STEEL BACKUP (SEESTRUCTURAL DRAWINGS)
13mm FRMT PLYWOOD
INFILL BETWEEN STEELTUBING W/ MTL STUDS @40mm O.C., TYP (WHERE
APPLICABLE)
3"
75
MIN 40mm GA STL ANGLE, FULLPERIMETER OF OPENING (BYMTL PNL MFR), TYP
SCHEDULED GLAZING
TERMINATE GYP BDW/TEAR-AWAY BEAD
SOLID SURFACE SILL;EASE EDGES W/ 3mm
ROUND OVER
8"
200
4"
100
PREFINISHED INSULATEDMETAL WALL PANEL
TWO-PIECE HEAD EXTRUSIONCAP WITH GASKET
FIELD DRILL 10mm DIA. WEEPHOLES IN EXTRUSION CAP
SEALANT AND BACKER ROD, FULLPERIMETER OF FRAME (BOTHSIDES)
DEFLECTION HEADRECEPTOR
ALUMINUM STOREFRONTWINDOW SYSTEM
TUBE STEEL BACK-UP (SEESTRUCTURAL DRAWINGS)
MOLD RESISTANT GYP. BOARDOR PLYWOOD (WHERE
SCHEDULED; REFER TO FINISHSCHEDULE)
SEALANT AND BACKER ROD,FULL PERIMETER OF FRAME
12mm FRMT PLYWOOD
METAL STUD @ 400mm O.C.
HEAD FLASHING W/END DAMS
SCHEDULED CEILING
90
5"
115
8"
200
4"
100
PREFINISHED INSULATEDMETAL WALL PANEL
SEALANT AND BACKERROD, FULL PERIMETEROF FRAME BOTH SIDES
ALUMINUM STOREFRONTWINDOW SYSTEM
TUBE STEEL BACK-UP (SEESTRUCTURAL DRAWINGS)
MOLD RESISTANT GYP BD ORFIRE-TREATED PLYWOOD
(WHERE SCHEDULED; REFER TOFINISH SCHEDULE)
SEALANT AND BACKER ROD
METAL STUD INFILL @ 40mmO.C. WHERE GYP BD OR
PLYWOOD IS SPECIFIED. SEEWALL SECTIONS FOR
ADDTIONAL INFORMATION.
TERMINATE GYP BD W/MTL J-BEAD
FACE OF SILL BELOW
MIN 40mm GA STL ANGLE BYMTL PNL MFR; FULL
PERIMETER OF OPENING,TYP
4"100
8"200
TWO-PIECEEXTRUSION CAP WITHGASKET
STEEL PROFILE REFER TO STRUCTURALDRAWINGS
EXISTING STRUCTURE
NEW INSULATED WALL
SITE APPLIED FIRE RATED INSULATION
INTERNAL CLOSURE FLASHING WITH 100mmOVERALP SEALED WITH FILM BACKED BUTYLTAPE OR GUN GRADE SEALANT
AIR SEAL 6mm BEAD OF GUN GRADE SEALANTOR COMPRESSIBLE FOAM TAPE
AIR SEAL GUN GRADE SEAL TO MALE JOINTINLINE WITH INTERNAL AIR SEAL
INSULATED CLADDING PANEL FINISH TOMATCH EXISTING
POLYETHYLENE BACKING RODAND SILICONE SEALANT
AWP JOINT FILLER
LOW PROFILE STICHING SCREWS WITHMIN. Ø14mm NON FERROUS EPDM BACKEDWASHER FITTED MAX.@ 450mm c/c
Ø4mm BUTYL RUBBER SEALANT
EXTERNAL ENCLOUSRE FLASHING WITH 100mmSEALED BUTT STRAPS
4"100
4"
100
NEW INSULATED WALL
INSULATED CLADDING PANEL FINISH TOMATCH EXISTING
AIR SEAL 6mm BEAD OF GUN GRADE
AIR SEAL GUN GRADE TO MALE JOINTINLINE WITH INTERNAL SEAL
STEEL PROFILE REFER TO STRUCTURALDRAWINGS FOR DETAIL
AIR SEAL CONTINOUS BEAD OF GUN GRADESEALANT
DRIP FLASHING WITH 100mm SEALED BUTTSTRAPS
EXISTING STRUCTURE
