E4-E5 Civil (Technical) Rev date: 20-04-11 BSNL India For Internal Circulation Only Page: 1 Chapter-1 STRUCTURAL DESIGN OF RCC BUILDING COMPONENTS Rajendra Mathur Dy. Dir(BS-C) 09412739 232(M) e-mail–[email protected]
Transcript
  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 1

    Chapter-1

    STRUCTURAL DESIGN

    OF

    RCC BUILDING

    COMPONENTS

    Rajendra Mathur Dy. Dir(BS-C) 09412739 232(M) e-mail–[email protected]

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 2

    Structural Design of RCC Building Components

    1.0 Introduction

    The procedure fo r ana lysis and design of a given building wil l

    depend on the t ype of building, its complexit y, the number of

    stories etc. First the architectural drawings of the building are

    studied , structural system is f ina lized sizes of structural members

    are decided and brought to the knowledge of the concerned

    architect. The p rocedure for structural design will invo lve some

    steps which will depend on the type of build ing and also its

    complexit y and the time ava ilable for structural design. Often, the

    work is required to start soon, so the steps in design are to be

    arranged in such a wa y the foundation d rawings can be taken up in

    hand within a reasonable period of time.

    Further, before start ing the structural design, the fo llowing

    informat ion o f data are requ ired: ( i) A set of architectural

    drawings;( ii) Soil Invest igation report (SIR) of soil data in lieu

    thereof; ( iii) Locat ion o f the place o r cit y in order to decide on

    wind and seismic loadings;( iv) Data fo r lift s, water tank capacit ies

    on top, special roof featu res o r loadings, etc.

    Choice of an appropriate structural system for a give n

    build ing is vital for its economy and safet y. There are two type of

    build ing systems:-

    (a) Load Bearing Masonr y Buildings.

    (b) Framed Buildings.

    (a) Load Bearing Masonry Buildings:-

    Small build ings like houses with small spans of beams, s labs

    genera lly constructed as load bearing brick walls with reinforced

    concrete slab beams. This system is su itable for building up to four

    or less stories.(as shown in f ig. below). In such build ings crushing

    strength of bricks shall be 100 kg/cm2 mi n i mu m for four stories. This

    system is adequate for vert ical loads it also serves to res ists

    horizontal loads like wind & earthquake by box act ion. Further, to

    ensure its act ion against earthquake , it is necessary to provide RCC

    Bands in horizo ntal & vertica l re inforcement in brick wall as per

    IS: 4326-1967( Indian Standards Code o f Practice for

    Earthquake Resistant Construction of Buildings.) . In some

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 3

    Buildings, 115mm thick brick walls are provided s ince these walls

    are incapable of supporting vert ica l loads, beams have to be provide

    alo ng the ir lengths to support adjo ining s lab & the weight of

    115mm thick b rick wall of upper

    storey. These beams are to rest on 230 mm thick b rick walls or

    reinforced concrete columns if required. The design of Load

    Bearing Masonr y Build ings are done as per IS:1905-1980 (Indian

    Standards Code of Practice for Structura l Safety of Buildings:

    Masonry Walls(Second Revision).

    Load bearing brick wall

    Structural system

    (b) Framed Buildings:- In these t ypes o f bu ildings re inforced concrete frames are provided

    in both p rincipal direct ions to resist vertical loads and the vertica l

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 4

    loads are transmitted to vert ical framing system i.e columns and

    Foundations. This t yp e of system is e ffect ive in res ist ing both

    vertical & horizontal loads. The brick walls are to be regarded as

    non load bearing filler walls only. This system is suitable for multi-

    storied build ing which is also effective in res ist ing horizonta l loads

    due to earthquake. In this

    system the f loor slabs, generally 100-150 mm thick with spans

    ranging from 3.0 m to 7.0 m. In certa in earthquake prone areas,

    even s ingle or double storey bu ildings a re made framed structures

    for safet y reasons. Also the s ingle storey bu ildings of large sto rey

    he ights (5 .0m or more ) , like electric substation etc. are made

    framed structure as brick walls of large heights are slender and load

    carrying capacit y of such walls reduces due to slenderness.

    Framed Structura l system

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 5

    2 .0 Basic Codes for Design . The design should be carried so as to conform to the

    following Indian code for reinforced concrete design, published b y

    the Bureau o f Indian Standards, New Delhi:

    Purpose of Codes

    National build ing codes have been formulated in different

    countries to la y down gu idelines for the design and construction of

    structure. The codes have evo lved from the co llect ive wisdom of

    expert structural engineers, ga ined over the years. These codes are

    periodica lly revised to bring them in line with current research, and

    often, current trends.

    The codes serve at least four distinct functions .

