CB200CB200e e Cabinet Extinguishant Cabinet Extinguishant Control PanelsControl Panels
• Designed for cabinet extinguishant systems
• 2 zone extinguishant co-incidence operation
• Selectable discharge circuit delay (0-10-20-30
seconds)
• Alarm circuit and C/O fire relay included
• Actuator and Solenoid compatible
• One man test facility
CB200 Conventional Control PanelsCB200 Conventional Control Panels
• Earth fault monitoring
• Surface or semi-flush mounting as standard
• Ample termination space
• Flame Resistant Polycarbonate enclosure
• Complies with EMC and LVD Directives
Cabinet SpecificationsCabinet Specifications
Panel dimensions are detailed in the Application
Guide.
Panel dimensions are detailed in the Application
Guide.
The removable gland plate and cable entry grommets obviate the need to drill wiring
holes in the panel on site.
The removable gland plate and cable entry grommets obviate the need to drill wiring
holes in the panel on site.
Semi-flush is available as standard because of the
construction of the CB200 enclosure.
Semi-flush is available as standard because of the
construction of the CB200 enclosure.
-
+
+
-
Mechanical AssemblyMechanical Assembly
This drawing shows the ample wiring space incorporated into
the CB200 panel design.
This drawing shows the ample wiring space incorporated into
the CB200 panel design.
Installer’s logo or brand
image may be added.
Installer’s logo or brand
image may be added.
Electronics are completely removable for convenience on site during fitting of the
back box.
Electronics are completely removable for convenience on site during fitting of the
back box.
PCB terminal support for mechanical reliability.
PCB terminal support for mechanical reliability.
There is space for two 12V 2.1AH batteries - suitable
for the 24hr standby requirements on an 8 zone
system.
There is space for two 12V 2.1AH batteries - suitable
for the 24hr standby requirements on an 8 zone
system.
Typical Wiring Schematic Typical Wiring Schematic
This is a typical CB200e wiring illustration as it appears in the
product documentation.
This is a typical CB200e wiring illustration as it appears in the
product documentation.
Apollo S60 detectors are illustrated, but the CB200e panel supports a wide variety of other manufacturers’ detectors - details
in the Application Guide.
Apollo S60 detectors are illustrated, but the CB200e panel supports a wide variety of other manufacturers’ detectors - details
in the Application Guide.
SUPPRESSION
FROM MAINS
DIODE
DIODEPOLARISING
COILACTUATOR
COILACTUATOR
RESISTOR3K9 EOL CAPACITORRESISTOR
3K9 EOL
WITH SCHOTTKY DIODEAPOLLO S60 DETECTOR BASE
RESISTOR FITTEDWITH 680 OHM
MANUAL CALL POINT
22uF EOL
2
2A1A
1
L1OUT
L1 IN
L212V
BATTERY12V
BATTERY
DISABLEBUZZER
PROC. FAULT RESET
(SEE MANUAL) RESETPROCESSOR
~~
ACTUATOR ALARM ZONE 2 ZONE 1IN
SECONDARYAUX FIRE RELAY 24V BATT. EARTHBAT+BAT-Z1+Z1-Z2+Z2-ALM+ALM-ACT+ACT-N/ CPN/ O AC IN AND ONE MAN TEST
TRANSFORMER