CERTIFICATE OF COMPLIANCE Certificate Number 20180626-E341165 Report Reference E341165-20171030 Issue Date 2018-June-26 Bruce Mahrenholz, Director North American Certification Program UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/ Page 1 of 3 Issued to: Enphase Energy Inc. 1420 N. McDowell Blvd. Petaluma, CA 94954-6515 This is to certify that representative samples of Photovolic Grid Support Utility Interactive Inverter with Rapid Shutdown Functionality Models IQ7-60, IQ7PLUS-72, and IQ7X-96, followed by -2, -5, -B, or - ACM, followed by -US+. Models IQ7PD-72-2-US and IQ7PD-84-2-US. Have been investigated by UL in accordance with the Standard(s) indicated on this Certificate. Standard(s) for Safety: UL 1741, Standard for Safety for Inverters, Converters, Controllers and Interconnection System Equipment for Use With Distributed Energy Resources, UL 1741, Second Edition, dated January 28, 2010. Including the requirements in UL 1741 Supplement SA, sections as noted in the Technical considerations. IEEE 1547, IEEE Standard for Interconnecting Distributed Resources with Electric Power Systems. IEEE 1547.1, IEEE Standard for Conformance Test Procedures for Equipment Interconnecting Distributed Resources with Electric Power Systems. UL 62109-1, Safety of Converters for Use in Photovoltaic Power Systems - Part 1: General Requirements; IEC 62109-2, Safety of Power Converters for use in Photovoltaic Power Systems - Part 2: Particular Requirements for Inverters. CSA C22.2 No. 107.1-01, General Use Power Supplies. Additional Information: See the UL Online Certifications Directory at www.ul.com/database for additional information Only those products bearing the UL Certification Mark should be considered as being covered by UL's Certification and Follow-Up Service. Look for the UL Certification Mark on the product.
Transcript
Page 1: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

C E R T I F I C A T E O F C O M P L I A N C ECertificate Number 20180626-E341165

Report Reference E341165-20171030 Issue Date 2018-June-26

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 1 of 3

Issued to: Enphase Energy Inc. 1420 N. McDowell Blvd. Petaluma, CA 94954-6515

This is to certify that representative samples of

Photovolic Grid Support Utility Interactive Inverter with Rapid Shutdown Functionality

Models IQ7-60, IQ7PLUS-72, and IQ7X-96, followed by -2, -5, -B, or -ACM, followed by -US+. Models IQ7PD-72-2-US and IQ7PD-84-2-US.

Have been investigated by UL in accordance with the Standard(s) indicated on this Certificate.

Standard(s) for Safety: UL 1741, Standard for Safety for Inverters, Converters, Controllersand Interconnection System Equipment for Use With Distributed Energy Resources, UL 1741, Second Edition, dated January 28, 2010. Including the requirements in UL 1741 Supplement SA, sections as noted in the Technical considerations.

IEEE 1547, IEEE Standard for Interconnecting Distributed Resources with Electric Power Systems.

IEEE 1547.1, IEEE Standard for Conformance Test Procedures for Equipment Interconnecting Distributed Resources with Electric Power Systems.

UL 62109-1, Safety of Converters for Use in Photovoltaic Power Systems - Part 1: General Requirements; IEC 62109-2, Safety of Power Converters for use in Photovoltaic Power Systems - Part 2: Particular Requirements for Inverters.

CSA C22.2 No. 107.1-01, General Use Power Supplies. Additional Information: See the UL Online Certifications Directory at

www.ul.com/database for additional information

Only those products bearing the UL Certification Mark should be considered as being covered by UL's Certification and Follow-Up Service.

Look for the UL Certification Mark on the product.

Page 2: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

C E R T I F I C A T E O F C O M P L I A N C E

Certificate Number 20180626-E341165 Report Reference E341165-20171030

Issue Date 2018-June-26

Bruce Mahrenholz, Director North American Certification Program UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 2 of 3

This is to certify that representative samples of the product as specified on this certificate were tested according to the current UL requirements. Standards for Safety: UL 1741, Standard for Safety for Inverters, Converters, Controllers and Interconnection System

Equipment for Use With Distributed Energy Resources, UL 1741, Second Edition, dated January 28, 2010. Including the requirements in UL 1741 Supplement SA, sections as noted in the Technical considerations.

IEEE 1547, IEEE Standard for Interconnecting Distributed Resources with Electric Power Systems. IEEE 1547.1, IEEE Standard for Conformance Test Procedures for Equipment Interconnecting

Distributed Resources with Electric Power Systems. UL 62109-1, Safety of Converters for Use in Photovoltaic Power Systems - Part 1: General

Requirements; IEC 62109-2, Safety of Power Converters for use in Photovoltaic Power Systems - Part 2: Particular Requirements for Inverters.

CSA C22.2 No. 107.1-01, General Use Power Supplies.

Page 3: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

C E R T I F I C A T E O F C O M P L I A N C E

Certificate Number 20180626-E341165 Report Reference E341165-20171030

Issue Date 2018-June-26

Bruce Mahrenholz, Director North American Certification Program UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 3 of 3

Components covered by this certificate provide functionality in compliance with UL 1741Supplement A (SA) when used in a UL Listed end product which has been evaluated by UL for it’s intended purpose. Compliance testing was conducted on samples of the products according to the test methods in UL 1741 with compliant results, and product ratings were reviewed for fulfillment of the requirements in the following SRDs:

See also Appendixes A - E: Grid Support Utility Interactive Inverter Worksheet

Grid Support Function Source Requirement Document(s)

Test Standard(s) and Section(s)

NRTL Certified Date

TRANSIENT OVERVOLTAGE (TrOV-2)

HECO APPENDIX 1: Transient Overvoltage Self-Certification

Instructions

N/A

N/A

LOW/HIGH VOLTAGE RIDE-THROUGH

SRD 14H V1.1: Part II.C. Table 4 UL 1741 SA 9 2018-May-28

LOW/HIGH FREQUENCY RIDE-THROUGH

SRD 14H V1.1: Part II.D.1 Table 5

UL 1741 SA 10 2018-May-28

RAMP RATES SRD 14H V1.1: Part II.G.1 UL 1741 SA 11.2 2018-May-28 RECONNECT BY "SOFT START" SRD 14H V1.1: Part II.G.2 UL 1741 SA 11.4 2018-May-28

SPECIFIED POWER FACTOR SRD 14H V1.1: Part II.A.1 UL 1741 SA 12 2018-May-28 DYNAMIC VOLT/VAR

OPERATIONS SRD 14H V1.1: Part II.A.2 Table

2, Figure 2 UL 1741 SA 13 2018-May-28

FREQUENCY-WATT SRD 14H V1.1: Part II.F Table 7 UL 1741 SA 14 2018-May-28

VOLT-WATT SRD 14H V1.1: Part II.B Table 3,

Figure 3 UL 1741 SA 15 2018-May-28

Page 4: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix A: Grid Support Utility Interactive  Worksheet

‐ ‐

‐ ‐

‐ ‐‐ ‐‐ ‐‐ ‐‐ ‐

‐ ‐

Min Max16 4827 37

‐ IQ7unitless

Volts 50 % < V  120 %at 240 V: 2.4 Vat 208 V: 2.08 V

Amps 100 %

15

DC voltage  ratingMaximum power point track range

Displacement 20 % < P  100 % 2

s 100 ms to 600 s 33*

Hz 50 to 66 Hz 0.1 HzWatts 20 % < P  100 %

Model #IQ7‐60‐x‐US

where x = 2, 5, B or ACM

Certification / Self‐Certification Certified

Manufacturer Enphase Energy Inc

Active PowerReactive PowerPower Factor

Time

UNITS

INVERTER DC (INPUT) SIDE

NRTL Name UL LLCCertificate # 20180307‐E341165

VAR 20 % < Q  100 % 5

*two line cycles or 1% of setting, whichever is larger

RATINGRANGE DESCRIPTION

Provide MSA for each model represented

±0.01•Vn

Not specified

Not specified

Report # E341165‐20171030

 SA Certification Date 2018‐June‐26

Responsible Engineer Bruce Mahernholz

VALUE DESCRIPTIONUNITSRATING

MANUFACTURER's STATED ACCURACY

VALUE

Model

Voltage, RMS

Current, RMSFrequency

Max input short‐circuit current

VDC‐ rating VoltsVoltsAmps

VMPPT‐RANGE

IDC max

GENERAL

List Applicable Model(s)

Choose 1

NOTESVALUE INFORMATION

Complete all fields highlighted in red.

Firmware version v02.14.02 Provide applicable firmware 

Page  1

Page 5: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix A: Grid Support Utility Interactive  Worksheet

UNITSVoltsVolts

NumberVA

AmpsAmps

Min Max Min Max Min Max

Underexcited, Inductive, Absorbing ‐70 100 ‐70 100 % ‐85% to 100% ‐

Overexcited, Capacitive, Injecting 100 70 100 70 % 100% to 85% ‐

Underexcited, Inductive, Absorbing ‐70 100 ‐70 100 % ‐90% to 100% Y

Overexcited, Capacitive, Injecting 100 70 100 70 % 100% to 90% Y

Nominal Voltage Phase‐phaseNumber of electrical phases

2401.00

>15 kW

<=15 kWCapacitive (var injection) power factor to Reactive (var absorption) power factor range.  RULE 14H  Default PF = ‐0.95 (Absorbing) for self certification purposes.

