EXHAUSTO A/S Odensevej 76 DK-5550 Langeskov Tel. +45 65 66 12 34 Fax +45 65 66 11 10 [email protected] www.exhausto.dk 3004402-2013-01-24.fm BACnet Protocol EXact/EXact2 RU Main station - Overview - Data collection - Alarm processing Heating Lights - Control of li ht Ventilation Motion sensor - Switch on ventilation - Switch on lights - Set point for temperature ventilation/heating Gateway
Transcript

EXHAUSTO A/SOdensevej 76DK-5550 Langeskov

Tel. +45 65 66 12 34Fax +45 65 66 11 [email protected]

3004402-2013-01-24.fm

BACnet ProtocolEXact/EXact2

RU

Main station- Overview- Data collection- Alarm processing

Heating - Control of heating installation

Lights - Control of

li ht

Ventilation - Control of ventilation

Motion sensor- Switch on ventilation- Switch on lights- Set point for temperature ventilation/heating

Gateway

3004402-2013-01-24.fm

1. GB - Introduction1.1 Overview............................................................................................................... 51.2 Communication.................................................................................................... 51.3 Supported BACnet Interoperability Building Blocks........................................ 51.4 Supported BACnet IP standard object types .................................................... 6

2. GB - Connection2.1 Connection MSTP ................................................................................................ 82.2 Connection BACnet IP ........................................................................................ 9

2.2.1 Configuring the web server ........................................................................... 92.2.2 Configuring BACnet..................................................................................... 10

2.3 Overriding external dampers ............................................................................ 112.3.1 Setting the override function (only air control method 8) ............................ 11

2.4 Example of device control ................................................................................ 122.4.1 Control of airflow, supply air temperature and manual mode/timer program 12

1. DK - Indledning1.1 Oversigt .............................................................................................................. 131.2 Kommunikation.................................................................................................. 131.3 Understøttede BACnet Interoperability Building Blocks ............................... 131.4 Understøttede BACnet IP standard objekttyper ............................................. 14

2. DK - Tilslutning2.1 Tilslutning MSTP................................................................................................ 162.2 Tilslutning BACnet IP ....................................................................................... 17

2.2.1 Opsætning af webserver ............................................................................. 172.2.2 Opsætning af BACnet ................................................................................. 18

2.3 Overstyring af eksterne spjæld ........................................................................ 192.3.1 Indstilling af overstyringsfunktion (kun luftreguleringsmetode 8) ................ 19

2.4 Eksempel på styring af anlæg .......................................................................... 202.4.1 Styring af luftmængde, tilluftstemperatur og manuel mode/urprogram ...... 20

1. DE - Einleitung1.1 Übersicht ............................................................................................................ 211.2 Kommunikation.................................................................................................. 211.3 Unterstützte BACnet Interoperability Building Blocks................................... 211.4 Unterstützte BACnet IP-Standardobjekttypen ................................................ 22

2. DE - Anschluss2.1 Anschließen von MSTP ..................................................................................... 242.2 Anschließen von BACnet IP ............................................................................. 25

2.2.1 Konfigurieren des Webservers .................................................................... 252.2.2 Konfigurieren von BACnet........................................................................... 26

2.3 Übersteuerung externer Klappen ..................................................................... 272.3.1 Einstellen der Übersteuerungsfunktion (nur Luftregelungsverfahren 8) ..... 27

2.4 Beispiel für Regelung der Anlage .................................................................... 292.4.1 Regelung von Luftmenge, Zulufttemperatur und manuellem Modus/Uhrprogramm 29

1. NO - Innledning1.1 Oversikt............................................................................................................... 301.2 Kommunikasjon ................................................................................................. 301.3 BACnet Interoperability Building Blocks understøttes.................................. 301.4 BACnet IP standard objekttyper understøttes ................................................ 31

2. NO - Tilkobling2.1 Tilkobling MSTP................................................................................................. 332.2 Tilkobling BACnet IP ........................................................................................ 34

2.2.1 Nettserver-oppsett....................................................................................... 342.2.2 BACnet-oppsett ........................................................................................... 35

2.3 Overstyring av eksterne spjeld......................................................................... 362.3.1 Innstilling av overstyringsfunksjon (kun luftreguleringsmetode 8) .............. 36

2.4 Eksempel på styring av anlegg ........................................................................ 372.4.1 Styring av luftmengde, tilluftstemperatur og manuell modus/urprogram .... 37

2/96

3004402-2013-01-24.fm

1. SE – Inledning1.1 Översikt............................................................................................................... 381.2 Kommunikation.................................................................................................. 381.3 BACnet Interoperability Building Blocks som stöds...................................... 381.4 BACnet IP standardobjekttyper som stöds..................................................... 39

2. SE- Anslutning2.1 Anslutning MSTP ............................................................................................... 412.2 Anslutning av BACnet IP .................................................................................. 42

2.2.1 Installation av webbserver:.......................................................................... 422.2.2 Uppsättning av BACnet ............................................................................... 43

2.3 Överstyrning av externa spjäll.......................................................................... 442.3.1 Inställning av överstyrningsfunktion (endast luftregleringsmetod 8) ........... 44

2.4 Exempel på styrning av anläggning................................................................. 452.4.1 Styrning av luftflöde, tilluftstemperatur och manuellt/timerprogram ........... 45

1. NL - Inleiding1.1 Overzicht............................................................................................................. 461.2 Communicatie .................................................................................................... 461.3 Ondersteuning van BACnet Interoperability Building Blocks....................... 461.4 Ondersteunde standaard objecttypen voor BACnet IP.................................. 47

2. NL - Aansluiting2.1 Aansluiting MSTP .............................................................................................. 492.2 Aansluiting BACnet IP ...................................................................................... 50

2.2.1 Instellen van de webserver.......................................................................... 502.2.2 Instellen van BACnet................................................................................... 51

2.3 Overnemen van externe klep ............................................................................ 522.3.1 Instelling van overnamefunctie (alleen voor luchtregelmethode 8) ............ 52

2.4 Voorbeeld van installatieregeling..................................................................... 532.4.1 Regeling van luchtvolume, toevoerluchttemperatuur en handmatige stand/klokprogram-

ma 53

1. FI - Johdanto1.1 Yleiskuvaus ........................................................................................................ 541.2 Tiedonsiirto ........................................................................................................ 541.3 BACnet Interoperability Building Blocks -yhteensopivuus ........................... 541.4 Yhteensopivat BACnet IP -vakio-objektityypit ................................................ 55

2. FI - Liitäntä2.1 MSTP-liitäntä ...................................................................................................... 572.2 BACnet IP -liitäntä ............................................................................................. 58

2.2.1 Web-palvelimen säädöt............................................................................... 582.2.2 BACnet-asetukset ....................................................................................... 59

2.3 Ulkoisten peltien ohitusohjaaminen ................................................................ 602.3.1 Ohitusohjaustoiminnon asetukset (vain ilmansäätömenetelmä 8) ............. 60

2.4 Esimerkki laitteiston ohjaamisesta .................................................................. 612.4.1 Ilmamäärän, tuloilman lämpötilan ja manuaalisen tilan / ajastusohjelman ohjaus 61

1. FR - Introduction1.1 Aperçu................................................................................................................. 621.2 Communication.................................................................................................. 621.3 BACnet Interoperability Building Blocks de soutien...................................... 621.4 Types d'objets standard BACnet IP de soutien .............................................. 63

2. FR - Raccordement2.1 Raccordement MSTP......................................................................................... 652.2 Raccordement IP BACnet ................................................................................ 66

2.2.1 Configuration du serveur web ..................................................................... 662.2.2 Configuration de BACnet............................................................................. 67

2.3 Commande asservie du registre externe......................................................... 682.3.1 Réglage de la fonction d'asservissement (uniquement pour la méthode de régulation de

l'air 8) 682.4 Exemple de commande de l'installation.......................................................... 70

3/96

3004402-2013-01-24.fm

2.4.1 Commande du débit d'air, de la température de l'air extrait et du programme manuel mode/heure 70

1. RU - Вводная часть1.1 Обзор................................................................................................................................. 711.2 Обмен данными .............................................................................................................. 711.3 Поддерживаемые функционально совместимые модули BACnet........................ 711.4 Поддерживаемые в BACnet типы объектов по стандарту IP ................................ 72

2. RU - Электрическое подключение2.1 Подключение MSTP....................................................................................................... 742.2 Подключение BACnet IP .............................................................................................. 75

2.2.1 Настройка веб-сервера ........................................................................................... 752.2.2 Настройка BACnet .................................................................................................. 76

2.3 Подавление (Блокировка автоматики) внешних заслонок ................................... 772.3.1 Настройка функции блокировки автоматики (только при методе

регулирования качества воздуха №8) 772.4 Примеры управления установкой .............................................................................. 79

2.4.1 Регулирование расхода воздуха, температуры приточного воздуха и ручной режим/программа таймера 79

3. Appendix - Complete list of Registers - in English3.1 Appendix............................................................................................................. 80

3.1.1 Object type AV ........................................................................................... 803.1.2 Object type AI ............................................................................................. 823.1.3 Object type BV ........................................................................................... 913.1.4 Object type BI ............................................................................................. 91

4/96

3004402-2013-01-24.fm GB - Introduction

1. GB - Introduction

Air handling unit (AHU) fitted with an EXHAUSTO EXact/EXact2 control unitBACnet functionality has been implemented in the EXHAUSTO EXact web server with softwareversion 3.0-xxxx or later. EXHAUSTO EXact is a BACnet Application SpecificController (B-ASC) with supported data link layer options: BACnet IP or BACnet MSTP.See also the document "EXact_EDE_ddmmyy" (Engineering Data Exchange).

TCP/IP: qty. 1 10/100 Mbit Ethernet, RJ45 connector.MSTP: qty. 1 RS-485

1.1 Overview

1.2 Communication

1.3 Supported BACnet Interoperability Building Blocks

Data sharing DS-RP-B Data Sharing-ReadProperty-B

Data sharing DS-RPM-B Data Sharing-ReadPropertyMultiple-B

Data sharing DS-WP-B Data Sharing-WriteProperty-B

Data sharing DS-WPM-B Data Sharing-WritePropertyMultiple-B

Device management

DM-DDB-B Device Management-DynamicDeviceBinding-B

Device management

DM-DOB-B Device Management-DynamicObjectBinding-B

Device management

DM-DCC-B Device Management-DeviceCommunicationControl-B

Device management

DM-RD-B Device Management-ReinitializeDevice-B

5/96

3004402-2013-01-24.fm GB - Introduction

1.4 Supported BACnet IP standard object types

Standard object typesRO = Read onlyRW = Read/Write

Features

Device Object_IdentifierObject_NameObject_TypeSystem_StatusVendor_NameVendor_IdentifierModel_NameFirmware_RevisionApplication_Software_VersionProtocol_VersionProtocol_RevisionProtocol_Services_SupportedProtocol_Object_Types_SupportedObject_ListMax_APDU_Length_AcceptedSegmentation_SupportedAPDU_TimeoutNumber_Of_APDU_RetriesDevice_Address_BindingDatabase_Revision

Analog input AI (RO) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceUnits

Analog output AO (RW)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceUnits

Dual input (RO) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServicePolarity

6/96

3004402-2013-01-24.fm GB - Introduction

Dual output DO (RW) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_Service

Multistate input (RO) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceNumber_Of_States

Multistate output (RW) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceNumber_Of_States

Standard object typesRO = Read onlyRW = Read/Write

Features

7/96

3004402-2013-01-24.fm GB - Connection

2. GB - Connection

Cable The BACnet MSTP cable must be 2 x 2 x 0.25 twisted pair cable.

The BACnet MSTP connection is connected to CN3 of the main control. Only BACnet MSTP A, B and 0 V DC (chassis) may be fitted. See diagram

EXact/EXact2

Key to diagram

CN3: BACnet MSTP (RS-485)

A and B signal (terminals 2-3) must be twisted pair.

Termination If the EXact/EXact2 control system is the final device on the cable, a terminating resistor of 120 Ω must be mounted. You do this at jumper JP2 on the web server.

2.1 Connection MSTP

Terminal Signal description1 Do not connect2 RS485 + (A)3 RS485 – (B)4 0V DC (Chassis)

8/96

3004402-2013-01-24.fm GB - Connection

Connecting the network

Connect the network to the Ethernet plug. If the web server is to be connected directly to the computer use crossover cable.

MAC address The web server's MAC address can be seen on the web server PCB and in menu 3.6 on the HMI panel.

Cable type and length

2.2.1 Configuring the web serverThe web server supports both static and dynamic IP addresses. These are configured in menu 3.6 on the HMI panel.

Example

Port number*) In the case of several devices on the same router, you can give them different port numbers and employ port forwarding.*) For BACnet, the port number is always 47808. The port number applies only to the web interface.

2.2 Connection BACnet IP

Cable Cable length

CAT5E STP cable (shielded cable)

EXHAUSTO recommends max. cable length: 70 m.

See “EXact Basic Instructions” on how to:- change settings- save changes

No

> 192.168.001.180

> 255.255.255.000

> 192.168.001.00180

00:1F:79:00:00:D0No

3.6 Web server

DHCP >IP address

Subnet mask

Standard gateway

Port number >MAC address

Reset password >

9/96

3004402-2013-01-24.fm GB - Connection

2.2.2 Configuring BACnetExample

• Select BACnet MSTP or BACnet IP across from BMS in menu 3.5

Only for BACnet MSTP

Set the following values, as defined by the systems manager:• Device ID (0 - 255)• Device name - NB this can only be set in the web server• Net Number (1 - 65534)• Address (0 - 127)• Baud rate (9600, 19200, 115200)

Only for BACnet IP

Set the following values, as defined by the systems manager:• Device ID (0 - 255)• Device name - NB this can only be set in the web server

BMS >Configuration >

3.5 BMSNone

3.5.2 ConfigurationDevice ID >Device name:

Net number >Adress >Baud rate >

0

0None

9

3.5.2 ConfigurationDevice ID >Device name:

0

10/96

3004402-2013-01-24.fm GB - Connection

In air control method 8, "External control of fan speeds", it may be necessary in certain operating situations to override external dampers in the duct system. External dampers may, for example, be VAV dampers.In case of fire, de-icing or night-time cooling, the VEX unit may send a signal to the BMS unit to open or close dampers in the extract air or supply air ducts.

2.3.1 Setting the override function (only air control method 8)

2.3 Overriding external dampers

Step Action The display shows

1 • Switch to menu Settings “->Device->Operating settings”• Set "Air control" to "8".

2 • Switch to menu "AUX"• Set "Type" to "BMS"

3 • Switch to menu "BMS"• Switch to menu "Override" under "Supply air"• Set "Override" to "Yes"• Set "Normal" to the desired value to be sent when the VEX unit

does not require an override on the supply air damper• Set "Open" to the desired value to be sent when the VEX unit

requires the supply dampers to be open• Set "Close" to the desired value to be sent when the VEX unit

requires the supply dampers to be closed• Return to menu "BMS"

3 • Switch to menu "Override" under "Extract air"• Set "Override" to "Yes"• Set "Normal" to the desired value to be sent when the VEX unit

does not require an override on the extract air damper• Set "Open" to the desired value to be sent when the VEX unit

requires the extract air dampers to be open• Set "Close" to the desired value to be sent when the VEX unit

requires the extract air dampers to be closed• Note that the values for Normal, Open and Closed must not be the

same.

If no override is desired on either or both ducts, set "Override" to "No".

IAQ. levels >Temp. reg. >Air reg. >AUX >Regulators >

3.1.1 Operating settings

Supply air82

3.1.1.4 AUX

Type >BFOBMS

101None

3.1.1.4.3.3 OverrideOverride >Normal >Open >Close >

No012

3.1.1.4.3.7 OverrideOverride >Normal >Open >Close >

No012

11/96

3004402-2013-01-24.fm GB - Connection

2.4.1 Control of airflow, supply air temperature and manual mode/timer programSettingair flow

Settingsupply air temperature

Timer program Set Object type BV - Index 00 - BMSInValue.CtrlMode to “1”, if the device is to return to the timer program.

2.4 Example of device control

Step Action

1 Set unit to manual mode:Set Object type BV - Index 00 - BMSInValue.CtrlMode to “0”.

2 Set Object type AV - Index 06 - BMSInValue.AirSP to a value between 0 and 100%. The value 0% will stop the unit.

Step Action

1 Set unit to manual mode: Set Object type BV - Index 00 - BMSInValue.CtrlMode to “0”.

2 Set Object type AV - Index 07 - BMSInValue.TempSP to a value between 10 and 35°C. NB: The temperature set point may be limited by other settings and functions.

12/96

3004402-2013-01-24.fm DK - Indledning

1. DK - Indledning

Luftbehandlingsaggregat (AHU), der er udstyret med en EXHAUSTO EXact/EXact2 styreenhed.BACnet funktionaliteten er implementeret i EXHAUSTO EXact webserver med softwareversion 3.0-xxxx eller nyere. EXHAUSTO EXact er en BACnet Application SpecificController (B-ASC) med understøttede data link layer valgmuligheder: BACnet IP eller BACnet MSTP.Der henvises desuden til dokumentet "EXact_EDE_ddmmyy" (Engineering Data Ex-change).

TCP/IP: 1 stk. 10/100 Mbit Ethernet, RJ45 kontakt.MSTP: 1 stk. RS-485

1.1 Oversigt

1.2 Kommunikation

1.3 Understøttede BACnet Interoperability Building Blocks

Datadeling DS-RP-B Data Sharing-ReadProperty-B

Datadeling DS-RPM-B Data Sharing-ReadPropertyMultiple-B

Datadeling DS-WP-B Data Sharing-WriteProperty-B

Datadeling DS-WPM-B Data Sharing-WritePropertyMultiple-B

Enheds håndtering DM-DDB-B Device Management-DynamicDeviceBinding-B

Enheds håndtering DM-DOB-B Device Management-DynamicObjectBinding-B

Enheds håndtering DM-DCC-B Device Management-DeviceCommunicationControl-B

Enheds håndtering DM-RD-B Device Management-ReinitializeDevice-B

13/96

3004402-2013-01-24.fm DK - Indledning

1.4 Understøttede BACnet IP standard objekttyper

Standard objekttyperRO = Read onlyRW = Read / Write

Egenskaber

Enhed Object_IdentifierObject_NameObject_TypeSystem_StatusVendor_NameVendor_IdentifierModel_NameFirmware_RevisionApplication_Software_VersionProtocol_VersionProtocol_RevisionProtocol_Services_SupportedProtocol_Object_Types_SupportedObject_ListMax_APDU_Length_AcceptedSegmentation_SupportedAPDU_TimeoutNumber_Of_APDU_RetriesDevice_Address_BindingDatabase_Revision

Analog indgang AI (RO)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceUnits

Analog værdi AO (RW) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceUnits

Binær indgang DI (RO) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServicePolarity

14/96

3004402-2013-01-24.fm DK - Indledning

Binær værdi DO (RW) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_Service

Multistate indgang (RO)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceNumber_Of_States

Multistate værdi (RW) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceNumber_Of_States

Standard objekttyperRO = Read onlyRW = Read / Write

Egenskaber

15/96

3004402-2013-01-24.fm DK - Tilslutning

2. DK - Tilslutning

Kabel BACnet MSTP kablet skal være 2 x 2 x 0,25 parsnoet kabel.

