ARMY & AIR FORCE EXCHANGE SERVICE CONVERT BASKIN ROBBINS TO FRESHENS PN 4085-15-000003 BLDG # 2527 FACILITY # 4085280100 100% CONSTRUCTION DOCUMENTS 01 DECEMBER 2015 ARCHITECTS WEST CONTACT - STEVE ROTH 210 EAST LAKESIDE AVE. COEUR D'ALENE, ID 83814 208.667.9402 208.667.6103 FAX [email protected] COFFMAN ENGINEERS CONTACT - BOB KOCA 10 NORTH POST ST., SUITE 500 SPOKANE, WA 99201 509.328.2994 509.328.2999 FAX [email protected] TRINDERA ENGINEERING CONTACT - JAMES FAWSON 1875 NORTH LAKEWOOD DR., SUITE 201 COEUR D'ALENE, ID 83814 208.676.8001 208.676.0100 FAX [email protected] THE EXCHANGE CONTACT - GREG PORTER 3911 S. WALTON WALKER BLVD. DALLAS, TX 75236-1598 214.312.4535 214.236.6857 FAX [email protected] www.shopmyexchange.com PROJECT TEAM BASE MAP VICINITY MAP PROJECT SITE PROJECT LOCATION DAVIS MONTHAN AFB TUCSON, AZ CONSTRUCTION ACCESS SWAN GATE HOURS 0600-1800 M-F DRAWN BY: CHECKED BY: DESIGN TYPE: DESIGN PHASE: DATE SUBMITTED: PROJECT: DRAWING TITLE: DESIGN SIZE: EXCHANGE SCALE: SHEET: Architects West 210 East Lakeside Avenue Coeur d'Alene, ID 83814 Ph: 208.667.9402 www.architectwest.com Architecture Landscape Architecture DAVIS MONTHAN A.F.B. TUCSON, ARIZONA GTO/SB SJR CONSTRUCTION DOCUMENTS 12/1/2015 A0.00 COVER SHEET/INDEX CONVERT BASKIN ROBBINS TO FRESHENS 4085-15-000003 DRAWING INDEX GENERAL A0.00 COVER SHEET/INDEX ARCHITECTURAL A1.01 GENERAL NOTES A2.01 FLOOR AND CEILING PLANS A2.02 EQUIPMENT PLAN A2.03 INTERIOR ELEVATIONS A3.01 PLUMBING AND ELECTRICAL PLANS A4.01 CASEWORK PLANS AND DETAILS A4.02 EQUIPMENT DETAILS A4.03 GRAPHICS DETAILS MECHANICAL M0.01 GENERAL NOTES, LEGENDS, SHEET INDEX M1.01 PLUMBING PLANS AND PLUMBING SCHEDULE ELECTRICAL E0.01 GENERAL NOTES, ABBREVIATIONS, AND LEGENDS ED.01 DEMOLITION PLAN E0.11 ONE-LINE DIAGRAM AND SCHEDULES E0.12 PANEL SCHEDULES E0.13 PANEL SCHEDULES E1.00 ELECTRICAL SITE PLAN E1.11 POWER PLAN & SPECIAL SYSTEMS PLAN Revision Schedule Revision # Revision Description Revision Date
Transcript
  • ARMY & AIR FORCE EXCHANGE SERVICE

    CONVERT BASKIN ROBBINS TO FRESHENSPN 4085-15-000003BLDG # 2527FACILITY # 4085280100

    100% CONSTRUCTION DOCUMENTS01 DECEMBER 2015

    ARCHITECTS WESTCONTACT - STEVE ROTH210 EAST LAKESIDE AVE.COEUR D'ALENE, ID 83814208.667.9402 208.667.6103 [email protected]

    COFFMAN ENGINEERSCONTACT - BOB KOCA10 NORTH POST ST., SUITE 500SPOKANE, WA 99201509.328.2994 509.328.2999 [email protected]

    TRINDERA ENGINEERINGCONTACT - JAMES FAWSON1875 NORTH LAKEWOOD DR., SUITE 201COEUR D'ALENE, ID 83814208.676.8001 208.676.0100 [email protected]

    THE EXCHANGECONTACT - GREG PORTER3911 S. WALTON WALKER BLVD.DALLAS, TX 75236-1598214.312.4535 214.236.6857 [email protected]

    PROJECT TEAM

    BASE MAP VICINITY MAP

    PROJECT SITE

    PROJECT LOCATION

    DAVIS MONTHAN AFBTUCSON, AZ

    CONSTRUCTION ACCESSSWAN GATE HOURS 0600-1800 M-F

    DRAWN BY:

    CHECKED BY:

    DESIGN TYPE:

    DESIGN PHASE:

    DATE SUBMITTED:

    PROJECT:

    DRAWING TITLE:

    DESIGN SIZE:

    EXCHANGE

    SCALE: SHEET:

    Ar c

    h itec

    t s W

    est

    210 E

    ast Lakesid

    e A

    venue

    Coeur

    d'A

    lene, ID

    83814

    Ph: 208.6

    67.9

    402

    ww

    w.a

    rchitectw

    est.com

    Ar c

    hitectu

    r e Landscape A

    rchitect u

    re

    DAVIS MONTHAN A.F.B.TUCSON, ARIZONA

    GTO/SB

    SJR

    CONSTRUCTION DOCUMENTS

    12/1/2015

    A0.00

    COVER SHEET/INDEX

    CONVERT BASKINROBBINS TOFRESHENS

    4085-15-000003

    DRAWING INDEXGENERAL

    A0.00 COVER SHEET/INDEX

    ARCHITECTURALA1.01 GENERAL NOTESA2.01 FLOOR AND CEILING PLANSA2.02 EQUIPMENT PLANA2.03 INTERIOR ELEVATIONSA3.01 PLUMBING AND ELECTRICAL PLANSA4.01 CASEWORK PLANS AND DETAILSA4.02 EQUIPMENT DETAILSA4.03 GRAPHICS DETAILS

    MECHANICALM0.01 GENERAL NOTES, LEGENDS, SHEET INDEXM1.01 PLUMBING PLANS AND PLUMBING SCHEDULE

    ELECTRICALE0.01 GENERAL NOTES, ABBREVIATIONS, AND LEGENDSED.01 DEMOLITION PLANE0.11 ONE-LINE DIAGRAM AND SCHEDULESE0.12 PANEL SCHEDULESE0.13 PANEL SCHEDULESE1.00 ELECTRICAL SITE PLANE1.11 POWER PLAN & SPECIAL SYSTEMS PLAN

    Revision Schedule

    Revision #Revision

    Description Revision Date

  • QUOTES GENERATED OFF PRELIMINARY PLANS ARE SUBJECT TO CHANGE UNTIL A SITE SURVEY HAS BEEN PERFORMED TO VERIFY EXISTING CONDITIONSAND DIMENSIONS. EVERY EFFORT IS MADE TO MAKE THE PRELIMINARY PLAN AND QUOTE AS COMPLETE AND ACCURATE AS POSSIBLE BASED ON THEINFORMATION PROVIDED. A FINAL QUOTE WILL BE GENERATED AFTER SITE SURVEY HAS BEEN PERFORMED AND FINAL DESIGN DRAWINGS HAVE BEENISSUED. FOR NEW CONSTRUCTION, THE FINAL EQUIPMENT PLAN AND QUOTE WILL BE BASED ON THE CONSTRUCTION DOCUMENTS PROVIDED BY THEPROJECT ARCHITECT. ANY CHANGES MADE DURING CONSTRUCTION MUST BE APPROVED BY FRESHËNS AND MAY REQUIRE REVISIONS TO THEEQUIPMENT LAYOUT AND QUOTE.

    GENERAL NOTES:

    1. IT IS THE LICENSED OPERATOR'S RESPONSIBILITY TO PROVIDE ALL CONSTRUCTION DOCUMENTS AS MAY BE REQUIRED BY LOCAL PERMITTINGAUTHORITIES, OFTEN REQUIRING THE SERVICES OF A REGISTERED ARCHITECT AND/OR ENGINEER.

    2. FRESHENS WILL WORK WITH THE OPERATOR'S ARCHITECT ON A CONSULTING BASIS ONLY. FRESHENS CANNOT PROVIDE SIGNED/SEALEDCONSTRUCTION DOCUMENTS.

    3. IT IS THE LICENSED OPERATOR'S RESPONSIBILITY TO VERIFY COMPLIANCE WITH ALL LOCAL CODES AND ORDINANCES. ANY DISCREPANCIES MUST BEIMMEDIATELY BROUGHT TO THE ATTENTION OF FRESHENS.

    4. THE LICENSED OPERATOR MUST PROVIDE QUALIFIED CONSTRUCTION TRADES (GC) TO PREPARE THE SPACE TO FRESHENS REQUIREMENTS INCLUDING(WHERE APPLICABLE), BUT NOT LIMITED TO; DEMOLITION, NEW PARTITIONS, FINISH MATERIALS, HARDWARE, PLUMBING AND ELECTRICAL ROUGH-INSAND FINAL CONNECTIONS.

    5. THE GC SHALL VISIT THE JOB SITE AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS, INCLUDING VERIFYING ALL DIMENSIONS AND LOCATIONS OFALL EXISTING UTILITIES. ANY DISCREPANCIES OR OMISSIONS MUST BE IMMEDIATELY BROUGHT TO THE ATTENTION OF FRESHENS.

    6. A PRE-CONSTRUCTION MEETING (OR CONFERENCE CALL) WILL BE SCHEDULED A MINIMUM OF 6 WEEKS PRIOR TO OPENING.

    7. A FOLLOW UP MEETING WILL BE SCHEDULED A MINIMUM OF 3 WEEKS PRIOR TO OPENING (PRIOR TO MILLWORK SHIPPING) TO VERIFY THAT THE SITE ISREADY TO RECEIVE MILLWORK AND EQUIPMENT AND IS ON SCHEDULE FOR OPENING.

    8. IT IS THE INTENT THAT THE WORK SHALL BE COMPLETE IN EVERY RESPECT AND THAT ANY MATERIAL OR WORK NOT SPECIFICALLY MENTIONED ORSHOWN ON THE DRAWINGS BUT NECESSARY TO FULLY COMPLETE THE WORK SHALL BE PROVIDED.

    9. THE GC WILL BE RESPONSIBLE FOR OFFLOADING ALL EQUIPMENT. IF A LOADING DOCK IS NOT AVAILABLE, UPON REQUEST, A TRUCK WITH LIFT GATECAN BE PROVIDED. A PALLET JACK WILL BE REQUIRED TO ASSIST IN OFF-LOADING.

    10. UPON RECEIPT, THE EQUIPMENT SHALL BE IMMEDIATELY INSPECTED FOR DAMAGE. ANY CLAIMS MUST BE FILED WITH SUPPORTING DOCUMENTATIONAND IN ACCORDANCE WITH THE TERMS OF THE CARRIER RESPONSIBLE FOR YOUR DELIVERY. FAILURE TO DO SO MAY RESULT IN THE CARRIERREFUSING TO HONOR THE CLAIM.