Capacitive (var injection) power factor to Reactive (var absorption) power factor range.  RULE 14H  Default PF = ‐0.95 (Absorbing) for self certification purposes.

POUTINOMINAL‐OUTPUT

DESCRIPTION

INVERTER AC (OUTPUT) SIDE

FIXED POWER FACTOR208 ‐

VAC‐NOMINAL(Phase‐phase) 240 208 ‐Number of Phases 1 1 ‐

240

Rated Power OutputNominal current per phaseMaximum output current at lowest operating voltage

SRD V1.1 Range

SRD V1.1 Compliant?

Nominal Voltage Phase‐neutral (if neutral available)

IMAXIMUM‐OUTPUT  (at Vlow) 1.15

VALUE RATINGVAC‐NOMINAL(Phase‐neutral) N/A N/A ‐

2401.151.32

DESCRIPTIONUNITS

Page  2

Page 6: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix A: Grid Support Utility Interactive  Worksheet

Min Max Min Max Min MaxIRMS_MAX@VRT( V = 120%) Amps ‐ ‐

tTRIP (V > 120%) 0.16 0.16 0.16 0.16 Sec. 0.16 YIRMS_MAX@VRT(V = 110%) Amps ‐ ‐

tRIDE‐THROUGH (110% < V  120%) 0.80 12.8 0.80 12.8 Sec. 0.92 YtTRIP (110% < V  120%) 1.00 13.0 1.00 13.0 Sec. 1 YIRMS_MAX@(V = 109%) Amps ‐ ‐

IRMS@(V = 100%) Amps ‐ ‐IRMS_MIN@(V = 90%) Amps ‐ ‐

IRMS_MIN@VRT(V = 75%) Amps ‐ ‐tRIDE‐THROUGH (70%  V  88%) 20 49.8 20 49.8 Sec. 20 Y

tTRIP (70%  V  88%) 21.0 50.0 21.0 50.0 Sec. 21 YIRMS_MIN@VRT(V = 70%) Amps ‐ ‐

tRIDE‐THROUGH (50%  V < 70%) 10.00 49.8 10.00 49.8 Sec. 10‐20 YtTRIP (50%  V < 70%) 11.00 50.0 11.00 50.0 Sec. 11‐21 Y

IRMS_MIN@VRT(V = 50%) Amps ‐ ‐tRIDE‐THROUGH (V <  50%) 0.30 20.8 0.30 20.8 Sec. ‐ ‐

tTRIP (V < 50%) 0.50 21.0 0.50 21.0 Sec. 2 Y

Min Max Min Max Min MaxIRMS_MAX@FRT(f = 64Hz) Amps ‐ ‐

tTRIP (f > 64 Hz) 0.16 1000.0 0.16 1000.0 Sec. 0.16 YIRMS_MAX@FRT(63 Hz < f  64Hz) Amps ‐ ‐tRIDE‐THROUGH (63 Hz< f  64 Hz) 20.00 999.8 20.00 999.8 Sec. 20 Y

tTRIP (63 Hz < f  64 Hz) 21 1000.0 21 1000.0 Sec. 21 YIRMS_MAX@ f = 63 Hz Amps ‐ ‐

IRMS@ f = 60 Hz Amps ‐ ‐IRMS_MIN@ f = 57 Hz Amps ‐ ‐

IRMS_MIN@FRT(56 Hz  f < 57 Hz) Amps ‐ ‐tRIDE‐THROUGH (56 Hz  f < 57 Hz) 20.00 999.8 20.00 999.8 Sec. 20 Y

tTRIP (56 Hz  f < 57 Hz) 21 1000.0 21 1000.0 Sec. 21 YIRMS_MIN@FRT(f < 56 Hz) Amps ‐ ‐

tTRIP (f < 56 Hz) 0.16 1000 0.16 1000 Sec. 0.16 Y

Nominal1.001.001.00

VOLTAGE RIDE‐THROUGH

UF1

UF2

OF2

OF1

OV2

1.00

N/A

N/A

N/A

Nominal0.941.001.15

‐240 208

N/A

N/A

N/A

N/A

N/A

FREQUENCY RIDE‐THROUGH

1.00

OV1

UV3

UV2

UV1

N/A

N/A

1.081.15

Minimum RMS current when voltage is 90%

Maximum RMS current when voltage goes above to 120% before trip; Not specifiedTrip timeMaximum RMS current when voltage is between 110% and 120% before trip; Not specifiedRide through timeTrip timeMaximum RMS current when voltage is 109%RMS current when voltage is 100%

1.32

1.00

1.00Trip time

1.15

1.151.151.151.15

1.15

Ride Through TimeTrip timeMaximum RMS current when the frequency is 63 HzRMS current when the frequency is 60 HzMinimum RMS current when the frequency is 57 HzMinimum RMS current when the frequency is between 56 and 57 Hz before tripRide Through Time

Minimum RMS current when the frequency is below 56 Hz before trip

Maximum RMS current when the frequency is between 63 and 64 Hz before trip

1.15

240 208 ‐

Maximum RMS current when the frequency is above 64 Hz before tripTrip time

Minimum RMS current when voltage is between 70% and 88% before trip; Not specifiedRide through timeTrip timeMinimum RMS current when voltage is between 50% and 70% before trip; Not specifiedRide through timeTrip timeMinimum RMS current when voltage is below 50% before trip;Not specified

Trip time

Ride through time

SRD V1.1 Range

SRD V1.1 Range

SRD V1.1 Compliant?

UNITS

Trip time

DESCRIPTION

DESCRIPTIONSRD V1.1 Compliant?

UNITS

Page  3

Page 7: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix A: Grid Support Utility Interactive  Worksheet

Min Max Min Max Min Max82 98 82 98 % VNOMINAL 94 Y

0 53 0 53% Q (Var Injection)

44 Y

97 100 97 100 % VNOMINAL 97 Y‐53 53 ‐53 53 % Q (0 VAr) 0 Y100 103 100 103 % VNOMINAL 103 Y‐53 53 ‐53 53 % Q (0 VAr) 0 Y102 118 102 108 % VNOMINAL 106 Y

‐53 0 ‐53 0% Q (Var 

Absorption)‐44 Y

1 90 1 90 Sec. 10 YReactive Reactive Reactive Reactive Unitless Reactive Y

Min Max Min Max Min Max1 100 1 100 % PRATED/sec. 100 Y0.1 100 0.1 100 % PRATED/sec. 0.33 Y

Min Max Min Max Min Max1.12 100 1.12 100 % PPRATED/V ‐25 Y105 109 105 109 % Vnom 106 Y107 110 107 110 % Vnom 110 Y1 90 1 90 Sec. 10 Y

unitlessPrated or Ppre‐

disturbanceY

Min Max Min Max Min Max

0.2 0.83 0.2 0.83 %Prated/Hz ~42 Y

60.017 61 60.017 61 Hz 60.04 Y0.05 3 0.05 3 Sec. 0.5 Y

unitlessPrated or Ppre‐

disturbanceY

Response Time Response tiem (If non‐adjustable range, place default value in MIN)Stop voltage Power reduction endpoint voltage

Response time (if non‐adjustable range, place default value in MIN)Response TimePower Priortity Power Priority

V2, UVVolt‐Var_MAX

% Q2, VArs@UV_Volt‐Var_MAX

V3, OVVolt‐Var_MIN

FWRATE

Power Rate

Power Reference

Soft Start RAMPRATE

POWER RAMP RATE240

VOLT‐WATT 240

Start voltage

% Q3, VArs@OV_Volt‐Var_MIN

V4, OVVolt‐Var_MAX

% Q4, VArs@OV_Volt‐Var_MAX

Connect/Reconnect RAMPRATE 

VOLT‐VAR, Q(V)240

V1, UVVolt‐Var_MIN

% Q1, VArs@UV_Volt‐Var_MIN

Lowest voltage where Volt‐VAr starts at overvoltageVArs at lowest overvoltage Volt‐VAR point

208 ‐

Lowest voltage where Volt‐VAr starts at undervoltageVArs at lowest undervoltage Volt‐VAR point (‐53% for aggregate generating facility >15 kW, ‐44% for aggregate generating facility <= 15 kW)Highest voltage where Volt‐VAr finish at undervoltageVArs at highest undervoltage Volt‐VAR point

Percentage of nominal generated power per second "Ramp Rate"

DESCRIPTION

208 ‐ SRD V1.1 Range

SRD V1.1 Compliant?

