Page 2: BC80 system catalog.

A wide range of applications. BC80 comprises an extensive product portfolio and can be installed in various building types. For instance, it is a perfect solution for:

Hotels Commercial buildings Residential complexes

Government buildings Retail stores

2

Page 3: BC80 system catalog.

3

� High quality – based on decades of experience, in-depth research,and state-of-the-art productiontechnology from Siemens

� A flexible solution – expandable and compatible with future developments

� Cost-effective – moderate investment and easy adaptation to changing requirements

BC80 – advantages at a glance:

� Siemens quality – high reliability

With the BC80 system, you can offeryour customers Siemens quality,based on in-depth research and de-velopment, state-of-the-art produc-tion technology and over 150 years of experience in fire protection. Theproducts meet all technical safetyrequirements, from short-circuit pro-tection to immunity against electro-magnetic interference.

BC80 offers the flexibility your cus-tomers need, whether they want toexpand or modernize their system.Thanks to its open topology, the sys-tem is forward-looking – for easyadaptation to growth and changingrequirements.

� Siemens technology – high cost-effectiveness

BC80 combines high-quality tech-nology with cost-effectiveness, in procurement as well as operation.Moderate hardware costs keep theinvestment manageable, while theflexible, expandable installation pro-tects the long-term view – genuinebrand quality at an economical price,for years to come.

High-quality Siemens products – reliable and economical.

Your customers are responsible for the protec-tion of their employees, buildings, and assets. They also experience cost competition. As a result, they need fire protection components that deliver reliable fire detection and alarm signaling, but which are also cost-efficient. Fire safety products from Siemens position you per-fectly to satisfy your customers’ requirements. The BC80 system products range from fire detec-tors to control panels. They are moderately priced and of reliable quality.

Page 4: BC80 system catalog.

4

� Easy installation – fast protection

Because the BC80 system units havebeen designed for easy installation,buildings can be protected quickly.BC80 provides polarity-free wiring;poles can no longer be accidentallyreversed. Therefore, the networkingof BC80 fire detectors, peripheralequipment, and BC80 control panelsis rapid and accurate. The use of spurlines and T-Branches (F-Bus) furthersimplifies installation.

� Easy configuration – fast commissioning

Commissioning of the BC80 systemis supported by an integrated auto-configuration function; with it, thesystem automatically detects all inte-grated devices (auto-mapping). Thisreduces manual configuration to aminimum – eliminating a potentialsource of error. You benefit from ashorter time to a fully-operational system.

More complex manual programmingcan be conducted via the control panels or by using Windows-basedsoftware.

Easy concepts make your work easier.

BC80 fire protection products are easy to imple-ment and service. They can be quickly installed and rapidly commissioned. This reduces your costs and speeds up order processing. Simplicityof design reduces the period needed to gain familiarity with the system, so you can offer your customers user-friendly fire protection in the shortest possible time.

� Easy maintenance – no interruption of operation

All devices displayed on the con-trollers are shown with both theiraddress number and position details.These help your customers assesserror messages as aids to decision-making, and you to keep a clearoverview during installation andmaintenance. Devices with conven-tional technology, such as collectivefire detectors, can also be wired to the BC80 system via spur lines.

Tracing faulty fire detectors or periph-eral devices during system operationis swift, targeted, and cost-efficient.

Page 5: BC80 system catalog.

5

� Easy installation and fast buildingprotection – thanks to installationaids and polarity-free non-shieldedcabling

� Fast commissioning – thanks toauto-mapping and Windows-basedsoftware

� Minimal maintenance – withaddress and position of all detectorsand peripheral devices needingservice directly indicated

� Smooth expansion – via card insertsfor control panels and T-Branchesfor cabling

� Easy modernization – through useof present cabling, compatibilitywith existing peripheral equipment,and simple software uploads

BC80 – advantages at a glance:

� Easy expandability – high flexibility

BC80 grows with your customers’requirements. When buildings orrooms are extended, the BC80 in-stallation can also be expanded, forexample with new T-Branches in thecabling and expansion cards in thecontrol panels.