    11. UNLESS NOTED OTHERWISE, THE GC IS RESPONSIBLE FOR INSTALLING ALL EQUIPMENT AND MAKING ALL FINAL PLUMBING AND ELECTRICALCONNECTIONS.

    12. SOME EQUIPMENT MAY ARRIVE IN KNOCK-DOWN CONDITION AND WILL REQUIRE ASSEMBLY BY THE GC.

    SCOPE OF WORK

    SCOPE RESPONSIBILITY COMMENTS

    ARCHITECTURAL AND ENGINEERING OWNERS ARCHITECT/ENGINEER

    PERMITTING GENERAL CONTRACTOR

    FLOORING AND BASE GENERAL CONTRACTOR

    WALL FINISHES GENERAL CONTRACTOR

    CEILING FINISHES GENERAL CONTRACTOR

    MILLWORK GENERAL CONTRACTOR

    MILLWORK SHOP DRAWINGS GENERAL CONTRACTOR

    MILLWORK SHOP DRAWING APPROVAL FRESHENS / ARCHITECT / GC

    MILLWORK FABRICATION GENERAL CONTRACTOR UPON SHOP DRAWING APPROVAL FROM FRESHENS

    MILLWORK INSTALLATION GENERAL CONTRACTOR

    UNLOAD AND STORE EQUIPMENT GENERAL CONTRACTOR

    EQUIPMENT INSTALLATION GENERAL CONTRACTOR SOME EQIPMENT REQUIRES ASSEMBLY

    PLUMBING ROUGH IN GENERAL CONTRACTOR

    FINAL PLUMBING CONNECTIONS GENERAL CONTRACTOR

    ELECTRICAL ROUGH IN GENERAL CONTRACTOR

    FINAL ELECTRICAL CONNECTIONS GENERAL CONTRACTOR

    HVAC GENERAL CONTRACTOR

    LIFE SAFTEY AND FIRE PROTECTION GENERAL CONTRACTOR

    SIGN INSTALLATION GENERAL CONTRACTOR

    VINYL GRAPHICS FRESHENS FURNISHED AND INSTALLED BY PUBLIC IMAGERY

    DIGITAL MENU FRESHENS FURNISHED AND INSTALLED BY ALLURE GLOBAL

    DRAWN BY:

    CHECKED BY:

    DESIGN TYPE:

    DESIGN PHASE:

    DATE SUBMITTED:

    PROJECT:

    DRAWING TITLE:

    DESIGN SIZE:

    EXCHANGE

    SCALE: SHEET:

    Ar c

    h itec

    t s W

    est

    210 E

    ast Lakesid

    e A

    venue

    Coeur

    d'A

    lene, ID

    83814

    Ph: 208.6

    67.9

    402

    ww

    w.a

    rchitectw

    est.com

    Ar c

    hitectu

    r e Landscape A

    rchitect u

    re

    3/8" = 1'-0"

    DAVIS MONTHAN A.F.B.TUCSON, ARIZONA

    SB

    SJR

    CONSTRUCTION DOCUMENTS

    12/1/2015

    A1.01

    GENERAL NOTES

    CONVERT BASKINROBBINS TOFRESHENS

    4085-15-000003

    Revision Schedule

    Revision #Revision

    Description Revision Date

  • FRESHENS

    REMOVE EXISTINGDOOR AND FRAME

    REMOVE EXISTING WALL

    REMOVE PORTION OFEXISTING WALL ANDHEADER

    REMOVE ALL BUILT-INCASEWORK AND FINISHES

    REMOVE EXISTING PLATFORM

    REMOVE EXISTING FLOORTILE IN THIS AREA INPREPARATION FORNEW WALLS, EQUIPMENT,CASEWORK, AND FINISHES

    FRESHENS

    2' - 1"5' - 3"

    2' -

    0"

    2' -

    5"

    1A2.02A2.01

    2A2.02A2.01

    A2.03

    A2.032

    1

    A2.03

    4

    53

    PATCH FLOOR TILE WHEREWALL WAS REMOVED

    PATCH AND REFINISHWALL WHERE EXIST.WALL WAS REMOVED

    NEW FLOOR TILE TOMATCH EXISTINGPREP AREA FLOOR TILE

    NEW H.M. DOOR IN H.M. FRAME.PAINT DOOR AND FRAME TO MATCHADJACENT WALL COLOR. DOORHARDWARE TO BE STORE-ROOMTYPE, KEY OPERATED FROM EXTERIORAND FREE EXITING FROM THE INTERIOR.MATCH EXISTING HARDWARE STYLE,BRAND, AND FINISH.

    NEW WALLS TO BE 3 5/8" METAL STUDSWITH 5/8" GYP. BD. ON EACH SIDE, TYP.

    FINISH NEW WALL TO BE FLUSHWITH EXISTING WALL

    6' - 0"

    9' - 0"

    7' - 0"

    9' - 0" 8' - 6"

    EXISTING WORKROOM CEILING

    PAINT WHITE

    PAINT WHITEPAINT FRESHENS YELLOW

    EXISTING CEILING, LIGHTS, DIFFUSERS,AND OTHER CEILING-MOUNTED ITEMSTO REMAIN

    REMOVE EXISTING ANGLED SOFFIT

    6"1'-

    6"5"

    PATCH SUSPENDED ACOUSTICALCEILING TO MATCH EXISTING

    DRAWN BY:

    CHECKED BY:

    DESIGN TYPE:

    DESIGN PHASE:

    DATE SUBMITTED:

    PROJECT:

    DRAWING TITLE:

    DESIGN SIZE:

    EXCHANGE

    SCALE: SHEET:

    Ar c

    h itec

    t s W

    est

    210 E

    ast Lakesid

    e A

    venue

    Coeur

    d'A

    lene, ID

    83814

    Ph: 208.6

    67.9

    402

    ww

    w.a

    rchitectw

    est.com

    Ar c

    hitectu

    r e Landscape A

    rchitect u

    re

    1/4" = 1'-0"

    DAVIS MONTHAN A.F.B.TUCSON, ARIZONA

    GTO/SB

    SJR

    CONSTRUCTION DOCUMENTS

    12/1/2015

    A2.01

    FLOOR AND CEILINGPLANS

    CONVERT BASKINROBBINS TOFRESHENS

    4085-15-000003

    1/4" = 1'-0"A2.012 FLOOR PLAN - DEMOLITION

    1/4" = 1'-0"A2.013 FLOOR PLAN

    1/4" = 1'-0"A2.014 REFLECTED CEILING PLAN

    Revision Schedule

    Revision #Revision

    Description Revision Date

  • 1719

    31

    18

    14 13

    16

    1215

    2223 21

    25 25

    24 20

    27 2826

    46

    4442 43

    45

    41

    18

    44

    29

    33 32

    61

    66

    63

    62

    67

    47 32 11

    48 4949 64

    50 50

    5152 5365

    30

    67

    67

    6869

    EQUIPMENT SCHEDULEMARK QTY DESCRIPTION MANUF / MODEL PROPRIETARY

    FRESHENS FRESH FOOD STUDIO EQUIPMENT11 1 FOOD GUARD WITH LIGHTING 16" TALL ENGLISH MFG M112A - 150.5" CC X12 1 HOT FOOD TABLE - PLATE SHELF-CUTTING BOARD EMI - TAMPA 48 X 38 X 36H X13 1 DROP IN HOT FOOD WARMER APW WYOTT HFWAT-3D14 1 72" MAGATOP REFRIGERATOR DELFIELD 4472N-30M X15 1 STAINLESS TABLE WITH PLATE SHELF, CUTTING BOARD EMI-TAMPA 22 X 38 X 36H X16 1 STAINLESS TABLE 48 X 36 X 36, OPEN BASE, CASTERS EMI-TAMPA X17 1 VENTLESS OVEN TURBO CHEF 2020T18 2 HOT HOLDING CABINET CAMBRO UPCH40019 1 72" MAGATOP REFRIGERATOR DELFIELD 4472N-30M X20 2 STAINLESS WALL SHELF, 15X72 ADVNACE TABCO WS-15-7221 1 STAINLESS WARMER TABLE, 16 X 48 X 36 EMI - TAMPA X22 1 STAINLESS CREPE IRON TABLE, 22 X 48 X 29.5 EMI - TAMPA X23 1 DROP IN 4 / 3 WARMER APW WYOTT HFW-43 X24 1 MICROWAVE PANASONIC NE-105425 2 CREPE IRON KRAMPOUZ CEBIF4 X26 1 CONVECTION STEAMER, STAND MARKET FORGE ALTAIR II-627 1 STEAM CONDENSER HOOD MARKET FORGE VEGA HOOD28 1 BLAST CHILLER DELFIELD CONVOCHILL T529 1 BLENDER HAMILTON BEACH HBF600 X30 1 STAINLESS SHELF ADVANCE TABCO MS-18-2431 1 STAINLESS CUP SHELF ADVANCE TABCO WS-10-2432 1 POS SYSTEM WITH SCALE FOR YOGURT EXISTING OR BY OTHERS33 1 HAND SINK ADVANCE 7-PS-60

    SMOOTHIE AND YOGURT EQUIPMENT41 1 STAINLESS TABLE, LOUVER DOORS, SPLASH EMI - TAMPA 32 X 78 X 36 X42 1 REFRIGERATED COLD PAN ATLAS WCMD-C-3 X43 1 ICE CADDIE CAMBRO44 2 BLENDERS HAMILTON BEACH HBF650-FR X45 1 RINSE SINK ADVANCE TABCO DI-1-1046 1 BLENDER RINSER HAMILTON BEACH BCR-10047 1 DIPPERWELL CECILWARE48 2 YOGURT MACHINE SURROUNDS EMI - TAMPA X49 2 YOGURT MACHINE FLAVOR MENU WINDOWS EMI - TAMPA X50 2 SOFT SERVE MACHINES TAYLOR 71351 1 TOPPINGS GUARD ENGLISH M-125, 54" CC X52 1 REFRIGERATED TOPPINGS PAN ATLAS WCM-C-153 1 DRY TOPPINGS PAN ATLAS WIC-1

    SIGN - MENU - GRAPHICS61 4 46-INCH DIGITAL MENU SYSTEM ALLURE GLOBAL X62 1 NUTRITIONAL TOUCH SCREEN ALLURE GLOBAL X63 2 DIGITAL MEDIA PLAYERS ALLURE GLOBAL X64 1 YOGURT MENU 20.5 X 33 SINTRA ON STANDOFFS FRESHENS X65 SET YOGURT FLAVOR DURATRANS FRESHENS X66 44 SF COUNTER GRAPHICS FRESHENS GRAPHIC COMPANY X67 275 SF WALL GRAPHICS FRESHENS GRAPHIC COMPANY X68 1 ILLUMINATED STOREFRONT SIGN, WALL MOUNTED MARIETTA SIGNS X69 1 STOREFRONT YOGURT SIGN, WALL MOUNTED MARIETTA SIGNS X

    9'-0

    "

    6'-0

    "

    6'-3

    "1'

    -6"

    (2) 48" LED STRIP LIGHTSON BULKHEAD

    9'-0

    "

    8'-6

    "