UNITS DESCRIPTION

Highest voltage where Volt‐VAr finish at overvoltageVVArs at highest overvoltage Volt‐VAR point (53% for aggregate generating faility  >15 kW, 44% for aggregate generating facility <= 15 kW)

SRD V1.1 Range

Percentage of power reduction per volt "Volt‐Watt rate"

208 ‐ SRD V1.1 Range

SRD V1.1 Compliant?

UNITS

Percentage of nominal generated power per second "Ramp Rate"

UNITS

Power Reference Prated Prated

SRD V1.1 Compliant?

Power reduction starting voltage

DESCRIPTION

Active power output

Power reduction Starting Frequency (Based on dbOF = 0.036 Hz)

Active power output

Response tiem (if non‐adjustable range, place default value in MIN)

METHODS FOR APPLYING SETPOINTS

FREQUENCY‐WATT 240 208 ‐

UNITSSRD V1.1 Range

SRD V1.1 Compliant?

DESCRIPTION

Minimum percentage of power reduction per hertz "frequency‐watt rate" (based on kOF = 0.04)

Prated Prated

Freq adjustment range at Start frequencyResponse Time

Page  4

Page 8: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix A: Grid Support Utility Interactive  Worksheet

Installers will use the Enphase Installer Tool Kit to connect to Enphase's cloud based Enlighten system to install one of the following grid profiles.HEI SRD V1.1 O+M+H CSS w/VWHEI SRD V1.1 O+M+H CSS no VWHEI SRD V1.1 O+M+H CGS w/VWHEI SRD V1.1 O+M+H CGS no VWHEI SRD V1.1 L+M CSS w/VWHEI SRD V1.1 L+M CSS no VWHEI SRD V1.1 L+M CGS w/VWHEI SRD V1.1 L+M CGS no VW

O+M+H = Oahu+Maui+HawaiiL+M = Lanai+MolokaiCSS = Customer Self SupplyCGS = Customer Grid Supplyw/VV = Volt‐Watt function enabledno VV = Volt‐Watt function  disabled

If customization of any of these grid profiles is required, the installer must contact Enphase Customer Service.

Page  5

Page 9: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix B: Grid Support Utility Interactive  Worksheet

‐ ‐

‐ ‐

‐ ‐‐ ‐‐ ‐‐ ‐‐ ‐

‐ ‐

Min Max16 6027 45

‐ IQ7PLUSunitless

Volts 50 % < V  120 %at 240 V: 2.4 Vat 208 V: 2.08 V

Amps 100 % N/A

15

DC voltage  ratingMaximum power point track range

Displacement 20 % < P  100 % 2

s 100 ms to 600 s 33*

Hz 50 to 66 Hz 0.1 HzWatts 20 % < P  100 % N/A

Model #IQ7PLUS‐72‐x‐US

where x = 2, 5, B or ACM

Certification / Self‐Certification Certified

Manufacturer Enphase Energy Inc

Active PowerReactive PowerPower Factor

Time

UNITS

INVERTER DC (INPUT) SIDE

NRTL Name ULCertificate # 20180307‐E341165

VAR 20 % < Q  100 % 5

*two line cycles or 1% of setting, whichever is larger

RATINGRANGE DESCRIPTION

Provide MSA for each model represented

±0.01•Vn

Not specified

Not specified

Report # E341165‐20171030

 SA Certification Date 2018‐June‐26

Responsible Engineer Bruce Mahernholz

VALUE DESCRIPTIONUNITSRATING

MANUFACTURER's STATED ACCURACY

VALUE

Model

Voltage, RMS

Current, RMSFrequency

Max input short‐circuit current

VDC‐ rating VoltsVoltsAmps

VMPPT‐RANGE

IDC max

GENERAL

List Applicable Model(s)

Choose 1

NOTESVALUE INFORMATION

Complete all fields highlighted in red.

Firmware version v02.14.02 Provide applicable firmware 

Page  1

Page 10: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix B: Grid Support Utility Interactive  Worksheet

UNITSVoltsVolts

NumberVA

AmpsAmps

Min Max Min Max Min Max

Underexcited, Inductive, Absorbing ‐70 100 ‐70 100 % ‐85% to 100% ‐

Overexcited, Capacitive, Injecting 100 70 100 70 % 100% to 85% ‐

Underexcited, Inductive, Absorbing ‐70 100 ‐70 100 % ‐90% to 100% Y

Overexcited, Capacitive, Injecting 100 70 100 70 % 100% to 90% Y

Nominal Voltage Phase‐phaseNumber of electrical phases

2901.21

>15 kW

<=15 kWCapacitive (var injection) power factor to Reactive (var absorption) power factor range.  RULE 14H  Default PF = ‐0.95 (Absorbing) for self certification purposes.

Capacitive (var injection) power factor to Reactive (var absorption) power factor range.  RULE 14H  Default PF = ‐0.95 (Absorbing) for self certification purposes.

POUTINOMINAL‐OUTPUT

DESCRIPTION

INVERTER AC (OUTPUT) SIDE

FIXED POWER FACTOR208 ‐

VAC‐NOMINAL(Phase‐phase) 240 208 ‐Number of Phases 1 1 ‐

240

Rated Power OutputNominal current per phaseMaximum output current at lowest operating voltage

SRD V1.1 Range

SRD V1.1 Compliant?

Nominal Voltage Phase‐neutral (if neutral available)

IMAXIMUM‐OUTPUT  (at Vlow) 1.37

VALUE RATINGVAC‐NOMINAL(Phase‐neutral) N/A N/A ‐

2901.391.58

DESCRIPTIONUNITS

Page  2

Page 11: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix B: Grid Support Utility Interactive  Worksheet

Min Max Min Max Min MaxIRMS_MAX@VRT( V = 120%) Amps ‐ ‐

tTRIP (V > 120%) 0.16 0.16 0.16 0.16 Sec. 0.16 YIRMS_MAX@VRT(V = 110%) Amps ‐ ‐

tRIDE‐THROUGH (110% < V  120%) 0.80 12.8 0.80 12.8 Sec. 0.92 YtTRIP (110% < V  120%) 1.00 13.0 1.00 13.0 Sec. 1 YIRMS_MAX@(V = 109%) Amps ‐ ‐

IRMS@(V = 100%) Amps ‐ ‐IRMS_MIN@(V = 90%) Amps ‐ ‐

IRMS_MIN@VRT(V = 75%) Amps ‐ ‐tRIDE‐THROUGH (70%  V  88%) 20 49.8 20 49.8 Sec. 20 Y

tTRIP (70%  V  88%) 21.0 50.0 21.0 50.0 Sec. 21 YIRMS_MIN@VRT(V = 70%) Amps ‐ ‐

tRIDE‐THROUGH (50%  V < 70%) 10.00 49.8 10.00 49.8 Sec. 10‐20 YtTRIP (50%  V < 70%) 11.00 50.0 11.00 50.0 Sec. 11‐21 Y

IRMS_MIN@VRT(V = 50%) Amps ‐ ‐tRIDE‐THROUGH (V <  50%) 0.30 20.8 0.30 20.8 Sec. ‐ ‐

tTRIP (V < 50%) 0.50 21.0 0.50 21.0 Sec. 2 Y

Min Max Min Max Min MaxIRMS_MAX@FRT(f = 64Hz) Amps ‐ ‐

tTRIP (f > 64 Hz) 0.16 1000.0 0.16 1000.0 Sec. 0.16 YIRMS_MAX@FRT(63 Hz < f  64Hz) Amps ‐ ‐tRIDE‐THROUGH (63 Hz< f  64 Hz) 20.00 999.8 20.00 999.8 Sec. 20 Y

tTRIP (63 Hz < f  64 Hz) 21 1000.0 21 1000.0 Sec. 21 YIRMS_MAX@ f = 63 Hz Amps ‐ ‐

IRMS@ f = 60 Hz Amps ‐ ‐IRMS_MIN@ f = 57 Hz Amps ‐ ‐

IRMS_MIN@FRT(56 Hz  f < 57 Hz) Amps ‐ ‐tRIDE‐THROUGH (56 Hz  f < 57 Hz) 20.00 999.8 20.00 999.8 Sec. 20 Y

tTRIP (56 Hz  f < 57 Hz) 21 1000.0 21 1000.0 Sec. 21 YIRMS_MIN@FRT(f < 56 Hz) Amps ‐ ‐

tTRIP (f < 56 Hz) 0.16 1000 0.16 1000 Sec. 0.16 Y

Nominal1.211.211.21

VOLTAGE RIDE‐THROUGH

UF1

UF2

OF2

OF1

OV2

1.21

N/A

N/A

N/A

Nominal1.111.211.37

‐240 208

N/A

N/A

N/A

N/A

N/A

FREQUENCY RIDE‐THROUGH

1.21

OV1

UV3

UV2

UV1

N/A

N/A

1.281.39

Minimum RMS current when voltage is 90%

Maximum RMS current when voltage goes above to 120% before trip; Not specifiedTrip timeMaximum RMS current when voltage is between 110% and 120% before trip; Not specifiedRide through timeTrip timeMaximum RMS current when voltage is 109%RMS current when voltage is 100%

1.58

1.21

1.21Trip time

1.39

1.391.391.391.39

1.39

Ride Through TimeTrip timeMaximum RMS current when the frequency is 63 HzRMS current when the frequency is 60 HzMinimum RMS current when the frequency is 57 HzMinimum RMS current when the frequency is between 56 and 57 Hz before tripRide Through Time

Minimum RMS current when the frequency is below 56 Hz before trip

Maximum RMS current when the frequency is between 63 and 64 Hz before trip

1.39

240 208 ‐

Maximum RMS current when the frequency is above 64 Hz before tripTrip time

Minimum RMS current when voltage is between 70% and 88% before trip; Not specifiedRide through timeTrip timeMinimum RMS current when voltage is between 50% and 70% before trip; Not specifiedRide through timeTrip timeMinimum RMS current when voltage is below 50% before trip; Not specified

Trip time

Ride through time

SRD V1.1 Range

SRD V1.1 Range

SRD V1.1 Compliant?