With an expansion card it is possibleto hook up an additional 127 periph-eral devices via the F-Bus, as many as32 additional control panels via the A-Bus, and up to three B-Bus devices,such as extinguishing control panelsor interlocking panels. This increasesoptions for larger projects.

� Easy conversion – fast modernization

Existing systems can be replaced andmodernized with BC80 without largecabling expenditures. Currently in-stalled cables can be used to networkBC80 devices, since neither the firedetector lines nor the notificationappliance circuits require a shieldedwire. The system can also be linkedwith existing peripheral devices,which saves time and money. Soft-ware updates can be uploaded via the USB port of the control panels.

Page 6: BC80 system catalog.

6

BC80 design and installation guidelines.

In this section, we illustrate best practice for installation of fire detection equipment. While not all possible cases may be covered, these are intended to provide guidelines. Local regulations may be more detailed and must always be ob-served. Please contact your local Siemens sales organization for more detailed information and documentation.

BC80 detectors – detectors should be positioned*� at least 0.5 m from the wall� max. 12 m from the previous

detector

BC80 manual call points – manual call points should be positioned*� in a clearly visible location� 1.5 m from floor level

BC80 fire control panels – mounting the fire controlpanel*Keep a minimum distance toobjects which could obscure the panel or the view to it

Page 7: BC80 system catalog.

7

* or observe local regulations

Detector positioning near elevators*

Detector positioning nearfresh air supply*

Use a support to install adetector at ceiling height*

Page 8: BC80 system catalog.

8

BC80 design and installation guidelines.

* or observe local regulations

Place the detector at thehighest point in the room*

Ensure the correct distanceto ceiling obstacles*

Position the detector withinthe top 10% of a space*

Ensure a minimum distanceto objects which could ob-struct the view to a manualcall point*

Manual call points should not be obscured by an opendoor*

Page 9: BC80 system catalog.

9

Planning aid for fieldbus.

BDS031

BDS051

BDS121

BDS132

BDS221

BDS152

BDS161

BDS331

Load Max. current (mA)Quiescent current (mA)Name Address points

0.71

0.71

0.43

0.6

0.61

0.07

4

10

0.89

0.89

2.86

3.8

2.19

0.5

16

90

1

1

1

1

2

0

10

1

Heat detector

Photoelectric smoke detector

Manual call point

Input module

Output module

Isolate module

Collective input module

Fire alarm display panel

BC8001

BC8001E

BC8001P

BC8001PE

BC8002-1

BC8002-2

BC8002-3

Source Max. current (mA)Quiescent current (mA)Name Address points

48.5

63.3

51.2

66.0

130.0

170.0

210.0

75.7

113.7

97.0

135.6

224.8

352.6

481.4

127

254

127

254

500

1,000

1,500

Compact controller with 1 line

Compact controller with 2 lines

Compact controller with 1 line, printer

Compact controller with 2 lines, printer

Wall-mounted (500 dev.)

Wall-mounted (1,000 dev.)

Wall-mounted (1,500 dev.)

Detectors and peripherals

Panels and systems

Page 10: BC80 system catalog.

A-Bus

Compact

Heat detector BDS031

Photoelectric smoke detector BDS051

Manual call point BDS121/e

Output module BDS221

Manualcall point BDS121/e

Input module BDS132

Collective input moduleBDS161Compact controller

BC8001

F-Bus

Interlocking panelBT8012

Interlocking panelBT8011

Compact controllerBC8001

Collective heat detector HI520

10

BC80 at a glance.

Page 11: BC80 system catalog.

B-BusExtinguishing panel BC8013

Standard control panelBC8002

Standard

F-Bus

Collective photoelectric smoke detector OP520

Standard control panelBC8002

11

Legend

A-Bus Network for connecting control panels (max. 32 control panels, bus length 1 km – can be extended with CAN-Bus bridge)

F-Bus Bus system for connecting line devices (max. 127 devices per line, bus length 1 km)

B-Bus Network for connecting up to 3 B-Bus devices (bus length 100 m)

Page 12: BC80 system catalog.

Building Technologies

BC80 – Innovative fire safety products from Siemens.