    MINIMUM STORAGE REQUIREMENTSCONVENIENT TO LOCATION:200 CU FT REFRIGERATOR100 CU FT FREEZER150 CU FT DRY STORAGE

    REMOVE PORTION OFEXISTING CEILING

    NEW SOFFIT 3 5/8" METAL STUDSWITH 5/8" GYP. BD. EACH SIDE

    REMOVE PORTION OFEXISTING CEILING

    NEW SOFFIT 3 5/8" METAL STUDSWITH 5/8" GYP. BD. EACH SIDE

    ADJUST HEIGHT OF EXIST.SOFFIT TO 9'-0"

    EXISTING

    EXISTING

    1'-6" 5"

    1/4" = 1'-0"A2.023 EQUIPMENT PLAN

    1/2" = 1'-0"A2.01 A2.021 SECTION

    1/2" = 1'-0"A2.01 A2.022 SECTION

    DRAWN BY:

    CHECKED BY:

    DESIGN TYPE:

    DESIGN PHASE:

    DATE SUBMITTED:

    PROJECT:

    DRAWING TITLE:

    DESIGN SIZE:

    EXCHANGE

    SCALE: SHEET:

    Ar c

    h itec

    t s W

    est

    210 E

    ast Lakesid

    e A

    venue

    Coeur

    d'A

    lene, ID

    83814

    Ph: 208.6

    67.9

    402

    ww

    w.a

    rchitectw

    est.com

    Ar c

    hitectu

    r e Landscape A

    rchitect u

    re

    As indicated

    DAVIS MONTHAN A.F.B.TUCSON, ARIZONA

    GTO/SB

    SJR

    CONSTRUCTION DOCUMENTS

    12/1/2015

    A2.02

    EQUIPMENT PLAN

    CONVERT BASKINROBBINS TOFRESHENS

    4085-15-000003

    Revision Schedule

    Revision #Revision

    Description Revision Date

  • YOGURT

    9'-0

    "

    COUNTER FURNISHED AND INSTALLED BY GC, SEE DETAILS PAGE 21-23VINYL GRAPHICS FURNISHED AND INSTALLED BY FRESHENS GRAPHICS COMPANY

    6" STAINLESS BASE

    8'-6

    "

    9'-0

    "

    3'-0

    "

    6'-3

    "1'

    -6" PAINT SHERWIN WILLIAMS 6904 GUSTO GOLD

    PAINT WHITE

    6'-0

    "

    YOGURT MENU

    3'-0

    "

    9'-0

    "

    6" STAINLESS BASE

    WHITE SEMI-GLOSS PAINTSHERWIN WILLIAMS 7005 PURE WHITE

    NUTRITIONAL TOUCH SCREENFURNISHED AND INSTALLED BYALLURE GLOBAL

    WHITE SEMI-GLOSS PAINTSHERWIN WILLIAMS 7005 PURE WHITE

    2'-1

    0"

    6'-6

    "

    3'-6

    "

    8'-6

    "

    9'-0

    "

    WHITE FRPWAINSCOTT

    DIGITAL MENU, FURNISHEDAND INSTALLED BYALLURE GLOBAL

    WHITE SEMI-GLOSS PAINTSHERWIN WILLIAMS 7005 PURE WHITELAST COAT AND TOUCH UP MINIMUM72 HOURS PRIOR TO GRAPHIC INSTALL

    PAINTWHITE

    6'-6

    "8'-0

    "

    WHITE SEMI-GLOSS PAINTSHERWIN WILLIAMS 7005 PURE WHITELAST COAT AND TOUCH UP MINIMUM72 HOURS PRIOR TO GRAPHIC INSTALL

    DIGITAL MENU, FURNISHEDAND INSTALLED BYALLURE GLOBAL

    WHITE FRPWAINSCOTT

    3'-6

    "

    6'-6

    "

    8'-6

    "

    3'-0

    "

    9'-0

    "

    WHITE SEMI-GLOSS PAINTSHERWIN WILLIAMS 7005 PURE WHITELAST COAT AND TOUCH UP MINIMUM72 HOURS PRIOR TO GRAPHIC INSTALL

    DIGITAL MENU, FURNISHEDAND INSTALLED BYALLURE GLOBAL

    WHITE FRPWAINSCOTT WHITE FRP

    WAINSCOTT

    H.M. DOOR AND FRAME.PAINT WHITE

    CERAMIC TILE BASE TOMATCH EXISTING

    CERAMIC TILE BASE TO MATCH EXISTING

    PAINTWHITE

    CERAMIC TILE BASE TO MATCH EXISTING

    H.M. DOOR ANDFRAME. PAINTWHITE

    PAINT WHITE

    PAINT GUSTO GOLD

    DRAWN BY:

    CHECKED BY:

    DESIGN TYPE:

    DESIGN PHASE:

    DATE SUBMITTED:

    PROJECT:

    DRAWING TITLE:

    DESIGN SIZE:

    EXCHANGE

    SCALE: SHEET:

    Ar c

    h itec

    t s W

    est

    210 E

    ast Lakesid

    e A

    venue

    Coeur

    d'A

    lene, ID

    83814

    Ph: 208.6

    67.9

    402

    ww

    w.a

    rchitectw

    est.com

    Ar c

    hitectu

    r e Landscape A

    rchitect u

    re

    1/2" = 1'-0"

    DAVIS MONTHAN A.F.B.TUCSON, ARIZONA

    GTO/SB

    SJR

    CONSTRUCTION DOCUMENTS

    12/1/2015

    A2.03

    INTERIOR ELEVATIONS

    CONVERT BASKINROBBINS TOFRESHENS

    4085-15-000003

    1/2" = 1'-0"A2.01 A2.031 STOREFRONT ELEVATION

    1/2" = 1'-0"A2.01 A2.032 STOREFRONT SIDE ELEVATION

    1/2" = 1'-0"A2.01 A2.033 NORTH ELEVATION

    1/2" = 1'-0"A2.01 A2.034 EAST ELEVATION

    1/2" = 1'-0"A2.01 A2.035 SOUTH ELEVATION

    Revision Schedule

    Revision #Revision

    Description Revision Date

  • PLUMBING SCHEDULE

    MARK QTY DESCRIPTION MANUF / MODEL PLUMBING

    13 1 DROP IN HOT FOODWARMER APW WYOTT HFWAT-3DDRAIN WITH ACCESSIBLE VALVE TO EMPTY AT NIGHT, INSTALL DRAIN ANDMANIFOLD WITH REAR EXTENSION.

    23 1 DROP IN 4 / 3 WARMER APW WYOTT HFW-43 DRAIN WITH ACCESSIBLE VALVE TO EMPTY AT NIGHT

    26 1 CONVECTION STEAMER ALTAIR II-6 COLD WATER, INDIRECT DRAIN TO FLOOR SINK WITH AIR GAP

    27 1 CONDENSER FOR STEAMER VEGA INDIRECT WASTE TO FLOOR SINK WITH AIR GAP (INSTALL SEPARATE FROMSTEAMER DRAIN)

    33 1 HAND SINK ADVANCE TABCO 7-PS-60 DRAIN TO FLOOR SINK WITH AIR GAP, HOT AND COLD WATER, MIXING VALVE IFREQUIRED TO PROVIDE SAFE TEMP FOR HAND WASHING.

    41 1 REFRIGERATED COLD PAN ATLAS WCMD-C-3 DRAIN WITH ACCESSIBLE VALVE FOR PERIODIC CLEANING

    45 1 RINSE SINK ADVANCT TABCO DI-1-10 COLD AND HOT WATER, INDIRECT WASTE TO FLOOR SINK WITH AIR GAP

    46 1 BLENDER RINSER HAMILTON BEACH BCR-100 COLD WATER ON APPROVED BACK FLOW PREVENTOR

    47 1 DIPPERWELL CECILWARE COLD WATER, INDIRECT WASTE TO FLOOR SINK WITH AIR GAP

    52 1 REFRIGERATEC COLD PAN ATLAS WCM-C-1 INDIRECT DRAIN TO FLOOR SINK WITH AIR GAP

    13

    23

    27 26

    46

    42

    4533 47

    52

    10'-0

    "

    REPLACE FLOOR DRAINWITH FLOOR SINK

    REPLACE FLOOR DRAINWITH FLOOR SINKEXTEND TO WORK RM

    ELECTRICAL SCHEDULEMARK DESCRIPTION MANUF / MODEL ELECTRICAL HEIGHT NOTES

    11 FOOD GUARD LIGHTING ENGLISH MFG 120 VOLT, 6 AMP 16" REFER TO LIGHTING PLAN

    13 DROP IN HOT FOOD WARMER APW WYOTT HFWAT-3D 208 VOLT, 2.55 KW, 12.3 AMPS 16" L6-20P

    14 72" MAGATOP REFRIGERATOR DELFIELD 4472N-30M 115 VOLT, 12 AMPS 16"

    17 VENTLESS OVEN TURBO CHEF 2020T 208 VOLT, 3 PH, 40 AMPS 48" NEMA 15-50P, 50 AMPBREAKER18 HOT HOLDING CABINET CAMBRO UPCH400 120 VOLT, 2.0 AMPS 16"18 HOT HOLDING CABINET CAMBRO UPCH400 120 VOLT, 2.0 AMPS 16"

    19 72" MAGATOP REFRIGERATOR DELFIELD 4472N-30M 115 VOLT, 12 AMPS 16"

    23 DROP IN 4 / 3 WARMER APW WYOTT HFW-43 120 VOLT, 1800 WATTS 16"24 MICROWAVE PANASONIC NE-1054 120 VOLT 1200 WATTS 16"25 CREPE IRON KRAMPOUZ CEBIF4 208 VOLT, 1 PH, 3.6 KW 16"25 CREPE IRON KRAMPOUZ CEBIF4 208 VOLT, 1 PH, 3.6 KW 16"

    26 CONVECTION STEAMER ALTAIR II-6 208 VOLT, 1 PH, 47.1 AMPS, 8.8KW 48"

    27 CONDENSER FOR STEAMER VEGA 120 VOLT, 6 AMPS 72"

    28 BLAST CHILLER DELFIELD CONVOCHILL T5 208 VOLT, 1PH, 10 AMPS 48"

    29 BLENDER HAMILTON BEACH HBF600 120 VOLT, 13 AMPS 48"

    41 REFRIGERATED COLD PAN ATLAS WCMD-C-3 120 VOLT, 3.9 AMPS 16"

    44 BLENDER HAMILTON BEACH 120 VOLT, 10 AMPS 48"44 BLENDER HAMILTON BEACH 120 VOLT, 10 AMPS 48"

    50 SOFT SERVE MACHINE TAYLOR 713 208 VOLT 1 PH 2P 3W, 25 AMPS 16"

    50 SOFT SERVE MACHINE TAYLOR 713 208 VOLT 1 PH 2P 3W, 23 AMPS 16"

    50 SOFT SERVE MACHINE TAYLOR 713 208 VOLT 1 PH 2P 3W, 25 AMPS 16"

    50 SOFT SERVE MACHINE TAYLOR 713 208 VOLT 1 PH 2P 3W, 23 AMPS 16"

    51 TOPPINGS GUARD LIGHTING ENGLISH M-125, 54" CC 120 VOLT, 6 AMP 16"

    52 REFRIGERATED TOPPINGS PAN ATLAS WCM-C-1 120 VOLT, 2.4 AMPS 16"

    33 POS SYSTEM TBD 120 VOLT, 6 AMPS 16"61 DIGITAL MENU SYSTEM ALLURE DIGITAL

    120 VOLT, 15 AMPS TOTAL

    96" PROVIDE UPS BACK UPPOWER SUPPLY AND SURGEPROTECTION

    62 NUTRITIONAL TOUCH SCREEN ALLURE DIGITAL 36"

    63 MEDIA PLAYERS ALLURE DIGITAL 84"

    68 STOREFRONT SIGN MARIETTA SIGN 120 VOLT, 10 AMPS CLG ON TIME CLOCK OR SWITCH

    69 STOREFRONT SIGN MARIETTA SIGN 120 VOLT, 10 AMPS CLG ON TIME CLOCK OR SWITCH

    F FUTURE EQUIPMENT TBD 120 VOLT, 15 AMPS

    T

    TT

    1719 18

    14 13

    23 25 2524

    27 2826

    4442

    18

    44

    29

    32

    61

    63

    6211

    50 50

    51526869

    5050

    61

    11F

    UNDERCOUNTER LIGHTS, CSL INVLED-4-NW, 4000K - 17 FTFURNISHED AND INSTALLED BY GC ELEC. CONTR.