UNITS

Trip time

DESCRIPTION

DESCRIPTIONSRD V1.1 Compliant?

UNITS

Page  3

Page 12: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix B: Grid Support Utility Interactive  Worksheet

Min Max Min Max Min Max82 98 82 98 % VNOMINAL 94 Y

0 53 0 53% Q (Var Injection)

44 Y

97 100 97 100 % VNOMINAL 97 Y‐53 53 ‐53 53 % Q (0 VAr) 0 Y100 103 100 103 % VNOMINAL 103 Y‐53 53 ‐53 53 % Q (0 VAr) 0 Y102 118 102 108 % VNOMINAL 106 Y

‐53 0 ‐53 0% Q (Var 

Absorption)‐44 Y

1 90 1 90 Sec. 10 YReactive Reactive Reactive Reactive Unitless Reactive Y

Min Max Min Max Min Max1 100 1 100 % PRATED/sec. 100 Y0.1 100 0.1 100 % PRATED/sec. 0.33 Y

Min Max Min Max Min Max1.12 100 1.12 100 % PPRATED/V ‐25 Y105 109 105 109 % Vnom 106 Y107 110 107 110 % Vnom 110 Y1 90 1 90 Sec. 10 Y

unitlessPrated or Ppre‐

disturbanceY

Min Max Min Max Min Max

0.2 0.83 0.2 0.83 %Prated/Hz ~42 Y

60.017 61 60.017 61 Hz 60.04 Y0.05 3 0.05 3 Sec. 0.5 Y

unitlessPrated or Ppre‐

disturbanceY

Response Time Response tiem (If non‐adjustable range, place default value in MIN)Stop voltage Power reduction endpoint voltage

Response time (if non‐adjustable range, place default value in MIN)Response TimePower Priortity Power Priority

V2, UVVolt‐Var_MAX

% Q2, VArs@UV_Volt‐Var_MAX

V3, OVVolt‐Var_MIN

FWRATE

Power Rate

Power Reference

Soft Start RAMPRATE

POWER RAMP RATE240

VOLT‐WATT 240

Start voltage

% Q3, VArs@OV_Volt‐Var_MIN

V4, OVVolt‐Var_MAX

% Q4, VArs@OV_Volt‐Var_MAX

Connect/Reconnect RAMPRATE 

VOLT‐VAR, Q(V)240

V1, UVVolt‐Var_MIN

% Q1, VArs@UV_Volt‐Var_MIN

Lowest voltage where Volt‐VAr starts at overvoltageVArs at lowest overvoltage Volt‐VAR point

208 ‐

Lowest voltage where Volt‐VAr starts at undervoltageVArs at lowest undervoltage Volt‐VAR point (‐53% for aggregate generating facility >15 kW, ‐44% for aggregate generating facility <= 15 kW)Highest voltage where Volt‐VAr finish at undervoltageVArs at highest undervoltage Volt‐VAR point

Percentage of nominal generated power per second "Ramp Rate"

DESCRIPTION

208 ‐ SRD V1.1 Range

SRD V1.1 Compliant?

UNITS DESCRIPTION

Highest voltage where Volt‐VAr finish at overvoltageVVArs at highest overvoltage Volt‐VAR point (53% for aggregate generating faility  >15 kW, 44% for aggregate generating facility <= 15 kW)

SRD V1.1 Range

Percentage of power reduction per volt "Volt‐Watt rate"

208 ‐ SRD V1.1 Range

SRD V1.1 Compliant?

UNITS

Percentage of nominal generated power per second "Ramp Rate"

UNITS

Power Reference Prated Prated

SRD V1.1 Compliant?

Power reduction starting voltage

DESCRIPTION

Active power output

Power reduction Starting Frequency (Based on dbOF = 0.036 Hz)

Active power output

Response tiem (if non‐adjustable range, place default value in MIN)

METHODS FOR APPLYING SETPOINTS

FREQUENCY‐WATT 240 208 ‐

UNITSSRD V1.1 Range

SRD V1.1 Compliant?

DESCRIPTION

Minimum percentage of power reduction per hertz "frequency‐watt rate" (based on kOF = 0.04)

Prated Prated

Freq adjustment range at Start frequencyResponse Time

Page  4

Page 13: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix B: Grid Support Utility Interactive  Worksheet

Installers will use the Enphase Installer Tool Kit to connect to Enphase's cloud based Enlighten system to install one of the following grid profiles.HEI SRD V1.1 O+M+H CSS w/VWHEI SRD V1.1 O+M+H CSS no VWHEI SRD V1.1 O+M+H CGS w/VWHEI SRD V1.1 O+M+H CGS no VWHEI SRD V1.1 L+M CSS w/VWHEI SRD V1.1 L+M CSS no VWHEI SRD V1.1 L+M CGS w/VWHEI SRD V1.1 L+M CGS no VW

O+M+H = Oahu+Maui+HawaiiL+M = Lanai+MolokaiCSS = Customer Self SupplyCGS = Customer Grid Supplyw/VV = Volt‐Watt function enabledno VV = Volt‐Watt function  disabled

If customization of any of these grid profiles is required, the installer must contact Enphase Customer Service.

Page  5

Page 14: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix C: Grid Support Utility Interactive  Worksheet

‐ ‐

‐ ‐

‐ ‐‐ ‐‐ ‐‐ ‐‐ ‐

‐ ‐

Min Max25 79.553 64

‐ IQ7Xunitless

Volts 50 % < V  120 %at 240 V: 2.4 Vat 208 V: 2.08 V

Amps 100 % N/A

10

DC voltage  ratingMaximum power point track range

Displacement 20 % < P  100 % 2

s 100 ms to 600 s 33*

Hz 50 to 66 Hz 0.1 HzWatts 20 % < P  100 % N/A

Model #IQ7X‐96‐x‐US

where x=2, 5, B or ACM

Certification / Self‐Certification Certified

Manufacturer Enphase Energy Inc

Active PowerReactive PowerPower Factor

Time

UNITS

INVERTER DC (INPUT) SIDE

NRTL Name UL LLCCertificate # 20180307‐E341165

VAR 20 % < Q  100 % 5

*two line cycles or 1% of setting, whichever is larger

RATINGRANGE DESCRIPTION

Provide MSA for each model represented

±0.01•Vn

Not specified

Not specified

Report # E341165‐20171030

 SA Certification Date 2018‐June‐26

Responsible Engineer Bruce Mahernholz

VALUE DESCRIPTIONUNITSRATING

MANUFACTURER's STATED ACCURACY

VALUE

Model

Voltage, RMS

Current, RMSFrequency

Max input short‐circuit current

VDC‐ rating VoltsVoltsAmps

VMPPT‐RANGE

IDC max

GENERAL

NOTESVALUE INFORMATION

Complete all fields highlighted in red.

Firmware version v02.14.02

Page  1

Page 15: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix C: Grid Support Utility Interactive  Worksheet

UNITSVoltsVolts

NumberVA

AmpsAmps

Min Max Min Max Min Max

Underexcited, Inductive, Absorbing ‐70 100 ‐70 100 % ‐85% to 100% ‐

Overexcited, Capacitive, Injecting 100 70 100 70 % 100% to 85% ‐

Underexcited, Inductive, Absorbing ‐70 100 ‐70 100 % ‐90% to 100% Y

Overexcited, Capacitive, Injecting 100 70 100 70 % 100% to 90% Y

Nominal Voltage Phase‐phaseNumber of electrical phases

3151.31

>15 kW

<=15 kWCapacitive (var injection) power factor to Reactive (var absorption) power factor range.  RULE 14H  Default PF = ‐0.95 (Absorbing) for self certification purposes.

Capacitive (var injection) power factor to Reactive (var absorption) power factor range.  RULE 14H  Default PF = ‐0.95 (Absorbing) for self certification purposes.

POUTINOMINAL‐OUTPUT

DESCRIPTION

INVERTER AC (OUTPUT) SIDE

FIXED POWER FACTOR208 ‐

VAC‐NOMINAL(Phase‐phase) 240 208 ‐Number of Phases 1 1 ‐

240

Rated Power OutputNominal current per phaseMaximum output current at lowest operating voltage

SRD V1.1 Range

SRD V1.1 Compliant?