Are you seeking reliable and easy to use fire safety products everywhere? With theaddressable BC80, Siemens offers an extensive and economical portfolio from firedetectors to control panels. Thanks to its open topology, BC80 is highly flexible andadapts easily to changing requirements. The perfect solution for a wide range of applications from small to large buildings, it can be quickly installed, networked, andput into service. Backed by 150 years of experience in fire protection, BC80 offers the effective protection you want for people, buildings and assets.For more information, please visit www.siemens.com/buildingtechnologies.

Genuine quality for your protection.

Page 13: BC80 system catalog.

Table of Contents

1© Siemens Building Technologies Group

Panels & Systems ................................................................................................................. 1-1

Addressable Control Panels .............................................................................................. 1-1

Detectors & Peripherals........................................................................................................ 2-5

Conventional Detectors and Bases (Collective).................................................................. 2-5

Addressable Detectors and Bases...................................................................................... 2-6

Manual Call Points ........................................................................................................... 2-7

Addressable Modules ....................................................................................................... 2-8

Spare Parts & Upgrades...................................................................................................... 3-10

Page 14: BC80 system catalog.
Page 15: BC80 system catalog.

Panels & SystemsAddressable Control Panels

1-1© Siemens Building Technologies Group

1

Type Order No.

BC8001.. BC8001 Compact Control Unit

BC8001 is a control unit suitable for small sized projects and construc-tions. It has the following features:

l Compatible to BDS series of field devices.l Features a polarity free F-BUS with a twisted pair of wires

(Φ 1.5mm2). Transmission distance is up to 1000m. All devices should be evenly distributed.

l Specialized BDS Algorithm enhance immunity against environment disturbances.

l Menu driven man-machine interface to allow very easy operation.l With optional extension card the device can be networked with up to

32 other BC80 control units (BC8001/BC8002).l With optional extension card it is possible to connect up to 3 B-Bus

devices‚ i.e. interlocking and extinguishing panels.l An optional printer can be mounted into the control unit.l The system can be easily configured directly on the panel or via PC.l Configuration data can be uploaded to a PC at any time.

Number of detector lines 1

Number of field devices 127

System Network -

Built-in printer -

LCD Display 240 x 128‚ Backlit

Auto Mapping Yes

Event memory 1000

Digital inputs/outputs 1 Dry contact (24 VDC / 3 A)1 OC output2 Monitored inputs

Operating voltage (Main Power) 187... 242 VAC50... 60 Hz

Battery capacity 24 VDC‚ 7 Ah

Download/Upload USB

Dimensions (W x H x D) 370 x 265 x 120 mm

Weight (without battery) 3.0 kg

Data sheet A5Q00016399A

BC8001..

BC8001 BC8001 Compact Control Unit with 1 F-Bus line for up to127 Devices

Technical details as BC8001..

A6C50000016

BC8001P BC8001P Compact Control Unit with 1F-Bus line and printer

As BC8001.. for technical details‚ but with the following differences:

One printer TP8000 (thermal sensitive printer) is built-in.

A6C50000018

Page 16: BC80 system catalog.

Panels & SystemsAddressable Control Panels

1-2 © Siemens Building Technologies Group

Type Order No.

BC8001E BC8001E Compact Control Unit with 2 F-Bus lines for up to 254 Devices

As BC8001.. for technical details‚ but with the following differences:

An extension card is built-in additionally in the BC8001. This allows

l Interconnection of up to 32 BC8001 or BC8002 control units (A-Bus).l Interconnection of up to 3 B-BUS equipments (BT8011/12 interlock-

ing panel‚ BC8013 extinguishing panel). Another external power supply (3 A @ 28 VDC) must be used.

A6C50000017

BC8001PE BC8001PE Compact Control Unit with 2 F-Bus lines and printer

As BC8001.. for technical details‚ but with the following differences:

Printer and extension card are built-in additionally.