BACnet MSTP forbindelsen tilsluttes hovedstyringens CN3. Kun BACnet MSTP A, B og stel må monteres. Se diagram.

EXact/EXact2

Forklaring til diagram

CN3: BACnet MSTP (RS-485)

A og B signalet (klemme 2 - 3) skal være parsnoet.

Endeterminering Hvis EXact/EXact2 styringen er den sidste enhed på kablet skal der monteres en termineringsmodstand på 120 Ω. Dette gøres via jumper JP2 på webserveren.

2.1 Tilslutning MSTP

Klemme Signalbeskrivelse1 Må ikke forbindes2 RS485 + (A)3 RS485 – (B)4 0V DC (Stel)

16/96

3004402-2013-01-24.fm DK - Tilslutning

Tilslutning af netværk

Netværksstikket monteres i ethernetstikket. Hvis webserveren skal tilsluttes direkte til PC, skal der anvendes et krydset netværkskabel.

MAC-adresse Webserverens MAC-adresse kan aflæses på webserver-printet samt i menu 3.6 i HMI-panelet.

Kabeltype og længde

2.2.1 Opsætning af webserverWebserver understøtter både statiske og dynamiske IP-adresser. Dette konfigureres i menu 3.6 i HMI-panelet.

Eksempel

Portnummer*) Hvis man har flere anlæg på samme router kan man give dem forskellige portnumre og så benytte sig af port forwarding.*) For BACnet er port nummeret fast på 47808. Port nummeret gælder kun for webinterface.

2.2 Tilslutning BACnet IP

Kabel Kabellængde

CAT5E STP-kabel (skærmet kabel)

EXHAUSTO anbefaler maks. kabellængde: 70 m.

Se i EXact basisvejledning hvordan du:- ændrer indstillinger- gemmer ændrede indstillinger

DHCP >IP-adresse

Undernetmaske

Standardgateway

Portnummer >MAC adresse

Nulstil adg.kode >

3.6 Web server

Nej

> 192.168.001.180

> 255.255.255.000

> 192.168.001.00180

00:1F:79:00:00:D0Nej

17/96

3004402-2013-01-24.fm DK - Tilslutning

2.2.2 Opsætning af BACnetEksempel

• Der skal vælges BACnet MSTP eller BACnet IP ud for BMS i menu 3.5.

Kun for BACnet MSTP

Indstil følgende værdier som defineret af den systemansvarlige:• Device ID (0 - 255)• Device name - Bemærk kan kun indstilles i Webserveren• Net Number (1 - 65534)• Adress (0 - 127)• Baud rate (9600, 19200, 115200)

Kun for BACnet IP

Indstil følgende værdier som defineret af den systemansvarlige:• Device ID (0 - 255)• Device name - Bemærk kan kun indstilles i Webserveren

BMS >Konfiguration >

3.5 BMSNone

3.5.2 KonfigurationDevice ID >Device name:

Net number >Adress >Baud rate >

0

0Ingen

9

3.5.2 KonfigurationDevice ID >Device name:

0

18/96

3004402-2013-01-24.fm DK - Tilslutning

Ved luft regulerings metode 8, ”Eksterne styring af ventilator hastigheder”, kan det i vis-se drift situationer være nødvendigt at overstyrer eksterne spjæld i kanal systemet. Eksterne spjæld kan f.eks. være VAV spjæld.Ved brand, afisning eller natkøling kan VEX aggregatet sende et signal til BMS anlæg-get om at åbne eller lukke spjæld i fraluft eller tilluft kanalen.

2.3.1 Indstilling af overstyringsfunktion (kun luftreguleringsmetode 8)

2.3 Overstyring af eksterne spjæld

Trin Handling Display viser...

1 • Skift til menu Indstillinger “->Anlæg->Driftindstillinger”• Indstil ”Luft reg.” til ”8”

2 • Skift til menu ”AUX”• Indstil ”Type” til ”BMS”

3 • Skift til menu “BMS”• Skift til menu ”Overstyring” under ”Tilluft”• Indstil ”Overstyring til ”Ja”• Indstil ”Normal” til den værdi der ønskes sendt, når VEX aggrega-

tet ikke kræver overstyring af tilluft spjæld• Indstil ”Åben” til den værdi der ønskes sendt, når VEX aggregatet

kræver at tilluft spjæld er åbne• Indstil ”Lukke” til den værdi der ønskes sendt, når VEX aggregatet

kræver at tilluft spjæld er lukkede• Skift tilbage til menu ”BMS”

3 • Skift til menu ”Overstyring” under ”Fraluft”• Indstil ”Overstyring til ”Ja”• Indstil ”Normal” til den værdi der ønskes sendt, når VEX aggrega-

tet ikke kræver overstyring af fraluft spjæld• Indstil ”Åben” til den værdi der ønskes sendt, når VEX aggregatet

kræver at fraluft spjæld er åbne• Indstil ”Lukke” til den værdi der ønskes sendt, når VEX aggregatet

kræver at fraluft spjæld er lukkede• Bemærk af værdierne for Normal, Åben og Lukket ikke må være

ens.

Ønskes der ingen overstyring for en eller begge kanaler sættes ”Overstyring” til ”Nej”.

Indeklimaniveauer >Temp. reg. >Luft reg. >AUX >Regulatorer >

3.1.1 Driftindstillinger

Tilluft82

3.1.1.4 AUX

Type >BFOBMS

Ingen

3.1.1.4.3.3 OverstyringOverstyring >Normal >Åben >Lukke >

Nej012

3.1.1.4.3.7 OverstyringOverstyring >Normal >Åben >Lukke >

Nej012

19/96

3004402-2013-01-24.fm DK - Tilslutning

2.4.1 Styring af luftmængde, tilluftstemperatur og manuel mode/urprogramIndstilling afluftmængden

Indstilling aftillufttemperaturen

Urprogram Sæt Object type BV - Index 00 - BMSInValue.CtrlMode til “1”, hvis aggregatet skal tilba-ge på urprogram.

2.4 Eksempel på styring af anlæg

Trin Handling

1 Sæt aggregatet i manuel mode:Sæt Object type BV - Index 00 - BMSInValue.CtrlMode til “0”.

2 Sæt Object type AV - Index 06 - BMSInValue.AirSP til en værdi mellem 0 og 100%. Værdien 0% standser aggregatet.

Trin Handling

1 Sæt aggregatet i manuel mode: Sæt Object type BV - Index 00 - BMSInValue.CtrlMode til “0”.

2 Sæt Object type AV - Index 07 - BMSInValue.TempSP til en værdi mellem 10 og 35°C. Bemærk: Temperatursetpunktet kan været begrænset af andre indstillinger og funktioner.

20/96

3004402-2013-01-24.fm DE - Einleitung

1. DE - Einleitung

Das Lüftungsgerät (AHU) ist mit einer EXact/EXact2-Automatik von EXHAUSTO aus-gerüstet.Die BACnet-Funktionalität wurde in den EXHAUSTO EXact-Webservern mit der Soft-ware Version 3.0-xxxx oder neuer eingeführt. EXHAUSTO EXact ist ein BACnet Appli-cation Specific Controller (B-ASC) mit unterstützten Daten-Link-Layer-Optionen: BACnet IP oder BACnet MSTP.Es wird ferner auf das Dokument "EXact_EDE_ddmmyy" (Engineering Data Exchange) verwiesen.

TCP/IP: 1 Stck. 10/100 Mbit Ethernet, RJ45-Kontakt.MSTP: 1 Stck. RS-485

1.1 Übersicht

1.2 Kommunikation

1.3 Unterstützte BACnet Interoperability Building Blocks

Datenteilung DS-RP-B Data Sharing-ReadProperty-B

Datenteilung DS-RPM-B Data Sharing-ReadPropertyMultiple-B

Datenteilung DS-WP-B Data Sharing-WriteProperty-B

Datenteilung DS-WPM-B Data Sharing-WritePropertyMultiple-B

Gerätemanager DM-DDB-B Device Management-DynamicDeviceBinding-B

Gerätemanager DM-DOB-B Device Management-DynamicObjectBinding-B

Gerätemanager DM-DCC-B Device Management-DeviceCommunicationControl-B

Gerätemanager DM-RD-B Device Management-ReinitializeDevice-B

21/96

3004402-2013-01-24.fm DE - Einleitung

1.4 Unterstützte BACnet IP-Standardobjekttypen

StandardobjekttypenRO = Read onlyRW = Read / Write

Eigenschaften

Einheit Object_IdentifierObject_NameObject_TypeSystem_StatusVendor_NameVendor_IdentifierModel_NameFirmware_RevisionApplication_Software_VersionProtocol_VersionProtocol_RevisionProtocol_Services_SupportedProtocol_Object_Types_SupportedObject_ListMax_APDU_Length_AcceptedSegmentation_SupportedAPDU_TimeoutNumber_Of_APDU_RetriesDevice_Address_BindingDatabase_Revision

Analogeingang AI (RO)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceUnits

Analogwert AO (RW) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceUnits

Binäreingang DI (RO) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServicePolarity

22/96

3004402-2013-01-24.fm DE - Einleitung

Binärwert DO (RW) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_Service

Multistate-Eingang (RO)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceNumber_Of_States

Multistate-Wert (RW) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceNumber_Of_States

StandardobjekttypenRO = Read onlyRW = Read / Write

Eigenschaften

23/96

3004402-2013-01-24.fm DE - Anschluss

2. DE - Anschluss

Kabel Das BACnet MSTP-Kabel muss vom Typ 2 x 2 x 0,25 Twisted-Pair-Kabel sein.

Der BACnet MSTP-Anschluss ist direkt an CN3 der Hauptautomatik anzuschließen. Es dürfen nur BACnet MSTP A, B und Masse angeschlossen werden. Siehe Diagramm.

EXact/EXact2

Erläuterung zum Diagramm

CN3: BACnet MSTP (RS-485)

Das Signal A und B (Klemme 2 - 3) muss paarweise gewunden sein.

Endterminierung Falls die EXact/EXact2-Automatik die letzte Einheit am Kabel ist, muss ein Terminierungswiderstand von 120 Ω montiert werden. Dies erfolgt über die Kurzschlussbrücke JP2 am Webserver.

2.1 Anschließen von MSTP

Klemme Signalbeschreibung1 Darf nicht benutzt werden2 RS485 + (A)3 RS485 – (B)4 0V DC (Masse)

24/96

3004402-2013-01-24.fm DE - Anschluss

Netzwerk-anschluss

Der Netzwerkanschluss wird im Ethernetstecker montieret. Wenn der Webserver direkt an einen PC angeschlossen werden soll, ist ein gekreuztes Netzwerkkabel erforderlich.

Mac-Adresse Die Mac-Adresse geht aus der Webserverplatine sowie aus Menü 3.6 im HMI-Panel hervor.

Kabeltyp und Länge

2.2.1 Konfigurieren des WebserversDer Webserver unterstützt statische wie dynamische IP-Adressen. Dies wird in Menü 3.6 im HMI-Panel konfiguriert.

Beispiel

Portnummer*) Wenn mehrere Anlagen am selben Router angeschlossen sind, kann man ihnen verschiedene Portnummern zuteilen und dann Portweiterleitung benutzen.*) Für BACnet liegt die Portnummer von 47808 fest. Die Portnummer gilt nur für Webinterface.

2.2 Anschließen von BACnet IP

Kabel Kabellänge

CAT5E STP-Kabel (geschirmtes Kabel)

EXHAUSTO empfiehlt als max. Kabellänge: 70 m.

Siehe die EXact-Basisanleitung bezüglich:- Ändern von Einstellungen- Speichern der geänderten Einstellungen

DHCP >IP-Adresse

Subnetzmaske

Standardgateway

Port-Nummer >MAC-adresse

Passwort reset >

3.6 Webserver

Nein

> 192.168.001.180

> 255.255.255.000

> 192.168.001.00180

00:1F:79:00:00:D0Nein

25/96

3004402-2013-01-24.fm DE - Anschluss

2.2.2 Konfigurieren von BACnetBeispiel

• Bei BMS in Menü 3.5 BACnet MSTP oder BACnet IP wählen.

Nur für BACnet MSTP

Folgende vom Systemverantwortlichen definierten Werte eingeben:• Device ID (0 - 255)• Device name - Hinweis: Lässt sich nur im Webserver einstellen• Net Number (1 - 65534)• Adress (0 - 127)• Baud-Rate (9600, 19200, 115200)

Nur für BACnet IP

Folgende vom Systemverantwortlichen definierten Werte eingeben:• Device ID (0 - 255)• Device name - Hinweis: Lässt sich nur im Webserver einstellen

BMS >Konfiguration >

3.5 BMSKeine

3.5.2 KonfigurationDevice ID >Device name:

Net number >Adress >Baud rate >

0

0Kein

9

3.5.2 KonfigurationDevice ID >Device name:

0

26/96

3004402-2013-01-24.fm DE - Anschluss

Bei Luftregelungsverfahren 8, ”Externe Regelung der Ventilatordrehzahl”, kann es in gewissen Situationen erforderlich sein, externe Klappen im Kanalsystem zu übersteu-ern. Externe Klappen sind beispielsweise VAV-Klappen.Bei Brand, Enteisung oder Nachtkühlung kann das VEX-Gerät ein Signal an die BMS-Anlage senden, dass Klappen im Abluft- oder Zuluftkanal geöffnet bzw. geschlossen werden müssen.

2.3.1 Einstellen der Übersteuerungsfunktion (nur Luftregelungsverfahren 8)7

2.3 Übersteuerung externer Klappen

Schritt Vorgehen Das Displayzeigt …

1 • Zum Menü Einstellungen “->Anlage->Bertriebseinstellungen” wechseln

• ”Luftreg.” auf ”8” einstellen

2 • Zum Menü ”AUX” wechseln• ”Typ” auf ”BMS” einstellen

3 • Zum Menü ”BMS” wechseln• Zum Menü ”Übersteuern” unter ”Zuluft” wechseln• ”Übersteuern" auf ”Ja” einstellen• ”Normal” auf den Wert einstellen, der übertragen werden soll,

wenn das VEX-Gerät keine Übersteuerung der Zuluftklappe erfordert

• ”Geöffnet” auf den Wert einstellen, der übertragen werden soll, wenn das VEX-Gerät erfordert, dass die Zuluftklappen geöffnet sind

• ”Geschlossen” auf den Wert einstellen, der übertragen werden soll, wenn das VEX-Gerät erfordert, dass die Zuluftklappen geschlossen sind

• Zurück zum Menü ”BMS” wechseln

Innenklimaniveau >Temp.reg. >Luftreg. >AUX >Regler >

3.1.1 Betriebseinstellungen

Zuluft82

3.1.1.4 AUX

Typ >BFOBMS

Kein

3.1.1.4.3.3 ÜbersteuerungÜbersteuerung >Normal >Geöffnet >Geschlossen >

Nein012

27/96

3004402-2013-01-24.fm DE - Anschluss

3 • Zum Menü ”Übersteuern” unter ”Abluft” wechseln• ”Übersteuern" auf ”Ja” einstellen• ”Normal” auf den Wert einstellen, der übertragen werden soll,

wenn das VEX-Gerät keine Übersteuerung der Abluftklappe erfordert

• ”Geöffnet” auf den Wert einstellen, der übertragen werden soll, wenn das VEX-Gerät erfordert, dass die Abluftklappen geöffnet sind

• ”Geschlossen” auf den Wert einstellen, der übertragen werden soll, wenn das VEX-Gerät erfordert, dass die Abluftklappen geschlossen sind

• Hinweis: Die Werte für Normal, Geöffnet und Geschlossen dürfen nicht identisch sein

Wenn für einen oder beide Kanäle keine Übersteuerung gewünscht wird, ist ”Übersteuern” auf ”Nein” einzustellen.

Schritt Vorgehen Das Displayzeigt …

3.1.1.4.3.7 ÜbersteuerungÜbersteuerung >Normal >Geöffnet >Geschlossen >

Nein012

28/96

3004402-2013-01-24.fm DE - Anschluss

2.4.1 Regelung von Luftmenge, Zulufttemperatur und manuellem Modus/UhrprogrammEinstellen derLuftmenge

Einstellen derZulufttemperatur

Uhrprogramm Object type BV - Index 00 - BMSInValue.CtrlMode auf “1” einstellen, wenn das Gerät auf Uhrprogramm zurückgeschaltet werden soll.

2.4 Beispiel für Regelung der Anlage

Schritt Vorgehen

1 Das Gerät auf den Modus manuell einstellen:Object type BV - Index 00 - BMSInValue.CtrlMode auf “0” einstellen.

2 Object type AV - Index 06 - BMSInValue.AirSP auf einen Wert zwischen 0 und 100% einstellen. Beim Wert 0% wird das Gerät abgeschaltet.

Schritt Vorgehen

1 Das Gerät auf den Modus manuell einstellen: Object type BV - Index 00 - BMSInValue.CtrlMode auf “0” einstellen.

2 Object type AV - Index 07 - BMSInValue.TempSP auf einen Wert zwischen 10 und 35°C einstellen. Hinweis: Der Temperatursollwert kann Begrenzungen durch andere Einstellungen und Funktionen unterliegen.

29/96

3004402-2013-01-24.fm NO - Innledning

1. NO - Innledning

Luftbehandlingsaggregat (AHU) som er utstyrt med en EXHAUSTO EXact/EXact2 sty-reenhet.BACnet-funksjonaliteten er implementert i EXHAUSTO EXact nettserver med program-vareversjon 3.0-xxxx eller nyere. EXHAUSTO EXact er en BACnet Application SpecificController (B-ASC) med understøttede data link layer-valgmuligheter: BACnet IP eller BACnet MSTP.Det henvises dessuten til dokumentet "EXact_EDE_ddmmyy" (Engineering Data Exchange).

