+ All Categories
Home > Documents > Bomba de Refrigerante036-043_jekel

Bomba de Refrigerante036-043_jekel

Date post: 05-Apr-2018
Category:
Upload: epaese
View: 221 times
Download: 0 times
Share this document with a friend

of 8

Transcript
  • 8/2/2019 Bomba de Refrigerante036-043_jekel

    1/8

    3 6 A S HR A E J o u r n a l a s h r a e . o r g A u g u s t 2 0 1 1

    Early practitioners of industrial refrigeration systems found they

    could increase the capacity of evaporators by supplying excess

    liquid refrigerant to the unit (overfeeding). In evaporators congured

    to operate with overfeed, the quantity of liquid refrigerant supplied is

    greater than the minimum amount required to meet the cooling loads

    as it undergoes the phase change from liquid to vapor. In this case, a

    mixture of low temperature liquid and vapor leaves the evaporator

    and returns to a vessel designed to separate the liquid from the vapor

    prior to the vapor being recompressed.

    Within limits, the cooling capacity o

    an overed evaporator increases due to

    the tendency or more o the evapora-

    tors interior suraces being wetted with

    saturated liquid rerigerant.1,2 Figure 1

    shows a simple liquid overed system

    typical o those designed and used today

    or large built-up industrial rerigeration

    systems.

    In a mechanically pumped overeed

    system, a centriugal pump draws low

    temperature saturated liquid rerig-

    erant rom a vessel reerred to as a

    pumped recirculator, pumped ac-

    cumulator, recirculator, or low-

    pressure receiver and raises the pres-

    sure o the liquid or delivery to one

    or more evaporators having a common

    rerigerant temperature requirement.

    Once pressurized by the pump, the

    saturated liquid becomes subcooled

    as it leaves the pump discharge and

    enters the recirculated liquid supply

    line. As individual evaporators call

    or cooling, local controls simply open

    a liquid eed solenoid valve, which al-lows low temperature pressurized liq-

    uid rom the liquid supply line to ow

    into the evaporator. Manually adjust-

    able hand-expansion (i.e., metering)

    valves are used at each evaporator as

    a means o balancing the supply o

    About the Authors

    Todd B. Jekel, Ph.D., P.E., is assistant director and

    Douglas T. Reindl, Ph.D., P.E., is director of the

    Industrial Refrigeration Consortium and professor

    at the University of Wisconsin, Madison, Wis.

    By Todd B. Jekel, Ph.D., P.E., Member ASHRAE, and Douglas T. Reindl, Ph.D., P.E., Fellow ASHRAE

    Liquid Refrigerant PumpingIn Industrial Refrigeration Systems

    TECHNICAL FEATUREThis article was published in ASHRAE Journal, August 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission of ASHRAE. For more informationabout ASHRAE Journal, visit www.ashrae.org.

  • 8/2/2019 Bomba de Refrigerante036-043_jekel

    2/8

    A u g us t 2 0 1 1 A SHR A E J our n a l 3 7

    liquid ow to individual evapo-

    rators throughout the system.

    The hand-expansion valves are

    adjusted to achieve appropriate

    liquid overeed rates as-required

    or given evaporator designs.Leaving each unit will be a mix-

    ture o saturated vapor produced

    by absorbing heat rom the rerig-

    eration loads and saturated liquid

    that was overed. The two-phase

    mixture is carried back to the same

    pumped recirculator vessel through

    the recirculated liquid return or

    wet suction return. The recircula-

    tor vessel separates overed liquid

    rom vapor and liquid alls to the

    bottom o the vessel to be pumped

    back out to the evaporators while

    the saturated vapor is directed to

    the compressors through the dry

    suction line. Liquid is made up to

    the recirculator vessel rom a high

    mass ow rate o vapor-phase rerigerant leaving the evapora-

    tor in lb/min [kg/s].