A6C50000019

BC8002.. BC8002-1/e wall-mounted Advanced Control Unit

BC8002 is an advanced control unit based on latest technology to sup-port easy operation and commissioning.

l Text and graphic Display with 10” LCD,640x320 dots‚ backlit.l Easy operation with a menu structure similar to Windows Explorer.l Advanced micro-processor system (32-bit ARM based micro-proces-

sor).l LCD display shows real time values of fire parameters for every detec-

tion point.l Auto mapping of the controller configuration simplifies commission-

ing.l Multi-tasking real time operating system monitors the system regu-

larly. This ensures high system reliability.l Up to 1000 events are stored in the event memory.l Modular structure allows flexible system customization.l System configurations can be done via panel keypads or via PC tool

(parameters and logic expressions).l Powerful interlocking features can be added for demanding control

functions.l Up to 32 control units can be interconnected via A-Bus network.

Transmission distance is up to 1000m with a twisted pair of wires (Φ 1.5mm2).

l BC8002 can be connected to a management station.

Mains voltage 220 VAC‚ 50 Hz

Operating voltage 23... 30 VDC

Battery capacity 24 VDC‚ 17 Ah

Quiescent current 40... 100 W

Fuse 2.0 A

Operating temperature -10... +50 °C

Relative humidity 95% (40 ± 2 °C)

Dimensions (W x H x D) 700 x 520 x 120 mm

Weight 22 kg

Data sheet A5Q00016408A

BC8002..

BC8002-1 BC8002-1/e wall-mounted Advanced Control Unit for up to 500 devices‚ 4 loops

As BC8002.. for technical details‚ but with the following differences:

The fire alarm control unit with the original 1 line card can connect up to 500 devices.

A6C50000029

Page 17: BC80 system catalog.

Panels & SystemsAddressable Control Panels

1-3© Siemens Building Technologies Group

1

Type Order No.

BC8002-2 BC8002-2 wall-mounted Advanced Control Unit for up to 1000 devices

As BC8002.. for technical details‚ but with the following differences:

The fire alarm control unit with an additional line card can connect up to 1000 devices‚ using 8 loops

A6C50000030

BC8002-3 BC8002-3 wall-mounted Advanced Control Unit forv1500 devices

As BC8002.. for technical details‚ but with the following differences:

The fire alarm control unit with 3 line cards can connect up to 1500 devices‚ using 12 loops

A6C50000030

BT80.. BT8011 / BT8012 Interlocking Panel

BT8011 / BT8012 are interlocking panels. It allows manual and auto-matic control of external equipment. It is usually installed in the fire control center together with fire alarm panels in order to control pumps‚ fans etc.

Operating voltage 24... 29 VDC

Quiescent current 50 mA

Operating temperature 0... +50 °C

Storage temperature -20... +60 °C

Relative humidity 95 % Rh

Load for each output 300 Ω 4 KΩ

Installation height 3 U

Data sheet A5Q00016409A

BT80..

BT8011 BT8011 Interlocking Panel

As BT80.. for technical details‚ but with the following differences:

l equipped with 16 inputs and 8 outputs. l Inputs: 8 inputs are for general purpose and 8 inputs are for confir-

mations. l Outputs: OC output capacity is 28 VDC / 80 mA.l Output can be configured as steady on or pulsed.l Device is connected with the control unit via B-Bus.l Indication of activation‚ confirmation and fault for each output .l Silence and lamp test keypad available.l Panel can be set to manual mode or automatic mode.l Panel address‚ output mode‚ connection mode are set with DIP-

switch.l TP8000 printer is built-in.

A6C50000032

BT8012 BT8012 Interlocking Panel (without printer)

As BT80.. for technical details‚ but with the following differences:

l Equipped with 16 outputs and 24 inputs.l Inputs: 8 inputs are for general purpose‚ 16 inputs are for confirma-

tionl Outputs: each OC output capacity is 28 VDC / 80 mA.l Output can be configured as steady on or pulsed.l Device is connected with the control unit via B-Bus.l Indication of activation‚ confirmation and fault for each output.l Silence and lamp test keypad available.l Panel can be set to manual mode or automatic mode.l Panel address‚ output mode‚ connection mode are set with DIP-

switch.

A6C50000033

Page 18: BC80 system catalog.

Panels & SystemsAddressable Control Panels

1-4 © Siemens Building Technologies Group

Type Order No.