TCP/IP: 1 stk. 10/100Mbit Ethernet, RJ45-tilkobling.MSTP: 1 stk. RS-485

1.1 Oversikt

1.2 Kommunikasjon

1.3 BACnet Interoperability Building Blocks understøttes

Datadeling DS-RP-B Data Sharing-ReadProperty-B

Datadeling DS-RPM-B Data Sharing-ReadPropertyMultiple-B

Datadeling DS-WP-B Data Sharing-WriteProperty-B

Datadeling DS-WPM-B Data Sharing-WritePropertyMultiple-B

Enhetshåndtering DM-DDB-B Device Management-DynamicDeviceBinding-B

Enhetshåndtering DM-DOB-B Device Management-DynamicObjectBinding-B

Enhetshåndtering DM-DCC-B Device Management-DeviceCommunicationControl-B

Enhetshåndtering DM-RD-B Device Management-ReinitializeDevice-B

30/96

3004402-2013-01-24.fm NO - Innledning

1.4 BACnet IP standard objekttyper understøttes

Standard objekttyperRO = Read OnlyRW = Read / Write

Egenskaper

Enhet Object_IdentifierObject_NameObject_TypeSystem_StatusVendor_NameVendor_IdentifierModel_NameFirmware_RevisionApplication_Software_VersionProtocol_VersionProtocol_RevisionProtocol_Services_SupportedProtocol_Object_Types_SupportedObject_ListMax_APDU_Length_AcceptedSegmentation_SupportedAPDU_TimeoutNumber_Of_APDU_RetriesDevice_Address_BindingDatabase_Revision

Analog inngang AI (RO)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceUnits

Analog verdi AO (RW) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceUnits

Binær inngang DI (RO) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServicePolarity

31/96

3004402-2013-01-24.fm NO - Innledning

Binær verdi DO (R/W) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_Service

Multistate inngang (RO)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceNumber_Of_States

Multistate verdi (RW) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceNumber_Of_States

Standard objekttyperRO = Read OnlyRW = Read / Write

Egenskaper

32/96

3004402-2013-01-24.fm NO - Tilkobling

2. NO - Tilkobling

Kabel BACnet MSTP-kabelen skal være 2 x 2 x 0,25 parsnodd kabel.

BACnet MSTP-forbindelsen kobles til CN3 på hovedstyringen. Kun BACnet MSTP A, B og jord kan monteres. Se skjema.

EXact/EXact2

Forklaring til skjemaet

CN3: BACnet MSTP (RS-485)

A- og B-signalet (klemme 2 - 3) må være parsnodd.

Terminering Dersom EXact/EXact2-styringen er den siste enheten på kabelen, må det monteres en termineringsmotstand på 120 Ω. Dette gjøres via jumper JP2 på nettserveren.

2.1 Tilkobling MSTP

Klemme Signalbeskrivelse1 Må ikke forbindes2 RS485 + (A)3 RS485 – (B)4 0V DC (jord)

33/96

3004402-2013-01-24.fm NO - Tilkobling

Tilkobling av nettverk

Nettverkskabelen kobles til Ethernet-kontakten. Dersom nettserveren skal tilkobles direkte til en PC, må det brukes en krysset nettverkskabel.

MAC-adresse Nettserverens MAC-adresse kan avleses på nettserver-kretskortet og i meny 3.6 i HMI-panelet.

Kabeltype og lengde

2.2.1 Nettserver-oppsettNettserveren understøtter både statiske og dynamiske IP-adresser. Dette konfigureres i meny 3.6 i HMI-panelet.

Eksempel

Portnummer*) Er flere anlegg tilkoblet samme ruter, kan man gi dem forskjellig portnummer og bruke portviderekobling (port forwarding).*) For BACnet er portnummeret fast: 47808. Portnummeret gjelder kun for nettgrensesnitt.

2.2 Tilkobling BACnet IP

Kabel Kabellengde

CAT5E STP-kabel (skjermet kabel)

EXHAUSTO anbefaler maks. kabellengde: 70 m.

Se i basisveiledningen for EXact hvordan du:- endrer innstillinger- lagrer endrede innstillinger

DHCP >IP-adresse

Undernettmaske

Standardgateway

Portnummer >MAC-adresse

Nullstill adg.kode >

3.6 Webserver

Nei

> 192.168.001.180

> 255.255.255.000

> 192.168.001.00180

00:1F:79:00:00:D0

Nei

34/96

3004402-2013-01-24.fm NO - Tilkobling

2.2.2 BACnet-oppsettEksempel

• Det må velges BACnet MSTP eller BACnet IP foran BMS i meny 3.5.

Kun for BACnet MSTP

Still inn følgende verdier som definert av den systemansvarlige:• Device ID (0 - 255)• Device name - Merk: Kan kun innstilles i nettserveren• Net Number (1 - 65534)• Adress (0 - 127)• Baud rate (9600, 19200, 115200)

Kun for BACnet IP

Still inn følgende verdier som definert av den systemansvarlige:• Device ID (0 - 255)• Device name - Merk: Kan kun innstilles i nettserveren

BMS >Konfigurasjon >

3.5 BMSIngen

3.5.2 KonfigurasjonDevice ID >Device name:

Net number >Adress >Baud rate >

0

0Ingen

9

3.5.2 KonfigurasjonDevice ID >Device name:

0

35/96

3004402-2013-01-24.fm NO - Tilkobling

Ved luft reguleringsmetode 8, «Ekstern styring av viftehastigheter», kan det i visse driftssituasjoner være nødvendig å overstyre eksterne spjeld i kanalsystemet. Eksterne spjeld kan f.eks. være VAV-spjeld.Ved brann, avising eller nattkjøling kan VEX-aggregatet sende et signal til BMS-anleg-get om å åpne eller stenge spjeld i avtrekks- eller tilluftskanalen.

2.3.1 Innstilling av overstyringsfunksjon (kun luftreguleringsmetode 8)

2.3 Overstyring av eksterne spjeld

Trin Handling Displayet viser ...

1 • Skift til menyen «Innstillinger->Anlegg->Driftsinnstillinger»• Still inn «Luft reg.» på «8»

2 • Skift til menyen «AUX»• Still inn «Type» på «BMS»

3 • Skift til menyen «BMS»• Skift til menyen «Overstyring» under «Tilluft»• Still inn «Overstyring» på «Ja»• Still inn «Normal» på verdien som ønskes sendt når VEX-aggre-

gatet ikke krever overstyring av tilluftsspjeld• Still inn «Åpen» på verdien som ønskes sendt når VEX-aggregatet

krever at tilluftsspjeld er åpne• Still inn «Stengt» på verdien som ønskes sendt når VEX-aggrega-

tet krever at tilluftsspjeld er stengt• Skift til tilbake til menyen «BMS»

3 • Skift til menyen «Overstyring» under «Avtrekk»• Still inn «Overstyring» på «Ja»• Still inn «Normal» på verdien som ønskes sendt når VEX-aggre-

gatet ikke krever overstyring av avtrekksspjeld• Still inn «Åpen» på verdien som ønskes sendt når VEX-aggregatet

krever at avtrekksspjeld er åpne• Still inn «Stengt» på verdien som ønskes sendt når VEX-aggrega-

tet krever at avtrekksspjeld er stengt• Merk at verdiene for Normal, Åpen og Stengt ikke må være like.

Ønskes det ikke overstyring for en eller begge kanaler, settes «Overstyring» til «Nei».

Inneklimanivåer >Temp. reg. >Luftreg. >AUX >Regulatorer >

3.1.1 Driftinnstillinger

Tilluft82

3.1.1.4 AUX

Type >BFOBMS

1010Ingen

3.1.1.4.3.3 OverstyringOverstyring >Normal >Åpen >Stengt >

Nei012

3.1.1.4.3.7 OverstyringOverstyring >Normal >Åpen >Stengt >

Nei012

36/96

3004402-2013-01-24.fm NO - Tilkobling

2.4.1 Styring av luftmengde, tilluftstemperatur og manuell modus/urprogramInnstilling avluftmengden

Innstilling avtilluftstemperaturen

Urprogram Sett Object type BV - Index 00 - BMSInValue.CtrlMode på «1» hvis aggregatet skal til-bake på urprogram.

2.4 Eksempel på styring av anlegg

Trinn Handling

1 Sett aggregatet i manuell modus:Sett Object type BV - Index 00 - BMSInValue.CtrlMode på «0».

2 Sett Object type AV - Index 06 - BMSInValue.AirSP på en verdi mellom 0 og 100 %. Verdien 0 % stopper aggregatet.

Trinn Handling

1 Sett aggregatet i manuell modus: Sett Object type BV - Index 00 - BMSInValue.CtrlMode på «0».

2 Sett Object type AV - Index 07 - BMSInValue.AirSP på en verdi mellom 10 og 35 °C. Merk: Temperatursettpunktet kan være begrenset av andre innstillinger og funksjoner.

37/96

3004402-2013-01-24.fm SE – Inledning

1. SE – Inledning

Luftbehandlingsaggregat (AHU), som är utrustat med en EXHAUSTO EXact/EXact2 styrenhet.BACnet-funktionen är implementerad i EXHAUSTO EXact webbserver med mjukvaraversion 3.0-xxxx eller senare. EXHAUSTO EXact är en BACnet Application SpecificController (B-ASC) med möjlighet att välja data link layer med fullt stöd: BACnet IP eller BACnet MSTP.Vidare hänvisar vi till dokumentet "EXact_EDE_ddmmyy" (Engineering Data Exchange).

TCP/IP: 1 st. 10/100 Mbit Ethernet, RJ45-kontakt.MSTP: 1 st. RS-485

1.1 Översikt

1.2 Kommunikation

1.3 BACnet Interoperability Building Blocks som stöds

Datadelning DS-RP-B Data Sharing-ReadProperty-B

Datadelning DS-RPM-B Data Sharing-ReadPropertyMultiple-B

Datadelning DS-WP-B Data Sharing-WriteProperty-B

Datadelning DS-WPM-B Data Sharing-WritePropertyMultiple-B

Enhetshantering DM-DDB-B Device Management-DynamicDeviceBinding-B

Enhetshantering DM-DOB-B Device Management-DynamicObjectBinding-B

Enhetshantering DM-DCC-B Device Management-DeviceCommunicationControl-B

Enhetshantering DM-RD-B Device Management-ReinitializeDevice-B

38/96

3004402-2013-01-24.fm SE – Inledning

1.4 BACnet IP standardobjekttyper som stöds

StandardobjekttyperRO = Read onlyRW = Read / Write

Egenskaper

Enhet Object_IdentifierObject_NameObject_TypeSystem_StatusVendor_NameVendor_IdentifierModel_NameFirmware_RevisionApplication_Software_VersionProtocol_VersionProtocol_RevisionProtocol_Services_SupportedProtocol_Object_Types_SupportedObject_ListMax_APDU_Length_AcceptedSegmentation_SupportedAPDU_TimeoutNumber_Of_APDU_RetriesDevice_Address_BindingDatabase_Revision

Analog ingång AI (RO) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceUnits

Analogt värde AO (RW)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceUnits

Binär ingång DI (RO) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServicePolarity

39/96

3004402-2013-01-24.fm SE – Inledning

Binärt värde DO (RW) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_Service

Multistate-ingång (RO) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceNumber_Of_States

Multistate-värde (RW) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceNumber_Of_States

StandardobjekttyperRO = Read onlyRW = Read / Write

Egenskaper

40/96

3004402-2013-01-24.fm SE- Anslutning

2. SE- Anslutning

Kabel BACnet MSTP-kabeln ska vara 2 x 2 x 0,25 tvinnad parkabel.

BACnet MSTP-förbindelsen ansluts till huvudstyrningens CN3. Endast BACnet MSTP A, B och stativ får monteras. Se schema.

EXact/EXact2

Förklaring till diagram

CN3: BACnet MSTP (RS-485)

A- och B-signalledningarna (anslutning 2–3) ska vara partvinnade.

Ändterminering Om EXact-/EXact2-styrningen är den sista enheten på kabeln ska ett termineringsmotstånd på 120 Ω monteras. Detta sker via jumper JP2 på webbservern.

2.1 Anslutning MSTP

Klämma Signalbeskrivning1 Får inte anslutas2 RS485 + (A)3 RS485 – (B)4 0VDC (chassi/jord)

41/96

3004402-2013-01-24.fm SE- Anslutning

Anslutning av nätverk

Nätverkskontakten sätts i ethernetanslutningen. Om webbservern ska anslutas direkt till en PC ska en korsad nätverkskabel användas.

MAC-adress Webbserverns MAC-adress finns på webbserver-kortet samt i meny 3.6 på manöverpanelen.

Kabeltyp och längd

2.2.1 Installation av webbserver:Webbservern stödjer både statiska och dynamiska IP-adresser. Detta konfigureras i meny 3.6 på manöverpanelen.

Exempel

Portnummer*) Om man har flera anläggningar på samma router kan man ge dem olika portnummer och använda sig av port forwarding.*) För BACnet är portnumret inställt på 47808. Portnumret gäller endast webbgränssnitt.

2.2 Anslutning av BACnet IP

Kabel Kabellängd

CAT5E STP-kabel (skärmad kabel)

EXHAUSTO rekommenderar max kabellängd: 70 m.

Läs i produkthandboken för EXact om hur du– ändrar inställningar– sparar ändrade inställningar.

DHCP >IP-adress

Undernätmask

Standardgateway

Portnummer >MAC-adress

Återställ lösenord >

3.6 Webbserver

Nej

> 192.168.001.180

> 255.255.255.000

> 192.168.001.00180

00:1F:79:00:00:D0Nej

42/96

3004402-2013-01-24.fm SE- Anslutning

2.2.2 Uppsättning av BACnetExempel

• Man ska välja BACnet MSTP eller BACnet IP under BMS i meny 3.5.

Endast för BACnet MSTP

Ställ in följande värden som definierade av systemansvarig:• Device ID (0 – 255)• Device name – Kan endast ställas in i webbservern• Net Number (1 – 65534)• Adress (0 – 127)• Baud rate (9600, 19200, 115200)

Endast för BACnet IP

Ställ in följande värden som definierade av systemansvarig:• Device ID (0 – 255)• Device name – Kan endast ställas in i webbservern

BMS >Konfiguration >

3.5 BMSIngen

3.5.2 KonfigurationDevice ID >Device name:

Net number >Adress >Baud rate >

0

0Ingen

9

3.5.2 KonfigurationDevice ID >Device name:

0

43/96

3004402-2013-01-24.fm SE- Anslutning

Vid luftregleringsmetod 8, ”Extern styrning av fläkthastigheter”, kan det i vissa driftssituationer vara nödvändigt att överstyra externa spjäll i kanalsystemet. Externa spjäll kan t.ex. vara VAV-spjäll.Vid brand, avfrostning eller nattkylning kan VEX-aggregatet skicka en signal till BMS-anläggningen om att öppna eller stänga spjäll i avlufts- eller tilluftskanalen.

2.3.1 Inställning av överstyrningsfunktion (endast luftregleringsmetod 8)

2.3 Överstyrning av externa spjäll

Steg Åtgärd Displayen visar …

1 • Växla till menyn Inställningar ”–>Anläggning–>Driftinställningar”• Ställ in ”Luft reg.” på ”8”

2 • Växla till menyn ”AUX”• Ställ in ”Typ” på ”BMS”

3 • Växla till menyn ”BMS”• Växla till menyn ”Överstyrning” under ”Tilluft”• Ställ in ”Överstyrning” på ”Ja”• Ställ in ”Normal” på det värde som man vill ska skickas när VEX-

aggregatet inte kräver överstyrning av tilluftsspjäll• Ställ in ”Öppna” på det värde som man vill skicka när VEX-

aggregatet kräver att tilluftsspjäll är öppna• Ställ in ”Stäng” på det värde som man vill skicka när VEX-

aggregatet kräver att tilluftsspjäll är stängda• Växla tillbaka till menyn ”BMS”

3 • Växla till menyn ”Överstyrning” under ”Frånluft”• Ställ in ”Överstyrning” på ”Ja”• Ställ in ”Normal” på det värde som man vill ska skickas när VEX-

aggregatet inte kräver överstyrning av avluftsspjäll• Ställ in ”Öppna” på det värde som man vill skicka när VEX-

aggregatet kräver att avluftsspjäll är öppna• Ställ in ”Stäng” på det värde som man vill skicka när VEX-

aggregatet kräver att avluftsspjäll är stängda• Observera att värdena för Normal, Öppna och Stäng inte får vara

lika.

Om det inte önskas någon överstyrning för en eller båda kanalerna ställs ”Överstyrning” in på ”Nej”.

Inomhusklimatnivåer >Temp. uppmätt >Luft uppmätt >AUX >Regulatorer >

3.1.1 Driftinställningar

Tilluft82

3.1.1.4 AUX

Type >BFOBMS

1010Ingen

3.1.1.4.3.3 ÖverstyrningÖverstyrning >Normal >Öppen >Stängd >

Nej012

3.1.1.4.3.7 ÖverstyrningÖverstyrning >Normal >Öppen >Stängd >

Nej012

44/96

3004402-2013-01-24.fm SE- Anslutning

2.4.1 Styrning av luftflöde, tilluftstemperatur och manuellt/timerprogramInställning avLuftflöden

Inställning avtilluftstemperaturen

Timerprogram Ställ in Object type BV – Index 00 – BMSInValue.CtrlMode på ”1”, om aggregatet ska gå tillbaka på timerprogram

2.4 Exempel på styrning av anläggning

Steg Åtgärd

1 Ställ aggregatet på manuellt läge:Ställ in Object type BV – Index 00 – BMSInValue.CtrlMode på ”0”.

2 Ställ in Object type AV – Index 06 – BMSInValue.AirSP på ett värde mellan 0 och 100 %. Värdet 0% stoppar aggregatet.

Steg Åtgärd

1 Ställ aggregatet på manuellt läge: Ställ in Object type BV – Index 00 – BMSInValue.CtrlMode på ”0”.

2 Ställ in Object type AV – Index 07 – BMSInValue.TempSP på ett värde mellan 10 och 35 °C. Obs! Temperaturinställningspunkten kan vara begränsad av andra inställningar och funktioner.

45/96

3004402-2013-01-24.fm NL - Inleiding

1. NL - Inleiding

Luchtbehandelingsunit (AHU), die voorzien is van een EXact/EXact2-regeleenheid van EXHAUSTO.De BACnet-functionaliteit is geïmplementeerd in de EXact-webserver van EXHAUSTO met softwareversie 3.0-xxxx of nieuwer. EXHAUSTO EXact is een BACnet Application SpecificController (B-ASC) met ondersteuning van de volgende keuzemogelijkheden voor data link layer: BACnet IP of BACnet MSTP.Zie voor meer informatie ook het document "EXact_EDE_ddmmyy" (Engineering Data Exchange).