    The total liquid rerigerant mass ow rate the pump needs

    to deliver is then:

    m m OR refrigerant pumped refrigerant min, ,= +( )1 (3)

    where mrefrigerant,pumped represents the mass ow rate o liquid

    rerigerant the pump must supply to the connected overeed

    evaporators expressed in lb/min (kg/s). The term (OR+1) is

    commonly reerred to as the circulating rate, Nr. The circu-

    lating rate represents the mass ratio o liquid pumped to the

    evaporators to the amount o vaporized liquid in the evapora-

    tors.1Table 1 shows the required recirculating liquid ow rate

    expressed in gallons per minute o liquid ow or each ton o

    rerigeration load over a range o saturation temperatures and

    circulating rates (OR+1).

    What overfeed rate is required for an individual evapo-

    rator? Evaporator manuacturers typically publish recom-mended overeed rates based on the units specifc design.

    Deviating signifcantly rom the manuacturers recommend-

    ed overeed rate can lead to lower operating capacity o the

    evaporator. Too low o a rerigerant ow rate will starve the

    unit but excessive liquid supply will cause the evaporator

    to brine. Excessive supply o liquid rerigerant ow also in-

    creases the likelihood o pump cavitation. Finally, excessive

    overeeding o liquid to evaporators increases the difculty

    associated with returning the unused liquid to the recircula-

    tor when the return path involves a vertical riser. In this case,

    there is an increased tendency or liquid to accumulate or log

    up in evaporators.

    Figure 1: Mechanically pumped liquid overfeed system arrangement.

    High Pressure Gas

    EvaporativeCondenser

    EvaporativeCondenser

    HighPressureReceiver

    Dry Suction

    Compressor(s)Centrifugal Liquid

    Refrigerant Pump

    PumpedRecirculator

    High PressureLiquid

    KingValve

    E

    qualizerLine

    OverfedEvaporator(s)

    Recir

    culat

    edLiquid

    Retur

    n(We

    tSucti

    on)

    Recir

    culat

    edLiquid

    Supply

    (Pum

    pedL

    iquid

    Line)

    T

    pressure part o the system to replace the liquid that is evaporated

    to meet the rerigeration loads; the recirculator vessel separates

    the ash gas ormed as a result o this throttling process just as it

    separates the two-phase mixture returning rom the evaporators.

    How Much Liquid Refrigerant Needs to Circulate?

    For industrial rerigeration systems using ammonia as the

    rerigerant, the ow rate o liquid rerigerant delivered by thepump to connected evaporators is relatively low due to the re-

    rigerants high heat o vaporization. The total pump ow rate

    will depend on the minimum mass ow rate required to meet

    the aggregate capacity o connected evaporators and the recom-

    mended overeed rate or the evaporators. The minimum mass

    ow rate o liquid required to meet the aggregate rerigeration

    load is given by:

    mQ

    hrefrigerant, min

    load, total

    fg

    = (1)

    where mrefrigerant,min is the minimum liquid rerigerant that

    must be supplied to all connected evaporators to meet theiraggregate load in lb/min (kg/s), Qload,total is the aggregate re-

    rigeration load in Btu/min (kW), and hfg is the enthalpy o

    vaporization or the rerigerant at the operating pressure o

    that suction level in Btu/lb (kJ/kg). The overeed rate (OR) is

    the ratio o liquid mass ow rate to vapor mass ow rate leav-

    ing the evaporator:1

    ORm

    m

    liquid

    vaporwet return

    =

    (2)

    where mliquid is the mass ow rate o liquid-phase rerig-

    erant leaving the evaporator in lb/min [kg/s] andmvapor is the

  • 8/2/2019 Bomba de Refrigerante036-043_jekel

    3/8

    3 8 A S HR A E J o u r n a l a s h r a e . o r g A u g u s t 2 0 1 1

    Recirculated Liquid Flow Rate (gpm/ton)

    Circulating

    Rate

    Liquid Saturation Temperature (F)

    60 40 20 0 20 40

    2:1 0.1117 0.1164 0.1216 0.1274 0.1340 0.1415

    3:1 0.1676 0.1746 0.1824 0.1911 0.2009 0.21224:1 0.2235 0.2328 0.2431 0.2548 0.2679 0.2829

    5:1 0.2793 0.2910 0.3039 0.3185 0.3349 0.3537

    Multiply by 0.0646 to convert table values to m3/h per kWT.

    Table 1: Recirculated gallons per minute per ton of refrigeration.