Nominal Voltage Phase‐neutral (if neutral available)

IMAXIMUM‐OUTPUT  (at Vlow) 1.46

VALUE RATINGVAC‐NOMINAL(Phase‐neutral) N/A N/A ‐

3151.511.67

DESCRIPTIONUNITS

Page  2

Page 16: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix C: Grid Support Utility Interactive  Worksheet

Min Max Min Max Min MaxIRMS_MAX@VRT( V = 120%) Amps ‐ ‐

tTRIP (V > 120%) 0.16 0.16 0.16 0.16 Sec. 0.16 YIRMS_MAX@VRT(V = 110%) Amps ‐ ‐

tRIDE‐THROUGH (110% < V  120%) 0.80 12.8 0.80 12.8 Sec. 0.92 YtTRIP (110% < V  120%) 1.00 13.0 1.00 13.0 Sec. 1 YIRMS_MAX@(V = 109%) Amps ‐ ‐

IRMS@(V = 100%) Amps ‐ ‐IRMS_MIN@(V = 90%) Amps ‐ ‐

IRMS_MIN@VRT(V = 75%) Amps ‐ ‐tRIDE‐THROUGH (70%  V  88%) 20 49.8 20 49.8 Sec. 20 Y

tTRIP (70%  V  88%) 21.0 50.0 21.0 50.0 Sec. 21 YIRMS_MIN@VRT(V = 70%) Amps ‐ ‐

tRIDE‐THROUGH (50%  V < 70%) 10.00 49.8 10.00 49.8 Sec. 10‐20 YtTRIP (50%  V < 70%) 11.00 50.0 11.00 50.0 Sec. 11‐21 Y

IRMS_MIN@VRT(V = 50%) Amps ‐ ‐tRIDE‐THROUGH (V <  50%) 0.30 20.8 0.30 20.8 Sec. ‐ ‐

tTRIP (V < 50%) 0.50 21.0 0.50 21.0 Sec. 2 Y

Min Max Min Max Min MaxIRMS_MAX@FRT(f = 64Hz) Amps ‐ ‐

tTRIP (f > 64 Hz) 0.16 1000.0 0.16 1000.0 Sec. 0.16 YIRMS_MAX@FRT(63 Hz < f  64Hz) Amps ‐ ‐tRIDE‐THROUGH (63 Hz< f  64 Hz) 20.00 999.8 20.00 999.8 Sec. 20 Y

tTRIP (63 Hz < f  64 Hz) 21 1000.0 21 1000.0 Sec. 21 YIRMS_MAX@ f = 63 Hz Amps ‐ ‐

IRMS@ f = 60 Hz Amps ‐ ‐IRMS_MIN@ f = 57 Hz Amps ‐ ‐

IRMS_MIN@FRT(56 Hz  f < 57 Hz) Amps ‐ ‐tRIDE‐THROUGH (56 Hz  f < 57 Hz) 20.00 999.8 20.00 999.8 Sec. 20 Y

tTRIP (56 Hz  f < 57 Hz) 21 1000.0 21 1000.0 Sec. 21 YIRMS_MIN@FRT(f < 56 Hz) Amps ‐ ‐

tTRIP (f < 56 Hz) 0.16 1000 0.16 1000 Sec. 0.16 Y

Nominal1.311.311.31

VOLTAGE RIDE‐THROUGH

UF1

UF2

OF2

OF1

OV2

1.31

N/A

N/A

N/A

Nominal1.201.311.46

‐240 208

N/A

N/A

N/A

N/A

N/A

FREQUENCY RIDE‐THROUGH

1.31

OV1

UV3

UV2

UV1

N/A

N/A

1.391.51

Minimum RMS current when voltage is 90%

Maximum RMS current when voltage goes above to 120% before trip; Not specifiedTrip timeMaximum RMS current when voltage is between 110% and 120% before trip; Not specifiedRide through timeTrip timeMaximum RMS current when voltage is 109%RMS current when voltage is 100%

1.67

1.31

1.31Trip time

1.51

1.511.511.511.51

1.51

Ride Through TimeTrip timeMaximum RMS current when the frequency is 63 HzRMS current when the frequency is 60 HzMinimum RMS current when the frequency is 57 HzMinimum RMS current when the frequency is between 56 and 57 Hz before tripRide Through Time

Minimum RMS current when the frequency is below 56 Hz before trip

Maximum RMS current when the frequency is between 63 and 64 Hz before trip

1.51

240 208 ‐

Maximum RMS current when the frequency is above 64 Hz before tripTrip time

Minimum RMS current when voltage is between 70% and 88% before trip; Not specifiedRide through timeTrip timeMinimum RMS current when voltage is between 50% and 70% before trip; Not specifiedRide through timeTrip timeMinimum RMS current when voltage is below 50% before trip; Not specified

Trip time

Ride through time

SRD V1.1 Range

SRD V1.1 Range

SRD V1.1 Compliant?

UNITS

Trip time

DESCRIPTION

DESCRIPTIONSRD V1.1 Compliant?

UNITS

Page  3

Page 17: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix C: Grid Support Utility Interactive  Worksheet

Min Max Min Max Min Max82 98 82 98 % VNOMINAL 94 Y

0 53 0 53% Q (Var Injection)

44 Y

97 100 97 100 % VNOMINAL 97 Y‐53 53 ‐53 53 % Q (0 VAr) 0 Y100 103 100 103 % VNOMINAL 103 Y‐53 53 ‐53 53 % Q (0 VAr) 0 Y102 118 102 108 % VNOMINAL 106 Y

‐53 0 ‐53 0% Q (Var 

Absorption)‐44 Y

1 90 1 90 Sec. 10 YReactive Reactive Reactive Reactive Unitless Reactive Y

Min Max Min Max Min Max1 100 1 100 % PRATED/sec. 100 Y0.1 100 0.1 100 % PRATED/sec. 0.33 Y

Min Max Min Max Min Max1.12 100 1.12 100 % PPRATED/V ‐25 Y105 109 105 109 % Vnom 106 Y107 110 107 110 % Vnom 110 Y1 90 1 90 Sec. 10 Y

unitlessPrated or Ppre‐

disturbanceY

Min Max Min Max Min Max

0.2 0.83 0.2 0.83 %Prated/Hz ~42 Y

60.017 61 60.017 61 Hz 60.04 Y0.05 3 0.05 3 Sec. 0.5 Y

unitlessPrated or Ppre‐

disturbanceY

Response Time Response tiem (If non‐adjustable range, place default value in MIN)Stop voltage Power reduction endpoint voltage

Response time (if non‐adjustable range, place default value in MIN)Response TimePower Priortity Power Priority

V2, UVVolt‐Var_MAX

% Q2, VArs@UV_Volt‐Var_MAX

V3, OVVolt‐Var_MIN

FWRATE

Power Rate

Power Reference

Soft Start RAMPRATE

POWER RAMP RATE240

VOLT‐WATT 240

Start voltage

% Q3, VArs@OV_Volt‐Var_MIN

V4, OVVolt‐Var_MAX

% Q4, VArs@OV_Volt‐Var_MAX

Connect/Reconnect RAMPRATE 

VOLT‐VAR, Q(V)240

V1, UVVolt‐Var_MIN

% Q1, VArs@UV_Volt‐Var_MIN

Lowest voltage where Volt‐VAr starts at overvoltageVArs at lowest overvoltage Volt‐VAR point

208 ‐

Lowest voltage where Volt‐VAr starts at undervoltageVArs at lowest undervoltage Volt‐VAR point (‐53% for aggregate generating facility >15 kW, ‐44% for aggregate generating facility <= 15 kW)Highest voltage where Volt‐VAr finish at undervoltageVArs at highest undervoltage Volt‐VAR point

Percentage of nominal generated power per second "Ramp Rate"

DESCRIPTION

208 ‐ SRD V1.1 Range

SRD V1.1 Compliant?

UNITS DESCRIPTION

Highest voltage where Volt‐VAr finish at overvoltageVVArs at highest overvoltage Volt‐VAR point (53% for aggregate generating faility  >15 kW, 44% for aggregate generating facility <= 15 kW)

SRD V1.1 Range

Percentage of power reduction per volt "Volt‐Watt rate"

208 ‐ SRD V1.1 Range

SRD V1.1 Compliant?

UNITS

Percentage of nominal generated power per second "Ramp Rate"

UNITS

Power Reference Prated Prated

SRD V1.1 Compliant?

Power reduction starting voltage

DESCRIPTION

Active power output

Power reduction Starting Frequency (Based on dbOF = 0.036 Hz)

Active power output

Response tiem (if non‐adjustable range, place default value in MIN)

METHODS FOR APPLYING SETPOINTS

FREQUENCY‐WATT 240 208 ‐

UNITSSRD V1.1 Range

SRD V1.1 Compliant?

