+ All Categories
Home > Documents > Bills of Quantity

Bills of Quantity

Date post: 04-Apr-2018
Category:
Upload: khaled3601
View: 232 times
Download: 0 times
Share this document with a friend

of 31

Transcript
  • 7/30/2019 Bills of Quantity

    1/31

    Bills of QuantityItem No.

    Description Manufacturer Country of Origin

    CatalogueReference

    1.1 FIRE FIGHTING

    1.1.1 Summary

    This Section includes fire alarm systems with manual stations, detectors, signalequipment, controls, and devices.

    1.1.2 System Description

    General: Non-coded, addressable-analog system with manual and automaticalarm initiation; automatic sensitivity control of certain smoke detectors; and mul-tiplexed signal transmission dedicated to fire alarm service only.

    Scope of Work: Provide the following:

    FACP manual stations, automatic fire detectors, interface with other systems, wiring, wire-ways and all accessories to form a complete system.

    1.1.3 Quality Assurance

    Codes and Standards: Comply with the following:

    NFPA 70, "National Electrical Code". NFPA 72, "National Fire Alarm Code". NFPA 101, "Code for Safety to Life from Fire in Buildings and Structures".

    1.1.4 Functional Description System

    Control of System: Fire Alarm Control Panel (FACP).

    System Supervision: Automatically detect and report open circuit, short circuit,and ground fault of wiring for initiating device, signaling line, and notification-ap-pliance circuits. System shall detect ground fault by panel, loop circuit, and de-vice.

    Priority of Signals: Automatic alarm response functions resulting from an alarmsignal from 1 zone or device are not altered by subsequent alarm, supervisory, or trouble signals. An alarm signal has the highest priority. Supervisory and troublesignals have second- and third-level priority. Higher-priority signals take prece-dence over signals of lower priority, even when the lower-priority condition occursfirst. Annunciate and display all alarm, supervisory, and trouble signals regard-less of priority or order received.

    Noninterference: A signal on one zone shall not prevent the receipt of signalsfrom other zones.

    System Reset: All zones are manually re-settable from the FACP after initiating

    devices are restored to normal.

  • 7/30/2019 Bills of Quantity

    2/31

    System shall continually monitor any changes in the sensitivity of individualsmoke or heat sensors due to environmental effects.

    The Contractor shall provide all necessary hardware, software, and auxiliaries toensure the following functions are fulfilled:

    Connection to airport network for interfacing with all other fire alarm systemsinstalled in the other buildings in the airport site.

    One main Graphic User Interface (GUI) located in the Security Room shallcontrol and monitor all fire alarm system and points of the new system speci-fied herein and the other fire alarm systems installed in the different buildingswithin the airport. It shall have full control and monitoring of these new firealarm systems through 2-way communication.

    The entire fire alarm system including integration arrangement detailed in (1)above shall be UL listed for life safety applications.

    System Alarm Capability during Circuit Fault Conditions: System wiring and cir-

    cuit arrangement prevent alarm capability reduction when an open circuit, groundor wire-to-wire short occurs, or an open circuit and a ground occur at the sametime in an initiating device circuit, signal line circuit, or notification-appliance cir-cuit.

    Initiating Device Circuits (IDC) System Wiring: Class A, Style D or E. Signaling Line Circuits (SLC) System Wiring: Class A, Style 7. Notification Appliance Circuits (NAC): Class A, Style Z.

    Loss of primary power at the FACP initiates a trouble signal. The FACP indicateswhen the fire alarm system is operating on the secondary power supply.

    Basic Alarm Performance Requirements: Unless otherwise indicated, automaticalarm operation of a smoke or heat detector initiates the following:

    Activation of presignal at FACP

    a. Local alarm in the control panel for the period of a programmable time T1. b. During this delay time (T1), a local (staff) alarm (stage 1) only is to be giv-

    en. If the alarm is not acknowledged before timer T1 runs out, this is toresult in notification-appliance operation (stage 2) as detailed in subpara-graph 1.1.4 below.

    c. If the alarm is acknowledged while T1 is still running, T1 is to be reset anda programmable timer T2 is to be started. T2 is to delay the notification-

    appliance operation (stage 2) further, and so provide time for human in-vestigation of the alarm cause.

    d. If no reset action takes place before T2 runs out, notification-applianceoperation (stage 2) is to be given.

    Notification-appliance operation (stage 2).a. Evacuation signal throughout the building.b. Activation of visual strobes.

    Identification at the FACP of the location and the type of device originatingthe alarm.

    Shutdown of fans and other air-handling equipment serving zone when alarmwas initiated.

  • 7/30/2019 Bills of Quantity

    3/31

    Closing of smoke dampers in air ducts of system serving zone where alarmwas initiated.

    Recording of the event in the system memory. Initiate operation of smoke management system. Recording of the event by the system printer.

    All operations shall be according to the approved cause & effect matrix.

    Alarm Silencing, System Reset and Indication: Controlled by switches in theFACP

    Silencing switch operation halts alarm operation of notification appliances andactivates an "alarm silence" light. Display of identity of the alarm zone or de-vice is retained.

    Subsequent alarm signals, from other devices or zones, shall reactivate notifi-cation appliances, until silencing switch is operated again.

    When alarm initiating, do not return to normal status, and system reset switch

    is operated; notification appliances operate again until alarm silence switch isreset.

    When fire alarm system is reset, all auxiliary systems shall be released fromfire mode.

    Remote Detector Sensitivity Adjustment: Manipulation of controls at the FACPcauses the selection of specific addressable smoke detectors for adjustment, dis-play of their current status and sensitivity settings, and control of changes inthose settings. Same controls can be used to program repetitive, scheduled, au-tomated changes in sensitivity of specific detectors. Sensitivity adjustments andsensitivity-adjustment schedule changes are recorded in system memory and areprinted out by the system printer.

    Removal of an alarm-initiating device or a notification appliance initiates the fol-lowing:

    A "trouble" signal indication at the FACP for the device or zone involved. Recording of the event by the system printer. Recording of the event in the system memory.

    Printout of Events: On receipt of the signal, print alarm, supervisory, and troubleevents. Identify zone, device, and function. Include type of signal (alarm, super-visory, or trouble), and date and time of occurrence. Differentiate alarm signalsfrom all other printed indications. Also print system-reset event, including thesame information for device, location, date, and time. Commands initiate theprintout of a list of existing alarm, supervisory, and trouble conditions in the sys-tem and a historical log of events.

    FACP Alphanumeric Display: Plain-English-language descriptions of alarm, su-pervisory, and trouble events; and addresses and locations of alarm-initiating or supervisory devices originating the report. Display monitoring actions, systemand component status, system commands, programming information, and datafrom the system's historical memory.

    System shall be able to report a map of all initiating devices connected to the sys-tem for confirmation of As-Built drawings, and it shall show physical wiring of T-type by device type and number.

  • 7/30/2019 Bills of Quantity

    4/31

    Expansion Capability: Increase number of devices in the future by 25 percentabove those indicated without adding any internal or external components or ca-ble conductors.

    1.1.5 Manual Stations

    Description: Fabricated of metal or plastic, and finished in red with molded,raised-letter operating instructions of contrasting color.

    Double-action mechanism requires two actions to initiate an alarm, nonbreak-glass, and lift-cover and pull lever type. FACP

    Station Reset: Key or wrench operated; double-pole, double-throw; switchrated for the voltage and current at which it operates.

    Weatherproof Protective Shield: Factory-fabricated clear plastic enclosure,hinged at the top to permit lifting for access to initiate an alarm.

    Manual station shall be addressable type to communicate manual-stationstatus (normal, alarm, or trouble) to the FACP.

    Manual station shall have integral LED. Manual station shall have integral test switch.

    1.1.6 Smoke Detectors

    General: Include the following features:

    Operating Voltage: 24 V dc, nominal. Self-Restoring: Detectors do not require resetting or readjustment after actu-

    ation to restore them to normal operation. Plug-in Arrangement: Detector and associated electronic components are

    mounted in a module that connects in a tamper-resistant manner to a fixed

    base with a twist-locking plug connection. Terminals in the fixed base acceptbuilding wiring.

