EXISTING CLADDING PANEL

THROUGH-WALL SILLFLASHING W/DRIP EDGE &END DAMS SET IN SEALANT;COLOR TO MATCH MTL PANEL

FACE OF STL BEYOND(SHOWN DASHED)

MIN 16 GA GALV STL ANGLE BYMTL PNL MFR, TYP FULLPERIMETER OF OPENING

TWO-PIECE HEAD EXTRUSIONCAP WITH GASKET, TYP

POSITVELY SLOPE FIBERDUCTS AWAY FROM BUILDINGSLIGHTLY TO SHED WATERAWAY FROM THE BUILDINGFACE, TYPDUCT FLANGE,TYP TOP ANDSIDES OF DUCT; ANCHOR TOTUBE STEEL

OVERHEAD FIBER DUCT (SEE TELECOM)

OVERHEAD FIBER (SEE TELECOM)

FILL GAP BETWEN TUBE STEELAND DUCT W/EXPANDINGSPRAY FOAM INSULATION, TYPFULL PERIMETER OF DUCT

SEALANT & BACKER ROD, TYP

TUBE STEEL FRAMING FULL PERIMETEROF OPENING (SEE STRUCTURAL)

EPDM PIPE SLEEVE; COORDINATESIZES MEP/TELECOM DRAWINGS

JOINT SEALANT, TYP

BACKER ROD AND SEALANT BOTH INTERIORAND EXTERIOR, FULL PERIMETER OFPENETRATION

PENETRATING PIPE

EXTERIOR CLADDINGPANEL

NOTE:PROVIDE SEALANT AS REQUIREDFOR WEATHER-TIGHT SYSTEM

SEAL EXT. PANEL AND BRAKE METALINFILL PER PANEL MANUFACTURERS

RECOMMENDATIONS

PIPE HANGER AND SUPPORT.REFER TO MECHANICAL

SET SLEEVE & COMPRESSIONRING IN SEALANT, TYP

SEE PLANS FOR INTERIOR FURRING &FINISH WHERE APPLICABLE, TYP

PROVIDE HORIZONTAL METALSTUDS TO MATCH GIRT DIMENSIONAT PENETRATION, BOTH SIDES(TYP)RIVET, TYP

METAL COMPRESSION RING,TYP

SEAL ENTIRE PERIMETER OFPENETRATION W/EXPANDING SPRAYFOAM INSULATION, TYP

WRAP PIPE W/INSULATION MIN 915mm IN TOTHE SPACE UNLESS NOTED OTHERWISE BYMECHANICAL DRAWINGS, TYPICAL

EXTERIOR CLADDING PANELINTERIOR WALL FINISH (WHERE

APPLICABLE - SEE PLANS)

TUBE STEEL OR METAL STUDFRAMING, TYP

SECTION

ELEVATION (EXTERIOR)

MANUFACTURER'SRECOMMENDED FASTENER,TYP

TRIM FLANGE; SET IN SEALANT FULLPERIMETER OF FRAME. BASIS OF DESIGN IS'ROXTEC GH FRAMES'. WWW.ROXTEC.COM

EXPANDING SPRAY FOAMINSULATION, TYP FULL

PERIMETER OF PENETRANTCAVITY

ON

NU

MB

ER

OF

PE

NE

TRA

NTS

SIZ

E A

S R

EQ

UIR

ED

BA

SE

D

ON NUMBER OF PENETRANTSSIZE AS REQUIRED BASED

BASIS OF DESIGN IS 'MULTI-DIAMETER'PENETRANT SEALS. WWW.ROXTEC.COM

CONDUIT/SMALL PIPE/CABLEPENETRANT (SEE ELECTRICAL ANDTELECOM DRAWINGS FORSIZES/QUANTITIES)

MANUFACTURER'SRECOMMENDED FASTENER,TYP

TRIM FLANGE; SET IN SEALANTFULL PERIMETER OF FRAME.BASIS OF DESIGN IS 'ROXTEC GHFRAMES'. WWW.ROXTEC.COM

BASIS OF DESIGN IS 'MULTI-DIAMETER' PENETRANT SEALS.WWW.ROXTEC.COM

CONDUIT/CABLE PENETRANT, TYP(SEE ELECTRICAL AND TELECOM

DRAWINGS)