DESCRIPTION

Minimum percentage of power reduction per hertz "frequency‐watt rate" (based on kOF = 0.04)

Prated Prated

Freq adjustment range at Start frequencyResponse Time

Page  4

Page 18: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix C: Grid Support Utility Interactive  Worksheet

Installers will use the Enphase Installer Tool Kit to connect to Enphase's cloud based Enlighten system to install one of the following grid profiles.HEI SRD V1.1 O+M+H CSS w/VWHEI SRD V1.1 O+M+H CSS no VWHEI SRD V1.1 O+M+H CGS w/VWHEI SRD V1.1 O+M+H CGS no VWHEI SRD V1.1 L+M CSS w/VWHEI SRD V1.1 L+M CSS no VWHEI SRD V1.1 L+M CGS w/VWHEI SRD V1.1 L+M CGS no VW

O+M+H = Oahu+Maui+HawaiiL+M = Lanai+MolokaiCSS = Customer Self SupplyCGS = Customer Grid Supplyw/VV = Volt‐Watt function enabledno VV = Volt‐Watt function  disabled

If customization of any of these grid profiles is required, the installer must contact Enphase Customer Service.

Page  5

Page 19: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix D: Grid Support Utility Interactive  Worksheet

RATING

Min Max Min Maxunitless

20 60 Volts22 40 Volts

Amps

Complete all fields highlighted in red.

Firmware version v02.14.02

GENERAL

Report # E341165‐20171030

 SA Certification Date 2018‐June‐26

Responsible Engineer Bruce Mahernholz

VALUERATING

Max input short‐circuit current

RATINGDESCRIPTION

DC voltage  ratingMaximum power point track range

Power Factor

NOTESVALUE INFORMATION

VMPPT‐RANGE

IDC max

DESCRIPTION

±0.01•Vn

Not specified

VDC‐ rating

Model IQ7PD‐72‐2‐US

Time

INVERTER DC (INPUT) SIDE

UNITS

20 % < P  100 % N/A

‐ IQ7PD‐72‐2‐USunitless

Volts 50 % < V  120 % at 240 V: 2.4 Vat 208 V: 2.08 V

Amps 100 % N/A

NRTL Name UL LLCCertificate # 20180307‐E341165

VAR 20 % < Q  100 % 5

RANGE

Displacement 20 % < P  100 % 2

Hz 50 to 66 Hz 0.1 HzWatts

MANUFACTURER's STATED ACCURACY

VALUE

Model

Voltage, RMS

Current, RMSFrequency

Active PowerReactive Power

Model # IQ7PD‐72‐2‐US

Certification / Self‐Certification Certified

Manufacturer Enphase Energy Inc

Not specified

Provide MSA for each model represented

*two line cycles or 1% of setting, whichever is largers 100 ms to 600 s 33*

UNITS

10

Page  1

Page 20: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix D: Grid Support Utility Interactive  Worksheet

UNITSunitlessVoltsVolts

NumberVA

AmpsAmps

Min Max Min Max Min Max

Underexcited, Inductive, Absorbing ‐70 100 ‐70 100 % ‐85% to 100% ‐

Overexcited, Capacitive, Injecting 100 70 100 70 % 100% to 85% ‐

Underexcited, Inductive, Absorbing ‐70 100 ‐70 100 % ‐90% to 100% Y

Overexcited, Capacitive, Injecting 100 70 100 70 % 100% to 90% Y

DESCRIPTION

INVERTER AC (OUTPUT) SIDE

UNITSSRD V1.1 

Compliant?

Model IQ7PD‐72‐2‐USNominal Voltage Phase‐neutral (if neutral available)

IMAXIMUM‐OUTPUT  (at Vlow) 0.90

VALUE RATING

VAC‐NOMINAL(Phase‐neutral) N/A N/A

DESCRIPTION

Rated Power OutputNominal current per phaseMaximum output current at lowest operating voltage

SRD V1.1 Range

1900.921.03

1900.80

FIXED POWER FACTOR208

VAC‐NOMINAL(Phase‐phase) 240 208Number of Phases 1 1

240

POUTINOMINAL‐OUTPUT

Capacitive (var injection) power factor to Reactive (var absorption) power factor range.  RULE 14H  Default PF = ‐0.95 (Absorbing) for self certification purposes.

Capacitive (var injection) power factor to Reactive (var absorption) power factor range.  RULE 14H  Default PF = ‐0.95 (Absorbing) for self certification purposes.

>15 kW

<=15 kW

Nominal Voltage Phase‐phaseNumber of electrical phases

Page  2

Page 21: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix D: Grid Support Utility Interactive  Worksheet

Min Max Min MaxIRMS_MAX@VRT( V = 120%) Amps ‐ ‐

tTRIP (V > 120%) 0.16 0.16 0.16 0.16 Sec. 0.16 YIRMS_MAX@VRT(V = 110%) Amps ‐ ‐

tRIDE‐THROUGH (110% < V  120%) 0.80 12.8 0.80 12.8 Sec. 0.92 YtTRIP (110% < V  120%) 1.00 13.0 1.00 13.0 Sec. 1 YIRMS_MAX@(V = 109%) Amps ‐ ‐

IRMS@(V = 100%) Amps ‐ ‐IRMS_MIN@(V = 90%) Amps ‐ ‐

IRMS_MIN@VRT(V = 75%) Amps ‐ ‐tRIDE‐THROUGH (70%  V  88%) 20 49.8 20 49.8 Sec. 20 Y

tTRIP (70%  V  88%) 21.0 50.0 21.0 50.0 Sec. 21 YIRMS_MIN@VRT(V = 70%) Amps ‐ ‐

tRIDE‐THROUGH (50%  V < 70%) 10.00 49.8 10.00 49.8 Sec. 10‐20 YtTRIP (50%  V < 70%) 11.00 50.0 11.00 50.0 Sec. 11‐21 Y

IRMS_MIN@VRT(V = 50%) Amps ‐ ‐tRIDE‐THROUGH (V <  50%) 0.30 20.8 0.30 20.8 Sec. ‐ ‐

tTRIP (V < 50%) 0.50 21.0 0.50 21.0 Sec. 2 Y

Min Max Min Max Min MaxIRMS_MAX@FRT(f = 64Hz) Amps ‐ ‐

tTRIP (f > 64 Hz) 0.16 1000.0 0.16 1000.0 Sec. 0.16 YIRMS_MAX@FRT(63 Hz < f  64Hz) Amps ‐ ‐tRIDE‐THROUGH (63 Hz< f  64 Hz) 20.00 999.8 20.00 999.8 Sec. 20 Y

tTRIP (63 Hz < f  64 Hz) 21 1000.0 21 1000.0 Sec. 21 YIRMS_MAX@ f = 63 Hz Amps ‐ ‐

IRMS@ f = 60 Hz Amps ‐ ‐IRMS_MIN@ f = 57 Hz Amps ‐ ‐

IRMS_MIN@FRT(56 Hz  f < 57 Hz) Amps ‐ ‐tRIDE‐THROUGH (56 Hz  f < 57 Hz) 20.00 999.8 20.00 999.8 Sec. 20 Y

tTRIP (56 Hz  f < 57 Hz) 21 1000.0 21 1000.0 Sec. 21 YIRMS_MIN@FRT(f < 56 Hz) Amps ‐ ‐

tTRIP (f < 56 Hz) 0.16 1000 0.16 1000 Sec. 0.16 Y

SRD V1.1 Compliant?

UNITS

UNITS

Minimum RMS current when voltage is between 70% and 88% before trip; Not specifiedRide through timeTrip timeMinimum RMS current when voltage is between 50% and 70% before trip; Not specifiedRide through timeTrip timeMinimum RMS current when voltage is below 50% before trip; Not specified

SRD V1.1 Range

SRD V1.1 Range

SRD V1.1 Compliant?