    Integral Visual-Indicating Light: LED type. Indicates detector has operated.LED brightness shall be high enough such that it could be clearly distin-guished with naked eye at 6 meters distance with ambient lighting conditions.

    Sensitivity: Can be tested and adjusted in-place after installation. Mounting: Surface or semi-recessed ceiling mounted type, located as shown

    on Drawings, with head removable from fixed twist-lock base. Removal of detector head is to interrupt supervisory circuit and cause trouble signal atcontrol panel. Normal flat surface coverage is to be over 100 m at mountingheight of 6 m.

    Integral Addressable Module: Arranged to communicate detector status (nor-mal, alarm, or trouble) to the FACP.

    Circuitry for 2-way communication with the FACP. Each time the detector ispolled, it is to communicate its type (ionization, optical, etc.) and ananalog/digitally-encoded value corresponding to its sensitivity and status withmicrocomputer processing in the control unit. Detector is to be automaticallyaddressed by its location in the signaling loop.

    Remote Controllability: Unless otherwise indicated, detectors are analog-ad-dressable type, individually monitored at the FACP for calibration, sensitivity,and alarm condition, and individually adjustable for sensitivity from the FACP.

    1.1.7 Fire Alarm Control Panel (FACP)

    Cabinet: Lockable steel enclosure. Arrange interior components so operationsrequired for testing or for normal maintenance of the system are performed from

  • 7/30/2019 Bills of Quantity

    5/31

    the front of the enclosure. If more than one unit is required to form a completecontrol panel, fabricate with matching modular unit enclosure to accommodatecomponents and to allow ample gutter space for field wiring and interconnectingpanels. FACP shall be of modular design and shall not have single point of fail-ure.

    Identify each enclosure with an engraved, red, laminated, phenolic-resinnameplate with lettering not less than 25 mm high. Identify individual compo-nents and modules within cabinets with permanent labels.

    Mounting: Surface.

    Alarm and Supervisory Systems: Separate and independent in the MFS/FACP. Alarm-initiating zone boards consist of plug-in cards. Construction requiring re-moval of field wiring for module replacement is unacceptable.

    Control Modules: Include types and capacities required to perform all functionsof fire alarm systems.

    Indications: Local, visible, and audible signals announce alarm, supervisory, andtrouble conditions. Each type of audible alarm has a different sound.

    Resetting Controls: Prevent the resetting of alarm, supervisory, or trouble signalswhile the alarm or trouble condition still exists.

    Alphanumeric Display and System Controls: Arranged for interface between hu-man operator at the FACP and addressable system components, including an-nunciation and supervision. Display alarm, supervisory, and component statusmessages and the programming and control menu.

    Display: Liquid-crystal type, 80 characters minimum, of which 40 charactersare available to the user for device location identification.

    Keypad: Arranged to permit entry and execution of programming, display,and control commands.

    Instructions: Printed or typewritten instruction card mounted behind a plastic or glass cover in a stainless steel or aluminum frame. Include interpretation and de-scribe appropriate response for displays and signals. Briefly describe the func-tional operation of the system under normal, alarm, and trouble conditions.

    Interface with other systems: Provide standard software protocol and requiredhardware to communicate and interface all information to the SACS, fire-fightingsystems.

    1.1.8 Emergency Power Supply

    General: Components include lead acid batteries, charger, and an automatictransfer switch.

    Battery Nominal Life Expectancy: 20 years, minimum.

    Battery Charger: Solid-state, fully automatic, variable-charging-rate type. Pro-vide capacity for 150 percent of the connected system load while maintaining bat-teries at full charge. If batteries are fully discharged, the charger recharges themcompletely within 4 hours. Charger output is supervised as part of system power supply supervision.

  • 7/30/2019 Bills of Quantity

    6/31

    Integral Automatic Transfer Switch: Transfers the load to the battery without lossof signals or status indications when normal power fails.

    Normal life: 24 hours under standby and 1/2 hour under full alarm load conditionsat the end of the 24 hours.

    Remote power supply for devices is not recommended. However, if provided ininevitable circumstances, the remote power supply shall be fully supervised bythe control panel and backed-up by battery as per paragraph 1.1.8.

    1.1.9 Wire

    Non-Power-Limited Circuits: Solid-copper conductors with 600 V rated, 75deg. C (167 deg. F), color-coded insulation.

    Initiating devices circuits: 1.5 mm (No. 16 AWG), minimum, and subject tocircuit load.

    Notification appliance circuits: 2.5 mm (No. 12 AWG), minimum, and subjectto circuit load.

    Loudspeaker circuits: 1.5 mm (No. 16 AWG), minimum, and subject to circuitload.

    Wires and Cables: Comply with NFPA 72 and 101, and certified to have passedIEC 331 and 332 flame resistance and fire retardant tests.

    Cables are to be silicone rubber insulated, with overall PVC sheath bonding tocoated aluminum foil.

    1.1.10 Execution: Equipment Installation

    Connect the FACP with a disconnect switch with lockable handle or cover.

    Manual Stations: Mount semi-flush in recessed back boxes.

    Ceiling-Mounted Smoke Detectors: Not less than 100 mm from a sidewall to thenear edge. For exposed solid-joist construction, mount detectors on the bottomof joists. On smooth ceilings, install not more than 9 m apart in any direction.

    Wall-Mounted Smoke Detectors: At least 100 mm , but not more than 300 mm ,below the ceiling.

    Smoke Detectors near Air Registers: Install no closer than 1520 mm .

    The selection and placement of smoke detectors shall take into account both theperformance characteristics of the detector and the areas into which the detec-tors are to be installed to prevent nuisance alarms or improper operation after in-stallation. Smoke detectors shall not be installed in areas where air velocity isgreater than 1.5m/sec, and shall not be located in a direct airflow. If sitting of de-tectors in such areas is unavoidable, use detectors specifically designed for usein such conditions.

    Audible Alarm-Indicating Devices: Install not less than 150 mm below the ceiling.Install bells and horns on flush-mounted back boxes with the device-operatingmechanism concealed behind a grille. Combine audible and visible alarms at thesame location into a single unit.

  • 7/30/2019 Bills of Quantity

    7/31

    Visible Alarm-Indicating Devices: Install adjacent to each alarm bell or alarmhorn and at least 150 mm below the ceiling.

    Device Location-Indicating Lights: Locate in public space near the device theymonitor.

    FACP Surface: mount with tops of cabinets not more than 1800 mm above thefinished floor.

    Annunciator: Install with the top of the panel not more than 1800 mm above thefinished floor.

    1.1.11 Wiring Installation

    Wiring Method: Install wiring in raceway according to Division 16 Section "Race-ways and Boxes." Conceal raceway except in unfinished spaces and as indicat-ed.

    Wiring within Enclosures: Separate power-limited and non-power-limited conduc-tors as recommended by the manufacturer. Install conductors parallel with or atright angles to sides and back of the enclosure. Bundle, lace, and train conduc-tors to terminal points with no excess. Connect conductors that are terminated,spliced, or interrupted in any enclosure associated with the fire alarm system toterminal blocks. Mark each terminal according to the system's wiring diagrams.Make all connections with approved crimp-on terminal spade lugs, pressure-typeterminal blocks, or plug connectors.

    Cable Taps: Use numbered terminal strips in junction, pull and outlet boxes, cab-inets, or equipment enclosures where circuit connections are made.

    Color-Coding: Color-code fire alarm conductors differently from the normal build-ing power wiring. Use one color-code for alarm circuit wiring and a different col-or-code for supervisory circuits. Color-code audible alarm-indicating circuits dif-ferently from alarm-initiating circuits. Use different colors for visible alarm-indicat-ing devices. Paint fire alarm system junction boxes and covers red.

    Risers: Install at least 2 vertical cable risers to serve the fire alarm system. Sep-arate risers in close proximity to each other with a minimum 1-hour-rated wall, sothat the loss of one riser does not prevent the receipt or transmission of signalfrom other floors or zones.

    1.1.12 Field Quality Control Verify the absence of unwanted voltages between circuit conductors and ground.

    Test all conductors for short circuits using an insulation-testing device.