    Figure 2: Single-stage centrifugal pump.3

    Discharge

    Suction

    Volute

    Impeller

    Impeller Eye

    Anatomy of a Centrifugal Pump

    At a undamental level, the centriu-

    gal pump used or circulating reriger-

    ants is similar to the centriugal pump

    used to move water or other secondary

    uids. Figure 2 shows a single-stagecentriugal pump common or moving

    liquids. The main eature o a centriu-

    gal pump is the impeller, which rotates

    within the pump casing creating a low

    pressure zone near its center (the eye).

    This area o low pressure draws liquid

    into the pump where the rotating impeller increases the kinetic

    energy o the uid by accelerating the liquid outward radially

    to the impeller tips. As the liquid leaves the impeller tips, its

    kinetic energy is at a maximum. The pump housing or volute

    surrounding the impeller then takes over to orderly collect the

    liquid leaving the impeller. The process o gathering liquid

    in the volute converts the kinetic energy o the uid to pres-

    sure (potential) energy. The higher pressure uid then leaves

    the pump through the discharge line.

    Because a rerigerant pump is moving a volatile uid, it is

    highly susceptible to cavitation during operation (see What is

    Cavitation? sidebar). To reduce the likelihood o cavitation,

    liquid rerigerant pumps include design details that dier

    rom ordinary water or secondary uid pumps to decrease the

    pressure loss through the pump suction.

    Liquid Refrigerant Pumps

    Beore discussing the operating details o centriugal re-

    rigerant pumps, it is important to consider a ew conceptsundamental to their successul operation. One o the most

    important concepts is net positive suction head (NPSH). Quite

    simply, suction head represents the pressure at the pumps

    suction. The term net positive is intended to account or the

    balance o positive pressures (static, i.e., height, and absolute

    pressure above the vapor pressure o the uid) and negative

    pressures (losses) attributable to uid ow. Eectively, NPSH

    is the dierence in pressure o rerigerant at the pump suc-

    tion and the rerigerants saturation pressure. An NPSH o 0

    or a pump attempting to move a volatile liquid rerigerant

    indicates that the liquid will ash to a vapor state as it moves

    into the pump.Two types o NPSH that need to be considered to ensure

    proper pump operation: net positive suction head required

    or NPSHr and net positive suction head available or NPSHa.

    NPSHr is the minimum net positive suction head required to

    prevent the liquid rerigerant rom ashing to a vapor. It is a

    characteristic o each given pump and varies with the pumps

    operating point (head and ow) as provided by the pump man-

    uacturer.

    NPSHa is the available net head at the pump suction ac-

    counting or those actors that eectively increase head (static

    head to the liquid elevation ahead o the pump suction, sub-

    cooling o liquid rerigerant within the vessel) and decrease

    head (rictional losses, heat gains, and orm losses). To pre-

    vent pump cavitation, the NPSH available to the pump must

    be greaterthan the minimum requiredby the pump.

    NPSH NPSHa r> (4)

    I a rerigerant pump is cavitating, several options can rem-

    edy the situation. First, determine the pump impeller diameter

    rom original equipment installation documentation or rom

    the data tag on the pump. Next, read the pressure on the dis-charge side o the pump during operation and compare with

    the vessels pressure to determine that the pump is developing

    a pressure rise and note the magnitude (estimated by dier-

    ence between the gauge reading and the vessel pressure). Then

    obtain the pump curve or that specifc model pump and im-

    peller diameter (see the next section).

    With this inormation, look at the manuacturers pump

    curve and determine the pumps ow rate and the required

    net positive suction head (NPSHr) corresponding to that op-

    erating point on the pump curve. I the pump is cavitating

    due to operating out on the curve (toward the right side o

    the pump curve), one approach to cure this cavitation is to

  • 8/2/2019 Bomba de Refrigerante036-043_jekel

    4/8

    www.info.hotims.com/37989-11

  • 8/2/2019 Bomba de Refrigerante036-043_jekel

    5/8

    4 0 A S HR A E J o u r n a l a s h r a e . o r g A u g u s t 2 0 1 1

    Photo 1: Liquid recirculator package showing excessive ice ac-

    cumulation on insulation indicating the failure of the insulation sys-

    tem with corresponding increases in liquid refrigerant heat gain.