DESCRIPTION

DESCRIPTION

Ride Through TimeTrip timeMaximum RMS current when the frequency is 63 HzRMS current when the frequency is 60 HzMinimum RMS current when the frequency is 57 HzMinimum RMS current when the frequency is between 56 and 57 Hz before tripRide Through Time

Minimum RMS current when the frequency is below 56 Hz before tripTrip time

Trip time

Maximum RMS current when the frequency is between 63 and 64 Hz before trip

N/A

N/A

Maximum RMS current when voltage goes above to 120% before trip; Not specifiedTrip time

Trip timeMaximum RMS current when voltage is 109%RMS current when voltage is 100%

1.03

N/A

Maximum RMS current when voltage is between 110% and 120% before trip; Not specifiRide through time

240 208

Maximum RMS current when the frequency is above 64 Hz before tripTrip time

OV1

0.800.90

0.80

0.80

1.31

0.92

0.920.92

0.92

Minimum RMS current when voltage is 90%N/A

N/A

N/ARide through time

Trip time

1.51

0.920.92

FREQUENCY RIDE‐THROUGH

0.80

240 208

UF1

UF2

OF2

OF1

OV2

Nominal0.800.800.80

VOLTAGE RIDE‐THROUGH

UV3

UV2

UV1

N/A

N/A

0.840.92

N/A

N/A

Nominal0.73

Page  3

Page 22: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix D: Grid Support Utility Interactive  Worksheet

Min Max Min Max Min Max82 98 82 98 % VNOMINAL 94 Y

0 53 0 53% Q (Var Injection)

44 Y

97 100 97 100 % VNOMINAL 97 Y‐53 53 ‐53 53 % Q (0 VAr) 0 Y100 103 100 103 % VNOMINAL 103 Y‐53 53 ‐53 53 % Q (0 VAr) 0 Y102 118 102 108 % VNOMINAL 106 Y

‐53 0 ‐53 0% Q (Var 

Absorption)‐44 Y

1 90 1 90 Sec. 10 YReactive Reactive Reactive Reactive Unitless Reactive Y

Min Max Min Max Min Max1 100 1 100 % PRATED/sec. 100 Y0.1 100 0.1 100 % PRATED/sec. 0.33 Y

Min Max Min Max Min Max1.12 100 1.12 100 % PPRATED/V ‐25 Y105 109 105 109 % Vnom 106 Y107 110 107 110 % Vnom 110 Y1 90 1 90 Sec. 10 Y

unitlessPrated or Ppre‐

disturbanceY

Min Max Min Max Min Max

0.2 0.83 0.2 0.83 %Prated/Hz ~42 Y

60.017 61 60.017 61 Hz 60.04 Y0.05 3 0.05 3 Sec. 0.5 Y

unitlessPrated or Ppre‐

disturbanceY

Active power output

Power reduction Starting Frequency (Based on dbOF = 0.036 Hz)

Active power output

Response tiem (if non‐adjustable range, place default value in MIN)

METHODS FOR APPLYING SETPOINTS

FREQUENCY‐WATT 240 208 0

UNITSSRD V1.1 Range

SRD V1.1 Compliant?

DESCRIPTION

Minimum percentage of power reduction per hertz "frequency‐watt rate" (based on kOF = 0.04)

Prated Prated

Freq adjustment range at Start frequencyResponse Time

Power Reference Prated Prated

FWRATE

DESCRIPTION

Percentage of power reduction per volt "Volt‐Watt rate"

208 SRD V1.1 Range

SRD V1.1 Compliant?

UNITS

Percentage of nominal generated power per second "Ramp Rate"

Highest voltage where Volt‐VAr finish at overvoltageVVArs at highest overvoltage Volt‐VAR point (53% for aggregate generating faility  >15 kW, 44% for aggregate generating facility <= 15 kW)

SRD V1.1 Range

SRD V1.1 Compliant?

Lowest voltage where Volt‐VAr starts at undervoltage

Power Rate

208

208

POWER RAMP RATE240

VOLT‐WATT 240

Start voltage

% Q3, VArs@OV_Volt‐Var_MIN

V4, OVVolt‐Var_MAX

% Q4, VArs@OV_Volt‐Var_MAX

Connect/Reconnect RAMPRATE 

VOLT‐VAR, Q(V)240

VArs at lowest undervoltage Volt‐VAR point (‐53% for aggregate generating facility >15 kW, ‐44% for aggregate generating facility <= 15 kW)Highest voltage where Volt‐VAr finish at undervoltage

UNITS

Percentage of nominal generated power per second "Ramp Rate"

DESCRIPTION

SRD V1.1 Range

SRD V1.1 Compliant?

UNITS DESCRIPTION

Power reduction starting voltage

V1, UVVolt‐Var_MIN

% Q1, VArs@UV_Volt‐Var_MIN

Lowest voltage where Volt‐VAr starts at overvoltageVArs at lowest overvoltage Volt‐VAR point

VArs at highest undervoltage Volt‐VAR point

Power Reference

Soft Start RAMPRATE

Response Time Response tiem (If non‐adjustable range, place default value in MIN)Stop voltage Power reduction endpoint voltage

Response time (if non‐adjustable range, place default value in MIN)Response TimePower Priortity Power Priority

V2, UVVolt‐Var_MAX

% Q2, VArs@UV_Volt‐Var_MAX

V3, OVVolt‐Var_MIN

Page  4

Page 23: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix D: Grid Support Utility Interactive  Worksheet

Installers will use the Enphase Installer Tool Kit to connect to Enphase's cloud based Enlighten system to install one of the following grid profiles.HEI SRD V1.1 O+M+H CSS w/VWHEI SRD V1.1 O+M+H CSS no VWHEI SRD V1.1 O+M+H CGS w/VWHEI SRD V1.1 O+M+H CGS no VWHEI SRD V1.1 L+M CSS w/VWHEI SRD V1.1 L+M CSS no VWHEI SRD V1.1 L+M CGS w/VWHEI SRD V1.1 L+M CGS no VW

O+M+H = Oahu+Maui+HawaiiL+M = Lanai+MolokaiCSS = Customer Self SupplyCGS = Customer Grid Supplyw/VV = Volt‐Watt function enabledno VV = Volt‐Watt function  disabled

If customization of any of these grid profiles is required, the installer must contact Enphase Customer Service.

Page  5

Page 24: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix E: Grid Support Utility Interactive  Worksheet

Min Max Min Maxunitless

20 60 Volts31 50 Volts

Amps10

RATINGDESCRIPTION

DC voltage  ratingMaximum power point track range

Power Factor

Time

INVERTER DC (INPUT) SIDE

*two line cycles or 1% of setting, whichever is largers 100 ms to 600 s 33*

UNITS

Model IQ7PD‐84‐2‐US

Complete all fields highlighted in red.

Firmware version v02.14.02

GENERAL

Report # E341165‐20171030

 SA Certification Date 2018‐June‐26

Responsible Engineer Bruce Mahernholz

VALUERATING

Max input short‐circuit current

NOTESVALUE INFORMATION

VMPPT‐RANGE

IDC max

VDC‐ rating

MANUFACTURER's STATED ACCURACY

VALUE

Model

Voltage, RMS

Current, RMSFrequency

Active PowerReactive Power

UNITS

20 % < P  100 % N/A

‐ IQ7PD‐84‐2‐USunitless

Volts 50 % < V  120 %at 240 V: 2.4 Vat 208 V: 2.08 V

Amps 100 % N/A

NRTL Name UL LLCCertificate # 20180307‐E341165

VAR 20 % < Q  100 % 5

RATINGRANGE DESCRIPTION

Provide MSA for each model represented

±0.01•Vn

Not specified

Not specified

Displacement 20 % < P  100 % 2

Hz 50 to 66 Hz 0.1 HzWatts

Model # IQ7PD‐84‐2‐US

Certification / Self‐Certification Certified

Manufacturer Enphase Energy Inc

Page  1

Page 25: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix E: Grid Support Utility Interactive  Worksheet

UNITSunitlessVoltsVolts

NumberVA

AmpsAmps

Min Max Min Max Min Max

Underexcited, Inductive, Absorbing ‐70 100 ‐70 100 % ‐85% to 100% ‐

Overexcited, Capacitive, Injecting 100 70 100 70 % 100% to 85% ‐

Underexcited, Inductive, Absorbing ‐70 100 ‐70 100 % ‐90% to 100% Y

Overexcited, Capacitive, Injecting 100 70 100 70 % 100% to 90% Y

Model IQ7PD‐84‐2‐USDESCRIPTION

INVERTER AC (OUTPUT) SIDE

UNITSSRD V1.1 

Compliant?

Nominal Voltage Phase‐neutral (if neutral available)

IMAXIMUM‐OUTPUT  (at Vlow) 0.99

VALUE RATING

VAC‐NOMINAL(Phase‐neutral) N/A N/A

DESCRIPTION

1.011.15

Rated Power OutputNominal current per phaseMaximum output current at lowest operating voltage

SRD V1.1 Range

240

POUTINOMINAL‐OUTPUT

210

Capacitive (var injection) power factor to Reactive (var absorption) power factor range.  RULE 14H  Default PF = ‐0.95 (Absorbing) for self certification purposes.

Capacitive (var injection) power factor to Reactive (var absorption) power factor range.  RULE 14H  Default PF = ‐0.95 (Absorbing) for self certification purposes.