LINER FLASHING, FULLPERIMETER OF PENETRANT;

SET IN SEALANT, TYP

NOTE: THIS DETAIL APPLIES FOR SITUATIONSWHERE MULTIPLE SMALL CONDUITS, SMALLPIPES, AND/OR CABLES PENETRATE THE SIDEOF A BUILDING. FOR INDIVIDUALPENETRATIONS, REFER TO ALTERNAE WALLPENETRATION DETAILS ON THIS SHEET.

'WEDGE BLOCK' (PRESSURESTHE SEALANT BLOCKS TOSEAL THE PENETRANTS)

'STAY-PLATE' BETWEEN ROWS, TYP

LARGE PENETRATION ROUGH OPENINGW/MULTIPLE ROUND PENETRANTS, TYPICAL. BASIS-OF-DESIGN ROXTEC. COORDINATE WITHSPECIFIED PRODUCT. REFER TO TELECOMDRAWINGS, MECHANICAL, PLUMBING, ANDELECTRICAL DRAWINGS.

PROVIDE DOUBLE METAL FRAMING STUDSTYPICAL AT ALL LARGE PENETRATION ROUGHOPENINGS. COORDINATE WITH SPECIFIEDPRODUCTS.

LARGE PENETRANT (DUCT, TELECOMFIBER, LARGE PIPES, ETC)NOTE:

1. THIS DETAIL IS SHOWN TO DEMONSTRATE THE NEED FOR SUPPLEMENTAL METAL STUD FRAMING AT LOCATIONSWHERE MECHANICAL, PLUMBING, ELECTRICAL, AND/OR TELECOM ITEMS PENETRATE THE EXTERIOR WALL OF THEBUILDING & THERE IS NO TUBE STEEL.

2. CONTRACTOR SHALL COORDINATE PENETRATION ROUGH OPENINGS WITH STRUCTURAL STEEL CONTRACTOR, METALFRAMING CONTRACTOR AND EXTERIOR METAL PANEL CONTRACTOR, TYPICAL.

3. CONTRACTOR SHALL COORDINATE BACKUP REQUIREMENTS WITH THE SELECTED METAL PANEL SUPPLIER.4. INTERIOR FURRING AND SHEATHING IS NOT SHOWN FOR CLARITY.5. FOR LOCATIONS W/ TUBE STEEL AROUND THE PERIMETER OF THE OPENING, NO SUPPLEMENTAL STUD FRAMING IS

REQUIRED.

STRUCTURAL STEEL, TYP (SEE STRU)

CONC CURB OR STRUCTURAL STEEL(SEE STRUCTURAL)

METAL ROOF DECK

CONT METAL ROOF DECK CLOSURE.CONFORM TO DECK PROFILE. SET INMASTIC AND SEAL AIR-TIGHT

VAPOUR RETARDER

RIGID ROOF INSULATION

PROTECTION BOARD

ROOFING MEMBRANE

ROOFING SEALANT / HEAT WELD

EXTEND ROOFING MEMBRANEAND VAPOUR RETARDER

HIGH-DOMED GASKETED FASTENER

MECHANICAL UNIT OR FANSET UNIT IN MASTICSEALANT TAPE PROVIDEDBY CURB MANUFACTURER

INSULATED PRE-MANUFACTURED CURB,FASTEN TO ROOF DECK

SUPPORTING FRAMING, SEESTRUCT DWGS

600m

m M

IN

MECH UNIT

T/CURB - LEVEL

EL. 300mm MIN ABOVEFINISHED ROOF

HIGH-DOMED GASKETED SHEETMETAL FASTENER

COUNTER FLASHING, SET INSEALANT

TERMINATION BAR, FASTEN TO DUCT 150mm OC

SEALANT

INSULATED DUCT,SEE MECHDRAWINGS

ROOFING MEMBRANEFLASHING FULLY ADHERED

CONT SHEET VAPOR RETARDERAROUND ALL SIDES OF DUCT CURB.TAPE AND SEAL TO DUCT AND CURB.TAPE AND SEAL ALL EDGES ANDSEAMS

FILL VOIDS WITH CONTBATT INSULATION

INTERIOROF DUCT

VAPOR RETARDER (SHOWN DASHED)