    With each circuit pair, short circuit at the far end of the circuit and measure thecircuit resistance with an ohmmeter. Record the circuit resistance of each circuiton Record (As-Built) Drawings.

    Verify that the control unit is in the normal condition as detailed in the manufac-turer's operation and maintenance manual.

    Test initiating and indicating circuits for proper signal transmission under opencircuit conditions. One connection each should be opened at not less than 10

  • 7/30/2019 Bills of Quantity

    8/31

    percent of initiating and indicating devices. Observe proper signal transmissionaccording to class of wiring used.

    Test each initiating and indicating device for alarm operation and proper re-sponse at the control unit. Test smoke detectors with actual products of combus-tion.

    Test the system for all specified functions according to the approved operationand maintenance manual. Systematically initiate specified functional perfor-mance items at each station, including making all possible alarm and monitoringinitiations and using all communications options. For each item, observe relatedperformance at all devices required to be affected by the item under all systemsequences. Observe indicating lights, displays, signal tones, and annunciator in-dications. Observe all voice audio for routing, clarity, and quality, freedom fromnoise and distortion, and proper volume level.

    1.1.13 Fire AppliancesConsistent with the life safety laws provisioning for manually operated fireextinguishers has been made in accordance with the type of risks identified andevaluated for the designated areas. Rooms of spaces that are identified to haveClass A fire threat perception are provided with water extinguishers. Similarly for Electrical Fires belonging to Class B we have provisioned the Carbon DioxideExtinguishers and Foam appliances for the Class A & B types of fire.

    All the fire extinguishers are well mounted and are located at or adjacent to the exitareas in line with the life safety code.

    Water ExtinguishersPortable hand operated water fire extinguishers are usually available in 9 litrecapacity with a fire extinguishing rating of 2 A. The extinguisher weighsapproximately 14kg and has a solid stream range of approximately 10.7 - 12.2metres horizontally. This extinguisher can be used intermittently but under continuous use it has a discharge of 50-55 seconds.

    Foam ExtinguishersThese extinguishers are commonly manufactured in 9 litre rating and are intendedfor use on Class A and Class B fire(s). On flammable liquid fires of appreciabledepth, best results are obtained when the discharge from the extinguisher is playedagainst the inside of the back wall of the vat or tank just above the burning surfaceto permit the natural spread of the foam back over the burning liquid. Theextinguishing agent is a solution of aqueous film forming (AFFF) surfactant in water that forms mechanical foam when discharged through the aspirating nozzle. On

    Class A fires the agent acts as both coolant and penetration to reducetemperatures below the ignition level. On Class B fires it acts as a barrier toexclude air or oxygen from the fuel surface.

    Carbon Dioxide ExtinguishersPortable Carbon Dioxide extinguishers are designated with a discharge horn.These extinguishers require a two hand operation. The Carbon Dioxide is retainedunder its own pressure in fluid form at room temperature. The agent is self expelling and is discharged by an operation of the cylinder valve that causes theCarbon Dioxide to be expelled through a horn in its vapour and solid phase.Carbon Dioxide Extinguishers are specifically effective on Electrical Fire conditions.

  • 7/30/2019 Bills of Quantity

    9/31

    1.2 CLOSED CIRCUIT TV (CCTV)

    1.2.1 General

    This Section includes closed circuit TV system consisting of cameras and datatransmission wiring with its associated equipment to be installed in the extendedportion of Terminal Building.

    1.2.2 Quality Assurance

    Installer Qualifications: An experienced installer who is an authorizedrepresentative of the CCTV equipment manufacturer, for both installation andmaintenance of units required for this Project, to supervise installation of thesystem.

    Experience: Minimum 5 years. Demonstrate that installer has satisfactorily completed at least 2 system

    installations similar in design and extent to that indicated for this Project, andwith a record of successful in-service performance.

    Standards: system is to be in accordance to CCIR and/or EIA standards or other equal and approved standards.

    1.2.3 System Requirements

    STANDARD CAMERAS

    Indoor & outdoor, fixed & high speed drive Cameras: Assembled and tested as amanufactured unit, containing a monochrome, motorized pan and tilt, zoom lens,and receiver/driver (for the controllable cameras), Camera and zoom lens.

    Pickup Device: CCD interlines transfer, 380,000[768 (H) by 494(V)] pixels. Horizontal Resolution: 480 lines. Signal-to-Noise Ratio: Not less than 50 dB, with the camera AGC off. With AGC, manually selectable on or off. Sensitivity: Camera shall provide usable images in low-light conditions,

    delivering an image at a scene illumination to the satisfaction of end-users. Sensitivity: Camera shall deliver 1-V peak-to-peak video signal at the

    minimum specified light level. The illumination for the test shall be with lampsrated at approximately 2200-K color temperature, and with the camera AGCoff.

    Automatic and manually selectable modes for backlight compensation or normal lighting. Pan and Tilt: Direct-drive motor, 360-degree rotation angle, and 180-degree

    tilt angle. Pan-and-tilt speed shall be variable controlled by operator.Movement from preset positions shall be not less than 300 degrees per second.

    Preset positioning: 8 user-definable scenes, each allowing 16-character titles. Controls shall include the following:

    a. In "sequence mode," camera shall continuously sequence through presetpositions, with dwell time and sequencing under operator control.

    b. Up to four preset positions may be selected to be activated by an alarm.Each of the alarm positions may be programmed to output a responsesignal.

  • 7/30/2019 Bills of Quantity

    10/31

    White Balance: Auto-tracing white balance, with manually settable fixedbalance option.

    1.2.4 Lenses

    Description: Optical-quality coated optics, designed specifically for videosurveillance applications, and matched to specified camera. Provide color-corrected lenses with color cameras.

    Auto-Iris Lens: Electrically controlled iris with circuit set to maintain a constantvideo level in varying lighting conditions.

    Fixed Lenses: Vary focal. Zoom Lenses: Motorized, Remote-controlled units, rated as "quiet operating."

    Features include the following:

    a. Electrical Leads: Filtered to minimize video signal interference.b. Motor Speed: Variable.c. Lens shall be available with preset positioning capability to recall the

    position of specific scenes.

    1.2.5 Video Monitors

    Type: color (CRT 14") desktop 4/3 format, mounted for operator consoleType: color (CRT 17") desktop 4/3 format, mounted for operator console

    1.2.6 Digital Video Recorder (DVR) and Storage

    Main functions All the pictures shall be recorded and stored, continuously or on event.The operation cameras shall be recorded all the time, at 6,25 frames/secondrate. The security cameras shall be recorded on event with pre and postalarm, at 25 frames/second rate. Stopping the recording shall be done in co-ordination with Police and Airport Authorities Engineer during the implemen-tation. Recording: variable quality (CIF to 4 CIF resolutions) according to thecompression rate. It has to support up to 25 frames/second in real-time or time lapse (selectable) recording per camera, with frame rate change up ontrigger or alarm input. The compression technology shall be MPEG-1, MPEG-2, MPEG4 or WAVELET technology. It supports individual frame rate andcompression rate for each camera recorded. Video refreshment: 1 frame/s to 25 frame/s

    The system shall support a wide range of automated storage optionsranging from as little as a few hours of online storage capacity to keep long-term storage using digital tape or other cost-effective long-term storage me-dia. Capable of supporting unlimited video storage capacity by enabling sys-tem operators to periodically remove and replace tape cartridge or other re-movable storage media Record and Storage capacity ensures at least the recording for all thecameras during one month continuously. Contractor has to submit designcalculations to justify the selection of the hard disk and the capacity of thetype library size according to the needs. Recorded and storage images accessible from workstation PCs connect-ed directly to the LAN or dial-up modem connections. Advanced video net-

    working managing multiple sites and recorders over IP networks The DVRMS system shall be designed to work :

  • 7/30/2019 Bills of Quantity

    11/31

    With the Network Management System in order to send record pictures toall monitors or remote workstations on request

    With cameras that generate a standard PAL composite video signal.Recorders use BNC connectors for video inputs.