TCP/IP: 1 st. 10/100 Mbit Ethernet, RJ45-contact.MSTP: 1 st. RS-485

1.1 Overzicht

1.2 Communicatie

1.3 Ondersteuning van BACnet Interoperability Building Blocks

Gegevensuitwisseling

DS-RP-B Data Sharing-ReadProperty-B

Gegevensuitwisseling

DS-RPM-B Data Sharing-ReadPropertyMultiple-B

Gegevensuitwisseling

DS-WP-B Data Sharing-WriteProperty-B

Gegevensuitwisseling

DS-WPM-B Data Sharing-WritePropertyMultiple-B

Apparaatbeheer DM-DDB-B Device Management-DynamicDeviceBinding-B

Apparaatbeheer DM-DOB-B Device Management-DynamicObjectBinding-B

Apparaatbeheer DM-DCC-B Device Management-DeviceCommunicationControl-B

Apparaatbeheer DM-RD-B Device Management-ReinitializeDevice-B

46/96

3004402-2013-01-24.fm NL - Inleiding

1.4 Ondersteunde standaard objecttypen voor BACnet IP

Standaard objecttypenRO = Read OnlyRW = Read / Write

Eigenschappen

Eenheid Object_IdentifierObject_NameObject_TypeSystem_StatusVendor_NameVendor_IdentifierModel_NameFirmware_RevisionApplication_Software_VersionProtocol_VersionProtocol_RevisionProtocol_Services_SupportedProtocol_Object_Types_SupportedObject_ListMax_APDU_Length_AcceptedSegmentation_SupportedAPDU_TimeoutNumber_Of_APDU_RetriesDevice_Address_BindingDatabase_Revision

Analoge ingang AI (RO)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceUnits

Analoge waarde AO (RW)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceUnits

Binaire ingang DI (RO) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServicePolarity

47/96

3004402-2013-01-24.fm NL - Inleiding

Binaire waarde DO (RW)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_Service

Multistate ingang DI (RO)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceNumber_Of_States

Multistate-waarde (RW)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceNumber_Of_States

Standaard objecttypenRO = Read OnlyRW = Read / Write

Eigenschappen

48/96

3004402-2013-01-24.fm NL - Aansluiting

2. NL - Aansluiting

Kabel De BACnet MSTP-kabel moet een getwiste 2 x 2 x 0,25 kabel zijn.

Sluit de BACnet MSTP-verbinding aan op de CN3 van de hoofdregeling. Alleen BACnet MSTP A, B en de massa mogen gemonteerd worden. Zie schema.

EXact/EXact2

Verklaring bij schema

CN3: BACnet MSTP (RS-485)

Het A en B-signaal (klem 2 - 3) moet een getwist aderpaar zijn.

Eindafsluiting Als de EXact/EXact2-regeling de laatste eenheid op de kabel is, moet er een afsluitingsweerstand van 120 Ω worden gemonteerd. Dit doet u via jumper JP2 op de webserver.

2.1 Aansluiting MSTP

Klem Signaalbeschrijving1 Mag niet verbonden worden2 RS485 + (A)3 RS485 – (B)4 0V DC (massa)

49/96

3004402-2013-01-24.fm NL - Aansluiting

Aansluiten van netwerk

Monteer de netwerkstekker in de ethernetstekker. Als de webserver direct op de pc wordt aangesloten, moet een gekruiste netwerkkabel worden gebruikt.

MAC-adres Het MAC-adres van de webserver kan worden afgelezen op de printplaat van de webserver en in menu 3.6 in het HMI-paneel.

Kabeltype en -lengte

2.2.1 Instellen van de webserverDe webserver ondersteunt zowel statische als dynamische IP-adressen. Dit kan worden geconfigureerd in menu 3.6 in het HMI-paneel.

Voorbeeld

Poortnummer*) Indien er meer installaties met dezelfde router verbonden zijn, kan men verschillende poortnummers aan deze installaties toewijzen en zo gebruik maken van 'port forwarding'.*) voor BACnet is het poortnummer vastgesteld op 47808. Het poortnummer is uitsluitend van toepassing op de webinterface.

2.2 Aansluiting BACnet IP

Kabel Kabellengte

CAT5E STP-kabel (afgeschermde kabel)

EXHAUSTO adviseert als max. kabellengte: 70 m.

Zie in de EXact-basishandleidinghoe u:- instellingen wijzigt- gewijzigde instellingen opslaat

DHCP >IP-adres

Submasker

Standaard gateway

Poortnummer >MAC-adres

Reset wachtwoord >

3.6 Webserver

Nee

> 192.168.001.180

> 255.255.255.000

> 192.168.001.00180

00:1F:79:00:00:D0Nee

50/96

3004402-2013-01-24.fm NL - Aansluiting

2.2.2 Instellen van BACnetVoorbeeld

• Er moet worden gekozen voor BACnet MSTP of BACnet IP uit voor BMS in menu 3.5.

Alleen voor BACnet MSTP

Stel de volgende waarden in zoals gedefinieerd door de systeembeheerder:• Device ID (0 - 255)• Device name - Opgelet: kan alleen in de webserver ingesteld worden• Net Number (1 - 65534)• Adress (0 - 127)• Baud rate (9600, 19200, 115200)

Alleen voor BACnet IP

Stel de volgende waarden in zoals gedefinieerd door de systeembeheerder:• Device ID (0 - 255)• Device name - Opgelet: kan alleen in de webserver ingesteld worden

BMS >Configuratie >

3.5 BMSGeen

3.5.2 ConfiguratieDevice ID >Device name:

Net number >Adress >Baud rate >

0

0Geen

9

3.5.2 ConfiguratieDevice ID >Device name:

0

51/96

3004402-2013-01-24.fm NL - Aansluiting

Bij luchtregelmethode 8, "Externe regeling van ventilatorsnelheden", kan het onder bepaalde bedrijfsomstandigheden noodzakelijk zijn om een externe klep in het kanaalsysteem over te nemen. Zo'n externe klep kan bijv. een VAV -klep zijn.Bij brand, ontdooien of nachtkoeling kan de VEX-unit een signaal sturen voor de BMS-installatie om een klep in het afvoer- of toevoerluchtkanaal te openen of te sluiten.

2.3.1 Instelling van overnamefunctie (alleen voor luchtregelmethode 8)

2.3 Overnemen van externe klep

Stap Handeling Het display toont...

1 • Wissel naar menu-instellingen "->Installatie->Bedrijfsinstellingen"• Stel "Luchtreg." in op "8"

2 • Wissel naar menu "AUX"• Stel "Type" in op "BMS"

3 • Wissel naar menu "BMS"• Wissel naar menu "Overnemen" onder "Toevoerlucht"• Stel "Overnemen" in op "Ja"• Stel "Normaal" in op de waarde die moet worden verzonden als de

VEX-unit geen overname van de toevoerluchtklep vereist• Stel "Open" in op de waarde die moet worden verzonden als de

VEX-unit vereist dat de toevoerluchtklep open is• Stel "Sluiten" in op de waarde die verzonden moet worden als de

VEX-unit vereist dat de toevoerluchtklep gesloten is• Wissel terug naar het menu "BMS"

3 • Wissel naar het menu "Overnemen" onder "Afvoerlucht"• Stel "Overnemen" in op "Ja"• Stel "Normaal" in op de waarde die moet worden verzonden als de

VEX-unit geen overname van de afvoerluchtklep vereist• Stel "Open" in op de waarde die moet worden verzonden als de

VEX-unit vereist dat de afvoerluchtklep open is• Stel "Sluiten" in op de waarde die verzonden moet worden als de

VEX-unit vereist dat de afvoerluchtklep gesloten is• Denk eraan dat de waarden voor Normaal, Open en Gesloten niet

hetzelfde mogen zijn.

Stel, wanneer overname van een of beide kanalen niet gewenst is, "Overnemen" in op "Nee".

Binnenklimaatniveaus >Temp. reg. >Luchtreg. >AUX >Regelaars >

3.1.1 Bedrijfsinstellingen

Toevoer82

3.1.1.4 AUX

Type >BFOBMS

1010Geen

3.1.1.4.3.3 OpheffenOpheffen >Normaal >Open >Dicht >

Nee012

3.1.1.4.3.7 OpheffenOpheffen >Normaal >Open >Dicht >

Nee012

52/96

3004402-2013-01-24.fm NL - Aansluiting

2.4.1 Regeling van luchtvolume, toevoerluchttemperatuur en handmatige stand/klokprogramma

Instelling vanhet luchtvolume...

Instelling vande toevoerluchttemperatuur

Klokprogramma Zet objecttype BV - Index 00 - BMSInValue.CtrlMode op "1" als de unit terug moet gaan naar het klokprogramma.

2.4 Voorbeeld van installatieregeling

Stap Handeling

1 Zet de unit in de handmatige stand:Zet objecttype BV - Index 00 - BMSInValue.CtrlMode op "0".

2 Zet objecttype AV - Index 06 - BMSInValue.AirSP op een waarde tussen 0 en 100%. De waarde 0% stopt de unit.

Stap Handeling

1 Zet de unit in de handmatige stand: Zet objecttype BV - Index 00 - BMSInValue.CtrlMode op "0".

2 Zet objecttype AV - Index 07 - BMSInValue.TempSP op een waarde tussen 10 en 35%. NB: Let erop dat het instelpunt voor de temperatuur beperkt kan zijn door andere instellingen en functies.

53/96

3004402-2013-01-24.fm FI - Johdanto

1. FI - Johdanto

Ilmankäsittelykone (AHU) on varustettu EXHAUSTO EXact/EXact2 -ohjausyksiköllä.BACnet-toiminto on käytössä EXHAUSTO EXact -web-palvelimessa, jonka ohjelmisto-versio on 3.0-xxxx tai uudempi. EXHAUSTO EXact on BACnet Application SpecificController (B-ASC). Siinä on seuraavat data link layer -vaihtoehdot: BACnet IP tai BACnet MSTP.Lisätietoja on asiakirjassa "EXact_EDE_ddmmyy" (Engineering Data Exchange).

TCP/IP: 1 kpl 10/100 Mbit Ethernet, RJ45-liitäntä.MSTP: 1 kpl RS-485

1.1 Yleiskuvaus

1.2 Tiedonsiirto

1.3 BACnet Interoperability Building Blocks -yhteensopivuus

Tietojen jakaminen DS-RP-B Data Sharing-ReadProperty-B

Tietojen jakaminen DS-RPM-B Data Sharing-ReadPropertyMultiple-B

Tietojen jakaminen DS-WP-B Data Sharing-WriteProperty-B

Tietojen jakaminen DS-WPM-B Data Sharing-WritePropertyMultiple-B

Yksikön käsittely DM-DDB-B Device Management-DynamicDeviceBinding-B

Yksikön käsittely DM-DOB-B Device Management-DynamicObjectBinding-B

Yksikön käsittely DM-DCC-B Device Management-DeviceCommunicationControl-B

Yksikön käsittely DM-RD-B Device Management-ReinitializeDevice-B

54/96

3004402-2013-01-24.fm FI - Johdanto

1.4 Yhteensopivat BACnet IP -vakio-objektityypit

Vakio-objektityypitRO = Vain luku (Read only)RW = Luku/kirjoitus (Read / Write)

Ominaisuudet

Yksikkö Object_IdentifierObject_NameObject_TypeSystem_StatusVendor_NameVendor_IdentifierModel_NameFirmware_RevisionApplication_Software_VersionProtocol_VersionProtocol_RevisionProtocol_Services_SupportedProtocol_Object_Types_SupportedObject_ListMax_APDU_Length_AcceptedSegmentation_SupportedAPDU_TimeoutNumber_Of_APDU_RetriesDevice_Address_BindingDatabase_Revision

Analoginen tulo AI (RO)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceYksiköt

Analoginen arvo AO (RW)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceUnits

Binaarinen tulo DI (RO)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServicePolarity

55/96

3004402-2013-01-24.fm FI - Johdanto

Binaarinen arvo DO (RW)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_Service

Multistate-tulo (RO) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceNumber_Of_States

Multistate-arvo (RW) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceNumber_Of_States

Vakio-objektityypitRO = Vain luku (Read only)RW = Luku/kirjoitus (Read / Write)

Ominaisuudet

56/96

3004402-2013-01-24.fm FI - Liitäntä

2. FI - Liitäntä

Kaapeli BACnet MSTP -kaapelin tulee olla 2 x 2 x 0,25 -kokoinen kierretty parikaapeli.

BACnet MSTP -liitäntä kytketään pääohjauksen CN3:een. Vain BACnet MSTP A, B ja runko voidaan asentaa. Katso kaaviota.

EXact/EXact2

Kaavioiden selitykset

CN3: BACnet MSTP (RS-485)

A- ja B-signaalin (liitännät 2-3) on oltava parikierretty.

Terminointi Jos EXact/EXact2-ohjaus on kaapelin viimeinen yksikkö, on asennettava 120 Ω:n terminointivastus. Tämä tehdään web-palvelimen JP2-hyppyjohtimella.

2.1 MSTP-liitäntä

Liitäntä Signaalin kuvaus1 Ei voida liittää2 RS485 + (A)3 RS485 – (B)4 0V DC (runko)

57/96

3004402-2013-01-24.fm FI - Liitäntä

Yhdistäminen verkkoon

Verkkopistoke asennetaan Ethernet-liitäntään. Jos web-palvelin liitetään suoraan tietokoneeseen, on käytettävä ristiinkytkettyä verkkokaapelia.

MAC-osoite Web-palvelimen MAC-osoite voidaan lukea web-palvelinpiiristä ja HMI-paneelin valikosta 3.6.

Kaapelin tyyppi ja pituus

2.2.1 Web-palvelimen säädötWeb-palvelin tukee staattisia ja dynaamisia IP-osoitteita. Ne määritetään HMI-paneelin valikossa 3.6.

Esimerkki

Portin numero*) Jos samaan reitittimeen on yhdistetty useita laitteistoja, niille voidaan antaa erilaiset porttien numerot. Tällöin port forwarding on käytettävissä.*) BACnet-portin numeron aina 47808. Portin numero koskee vain web-käyttöliittymää

2.2 BACnet IP -liitäntä

Kaapeli Kaapelin pituus

CAT5E STP-kaapeli (suojattu) EXHAUSTOn suosittelema kaapelin enimmäispituus: 70 m.

Katso EXact-käyttöoppaasta, kuinka- muutat asetuksia- tallennat muutetut asetukset.

DHCPIP-osoite

Aliverkkomaski

Vakioväylä

Porttinumero >MAC-osoite

Vaihda salasana >

3.6 Web-palvelin

Ei

> 192.168.001.180

> 255.255.255.000

> 192.168.001.00180

00:1F:79:00:00:D0Ei

58/96

3004402-2013-01-24.fm FI - Liitäntä

2.2.2 BACnet-asetuksetEsimerkki

• Valikossa 3.5 on valittava BMS-asetukseksi BACnet MSTP tai BACnet IP.

Vain BACnet MSTP

Aseta seuraavat järjestelmän pääkäyttäjän määrittämät arvot:• Device ID (0 - 255)• Device name - voidaan asettaa vain Web-palvelimessa• Net Number (1 - 65534)• Adress (0 - 127)• Baud rate (9600, 19200, 115200)

Vain BACnet IP

Aseta seuraavat järjestelmän pääkäyttäjän määrittämät arvot:• Device ID (0 - 255)• Device name - voidaan asettaa vain Web-palvelimessa

BMS >Konfiguraatio >

3.5 BMSEi

3.5.2 MääritysDevice ID >Device name:

Net number >Adress >Baud rate >

0

0Ei mitään

9

3.5.2 MääritysDevice ID >Device name:

0

59/96

3004402-2013-01-24.fm FI - Liitäntä

Jos käytössä on ilmansäätömenetelmä 8 Puhallinnopeuksien ulkoinen säätö, tietyissä käyttötilanteissa on ohitusohjattava kanavajärjestelmän ulkoisia peltejä. Ulkoinen pelti voi olla esimerkiksi VAV-pelti.Tulipalo-, jäänpoisto- tai yöjäähdytystilanteessa VEX-laite voi lähettää signaalin BMS-laitteelle tulo- tai poistoilmakanavan pellin avaamiseksi tai sulkemiseksi.

2.3.1 Ohitusohjaustoiminnon asetukset (vain ilmansäätömenetelmä 8)

2.3 Ulkoisten peltien ohitusohjaaminen

Vaihe Toimenpide Näytön näkymä

1 • Siirtää edelliseen Asetukset ->Laitteisto ->Käyttöasetukset -valikkoon.

• Valitse Ilman rek. -asetukseksi 8.

2 • Siirtää AUX-valikkoon.• Aseta Tyyppi-asetukseksi BMS.

3 • Siirtää BMS-valikkoon.• Siirtää Tuloilma-kohdan Ohitusohjaus-valikkoon.• Valitse Ohitusohjaus-asetukseksi Kyllä.• Aseta Normaali-kohtaan arvo, joka halutaan lähettää, kun VEX-

laitteen ei tarvitse ohitusohjata tuloilmapeltiä.• Aseta Avaa-kohtaan arvo, joka halutaan lähettää, kun VEX-

laitteen täytyy avata tuloilmapelti.• Aseta Sulje-kohtaan arvo, joka halutaan lähettää, kun VEX-

laitteen täytyy sulkea tuloilmapelti.• Siirtää takaisin BMS-valikkoon.

3 • Siirtää Poistoilma-kohdan Ohitusohjaus-valikkoon.• Valitse Ohitusohjaus-asetukseksi Kyllä.• Aseta Normaali-kohtaan arvo, joka halutaan lähettää, kun VEX-

laitteen ei tarvitse ohitusohjata poistoilmapeltiä.• Aseta Avaa-kohtaan arvo, joka halutaan lähettää, kun VEX-

laitteen täytyy avata poistoilmapelti.• Aseta Sulje-kohtaan arvo, joka halutaan lähettää, kun VEX-

laitteen täytyy sulkea poistoilmapelti.• Huomaa, että Normaali-, Avaa- ja Sulje-arvot eivät saa olla

samoja.

Jos ohitusohjausta ei tarvita, yhden kanavan tai molempien kanavien Ohitusohjaus-arvoksi asetetaan Ei.