PROTECTION BOARD, TYP

METAL ROOF DECK

STEEL FRAMING AT DUCTPENETRATION, REFER TOSTRUCTURAL DRAWINGS

ROOFING MEMBRANE CURB FLASHING.EXTEND OVER TOP OF CURB

SINGLE-PLY ROOFING MEMBRANE

ADHERE CONTINUOUS VAPOR RETARDER OVERCURB FLANGE. SEAL TO CURB AND ROOF VAPOR

RETARDERROOF CURB FLANGE, SET IN CONTINUOUS

ROOFING SEALANT AND FASTENED

RIGID ROOF INSULATION

ROOFING MEMBRANE FLASHING FULLYADHERED OVER BACKER ROD

BACKER ROD EXPANSION JOINT40mm

PT WOOD NAILER

PRE-MANUFACTURED INSULATEDROOF CURB W/ PT WOOD NAILER

SEALANT

22 GA MTL FLASHINGW/HEMMED EDGE, TYP; FINISHTO MATCH MTL PANELS

FACE OF MTL PANEL

RIVET CLOSED END OR CHERRYMAXIBOLT; PAINT EXPOSED HEADTO MATCH MTL SIDING COLOR

CONT BUTYL SEALANT BEAD INBULGE

COMPRESSION SEAL; FASTENW/POP RIVET. EXPOSED HEADTO MATCH MTL SIDING COLOR

CONT TERMINATION BAR

SEALANT

5"

115

mm

MIN

3"75

6"140

ROOF MEMBRANE; TURNUP FACE OF METAL PANELMIN 450mm AND FULLYADHERE.

AIR SEAL - CONTINUOUS 20 x 6mmPVC FOAM TAPE.

INTERNAL FINISH TO ARCHITECTSDETAILS AND SPECIFICATION.

VOID FILLED WITH 25mm THICKRIGID INSULATION BOARD.

LOUVRE SYSTEM & SEALS BYLOUVRE SPECIALIST.

POLYESTER POWDER COATEDALUMINIUM SOFFIT FLASHING.

AIR SEAL - POLYESTER POWDERCOATED ALUMINIUM SOFFIT

FLASHING TO BE FULLY SEALED TOSUPPORT WITH VAPOUR SEAL TAPE.

AIR SEAL - CONTINUOUS 20 x 6mmPVC FOAM TAPE.

INTERNAL FINISH TO ARCHITECTSDETAILS AND SPECIFICATION.

AIR SEAL - POLYESTER POWDERCOATED ALUMINIUM SOFFIT FLASHING

TO BE FULLY SEALED TO SUPPORTWITH VAPOUR SEAL TAPE.

LOUVRE SYSTEM & SEALS BYLOUVRE SPECIALIST.

HORIZONTAL SUPPORT TO STRUCTURALENGINEER'S DETAILS AND SPECIFICATION.

MIN 60mm BEARING.POLYESTER POWDER COATEDALUMINIUM DRIP FLASHING.

HORIZONTAL SUPPORT TO STRUCTURALENGINEER'S DETAILS AND SPECIFICATION.

MIN 60mm BEARING.

TOP OF PANEL TO BE TRIMMED TO SUIT.

POLYESTER POWDER COATED ALUMINIUM CILLFLASHING. FLASHING TO BE FIXED AND SEALED TO PANELWITH 9mmx3mm BUTYL RUBBER SEALANT.

LOW PROFILE STAINLESS STEEL STITCHING SCREWS WITH

14mm DIAMETER NON-FERROUS EPDM BACKED WASHER

FITTED AT 450mm CENTRES .

KS1100AB LPCB CERTIFIED INSULATED

WALL PANEL, HORIZONTALLY LAID.