    First ly, they ensure adequate structural safet y, b y spec ifying certain

    essent ia l minimum requ irement for design.

    Secondly, the y render the task of the designer relat ively simple;

    often, the result o f sophist icate analyses is made ava ilable in the

    form of a simple formula or chart.

    Thirdly, the codes ensure a measure of consistency among different

    designers.

    Fina lly, they have some legal validit y in that they protect the

    structural designer from any liab ilit y due to structural failures that

    are caused by inadequate supervis ion and/or fau lt y mater ial and

    construct ion.

    ( i)IS 456 : 2000 – Plain and reinforced concrete – code of

    practice (fourth revision)

    ( ii) Loading Standards

    These loads to be considered fo r structural design are specified in

    the fo llowing load ing standards:

    IS 875 (Part 1 -5 ) : 1987 – Code of practice for design loads

    (other than earthquake) for buildings and structures (second

    revision)

    Part 1 : Dead loads

    Part 2 : Imposed (live) loads

    Part 3 : Wind loads

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 6

    Part 4 : Snow loads

    Part 5 : Special loads and load combinations

    IS 1893 : 2002 – Criteria for earthquake resistant design of structure (fourth revision) .

    IS 13920 : 1993 – Ductile deta iling o f reinforced concrete

    structure subject to seismic forces.

    Design Handbooks

    The Bureau of Indian standards has also published the following

    handbooks, which serve as usefu l supplement to the 1978 vers ion of

    the codes. Although the handbooks need to be updated to bring them

    in line with the recent ly revised (2000 version) o f the Code, many

    of the p rovisions continue to be va lid (especially with regard to

    structural design provis ions).

    SP 16 : 1980 – Design Aids (for Reinforced Concrete) to IS 456 :

    1978

    SP 24 : 1983 – Explanatory handbook on IS 456 : 1978

    SP 34 : 1987 – Handbooks on Concrete Reinforced and Detailing.

    General Design Consideration of IS: 456-2000.

    The general design and construction of reinforced concrete buildings shall be

    governed by the provisions of IS 456 –2000

    AIM OF DESIGN

    The aim of design is achievement of an acceptable probability that structures

    being designed shall, with an appropriate degree of safety –

    � Perform satisfactorily during their intended life.

    � Sustain all loads and deformations of normal construction & use

    � Have adequate durability

    � Have adequate resistance to the effects of misuse and fire.

    METHOD OF DESIGN –

    � Structure and structural elements shall normally be designed by Limit

    State Method.

    � Where the Limit State Method cannot be conveniently adopted, Working

    Stress Method may be used

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 7

    MINIMUM GRADE OF CONCRETE

    The minimum grade of concrete for plain & reinforced concrete shall be as per

    table below –

    26.4 Nominal Cover to Reinforcement

    26.4.1 Nominal Cover

    Nominal cover is the design depth of concrete cover to all steel

    reinforcements, including links. It is the dimension used in design and

    indicated in the drawings. It shall be not less than the diameter of the bar.

    26.4.2 Nominal Covers to Meet Durability Requirement

    Minimum values for the nominal cover of normal weight aggregate

    concrete which should be provided to all reinforcement, including links

    depending on the condition of exposure described in 8.2.3 shall be as

    given in Table 16.

    Table 16 Nominal Cover to Meet Durability Requirements

    (Clause 26.4.2)

    Exposure Nominal Concrete Cover in mm not Less Than

    Mild 20

    Moderate 30

    Severe 45

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 8

    Very Severe 50

    Extreme 75

    NOTES

    1. For main reinforcement up to 12 mm diameter bar for mild

    exposure the nominal cover may be reduced by 5 mm.

    2. Unless specified otherwise, actual concrete cover should not

    deviate from the required nominal cover by + 10 mm

    3. For exposure condition ‘severe’ and ‘very severe’, reduction of 5

    mm may be made, where concrete grade is M35 and above.

    26.4.2.1 However for a longitudinal reinforcing bar in a column nominal cover

    shall in any case not be less than 40 mm, or less than the diameter of

    such bar. In the case of columns of minimum dimension of 200 mm or

    under, whose reinforcing bars do not exceed 12 mm, a nominal cover of

    25 mm may be used.

    26.4.2.2 For footing minimum cover shall be 50 mm.

    26.4.3 Nominal Cover to Meet Specified Period of Fire Resistance

    Minimum values of nominal cover of normal-weight aggregate concrete to be

    provided to all reinforcement including links to meet specified period of fire

    resistance shall be as given in Table 16A.