    reduce down (close) the hand-expansion valves on the liq-

    uid overed evaporators being served by the pump. Adjusting

    down on, or more, hand-expansion valves will increase the

    discharge head on the pump; thereby, decreasing its ow rateand the corresponding NPSHr. This process should ocus

    on the largest evaporators frst since they have the greatest

    impact on liquid demand. I cavitation-ree pump operation

    cannot be achieved by this approach and the recirculator is

    equipped with a capacitance probe or liquid level sensing/

    control, it may be possible to raise the vessels liquid operat-

    ing level to increase the available net positive suction head

    (NPSHa). However, raising the operating level will reduce

    the capacity o the recirculator vessel or surge (i.e., unex-

    pected return o liquid) rom the system. Another possible

    reason or pump cavitation is excess parasitic heat gain be-

    tween the vessel and the pump suction. Visible rost on thesuction piping, as shown in Photo 1 is an indication o a

    loss o insulation integrity, which increases the heat gain to

    the rerigerant. To remedy this it will require reinsulating the

    pump suction piping.

    The Pump Curve

    A pump curve is a compact, graphical representation o

    a pumps perormance (Figure 3). Lets review the basics

    o reading a pump curve or a liquid rerigerant pump. In

    this case, we will consider an open-drive pump operating

    with ammonia (specifc gravity o 0.7). The horizontal axis

    o the pump curve shows the pumps developed ow rate

    Cavitation is the formation of vapor bubbles within a

    pump followed by their rapid collapse. The formation and

    collapse of vapor bubbles produces a distinct audible sig-

    nature that sounds as if the pump is circulating gravel.Although cavitation can occur in the process of pumping

    any liquid, refrigerant pumps are more susceptible to cavi-

    tation because uid being pumped is at or near saturation

    conditions (i.e., its boiling point). When cavitation occurs,

    the pump loses its ability to consistently move liquid and

    to develop pressure lift. The loss of pump capacity (ow)

    can starve evaporators leading to a loss of refrigeration

    capacity. The action of vapor bubbles collapsing in the

    pump causes erosion of the pump impeller with subsequent

    degradation of pump capacity and efciency. For semi-

    hermetic pumps, the reduction in refrigerant ow can result

    in a reduction of electric motor cooling leading to prema-ture motor failure.

    Preventing cavitation requires keeping the pressure of

    the liquid refrigerant above the saturation pressure cor-

    responding to the refrigerants temperature as it enters

    the pump. This is accomplished by ensuring the refriger-

    ant being pumped has adequate net positive suction head

    (NPSH).

    What Is Cavitation?

    expressed in gal/min. The vertical axis o the pump curve

    shows the generated pump pressure dierential (head) ex-

    pressed in psi.

    The lines that project horizontally rom the vertical axis to

    the right sloping downward represents this models pump per-

    ormance with varying, but discrete, impeller diameters rang-

    ing rom 8 in. (200 mm), the lowermost curve, to 10.375 in.

    (264 mm), the uppermost curve. The dashed lines that run on

    a diagonal rom upper let to lower right represent the required

    pump power ranging rom 1.5 to 5 hp (1.12 to 3.73 kW). The

    semicircular lines represent the pump efciency range rom50% to 65%.

    Below the upper portion o the plot (i.e., the pump curve)

    is an additional plot o the pumps NPSH requirement with

    a 10.375 in. (264 mm) impeller diameter operating with

    a discharge pressure o 23.7 psig (265 kPa) connected to

    an ammonia recirculator operating at a pressure o 8.8 in.

    Hg (40F [40C]). Since the system is operating in a

    vacuum, we must frst determine the pressure developed by

    the pump. The saturation pressure in the recirculator ves-

    sel is 8.8 in. Hg (40F [40C]) or 4.3 psig; thereore,

    the total head or pressure developed by the pump is 28 psi

    (294 kPa). The ow delivered at that pressure dierential(i.e., head) can be determined by drawing a horizontal line

    rom the 28 psi (294 kPa) hash mark to the 10.375 in. (264

    mm) diameter impeller pump curve (blue line). The inter-

    section o this pressure with the pump curve represents the

    pumps operating point. Projecting a vertical line rom the

    pump operating point down to the horizontal axis gives the

    ow delivered by the pump. In this case, the ow is 140

    gpm (31.8 m3/h). From this operating point, other operat-

    ing characteristics o the pump can be obtained such as the

    pump efciency (~64%) and operating power required (~4

    hp [~3 kW]). The last piece o inormation is the NPSHr,

    which is 2 t (0.61 m) in this case.