    Digital Video Recorder (DVRMS) system shall be an open architecture for

    easy system integration and additional capability to run specific software,such intelligent video content analysis (facial recognition, suspect behavior detection). Select cameras to be recorded including date & time, title, update rate(real time and/or time lapse). Video input: analog composite video (BNC socket). Each input shall havea video loop-through termination. Video Output : digital video over IP and analog output Playback and recording of cameras simultaneously Playback with high speed date/time searching, skip searching, indexsearching, alarm list searching, and multi-screen option. Flexible storage architecture (centralized, local and remote storage) for

    enabling best storage utilization Suitable backup shall be proposed for DVRMS including backup manage-ment for archiving and restoring information from the DVRMS. Playback digital zooming (option); it shall allow the operator to zoom intoa selected area of the image during playback and video authentication. Software should be programmable for any recording or playback se-quence. DVRMS system shall be capable of performing the following tasks simul-taneously:

    Digitizing and compressing video and calculating digital signaturesfor video authentication. Writing video to files on local hard disks and maintaining anaccurate index of video files stored on local disks. Deleting the older video files as needed to free up space to recordnew video files. Selectively transferring recorded video to long-term storage media

    Tasks related to alarms: Executing video image analysis algorithms (video sensor), includingactivity detection and video loss detection and generating alarmmessages. Receiving signals from alarm inputs and generating alarmmessages.

    Sending alarm messages to the server or program that managesalarm responses. Processing alarm response instructions, changing recording modesand controlling alarm relay outputs. Forwarding alarms from a remote DVRMS to a central alarmmonitoring site, including modem or LAN/WAN communication. Motion detection feature shall be provided for fixed cameras lookingat sensitive areas, in order to initiate alarm when unauthorized movementis detected. Contractor shall coordinate and check precise location

    Tasks performed in response to requests from oneor more workstations:

    Supplying one or more live video streams.

  • 7/30/2019 Bills of Quantity

    12/31

    Enabling one or more users to play back previously recordedvideo, including instant replay of video recorded within the last fewseconds.

    a. Scheduled recording administration:

    Establish a recording schedule based on hours of the day and daysof the week.

    Specify the times during which each camera will be recorded alongwith the recorder settings to be used during each period including the framerate, resolution, and quality settings.

    a. Alarm recording

    Enable the system administrator to define alarm responsesincluding instructions to trigger recording of specified cameras at specifiedframe rates and quality settings.

    Record the pre-alarm video. Enable system administrators todetermine the pre-alarm duration (at least 20 seconds).

    Record cost-effective low frame rate video during non-alarmperiods, then start recording on high frame rate real-time recorders inresponse to alarm events.

    Selectively copy video to long-term storage media; enable systemadministrators to determine whether video will be retained on long-termstorage media for each continuous or scheduled recording instruction.

    Automatically retain video on long-term storage media when video is

    recorded as part of a defined response to an alarm event. Enable authorized users to stop and start recording from withinthe GUI application software. Environmental conditions : operable between 0C to 50C tem-perature and 10-90% non-condensing humidity Includes GUI software designed to run on PCs equipped with thelatest Microsoft Windows operating system edition, GUI application soft-ware functions include system set up, administration, and monitoring,video playback, alarm monitoring.

    1.2.7 Power Supplies

    Power Supplies: Low-voltage power supplies matched for voltage and current re-quirements of cameras and accessories, type as recommended by camera andlens manufacturer.

    Enclosure: NEMA 250, Type 3 All cameras shall be powered from facility UPS 220V. All cameras are to be

    supplied from phase R.

    1.2.8 Camera-Supporting Equipment

    Minimum Load Rating: rated for load in excess of the total weight supportedtimes a minimum safety factor of two.

  • 7/30/2019 Bills of Quantity

    13/31

    1.2.9 Cabinets

    Equipment cabinets are to comprise wall mounted LIC (Local Interface Cabinet).Size shall be 600x1000mm.Standard holes are to be provided for panel mountingof control equipment and cable distribution terminal boards, which are to be easi-ly accessible for maintenance. Cabinets are to be galvanized sheet steel boxconstructed with joints welded on inside. Multi-formed mounting channels are tobe standard gauge cold rolled steel, with secondary chassis providing infinitefront-to-back adjustment. Base section is to be minimum 1.5-mm thick cold rolledsteel. Blower panels are to be installed in base section of each cabinet to providerequired filtered air at zero static pressure. Depth of unit is to allow cable accessthrough bottom and back of racks.

    Finishes: Steel cabinet is to be phosphatized and treated with one weatherproof base coat and two coats of epoxy paint or approved air-drying enamel of color tobe selected by Engineer.

    1.2.10 Signal Transmission Components

    Cable: Coaxial cable elements have 75-ohms nominal impedance.

    Video Surveillance Coaxial Cable Connectors: BNC type, 75 ohms. Of three-piece construction, consisting of a crimp-type center tit, sleeve, and main body.

    Contractor shall be responsible for ensuring the professional quality picture levelusing the proper type of coaxial cables. Submit calculations supporting this re-quirement.

    1.2.11 CCTV Installation

    Installation shall be supervised and tested by a representative of the manufac-turer of the system equipment. The work shall be performed by skilled techni-cians under the direction of experienced engineers, all of whom shall be properlyfactory trained and qualified for this work.

    Install column and wall-mount cameras with 3000-mm- minimum clear space be-low cameras and their mountings. Change type of mounting to achieve requiredclearance.

    Install power supplies and other auxiliary components at control stations, unlessotherwise indicated.

    Identify system components, wiring, cabling, and terminals according to Divi-sion 16 Section "Basic Electrical Materials and Methods." Color-code conductors,and apply wire and cable marking tape to designate wires and cables so mediaare identified and in coordination with system wiring diagrams.

    1.2.12 Identification

    Label all components of the system: cameras, wires, etc. Coordinate with DCA.

    1.2.13 Field Quality Control

    Inspection: Verify that units and controls are properly installed, connected, andlabeled, and that interconnecting wires and terminals are identified.

  • 7/30/2019 Bills of Quantity

    14/31

    Pretesting: Align and adjust system and pretest components, wiring, and func-tions to verify that they comply with specified requirements. Conduct tests atvarying lighting levels, including day and night scenes as applicable. Preparevideo surveillance equipment for acceptance and operational testing as follows:

    Prepare equipment list described in Part 1 "Submittals" Article. Verify operation of auto-iris lenses. Set back-focus of fixed focal length lenses. At focus set to infinity, simulate

    nighttime lighting conditions by using a dark glass filter of a density that pro-duces a clear image. Adjust until image is in focus with and without the filter.

    Set back-focus of zoom lenses. At focus set to infinity, simulate nighttimelighting conditions by using a dark glass filter of a density that produces aclear image. Additionally, set zoom to full wide angle and aim camera at anobject 17 to 23 m away. Adjust until image is in focus from full wide angle tofull telephoto, with the filter in place.

    Set and name all preset positions; consult Owner's personnel. Verify operation of control-station equipment.

    Operational Tests: Perform operational system tests to verify that system com-plies with Specifications. Include all modes of system operation. Test equipmentfor proper operation in all functional modes.

    1.3 DUCT ACCESSORIES

    1.3.1 Summary

    This Section includes the following:

    Backdraft dampers. Manual-volume dampers. Fire dampers. Duct silencers. Turning vanes. Duct-mounted access doors and panels. Flexible ducts. Flexible connectors. Duct accessory hardware.

    1.3.2 Quality Assurance

    NFPA Compliance: Comply with the following NFPA standards:

    NFPA 90A, "Installation of Air Conditioning and Ventilating Systems."

    NFPA 90B, "Installation of Warm Air Heating and Air Conditioning Systems."

    1.3.3 Sheet Metal Materials

    forming quality; ASTM A 653/A 653M, Z275 coating designation; mill-phospha-tized finish for surfaces of ducts exposed to view.

    Carbon-Steel Sheets: ASTM A 366/A 366M, cold-rolled sheets, commercial qual-

    ity, with oiled, exposed matte finish.

  • 7/30/2019 Bills of Quantity

    15/31

    Aluminum Sheets: ASTM B 209M , Alloy 3003, Temper H14, sheet form; withstandard, one-side bright finish for ducts exposed to view and mill finish for con-cealed ducts.