SELF-DRILLING, SELF-TAPPING LOW

PROFILE STAINLESS STEEL PRIMARY

FIXINGS WITH 16mm DIAMETER

NON-FERROUS EPDM BACKED WASHER .

AT 1000mm CENTRES.

SELF-DRILLING, SELF-TAPPING LOW PROFILE STAINLESSSTEEL PRIMARY FIXINGS WITH 16mm DIAMETERNON-FERROUS EPDM BACKED WASHER AT 1000mm CENTRES.

KS1100 AB LPCB CERTIFIED INSULATED

WALL PANEL , HORIZONTALLY LAID.

BOTTOM OF PANEL TO BE TRIMMED TO SUIT.

PANEL THICKNESS

PANEL THICKNESS

60 30 60

Internal.

External.

Gap between panel ends to be filled using FR canisterinsulation and cut flush prior to butyl tape application.Self-drill, self-tapping fastener complete with convex

washer. Minimum 3 No. per panel per support . Drill endsremoved.

Panel sealed along its full length using two runs of 12 x 6mm foam tape - Premier Sealants ref: SBV25 .

Kingspan KS1 100 CS EcoSafe insulated wall panel horizontally laid.

Continuous 6mm bead of FR silicone sealantNullifire M703 or similar , in female joint on internaland externa face prior to panel installation.

4mm diameter butyl rubber sealant (site applied) .

Top Hat Flashing (RWH1) . Top-hat support cleats at 500mmcentres fixed using rivets.Flush 'Snap-in' insert with clip.

Internal.

External.

Kingspan KS1 1 00AB EcoSafe insulated wall panel horizontally laid.

Blind rivets.

4mm diameter butyl rubber sealant (site applied) .Top Hat Flashing (RWH1).

Flush 'Snap-in' insert with clip.

Top Hat fixed to top hat support cleats usingstitching screws complete with clip .

Continuous 6mm bead of FR silicone sealantNullifire M703 or similar , to male joint prior to panelinstallation.

face 75mm

40mmMin. Steelbearing

face 75mm

Min. Steelbearing

To be read in conjunctionwith specification

NOTE - THIS IS A STANDARD KINGSPAN DETAIL: SYSTEM- Boundary Wall - Hz Wall Vt Joint Detail Hz SFS 001 Drawing Nº.: KCE 5035_2

NOTE - THIS IS A STANDARD KINGSPAN DETAIL: SYSTEM- Boundary Wall - Hz Wall Vt Joint Detail Drawing Nº.: KCE 5035_1

INSULATED METAL WALL PANEL

METAL TRIM FLASHING, TYP

150mm METAL FRAMING

FILL CAVITY WITH SPRAY FOAM

SEALANT. TYPICAL.

INSULATION ON MECHANICAL DUCT(SEE MECHANICAL DRAWINGS)

DUCT WRAP (SEEMECHANICAL DRAWINGS)

CONTINUOUS VAPOR BARRIER;SEAL TO STRUCTURE

SEE PLANS FOR INTERIORFURRING AND FINISH (WHEREAPPLICABLE), TYP

STL TUBE FRAMING, TYP (SEESTRUCTURAL DRAWINGS)

(SE

E M

EC

H F

OR

SIZ

E)

ME

CH

AN

ICA

L D

UC

T

10mm SEALANT JOINT WITHCOMPRESSIBLE BACKER ROD (FULLPERIMETER, BOTH SIDES)

NOTE: SLOPE EXTERIORPORTION OF DUCT AWAYFROM BLDG FACESLIGHTLY TO SHEDWATER

ALUMINUM THERMAL SILLRECEPTOR BY WINDOWMANUFACTURER

SEALANT AND BACKERROD (FULL PERIMETEROF FRAME, BOTHSIDES)

SEALANT AND BACKERROD, TYP.