  • 8/2/2019 Bomba de Refrigerante036-043_jekel

    6/8

    Get the free app for your phone athttp://gettag.mobi

    SNAP

    IT

    Whether you are an HVAC&R system designer, architect,

    building owner, building manager/operator, or contrac-

    tor charged with designing a green building, ASHRAE

    GreenGuide helps answer your biggest questionWhat

    do I do now? Using an integrated, building systems

    perspective, it gives you the need-to-know information

    on what to do, where to turn, what to suggest, and how

    to interact with other members of the design team in a

    productive way.

    This third edition of ASHRAE GreenGuide is an easy-

    to-use reference with information on almost any subject

    that should be considered in green-building design.

    The GreenTips found throughout this edition highlight

    techniques, processes, measures, or special systems in

    a concise, often bulleted, format. Information is provided

    in dual unitsInch-Pound (I-P) and International System

    (SI)so that the content is easily applicable worldwide.

    NEW in this edition:

    Guidelines on sustainable energy master planning

    Updates on teaming strategies

    Information on how issues related to carbon emissions affect building design and operational decisions

    Strategies for greening existing buildings

    Updates on newly developed green-building rating systems and standards

    Additional information on building energy modeling and follow-up measurement and verication

    Compliance strategies for key ASHRAE standards

    A new chapter on water efciency

    New GreenTips, including those with green strategies for chilled-water plant and boiler plant design

    ASHRAE GreenGuideThe Design, Construction, andOperation of Sustainable BuildingsThird Edition

    ASHRAE Member Price: $83List Price: $98Visit www.ashrae.org/greenguide

    ASHRAE GreenGuideThe Design, Construction, and Operation

    of Sustainable Buildings

    American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.

    Third Edition

    NEW!

    www.info.hotims.com/37989-85

  • 8/2/2019 Bomba de Refrigerante036-043_jekel

    7/8

    4 2 A S HR A E J o u r n a l a s h r a e . o r g A u g u s t 2 0 1 1

    Other Considerations

    Minimum Flow Protection.While operating, liquid reriger-

    ant pumps always need to move some amount o liquid to avoid

    orming vapor within the pump due to heat addition rom the in-

    efciency o the pump or motor (i its a semi-hermetic confgu-

    ration). The added heat at low ow conditions can also cause the

    liquid rerigerant in the pump to boil, leading to cavitation. To

    prevent this orm o cavitation, a bypass (or minimum ow)

    line rom the pump discharge back to the pumped recircula-

    tor or recirculated liquid return is installed with an orifce (or

    metering valve) set at a manuacturers required minimum ow.

    During normal operation, the heat gain rom the pump powerinput is small, or the example we used earlier the heat gain

    would result in a temperature rise o 0.18F (0.1C).

    Presence of EPRs on Pump Discharge Pressure Require-

    ment. Pumping liquid to evaporators equipped with evapora-

    tor pressure regulators (EPRs) requires special attention. First,

    the liquid eed pressure at the evaporator, and thus the pump

    discharge pressure, must be higher than the EPR set pressure

    to get liquid into the evaporator. Second, it is important to re-

    alize that the pumped liquid rerigerant being supplied to an

    EPR-ftted evaporator is subcooledas it enters the evaporator.

    The liquid rerigerant entering the evaporator is essentially at

    the temperature o the liquid in the pumped recirculator (plus a

    slight temperature rise due to heat gain in the pump and in the

    liquid piping). Since the liquid rerigerant supply temperature

    is below the saturation temperature corresponding to the EPR

    pressure setting, the liquid rerigerant entering the evaporator

    has to absorb heat to sensibly raise the rerigerant temperature

    until it reaches its saturation temperature corresponding to the

    operating pressure prior to its boiling. Evaporators operating

    with liquid rerigerant supply temperatures more than 10F

    (5.6C) below saturation temperature will likely result in poor

    evaporator perormance.