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 9

    21.4 Minimum Dimensions of RC members for specified Period of Fire

    Resistance

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 10

    DESIGN LOAD

    Design load is the load to be taken for use in appropriate method of design. It is –

    � Characteristic load in case of working stress method &

    � Characteristic load with appropriate partial safety factors for limit

    state design.

    LOAD COMBINATIONS

    As per IS 1893 (Part 1): 2002 Clause no. 6.3.1.2, the following load cases have to

    be considered for analysis:

    � 1.5 (DL + IL)

    � 1.2 (DL + IL ± EL)

    � 1.5 (DL ± EL)

    � 0.9 DL ± 1.5 EL

    � Earthquake load must be considered for +X, -X, +Z and –Z directions.

    � Moreover, accidental eccentricity during earthquake can be such that it

    causes clockwise or anticlockwise moments. So both clockwise &

    anticlockwise torsion is to be considered.

    � Thus, ±EL above implies 8 cases, and in all, 25 cases must be considered.

    It is possible to reduce the load combinations to 13 instead of 25 by not using

    negative torsion considering the symmetry of the building.

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 11

    STIFFNESS

    22.3.1 Relative Stiffness: The relative stiffness of the members may be based

    on the moment of inertia of the section determined on the basis of any

    one of the following definitions:

    a) Gross Section

    The cross-section of the member ignoring reinforcement

    b) Transformed Section

    The concrete cross-section plus the area of reinforcement transformed on the basis of modular ratio

    c) Cracked Section

    The area of concrete in compression plus the area of reinforcement transformed on the basis of modular ratio

    The assumptions made shall be consistent for all the numbers of the

    structure throughout any analysis.

    22.3.2 For deflection calculations, appropriate values of moment of inertia as

    specified in Annexure of IS 456-2000 should be used.

    STRUCTURAL FRAMES

    22.4 The simplifying assumptions as given in 22.4.1 to 22.4.3 may be used

    in the analysis of frames.

    ARRANGEMENT OF LIVE LOAD

    22.4.1 a) Consideration may be limited to combinations of: 1) Design dead load on all spans with full design live load on two

    adjacent spans; and

    2) Design dead load on all spans with dull design live load on

    alternate spans.

    22.4.1 b) When design live load does not exceed three-fourths of the design

    dead load, the load arrangement may be design dead load and design

    live load on all the spans.

    Note: For beams continuous over support 22.4.1 (a) may be assumed. 22.4.2 Substitute Frame: For determining the moments and shears at any

    floor or roof level due to gravity loads, the beams at that level together

    with columns above and below with their far ends fixed may be

    considered to constitute the frame.

    22.4.3 For lateral loads, simplified methods may be used to obtain the

    moments and shears for structures that are symmetrical. For

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 12

    unsymmetrical or very tall structures, more rigorous methods should

    be used.

    MOMENT AND SHEAR COFFICIENTS FOR CONTINUOUS BEAMS 22.5.1 Unless more exact estimates are made, for beams of uniform cross-

    section which support substantially uniformly distributed load over

    three or more spans which do not differ by more than 15 percent of the

    longest, the bending moments and shear forces used in design may be

    obtained using the coefficients given in Tables below.

    For moments at supports where two unequal spans meet or in case

    where the spans are not equally loaded, the average of the two values

    for the negative moment at the support may be taken for design.

    Where coefficients given in Table below are used for calculation of

    bending moments, redistribution referred to in 22.7 shall not be

    permitted.

    22.5.2 Beams Over Free End Supports

    Where a member is built into a masonry wall which develops only

    partial restraint, the member shall be designed to resist a negative

    moment at the face of the support of W1/24 where W is the total

    design load and 1 is the effective span, or such other restraining

    moment as may be shown to be applicable. For such a condition shear

    coefficient given in Table below at the end support may be increased

    by 0.05.

    -------------------------------------------------------------------------------------------------------

    BENDING MOMENT COFFICIENTS

    ---------------------------------------------------------------------------------------------------

    ----

    Span Moments Support Moments ------------------------------------------------------------------------------------- Types of Load Near Middle At Middle At Support At Other of End Span of interior next to the Interior span end support Supports ------------------------------------------------------------------------------------------------------- Dead load and 1 1 1 1 imposed load +-- +-- (- )-- (- )-- (fixed) 12 16 10 12

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 13

    Imposed load 1 1 1 1 (not fixed) +-- +-- (- )-- (- )-- 10 12 9 9 Note:For obtaining the bending moment, the coefficient shall be multiplied by the total design load and effective span. ----------------------------------------------------------------------------------------------------- ---------------------------------------------------------------------------------------------------

    ----

    SHEAR FORCE COFFICIENTS

    ---------------------------------------------------------------------------------------------------

    ----

    Type of Load At End At Support Next At All Other Support to the end Support Interior Support Outer side Inner Side ------------------------------------------------------------------------------------------------------- Dead load and imposed load 0.40 0.60 0.55 0.50 (fixed) Imposed load 0.45 0.60 0.60 0.60 (not fixed) Note: For obtaining the shear force, the coefficient shall be multiplied by the total design load. -----------------------------------------------------------------------------------------------------

    CRITICAL SECTIONS FOR MOMENT AND SHEAR

    22.6.1 For monolithic construction, the moments computed at the face of the

    supports shall be used in the design of the members at those sections.