BC8013.. BC8013 Extinguishing Panel

The extinguishing panel is used for the control of the extinguishingsections of a fire installation.

l One panel monitors 2 extinguishing sections.l Each section is equipped with 3 outputs to activate extinguishing

alert‚ extinguishing section separation and gas release. 3 inputs serve as confirmation of above control outputs.

l The device is connected via B-Bus. The address is set with a DIP-switch.

l Important information of the extinguishing section are displayed on the control unit.

l Parameters can be configured on the panel directly or via PC-Tool.l External control wires are monitored for short or open circuit.l Panel can be set to automatic mode and manual mode.l Panel supports auto mapping feature .

Operating voltage 24... 28 VDC

Quiescent current 40 mA

Operating current 200 m A

Output current 80 m A

Maximum current per output 200 m A

Operating temperature -20... +40 °C

Data sheet A5Q00016401A

BC8013..

BC8013 BC8013 Extinguishing Panel

Same technical details as BC8013..

A6C50000038

BC8013H BC8013H wall-mounted Extinguishing Panel

As BC8013.. for technical details‚ but with the following differences:

Wall-mounted Extinguishing Panel

A6C50000022

Page 19: BC80 system catalog.

Detectors & PeripheralsConventional Detectors and Bases (Collective)

2-5© Siemens Building Technologies Group

2

Type Order No.

HI520 HI520 Collective Heat Detector (Rate of Rise and Fix Temperature)

l Newly developed circuit and sensor ensure high performance of fixed and rate of rise temperature detection.

l High stability against dust‚ electromagnetic interference‚ tempera-ture fluctuation‚ humidity and corrosion.

l Produced with SMT advanced technology.

Operating voltage 16... 32 VDC

Output voltage 5... 13 VDC

Operating temperature -10... +50 °C

Storage temperature -30... +75 °C

Relative humidity 95 % (40 ± 2 °C)

Quiescent current 100 μA

Alarm current 1.5 mA

EMC 10 V/m

Data sheet A5Q00016379A

A6C50000009

OP520 OP520 Collective Optical Smoke Detector

The OP520 is an non addressable detector which can be connected in to S11 and BC80 system via corresponding collective input modules.

l Patented optical structure and labyrinth.l Homogeneous sensitivity for different kind of smoke.l High stability against dust‚ electromagnetic interference‚ tempera-

ture fluctuation‚ humidity and corrosion.l Produced with advanced SMT technology.l Connection is independent of line polarity.

Operating voltage 21... 29 VDC

Output voltage 5... 13 VDC

Operating temperature -10... +50 °C

Storage temperature -30... +75 °C

Relative humidity 95 % (40 ± 2 °C)

Quiescent current 100 μA

Alarm current 1.5 mA

EMC 10 V/m

Data sheet A5Q00016380A

A6C50000010

SO520 SO520 Collective Detector Base

The detector base for field devices HI520 and OP520.

Data sheet A5Q00016382A

A6C50000011

Page 20: BC80 system catalog.

Detectors & PeripheralsAddressable Detectors and Bases

2-6 © Siemens Building Technologies Group

Type Order No.

BDS031 BDS031 Addressable Heat Detector (Rate of Rise and Fix Tempera-ture)

BDS031 is a heat detectors which can be connected to the F-Bus

l Newly developed circuit and sensor ensure high performance of fixed and rate of rise temperature detection.

l High stability against dust‚ electromagnetic interference‚ tempera-ture fluctuation‚ humidity and corrosion.

l Produced with SMT advanced technology.

Operating voltage 16... 32 VDC

Operating temperature -10... +50 °C

Storage temperature -30... +75 °C

Relative humidity 95 % (40 ± 2 °C)

Quiescent current 1.0 mA

Alarm current 3.0 mA

EMC 10 V/m

Data sheet A5Q00016383A

A6C50000001

BDS051 BDS051 Addressable Optical Smoke Detector

BDS051 is smoke detector which can be connected to the F-Bus.

l Patented labyrinth optical structure.l New built-in ASIC ensures high reliability of data processing.l Homogeneous response to different kind of smoke.l High stability against dust‚ electromagnetic interference‚ tempera-

ture fluctuation‚ humidity and corrosion.l Produced with SMT advanced technology.