    Static Head Requirements in Open Loops (Why VFDs

    Are Not Great For Refrigerant Pumps).Another issue withopen loop pumping circuits is that the static head requirement

    sets the minimum discharge pressure to get ow to the evapo-

    rators. This means that beore there is any ow to the evapora-

    tors, the pressure required to lit the liquid to the roo (or to the

    elevation o evaporators) must be overcome. I the pressure

    generated by the pump is not sufcient, the pump will operate

    at its minimum ow with a column o liquid standing in the

    riser supplying liquid rerigerant to the roo. In other words,

    the pump is not capable o delivering ow to the evaporators.

    This is the main reason that variable requency drives (VFDs)

    are generally not suitable applications or rerigerant pumping

    in liquid overeed applications. Note that a 50 t (15.24 m) rise

    Figure 3: Pump curve for a liquid refrigerant pump.

    gpm

    10.375 in. 50

    50

    55

    55

    60

    62 64 65

    1.5 hp55

    50

    2 hp

    64

    6260

    55

    50

    3 hp

    8 in.

    35

    30

    25

    20

    15

    10

    5

    0

    NPSHr

    (ft)

    Head

    (psi)

    40

    30

    20

    10

    0

    10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210

    5 hp

    10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210

  • 8/2/2019 Bomba de Refrigerante036-043_jekel

    8/8

    www.info.hotims.com/37989-24www.info.hotims.com/37989-41

    A u g us t 2 0 1 1 A SHR A E J our n a l 4 3

    in an ammonia liquid line requires a pressure dierence o

    approximately 15 psi (103 kPa) just to lit liquid to the roo.

    Hydrostatic Lock-Up. Hydrostatic lock-up is the trapping

    o subcooled (or pressurized) liquid rerigerant in a fxed vol-

    ume and exposing that trapped volume to a heat source. As the

    trapped liquid absorbs heat, it causes an increase in temperature,which causes the trapped liquid to volumetrically expand leading

    to a substantial increase in rerigerant pressure and an increased

    likelihood o component or equipment ailure. It is important

    to identiy locations within a rerigeration system that can trap

    liquid and provide suitable means o overpressure protection.

    ASHRAE Standard 15-2010, Safety Standard for Refrigerating

    Systems, provides requirements or protection rom hydrostatic

    lock-up. The liquid eed valve train on an overed evaporator is a

    location where hydrostatic lock-up is only a danger during main-

    tenance procedures; thereore, can be eectively managed with

    proper procedures and employee training. However, the liquid

    supply piping between the pump discharge check valve and the

    liquid eed solenoids on the evaporators must be protected rom

    hydrostatic lock-up in the event o a plant-wide power ailure.

    No amount o procedures or training can mitigate this hydraulic

    lock-up scenario; thereore, the installation o a hydrostatic re-

    lie device downstream o the pump discharge check valve piped

    back to the recirculator vessel is required.

    Summary

    This article introduced concepts that are distinctive to

    pumping rerigerants with centriugal pumps. In industrial

    rerigeration systems, the use o centriugal pumps or sup-

    plying low temperature liquid rerigerant to loads has be-

    come quite common. Although a simple concept, the suc-cessul design, installation, and operation o centriugal

    liquid rerigerant pumps does require care and attention to

    a number o details. One o the most common operational

    problems ought in the feld is rerigerant pump cavitation.

    In a number o installations, we have ound the contributing

    or root cause to cavitation is the excess ow o liquid through

    the pump due to hand-expansion valves on individual evapo-

    rators being set too ar open. When cavitation occurs, cool-

    ing capacity is lost and the likelihood o premature pump

    (or motor) ailure increases. We hope this article helps you

    understand and troubleshoot potential problems that may ex-

    ist in rerigerant pumping systems.

    References

    1. 2010 ASHRAE HandbookRefrigeration.

    2. Stoecker, W.F. 1998.Industrial Refrigeration Handbook. McGraw

    Hill Publishers.

    3. Chaurette, J. 2011. Personal communication.


Recommended