    For non-monolithic construction the design of the member shall be

    done keeping in view 22.2.

    22.6.2 Critical Section for Shear The shears computed at the face of the Support shall be used in the

    design of the member at that section except as in 22.6.2.1

    22.6.2.1 When the reaction in the direction of the applied shear introduces

    compression into the end region of the member, sections located at a

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 14

    distance less than d from the face of the support may be designed for

    the same shear as that computed at distance d.

    REDISTRIBUTION OF MOMENTS 22.7 Redistribution of moments may be done in accordance with 37.1.1 for

    limit state method and in accordance with B-1.2 for working stress method. However, where simplified analysis using coefficients is adopted, redistribution of moments shall not be done.

    EFFECTIVE DEPTH

    23.0 Effective depth of a beam is the distance between the centroid of the

    area of tension reinforcement and the maximum compression fibre,

    excluding the thickness of finishing material not placed monolithically

    with the member and the thickness of any concrete provided to allow

    for wear. This will not apply to deep beams.

    CONTROL OF DEFLECTION

    23.2 The deflection of a structure or part thereof shall not adversely affect the

    appearance or efficiency of the structure or finishes or partitions. The

    deflection shall generally be limited to the following:

    a) The final deflection due to all loads including the effects of

    temperature, creep and shrinkage and measured from the as-cast level

    of the supports of floors, roofs and all other horizontal members

    should not normally exceed span/250.

    b) The deflection including the effects of temperature, creep and

    shrinkage occurring after erection of partitions and the application of

    finishes should not normally exceed span/350 or 20mm whichever is

    less.

    23.2.1 For beams, the vertical deflection limits may generally be assumed to be

    satisfied provided that the span to depth ratio are not greater than the value

    obtained as below:

    a) Basic values of span to effective depth ratios for spans up to 10m:

    Cantilever 7

    Simply supported 20 Continuous 26

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 15

    b) For spans above 10m, the values in (a) may be multiplied by 10/span

    in metres, except for cantilever in which case deflection calculations

    should be made.

    c) Depending on the area and the type of steel for tension reinforcement,

    the value in (a) or (b) shall be modified as per Fig. 4

    d) Depending on the area of compression reinforcement, the value of

    span to depth ratio be further modified as per Fig. 5

    e) For flanged beams, the value of (a) or (b) be modified as per Fig. 6 and

    the reinforcement percentage for use in fig. 4 and 5 should be based on

    area of section equal to bf d.

    Note: When deflections are required to be calculated, the method given

    Annexure ‘C’ of IS 456-2000 may be used.

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 16

    CONTROL OF DEFLECTION – SOLID SLABS

    24.1 General

    The provisions of 32.2 for beams apply to slabs also. NOTES

    1. For slabs spanning in two directions, the shorter of the two spans should

    be used for calculating the span to effective depth rations.

    2. For two-way slabs of shorter spans (up to 3.5 m) with mild steel

    reinforcement, the span to overall depth rations given below may

    generally be assumed to satisfy vertical deflection limits for loading class

    up to 3 kN/m2.

    Simply supported slab 35

    Continuous slabs 40

    For high strength deformed bars of grade Fe 415,the values given

    above should be multiplied by 0.8.

    Simply supported slab 28

    Continuous slabs 32

    23.3 Slabs Continuous Over Supports

    Slabs spanning in one direction and continuous over supports shall be

    designed according to the provisions applicable to continuous beams.

    23.4 Slabs Monolithic with Supports Bending moments in slabs (except flat

    slabs) constructed monolithically with the supports shall be calculated by

    taking such slabs either as continuous over supports and capable of free, or as

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 17

    members of a continuous frame work with the supports, taking into account

    the stiffness of such support. If such supports are formed due to beams which

    justify fixity at the support of slabs, then the effects on the supporting beam,

    such as, the bending of the web in the transverse direction of the beam,

    wherever applicable, shall also be considered in the design of the beams.

    23.4.1 For the purpose of calculation of moment in slabs in a monolithic

    structure, it will generally be sufficiently accurate to assumed direct

    members connected to the ends of such slab are fixed in position and

    direction at the end remote from their connection with the slab.