SITE APPLIED PIR INSULATION BOARDANY GAPS FILLED WITH FIRE RATEDCANNISTER INSULATION
EXISTING STRUCTURE
NEW INSULATED WALLSTEEL PROFILE REFER TO STRUCTURALDRAWINGS FOR DETAIL
SILICONE SEALANT
DRIP FLASHING WITH 100mm SEALED BUTTSTRAPSAIR SEAL GUN GRADE TO MALE JOINTINLINE WITH INTERNAL SEAL
AIR SEAL 6mm BEAD OF GUN GRADESEALANTSITE APPLIED PIR INSULATION BOARDANY GAPS FILLED WITH FIRE RATEDCANNISTER INSULATION
INSULATED CLADDING PANEL FINISH TOMATCH EXISTING
4"
100
N
ENGINEERING EXCELLENCE
NOTE: EVERY SHEET NOTE MAY NOT APPEAR ON THIS PAGE
KEY PLAN
GENSLER 2017All rights reserved, including but not limited to The Copyright, Design and Patents Act 1988Do not scale from drawings. All discrepancies to be reported to Gensler architect immediately.All dimensions to be verified by contractor on site prior to any works
C
Thomas More SquareLondon
E1W 1YW
England, UK
Tel (0)20 7073 9600
Fax (0)20 7539 1917
WOOLVERSTONE HOUSE61 BERNERS STREETLONDONW1T 3NJ
Tel: 0207 0433410
Scale:
DRAWN:REVIEW:PROJECT NO.:
SHEET TITLE
SEAL/SIGNATURE
SHEET NO:
ISSUES & REVISIONS
10400 Rodgers RoadHouston, Texas 77070
Phone: 281-374-8644Fax: 281-374-8992
RED ENGINEERING DESIGN LTDWOOLVERSTONE HOUSE61 BERNERS STREETLONDONW1T 3NJ
Tel: 0207 2998260
PERMIT ITEM NUMBER
SUBJECT TO LOCALARCHITECT REVIEW FOR
STATUTORY CODECOMPLIANCE
As indicated @ A0
A9.051
Ces
snal
aan
32,
111
9 N
L S
chip
ho
l-R
ijk, N
eth
erla
nd
s
08.7142.101
Pro
ject
Nu
mb
er:
08.7
142.
101
DETAILS - EXTERIOR
SCALE: 1 : 5
TYP OVERHEAD FIBER DUCT ENTRANCE DETAIL03
SCALE: 1 : 10
TYP WALL PENETRATION - SINGLE PIPE/CONDUIT02
SCALE: 1 : 5
TYP EXT WALL CABLE PENETRATION DETAIL07
SCALE: 1 : 20
WALL PENETRATION ELEVATION01
SCALE: 1 : 5
TYPICAL MECHANICAL CURB DETAIL10
SCALE: 1 : 5
TYP AHU DUCT ROOF PENETRATION DETAIL11
SCALE: 1 : 2
TYP MTL COUNTER FLASHING DETAIL06
Issue # Rev # Issue Date Issue Description
3 1 20.01.17 90% - ISSUE FOR REVIEW
4 2 17.02.17 TENDER ISSUE
7 3 xx.xx.xx REVISION xx
SCALE: 1 : 5
KINGSPAN STANDARD LOUVRE DETAIL15
SCALE: 1 : 5
TYP INSULATED DUCT WALL PENETRATION04
SCALE: 1 : 5
TYP EXTERIOR WINDOW SILL DETAIL13
SCALE: 1 : 5
TYP EXTERIOR WINDOW HEAD DETAIL14
3
SCALE: 1 : 5
TYP EXTERIOR WINDOW JAMB DETAIL12
3
SCALE: 1 : 5
WINDOW OPENING INFILL JAMB DETAIL05SCALE: 1 : 5
WINDOW OPENING INFILL SILL DETAIL08
SCALE: 1 : 5
WINDOW OPENING INFILL HEAD DETAIL09
3