Operating voltage 16... 32 VDC

Operating temperature -10... +50 °C

Storage temperature -30... +75 °C

Relative humidity 95 % (40 ± 2 °C)

Quiescent current 1.0 mA

Alarm current 3.0 mA

EMC 10 V/m

Data sheet A5Q00016384A

A6C50000002

BDS000 BDS000 Addressable Detector Base

Detector base is for field devices BDS051 and BDS031.The detector covers the whole base‚ the wiring capacity is 1.0 to 1.5 mm².

Data sheet A5Q00016385A

A6C50000000

Page 21: BC80 system catalog.

Detectors & PeripheralsManual Call Points

2-7© Siemens Building Technologies Group

2

Type Order No.

BDS121 BDS121 Manual Call Point

Manual call point can immediate trigger a fire alarm by breaking the glass.

l Connected to F-Busl Installed in the public area such as staircase‚ elevator lobby‚ etcl Device address can be set via a DIP-switch.l A built-in dry contact can be used to activate another equipment.l Mounted on the wall 1.5 meters above the ground.l Electronic part and housing are delivered separately.

Operating voltage 24 VDC

Operating temperature -20... +55 °C

Relative humidity 95 % (40 ± 2 °C)

Quiescent current 1 mA

Alarm current 3.0 mA

Capacity of dry contact 24 VDC / 0.1 A

EMC 10 V/m

Data sheet A5Q00016386A

A6C50000003

Page 22: BC80 system catalog.

Detectors & PeripheralsAddressable Modules

2-8 © Siemens Building Technologies Group

Type Order No.

BDS132 BDS132 Input Module

The input module serves as an interface to transmit alarms or technical signals from other equipments to the fire alarm control unit.

l Connected to the F-Bus‚ device address can be set with a DIP-switch.l Serves as interface for potential free signals from flow switches‚ pres-

sure switches‚ etc to the fire alarm system.l The signal will be transmitted to the controller and trigger corre-

sponding actions.l Connection faults will be automatically detected and displayed on

the controller.

Operating voltage 24 VDC

Operating temperature -20... +55 °C

Relative humidity 95 % (40 ± 2 °C)

Activation current 3 m A

Quiescent current 1 mA

Wiring Capacity 1.0 1.5 mm²

Data sheet A5Q00016394A

A6C50000004

BDS152 BDS152 Isolation Module

The isolation module is used to isolate a short circuit on the detection bus. The device will automatically recover to its normal status when the cause of the short circuit disapears.

l The isolation module separates a short circuit on the F-Bus.l Parallel connection on the first place of each branch or stub is possi-

ble.l No device address is required.l When a single loop is used to connect devices mounted on several

floors it is recommended to install one isolation module on each floor.

l Up to 25 field devices can be mounted to an isolation module.l The connection is polarity free.l Faults will be automatically detected and displayed on the controller.

Operating temperature -20... +50 °C

Relative humidity 95 % (40 ± 2 °C)

Activation current 0.5 mA

Pass through voltage 1 VDC

Wiring Capacity 1.0... 1.5 mm²

Data sheet A5Q00016395A

A6C50000005

Page 23: BC80 system catalog.

Detectors & PeripheralsAddressable Modules

2-9© Siemens Building Technologies Group

2

Type Order No.

BDS161 BDS161 Collective Input Module

Collective input module can connect collective detectors to the F-Bus

l Directly connected to the F-Bus‚ addresses are set with a DIP-switchl Up to 15 collective detectors can be connected to the modulel An end of line element P6KE18CA has to be used.l Module transmits alarm‚ fault and danger level signal to the control

unitl The same indications are displayed on the module.l Connection is polarity free.l Faults will be automatically detected and displayed on the control

unit.