Sisäilmastotasot >Lämpöt.säätö >Ilmav.säätö >AUX >Säätimet >

3.1.1 Käytön asetukset

Tuloilma82

3.1.1.4 AUX

Tyyppi >BFOBMS

1I010Ei

3.1.1.4.3.3 YliohjausYliohjaus >Normaali >Avoin >Suljettu >

Ei012

3.1.1.4.3.7 YliohjausYliohjaus >Normaali >Avoin >Suljettu >

Ni012

60/96

3004402-2013-01-24.fm FI - Liitäntä

2.4.1 Ilmamäärän, tuloilman lämpötilan ja manuaalisen tilan / ajastusohjelman ohjausIlmamääränasetus

Tuloilman lämpötilanasetus

Ajastinohjelma Aseta Object type BV - Index 00 - BMSInValue.CtrlMode -arvoksi 1, jos laitteiston halutaan palaavan ajastinohjelmaan.

2.4 Esimerkki laitteiston ohjaamisesta

Vaihe Toimenpide

1 Siirrä laite manuaaliseen tilaan.Aseta Object type BV - Index 00 - BMSInValue.CtrlMode -arvoksi 0.

2 Aseta Object type AV - Index 06 - BMSInValue.AirSP -arvo väliltä 0 - 100 %. Arvo 0 % pysäyttää laitteen.

Vaihe Toimenpide

1 Siirrä laite manuaaliseen tilaan. Aseta Object type BV - Index 00 - BMSInValue.CtrlMode -arvoksi 0.

2 Aseta Object type AV - Index 07 - BMSInValue.TempSP -arvo alueelle 10 - 35 °C. Huomaa: Muut asetukset ja toiminnot voivat rajoittaa lämpötilan asetuspistettä.

61/96

3004402-2013-01-24.fm FR - Introduction

1. FR - Introduction

Appareil de traitement de l'air (AHU) équipé d'une unité de commande EXHAUSTO EXact/EXact2.La fonction BACnet est implémentée dans le serveur web EXHAUSTO EXact avec le le logicielversion 3.0-xxxx ou plus récente. EXHAUSTO EXact est un BACnet Application SpecificController (B-ASC) avec des possibilités de choix par couches liaison de données de soutien : BACnet IP ou BACnet MSTP.De plus, nous vous conseillons de consulter le document "EXact_EDE_ddmmyy" (Engineering Data Exchange).

TCP/IP : 1 x 10/100 Mbit Ethernet, contact RJ45.MSTP : 1 x RS-485

1.1 Aperçu

1.2 Communication

1.3 BACnet Interoperability Building Blocks de soutien

Partage des données

DS-RP-B Data Sharing-ReadProperty-B

Partage des données

DS-RPM-B Data Sharing-ReadPropertyMultiple-B

Partage des données

DS-WP-B Data Sharing-WriteProperty-B

Partage des données

DS-WPM-B Data Sharing-WritePropertyMultiple-B

Maniement de l'unité

DM-DDB-B Device Management-DynamicDeviceBinding-B

Maniement de l'unité

DM-DOB-B Device Management-DynamicObjectBinding-B

Maniement de l'unité

DM-DCC-B Device Management-DeviceCommunicationControl-B

Maniement de l'unité

DM-RD-B Device Management-ReinitializeDevice-B

62/96

3004402-2013-01-24.fm FR - Introduction

1.4 Types d'objets standard BACnet IP de soutien

Types d'objets standardRO = Read onlyRW = Read / Write

Propriétés

Unité Object_IdentifierObject_NameObject_TypeSystem_StatusVendor_NameVendor_IdentifierModel_NameFirmware_RevisionApplication_Software_VersionProtocol_VersionProtocol_RevisionProtocol_Services_SupportedProtocol_Object_Types_SupportedObject_ListMax_APDU_Length_AcceptedSegmentation_SupportedAPDU_TimeoutNumber_Of_APDU_RetriesDevice_Address_BindingDatabase_Revision

Entrée analogique AI (RO)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceUnits

Valeurs analogiques AO (RW)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceUnits

Entrée binaire DI (RO) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServicePolarité

63/96

3004402-2013-01-24.fm FR - Introduction

Valeur binaire DO (RW)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_Service

Entrée Multistate (RO) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceNumber_Of_States

Valeur Multistate (RW) Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceNumber_Of_States

Types d'objets standardRO = Read onlyRW = Read / Write

Propriétés

64/96

3004402-2013-01-24.fm FR - Raccordement

2. FR - Raccordement

Câble Le câble MSTP de BACnet doit être un câble à paire torsadée 2 x 2 x 0,25 .

La connexion BACnet MSTP est raccordée à la commande principale CN3. Monter uniquement BACnet MSTP A, B et la mise à la terre. Voir diagramme.

EXact/EXact2

Explication du diagramme

CN3 : BACnet MSTP (RS-485)

Le signal A et B (borne 2 - 3) doit être à paire torsadée.

Connecteur d'extrémité

Si la commande EXact/EXact2 est la dernière unité sur le câble, monter une résistance de terminaison de 120 Ω. Pour ce faire, utiliser le jumper JP2 sur le serveur web.

2.1 Raccordement MSTP

Borne Description du signal1 Ne doit pas être raccordé2 RS485 + (A)3 RS485 – (B)4 0V DC (mise à la terre)

65/96

3004402-2013-01-24.fm FR - Raccordement

Raccordement du réseau

Monter le raccordement de réseau dans le connecteur Ethernet Si le serveur web doit être raccordé directement au niveau du PC, utiliser un câble de réseau croisé.

Adresse MAC L'adresse MAC du serveur web peut être consultée sur la platine du serveur web ainsi que dans le menu 3.6 dans le panneau HMI.

Type et longueur de câble

2.2.1 Configuration du serveur webLe serveur web soutient aussi bien les adresses IP statiques que dynamiques. La configuration s'effectue dans le menu 3.6 dans le panneau HMI.

Exemple

Numéro de port*) Si plusieurs installations sont raccordées sur le même routeur, il est possible de leur attribuer des numéros de port différents et d'utiliser le transfert de port.*) Le numéro de port fixe de BACnet est 47808. Le numéro de port n'est valable que pour l'interface web.

2.2 Raccordement IP BACnet

Câble Longueur de câble

Câble CAT5E STP (câble isolé) EXHAUSTO recommande une longueur de câble max. : 70 m

Consulter les instructions de basdans EXact pour :- modifier les réglages- sauvegarder les réglages modif

DHCP >Adresse IP

Masque de sous-réseau

Accès standard

Numéro port >Adresse MAC

Réinit. mot passe >

3.6 Seveur Web

Non

> 192.168.001.180

> 255.255.255.000

> 192.168.001.00180

00:1F:79:00:00:D0Non

66/96

3004402-2013-01-24.fm FR - Raccordement

2.2.2 Configuration de BACnetExemple

• Sélectionner BACnet MSTP ou BACnet IP depuis BMS dans le menu 3.5.

Uniquement pour BACnet MSTP

Régler les valeurs suivantes telles que définies par le responsable de système :• Device ID (0 - 255)• Device name - Remarque : peut uniquement être réglé dans le serveur web• Net Number (1 - 65534)• Adress (0 - 127)• Baud rate (9600, 19200, 115200)

Uniquement pour BACnet IP

Régler les valeurs suivantes telles que définies par le responsable de système :• Device ID (0 - 255)• Device name - Remarque : peut uniquement être réglé dans le serveur web

BMS >Configuration >

3.5 BMSAucun

3.5.2 ConfigurationDevice ID >Device name:

Net number >Adress >Baud rate >

0

0Aucun

9

3.5.2 MääritysDevice ID >Device name:

0

67/96

3004402-2013-01-24.fm FR - Raccordement

Lors de l'application de la méthode de régulation de l'air 8 "Commande externe des vitesses du ventilateur", il peut arriver, dans certaines situations de service, qu'il devienne nécessaire d'asservir le registre externe dans le système du conduit. Un registre externe est par ex. le registre VAV. En cas d'incendie, de gel ou de rafraîchissement nocturne, le VEX peut envoyer un signal à l'installation BMS pour ouvrir ou fermer le registre dans le conduit d'air soufflé ou d'air extrait.

2.3.1 Réglage de la fonction d'asservissement (uniquement pour la méthode de régulation de l'air 8)

2.3 Commande asservie du registre externe

Action Handling L'écran affiche...

1 • Passer au menu Réglages“->Installation->Réglages de service”• Régler ”Rég air.” sur ”8”

2 • Passer au menu ”AUX”• Régler ”Type” sur ”BMS”

3 • Passer au menu ”BMS”• Passer au menu ”Asservissement” sous ”Air extrait”• Régler ”Asservissement” sur ”Oui”• Régler ”Normal” à la valeur que vous souhaitez envoyer lorsque le

VEX ne nécessite pas un asservissement du registre d'air extrait• Régler ”Ouvert” à la valeur que vous souhaitez envoyer lorsque le

VEX nécessite l'ouverture du registre d'air extrait• Régler ”Fermer” à la valeur que vous souhaitez envoyer lorsque le

VEX nécessite la fermeture du registre d'air extrait• Retourner au menu ”BMS”

3 • Passer au menu ”Asservissement” sous ”Air souffl锕 Régler ”Asservissement” sur ”Oui”• Régler ”Normal” à la valeur que vous souhaitez envoyer lorsque le

VEX ne nécessite pas un asservissement du registre d'air soufflé• Régler ”Ouvert” à la valeur que vous souhaitez envoyer lorsque le

VEX nécessite l'ouverture du registre d'air soufflé• Régler ”Fermer” à la valeur que vous souhaitez envoyer lorsque le

VEX nécessite la fermeture du registre d'air soufflé• Veuillez noter que les valeurs pour Normal, Ouvert et Fermé ne

doivent pas être identiques.

Niveaux air ambiant >Régul. temp. >Régulation air >AUX >Régulateurs >

3.1.1 Réglages fonctionnem.

Évacué82

3.1.1.4 AUX

Type >BFOBMS

1010Aucun

3.1.1.4.3.3 SurpassementSurpassement >Normal >Ouvert >Fermé >

Non012

3.1.1.4.3.7 SurpassementSurpassement >Normal >Ouvert >Fermé >

Non012

68/96

3004402-2013-01-24.fm FR - Raccordement

Si vous ne souhaitez pas d'asservissement pour l'un ou les deux conduits, réglez "Asservissement" sur "Non".

Action Handling L'écran affiche...

69/96

3004402-2013-01-24.fm FR - Raccordement

2.4.1 Commande du débit d'air, de la température de l'air extrait et du programme manuel mode/heure

Réglage dudébit d'air

Réglage de la température de l'air extrait

Programme heure Régler Object type BV - Index 00 - BMSInValue.CtrlMode sur “1”, si l'appareil doit être commuté sur le programme heure.

2.4 Exemple de commande de l'installation

Action Handling

1 Régler l'appareil en mode manuel :Régler Object type BV - Index 00 - BMSInValue.CtrlMode sur “0”.

2 Régler Object type AV - Index 06 - BMSInValue.AirSP sur une valeur située entre 0 et 100%. La valeur 0% coupe l'appareil.

Action Handling

1 Régler l'appareil en mode manuel : Régler Object type BV - Index 00 - BMSInValue.CtrlMode sur “0”.

2 Régler Object type AV - Index 07 - BMSInValue.TempSP sur une valeur située entre 10 et 35°C. Remarque : le point de réglage de la température peut être limité par d'autres réglages et fonctions.

70/96

3004402-2013-01-24.fm RU - Вводная часть

1. RU - Вводная часть

Приточно-вытяжная установка (AHU) с блоком автоматического управления EXHAUSTO EXact2.Функциональность BACnet реализуется в веб-сервере EXHAUSTO EXact с программным обеспечениемверсии 3.0-xxxx или новее. EXHAUSTO EXact представляет собой ориентированный на специфическое приложение BACnetконтроллер (B-ASC) с возможностью выбора уровня передачи данных: BACnet IP или BACnet MSTP.См. также документ "EXact_EDE_ddmmyy" (Обмен техническими данными).

TCP/IP: Разъем RJ45, 10/100 Mbit Ethernet, 1 шт.MSTP: 1 шт. RS-485.

1.1 Обзор

1.2 Обмен данными

1.3 Поддерживаемые функционально совместимые модули BACnet

Совместное использование данных

DS-RP-B Data Sharing-ReadProperty-B

Совместное использование данных

DS-RPM-B Data Sharing-ReadPropertyMultiple-B

Совместное использование данных

DS-WP-B Data Sharing-WriteProperty-B

Совместное использование данных

DS-WPM-B Data Sharing-WritePropertyMultiple-B

Управление устройствами

DM-DDB-B Device Management-DynamicDeviceBinding-B

Управление устройствами

DM-DOB-B Device Management-DynamicObjectBinding-B

Управление устройствами

DM-DCC-B Device Management-DeviceCommunicationControl-B

Управление устройствами

DM-RD-B Device Management-ReinitializeDevice-B

71/96

3004402-2013-01-24.fm RU - Вводная часть

1.4 Поддерживаемые в BACnet типы объектов по стандарту IP

Стандартные типы объектовRO = Read only (только для считывания)RW = Read / Write (для чтения и записи)

Свойства

Модуль Object_IdentifierObject_NameObject_TypeSystem_StatusVendor_NameVendor_IdentifierModel_NameFirmware_RevisionApplication_Software_VersionProtocol_VersionProtocol_RevisionProtocol_Services_SupportedProtocol_Object_Types_SupportedObject_ListMax_APDU_Length_AcceptedSegmentation_SupportedAPDU_TimeoutNumber_Of_APDU_RetriesDevice_Address_BindingDatabase_Revision

Аналоговый вход AI (RO)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceUnits

Аналоговая величина AO (RW)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceUnits

Двоичный вход DI (RO)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServicePolarity

72/96

3004402-2013-01-24.fm RU - Вводная часть

Двоичная величина DO (RW)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_Service

Вход данных о нескольких состояниях (RO)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceNumber_Of_States

Величина с несколькими состояниями (RW)

Object_IdentifierObject_NameObject_TypePresent_ValueStatus_FlagsEvent_StateOut_Of_ServiceNumber_Of_States

Стандартные типы объектовRO = Read only (только для считывания)RW = Read / Write (для чтения и записи)

Свойства

73/96

3004402-2013-01-24.fm RU - Электрическое подключение

2. RU - Электрическое подключение

Кабель Кабельное соединение MSTP для BACnet должно осуществляться по стандартной витой паре 2 x 2 x 0,25 .

Кабель MSTP для BACnet присоединяют к CN3 главного блока управления. Допускается только монтаж кабеля BACnet MSTP A, B и корпуса. См. схему.

EXact/EXact2

Условные обозначения на схеме

CN3: BACnet MSTP (RS-485)

Сигнал А и В (клемма 2 - 3) должен идти по витой паре.

Оконцевание/терминирование

Если блок управления EXact/EXact2 является последним устройством, присоединенным к кабелю, необходимо установить оконечный резистор 120Ω. Это производится через джампер JP2 на веб-сервере.

2.1 Подключение MSTP

Клемма Описание сигнала1 Соединений не допускается2 RS485 + (A)3 RS485 – (B)4 0V DC (Корпус)

74/96

3004402-2013-01-24.fm RU - Электрическое подключение

Сетевое подключение

Сетевой разъем монтируют в разъем ethernet. Если веб-сервер требуется подключить непосредственно к ПК, необходимо использовать скроссированный сетевой кабель.

MAC-адрес MAC-адрес веб-сервера можно считать с печатной платы веб-сервера или в меню 3.6 пульта управления/ЧМИ.

Тип и длина кабеля

2.2.1 Настройка веб-сервераВеб-сервер поддерживает как статические, так и динамические IP-адреса. Конфигурирование производится в меню 3.6 пульта управления/ЧМИ.

Пример

№ порта*) Если к одному маршрутизатору (роутеру) подключено несколько установок, можно присвоить каждой из них собственный номер порта и воспользоваться переадресацией портов.*) Для BACnet номер порта жестко задан как 47808. Номер порта действителен

2.2 Подключение BACnet IP

Кабель Длина кабеля

Кабель CAT5E STP (экранированный кабель)

EXHAUSTO рекомендует макс. длину кабеля: 70 м.

См. в «Автоматика EXact, Общо том, как- изменить настройки- сохранить произведенные изм

DHCP >IP-

. >MAC-

>

3.6 -

> 192.168.001.180

> 255.255.255.000

> 192.168.001.00180

00:1F:79:00:00:D0

75/96

3004402-2013-01-24.fm RU - Электрическое подключение

только для веб-интерфейса.2.2.2 Настройка BACnet

Пример

• В меню 3.5 для СУЗ необходимо выбрать BACnet MSTP или BACnet IP.

Только для BACnet MSTP

Задайте следующие значения величин, определенные системным администратором:

• Device ID (0 - 255) • Device name - Обратите внимание, может быть задано только в Веб-

сервере • Net Number (1 - 65534) • Address (0 - 127) • Baud rate (9600, 19200, 115200)

Только для BACnet IP

Задайте следующие значения величин, определенные системным администратором:

• Device ID (0 - 255) • Device name - Обратите внимание, может быть задано только в Веб-

сервере

BMS > >

3.5 BMS

3.5.2 Device ID >Device name:

Net number >Adress >Baud rate >

0

0

9

3.5.2 Device ID >Device name:

0

76/96

3004402-2013-01-24.fm RU - Электрическое подключение

При использовании метода регулирования качества воздуха №8 «Внешнее управление скоростью вращения вентиляторов», в некоторых ситуациях может быть необходима блокировка автоматического управления заслонками в системе воздуховодов. Внешние заслонки могут быть, например, рассчитаны на переменный расход воздуха (VAV).При пожаре, замерзании или ночном охлаждении агрегат VEX может направлять СУЗ сигнал о необходимости открыть или закрыть заслонку в канале приточного или вытяжного воздуха.

2.3.1 Настройка функции блокировки автоматики (только при методе регулирования

качества воздуха №8)

2.3 Подавление (Блокировка автоматики) внешних заслонок

Шаг Действие На дисплей выводится...

1 • Перейдите в меню «Настройки->системы>эксплуатации» • Выставьте «Рег. возд.» как 8

2 • Перейдите в меню «ДОП» • Задайте «Тип» как «СУЗ»

3 • Перейдите в меню «СУЗ» • Выберите меню «Блокировка» под «Приток» • Задайте «Блокировка» как «Да» • Настройте «Нормально» на то значение, которое нужно будет

высылать, когда агрегат VEX не требует блокировки автоматики заслонок притока

• Настройте «Открыть» на то значение, которое нужно будет высылать, когда агрегат VEX требует открытия заслонок притока

• Настройте «Закрыть» на то значение, которое нужно будет высылать, когда агрегат VEX требует закрытия заслонок притока

• Вернитесь в меню «СУЗ»

. . . . >. . >. . . >

. . > >

3.1.1

82

3.1.1.4 . .