    61

    62

    63

    (4) 46" LED MONITORS

    DIGITAL MENU WIRING SCHEMATIC

    DUPLEXRECEPTACLE

    MEDIA PLAYERS INSTALLEDON SHELF HIGH ON WALLSEE EQUIPMENT PLANFOR LOCATION

    LED MONITORS, MEDIA PLAYER AND DIGITAL CABLEFURNISHED AND INSTALLED BY ALLURE GLOBALELECTRICAL BY GC ELECTRICAL CONTRACTOR

    DUPLEXRECEPTACLE

    NUTRITIONALTOUCH SCREEN

    DUPLEXRECEPTACLE

    DUPLEXRECEPTACLE

    DRAWN BY:

    CHECKED BY:

    DESIGN TYPE:

    DESIGN PHASE:

    DATE SUBMITTED:

    PROJECT:

    DRAWING TITLE:

    DESIGN SIZE:

    EXCHANGE

    SCALE: SHEET:

    Ar c

    h itec

    t s W

    est

    210 E

    ast Lakesid

    e A

    venue

    Coeur

    d'A

    lene, ID

    83814

    Ph: 208.6

    67.9

    402

    ww

    w.a

    rchitectw

    est.com

    Ar c

    hitectu

    r e Landscape A

    rchitect u

    re

    As indicated

    DAVIS MONTHAN A.F.B.TUCSON, ARIZONA

    SB

    SJR

    CONSTRUCTION DOCUMENTS

    12/1/2015

    A3.01

    PLUMBING ANDELECTRICAL PLANS

    CONVERT BASKINROBBINS TOFRESHENS

    4085-15-000003

    1/4" = 1'-0"A3.011 PLUMBING PLAN

    1/4" = 1'-0"A3.012 ELECTRICAL PLAN

    1/2" = 1'-0"A3.013 DIGITAL MENU WIRING

    Revision Schedule

    Revision #Revision

    Description Revision Date

  • 36383/4 5

    1551/2

    81/4 24 24 81/4

    1451/2 5

    191 / 4

    2541

    / 4

    36641/2

    1222

    1 / 2

    32

    1224

    12

    633/4 36 61/2 144 61/2

    191 / 4

    291 / 4

    32

    42

    157

    13

    421/2 2141/4

    391/2

    12

    6 221/2 3 221/2

    43/ 4

    141 / 2

    43/ 4

    9

    3

    2563/4

    2563/4

    3/4

    163 / 4

    163 / 4 31/43

    1/4

    10

    3

    366

    VARIES

    23/ 4

    11/ 2

    34

    4

    30

    10

    221/2 12

    8

    181 / 4

    121/4

    R11/ 4

    �51

    / 2

    6

    43/ 4

    � 7/8

    24

    B

    A

    B

    A

    COUNTERTOP PLANGLACIER WHITE CORIANFURNISHED AND INSTALLED BY GC

    + 36" AFF

    + 34" AFF

    6" TURN DOWN

    BASE CABINET PLANWHITE LAMINATE ALL SURFACESFURNISHED AND INSTALLED BY GC

    1-1/2" TURN DOWN

    1 116" DIA HOLE FORSNEEZE GUARD LIGHTS

    1 116" DIA HOLE FORSNEEZE GUARD LIGHTS

    PROVIDE ACCESS PANELS FORELECTRICAL WIRING AND

    FOOD GUARD LIGHTING BALLASTS

    + 30

    " AFF

    4" TURN DOWN

    1-1/2" TURN DOWN

    8" SPLASH

    8" S

    PLAS

    H

    OPEN END FORVENTILATION

    OPEN TO FLOOR(NO BASECABINET)

    UNDERCOUNTER LED STRIP,REFER TO ELECTRICAL PLANFURNISHED AND INSTALLEDBYELECTRICAL CONTRACTORWHITE LAMINATE, FLUSH SEAMSVINYL GRAPHICS FURNISHEDAND INSTALLED BY FRESHENS

    6" STAINLESSCOVE BASEFURNISHED ANDINSTALLED BY GC

    PROVIDE ACCESSPANELS

    AND WIRINGCHASE FOR

    ELECTRICIAN

    GLACIER WHITECORIANEASED EDGES

    1 116" DIA HOLE FORSNEEZE GUARD LIGHTS

    10" TURN DOWN

    4" TURN DOWN

    DRAWN BY:

    CHECKED BY:

    DESIGN TYPE:

    DESIGN PHASE:

    DATE SUBMITTED:

    PROJECT:

    DRAWING TITLE:

    DESIGN SIZE:

    EXCHANGE

    SCALE: SHEET:

    Ar c

    h itec

    t s W

    est

    210 E

    ast Lakesid

    e A

    venue

    Coeur

    d'A

    lene, ID

    83814

    Ph: 208.6

    67.9

    402

    ww

    w.a

    rchitectw

    est.com

    Ar c

    hitectu

    r e Landscape A

    rchitect u

    re

    3/4" = 1'-0"

    DAVIS MONTHAN A.F.B.TUCSON, ARIZONA

    SB

    SJR

    CONSTRUCTION DOCUMENTS

    12/1/2015

    A4.01

    CASEWORK PLANSAND DETAILS

    CONVERT BASKINROBBINS TOFRESHENS

    4085-15-000003

    Revision Schedule

    Revision #Revision

    Description Revision Date

  • 1501/2

    18

    16

    20

    16

    145/8

    149 / 1

    6

    2016

    636

    78

    42

    221 / 2

    24

    366

    51/ 2

    8

    108

    61/2 27 3 27 61/2

    606

    366

    30

    108

    3060

    636

    6

    131/4

    71/2

    3

    53/4

    5410

    71/ 4

    61/2 27 3 27 61/2

    131 / 4 71

    / 2 11/ 2

    53/ 4

    11

    41

    51

    48 FOOD GUARDENGLISH MFG M112A FURNISHED BY FRESHENS INSTALLED BY GC

    (2) END POSTS COMPLETE WITH GLASS END PANELS AND ELECTRICAL FEEDS

    (3) INTERMEDIATE POSTS

    LED LIGHTING

    3/ 8 TEMPERED GLASS FRONT AND TOP

    1/ 4" TEMPERED GLASS END PANELS

    (3) INTERMEDIATE POSTS

    LEDLIGHTING

    (2) END POSTS

    TEMPERED GLASSEND PANEL

    WITH POLISHED EDGES

    PLAN VIEW

    FRONT VIEW

    LEG BRACEBACK AND SIDE

    SPLASH BACK AND LEFT END

    STAINLESS SMOOTHIE TABLEFABRICATED BY EMI - TAMPAFURNISHED BY MATTINGLY, INSTALLED BY GC

    LOUVER DOORS

    OPEN FORICE CADDIE

    COLD PANCUTOUT

    TOPPINGS GUARDENGLISH MFG M112A FURNISHED BY FRESHENS INSTALLED BY GC

    RIGHT END POSTS WITH GLASS END PANEL AND ELECTRICAL FEED

    LEFT END POST WITHIN 3" OF WALL (NO END PANEL REQD)

    LED LIGHTING

    3/ 8 TEMPERED GLASS FRONT AND TOP

    1/ 4" TEMPERED END PANELS

    PLAN VIEW

    FRONT VIEW

    ELECTRICAL FEEDTHIS POST

    ELECTRICALFEED

    THIS POSTRIGHT END

    NO END PANELTHIS SIDE

    WITHIN 3" OF WALL

    YOGURT MACHINE SURROUNDFURNISHED BY EMI - ALPHARETTA, ASSEMBLY AND INSTALL BY GC

    EMI SHALL SUBMIT SHOP DRAWINGS FOR APPROVAL PRIOR TO FABRICATION

    ALL SURFACES ARBORITE HPL P-258 CA TATAMI KURIMU WITH MATCHING PVC EDGEBANDING

    (2) STANDARD MENU WINDOWS, WHITE PAINTED FINISH

    STAINLESS COVE BASE FURNISHED AND INSTALLED BY GC

    FRONT VIEW SECTION

    PLAN VIEW

    DRAWN BY:

    CHECKED BY:

    DESIGN TYPE:

    DESIGN PHASE:

    DATE SUBMITTED:

    PROJECT:

    DRAWING TITLE:

    DESIGN SIZE:

    EXCHANGE

    SCALE: SHEET:

    Ar c

    h itec

    t s W

    est

    210 E

    ast Lakesid

    e A

    venue

    Coeur

    d'A

    lene, ID

    83814

    Ph: 208.6

    67.9

    402

    ww

    w.a

    rchitectw

    est.com

    Ar c

    hitectu

    r e Landscape A

    rchitect u

    re

    1/2" = 1'-0"

    DAVIS MONTHAN A.F.B.TUCSON, ARIZONA

    SB

    SJR

    CONSTRUCTION DOCUMENTS

    12/1/2015

    A4.02

    EQUIPMENT DETAILS

    CONVERT BASKINROBBINS TOFRESHENS

    4085-15-000003

    Revision Schedule

    Revision #Revision

    Description Revision Date

  • YOGURT

    921

    / 4 191

    / 2

    933/4

    727/16

    48

    82 1

    75/ 1

    6

    5613/16

    303 / 4

    68

    67

    66 69STOREFRONT SIGNILLUMINATED CHANNEL LETTERSFURNISHED BY FRESHENS, INSTALLED BY GCREFER TO ELEVATIONDIMENSIONS ARE APPROXIMATE, ACTUAL MIGHT VERY