Alarm voltage 3.7... 16.4 VDC

Fault voltage 0... 3.7 VDC (short)22.1 VDC (open)

Normal voltage 16.4... 22.1 VDC

Alarm current <16 mA

Operating temperature -10... +50 °C

Quiescent current <4 mA

Relative humidity 95 % (40 ± 2 °C)

Wiring Capacity 1.0... 1.5 mm²

Data sheet A5Q00016397A

A6C50000006

BDS221 BDS221 Output Module

The output module is used to activate external equipment according to the function of the fire alarm unit.

l Connected to F-Bus‚ addresses are set with a DIP-switch.l Output can be configured as pulse or steady on with DIP-switch.l Connection is polarity free.l The input signal for feedback is a potential free contact.l It is not recommended to use this module for extinguishing control

directly.l Faults will be automatically detected and displayed on the controller.

Operating voltage 24 VDC

Operating temperature -10... +50 °C

Relative humidity 95 % (40 ± 2 °C)

Activation current 3 mA

Quiescent current 1 mA

Relay output 125 VAC / 0.6 A24 VDC / 2 A

Status LEDs Steady output - Steady ONPulse Output - Flashing

Wiring Capacity 1.0... 1.5 mm²

Data sheet A5Q00016398A

A6C50000007

Page 24: BC80 system catalog.

Spare Parts & Upgrades

3-10 © Siemens Building Technologies Group

Type Order No.

TP8000 TP8000 Printer

A thermal sensitive printer is used to print events.

Data sheet A5Q00016403A

A6C50000028

BCE8001 BCE8001 Extension Card

Extension card for BC8001 compact controller. This card contains the following interfaces:

l A-Bus interface to add the network feature to the compact controller (networkable up to 32 controllers).

l B-Bus interface to allow BC8001 to connect up to 3 B-Bus devices.l F-Bus interface for additional up to 127 devices.

Data sheet A5Q00016402A

A6C50000024

BCC8001 BCC 8001 Main Board of BC80 Compact

Data sheet A5Q00016405A

A6C50000035

BT8002 BT8002 Operation Panel

The BT8002 is the operation panel of BC8002 Advanced Control Unit.

l The operation panel consists of the main board BCC8002‚ the CPU board BCC8011‚ LCD and the keypads‚ and LED's as indicators.

l Connected with other control units via A-Bus.l Connected with interlocking panels‚ line cards‚ extinguishing panels

via B-Bus.l Download/Upload port on the CPU board.l BT8002 Operation panel features also numerical keys and loud

speaker.l A communication port for connection to a management station is

built-in.

Data sheet A5Q00016413A

A6C50000034

Page 25: BC80 system catalog.

Spare Parts & Upgrades

3-11© Siemens Building Technologies Group

3

Type Order No.

BCB8001 BCB8001 Wall-mounted Power Supply (8A)

Input voltage 220 VAC / 50HZ187... 242 VAC (Effective)

Output voltage 20... 28 VDC / 8 A (Main power ork-ing)24 VDC (Only battery working)

Operating temperature -10... 50 °C

Relative humidity 95 % Rh

Protection Output 8.0 * 110 % (Over current protection)Output 1.0 Ω (Output short pro-tection)Voltage <20.0 V (Battery low pro-tection)

Battery CB12170 (12 V / 17 AH)‚CB12250 (12 V / 25 AH)‚CB12380 (12 V / 38 AH)‚DJW (12 V / 24 AH)‚DJW (12 V / 38 AH)‚NP (12 V / 24 AH)‚NP (12 V / 38 AH)

Data sheet A5Q00016411A

A6C50000039

BCC8002 BCC8002 Main Board of BC8002 Advanced Control Unit

The main board includes l A-Bus port ‚ l B-Bus port‚ l I/O port‚ l FMS connection port‚ l power signal port etc. The board handles data gathered from F-Bus and other channels. It serves as the data processing center of the control unit.

Data sheet A5Q00016407A

A6C50000036

Page 26: BC80 system catalog.

Spare Parts & Upgrades

3-12 © Siemens Building Technologies Group

Type Order No.

BCM8001 BCM8001 Line Card for BC8002 Advanced Control Unit

The BCM8001 is the line card connecting BDS field devices

l Each BCM8001 can connect 4 loops; each loop can connect up to 127 devices.

l Overload protection: recovers to normal status when the cause of overload disappears.

l B-Bus address is set with a DIP-switch on the board.