>BFOBMS

3.1.1.4.3.3 > >

> >

012

77/96

3004402-2013-01-24.fm RU - Электрическое подключение

3 • Выберите меню «Блокировка» под «Вытяжка» • Задайте «Блокировка» как «Да» • Настройте «Нормально» на то значение, которое нужно будет

высылать, когда агрегат VEX не требует блокировки автоматики заслонок вытяжки

• Настройте «Открыть» на то значение, которое нужно будет высылать, когда агрегат VEX требует открытия заслонок вытяжки

• Настройте «Закрыть» на то значение, которое нужно будет высылать, когда агрегат VEX требует закрытия заслонок вытяжки

• Обратите внимание, значения «Нормально», «Открыть» и «Закрыть» не должны совпадать.

Если возможность блокировки не требуется для одного или обоих каналов, «Блокировка» выставляется как «Нет».

Шаг Действие На дисплей выводится...

3.1.1.4.3.7 > >

> >

012

78/96

3004402-2013-01-24.fm RU - Электрическое подключение

2.4.1 Регулирование расхода воздуха, температуры приточного воздуха и ручной режим/программа таймера

Настройкарасхода воздуха

Настройкатемпературы приточного воздуха

Программа таймера

2.4 Примеры управления установкой

Шаг Действие

1 Переведите агрегат в ручной режим:Задайте Object type BV - Index 00 - BMSInValue.CtrlMode как 0.

2 Задайте Object type AV - Index 06 - BMSInValue.AirSP как значение между 0 и 100%. Значение 0% остановит агрегат.

Шаг Действие

1 Переведите агрегат в ручной режим: Задайте Object type BV - Index 00 - BMSInValue.CtrlMode как 0.

2 Задайте Object type AV - Index 07 - BMSInValue.TempSP как значение между 10 и 35°C. Внимание: Значение уставки температуры может ограничиваться другими настройками и функциями.

79/96

3004402-2013-01-24.fm Appendix - Complete list of Registers - in English

3.A

ppen

dix

- Com

plet

e lis

t of R

egis

ters

- in

Eng

lish

3.1

App

endi

x

3.1.

1O

bjec

t typ

e AV

Inde

xN

ame

Def

ault

valu

ePo

ll in

terv

alU

nit

Des

crip

tion

00BM

SInV

alue

.Tim

eSec

ond

60.0

3073

/Sec

onds

Seco

nd fr

om in

tern

al re

al ti

me

cloc

k01

BMSI

nVal

ue.T

imeM

inut

e60

.030

72/M

inut

esM

inut

e fro

m in

tern

al re

al ti

me

cloc

k02

BMSI

nVal

ue.T

imeH

our

2430

71/H

ours

Hou

r fro

m in

tern

al re

al ti

me

cloc

k03

BMSI

nVal

ue.T

imeD

ay0

3070

/Day

Day

in m

onth

from

inte

rnal

real

tim

e cl

ock

04BM

SInV

alue

.Tim

eMon

th0

3068

/Mon

thM

onth

from

inte

rnal

real

tim

e cl

ock

05BM

SInV

alue

.Tim

eYea

r20

9930

67/Y

ear

Year

from

inte

rnal

real

tim

e cl

ock

06BM

SInV

alue

.AirS

P10

0130

98/%

Airfl

ow s

et p

oint

.Th

is re

gist

er s

ets

the

airfl

ow s

et p

oint

. The

val

ue is

onl

y us

ed if

Ctrl

Mod

e =

0 fo

r “O

bjec

t typ

e BV

- In

dex0

0 - B

MSI

nVal

ue”.

07BM

SInV

alue

.Tem

pSP

030

62/°C

Tem

pera

ture

set

poi

nt:

This

regi

ster

is u

sed

to s

et th

e te

mpe

ratu

re s

et p

oint

to th

e su

pply

air

or ro

om te

mpe

ratu

re

regu

lato

r, de

pend

ing

the

conf

igur

atio

n. T

he v

alue

is o

nly

used

if C

trlM

ode

= 0

for “

Obj

ect t

ype

BV -

Inde

x00

- BM

SInV

alue

”.08

BMSI

nVal

ue.A

irSPF

ixed

1000

130

87/ l

/sFi

xed

airfl

ow s

et p

oint

:Th

is re

gist

er s

ets

the

airfl

ow s

et p

oint

for t

he e

xtra

ct a

ir ai

r fan

or s

uppl

y ai

r fan

, whe

n us

ing

air

regu

latio

n m

etho

d 4

or 3

.09

BMSI

nVal

ue.B

alan

ce0

3095

Air b

alan

ce:

This

regi

ster

indi

cate

s th

e ba

lanc

e se

t poi

nt b

etw

een

supp

ly a

ir an

d ex

tract

air

set p

oint

.10

BMSI

nVal

ue.R

H0

3098

/%R

elat

ive

hum

idity

:Th

is re

gist

er h

olds

the

mea

sure

d R

H v

alue

for t

he c

ompe

nsat

ion

func

tion.

11BM

SInV

alue

.CO

20

3096

/ppm

CO

2:

This

regi

ster

hol

ds th

e m

easu

red

CO

2 va

lue

for t

he c

ompe

nsat

ion

func

tion.

12BM

SInV

alue

.Out

DTe

mp

1500

3062

/°CO

utdo

or te

mpe

ratu

re c

ompe

nsat

ion

of s

uppl

y ai

r:Th

is re

gist

er h

olds

the

mea

sure

d te

mpe

ratu

re fo

r the

com

pens

atio

n fu

nctio

n.13

BMSI

nVal

ue.A

irRed

Tem

p15

0030

62/°C

Supp

ly te

mpe

ratu

re c

ontro

lled

air r

educ

tion:

This

regi

ster

hol

ds th

e m

easu

red

tem

pera

ture

for t

he c

ompe

nsat

ion

func

tion.

14BM

SInV

alue

.EFd

PWar

n25

630

53/P

aEx

tract

air

filte

r war

ning

leve

l:Th

is re

gist

er h

olds

the

valu

e fo

r the

ext

ract

air

filte

r war

ning

leve

l.15

BMSI

nVal

ue.E

FdPA

lm25

630

53/P

aEx

tract

air

filte

r ala

rm le

vel:

This

regi

ster

hol

ds th

e va

lue

for t

he e

xtra

ct a

ir fil

ter a

larm

leve

l.

80/96

3004402-2013-01-24.fm Appendix - Complete list of Registers - in English

16BM

SInV

alue

.SFd

PWar

n25

630

53/P

aSu

pply

air

filte

r war

ning

leve

l:Th

is re

gist

er h

olds

the

valu

e fo

r the

sup

ply

air f

ilter

war

ning

leve

l.17

BMSI

nVal

ue.S

FdPA

lm25

630

53/P

aSu

pply

filte

r ala

rm le

vel:

This

regi

ster

hol

ds th

e va

lue

for t

he s

uppl

y ai

r filt

er A

larm

leve

l.18

VEXC

onfig

.Hea

tReg

Type

030

95H

eat r

egul

ator

type

:Th

is v

aria

ble

hold

s th

e va

lue

for t

he c

urre

nt h

eat r

egul

ator

type

. 0

= Su

pply

tem

pera

ture

regu

latio

n.1

= R

oom

tem

pera

ture

regu

latio

n.19

BMSI

nVal

ue.A

UXE

xtSe

t10

0130

98/%

Extra

ct fa

n sp

eed

setp

oint

whe

n co

ntro

lling

VEX

unit

from

BM

S.

0-10

00 =

0.0

-100

.0%

. 10

01 =

def

ault

valu

e.Ai

r reg

. = 8

(men

u 3.

1.1)

and

AU

X =

BMS

(men

u 3.

1.14

).20

BMSI

nVal

ue.A

UXS

upSe

t10

0130

98/%

Supp

ly fa

n sp

eed

setp

oint

whe

n co

ntro

lling

VEX

unit

from

BM

S.

0-10

00 =

0.0

-100

.0%

. 10

01 =

def

ault

valu

e.Ai

r reg

. = 8

(men

u 3.

1.1)

and

AU

X =

BMS

(men

u 3.

1.14

).21

BMSO

utVa

lue.

AUXE

xtO

r65

535

3095

BMS

over

ride

outp

ut fo

r dam

pers

in e

xtra

ct d

uct.

This

var

iabl

e ho

lds

a us

er s

peci

fied

valu

e, th

at in

dica

tes

wea

ther

ext

erna

l dam

pers

mus

t be

open

, clo

sed

or fr

ee ru

nnin

g.Se

e “E

Xact

men

ugui

de” f

or in

stru

ctio

ns.

22BM

SOut

Valu

e.AU

XSup

Or

6553

530

95BM

S ov

errid

e ou

tput

for d

ampe

rs in

ext

ract

duc

t.Th

is v

aria

ble

hold

s a

user

spe

cifie

d va

lue,

that

indi

cate

s w

eath

er e

xter

nal d

ampe

rs m

ust b

e op

en, c

lose

d or

free

runn

ing.

See

“EXa

ct m

enug

uide

” for

inst

ruct

ions

.

3.1.

1O

bjec

t typ

e AV

Inde

xN

ame

Def

ault

valu

ePo

ll in

terv

alU

nit

Des

crip

tion

81/96

3004402-2013-01-24.fm Appendix - Complete list of Registers - in English

3.1.

2O

bjec

t typ

e A

I

Inde

xN

ame

Def

ault

valu

ePo

ll in

terv

al

Uni

t/A

ctiv

e te

xt

Des

crip

tion

0BM

SOut

Valu

e.Ip

Adr3

0.0

3095

IP A

ddre

ss 1

:Th

is re

gist

er in

dica

tes

the

IP a

ddre

ss fo

r the

onb

oard

web

serv

er.

01BM

SOut

Valu

e.Ip

Adr2

0.0

3095

IP A

ddre

ss 2

:Th

is re

gist

er in

dica

tes

the

IP a

ddre

ss fo

r the

onb

oard

web

serv

er.

02BM

SOut

Valu

e.Ip

Adr1

0.0

3095

IP A

ddre

ss 3

:Th

is re

gist

er in

dica

tes

the

IP a

ddre

ss fo

r the

onb

oard

web

serv

er.

03BM

SOut

Valu

e.Ip

Adr0

0.0

3095

IP A

ddre

ss 4

:Th

is re

gist

er in

dica

tes

the

IP a

ddre

ss fo

r the

onb

oard

web

serv

er.

04BM

SOut

Valu

e.Ip

Mas

k30.

030

95IP

Mas

k 1:

This

regi

ster

indi

cate

s th

e IP

mas

k fo

r the

onb

oard

web

serv

er.

05BM

SOut

Valu

e.Ip

Mas

k20.

030

95IP

Mas

k 2:

This

regi

ster

indi

cate

s th

e IP

mas

k fo

r the

onb

oard

web

serv

er.

06BM

SOut

Valu

e.Ip

Mas

k10.

030

95IP

Mas

k 3:

This

regi

ster

indi

cate

s th

e IP

mas

k fo

r the

onb

oard

web

serv

er.

07BM

SOut

Valu

e.Ip

Mas

k00.

030

95IP

Mas

k 4:

This

regi

ster

indi

cate

s th

e IP

mas

k fo

r the

onb

oard

web

serv

er.

08BM

SOut

Valu

e.Ip

Gat

eway

30.

030

95IP

Gat

eway

1:

This

regi

ster

indi

cate

s th

e IP

gat

eway

for t

he o

nboa

rd w

ebse

rver

.09

BMSO

utVa

lue.

IpG

atew

ay2

0.0

3095

IP G

atew

ay 2

:Th

is re

gist

er in

dica

tes

the

IP g

atew

ay fo

r the

onb

oard

web

serv

er.

10BM

SOut

Valu

e.Ip

Gat

eway

10.

030

95IP

Gat

eway

3:

This

regi

ster

indi

cate

s th

e IP

gat

eway

for t

he o

nboa

rd w

ebse

rver

.11

BMSO

utVa

lue.

IpG

atew

ay0

0.0

3095

IP G

atew

ay 4

:Th

is re

gist

er in

dica

tes

the

IP g

atew

ay fo

r the

onb

oard

web

serv

er.

12FC

1.W

Freq

Ref

0.0

3095

MC

1 se

tpoi

nt:

Dep

ends

on

the

mot

orty

pe; H

z fo

r FC

-mot

ors

and

rpm

for E

C-m

otor

s.Th

is re

gist

er in

dica

tes

the

curre

nt fr

eque

ncy

outp

ut fr

om th

e FC

.13

FC1.

Out

Pow

er0.

030

47/W

FC1

pow

er:

This

regi

ster

indi

cate

s th

e cu

rrent

pow

er o

utpu

t fro

m th

e FC

.14

FC2.

WFr

eqR

ef0.

030

95M

C2

setp

oint

:D

epen

ds o

n th

e m

otor

type

; Hz

for F

C-m

otor

s an

d rp

m fo

r EC

-mot

ors.

This

regi

ster

indi

cate

s th

e cu

rrent

freq

uenc

y ou

tput

from

the

FC.

82/96

3004402-2013-01-24.fm Appendix - Complete list of Registers - in English

15FC

2.O

utPo

wer

0.0

3047

/WFC

2 po

wer

:Th

is re

gist

er in

dica

tes

the

curre

nt p

ower

out

put f

rom

the

FC.

16R

HX2

M.S

etpo

int

0.0

3098

/%R

HX2

M s

et p

oint

:Th

is re

gist

er in

dica

tes

is th

e se

t poi

nt fo

r the

rota

ry h

eat e

xcha

nger

uni

t.17

MH

C1.

Setp

oint

0.0

3098

/%H

eatin

g un

it 1

set p

oint

:Th

is re

gist

er in

dica

tes

the

set p

oint

for t

he h

eatin

g un

it.18

MH

C1.

Valv

eSet

0.0

3098

/%H

eatin

g un

it 1

stat

us:

This

regi

ster

indi

cate

s th

e st

atus

of t

he h

eatin

g un

it.Va

lue:

0 =

Hea

t ret

etio

n m

ode

1 =

Nor

mal

ope

ratio

n, w

ith fr

ost s

afet

y su

rvel

lianc

e ac

tivat

ed.

19M

HC

1.M

HC

E_O

ut0.

030

98/%

Hea

ting

unit

1 va

lve

set p

oint

:Th

is re

gist

er in

dica

tes

the

set p

oint

to th

e va

lve.

20M

HC

4.Se

tpoi

nt0.

030

98/%

Exte

rnal

coo

ling

unit

set p

oint

This

regi

ster

indi

cate

s th

e se

t poi

nt to

the

cool

ing

unit.

21M

HC

4.Va

lveS

et0.

030

98/%

Exte

rnal

coo

ling

unit

valv

e se

t poi

ntTh

is re

gist

er in

dica

tes

the

set p

oint

to th

e va

lve.

22M

CU

C.S

etpo

int

0.0

3098

/%C

oolin

g un

it se

t poi

nt:

This

regi

ster

indi

cate

s th

e se

t poi

nt to

the

cool

ing

unit.

23Ai

r.Set

poin

t0.

030

98/%

Airfl

ow s

et p

oint

:Th

is re

gist

er in

dica

tes

the

actu

al a

irflo

w s

et p

oint

in p

erce

nt.

24Ai

r.Set

poin

tFix

0.0

3087

/ l/s

Fixe

d ai

rflow

set

poi

ntTh

is re

gist

er in

dica

tes

the

airfl

ow s

et p

oint

for t

he e

xtra

ct a

ir fa

n or

sup

ply

fan,

whe

n us

ing

air-

flow

regu

latio

n m

etho

de 4

or 3

.25

Air.E

xtSp

eed

0.0

3098

/%Ex

tract

air

fan

spee

d:Th

is re

gist

er in

dica

tes

the

fan

spee

d.26

Air.E

xtSp

eedM

in0.

030

98/%

Min

imum

ext

ract

air

fan

spee

d:Th

is re

gist

er in

dica

tes

the

min

imum

fan

spee

d.27

Air.E

xtSp

eedM

ax0.

030

98/%

Max

imum

ext

ract

air

fan

spee

d:Th

is re

gist

er in

dica

tes

the

max

imum

fan

spee

d.28

Air.S

upSp

eed

0.0

3098

/%Su

pply

air

fan

spee

d:Th

is re

gist

er in

dica

tes

the

fan

spee

d.29

Air.S

upSp

eedM

in0.

030

98/%

Min

imum

sup

ply

air f

an s

peed

:Th

is re

gist

er in

dica

tes

the

min

imum

fan

spee

d.

3.1.

2O

bjec

t typ

e A

I

Inde

xN

ame

Def

ault

valu

ePo

ll in

terv

al

Uni

t/A

ctiv

e te

xt

Des

crip

tion

83/96

3004402-2013-01-24.fm Appendix - Complete list of Registers - in English

30Ai

r.Sup

Spee

dMax

0.0

3098

/%M

axim

um s

uppl

y ai

r fan

spe

ed:

This

regi

ster

indi

cate

s th

e m

axim

um fa

n sp

eed.

31Ai

r.Set

pCom

p0.

030

98/%

Airfl

ow s

et p

oint

com

pens

ated

:Th

is re

gist

er is

use

d to

indi

cate

the

com

pens

ated

air

set p

oint

. C

O2

and

RH

leve

l affe

cts

this

val

ue.

32Ai

r.Set

pExt

0.0

3098

/%Ex

tract

air

set p

oint

:Th

is re

gist

er in

dica

tes

the

set p

oint

to th

e ex

tract

airf

low

regu

lato

r.Th

is is

the

outp

ut fr

om e

ither

fixe

d sp

eed,

con

stan

t flo

w o

r con

stan

t pre

ssur

e re

gula

tor.

33Ai

r.Set

pSup

0.0

3098

/%Su

pply

air

set p

oint

:Th

is re

gist

er in

dica

tes

the

set p

oint

to th

e su

pply

airf

low

regu

lato

r.Th

is is

the

outp

ut fo

rm e

ither

fixe

d sp

eed,

con

stan

t flo

w o

r con

stan

t pre

ssur

e re

gula

tor.

34Ai

r.Mod

e0.

030

95Ai

rflow

regu

lato

r mod

e:Th

is re

gist

er in

dica

tes

the

stat

e of

the

airfl

ow re

gula

tor.