    Extruded Aluminum: ASTM B 221M , Alloy 6063, Temper T6.

    Reinforcement Shapes and Plates: Galvanized steel reinforcement where in-stalled on galvanized, sheet metal ducts; compatible materials for aluminum andstainless-steel ducts.

    Tie Rods: Galvanized steel, 8 mm minimum diameter for 900 mm length or less;10 mm minimum diameter for lengths longer than 900 mm .

    1.3.4 Backdraft Dampers

    Description: Suitable for horizontal or vertical installations. Dampers shall notproduce noise while in operation.

    Frame: 1.3 mm thick, galvanized, sheet steel, with welded corners and mount-ing flange.

    Blades: 1.2 mm thick aluminum sheet.

    Blade Seals: Neoprene.

    Blade Axles: Galvanized steel.

    Tie Bars and Brackets: Galvanized steel.

    Return Spring: Adjustable tension.

    1.3.5 Manual-Volume Dampers

    General: Factory fabricated with required hardware and accessories. Stiffendamper blades for stability. Include locking device to hold single-blade dampersin a fixed position without vibration. Close duct penetrations for damper compo-nents to seal duct consistent with pressure class.

    Pressure Classifications of 500 Pa or Higher: End bearings or other seals for ducts with axles full length of damper blades and bearings at both ends of op-erating shaft.

    Low-Leakage Volume Dampers: Multiple- or single-blade, parallel- or opposed-blade design as indicated, low-leakage rating, with linkage outside air stream,and suitable for horizontal or vertical applications.

    Steel Frames: Hat-shaped, galvanized, sheet steel channels, minimum of 1.6mm thick, with mitered and welded corners; frames with flanges where indi-cated for attaching to walls; and flangeless frames where indicated for in-stalling in ducts.

    Aluminum Frames to be installed where aluminum ducts are installed: Hat-shaped, 1.6 mm thick, extruded-aluminum channels; frames with flanges

    where indicated for attaching to walls; and flangeless frames where indicatedfor installing in ducts.

  • 7/30/2019 Bills of Quantity

    16/31

    Roll-Formed Steel Blades: 1.6 mm thick, galvanized, sheet steel. Roll-Formed Aluminum Blades: 2.5 mm thick aluminum sheet. Blade Axles: Galvanized steel. Tie Bars and Brackets: Aluminum where aluminum ducts are installed. Tie Bars and Brackets: Galvanized steel.

    Jackshaft: 25 mm diameter, galvanized steel pipe rotating within a pipe-bearingassembly mounted on supports at each mullion and at each end of multiple-damper assemblies.

    Length and Number of Mountings: Appropriate to connect linkage of eachdamper of a multiple-damper assembly.

    Damper Hardware: Zinc-plated, die-cast core with dial and handle made of 2.4mm thick zinc-plated steel, and a 19 mm hexagon locking nut. Include center hole to suit damper operating-rod size. Include elevated platform for insulatedduct mounting.

    1.3.6 Motorized Volume Dampers

    Dampers: AMCA-rated, opposed-blade design; 2.8 -mm minimum, galvanized-steel frames with holes for duct mounting; damper blades shall not be less than1.6 -mm galvanized steel with maximum blade width of 200 mm , and with edgeseals.

    Blades shall be secured to 13 -mm diameter, zinc-plated axles using zinc-plated hardware, with nylon blade bearings, blade-linkage hardware of zinc-plated steel and brass, ends sealed against spring-stainless-steel blade bear-ings, and thrust bearings at each end of every blade.

    Operating Temperature Range: From minus 40 to plus 93 deg. C . For standard applications, include optional closed-cell neoprene edging. For low-leakage applications, use parallel- or opposed-blade design with in-

    flatable seal blade edging, or replaceable rubber seals, rated for leakage atless than 51 L/s per sq. m of damper area, at differential pressure of 995 Pawhen damper is being held by torque of 5.6 N x m ; when tested according to

    AMCA 500D

    1.3.7 Fire Dampers

    General: Labeled to UL 555.

    Fire Rating: One and one-half and three hours.

    Frame: SMACNA Type B with blades out of air stream; fabricated with roll-formed, 0.85 mm thick galvanized steel; with mitered and interlocking corners.

    Mounting Sleeve: Factory- or field-installed galvanized, sheet steel.

    Minimum Thickness: 1.3 mm or 3.5 mm thick as indicated, and length to suitapplication.

    Exceptions: Omit sleeve where damper frame width permits direct attach-ment of perimeter mounting angles on each side of wall or floor, and thick-

    ness of damper frame complies with sleeve requirements.

  • 7/30/2019 Bills of Quantity

    17/31

    Mounting Orientation: Vertical or horizontal as indicated.

    Blades: Roll-formed, interlocking, 0.85 mm thick, galvanized, sheet steel. Inplace of interlocking blades, use full-length, 0.85 mm thick, galvanized steel bladeconnectors.

    Horizontal Dampers: Include a blade lock and stainless-steel negator closurespring.

    Fusible Link: Replaceable, 74deg. C rated.

    1.3.8 Duct Silencers

    General: Factory-fabricated and -tested, round or rectangular silencer with per-formance characteristics and physical requirements as indicated.

    Fire Performance: Adhesives, sealers, packing materials, and accessory materi-

    als shall have fire ratings not exceeding 25 for flame spread and 50 for smokedeveloped when tested according to ASTM E 84.

    Rectangular Units: Fabricate casings with a minimum of 0.85 mm thick, solidsheet metal for outer casing and 0.55 mm thick, perforated sheet metal for inner casing.

    Sheet Metal Perforations: 3 mm diameter for inner casing and baffle sheet metal.

    Fibrous Acoustic-Fill Material: Inert and vermin-proof fibrous material, packedunder not less than 5 percent compression.

    Fabricate silencers to form rigid units that will not pulsate, vibrate, rattle, or other-wise react to system pressure variations.

    Do not use nuts, bolts, and sheet metal screws for unit assemblies. Lock form and seal or continuously weld joints. Suspended Units: Factory-installed suspension hooks or lugs attached to

    frame in quantities and spaced to prevent deflection or distortion. Reinforcement: Cross or trapeze angles for rigid suspension.

    Source Quality Control: Perform the following factory tests:

    Acoustic Performance: Test according to ASTM E 477, with airflow in both di-rections through silencer.

    Record acoustic ratings, including dynamic insertion loss and self-noise pow-er levels, for both forward flow (air and noise in same direction) and reverseflow (air and noise in opposite directions) with an airflow of at least 10-m/sface velocity.

    Leak Test: Test units for airtightness at 200 percent of associated fan staticpressure or 1500-Pa static pressure, whichever is greater.

    1.3.9 Turning Vanes

    Fabricate to comply with SMACNA's "HVAC Duct Construction Standards--Metal

    and Flexible."

  • 7/30/2019 Bills of Quantity

    18/31

    Manufactured Turning Vanes: Fabricate of 38 mm wide, curved blades set 19mm o.c.; support with bars perpendicular to blades set 50 mm o.c.; and set intoside strips suitable for mounting in ducts.

    Acoustic Turning Vanes: Fabricate of airfoil-shaped aluminum extrusions with

    perforated faces and fibrous-glass fill.1.3.10 Duct-Mounted Access Doors and Panels

    Door shall be rigid and airtight with neoprene gaskets and two or more chrome-plated enamel painted steel hinges and quick fastening locking devices. Providedoors as large as practical. Include vision panel where indicated. Include 25-by-25 mm butt or piano hinge and cam latches. Access doors up to 300 X 300 mmshall have two cam locks, larger sizes shall have four cam locks.

    Mount doors, if possible, so that air pressure holds them closed. As an alterna-tive, removable access doors may be used.

    Access doors shall be constructed from stamped sheet metal and consist of aninner and outer door panel. Where insulated doors are needed, the inner door shall consist of two panels spot-welded together which totally encapsulate insula-tion identical to corresponded ductwork insulation. The inner and outer doorsshall be joined by bolts and threaded handles in such a configuration that thepanels can be drawn together to secure the door to the duct in a sandwich fash-ion.