Number of loops 4

Number of addresses 127 (on one loop)

Max. load factor 150 (for each loop)

Wiring Capacity RVS1.0... RVS1.5

Max. distance per line 1000 m

Resistor per line 300 Ω

Capacitor per line 300 nF

Protection Short protectionOver voltage protection

Connectable field devices BDS Series

Operating voltage Modulated 16... 32 VDC

Quiescent current Full load: 200 mANo Load: 110 mA

Data sheet A5Q00016410A

A6C50000037

Page 27: BC80 system catalog.

Type Index

1© Siemens Building Technologies Group

Type Description Order No. Page

BC8001 BC8001 Compact Control Unit with 1 F-Bus line for up to127 Devices

A6C50000016 1-1

BC8001.. BC8001 Compact Control Unit BC8001.. 1-1

BC8001E BC8001E Compact Control Unit with 2 F-Bus lines for up to 254 Devices

A6C50000017 1-2

BC8001P BC8001P Compact Control Unit with 1F-Bus line and printer A6C50000018 1-1

BC8001PE BC8001PE Compact Control Unit with 2 F-Bus lines and printer A6C50000019 1-2

BC8002-1 BC8002-1/e wall-mounted Advanced Control Unit for up to 500 devices‚ 4 loops

A6C50000029 1-2

BC8002-2 BC8002-2 wall-mounted Advanced Control Unit for up to 1000 devices

A6C50000030 1-3

BC8002-3 BC8002-3 wall-mounted Advanced Control Unit forv1500 devices A6C50000031 1-3

BC8002.. BC8002-1/e wall-mounted Advanced Control Unit BC8002.. 1-2

BC8013 BC8013 Extinguishing Panel A6C50000038 1-4

BC8013.. BC8013 Extinguishing Panel BC8013.. 1-4

BC8013H BC8013H wall-mounted Extinguishing Panel A6C50000022 1-4

BCB8001 BCB8001 Wall-mounted Power Supply (8A) A6C50000039 3-11

BCC8001 BCC 8001 Main Board of BC80 Compact A6C50000035 3-10

BCC8002 BCC8002 Main Board of BC8002 Advanced Control Unit A6C50000036 3-11

BCE8001 BCE8001 Extension Card A6C50000024 3-10

BCM8001 BCM8001 Line Card for BC8002 Advanced Control Unit A6C50000037 3-12

BDS000 BDS000 Addressable Detector Base A6C50000000 2-6

BDS031 BDS031 Addressable Heat Detector (Rate of Rise and Fix Temper-ature)

A6C50000001 2-6

BDS051 BDS051 Addressable Optical Smoke Detector A6C50000002 2-6

BDS121 BDS121 Manual Call Point A6C50000003 2-7

BDS132 BDS132 Input Module A6C50000004 2-8

BDS152 BDS152 Isolation Module A6C50000005 2-8

BDS161 BDS161 Collective Input Module A6C50000006 2-9

BDS221 BDS221 Output Module A6C50000007 2-9

BT80.. BT8011 / BT8012 Interlocking Panel BT80.. 1-3

BT8002 BT8002 Operation Panel A6C50000034 3-10

BT8011 BT8011 Interlocking Panel A6C50000032 1-3

BT8012 BT8012 Interlocking Panel (without printer) A6C50000033 1-3

HI520 HI520 Collective Heat Detector (Rate of Rise and Fix Temperature) A6C50000009 2-5

OP520 OP520 Collective Optical Smoke Detector A6C50000010 2-5

SO520 SO520 Collective Detector Base A6C50000011 2-5

TP8000 TP8000 Printer A6C50000028 3-10

Page 28: BC80 system catalog.

12

www.siemens.com/buildingtechnologies

Siemens Switzerland LtdBuilding Technologies GroupInternational HeadquartersGubelstrasse 22CH-6301 ZugTel +41 41 724 24 24 Fax +41 41 724 35 22

The information in this document contains general descriptions of technical options available, which do not always have to be present in individual cases. The required features should thereforebe specified in each individual case at the time of closing the contract.

Windows is a registered trademark of Microsoft Corporation

Subject to change • Order no. 0-92065-en • © Siemens Switzerland Ltd • Printed in Switzerland • 10705 Ah


Recommended