GASKETED ALUMINUM SILLFLASHING WITH END DAMS

PREFINISHED INSULATEDMETAL WALL PANEL

TUBE STEEL BACKUP (SEESTRUCTURAL DRAWINGS)

13mm FRMT PLYWOOD

INFILL BETWEEN STEELTUBING W/ MTL STUDS @40mm O.C., TYP (WHERE

APPLICABLE)

3"

75

MIN 40mm GA STL ANGLE, FULLPERIMETER OF OPENING (BYMTL PNL MFR), TYP

SCHEDULED GLAZING

TERMINATE GYP BDW/TEAR-AWAY BEAD

SOLID SURFACE SILL;EASE EDGES W/ 3mm

ROUND OVER

8"

200

4"

100

PREFINISHED INSULATEDMETAL WALL PANEL

TWO-PIECE HEAD EXTRUSIONCAP WITH GASKET

FIELD DRILL 10mm DIA. WEEPHOLES IN EXTRUSION CAP

SEALANT AND BACKER ROD, FULLPERIMETER OF FRAME (BOTHSIDES)

DEFLECTION HEADRECEPTOR

ALUMINUM STOREFRONTWINDOW SYSTEM

TUBE STEEL BACK-UP (SEESTRUCTURAL DRAWINGS)

MOLD RESISTANT GYP. BOARDOR PLYWOOD (WHERE

SCHEDULED; REFER TO FINISHSCHEDULE)

SEALANT AND BACKER ROD,FULL PERIMETER OF FRAME

12mm FRMT PLYWOOD

METAL STUD @ 400mm O.C.

HEAD FLASHING W/END DAMS

SCHEDULED CEILING

90

5"

115

8"

200

4"

100

PREFINISHED INSULATEDMETAL WALL PANEL

SEALANT AND BACKERROD, FULL PERIMETEROF FRAME BOTH SIDES

ALUMINUM STOREFRONTWINDOW SYSTEM

TUBE STEEL BACK-UP (SEESTRUCTURAL DRAWINGS)

MOLD RESISTANT GYP BD ORFIRE-TREATED PLYWOOD

(WHERE SCHEDULED; REFER TOFINISH SCHEDULE)

SEALANT AND BACKER ROD

METAL STUD INFILL @ 40mmO.C. WHERE GYP BD OR

PLYWOOD IS SPECIFIED. SEEWALL SECTIONS FOR

ADDTIONAL INFORMATION.

TERMINATE GYP BD W/MTL J-BEAD

FACE OF SILL BELOW

MIN 40mm GA STL ANGLE BYMTL PNL MFR; FULL

PERIMETER OF OPENING,TYP

4"100

8"200

TWO-PIECEEXTRUSION CAP WITHGASKET

STEEL PROFILE REFER TO STRUCTURALDRAWINGS

EXISTING STRUCTURE

NEW INSULATED WALL

SITE APPLIED FIRE RATED INSULATION

INTERNAL CLOSURE FLASHING WITH 100mmOVERALP SEALED WITH FILM BACKED BUTYLTAPE OR GUN GRADE SEALANT

AIR SEAL 6mm BEAD OF GUN GRADE SEALANTOR COMPRESSIBLE FOAM TAPE

AIR SEAL GUN GRADE SEAL TO MALE JOINTINLINE WITH INTERNAL AIR SEAL

INSULATED CLADDING PANEL FINISH TOMATCH EXISTING

POLYETHYLENE BACKING RODAND SILICONE SEALANT

AWP JOINT FILLER

LOW PROFILE STICHING SCREWS WITHMIN. Ø14mm NON FERROUS EPDM BACKEDWASHER FITTED MAX.@ 450mm c/c

Ø4mm BUTYL RUBBER SEALANT

EXTERNAL ENCLOUSRE FLASHING WITH 100mmSEALED BUTT STRAPS

4"100

4"