    The handles shall be high impact plastic with threaded metal inserts. Conicalsprings shall be used between the door panels to facilitate installation and re-moval of the door. Fireproof neoprene gasket shall be used around the outsideedge of the inner or outer panel, but not both, to seal the door.

    This type of door is approved for use on rectangular, round and flat-oval duct-work.

    1.3.11 Flexible Connectors

    General: Flame-retarded or noncombustible fabrics, coatings, and adhesivescomplying with UL 181, Class 1.

    Standard Metal-Edged Connectors: Factory fabricated with a strip of fabric 89mm wide attached to two strips of 70 mm wide, 0.7 mm thick, galvanized, sheet

    steel or 0.8 mm aluminum sheets. Select metal compatible with connected ducts. Extra-Wide Metal-Edged Connectors for use with extra heavy equipment and

    large ducts: Factory fabricated with a strip of fabric 146 mm wide attached to twostrips of 70 mm wide, 0.7 mm thick, galvanized, sheet steel or 0.8 mm aluminumsheets. Select metal compatible with connected ducts.

    Transverse Metal-Edged Connectors suitable for use with flanged connections:Factory fabricated with a strip of fabric 89 mm wide attached to two strips of 111mm wide, 0.7 mm thick, galvanized, sheet steel or 0.8 mm aluminum sheets. Se-lect metal compatible with connected ducts.

    Conventional, Indoor System Flexible Connector Fabric: Glass fabric doublecoated with polychloroprene.

  • 7/30/2019 Bills of Quantity

    19/31

  • 7/30/2019 Bills of Quantity

    20/31

    1.3.14 Installation

    Install duct accessories according to applicable details shown in SMACNA's"HVAC Duct Construction Standards--Metal and Flexible" for metal ducts andNAIMA's "Fibrous Glass Duct Construction Standards" for fibrous-glass ducts.

    Install volume dampers in lined duct; avoid damage to and erosion of duct liner.

    Provide test holes at fan inlet and outlet and elsewhere as indicated.

    Install fire and smoke dampers according to manufacturer's UL-approved writteninstructions.

    Install fusible links in fire dampers.

    Install duct access panels for access to both sides of duct coils. Install duct ac-cess panels downstream from volume dampers, fire dampers, turning vanes, and

    equipment. Install duct access panels to allow access to interior of ducts for cleaning, in-

    specting, adjusting, and maintaining accessories and terminal units. Install access panels on side of duct where adequate clearance is available. Label access doors according to Division 15 Section "Mechanical Identifica-

    tion."

    1.3.15 Adjusting

    Adjust duct accessories for proper settings.

    Adjust fire and smoke dampers for proper action.

    Final positioning of manual-volume dampers is specified in Division 15 Section"Testing, Adjusting, and Balancing."

    1.4 DUCT INSULATION OR DUCT INSTALLATION

    1.4.1 Summary

    This Section includes semirigid and flexible duct, plenum, and breeching insula-tion; insulating cements; field-applied jackets; accessories and attachments;

    and sealing compounds.

    1.4.2 Quality Assurance

    Installer Qualifications: Skilled mechanics who have completed successfully acraft training program certified by an agency acceptable to the Engineer.

    Fire-Test-Response Characteristics: As determined by testing materials identicalto those specified in this Section according to ASTM E 84, UL-723, NFPA 225 or

    ANSI A.2.5, by a testing and inspecting agency acceptable to the Engineer. Fac-tory label insulation and jacket materials and sealer and cement material contain-ers with appropriate markings of applicable testing and inspecting agency.

  • 7/30/2019 Bills of Quantity

    21/31

    Insulation Installed Indoors: Flame-spread rating of 25 or less, and smoke-developed rating of 50 or less.

    Insulation Installed Outdoors: Flame-spread rating of 75 or less, and smoke-developed rating of 150 or less.

    Mockups: Before installing insulation, build mockups for each type of insulationand finish listed below to demonstrate quality of insulation application and finish-es. Build mockups according to the following requirements, using materials indi-cated for the completed Work:

    Include the following mockups:

    a. One (1) 3 m section of rectangular straight duct.b. One (1) 90 degree square elbow and one 90 degree radius elbow.c. One (1) branch takeoff.d. One (1) transition fitting.e. Four (4 )support hangers.

    Build mockups with cutaway sections to allow observation of application de-tails for insulation materials, mastics, attachments, and jackets.

    Build mockups in the location indicated or, if not indicated, as directed by theEngineer.

    Notify the Engineer 7 days in advance of dates and times when mockups willbe constructed.

    Obtain the Engineer's approval of mockups before starting insulation applica-tion.

    Maintain mockups during construction in an undisturbed condition as a stan-dard for judging the completed Work.

    Demolish and remove mockups when directed. Approved mockups may become part of the completed Work if undisturbed at

    time of Substantial Completion.

    1.4.3 Insulation Materials

    Insulation conductance shall be maximum values, as tested at any point, not anaverage. Insulation conductance found by test to exceed the stipulated maxi-mum shall either be replaced or augmented by an additional thickness to bring itto the required maximum conductance.

    Mineral-Fiber Board Thermal Insulation: Glass fibers bonded with a thermosetting

    resin. Comply with ASTM C 612, Type IB, without facing and with all-service jacket manufactured from kraft paper, reinforcing scrim, aluminum foil and vinylfilm.

    Thermal Conductivity: 0.038W/mK at 20 deg. C (68 deg. F). Density : 48kg/m 3.

    Mineral-Fiber Blanket Thermal Insulation: Glass fibers bonded with a thermoset-ting resin. Comply with ASTM C 553, Type II, without facing and with all-service

    jacket manufactured from kraft paper, reinforcing scrim, aluminum foil, and vinylfilm.

    Thermal Conductivity: 0.038W/mK at 20 deg. C (68 deg. F). Density : 24kg/m 3.

  • 7/30/2019 Bills of Quantity

    22/31

    Density : 24kg/m 3. Calcium Silicate Insulation: Flat-, curved-, and grooved-blocksections of noncombustible, inorganic, hydrous calcium silicate with a non-as-bestos fibrous reinforcement. Comply with ASTM C 533, Type I.

    1.4.4 Field-Applied Jackets

    General: ASTM C 921, Type 1, maximum moisture vapor transmission 0.02perms, (measured before factory application or installation), minimum punctureresistance 50 Beach units on all surfaces. Minimum tensile strength, 6.1 N/mmwidth. Jackets used on insulation exposed in finished areas shall have white fin-ish suitable for painting without sizing.

    Aluminum Jacket: Aluminum jackets shall be corrugated, embossed or smoothsheet, ASTM B 209M, and having an integrally bonded moisture barrier over en-tire surface in contact with insulation. Corrugated aluminum jacket shall not beused outdoors.

    Finish and Thickness: Stucco embossed finish, 0.6 mm thick for indoor in-stallation and 0.8 mm for outdoor installation unless otherwise noted.

    1.4.5 Accessories and Attachments

    Materials shall be compatible and shall not contribute to corrosion, soften, or oth-erwise attack surfaces to which they are applied in either the wet or dry state.Materials to be used on stainless-steel surfaces shall meet ASTM C 795 require-ments. Materials shall be asbestos free and conform to the following.

    Glass Cloth and Tape: Comply with MIL-C-20079H, Type I for cloth and Type IIfor tape. Woven glass-fiber fabrics, plain weave, presized a minimum of 270g/sq. m .

    Tape Width: 100 mm .

    Bands: 19 mm wide, in one of the following materials compatible with jacket:

    Stainless-Steel: ASTM A 666, Type 304; 0.5 mm thick. Galvanized Steel: 0.13 mm thick. Aluminum: 0.18 mm thick. Brass: 0.25 mm thick.

    Nickel-Copper Alloy: 0.13 mm thick. Wire: 2.0 mm , nickel-copper alloy; 1.6 mm , soft-annealed, stainless steel; or 1.6

    mm , soft-annealed, galvanized steel.

    Adhesive-Attached Anchor Pins and Speed Washers: Galvanized steel plate,pin, and washer manufactured for attachment to duct and plenum with adhesive.Pin length sufficient for insulation thickness indicated.