    PEPPER

    WALL GRAPHICSAPPROX 275 SF

    LETTUCE

    FURNISHED AND INSTALLED BY FRESHENS GRAPHICS COMPANY GC TO FIELD VERIFY WALL DIMENSIONS GRAPHICS COMPANY TO PROVIDE SHOP DRAWING FOR APPROVAL PRIOR TO PRINTING REFER TO RENDERING FOR PLACEMENT OF GRAPHIC ELEMENTS

    COUNTER GRAPHICSAPPROX 44 SF

    FURNISHED AND INSTALLED BY FRESHENS GRAPHICS COMPANY GC TO FIELD VERIFY DIMENSIONS GRAPHICS COMPANY TO PROVIDE SHOP DRAWING FOR APPROVAL PRIOR TO PRINTING

    2'-0

    "

    4'-0

    "

    40'-5"

    5'-4" 29'-11" 3'-4" 2'-3"

    5"

    2'-6

    "5'

    -0"

    3'-8

    "

    3'-6

    "

    STRAWBERRY STRAWBERRYORANGE

    YOGURT SIGNILLUMINATED CHANNEL LETTERSFURNISHED BY FRESHENS, INSTALLED BY GCREFER TO ELEVATIONDIMENSIONS ARE APPROXIMATE, ACTUAL MIGHT VERY

    21'-71/4"

    12'-111/2"

    21/2"

    3'-91/2"2'-0"2'-0"

    73/4"

    DRAWN BY:

    CHECKED BY:

    DESIGN TYPE:

    DESIGN PHASE:

    DATE SUBMITTED:

    PROJECT:

    DRAWING TITLE:

    DESIGN SIZE:

    EXCHANGE

    SCALE: SHEET:

    Ar c

    h itec

    t s W

    est

    210 E

    ast Lakesid

    e A

    venue

    Coeur

    d'A

    lene, ID

    83814

    Ph: 208.6

    67.9

    402

    ww

    w.a

    rchitectw

    est.com

    Ar c

    hitectu

    r e Landscape A

    rchitect u

    re

    1/2" = 1'-0"

    DAVIS MONTHAN A.F.B.TUCSON, ARIZONA

    SB

    SJR

    CONSTRUCTION DOCUMENTS

    12/1/2015

    A4.03

    GRAPHICS DETAILS

    CONVERT BASKINROBBINS TOFRESHENS

    4085-15-000003

    Revision Schedule

    Revision #Revision

    Description Revision Date

  • E0.01 GENERAL NOTES, ABBREVIATIONS AND LEGENDS

    ED.01 DEMOLITION PLAN

    E0.11 ONE-LINE DIAGRAMS

    E0.12 PANEL SCHEDULES

    E0.13 PANEL SCHEDULES

    E1.00 ELECTRICAL SITE PLAN

    E1.11 POWER AND SPECIAL SYSTEMS PLAN

    S H E E T I N D E X

    1. "GENERAL NOTES" APPLY TO ALL DRAWINGS. "SHEET NOTES"

    APPLY TO ALL OF THE SHEETS ON WHICH THEY OCCUR.

    "KEYNOTES" APPLY ONLY WHERE CALLED OUT.

    2. ALL EQUIPMENT SHOWN IN BOLD IS TO BE PROVIDED AND

    INSTALLED BY CONTRACTOR UNLESS OTHERWISE NOTED.

    3. CONTRACTOR SHALL PROVIDE CONDUIT AND WIRE FROM ALL

    CONTROL DEVICES TO LUMINAIRES FOR CONTROL OF

    LUMINAIRES SHOWN.

    4. LUMINAIRES SHOWN ON DRAWINGS FOR QUANTITY AND

    CIRCUITING ONLY. SEE ARCHITECTURAL DRAWINGS FOR EXACT

    LOCATIONS.

    5. ALL FEEDERS AND BRANCH CIRCUITS SHALL CONTAIN AN

    EQUIPMENT GROUND CONDUCTOR SIZED PER NEC TABLE

    250.122.

    6. ALL BRANCH CIRCUITS SHALL BE 3/4"C, (2)#12, #12G UNLESS

    OTHERWISE NOTED. WHERE CONTRACTOR CHOOSES TO RUN

    MORE THAN THREE CURRENT CARRYING CONDUCTORS WITHIN

    ONE RACEWAY OR CABLE, CONDUCTORS SHALL BE INCREASED IN

    SIZE TO COMPENSATE FOR THE DERATING REQUIRED PER NEC

    SECTION 310.15. CONDUCTOR AMPACITIES SHALL BE TAKEN

    7. WIRING FOR EMERGENCY LIGHTING CIRCUITS OR OTHER

    EMERGENCY EQUIPMENT SHALL BE KEPT ENTIRELY INDEPENDENT

    OF ALL OTHER WIRING AND EQUIPMENT AND SHALL MEET ALL

    REQUIREMENTS OF NEC SECTION 700.10.

    8. CONTRACTOR SHALL PROVIDE CONDUIT AND WIRE FOR ALL

    CIRCUITS SHOWN ON DRAWINGS.

    9. PROVIDE DEDICATED NEUTRALS FOR ALL CIRCUITS.

    10. SOME LEGEND SYMBOLS OR ABBREVIATIONS SHOWN IN

    LEGENDS ARE NOT USED ON THE FOLLOWING DRAWINGS.

    11. WHERE EQUIPMENT PART NUMBERS ARE SHOWN ON THESE

    PLANS THEY SHALL SUPERCEDE THE REQUIREMENTS OF THE

    SPECIFICATIONS.

    12. WHERE THE DRAWINGS AND SPECIFICATIONS CONFLICT, THE

    CONTRACTOR SHALL BID THE MORE COSTLY MATERIAL AND

    INSTALLATION. PRIOR TO ORDERING, THE CONTRACTOR SHALL

    NOTIFY THE ENGINEER OF THOSE DISCREPANCIES AND OBTAIN

    DIRECTION FROM THE ENGINEER.

    13. ALL CONDUITS SHALL BE CONCEALED UNLESS OTHERWISE

    NOTED.

    14. CONTRACTOR SHALL KEEP A FULL SIZE DRAWING SET ON SITE

    AND NOTE ALL DEVIATIONS TO THE CONSTRUCTION DRAWINGS

    AS WELL AS NOTE LOCATIONS OF CONDUIT RUNS (OR OTHER

    ITEMS) WHICH ARE NOT SHOWN ON THE CONSTRUCTION

    DRAWINGS. THESE DRAWINGS SHALL BE TRANSCRIBED UPON

    COMPLETION OF THE PROJECT ONTO A CLEAN SET AND BECOME

    THE PROJECT'S RECORD DRAWINGS. THEY SHALL BE TURNED

    OVER TO THE OWNER PRIOR TO FINAL PAYMENT.

    15. FACILITY IS A 24/7 OPERATION FACILITY. FACILITY SHALL BE IN

    OPERATION DURING CONSTRUCTION.

    16. ALL WORK SHALL BE STAGED TO PROVIDE AS MINIMAL

    DISRUPTION AS POSSIBLE.

    G E N E R A L N O T E S

    M

    ST

    M

    XXX/X

    AUTOMATIC TRANSFER SWITCH

    CIRCUIT BREAKER, NUMBER OF POLES, FRAME

    AND TRIP RATINGS AS INDICATED. (I.E. 60/3 =

    3-POLE, 60A)

    XXX/X

    FUSE, RATING AND TYPE AS INDICATED.

    (I.E. 60/3 = 3-POLE, 60A)

    XXX/X

    SWITCH, NUMBER OF POLES AND RATING AS

    INDICATED.

    (I.E. 60/3 = 3-POLE, 60A)

    TRANSFORMER, SIZE AS INDICATED. GROUND

    CONDUCTOR SIZES AS INDICATED ON

    TRANSFORMER SCHEDULE.

    GROUND. SEE DETAILS

    GROUND WELL, WITH GROUND ROD. SEE DETAILS

    MOTOR RATED SWITCH WITH THERMAL OVERLOAD

    PROTECTION

    DISCONNECT SWITCH WITHOUT FUSE. (30AF UON)

    DISCONNECT SWITCH WITH FUSE(S). (30AF UON)

    COMBINATION STARTER WITH SWITCH, FUSE(S),

    CONTRACTOR AND THERMAL OVERLOAD

    PROTECTION.

    JUNCTION BOXJ

    CONCEALED CONDUIT OR CONDUCTOR

    EQUIPMENT TO BE REMOVED

    CONDUIT CAPPED

    SHUNT TRIP PUSHBUTTON OR KEY-SWITCH

    PANELBOARD, SWITCHBOARD, OR

    SWITCHGEAR. DASHED BOX INDICATES CODE

    REQUIRED WORKING CLEARANCE.

    ENCLOSURE/CABINET

    METER

    ELECTRIC MOTOR

    GENERATOR REMOTE ANNUNCIATORA

    HARDWIRED CONNECTION

    K

    M

    I

    INTERCOM/ACCESS CONTROL DOOR STATION

    A = AUDIO ONLY M = MASTER STATION

    V = AUDIO/VIDEO

    D

    W

    DE

    C

    P

    ES

    DH

    D

    ML

    OD

    CARD SWIPE

    DELAY EGRESS LOCK

    DOOR CONTACT

    DURESS PUSH BUTTON

    ELECTRIC STRIKE

    KEYPAD W = WEATHERPROOF

    MAGNETIC DOOR HOLD (SECURITY)

    MAGNETIC LOCK

    MOTION DETECTOR

    OVERHEAD DOOR CONTACT

    PROXIMITY DETECTOR

    PROXIMITY CARD READER

    REQUEST TO EXIT

    IP SECURITY CAMERA. CONTRACTOR TO PROVIDE

    JUNCTION BOX AND 3/4" CONDUIT WITH NYLON PULL

    STRING TO ACCESSIBLE CEILING SPACE.

    PTZ = PAN TILT ZOOM

    NOT SHADED = INDOOR

    SHADED = OUTDOOR

    W

    WINDOW CONTACT

    A

    R

    SIREN

    S

    A

    ACCESS CONTROL PANEL

    PTZ

    PTZ

    GLASS BREAK DETECTOR

    G

    SPECIAL PURPOSE RECEPTACLE, RATING AS

    INDICATED

    STANDARD RECEPTACLES: 125V, 20A 18"

    AFF, UON. TYPES: SIMPLEX /DUPLEX

    /QUADRUPLEX /FLOOR DUPLEX /FLOOR

    QUADRUPLEX

    GFCI RECEPTACLES: 125V, 20A 18" AFF,

    UON. TYPES: SIMPLEX /DUPLEX

    /QUADRUPLEX /FLOOR DUPLEX /FLOOR

    QUADRUPLEX

    CCEILING MOUNTED

    IISOLATED GROUND

    WWEATHER PROOF WHILE IN USE

    aLOWER CASE LETTER INDICATES SWITCH CONTROL

    2"

    MEASUREMENT INDICATES HEIGHT ABOVE

    BACKSPLASH/MILLWORK

    TTAMPER RESISTANT

    SHALF SWITCHED

    A

    INDICATES MOUNT ABOVE BACKSPLASH/MILLWORK.

    COORDINATE HEIGHT WITH TRADES.