Valu

e: 0

= O

FF1

= St

artin

g 2

= D

ampe

rs o

peni

ng

3 =

Extra

ct a

ir fa

n st

artin

g4

= Su

pply

air

fan

star

ting

5 =

Uni

t is

runn

ing

6 =

Uni

t is

stop

ping

but

is d

oing

pos

t ven

tilat

ion

7 =

Dam

pers

are

clo

sing

35Ai

r_Q

v.Ex

tP_I

nLet

0.0

3053

/Pa

Extra

ct a

ir fa

n in

let p

ress

ure:

This

regi

ster

indi

cate

s th

e pr

essu

re d

rop

acro

ss th

e ex

tract

air

fan

inle

t. Th

is p

ress

ure

is c

on-

verte

d to

tem

pera

ture

com

pens

ated

flow

in in

dex

36.

36Ai

r_Q

v.Ex

t_Q

v0.

030

87/ l

/sEx

tract

air

flow

:Th

is re

gist

er in

dica

tes

flow

in th

e ex

tract

air

duct

.37

Air_

Qv.

SupP

_Inl

et0.

030

53/P

aSu

pply

air

fan

inle

t pre

ssur

e:Th

is re

gist

er in

dica

tes

the

pres

sure

dro

p ac

ross

the

supp

ly a

ir fa

n in

let.

This

pre

ssur

e is

con

-ve

rted

to te

mpe

ratu

re c

ompe

nsat

ed fl

ow in

inde

x 38

.38

Air_

Qv.

Sup_

Qv

0.0

3087

/ l/s

Supp

ly a

irflo

w:

This

regi

ster

indi

cate

s ai

rflow

in th

e su

pply

air

duct

.39

Air_

Filte

r.Ext

ract

0.0

3053

/Pa

Extra

ct a

ir fil

ter p

ress

ure

drop

:Th

is re

gist

er in

dica

tes

the

pres

sure

dro

p ac

ross

the

extra

ct a

ir fil

ter.

3.1.

2O

bjec

t typ

e A

I

Inde

xN

ame

Def

ault

valu

ePo

ll in

terv

al

Uni

t/A

ctiv

e te

xt

Des

crip

tion

84/96

3004402-2013-01-24.fm Appendix - Complete list of Registers - in English

40Ai

r_Fi

lter.S

uppl

y0.

030

53/P

aSu

pply

air

filte

r pre

ssur

e dr

op:

This

regi

ster

indi

cate

s th

e pr

essu

re d

rop

acro

ss th

e su

pply

air

filte

r.41

Air_

Duc

t.Ext

ract

0.0

3053

/Pa

Extra

ct a

ir du

ct p

ress

ure.

This

regi

ster

indi

cate

s th

e pr

essu

re in

ext

ract

air

duct

. 42

Air_

Duc

t.Sup

ply

0.0

3053

/Pa

Supp

ly a

ir du

ct p

ress

ure.

This

regi

ster

indi

cate

s th

e pr

essu

re in

sup

ply

air

duct

. 43

AirC

FExt

.SP_

Uni

t0.

030

87/ l

/sC

onst

ant e

xtra

ct a

irflo

w re

gula

tor s

et p

oint

:Th

is re

gist

er in

dica

tes

the

set p

oint

for t

he e

xtra

ct a

ir flo

w re

gula

tor.

44Ai

rCFE

xt.P

V_U

nit

0.0

3087

/ l/s

Con

stan

t ext

ract

airf

low

regu

lato

r fee

dbac

k:Th

is re

gist

er in

dica

tes

the

set p

oint

for t

he e

xtra

ct a

ir flo

w re

gula

tor.

45Ai

rCFS

up.S

P_U

nit

0.0

3087

/ l/s

Con

stan

t sup

ply

airfl

ow re

gula

tor s

et p

oint

:Th

is re

gist

er in

dica

tes

the

set p

oint

for t

he s

uppl

y a

ir flo

w re

gula

tor.

46Ai

rCFS

up.P

V_U

nit

0.0

3087

/ l/s

Con

stan

t sup

ply

airfl

ow re

gula

tor f

eedb

ack:

This

regi

ster

indi

cate

s th

e se

t poi

nt fo

r the

sup

ply

air f

low

regu

lato

r.47

AirC

SExt

.SP_

Uni

t0.

030

98/ %

Con

stan

t ext

ract

air

spee

d re

gula

tor s

et p

oint

:Th

is re

gist

er in

dica

tes

the

set p

oint

for t

he e

xtra

ct a

ir sp

eed

regu

lato

r.48

AirC

SSup

.SP_

Uni

t0.

030

98/ %

Con

stan

t sup

ply

air

spee

d re

gula

tor s

et p

oint

:Th

is re

gist

er in

dica

tes

the

set p

oint

for t

he s

uppl

y a

ir sp

eed

regu

lato

r.49

AirC

PExt

.SP_

Uni

t0.

030

53/P

aC

onst

ant e

xtra

ct a

ir pr

essu

re re

gula

tor s

et p

oint

:Th

is re

gist

er in

dica

tes

the

set p

oint

for t

he e

xtra

ct a

ir pr

essu

re re

gula

tor.

50Ai

rCPE

xt.P

V_U

nit

0.0

3053

/Pa

Con

stan

t ext

ract

air

pres

sure

regu

lato

r fee

dbac

k:Th

is re

gist

er in

dica

tes

the

set p

oint

for t

he e

xtra

ct a

ir pr

essu

re re

gula

tor.

51Ai

rCPS

up.S

P_U

nit

0.0

3053

/Pa

Con

stan

t sup

ply

air p

ress

ure

regu

lato

r set

poi

nt:

This

regi

ster

indi

cate

s th

e se

t poi

nt fo

r the

sup

ply

air

pres

sure

regu

lato

r.52

AirC

PSup

.PV_

Uni

t0.

030

53/P

aC

onst

ant s

uppl

y ai

r pre

ssur

e re

gula

tor f

eedb

ack:

This

regi

ster

indi

cate

s th

e se

t poi

nt fo

r the

sup

ply

air

pres

sure

regu

lato

r.53

Alar

m.A

larm

00.

030

95C

urre

nt a

ctiv

e al

arm

1 o

utpu

t:Th

e re

gist

er s

how

s th

ere

is a

n ac

tive

alar

m. S

ee a

lso

EXac

t con

trol m

enu

4.5

"Cur

rent

Lis

t".54

Alar

m.A

larm

10.

030

95C

urre

nt a

ctiv

e al

arm

2 o

utpu

t:Th

e re

gist

er s

how

s th

ere

is a

n ac

tive

alar

m. S

ee a

lso

EXac

t con

trol m

enu

4.5

"Cur

rent

Lis

t".55

Alar

m.A

larm

20.

030

95C

urre

nt a

ctiv

e al

arm

3ou

tput

:Th

e re

gist

er s

how

s th

ere

is a

n ac

tive

alar

m. S

ee a

lso

EXac

t con

trol m

enu

4.5

"Cur

rent

Lis

t".

3.1.

2O

bjec

t typ

e A

I

Inde

xN

ame

Def

ault

valu

ePo

ll in

terv

al

Uni

t/A

ctiv

e te

xt

Des

crip

tion

85/96

3004402-2013-01-24.fm Appendix - Complete list of Registers - in English

56Al

arm

.Ala

rm3

0.0

3095

Cur

rent

act

ive

alar

m 4

out

put:

The

regi

ster

sho

ws

ther

e is

an

activ

e al

arm

. See

als

o EX

act c

ontro

l men

u 4.

5 "C

urre

nt L

ist".

57Al

arm

.Ala

rm4

0.0

3095

Cur

rent

act

ive

alar

m 5

out

put:

The

regi

ster

sho

ws

ther

e is

an

activ

e al

arm

. See

als

o EX

act c

ontro

l men

u 4.

5 "C

urre

nt L

ist".

58Al

arm

.Ala

rm5

0.0

3095

Cur

rent

act

ive

alar

m 6

out

put:

The

regi

ster

sho

ws

ther

e is

an

activ

e al

arm

. See

als

o EX

act c

ontro

l men

u 4.

5 "C

urre

nt L

ist".

59Al

arm

.Ala

rm6

0.0

3095

Cur

rent

act

ive

alar

m 7

out

put:

The

regi

ster

sho

ws

ther

e is

an

activ

e al

arm

. See

als

o EX

act c

ontro

l men

u 4.

5 "C

urre

nt L

ist".

60Al

arm

.Ala

rm7

0.0

3095

Cur

rent

act

ive

alar

m 8

out

put:

The

regi

ster

sho

ws

ther

e is

an

activ

e al

arm

. See

als

o EX

act c

ontro

l men

u 4.

5 "C

urre

nt L

ist".

61Al

arm

.Ala

rm8

0.0

3095

Cur

rent

act

ive

alar

m 9

out

put:

The

regi

ster

sho

ws

ther

e is

an

activ

e al

arm

. See

als

o EX

act c

ontro

l men

u 4.

5 "C

urre

nt L

ist".

62Al

arm

.Ala

rm9

0.0

3095

Cur

rent

act

ive

alar

m 1

0 ou

tput

:Th

e re

gist

er s

how

s th

ere

is a

n ac

tive

alar

m. S

ee a

lso

EXac

t con

trol m

enu

4.5

"Cur

rent

Lis

t".63

Alar

m.A

larm

100.

030

95C

urre

nt a

ctiv

e al

arm

11

outp

ut:

The

regi

ster

sho

ws

ther

e is

an

activ

e al

arm

. See

als

o EX

act c

ontro

l men

u 4.

5 "C

urre

nt L

ist".

64Al

arm

.Ala

rm11

0.0

3095

Cur

rent

act

ive

alar

m 1

2 ou

tput

:Th

e re

gist

er s

how

s th

ere

is a

n ac

tive

alar

m. S

ee a

lso

EXac

t con

trol m

enu

4.5

"Cur

rent

Lis

t".65

Alar

m.A

larm

120.

030

95C

urre

nt a

ctiv

e al

arm

13

outp

ut:

The

regi

ster

sho

ws

ther

e is

an

activ

e al

arm

. See

als

o EX

act c

ontro

l men

u 4.

5 "C

urre

nt L

ist".

66Al

arm

.Ala

rm13

0.0

3095

Cur

rent

act

ive

alar

m 1

4 ou

tput

:Th

e re

gist

er s

how

s th

ere

is a

n ac

tive

alar

m. S

ee a

lso

EXac

t con

trol m

enu

4.5

"Cur

rent

Lis

t".67

Alar

m.A

larm

140.

030

95C

urre

nt a

ctiv

e al

arm

15

outp

ut:

The

regi

ster

sho

ws

ther

e is

an

activ

e al

arm

. See

als

o EX

act c

ontro

l men

u 4.

5 "C

urre

nt L

ist".

68Al

arm

.Ala

rm15

0.0

3095

Cur

rent

act

ive

alar

m 1

6 ou

tput

:Th

e re

gist

er s

how

s th

ere

is a

n ac

tive

alar

m. S

ee a

lso

EXac

t con

trol m

enu

4.5

"Cur

rent

Lis

t".69

Bala

nce.

Bala

nce

0.0

3095

Air b

alan

ce:

This

regi

ster

indi

cate

s ba

lanc

e se

t poi

nt b

etw

een

supp

ly a

ir an

d ex

tract

air

set p

oint

.70

Com

p_R

oom

.SP_

Com

p0.

030

62/°C

Out

door

tem

pera

ture

com

pens

atio

n of

room

tem

pera

ture

set

poi

nt:

This

regi

ster

indi

cate

s th

e se

t poi

nt fo

r sta

rting

of r

oom

tem

pera

ture

com

pens

atio

n71

Com

p_Su

pply.

SP_C

omp

0.0

3062

/°CO

utdo

or te

mpe

ratu

re c

ompe

nsat

ion

of s

uppl

y ai

r tem

pera

ture

set

poi

nt:

This

regi

ster

indi

cate

s th

e se

t poi

nt fo

r beg

inni

ng o

f sup

ply

air t

empe

ratu

re c

ompe

nsat

ion

3.1.

2O

bjec

t typ

e A

I

Inde

xN

ame

Def

ault

valu

ePo

ll in

terv

al

Uni

t/A

ctiv

e te

xt

Des

crip

tion

86/96

3004402-2013-01-24.fm Appendix - Complete list of Registers - in English

72M

anag

er.A

ctPr

ofile

0.0

3095

Activ

e pr

ofile

:Th

is re

gist

er in

dica

tes

whi

ch p

rofil

e is

act

ive.

Valu

e: -1

= O

ff0

= C

omfo

rt1

= St

andb

y2

= Ec

onom

y73

Cou

nter

.Hea

t10.

030

95H

our c

ount

hea

ting

unit

1:Th

is re

gist

er in

dica

tes

the

hour

cou

nt fo

r the

uni

t.74

Cou

nter

.Rot

or0.

030

95H

our c

ount

rota

ry h

eat e

xcha

nger

uni

t:Th

is re

gist

er in

dica

tes

the

hour

cou

nt fo

r the

uni

t.75

Cou

nter

.Coo

l0.

030

95H

our c

ount

coo

ling

unit:

This

regi

ster

indi

cate

s th

e ho

ur c

ount

for t

he u

nit.

76C

ount

er.E

xtra

ctFa

n0.

030

95H

our c

ount

ext

ract

air

fan

unit:

This

regi

ster

indi

cate

s th

e ho

ur c

ount

for t

he u

nit.

77C

ount

er.S

uppl

yFan

0.0

3095

Hou

r cou

nt s

uppl

y ai

r fan

uni

t:Th

is re

gist

er in

dica

tes

the

hour

cou

nt fo

r the

uni

t.78

Tem

p_Se

t.Set

poin

t0.

030

62/°C

Tem

pera

ture

set

poi

nt:

This

regi

ster

indi

cate

s th

e cu

rrent

tem

pera

ture

set

poi

nt.

79Te

mp_

Set.S

etpo

int

0.0

3062

/°CC

ompe

nsat

ed te

mpe

ratu

re s

et p

oint

:Th

is re

gist

er in

dica

tes

the

com

pens

ated

tem

pera

ture

regu

lato

r set

poi

nt.

80Te

mp_

Set.S

tate

0.0

3095

Tem

pera

ture

regu

lato

r sta

tus:

This

regi

ster

indi

cate

s if

the

tem

pera

ture

regu

lato

r is

activ

e.St

ate:

0 =

Not

act

ive,

1 =

Act

ive

81Te

mp_

Set.M

ode

0.0

3095

Tem

para

ture

regu

lato

r mod

e:

This

regi

ster

indi

cate

s th

e cu

rrent

mod

e of

the

tem

pera

ture

regu

lato

r.Va

lue:

0 =

Off

1 =

On

2 =

Hea

t 3

= C

ool

4 =

Hea

t rec

over

y5

= C

ool r

ecov

ery

82Te

mp_

Out

put.H

eat1

0.0

3098

/%H

eatin

g un

it 1

set p

oint

:Th

is re

gist

er in

dica

tes

the

set p

oint

for h

eatin

g un

it 1.

3.1.

2O

bjec

t typ

e A

I

Inde

xN

ame

Def

ault

valu

ePo

ll in

terv

al

Uni

t/A

ctiv

e te

xt

Des

crip

tion

87/96

3004402-2013-01-24.fm Appendix - Complete list of Registers - in English

83Te

mp_

Out

put.R

ecov

_Hea

t0.

030

98/%

Hea

t rec

over

y un

it se

t poi

nt:

This

regi

ster

indi

cate

s th

e se

t poi

nt fo

r the

hea

t rec

over

y un

it.84

Tem

p_O

utpu

t.Rec

ov_C

ool

0.0

3098

/%C

ool r

ecov

ery

unit

set p

oint

:Th

is re

gist

er in

dica

tes

the

set p

oint

for t

he c

ool r

ecov

ery

unit.

85Te

mp_

Out

put.C

ool

0.0

3098

/%C

oolin

g un

it se

t poi

nt:

This

regi

ster

indi

cate

s th

e se

t poi

nt fo

r the

coo

ling

unit.

86Te

mpC

Supp

ly.Se

tpoi

nt0.

030

62/°C

Con

stan

t sup

ply

tem

pera

ture

regu

lato

r set

poi

nt:

This

regi

ster

indi

cate

s th

e se

t poi

nt fo

r the

sup

ply

air t

empe

ratu

re re

gula

tor

87Te

mpC

Supp

ly.Fe

edba

ck0.

030

62/°C

Con

stan

t sup

ply

air t

empe

ratu

re re

gula

tor f

eedb

ack:

This

regi

ster

indi

cate

s th

e fe

edba

ck fo

r the

sup

ply

air t

empe

ratu

re re

gula

tor

88Te

mpC

Supp

ly.Sp

_Hea

t10.

030

62/°C

Hea

ting

unit

1 re

gula

tor s

et p

oint

:Th

is re

gist

er in

dica

tes

the

set p

oint

for t

he h

eatin

g un

it 1

regu

lato

r 89

Tem

pCSu

pply.

Sp_R

ecov

er0.

030

62/°

CR

ecov

ery

unit

regu

lato

r set

poi

nt:

This

regi

ster

indi

cate

s th

e se

t poi

nt fo

r the

reco

very

uni

t reg

ulat

or.

90Te

mpC

Supp

ly.Sp

_Coo

l0.

030

62/°C

Coo

ling

unit

regu

lato

r set

poi

nt:

This

regi

ster

indi

cate

s th

e se

t poi

nt fo

r the

coo

ling

unit

regu

lato

r.91

Tem

pCR

oom

.Set

poin

t0.

030

62/°C

Con

stan

t roo

m te

mpe

ratu

re re

gula

tor s

et p

oint

:Th

is re

gist

er in

dica

tes

the

set p

oint

for t

he ro

om te

mpe

ratu

re re

gula

tor

92Te

mpC

Roo

m.F

eedb

ack

0.0

3062

/°CC

onst

ant r

oom

tem

pera

ture

regu

lato

r fee

dbac

k:Th

is re

gist

er in

dica

tes

the

feed

back

for t

he ro

om te

mpe

ratu

re re

gula

tor

93Te

mpC

Roo

m.O

utpu

t0.

030

62/°C

Con

stan

t roo

m te

mpe

ratu

re re

gula

tor:

This

regi

ster

indi

cate

s th

e ou

tput

of t

he ro

om te

mpe

ratu

re re

gula

tor

94Te

mp_

Sens

or.S

uppl

y0.