    Adhesive: Recommended by the anchor pin manufacturer as appropriate for surface temperatures of ducts, plenums, and breechings; and to achieve aholding capacity of 45 kg for direct pull perpendicular to the adhered surface.

    Adhesives:

  • 7/30/2019 Bills of Quantity

    23/31

    Cloth: Adhesives for adhering, sizing, and finishing open-weave glass clothshall be pigmented polyvinyl acetate emulsion and shall conform to the re-quirements of ASTM C 916, Type I.

    Cellular Elastomer: Adhesive for cellular elastomer insulation shall be a sol-vent cutback chloroprene elastomer conforming to ASTM C 916, Type I, andshall be a type approved by the manufacturer of the cellular elastomer for theintended use.

    Coatings:

    Outdoor and Indoor Non-Vapor-Barrier Finishing: Coatings for outdoor and in-door non-vapor-barrier finishing of insulation surfaces shall be pigmentedpolymer emulsion recommended by the insulation-material manufacturer for the surface to be coated and shall be applied to the specified dry-film thick-ness.

    Cellular Elastomer Insulation: Finish coating for cellular elastomer insulationshall be a polyvinylchloride lacquer approved by the manufacturer of the cel-lular elastomer for the intended use.

    Coating Color: Coating color shall conform to color code specified or as di-rected by the Engineer.

    1.4.6 Examination

    Examine substrates and conditions for compliance with requirements for installa-tion and other conditions affecting performance of insulation application.

    Proceed with installation only after unsatisfactory conditions have been corrected.

    1.4.7 Preparation

    Surface Preparation: Clean and dry surfaces to receive insulation. Removematerials that will adversely affect insulation application.

    1.4.8 General Application Requirements

    Apply insulation materials, accessories, and finishes according to the manufac-turer's written instructions; with smooth, straight, and even surfaces; and free of voids throughout the length of ducts and fittings.

    Refer to schedules at the end of this Section for materials, forms, jackets, andthicknesses required for each duct system.

    Use accessories compatible with insulation materials and suitable for the service.Use accessories that do not corrode, soften, or otherwise attack insulation or

    jacket in either wet or dry state.

    Apply multiple layers of insulation with longitudinal and end seams staggered.

    Seal joints and seams with vapor-retarder mastic on insulation indicated to re-ceive a vapor retarder.

    Keep insulation materials dry during application and finishing.

    Apply insulation with tight longitudinal seams and end joints. Bond seams and joints with adhesive recommended by the insulation material manufacturer.

  • 7/30/2019 Bills of Quantity

    24/31

    Apply insulation with the least number of joints practical.

    Apply insulation over fittings and specialties, with continuous thermal and vapor-retarder integrity, unless otherwise indicated.

    Hangers and Anchors: Where vapor retarder is indicated, seal penetrations in in-sulation at hangers, supports, anchors, and other projections with vapor-retarder mastic. Apply insulation continuously through hangers and around anchor at-tachments.

    Insulation Terminations: For insulation application where vapor retarders are in-dicated, seal ends with a compound recommended by the insulation materialmanufacturer to maintain vapor retarder.

    Apply insulation with integral jackets as follows:

    Pull jacket tight and smooth. Joints and Seams: Cover with tape and vapor retarder as recommended by

    insulation material manufacturer to maintain vapor seal. Vapor-Retarder Mastics: Where vapor retarders are indicated, apply mastic

    on seams and joints and at ends adjacent to duct flanges and fittings.

    Cut insulation according to manufacturer's written instructions to prevent com-pressing insulation to less than 75 percent of its nominal thickness.

    Install vapor-retarder mastic on ducts and plenums scheduled to receive vapor retarders.

    Ducts with Vapor Retarders: Overlap insulation facing at seams and seal withvapor-retarder mastic and pressure-sensitive tape having same facing as insu-lation. Repair punctures, tears, and penetrations with tape or mastic to main-tain vapor-retarder seal.

    Ducts without Vapor Retarders: Overlap insulation facing at seams and se-cure with outward clinching staples and pressure-sensitive tape having samefacing as insulation.

    Roof Penetrations: Apply insulation for interior applications to a point even withtop of roof flashing.

    Seal penetrations with vapor-retarder mastic.

    Apply insulation for exterior applications tightly joined to interior insulationends. Seal insulation to roof flashing with vapor-retarder mastic.

    Interior Wall and Partition Penetrations: Apply insulation continuously throughwalls and partitions, except fire-rated walls and partitions.

    Fire-Rated Wall and Partition Penetrations: Terminate insulation at fire/smokedamper sleeves for fire-rated wall and partition penetrations.

    Floor Penetrations: Terminate insulation at underside of floor assembly and atfloor support at top of floor.

  • 7/30/2019 Bills of Quantity

    25/31

    For insulation indicated to have vapor retarders, taper termination and seal in-sulation ends with vapor-retarder mastic.

    1.4.9 Mineral-Fiber Insulation Application

    Blanket Applications for Ducts and Plenums: Secure blanket insulation with ad-hesive and anchor pins and speed washers.

    Apply adhesives according to manufacturer's recommended coverage ratesper square foot, for 100 percent coverage of duct and plenum surfaces.

    Apply adhesive to entire circumference of ducts and to all surfaces of fittingsand transitions.

    Install anchor pins and speed washers on sides and bottom of horizontalducts and sides of vertical ducts as follows:

    a. On duct sides with dimensions 450 mm and smaller, along longitudinalcenterline of duct. Space 75 mm maximum from insulation end joints,

    and 400 mm o.c. b. On duct sides with dimensions larger than 450 mm . Space 400 mm o.c.each way, and 75 mm maximum from insulation joints. Apply additionalpins and clips to hold insulation tightly against surface at cross bracing.

    c. Anchor pins may be omitted from top surface of horizontal, rectangular ducts, and plenums.

    d. Do not overcompress insulation during installation.

    Impale insulation over anchors and attach speed washers. Cut excess portion of pins extending beyond speed washers or bend parallel

    with insulation surface. Cover exposed pins and washers with tape matchinginsulation facing.

    Create a facing lap for longitudinal seams and end joints with insulation by re-moving 50 mm from one edge and one end of insulation segment. Securelaps to adjacent insulation segment with 13 mm staples, 25 mm o.c., and cov-er with pressure-sensitive tape having same facing as insulation.

    Overlap unfaced blankets a minimum of 50 mm on longitudinal seams andend joints. Secure with steel band at end joints and spaced a maximum of 450 mm o.c.

    Apply insulation on rectangular duct elbows and transitions with a full insula -tion segment for each surface. Apply insulation on round and flat-oval ductelbows with individually mitered gores cut to fit the elbow.

    Insulate duct stiffeners, hangers, and flanges that protrude beyond the insula-tion surface with 150 mm wide strips of the same material used to insulateduct. Secure on alternating sides of stiffener, hanger, and flange with anchor pins spaced 150 mm o.c.

    Board Applications for Ducts and Plenums: Secure board insulation with adhe-sive and anchor pins and speed washers.

    Apply adhesives according to manufacturer's recommended coverage ratesfor 100 percent coverage of duct and plenum surfaces.

    Apply adhesive to entire circumference of ducts and to all surfaces of fittingsand transitions.

    Space anchor pins as follows:

  • 7/30/2019 Bills of Quantity

    26/31

    a. On duct sides with dimensions 450 mm and smaller, along longitudinalcenterline of duct. Space 75 mm maximum from insulation end joints,and 400 mm o.c.

    b. On duct sides with dimensions larger than 450 mm . Space 400 mm o.c.each way, and 75 mm maximum from insulation joints. Apply additionalpins and clips to hold insulation tightly against surface at cross bracing.

    c. Anchor pins may be omitted from top surface of horizontal, rectangular ducts, and plenums.

    d. Do not over compress insulation during installation.

    Cut excess portion of pins extending beyond speed washers or bend parallelwith insulation surface. Cover exposed pins and washers with tape matchinginsulation facing.

    Create a facing lap for longitudinal seams and end joints with insulation by re-moving 50 mm from one edge and one end of insulation segment. Securelaps to adjacent insulation segment with 13 mm staples, 25 mm o.c., and cov-er with pressure-sensitive tape having same facing as insulation.