    P O W E R

    TTHERMOSTAT

    C

    C

    PULL STATION WITH CLEAR PLASTIC COVERF

    DUCT SMOKE DETECTORS

    S SMOKE DETECTOR

    STROBE ONLY C = CEILING MOUNT W =

    WEATHERPROOF

    HORN AND STROBE C = CEILING MOUNT W =

    WEATHERPROOF

    W

    W

    R

    ADDRESSABLE RELAY

    A

    REMOTE ANNUNCIATOR

    K

    KITCHEN HOOD FIRE SUPPRESSION SYSTEM

    T

    FIRE SPRINKLER TAMPER SWITCH

    P

    PRESSURE SWITCH

    F

    FIRE SPRINKLER WATER FLOW SWITCH

    BWATER FLOW BELL

    KXKNOX BOX

    PC PULL CORD STATION

    D

    MAGNETIC DOOR HOLD (FIRE ALARM)

    HEAT DETECTOR

    M

    M/C

    FFH

    FFJ

    B

    T

    B

    R

    S ELEVATOR RECALL SMOKE DETECTOR

    EL

    NOTIFICATION APPLIANCE CIRCUIT POWER SUPPLY

    N

    POST INDICATOR VALVE

    V

    HORN ONLY C = CEILING MOUNT W =

    WEATHERPROOF

    C W

    BEAM DETECTOR TRANSMITTING DEVICE, MOUNTED

    ON WALL AT MAXIMUM HEIGHT BUT BELOW BOTTOM

    OF STRUCTURAL CEILING AND BELOW ANY

    PERMANENT OBSTRUCTIONS.

    BEAM DETECTOR RECEIVING DEVICE, MOUNTED ON

    WALL AT MAXIMUM HEIGHT BUT BELOW BOTTOM

    OF STRUCTURAL CEILING AND BELOW ANY

    PERMANENT OBSTRUCTIONS.

    FIREFIGHTER 2-WAY VOICE COMMUNICATION

    SYSTEM HANDSET STATION

    ADDRESSABLE MODULE M = MONITOR

    C = CONTROL

    FIREFIGHTER 2-WAY VOICE COMMUNICATION

    SYSTEM JACK

    "1"

    "a"

    "NL"

    "E"

    "a/E" INDICATES POWER TO SWITCHED EMERGENCY LIGHTING

    CONTAINED IN SAME AREA WHICH HAS BEEN PROVIDED

    WITH AUTOMATIC POWER TRANSFER DEVICE.

    INDICATES PANELBOARD AND CIRCUIT PROVIDING POWER

    TO SWITCHLEG INDICATED FOR LUMINAIRES CONTAINED

    IN SAME ROOM/AREA.

    INDICATES TYPE PER LIGHTING EQUIPMENT SCHEDULE.

    INDICATES NIGHT LIGHT LUMINAIRE.

    INDICATES CONTROL PER SWITCH.

    INDICATES POWER TO UNSWITCHED EMERGENCY

    LIGHTING CONTAINED IN SAME ROOM/AREA.

    1 E NL a

    PNL-4

    INDICATES CIRCUIT NUMBER.

    INDICATES POWER SOURCE."PNL"

    "4"

    ROOM CIRCUITING UNLESS OTHERWISE NOTED, ALL

    RECEPTACLES IN ROOM ARE TO BE CIRCUITED FROM THIS

    CIRCUIT.

    "PNL"INDICATES POWER SOURCE

    "X" INDICATES CIRCUIT NUMBER

    RECEPTACLE, TYPICAL:

    LIGHTING LUMINAIRE, TYPICAL:

    PNL-6, R1

    "6"

    "PNL"

    "R1"

    EQUIPMENT OR HOMERUN, TYPICAL:

    INDICATES POWER SOURCE.

    INDICATES CIRCUIT NUMBER.

    INDICATES RELAY NUMBER.

    X-Xa/E

    X-XE

    X-Xa

    PNL 04

    CS

    WAP

    TV

    WIRELESS ACCESS PORT; SEE SPECIAL SYSTEMS

    CONNECTION SCHEDULE.

    WALL MOUNTED SPEAKER/CLOCK COMBINATION

    CCLOCK

    S

    SPEAKER W = WEATHERPROOF

    CABLE TRAY

    TELEVISION OUTLET, 18" AFF UON. STUB 3/4" CO INTO

    ACCESSIBLE CEILING SPACE.

    RECESSED AUDIO FLOOR BACK BOX, OUTLET AND CONDUITA/V

    W

    WALL MOUNTED TELECOMMUNICATIONS OUTLET.

    T# - INDICATES TYPE/CONFIGURATION OF SERVICES AT

    OUTLET. REFER TO TELECOM SCHEDULE FOR SPECIFIC

    INFORMATION.

    T#

    FLOOR OR CEILING MOUNTED TELECOMMUNICATIONS OUTLET.

    T# - INDICATES TYPE/CONFIGURATION OF SERVICES AT

    OUTLET. REFER TO TELECOM SCHEDULE FOR SPECIFIC

    INFORMATION.

    T#

    SHORT THROW PROJECTOR. MOUNT AT 86" AFF.

    PNL X

    X-X

    AFC

    AFG

    AF

    AFF

    AIC

    AHJ

    ATS

    BP

    C

    CATV

    CB

    CIRCUITV

    CL

    CLG

    CO

    COMM

    CP

    DDC

    DP

    EAS

    ECS

    EM

    EMT

    ETR

    EW

    FAAP

    FACP

    FATC

    FCIO

    FOIC

    GFCI

    GFP

    GND

    GRS

    HTR

    IG

    IMC

    JBOX

    LCP

    LTG

    MCA

    MCC

    MDP

    MGAP

    MLO

    MOP

    MS

    MTD

    NCC

    NEC

    NIC

    NL

    NTS

    OC

    OH

    OS

    PIV

    POS

    PNL

    PVC

    R

    RCPT

    SAC

    SB,SWBD

    SG

    SPD

    TEL

    TJB

    TR

    TYP

    UON

    UL

    UG

    VD

    VFD

    WCR

    W

    XFMR

    AVAILABLE FAULT CURRENT

    ABOVE FINISHED GRADE

    AMP FRAME

    ABOVE FINISHED FLOOR

    AMPERE INTERRUPTING CAPACITY

    AUTHORITY HAVING JURISDICTION

    AUTOMATIC TRANSFER SWITCH

    BRANCH PANELBOARD

    CONDUIT OR CEILING

    CABLE TELEVISION

    CIRCUIT BREAKER

    CLOSED CIRCUIT TELEVISION

    CONNECTOR LIGHTING

    CEILING

    CONDUIT ONLY

    COMMUNICATIONS

    CHILD PROOF

    DIRECT DIGITAL CONTROLS

    DISTRIBUTION PANELBOARD

    ELECTRONIC ARTICLE SURVEILLANCE

    EQUIPMENT CONNECTION SCHEDULE

    EMERGENCY

    ELECTRICAL METALLIC TUBING

    EXISTING TO REMAIN

    EACH WAY

    FIRE ALARM ANNUNCIATOR PANEL

    FIRE ALARM CONTROL PANEL

    FIRE ALARM TERMINAL CABINET

    FURNISHED BY CONTRACTOR, INSTALLED

    BY OWNER

    FURNISHED BY OWNER, INSTALLED BY

    CONTRACTOR

    GROUND FAULT CIRCUIT INTERRUPTER

    GROUND FAULT PROTECTION

    GROUND

    GALVANIZED RIGID STEEL

    HEATER

    ISOLATED GROUND

    INTERMEDIATE METALLIC CONDUIT

    JUNCTION BOX

    LIGHTING CONTROL PANEL

    LIGHTING

    MINIMUM CIRCUIT AMPACITY

    MOTOR CONTROL CENTER

    MAIN DISTRIBUTION PANEL

    MEDICAL GAS ALARM PANEL

    MAIN LUGS ONLY

    MAXIMUM OVERCURRENT PROTECTION

    MOTOR STARTER

    MOUNTED

    NURSE CALL CONTROL CABINET

    NATIONAL ELECTRICAL CODE

    NOT IN CONTRACT

    NIGHT LIGHT

    NOT TO SCALE

    ON CENTER

    OVERHEAD

    OCCUPANCY SENSOR

    POST INDICATOR VALVE

    POINT OF SALES

    PANEL

    POLYVINYL CHLORIDE

    EXISTING TO BE REMOVED

    RECEPTACLE

    SMALL APPLIANCE CIRCUIT

    SWITCHBOARD

    SWITCHGEAR

    SURGE PROTECTIVE DEVICE

    TELEPHONE

    TELECOMMUNICATIONS J-BOX

    TAMPER RESISTANT

    TYPICAL

    UNLESS OTHERWISE NOTED

    UNDERWRITERS LABORATORIES

    UNDERGROUND

    VOLTAGE DROP

    VARIABLE FREQUENCY DRIVE

    WITHSTAND AND CLOSE RATING

    WEATHERPROOF (WHILE IN-USE)

    TRANSFORMER

    RECEPTACLES

    W I R I N G S U B S C R I P T

    S E C U R I T Y

    P PHOTOCELL

    LUMINAIRE CONTROLS

    SWITCH

    #

    NEW LUMINAIRE CONTROL. SEE LIGHTING

    CONTROL LEGEND LOCATED ON LIGHTING SHEETS.

    F I R E A L A R M C O M M U N I C A T I O N S

    HALF SHADED LUMINAIRES INDICATE IT IS AN

    EMERGENCY EGRESS LUMINAIRE AND IS TO BE

    PROVIDED WITH EMERGENCY BATTERY AS PER

    SPECIFICATION.

    CIRCUIT DESIGNATION

    CONDUIT SIZING

    UNLESS INDICATED OTHERWISE, CONDUIT AND CONDUCTORS SHALL

    BE SIZED AS SHOWN BELOW. MINIMUM CONDUIT IN EXTERIOR AND

    UNDERGROUND LOCATIONS TO BE 1". CONDUITS FROM LUMINAIRES

    TO LOCAL USER CONTROL DEVICES (SWITCHES, OCCUPANCY

    SENSORS, ETC.) MAY BE 1/2" OR AS INDICATED IN SPECIFICATIONS.

    PROVIDE ADDITIONAL CONDUCTOR FOR UNSWITCHED "HOT" TO

    LIGHTING LUMINAIRES WITH EMERGENCY POWER BATTERIES OR

    GENERATOR TRANSFER DEVICES.

    20A/1P AND 2P- 3/4"C.-2#12,#12G

    20A/3P- 3/4"C.-3#12,#12G

    30A/1P AND 2/P-3/4"C.-2#10,#10G

    30A/3P- 3/4"C.-3#10,#10G

    40A/3P- 3/4"C.-3#8,#10G

    L U M I N A I R E S

    PUSH BUTTON

    DOOR BELL CHIME

    INDOOR SERVICE POLE

    DC

    OS

    LIGHTING WITHIN ROOM CONTROLLED BY CEILING

    MOUNTED OCCUPANCY SENSORS. CONTRACTOR

    SHALL PROVIDE SHOP DRAWINGS OF OCCUPANCY

    SENSOR SYSTEM AS PER PROJECT SPECIFICATION

    AS PART OF THE SUBMITTAL PROCESS PRIOR TO

    COMMENCEMENT OF LABOR.