030

62/°C

Supp

ly a

ir te

mpe

ratu

re s

enso

r:Th

is re

gist

er in

dica

tes

the

valu

e of

the

curre

nt a

ctiv

e su

pply

air

tem

pera

ture

se

nsor

.95

Tem

p_Se

nsor

.Sup

plyI

nt0.

030

62/°

CSu

pply

air

tem

pera

ture

sen

sor i

nter

nal:

This

regi

ster

indi

cate

s th

e va

lue

of th

e in

tern

al s

uppl

y ai

r tem

pera

ture

sen

sor.

96Te

mp_

Sens

or.S

uppl

yHea

t10.

030

62/°C

Supp

ly a

ir te

mpe

ratu

re s

enso

r hea

ting

unit

1:Th

is re

gist

er in

dica

tes

the

valu

e of

the

supp

ly a

ir te

mpe

ratu

r sen

sor i

n he

atin

g un

it 1.

97Te

mp_

Sens

or.S

uppl

yCoo

l0.

030

62/°C

Supp

ly a

ir te

mpe

ratu

re s

enso

r coo

ling

unit:

This

regi

ster

indi

cate

s th

e va

lue

of th

e su

pply

air

tem

pera

tur s

enso

r in

the

cool

ing

unit.

98Te

mp_

Sens

or.O

utdo

or0.

030

62/°C

Out

door

air

tem

pera

ture

sen

sor:

This

regi

ster

indi

cate

s th

e va

lue

of th

e cu

rrent

act

ive

outd

oor

air t

empe

ratu

r sen

sor.

3.1.

2O

bjec

t typ

e A

I

Inde

xN

ame

Def

ault

valu

ePo

ll in

terv

al

Uni

t/A

ctiv

e te

xt

Des

crip

tion

88/96

3004402-2013-01-24.fm Appendix - Complete list of Registers - in English

99Te

mp_

Sens

or.O

utdo

orIn

t0.

030

62/°C

Out

door

air

tem

pera

ture

sen

sor i

nter

nal:

This

regi

ster

indi

cate

s th

e va

lue

of th

e in

tern

al o

utdo

or a

ir te

mpe

ratu

r sen

sor.

100

Tem

p_Se

nsor

.Out

door

Ext

0.0

3062

/°CO

utdo

or a

ir te

mpe

ratu

re s

enso

r ext

erna

l:Th

is re

gist

er in

dica

tes

the

valu

e of

the

exte

rnal

out

door

air

tem

pera

tur s

enso

r.10

1Te

mp_

Sens

or.E

xhau

st0.

030

62/°C

Exha

ust a

ir te

mpe

ratu

re s

enso

r:Th

is re

gist

er in

dica

tes

the

valu

e of

the

exha

ust a

ir te

mpe

ratu

r sen

sor.

102

Tem

p_Se

nsor

.Ext

ract

0.0

3062

/°CEx

tract

air

tem

pera

ture

sen

sor:

This

regi

ster

indi

cate

s th

e va

lue

of th

e cu

rrent

act

ive

extra

ct a

ir te

mpe

ratu

r sen

sor.

103

Tem

p_Se

nsor

.Ext

ract

Int

0.0

3062

/°CEx

tract

air

tem

pera

ture

sen

sor i

nter

nal:

This

regi

ster

indi

cate

s th

e va

lue

of th

e in

tern

al e

xtra

ct a

ir te

mpe

ratu

r sen

sor.

104

Tem

p_Se

nsor

.Ext

ract

Roo

m0.

030

62/°C

Extra

ct a

ir te

mpe

ratu

re s

enso

r ext

erna

l:Th

is re

gist

er in

dica

tes

the

valu

e of

the

Exte

rnal

ext

ract

air

tem

pera

tur s

enso

r.10

5Te

mp_

Sens

or.R

etPi

pe1

0.0

3062

/°CR

etur

n pi

pe te

mpe

ratu

re h

eatin

g co

il 1:

This

regi

ster

indi

cate

s th

e te

mpe

ratu

re o

n th

e in

tern

al re

turn

pip

e on

wat

er h

eatin

g co

il 1

(TE-

RPT

).10

6Te

mp_

Sens

or.R

etPi

peX1

0.0

3062

/°CR

etur

n pi

pe te

mpe

ratu

re e

xter

nal h

eatin

g co

il 1:

This

regi

ster

indi

cate

s th

e te

mpe

ratu

re o

n th

e ex

tern

al re

turn

pip

e on

wat

er h

eatin

g co

il 1

(TE-

RPT

-X).

107

Tem

p_Se

nsor

.Sup

Pipe

10.

030

62/°C

Supp

ly p

ipe

tem

pera

ture

hea

ting

coil

1:Th

is re

gist

er in

dica

tes

the

tem

pera

ture

on

the

inte

rnal

sup

ply

air p

ipe

on w

ater

hea

ting

coil

1 (T

E-SP

T).

108

DeI

ce.H

eatE

xPre

ss0.

030

53/P

aPr

essu

re a

cros

s th

e he

at e

xcha

nger

in th

e ex

tract

air.

This

var

iabl

e in

dica

tes

the

curre

nt p

ress

ure

acro

ss th

e he

at e

xcha

nger

.A

incr

easi

ng p

ress

ure

at a

con

stan

t air

flow

can

indi

cate

eith

er m

oist

ure

or ic

e bu

ild u

p in

side

th

e he

at e

xcha

nger

.10

9D

eIce

.Pre

ssIn

c0.

030

98/%

Hea

t exc

hang

er p

ress

ure

incr

ease

in %

.Th

is v

aria

ble

indi

cate

s ho

w m

uch

the

pres

sure

has

incr

ease

d, a

cros

s th

e he

at e

xcha

nger

co

mpa

red

to th

e no

rmal

pre

ssur

e dr

op, w

hen

the

heat

exc

hang

er is

dry

. Val

ues

over

0%

indi

-ca

tes

build

up

of m

oist

ure

or ic

e.11

0Te

mp_

Sens

or.T

Ice

0.0

3062

/°CTe

mpe

ratu

re in

side

the

heat

exc

hang

er.

This

var

iabl

e sh

ows

the

tem

pera

ture

insi

de th

e he

at e

xcha

nger

. Thi

s is

use

d to

con

trol t

he

deic

e fu

nctio

n, w

hen

the

DeI

ce fu

nctio

n is

set

to T

Ice.

3.1.

2O

bjec

t typ

e A

I

Inde

xN

ame

Def

ault

valu

ePo

ll in

terv

al

Uni

t/A

ctiv

e te

xt

Des

crip

tion

89/96

3004402-2013-01-24.fm Appendix - Complete list of Registers - in English

111

VEXC

onfig

.AirR

egTy

pe0.

030

95Ai

r reg

ulat

ions

met

hod.

This

var

iabl

e sh

ows

whi

ch a

ir re

gula

tion

curre

nt is

act

ive.

1 - M

anua

l con

trol

2 - A

irflo

w c

ontro

l3

- Con

stan

t pre

ssur

e re

gula

tion

of e

xtra

ct a

ir4

- Con

stan

t pre

ssur

e re

gula

tion

of s

uppl

y ai

r5

- Con

stan

t pre

ssur

e re

gula

tion

of e

xtra

ct a

ir6

- Con

stan

t pre

ssur

e re

gula

tion

of s

uppl

y ai

r7

- Con

stan

t pre

ssur

e re

gula

tion

of b

oth

extra

ct a

ir an

d su

pply

air

8 - E

xter

nal c

ontro

l of f

an s

peed

s11

2N

ight

Coo

l.Sta

tus

0.0

3095

Nig

ht-ti

me

cool

ing

stat

us:

This

out

put n

etw

ork

varia

ble

indi

cate

s if

the

nigh

t coo

ling

func

tion

is a

ctiv

eSt

ate:

0 =

Inac

tive,

1 =

Act

ive.

113

DeI

ce.S

tate

0.0

3095

Activ

e D

eIce

sta

te.

This

var

iabl

e in

dica

tes

whi

ch D

eIce

sta

te c

urre

ntly

is a

ctiv

e.0

= O

ff. N

o Ic

e is

det

ecte

d.1

= Id

le. I

ce is

pre

set,

but d

eIce

is n

ot y

et a

ctiv

e.2

= R

etur

n Ai

r (VE

X340

Onl

y) o

r Byp

ass

deic

e fu

nctio

n is

act

ive.

3

= Ba

lanc

ed a

ir re

duct

ion

is a

ctiv

e.4

= U

nbal

ance

d su

pply

air

redu

ctio

n is

act

ive.

5 =

Unb

alan

ced

extra

ct a

ir in

crea

se is

act

ive.

6 =

Hib

erna

tion.

VEX

uni

t is

tem

pora

rily

in h

iber

natio

n.7

= H

iber

natio

n re

star

t. VE

X un

it is

atte

mpt

ing

to re

star

t afte

r hib

erna

tion.

8 =

Dei

ce fa

lied.

The

pre

ssur

e ac

ross

the

heat

exc

hang

er h

as e

xcee

ded

max

imum

allo

wed

pr

essu

re o

r the

num

ber o

f res

tart

atte

mpt

s ha

s be

en e

xcee

ded.

3.1.

2O

bjec

t typ

e A

I

Inde

xN

ame

Def

ault

valu

ePo

ll in

terv

al

Uni

t/A

ctiv

e te

xt

Des

crip

tion

90/96

3004402-2013-01-24.fm Appendix - Complete list of Registers - in English

3.1.

3O

bjec

t typ

e B

V

Inde

xN

ame

Def

ault

valu

ePo

ll in

terv

al

Uni

t/A

ctiv

e te

xt

Uni

t/In

activ

e te

xt

Des

crip

tion

00BM

SInV

alue

.Ctrl

Mod

e0

30O

nO

ffC

ontro

l mod

e:Th

is re

gist

er h

olds

the

valu

e fo

r the

con

trol m

ode

of th

e U

nit.

Valu

e: O

ff =

Man

ual,

Valu

e: O

n =

Wee

kly

plan

01BM

SInV

alue

.Res

etAl

arm

030

On

Off

Alar

m re

set:

This

regi

ster

hol

des

the

valu

e fo

r the

ala

rm re

set f

lag.

Valu

e: O

ff =

Not

act

ive,

Val

ue: O

n =

Activ

e02

BMSI

nVal

ue.N

ight

Coo

lEn

030

On

Off

Nig

ht-ti

me

cool

ing

enab

led:

This

regi

ster

hol

ds th

e en

able

val

ue fo

r the

nig

ht c

oolin

g fu

nctio

n.Va

lue:

Off

= D

isab

led,

On

= En

able

d

3.1.

4O

bjec

t typ

e B

I

Inde

xN

ame

Def

ault

valu

ePo

ll in

terv

al

Uni

t/A

ctiv

e te

xt

Uni

t/In

activ

e te

xt

Des

crip

tion

00M

anag

er.O

nOff

030

On

Off

Stat

e:Th

is re

gist

er in

dica

tes

if th

e un

it is

runi

nng

or n

ot.

01Al

arm

.A_A

larm

030

On

Off

A Al

arm

.Th

is v

aria

ble

show

s if

an A

ala

rm is

act

ive.

A Al

arm

is s

et w

hen

alar

ms

code

s en

ding

on

3, 4

or 5

are

act

ive.

02Al

arm

.B_A

larm

030

On

Off

B Al

arm

(War

ning

).Th

is v

aria

ble

show

s if

a B

alar

m is

act

ive.

B Al

arm

is s

et w

hen

alar

m c

odes

end

ing

on 2

are

act

ive.

03BM

S_C

onfig

.Use

DH

CP

030

Yes

No

Use

DH

CP:

This

regi

ster

indi

cate

s if

the

onbo

ard

web

serv

er u

ses

DH

CP.

Stat

e: O

ff =

Doe

s no

t use

DH

CP

, On

= U

ses

DH

CP

04FC

1.O

pera

tion

030

On

Off

FC1

oper

atio

n:Th

is re

gist

er in

dica

tes

if th

e FC

is ru

nnin

g or

not

.St

ate:

Off

= N

ot ru

nnin

g, O

n =

Run

ning

05FC

2.O

pera

tion

030

On

Off

FC2

oper

atio

n:Th

is re

gist

er in

dica

tes

if th

e FC

is ru

nnin

g or

not

.St

ate:

Off

= N

ot ru

nnin

g, O

n =

Run

ning

91/96

3004402-2013-01-24.fm Appendix - Complete list of Registers - in English

06R

HX2

M.O

n_O

ff0

30O

nO

ffR

HX2

M s

tatu

s:Th

is re

gist

er in

dica

tes

if th

e ro

tary

hea

t exc

hang

er u

nit i

s on

line

or n

ot.

Stat

e: O

ff =

Not

runn

ing,

On

= R

unni

ng07

MH

C1.

Run

030

On

Off

Hea

ting

unit

1 st

atus

:Th

is re

gist

er in

dica

tes

the

stat

us o

f the

hea

ting

unit.

Valu

e: O

ff =

Hea

t ret

etio

n m

ode,

Off

= N

orm

al o

pera

tion,

with

fros

t saf

ety

surv

elli-

ance

act

ivat

ed.

08M

HC

1.Pu

mpS

tate

030

On

Off

Hea

ting

unit

1 pu

mp

stat

eTh

is re

gist

er in

dica

tes

the

curre

nt s

tate

of t

he p

ump.

09M

HC

4.R

un0

30O

nO

ffEx

tern

al c

oolin

g un

it st

atus

This

regi

ster

indi

cate

s th

e st

atus

of t

he c

oolin

g un

it.10

MH

C4.

Pum

pSta

te0

30O

nO

ffEx

tern

al c

oolin

g un

it pu

mp

stat

us:

This

regi

ster

indi

cate

s th

e cu

rrent

sta

te o

f the

pum

p.11

MC

UC

.Sta

te0

30O

nO

ffC

oolin

g un

it st

atus

: Th

is re

gist

er in

dica

tes

the

stat

us o

f the

coo

ling

unit.

12Ai

r.LSA

030

On

Off

Extra

ct a

ir da

mpe

r sta

tus:

This

regi

ster

indi

cate

s th

e st

ate

of th

e ex

tract

air

dam

per.

Stat

e: O

ff =

Clo

sed,

On

= O

pen

13Ai

r.LSF

030

On

Off

Supp

ly a

ir da

mpe

r sta

tus:

This

regi

ster

indi

cate

s th

e st

ate

of th

e su

pply

air

dam

per.

Stat

e: O

ff =

Clo

sed,

On

= O

pen

14Ai

r.Sta

te0

30O

nO

ffAi

rflow

regu

lato

r sta

tus:

This

regi

ster

indi

cate

s th

e st

ate

of th

e ai

rflow

regu

lato

r.15

Com

p_R

H.A

ctiv

e0

30O

nO

ffR

elat

ive

hum

idity

com

pens

atio

n st

atus

:Th

is re

gist

er in

dica

tes

if R

H c

ompe

nsat

ion

is a

ctiv

e.St

ate:

Off

= In

activ

e, O

n =

Activ

e16

Com

p_C

O2.

Activ

e0

30O

nO

ffC

O2

com

pens

atio

n st

atus

:Th

is re

gist

er in

dica

tes

if C

O2

com

pens

atio

n is

act

ive.

Stat

e: O

ff =

Inac

tive,

On

= Ac

tive

17C

omp_

Out

D.A

ctiv

e0

30O

nO

ffO

utdo

or te

mpe

ratu

re c

ompe

nsat

ion

of s

uppl

y ai

r sta

tus:

This

regi

ster

indi

cate

s if

outd

oor t

empe

ratu

re c

ompe

nsat

ion

of s

uppl

y ai

r is

activ

e.St

ate:

Off

= In

activ

e, O

n =

Activ

e

3.1.

4O

bjec

t typ

e B

I

Inde

xN

ame

Def

ault

valu

ePo

ll in

terv

al

Uni

t/A

ctiv

e te

xt

Uni

t/In

activ

e te

xt

Des

crip

tion

92/96

3004402-2013-01-24.fm Appendix - Complete list of Registers - in English

18C

omp_

AirR

.Act

ive

030

On

Off

Supp

ly a

ir te

mpe

ratu

re c

ontro

lled

air r

educ

tion

stat

us:

This

regi

ster

indi

cate

s if

supp

ly a

ir te

mpe

ratu

re c

ontro

lled

air r

educ

tion

is a

ctiv

e.St

ate:

Off

= In

activ

e, O

n =

Activ

e19

Com

p_R

oom

.Act

ive

030

On

Off

Out

door

tem

pera

ture

com

pens

atio

n of

room

tem

pera

ture

sta

tus:

This

regi

ster

indi

cate

s if

outd

oor a

ir te

mpe

ratu

re c

ompe

nsat

ion

of ro

om te

mpe

ra-

ture

is a

ctiv

e.St

ate:

Off

= In

activ

e, O

n =

Activ

e20

Com

p_Su

pply.

Activ

e0

30O

nO

ffO

utdo

or te

mpe

ratu

re c

ompe

nsat

ion

of s

uppl

y ai

r tem

pera

ture

act

ive:

This

regi

ster

indi

cate

s if

outd

oor t

empe

ratu

re c

ompe

nsat

ion

of s

uppl

y ai

r te

mpe

ratu

re is

act

ive.

Stat

e: O

ff =

Inac

tive,

On

= Ac

tive

21VE

XCon

fig.D

ST0

30O

nO

ffD

aylig

ht s

avin

gs ti

me:

This

regi

ster

indi

cate

s if

dayl

ight

sav

ings

tim

e is

now

.St

ate:

Off

= N

o, O

n =

Yes

22D

eIce

.Allo

wed

030

On

Off

DeI

ce a

llow

ed.

This

var

iabl

e sh

ows

if th

e D

eIce

func

tion

is a

llow

ed.

Off

= N

ot a

llow

ed, O

n =

Allo

wed

23M

HC

1.FS

_Act

iv0

30O

nO

ffFr

ost s

afty

func

tion

for H

CW

is a

ctiv

e.Th

is v

aria

ble

show

s if

the

frost

saf

ty fu

nctio

n fo

r eith

er M

HC

W o

r iH

CW

cur

rent

ly is

ac

tive.

Off

= In

activ

e , O

n =

Activ

e

3.1.

4O

bjec

t typ

e B

I

Inde

xN

ame

Def

ault

valu

ePo

ll in

terv

al

Uni

t/A

ctiv

e te

xt

Uni

t/In

activ

e te

xt

Des

crip

tion

93/96

3004402-2013-01-24.fm Appendix - Complete list of Registers - in English

94/96

3004402-2013-01-24.fm Appendix - Complete list of Registers - in English

95/96


Recommended