    26.5 REQUIREMENT OF REINFORCEMENT FOR STRUCTURAL

    MEMBER

    26.5.1 Beams

    26.5.1.1 Tension reinforcement

    (a) Minimum reinforcement:- The minimum area of tension reinforcement

    shall not be less than that given by the following:-

    As = 0.85 bd fy

    where

    As = minimum area of tension reinforcement.

    b = breadth of beam or the breadth of the web of T-beam.

    d = effective depth, and

    fy = characteristic strength of reinforcement in M/mm2

    (b) Maximum reinforcement:- the maximum area of tension reinforcement

    shall not exceed 0.04bD.

    26.5.1.2 Compression reinforcement

    The maximum area of comparison reinforcement shall not exceed 0.04 bd.

    Comparison reinforcement in beams shall be enclosed by stirrups for effective

    lateral restraint.

    26.5.1.3 Side face reinforcement

    Where the depth of the web in the beam exceeds 750mm, side face reinforcement

    shall be provided along the two faces. The total area of such reinforcement shall

    be not less than 0.1 % of the web area and shall be distributed on the equally on

    the two face at spacing not exceeding 300mm or web thickness whichever is less.

    26.5.1.4 Transverse reinforcement in beam for shear torsion

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 18

    The transverse reinforcement in beam shall be taken around the outer most

    tension & compression bars. In T-beams and I-beams, such reinforcement shall

    pass around longitudinal bars located close to the outer face of the flange.

    26.5.1.5 Maximum spacing of shear reinforcement

    Maximum spacing of shear reinforcement means long by axis of the member shall

    not exceed 0.75 d for vertical stirrups and d for inclined stirrups at 45” where d is

    the effective depth on the section under consideration. In no case shall be spacing

    exceed 300mm.

    26.5.1.6 Minimum shear reinforcement

    Minimum shear reinforcement in the form of stirrups shall be provided such that:

    Asv 0.4 bsv 0.87 fy Where Asv = total cross-sectional area of stirrups legs effective in shear.

    Sv = stirrups spacing along the length of the member

    B = breadth of the beam or breadth of the web of flange beam, and

    fy = characteristic strength of the stirrups reinforcement in N/mm2 which shall not

    taken greater than 415 N/mm2

    Where the maximum shear stress calculated is less than half the permissible value

    in member of minor structure importance such as lintels, this provision need not

    to be complied with.

    26.5.1.7 Distribution of torsion reinforcement

    When a member is designed for torsion torsion reinforcement shall be provided as

    below:

    a) the transverse reinforcement for torsion shall be rectangular closed stirrups

    placed perpendicular to the axis of the member. The spacing of the stirrups

    shall not exceed the list of x1, x1+y1/4 and 300 mm, where x1, y1 are

    respectively the short & long dimensions of the stirrup.

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 19

    b) Longitudinal reinforcement shall be place as closed as is practicable to the

    corner of the cross section & in all cases, there shall be atleast one

    longitudinal bar in each corner of the ties. When the cross sectional

    dimension of the member exceed 450 mm additional longitudinal bar

    shall be provided to satisfied the requirement of minimum reinforcement

    & spacing given in 26.5.1.3.

    26.3.2 Minimum Distance between Individual Bars

    (a) The horizontal distance between two parallel main reinforcing bars shall

    usually be not-less than the greatest of the following:

    (i) Dia of larger bar and

    (ii) 5 mm more than nominal maximum size of coarse aggregate.

    (b) When needle vibrators are used it may be reduced to 2/3rd of nominal

    maximum size of coarse aggregate,

    Sufficient space must be left between bars to enable vibrator to be immersed.

    (c) Where there are two or more rows of bars, bars shall be vertically in line

    and the minimum vertical distance between bars shall be 15 mm, 2/3rd of

    nominal maximum size of aggregate or the maximum size of bars, whichever

    is greater.

    26.5.2 Slabs

    The rule given in 26.5.2.1 and 26.5.2.2 shall apply to slabs in addition to those

    given in the appropriate clause.

    26.5.2.1 Minimum reinforcement

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 20

    The mild steel reinforcement in either direction in slabs shall not be less than 0.15

    percent of the total cross-sectional area. However, this value can be reduced to

    0.12 percent when high strength deformed bars or welded wire fabric are used.

    26.5.2.2 Maximum diameter The diameter of reinforcing bars shall not exceed one eight of the total thickness of slab.

    26.3.3 Maximum distance between bars - Slabs

    1) The horizontal distance between parallel main reinforcement bars shall not be

    more than three times the effective depth of solid slab or 300 mm whichever is

    smaller.