    Provide solid inserts to ductwork insulation where supported by bracket. Cre-ate overlap of vapour barrier through brackets. Apply insulation on rectangular duct elbows and transitions with a full insula -

    tion segment for each surface. Groove and score insulation to fit as closelyas possible to outside and inside radius of elbows. Apply insulation on roundand flat-oval duct elbows with individually mitered gores cut to fit the elbow.

    Insulate duct stiffeners, hangers, and flanges that protrude beyond the insula-tion surface with 150 mm wide strips of the same material used to insulateduct. Secure on alternating sides of stiffener, hanger, and flange with anchor pins spaced 150 mm o.c.

    1.4.10 Finishes

    Flexible Elastomeric Thermal Insulation: After adhesive has fully cured, applytwo coats of insulation manufacturer's recommended protective coating.

    Color: Final color as selected by the Engineer. Vary first and second coats to al-low visual inspection of the completed Work.

    1.4.11 Indoor Duct and Plenum Application Schedule

    Service: Supply-air ducts in concealed spaces and exposed to view in air-condi-tioned area.

    Material: Mineral-fiber blanket. Thickness: 50 mm applied to 25 mm final compressed thickness. Number of Layers: One. Field-Applied Jacket: Aluminum jacket for all areas and stainless steel

    where exposed in the front-of-house and finished areas Vapor Retarder Required: Yes.

    Service: Return-air ducts in concealed spaces and exposed to view in air-condi-tioned area.

    Material: Mineral-fiber blanket.

    Thickness: 5 0 mm applied to 25 mm final compressed thickness Number of Layers: One.

  • 7/30/2019 Bills of Quantity

    27/31

  • 7/30/2019 Bills of Quantity

    28/31

    1.5 SPLIT SYSTEM AIR-CONDITIONING UNITS

    1.5.1 SummaryThis Section includes split-system air-conditioning units consisting of separateevaporator-fan and compressor-condenser components. Units are designed for exposed

    or concealed mounting, and may be connected to ducts.1.5.2 Quality Assurance

    Product Options: Drawings indicate size, profiles, and dimensional requirementsof split-system units and are based on the specific system indicated. Other man-ufacturers' systems with equal performance characteristics may be considered.

    Electrical Components, Devices, and Accessories: Listed and labeled as definedin NFPA 70, Article 100.

    Paint finish shall be suitable for hot and humid climates. Unit shall be capable

    and suitable of working at outdoor ambient temperature of 50 deg. C. Sound-power-level, decibels reference, 10 to the minus 12 power watt, at the fan

    operating speed selected to meet the specified capacity. Sound level shall not ex-ceed 40dBa at low speed and 48dBa at high speed.

    Sound-power-level data or values for these units shall be obtained in accordancewith the test procedures specified in ANSI S12.23. Sound-power values apply tounits provided with factory-fabricated cabinet enclosures and standard grilles.Values obtained for the standard cabinet models will be acceptable for concealedmodels without separate tests provided there is no variation between models asto the coil configuration, blowers, motor speeds, or relative arrangement of parts.

    Each unit shall be fastened securely to the building structure.1.5.3 Concealed Evaporator-Fan Components

    Chassis: Galvanized steel with flanged edges, removable panels for servicing,and insulation on back of panel.

    Insulation: Faced, glass-fiber duct liner. Drain Pans: Stainless steel, with connection for drain; insulated with poly-

    styrene.

    Refrigerant Coil: Copper tube, with mechanically bonded aluminum fins, comply-

    ing with ARI 210/240, and with thermal-expansion valve. Fan: Forward-curved, double-width wheel of galvanized steel; directly connected

    to motor.

    Fan Motor: Multispeed, PSC type.

    Filters: 25 mm thick, permanent, washable, cleanable type in aluminum frames.

    Wiring Terminations: Connect motor to chassis wiring with plug connection.

  • 7/30/2019 Bills of Quantity

    29/31

    1.5.4 Wall or Ceiling Mounted, Evaporator Fan Components

    Cabinet: Enameled steel with removable panels on front and ends, and dis-charge drain pans with drain connection.

    Refrigerant Coil: Copper tube, with mechanically bonded aluminum fins, comply-ing with ARI 210/240, and with thermal-expansion valve.

    Fan and Motor: Centrifugal fan, directly driven by multispeed, electric motor withintegral overload protection; resiliently mounted.

    Filters: 25 mm thick, permanent, washable, cleanable type in aluminum frames.

    1.5.5 Air-Cooled, Compressor-Condenser Components

    Casing: Steel, finished with baked enamel, with removable panels for access tocontrols, weep holes for water drainage, and mounting holes in base. Providebrass service valves, fittings, and gage ports on exterior of casing.

    Compressor: Hermetically sealed with crankcase heater and mounted on vibra-tion isolation. Compressor motor shall have thermal- and current-sensitive over-load devices, start capacitor, relay, and contactor.

    Compressor Type: Reciprocating or Scroll. Two-speed compressor motor with manual-reset high-pressure switch and

    automatic-reset low-pressure switch.

    Refrigerant Coil: Copper tube, with mechanically bonded aluminum fins, comply-ing with ARI 210/240, and with liquid subcooler.

    Fan: Aluminum-propeller type, directly connected to motor.

    Motor: Permanently lubricated, with integral thermal-overload protection.

    Mounting Base: Polyethylene.

    1.5.6 Accessories

    Thermostat: DDC wall type. Refer to specification section 15900, clause 2.5A

    Automatic-reset timer to prevent rapid cycling of compressor.

    Refrigerant Line Kits: Soft-annealed copper suction and liquid lines factorycleaned, dried, pressurized, and sealed; factory-insulated suction line with flaredfittings at both ends.

    1.5.7 Execution: Installation

    Install units level and plumb.

    Install evaporator-fan components using manufacturer's standard mounting de-vices securely fastened to building structure.

    Install ground-mounted, compressor-condenser components on minimum 100mm thick, reinforced concrete base; 100 mm larger on each side than unit. Con-

  • 7/30/2019 Bills of Quantity

    30/31

    crete, reinforcement, and formwork are specified in Division 3, "Cast-in-PlaceConcrete." Coordinate anchor installation with concrete base.

    Install compressor-condenser components on restrained, spring isolators with aminimum static deflection of 25 mm .

    Connect precharged refrigerant tubing to component's quick-connect fittings. In-stall tubing to allow access to unit.

    1.5.8 Connections

    Piping installation requirements are specified in other Sections. Drawings indi-cate general arrangement of piping, fittings, and specialties.

    Install piping adjacent to unit to allow service and maintenance.

    Unless otherwise indicated, connect piping with unions and shutoff valves to al-

    low units to be disconnected without draining piping. Refer to piping system Sec-tions for specific valve and specialty arrangements.

    Ground equipment.

    Tighten electrical connectors and terminals according to manufacturer's pub-lished torque-tightening values. If manufacturer's torque values are not indicated,use those specified in UL 486A and UL 486B.

    1.5.9 Inspection and Testing

    Installation Inspection: Engage a factory-authorized service representative to in-

    spect field-assembled components and equipment installation, including pipingand electrical connections, and to prepare a written report of inspection.

    Leak Test: After installation, charge system and test for leaks. Repair leaks andretest until no leaks exist.

    Operational Test: After electrical circuitry has been energized, start units to con-firm proper motor rotation and unit operation. Remove malfunctioning units, re-place with new components, and retest.

    Test and adjust controls and safeties. Replace damaged and malfunctioningcontrols and equipment.

    1.6 BAGGAGE HANDLING UNIT

    1.6.1 Flat Belt Conveyor

    1. Width (Over all) 41 nominal

    2.Width of Conveying Surface 35 nominal

    3. Pallet Construction Hot Rolled Steel

    4. Pallet Finish Black Paint

    5. Load Capacity 250 Lbs/ linear foot

    6. Height 24

  • 7/30/2019 Bills of Quantity

    31/31

    7. Conveying Speed 90 FPM

    8. Drive Dual Roller Chain

    9. Pallet Support Urethane Bearing Wheels

    10. Frame Trim Hot rolled steel , Painted

    11. Frame Work Structural Steel Shapes


Recommended