100

NEW INSULATED WALL

INSULATED CLADDING PANEL FINISH TOMATCH EXISTING

AIR SEAL 6mm BEAD OF GUN GRADE

AIR SEAL GUN GRADE TO MALE JOINTINLINE WITH INTERNAL SEAL

STEEL PROFILE REFER TO STRUCTURALDRAWINGS FOR DETAIL

AIR SEAL CONTINOUS BEAD OF GUN GRADESEALANT

DRIP FLASHING WITH 100mm SEALED BUTTSTRAPS

EXISTING STRUCTURE

SITE APPLIED PIR INSULATION BOARDANY GAPS FILLED WITH FIRE RATEDCANNISTER INSULATION

EXISTING STRUCTURE

NEW INSULATED WALLSTEEL PROFILE REFER TO STRUCTURALDRAWINGS FOR DETAIL

SILICONE SEALANT

DRIP FLASHING WITH 100mm SEALED BUTTSTRAPSAIR SEAL GUN GRADE TO MALE JOINTINLINE WITH INTERNAL SEAL

AIR SEAL 6mm BEAD OF GUN GRADESEALANTSITE APPLIED PIR INSULATION BOARDANY GAPS FILLED WITH FIRE RATEDCANNISTER INSULATION

INSULATED CLADDING PANEL FINISH TOMATCH EXISTING

4"

100

N

ENGINEERING EXCELLENCE

NOTE: EVERY SHEET NOTE MAY NOT APPEAR ON THIS PAGE

KEY PLAN

GENSLER 2017All rights reserved, including but not limited to The Copyright, Design and Patents Act 1988Do not scale from drawings. All discrepancies to be reported to Gensler architect immediately.All dimensions to be verified by contractor on site prior to any works

C

Thomas More SquareLondon

E1W 1YW

England, UK

Tel (0)20 7073 9600

Fax (0)20 7539 1917

WOOLVERSTONE HOUSE61 BERNERS STREETLONDONW1T 3NJ

Tel: 0207 0433410

Scale:

DRAWN:REVIEW:PROJECT NO.:

SHEET TITLE

SEAL/SIGNATURE

SHEET NO:

ISSUES & REVISIONS

10400 Rodgers RoadHouston, Texas 77070

Phone: 281-374-8644Fax: 281-374-8992

RED ENGINEERING DESIGN LTDWOOLVERSTONE HOUSE61 BERNERS STREETLONDONW1T 3NJ

Tel: 0207 2998260

PERMIT ITEM NUMBER

SUBJECT TO LOCALARCHITECT REVIEW FOR

STATUTORY CODECOMPLIANCE

As indicated @ A0

A9.051

Ces

snal

aan

32,

111

9 N

L S

chip

ho

l-R

ijk, N

eth

erla

nd

s

08.7142.101

Pro

ject

Nu

mb

er:

08.7

142.

101

DETAILS - EXTERIOR

SCALE: 1 : 5

TYP OVERHEAD FIBER DUCT ENTRANCE DETAIL03

SCALE: 1 : 10

TYP WALL PENETRATION - SINGLE PIPE/CONDUIT02

SCALE: 1 : 5

TYP EXT WALL CABLE PENETRATION DETAIL07

SCALE: 1 : 20

WALL PENETRATION ELEVATION01

SCALE: 1 : 5

TYPICAL MECHANICAL CURB DETAIL10

SCALE: 1 : 5

TYP AHU DUCT ROOF PENETRATION DETAIL11

SCALE: 1 : 2

TYP MTL COUNTER FLASHING DETAIL06

Issue # Rev # Issue Date Issue Description

3 1 20.01.17 90% - ISSUE FOR REVIEW

4 2 17.02.17 TENDER ISSUE

7 3 xx.xx.xx REVISION xx

SCALE: 1 : 5

KINGSPAN STANDARD LOUVRE DETAIL15

SCALE: 1 : 5

TYP INSULATED DUCT WALL PENETRATION04

SCALE: 1 : 5

TYP EXTERIOR WINDOW SILL DETAIL13

SCALE: 1 : 5

TYP EXTERIOR WINDOW HEAD DETAIL14

3

SCALE: 1 : 5

TYP EXTERIOR WINDOW JAMB DETAIL12

3

SCALE: 1 : 5

WINDOW OPENING INFILL JAMB DETAIL05SCALE: 1 : 5

WINDOW OPENING INFILL SILL DETAIL08

SCALE: 1 : 5

WINDOW OPENING INFILL HEAD DETAIL09

3