    2) The horizontal distance between parallel reinforcement bars provided against

    shrinkage and temperature shall not be more than five times the effective depth of

    a solid slab or 300 mm whichever is smaller.

    Torsion reinforcement - Slab

    Torsion reinforcement is to be provided at any corner where the slab is simply

    supported on both edges meeting at that corner. It shall consist of top and bottom

    reinforcement, each with layers of bars placed parallel to the sides of the slab and

    extending from the edges a minimum distance of one-fifth of the shorter span.

    The area of reinforcement in each of these four layers shall be three-quarters of

    the area required for the maximum mid-span moment in the slab.

    D-l.9 Torsion reinforcement equal to half that described in D-l.8 shall be provided

    at a corner contained by edges over only one of which the slab is continuous.

    D-1.10 Torsion reinforcements need not be provided at any comer contained by

    edges over both of which the slab is continuous.

    26.5.3 Columns

    A. Longitudinal Reinforcement

    a. The cross sectioned area of longitudinal reinforcement shall be not less

    than 0.8% nor more than 6% of the gross sectional area of the column.

    Although it is recommended that the maximum area of steel should not

    exceed 4% to avoid practical difficulties in placing & compacting concrete.

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 21

    b. In any column that has a larger cross sectional area than that required to

    support the load, the minimum percentage steel must be based on the area

    of concrete resist the direct stress & not on the actual area.

    c. The bar should not be less than 12 mm in diameter so that it is sufficiently

    rigid to stand up straight in the column forms during fixing and concerting.

    d. The minimum member of longitudinal bars provided in a column shall be

    four in rectangular columns & six in circular columns.

    e. A reinforced concrete column having helical reinforcement must have at

    least six bars of longitudinal reinforcement with the helical reinforcement.

    These bars must be in contact with the helical reinforcement & equidistance

    around its inner circumference.

    f. Spacing of longitudinal should not exceed 300 mm along periphery of a

    column.

    g. In case of pedestals, in which the longitudinal reinforcement is not taken

    into account in strength calculations, nominal reinforcement should be not

    be less than 0.15% of cross sectional area.

    B. Transverse Reinforcement

    a. The diameter of lateral ties should not be less than ¼ of the diameter of

    the largest longitudinal bar in no case should not be less than 6 mm.

    b. Spacing of lateral ties should not exceed least of the following:-

    • Least lateral dimension of the column.

    • 16 times the smallest diameter of longitudinal bars to be tied.

    • 300mm.

    SHEAR

    40.1 Nominal Shear Stress

    The nominal shear stress in beams of uniform depth shall be obtained by the

    following equation:

    τv = Vu/ b.d where Vu = shear force due to design loads;

    b = breadth of the member, which for flanged section shall be taken as the breadth

    of the web, bw; and

    d = effective depth.

    40.2.3 With Shear Reinforcement

    Under no circumstances, even with shear reinforcement, shall the nominal shear

    stress in beams should not exceed given in Table 20.

    40.2.3.1 For solid slabs, the nominal shear stress shall not exceed half the

    appropriate values given in Table 20.

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 22

    40.3 Minimum Shear Reinforcement

    When τv, is less than τc given in Table 19, minimum shear reinforcement shall be provided in accordance with 26.5.1.6.

    40.4 Design of Shear Reinforcement

    When τv, is exceeds τc , given in Table 19, shear reinforcement shall be provided

    in any of the following forms:

    a) Vertical stirrups,

    b) Bent-up bars along with stirrups, and where bent-up bars are provided, their

    contribution towards shear resistance shall not be more than half that of the total

    shear reinforcement.

    Shear reinforcement shall be provided to carry a shear equal to Vu – τ c b d. the

    strength of shear reinforcement Vus shall be calculated as below:

    a) For Vertical Stirrups:

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 23

    0.87 fy Asv d

    Vus = ___________ Sv

    b) For inclined stirrups or a series of bars bent up at different cross –section:

    0.87 fy Asv d

    Vus = ___________ (Sin ά + Cos ά) Sv

    c) For single bar or single group of parallel bars, all bent up at the same cross sections:

    Vus = 0.87 fy Asv Sin ά

    Where Asv = total cross –sectional area of stirrups legs or

    bent-up bar within a distance Sv,

    Sv = spacing of the stirrups or bent-up bars along

    the

    length of the member.

    τ v = nominal shear stress, τ c = design shear strength of the concrete, b = breadth of the member which for flanged

    beams, shall be taken as the breadth of the web bw. fy = characteristic strength of the stirrup or bent-

    up reinforcement which shall not be taken

    greater

    than 415 N/mm2,

    ά = angle between the inclined stirrup or bent up

    bar

    and the axis of the member not less than 45o,

    and

    d = effective depth

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 24

    DEVELOPMENT LENGTH OF BARS

    26.2 Development of Stress in Reinforcement

    The calculated tension or compression in any bar at any section shall be

    developed on each side of the section by an appropriate development length or

    end anchorage or by a combination thereof.