    DRAWN BY:

    CHECKED BY:

    DESIGN TYPE:

    DESIGN PHASE:

    DATE SUBMITTED:

    PROJECT:

    DRAWING TITLE:

    DESIGN SIZE:

    SCALE: SHEET:

    Arc

    hite

    cts W

    est

    SEE PLANS

    TJB

    WJB

    CONSTRUCTION DOCUMENTS

    12/01/2015

    CONVERT BASKIN

    ROBBINS TO

    FRESHENS

    DAVIS MONTHAN A.F.B.

    TUCSON, ARIZONA

    Revision Schedule

    Revision #

    Revision

    Description Revision Date

    1875 N. LAKEWOOD DRIVE, SUITE #201

    COEUR D'ALENE, IDAHO 83814

    (208) 676-8001 (208) 676-0100

    A

    ISSUED FOR

    REVIEW

    11.04.2015

    E0.01

    GENERAL

    NOTES,

    ABBREVIATIONS

    AND LEGENDS

  • FRESHENS

    a

    b

    C

    5

    L4CR

    L4CL

    ETR

    ETR

    ETR ETR

    DRAWN BY:

    CHECKED BY:

    DESIGN TYPE:

    DESIGN PHASE:

    DATE SUBMITTED:

    PROJECT:

    DRAWING TITLE:

    DESIGN SIZE:

    SCALE: SHEET:

    Arc

    hite

    cts W

    est

    SEE PLANS

    TJB

    WJB

    CONSTRUCTION DOCUMENTS

    12/01/2015

    CONVERT BASKIN

    ROBBINS TO

    FRESHENS

    DAVIS MONTHAN A.F.B.

    TUCSON, ARIZONA

    Revision Schedule

    Revision #

    Revision

    Description Revision Date

    1875 N. LAKEWOOD DRIVE, SUITE #201

    COEUR D'ALENE, IDAHO 83814

    (208) 676-8001 (208) 676-0100

    A

    ISSUED FOR

    REVIEW

    11.04.2015

    ED.01

    DEMOLITION PLAN

    1/2" = 1'-0"

    ED.01

    1DEMOLITION PLAN

    KEYNOTES

    DEMOLISH AND REMOVE INDICATED ELECTRICAL

    EQUIPMENT AND APPURTENANCES BACK TO

    PANEL L4CR.

    DEMOLISH AND REMOVE INDICATED ELECTRICAL

    EQUIPMENT AND APPURTENANCES BACK TO

    PANEL L4CL.

    1

    420

    SCALE IN FEET

    12

    2

    1

    2

    2

    2

  • DRAWN BY:

    CHECKED BY:

    DESIGN TYPE:

    DESIGN PHASE:

    DATE SUBMITTED:

    PROJECT:

    DRAWING TITLE:

    DESIGN SIZE:

    SCALE: SHEET:

    Arc

    hite

    cts W

    est

    SEE PLANS

    TJB

    WJB

    CONSTRUCTION DOCUMENTS

    12/01/2015

    CONVERT BASKIN

    ROBBINS TO

    FRESHENS

    DAVIS MONTHAN A.F.B.

    TUCSON, ARIZONA

    Revision Schedule

    Revision #

    Revision

    Description Revision Date

    1875 N. LAKEWOOD DRIVE, SUITE #201

    COEUR D'ALENE, IDAHO 83814

    (208) 676-8001 (208) 676-0100

    A

    ISSUED FOR

    REVIEW

    11.04.2015

    E0.11

    ONE-LINE

    DIAGRAM AND

    SCHEDULES

    EXISTING ELECTRICAL ONE-LINE DIAGRAM

    1

    -

    CONTINUED TO EXISTING PANELS

    NOT AFFECTED BY DESIGN

    CONTINUED TO EXISTING PANELS

    NOT AFFECTED BY DESIGN

    PANELBOARD

    "L4CR"

    PANELBOARD

    "L4CL"

    TRANSFORMER "T4"

    480/277:208/120v

    300 KVA

    500A

    600A

    CONTINUED TO EXISTING

    ELECTRICAL NOT AFFECTED BY

    DESIGN

    KEYNOTES

    ALL EXISTING PANELS, EQUIPMENT AND

    APPURTENANCES NOT SHOWN FOR CLARITY

    PURPOSES.

    INSTALL NEW (4) 4/O THHN COPPER WITH (1)

    #4 THHN COPPER GND IN (1) 2-1/2" C.

    INSTALL 225A/3P CIRCUIT BREAKER IN

    REMAINING SPACE FOR PANEL "L4CR". MATCH

    TYPE, MANUFACTURER, AND AIC RATING AS

    EXISTING BREAKERS.

    SEPARATE PANELBOARD "L4CL" AND "L4CR"

    BY REMOVING BUSSING CONDUCTORS FROM

    "L4CR" AND "L4CR". SEAL ALL

    PENETRATIONS.

    1

    1

    1

    1

    1

    PANELBOARD

    "L4"

    CONTINUED TO EXISTING

    ELECTRICAL NOT AFFECTED BY

    DESIGN

    NEW ELECTRICAL ONE-LINE DIAGRAM

    2

    -

    CONTINUED TO EXISTING PANELS

    NOT AFFECTED BY DESIGN

    CONTINUED TO EXISTING PANELS

    NOT AFFECTED BY DESIGN

    PANELBOARD

    "L4CR"

    PANELBOARD

    "L4CL"

    TRANSFORMER "T4"

    480/277:208/120v

    300 KVA

    500A

    600A

    CONTINUED TO EXISTING

    ELECTRICAL NOT AFFECTED BY

    DESIGN

    PANELBOARD

    "L4"

    CONTINUED TO EXISTING

    ELECTRICAL NOT AFFECTED BY

    DESIGN

    4

    2

    3

    2

    3

    4

  • DRAWN BY:

    CHECKED BY:

    DESIGN TYPE:

    DESIGN PHASE:

    DATE SUBMITTED:

    PROJECT:

    DRAWING TITLE:

    DESIGN SIZE:

    SCALE: SHEET:

    Arc

    hite

    cts W

    est

    SEE PLANS

    TJB

    WJB

    CONSTRUCTION DOCUMENTS

    12/01/2015

    CONVERT BASKIN

    ROBBINS TO

    FRESHENS

    DAVIS MONTHAN A.F.B.

    TUCSON, ARIZONA

    Revision Schedule

    Revision #

    Revision

    Description Revision Date

    1875 N. LAKEWOOD DRIVE, SUITE #201

    COEUR D'ALENE, IDAHO 83814

    (208) 676-8001 (208) 676-0100

    A

    ISSUED FOR

    REVIEW

    11.04.2015

    E0.12

    PANEL

    SCHEDULES

    KEYNOTES

    1

    1

    2

    2

  • DRAWN BY:

    CHECKED BY:

    DESIGN TYPE:

    DESIGN PHASE:

    DATE SUBMITTED:

    PROJECT:

    DRAWING TITLE:

    DESIGN SIZE:

    SCALE: SHEET:

    Arc

    hite

    cts W

    est

    SEE PLANS

    TJB

    WJB

    CONSTRUCTION DOCUMENTS

    12/01/2015

    CONVERT BASKIN

    ROBBINS TO

    FRESHENS

    DAVIS MONTHAN A.F.B.

    TUCSON, ARIZONA

    Revision Schedule

    Revision #

    Revision

    Description Revision Date

    1875 N. LAKEWOOD DRIVE, SUITE #201

    COEUR D'ALENE, IDAHO 83814

    (208) 676-8001 (208) 676-0100

    A

    ISSUED FOR

    REVIEW

    11.04.2015

    E0.13

    PANEL

    SCHEDULES

    KEYNOTES

    1

    2

    2

    2

    2

    11

    2

  • 1

    2

    3

    DRAWN BY:

    CHECKED BY:

    DESIGN TYPE:

    DESIGN PHASE:

    DATE SUBMITTED:

    PROJECT:

    DRAWING TITLE:

    DESIGN SIZE:

    SCALE: SHEET:

    Arc

    hite

    cts W

    est

    SEE PLANS

    TJB

    WJB

    CONSTRUCTION DOCUMENTS

    12/01/2015

    CONVERT BASKIN

    ROBBINS TO

    FRESHENS

    DAVIS MONTHAN A.F.B.

    TUCSON, ARIZONA

    Revision Schedule

    Revision #

    Revision

    Description Revision Date

    1875 N. LAKEWOOD DRIVE, SUITE #201

    COEUR D'ALENE, IDAHO 83814

    (208) 676-8001 (208) 676-0100

    A

    ISSUED FOR

    REVIEW

    11.04.2015

    E1.00

    ELECTRICAL

    SITE PLAN

    1/8" = 1'-0"

    E1.11

    1ELECTRICAL SITE PLAN

    KEYNOTES

    PROVIDE NEW 2-1/2" CONDUIT. ROUTE CONDUIT IN A NEAT AND WORKMAN LIKE

    MANNER AS DESCRIBED IN THE NEC. PROVIDE SUFFICIENT JUNCTION BOXES AS

    NEEDED FOR INSTALLATION. COORDINATE ANY POWER DISRUPTIONS WITH BASE

    AHEAD OF SCHEDULE. PROVIDE MINIMAL IMPACT ON OPERATION OF FACILITY.

    EXISTING IDF3, CONTRACTOR SHALL INSTALL (2) CAT 6 CABLES WITHIN CABLE

    TRAY AS MUCH AS POSSIBLE FROM IDF TO MEDIA PLAYERS. IN LOCATIONS WHERE

    CABLE TRAY IS NOT UTILIZED, CABLE SHALL BE INSTALLED WITH OTHER

    TELECOMMUNICATIONS CABLES PER BASE STANDARDS. COORDINATE

    TELECOMMUNICATIONS INSTALLATION WITH I.T. REPRESENTATIVE.

    INSTALL TELECOMMUNICATIONS JACKS AS CLOSE AS POSSIBLE TO MEDIA

    PLAYERS AS SHOWN ON SHEET E1.11.

    1

    L4

    8

    SCALE IN FEET

    4 0 8 16

    L4CLL4CR

    2

    3

    MDP

    43

    21 22

  • FRESHENS

    J J

    J

    JJ

    J

    J

    J

    J

    J

    J

    J

    1

    2

    3

    4

    5

    6

    7

    10

    11

    14

    15

    16

    17

    18

    20

    21

    22

    23

    24

    25

    26

    27

    28

    29

    30

    31

    32

    J

    GFCI 16" AFF

    GFCI 16" AFF

    GFCI 16" AFF

    GFCI 36" AFF

    16" AFF

    16" AFF

    CLG

    16" AFF

    16" AFF

    16" AFF

    8

    16" AFF

    9

    CLG

    12

    16" AFF

    13

    16" AFF

    GFCI 16" AFF

    GFCI 48" AFF

    GFCI 48" AFF

    48" AFF

    GFCI 72" AFF'

    48" AFF

    GFCI 16" AFF

    GFCI 48" AFF

    GFCI 84" AFF

    19

    GFCI 16"AFF

    16" AFF

    GFCI 16" AFF

    GFCI 16" AFF

    GFCI 84" AFF

    GFCI 16" AFF

    GFCI 84" AFF

    GFCI 16" AFF

    GFCI 48" AFF

    33

    35

    35

    34

    L4CL

    L4CR

    84" AFF

    84" AFF

    14" AFF

    DRAWN BY:

    CHECKED BY:

    DESIGN TYPE:

    DESIGN PHASE:

    DATE SUBMITTED:

    PROJECT:

    DRAWING TITLE:

    DESIGN SIZE:

    SCALE: SHEET:

    Arc

    hite

    cts W

    est

    SEE PLANS

    TJB

    WJB

    CONSTRUCTION DOCUMENTS

    12/01/2015

    CONVERT BASKIN

    ROBBINS TO

    FRESHENS

    DAVIS MONTHAN A.F.B.