Nominal Voltage Phase‐phaseNumber of electrical phases

2100.88

>15 kW

<=15 kW

FIXED POWER FACTOR208

VAC‐NOMINAL(Phase‐phase) 240 208Number of Phases 1 1

Page  2

Page 26: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix E: Grid Support Utility Interactive  Worksheet

Min Max Min MaxIRMS_MAX@VRT( V = 120%) Amps ‐ ‐

tTRIP (V > 120%) 0.16 0.16 0.16 0.16 Sec. 0.16 YIRMS_MAX@VRT(V = 110%) Amps ‐ ‐

tRIDE‐THROUGH (110% < V  120%) 0.80 12.8 0.80 12.8 Sec. 0.92 YtTRIP (110% < V  120%) 1.00 13.0 1.00 13.0 Sec. 1 YIRMS_MAX@(V = 109%) Amps ‐ ‐

IRMS@(V = 100%) Amps ‐ ‐IRMS_MIN@(V = 90%) Amps ‐ ‐

IRMS_MIN@VRT(V = 75%) Amps ‐ ‐tRIDE‐THROUGH (70%  V  88%) 20 49.8 20 49.8 Sec. 20 Y

tTRIP (70%  V  88%) 21.0 50.0 21.0 50.0 Sec. 21 YIRMS_MIN@VRT(V = 70%) Amps ‐ ‐

tRIDE‐THROUGH (50%  V < 70%) 10.00 49.8 10.00 49.8 Sec. 10‐20 YtTRIP (50%  V < 70%) 11.00 50.0 11.00 50.0 Sec. 11‐21 Y

IRMS_MIN@VRT(V = 50%) Amps ‐ ‐tRIDE‐THROUGH (V <  50%) 0.30 20.8 0.30 20.8 Sec. ‐ ‐

tTRIP (V < 50%) 0.50 21.0 0.50 21.0 Sec. 2 Y

Min Max Min Max Min MaxIRMS_MAX@FRT(f = 64Hz) Amps ‐ ‐

tTRIP (f > 64 Hz) 0.16 1000.0 0.16 1000.0 Sec. 0.16 YIRMS_MAX@FRT(63 Hz < f  64Hz) Amps ‐ ‐tRIDE‐THROUGH (63 Hz< f  64 Hz) 20.00 999.8 20.00 999.8 Sec. 20 Y

tTRIP (63 Hz < f  64 Hz) 21 1000.0 21 1000.0 Sec. 21 YIRMS_MAX@ f = 63 Hz Amps ‐ ‐

IRMS@ f = 60 Hz Amps ‐ ‐IRMS_MIN@ f = 57 Hz Amps ‐ ‐

IRMS_MIN@FRT(56 Hz  f < 57 Hz) Amps ‐ ‐tRIDE‐THROUGH (56 Hz  f < 57 Hz) 20.00 999.8 20.00 999.8 Sec. 20 Y

tTRIP (56 Hz  f < 57 Hz) 21 1000.0 21 1000.0 Sec. 21 YIRMS_MIN@FRT(f < 56 Hz) Amps ‐ ‐

tTRIP (f < 56 Hz) 0.16 1000 0.16 1000 Sec. 0.16 Y

DESCRIPTION

DESCRIPTIONSRD V1.1 

Compliant?UNITS

UNITS

Minimum RMS current when voltage is between 70% and 88% before trip; Not specifiedRide through timeTrip timeMinimum RMS current when voltage is between 50% and 70% before trip; Not specifiedRide through timeTrip timeMinimum RMS current when voltage is below 50% before trip; Not specified

Trip time

SRD V1.1 Range

SRD V1.1 Range

SRD V1.1 Compliant?

1.01

240 208

Maximum RMS current when the frequency is above 64 Hz before tripTrip time

Trip time

1.31

Ride through time

Trip time

1.51

1.011.011.011.01

1.01

Ride Through TimeTrip timeMaximum RMS current when the frequency is 63 HzRMS current when the frequency is 60 HzMinimum RMS current when the frequency is 57 HzMinimum RMS current when the frequency is between 56 and 57 Hz before tripRide Through Time

Minimum RMS current when the frequency is below 56 Hz before trip

Maximum RMS current when the frequency is between 63 and 64 Hz before trip

0.88

0.88

Minimum RMS current when voltage is 90%

Maximum RMS current when voltage goes above to 120% before trip; Not specifiedTrip timeMaximum RMS current when voltage is between 110% and 120% before trip; Not specifiRide through timeTrip timeMaximum RMS current when voltage is 109%RMS current when voltage is 100%

1.15N/A

N/A

N/A

N/A

N/A

FREQUENCY RIDE‐THROUGH

0.88

OV1

240 208

UV3

UV2

UV1

N/A

N/A

0.931.01

N/A

N/A

N/A

Nominal0.080.880.99

UF1

UF2

OF2

OF1

OV2

Nominal0.880.880.88

VOLTAGE RIDE‐THROUGH

Page  3

Page 27: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix E: Grid Support Utility Interactive  Worksheet

Min Max Min Max Min Max82 98 82 98 % VNOMINAL 94 Y

0 53 0 53% Q (Var Injection)

44 Y

97 100 97 100 % VNOMINAL 97 Y‐53 53 ‐53 53 % Q (0 VAr) 0 Y100 103 100 103 % VNOMINAL 103 Y‐53 53 ‐53 53 % Q (0 VAr) 0 Y102 118 102 108 % VNOMINAL 106 Y

‐53 0 ‐53 0% Q (Var 

Absorption)‐44 Y

1 90 1 90 Sec. 10 YReactive Reactive Reactive Reactive Unitless Reactive Y

Min Max Min Max Min Max1 100 1 100 % PRATED/sec. 100 Y0.1 100 0.1 100 % PRATED/sec. 0.33 Y

Min Max Min Max Min Max1.12 100 1.12 100 % PPRATED/V ‐25 Y105 109 105 109 % Vnom 106 Y107 110 107 110 % Vnom 110 Y1 90 1 90 Sec. 10 Y

unitlessPrated or Ppre‐

disturbanceY

Min Max Min Max Min Max

0.2 0.83 0.2 0.83 %Prated/Hz ~42 Y

60.017 61 60.017 61 Hz 60.04 Y0.05 3 0.05 3 Sec. 0.5 Y

unitlessPrated or Ppre‐

disturbanceY

Active power output

Power reduction Starting Frequency (Based on dbOF = 0.036 Hz)

Active power output

Response tiem (if non‐adjustable range, place default value in MIN)

METHODS FOR APPLYING SETPOINTS

FREQUENCY‐WATT 240 208 0

UNITSSRD V1.1 Range

SRD V1.1 Compliant?

DESCRIPTION

Minimum percentage of power reduction per hertz "frequency‐watt rate" (based on kOF = 0.04)

Prated Prated

Freq adjustment range at Start frequencyResponse Time

Power Reference Prated Prated

FWRATE

Power reduction starting voltage

DESCRIPTION

Percentage of power reduction per volt "Volt‐Watt rate"

208 SRD V1.1 Range

SRD V1.1 Compliant?

UNITS

Percentage of nominal generated power per second "Ramp Rate"

UNITS

Percentage of nominal generated power per second "Ramp Rate"

DESCRIPTION

208 SRD V1.1 Range

SRD V1.1 Compliant?

UNITS DESCRIPTION

Highest voltage where Volt‐VAr finish at overvoltageVVArs at highest overvoltage Volt‐VAR point (53% for aggregate generating faility  >15 kW, 44% for aggregate generating facility <= 15 kW)

SRD V1.1 Range

SRD V1.1 Compliant?

VArs at highest undervoltage Volt‐VAR point

VArs at lowest overvoltage Volt‐VAR point

Power Rate

Power Reference

Soft Start RAMPRATE

POWER RAMP RATE240

VOLT‐WATT 240

Start voltage

% Q3, VArs@OV_Volt‐Var_MIN

V4, OVVolt‐Var_MAX

% Q4, VArs@OV_Volt‐Var_MAX

Connect/Reconnect RAMPRATE 

VOLT‐VAR, Q(V)240 208

Lowest voltage where Volt‐VAr starts at undervoltageVArs at lowest undervoltage Volt‐VAR point (‐53% for aggregate generating facility >15 kW, ‐44% for aggregate generating facility <= 15 kW)Highest voltage where Volt‐VAr finish at undervoltage

V1, UVVolt‐Var_MIN

% Q1, VArs@UV_Volt‐Var_MIN

Lowest voltage where Volt‐VAr starts at overvoltage

Response Time Response tiem (If non‐adjustable range, place default value in MIN)Stop voltage Power reduction endpoint voltage

Response time (if non‐adjustable range, place default value in MIN)Response TimePower Priortity Power Priority

V2, UVVolt‐Var_MAX

% Q2, VArs@UV_Volt‐Var_MAX

V3, OVVolt‐Var_MIN

Page  4

Page 28: CERTIFICATE OF COMPLIANCE_IQ7X_HECO_SRD1.1...CERTIFICATE OF COMPLIANCE . Certificate Number . 20180626-E341165 . Report Reference . E341165-20171030 . Issue Date . 2018-June-26 . Bruce

Appendix E: Grid Support Utility Interactive  Worksheet

Installers will use the Enphase Installer Tool Kit to connect to Enphase's cloud based Enlighten system to install one of the following grid profiles.HEI SRD V1.1 O+M+H CSS w/VWHEI SRD V1.1 O+M+H CSS no VWHEI SRD V1.1 O+M+H CGS w/VWHEI SRD V1.1 O+M+H CGS no VWHEI SRD V1.1 L+M CSS w/VWHEI SRD V1.1 L+M CSS no VWHEI SRD V1.1 L+M CGS w/VWHEI SRD V1.1 L+M CGS no VW