    Development length Ld is given by

    Ld = φσst /4τbd

    φ = nominal diameter of bar, τbd = design bond stress

    σst = stress in bar at the section considered at design load

    � Design bond stress in limit state method for plain bars in tension is given

    in clause 26.2.1.1

    � For deformed bars conforming to IS 1786 these values are to be increased

    by 60 %.

    � For bars in compression, the values of bond stress for bars in tension is to

    be increased by 25 percent

    B. Shear reinforcement (STIRRUPS)

    Development length and anchorage requirement is satisfied, in case of stirrups

    and transverse ties, when Bar is bent –

    • Through an angle of at least 90 degrees (round a bar of at least its own dia)

    & is continued beyond for a length of at least 8 φ, or

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 25

    • Through an angle of 135 degrees & is continued beyond for a length of at

    least 6 φ or

    • Through an angle of 180 degrees and is continued beyond for a length of

    at least 4 φ

    DUCTILE DETAILING AS PER IS: 13920

    • Provisions of IS 13920-1993 shall be adopted in all reinforced concrete

    structures which are located in seismic zone III, IV or V

    The provisions for reinforced concrete construction given in IS 13920-1993

    shall apply specifically to monolithic reinforced concrete construction. Precast

    and/or prestressed concrete members may be used only if they can provide the

    same level of ductility as that of a monolithic reinforced concrete construction

    during or after an earthquake.

    The definition of seismic zone and importance factor are given in IS 1893-2002.

    CODAL PROVISIONS OF IS 13920

    5.2 For all buildings which are more than 3 storeys in height, the minimum grade

    of concrete shall be M20 (fck = 20 MPa ).

    5.3 Steel reinforcements of grade Fe 415 (see IS 1786 : 1985 ) or less only shall

    be used. However, high strength deformed steel bars, produced by the thermo-

    mechanical treatment process, of grades Fe 500 and Fe 550, having elongation

    more than 14.5 percent and conforming to other requirements of IS 1786 : 1985

    may also be used for the reinforcement.

    Flexure Members

    6.1.2 The member shall preferably have a width-to-depth ratio of more than 0.3.

    6.1.3 The width of the member shall not be less than 200 mm.

    6.1.4 The depth D of the member shall preferably be not more than 1/4 of the

    clear span.

    6.2 Longitudinal Reinforcement

    6.2.1 a) The top as well as bottom reinforcement shall consist of at least two bars

    throughout the member length.

    b) The tension steel ratio on any face, at any section, shall not be less than ρmin =

    0.24(fck)1/2 /fy ; where fck and fy are in MPa.

    6.2.2 The maximum steel ratio on any face at any section, shall not exceed ρmax

    = 0.025.

    6.2.3 The positive steel at a joint face must be at least equal to half the negative

    steel at that face.

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 26

    6.2.4 The steel provided at each of the top and bottom face of the member at any

    section along its length shall be at least equal to one-fourth of the maximum

    negative moment steel provided at the face of either joint

    6.2.6 The longitudinal bars shall be spliced, only if hoops are provided over the

    entire splice length, at a spacing not exceeding 150 mm 6.3

    Web Reinforcement

    6.3.1 Web reinforcement shall consist of vertical hoops. A vertical hoop is a

    closed stirrup having a 135° hook with a 10 diameter extension (but not < 75 mm)

    at each end that is embedded in the confined core

    6.3.2 The minimum diameter of the bar forming a hoop shall be 6 mm. However,

    in

    beams with clear span exceeding 5 m, the minimum bar diameter shall be 8 mm.

    6.3.4 The contribution of bent up bars and inclined hoops to shear resistance of

    the section shall not be considered.

    6.3.5 The spacing of hoops over a length of 2d at either end of a beam shall not

    exceed (a) d/4, and (b) 8 times the diameter of the smallest longitudinal bar;

    however, it need not be less than 100 mm. elsewhere, the beam shall have vertical

    hoops at a spacing not exceeding d/2.

    Columns

    7.1.2 The minimum dimension of the member shall not be less than 200 mm.

    However, in

    frames which have beams with centre to centre span exceeding 5 m or columns of

    unsupported length exceeding 4 m, the shortest dimension of the column shall not

    be less than 300 mm.

    7.1.3 The ratio of the shortest cross sectional dimension to the perpendicular

    dimension shall preferably not be less than 0.4.