    TUCSON, ARIZONA

    Revision Schedule

    Revision #

    Revision

    Description Revision Date

    1875 N. LAKEWOOD DRIVE, SUITE #201

    COEUR D'ALENE, IDAHO 83814

    (208) 676-8001 (208) 676-0100

    A

    ISSUED FOR

    REVIEW

    11.04.2015

    E1.11

    POWER AND

    SPECIAL

    SYSTEMS PLAN

    1/2" = 1'-0"

    E1.11

    1POWER PLAN

    KEYNOTES

    SOFT SERVE MACHINE. PROVIDE (2) #10 THHN COPPER WIRES, (1) #10 THHN

    COPPER GROUND WIRE. INSTALL ON PANEL L4CR CIRCUITS #1 AND #3. HARD

    WIRED.

    SOFT SERVE MACHINE. PROVIDE (2) #10 THHN COPPER WIRES, (1) #10 THHN

    COPPER GROUND WIRE. INSTALL ON PANEL L4CR CIRCUITS #5 AND #7. HARD

    WIRED.

    STOREFRONT SIGN. PROVIDE (2) #12 THHN COPPER WIRES, (1) #12 THHN COPPER

    GROUND WIRE. INSTALL ON PANEL L4CR CIRCUIT #17. HARD WIRED

    SOFT SERVE MACHINE. PROVIDE (2) #10 THHN COPPER WIRES, (1) #10 THHN

    COPPER GROUND WIRE. INSTALL ON PANEL L4CR CIRCUITS #9 AND #11. HARD

    WIRED.

    SOFT SERVE MACHINE. PROVIDE (2) #10 THHN COPPER WIRES, (1) #10 THHN

    COPPER GROUND WIRE. INSTALL ON PANEL L4CR CIRCUITS #13 AND #15. HARD

    WIRED.

    REFRIGERATED TOPPINGS PAN. PROVIDE (2) #12 THHN COPPER WIRES, (1) #12

    THHN COPPER GROUND WIRE. INSTALL ON PANEL L4CR CIRCUIT #12. UTILIZE NEMA

    5-15R.

    REFRIGERATED TOPPING GUARD. PROVIDE (2) #12 THHN COPPER WIRES, (1) #12

    THHN COPPER GROUND WIRE. INSTALL ON PANEL L4CR CIRCUIT #12. HARD WIRED.

    POINT OF SALE. PROVIDE (2) #12 THHN COPPER WIRES, (1) #12 THHN COPPER

    GROUND WIRE. INSTALL ON PANEL L4CR CIRCUIT #12. HARD WIRED. RELOCATE

    DATA CABLE FROM EXISTING POS. PROVIDE NEW DATA JACK.

    ILLUMINATED STOREFRONT SIGN. PROVIDE (2) #12 THHN COPPER WIRES, (1) #12

    THHN COPPER GROUND WIRE. INSTALL ON PANEL L4CR CIRCUIT #2. HARD WIRED.

    RECEPTACLE FOR FUTURE EQUIPMENT. PROVIDE (2) #12 THHN COPPER WIRES, (1)

    #12 THHN COPPER GROUND WIRE. INSTALL ON PANEL L4CR CIRCUIT #33. UTILIZE

    NEMA 5-20R.

    72" MAGATOP REFRIGERATOR. PROVIDE (2) #12 THHN COPPER WIRES, (1) #12 THHN

    COPPER GROUND WIRE. INSTALL ON PANEL L4CR CIRCUIT #4. UTILIZE NEMA 5-15R.

    DROP IN HOT FOOD WARMER. PROVIDE (2) #12 THHN COPPER WIRES, (1) #12 THHN

    COPPER GROUND WIRE. INSTALL ON PANEL L4CR CIRCUITS #6 AND #8. HARD

    WIRED.

    FOOD GUARD LIGHTING. PROVIDE (2) #12 THHN COPPER WIRES, (1) #12 THHN

    COPPER GROUND WIRE. INSTALL ON PANEL L4CR CIRCUIT #10. HARD WIRED.

    NUTRITIONAL TOUCH SCREEN. PROVIDE (2) #12 THHN COPPER WIRES, (1) #12 THHN

    COPPER GROUND WIRE. INSTALL ON PANEL L4CR CIRCUIT #38. UTILIZE NEMA

    5-15R.

    VENTLESS OVEN. PROVIDE (3) #6 THHN COPPER WIRES, (1) #6 THHN COPPER

    GROUND WIRE. INSTALL ON PANEL L4CR CIRCUITS #14, #16, AND #18. UTILIZE NEMA

    15-50R.

    HOT HOLDING CABINET. PROVIDE (2) #12 THHN COPPER WIRES, (1) #12 THHN

    COPPER GROUND WIRE. INSTALL ON PANEL L4CR CIRCUIT #22. UTILIZE NEMA

    5-15R.

    DIGITAL MENU SYSTEM. PROVIDE (2) #12 THHN COPPER WIRES, (1) #12 THHN

    COPPER GROUND WIRE. INSTALL ON PANEL L4CR CIRCUIT #38. UTILIZE NEMA

    5-15R.

    72" MAGATOP REFRIGERATOR. PROVIDE (2) #12 THHN COPPER WIRES, (1) #12 THHN

    COPPER GROUND WIRE. INSTALL ON PANEL L4CR CIRCUIT #20. UTILIZE NEMA

    5-15R.

    DIGITAL MENU SYSTEM. PROVIDE (2) #12 THHN COPPER WIRES, (1) #12 THHN

    COPPER GROUND WIRE. INSTALL ON PANEL L4CR CIRCUIT #38. UTILIZE NEMA

    5-15R.

    CREPE IRON. PROVIDE (2) #10 THHN COPPER WIRES, (1) #10 THHN COPPER

    GROUND WIRE. INSTALL ON PANEL L4CR CIRCUITS #23 AND #25. UTILIZE NEMA

    6-20R.

    MICROWAVE. PROVIDE (2) #12 THHN COPPER WIRES, (1) #12 THHN COPPER

    GROUND WIRE. INSTALL ON PANEL L4CR CIRCUIT #19. UTILIZE NEMA 5-15R.

    DROP IN 4/3 WARMER. PROVIDE (2) #12 THHN COPPER WIRES, (1) #12 THHN

    COPPER GROUND WIRE. INSTALL ON PANEL L4CR CIRCUIT #21. UTILIZE HARD

    WIRED.

    CREPE IRON. PROVIDE (2) #10 THHN COPPER WIRES, (1) #10 THHN COPPER

    GROUND WIRE. INSTALL ON PANEL L4CR CIRCUITS #24 AND #26. UTILIZE NEMA

    6-20R.

    BLENDER. PROVIDE (2) #12 THHN COPPER WIRES, (1) #12 THHN COPPER GROUND

    WIRE. INSTALL ON PANEL L4CR CIRCUIT #27. UTILIZE NEMA 5-15R.

    BLENDER. PROVIDE (2) #12 THHN COPPER WIRES, (1) #12 THHN COPPER GROUND

    WIRE. INSTALL ON PANEL L4CR CIRCUIT #29. UTILIZE NEMA 5-15R.

    REFRIGERATED COLD PAN. PROVIDE (2) #12 THHN COPPER WIRES, (1) #12 THHN

    COPPER GROUND WIRE. INSTALL ON PANEL L4CR CIRCUIT #31. UTILIZE NEMA

    5-15R.

    CONVECTION STEAMER. PROVIDE (2) #6 THHN COPPER WIRES, (1) #6 THHN

    COPPER GROUND WIRE. INSTALL ON PANEL L4CR CIRCUITS #28 AND #30. HARD

    WIRED.

    CONDENSER HOOD FOR STEAMER. PROVIDE (2) #12 THHN COPPER WIRES, (1) #12

    THHN COPPER GROUND WIRE. INSTALL ON PANEL L4CR CIRCUIT #22. UTILIZE NEMA

    5-15R.

    HOT HOLDING CABINET. PROVIDE (2) #12 THHN COPPER WIRES, (1) #12 THHN

    COPPER GROUND WIRE. INSTALL ON PANEL L4CR CIRCUIT #22. UTILIZE NEMA

    5-15R.

    BLAST CHILLER. PROVIDE (2) #12 THHN COPPER WIRES, (1) #12 THHN COPPER

    GROUND WIRE. INSTALL ON PANEL L4CR CIRCUITS #32 AND #34. HARD WIRED.

    BLENDER. PROVIDE (2) #12 THHN COPPER WIRES, (1) #12 THHN COPPER GROUND

    WIRE. INSTALL ON PANEL L4CR CIRCUIT #36. UTILIZE NEMA 5-15R.

    MEDIA PLAYERS. PROVIDE (2) #10 THHN COPPER WIRES, (1) #10 THHN COPPER

    GROUND WIRE. INSTALL ON PANEL L4CR CIRCUIT #38. UTILIZE NEMA L5-30R.

    INSTALL VGA CABLE PROVIDED BY MANUFACTURER FROM MEDIA PLAYERS TO

    SCREENS VIA 1" CONDUIT. PROVIDE UPS BACK-UP POWER SUPPLY APC SMT3000,

    OR APPROVED EQUAL, LOCATED ON SHELF WITH MEDIA PLAYERS.

    INSTALL VGA CABLE PROVIDED BY MANUFACTURER FROM MEDIA PLAYER TO

    NUTRITIONAL TOUCH SCREEN VIA 1" CONDUIT.

    INSTALL VGA CABLE PROVIDED BY MANUFACTURER FROM MEDIA PLAYER TO

    DIGITAL MENU SYSTEM VIA 1" CONDUIT.

    1

    420

    SCALE IN FEET

    12

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    21

    22

    23

    24

    25

    26

    27

    28

    29

    30

    31

    32

    33

    34

    35

    SheetsA1.01 - GENERAL NOTESA2.01 - FLOOR AND CEILING PLANSA2.02 - EQUIPMENT PLANA2.03 - INTERIOR ELEVATIONSA3.01 - PLUMBING AND ELECTRICAL PLANSA4.01 - CASEWORK PLANS AND DETAILSA4.02 - EQUIPMENT DETAILS

    1574 DM AFB - Freshens.pdfSheetsA0.00 - COVER SHEET/INDEXA4.03 - GRAPHICS DETAILS