    7.2 Longitudinal Reinforcement

    7.2.1 Lap splices shall be provided only in the central half of the member length.

    It should be proportioned as a tension splice. Hoops shall be provided over the

    entire splice length at spacing not exceeding 150 mm centre to centre. Not more

    than 50 percent of the bars shall be spliced at one section.

    7.3 Transverse Reinforcement

    7.3.1 Transverse reinforcement for circular columns shall consist of spiral or

    circular hoops. In rectangular columns, rectangular hoops may be used. A

    rectangular hoop is a closed stirrup, having a 135° hook with a 10 diameter

    extension (but not < 75 mm) at each end that is embedded in the confined core.

    7.3.3 The spacing of hoops shall not exceed half the least lateral dimension of the

    column, except where special confining reinforcement is provided, as per 7.4.

    7.4 Special Confining Reinforcement

    This requirement shall be met with, unless a larger amount of transverse

    reinforcement is required from shear strength considerations.

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 27

    7.4.1 Special confining reinforcement shall be provided over a length lo from

    each joint face, towards midspan, and on either side of any section, where flexural

    yielding may occur under the effect of earthquake forces. The length ‘lo’ shall not

    be less than

    (a) larger lateral dimension of the member at the section where yielding occurs,

    (b) 1/6 of clear span of the member, and (c) 450 mm.

    7.4.2 When a column terminates into a footing or mat, special confining

    reinforcement shall extend at least 300 mm into the footing or mat.

    7.4.6 The spacing of hoops used as special confining reinforcement shall not

    exceed 1/4 of minimum member dimension but need not be less than 75 mm nor

    more than 100 mm.

    8 JOINTS OF FRAMES

    8.1 The special confining reinforcement as required at the end of column shall be

    provided through the joint as well, unless the joint is confined as specified by 8.2.

    8.2 A joint which has beams framing into all vertical faces of it and where each

    beam width is at least 3/4 of the column width, may be provided with half the

    special confining reinforcement required at the end of the column. The spacing of

    hoops shall not exceed 150 mm.

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 28

    As per IS-875(Part-1)-1987

    0.16-0.23STEEL WORK -ROOFING

    0.65MANGLORE TILES

    0.15GI SHEET -ROOFING

    0.16AC SHEET -ROOFING

    78.5STEEL

    18LIME -PLASTER

    21CEMENT-PLASTER

    6-10TIMBER

    21-27STONE MASONRY

    19-20BRICK MASONRY

    25REINFORCED CONCRETE

    24PLAIN CONCRETE

    kN/m2kN/m3

    UNIT WEIGHT

    MATERIAL

    DEAD LOADS – UNIT WEIGHTS OF SOME MATERIALS/BUILDING COMPONENTS

    4.0�STAIRS-NOT LIABLE TO OVER CROWDING

    5.0- LIABLE TO OVER CROWDING

    7.5–HEAVY VEHICLES

    4.0�GARRAGES –LIGHT VEHICLES

    10.0�STACK ROOM IN LIBRARIES ,BOOK STORES

    5.0-10� FACTORIES & WAREHOUSES

    5.0- WITHOUT FIXED SEATING

    4.0- WITH FIXED SEATING

    � SHOPS,CLASS ROOMS,WAITINGS ROOMS,

    RESTAURANTS,WORK ROOMS,THEATRES ETC

    4.0– WITHOUT SEPARATE STORAGE

    2.5� OFFICIAL – WITH SEPARATE STORAGE

    2.0� RESIDENTIAL

    LIVE LOAD

    (kN/m2)TYPE OF FLOOR USAGE

    LIVE LOADS ON FLOORS AS PER IS-875(Part-2)-1987

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 29

    0.75� ROOF WITHOUT ACCESS

    1.5� ROOF WITH ACCESS

    LIVE LOADS ON ROOFS

    12.0� WEATHER MAKER

    10.0� MDF ROOM

    6.0� OMC ROOM,DDF ROOM,POWER PLANT,

    BATTERY ROOM

    6.0� SWITCH ROOM(NEW TECHNOLOGY)

    LIVE LOAD (kN/m2)TYPE OF FLOOR USAGE

    LIVE LOADS ON FLOORS OF T.E.BLDGS

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 30

    3.0 Steps for Design of a Multi-Storeyed Building:-

    Manual Method of Analysis & Design:-

    Step1: Study of architectural Drawings:- Before proceeding for

    structural design of any building it is ensure that approved working drawings

    are available in the office. All working drawings i.e. each floor plan, elevations,

    sections, are studied thoroughly & discrepancy if any brought to the notice of

    concern Architect for rectification/correction. The problems coming in

    finalization of structural configuration may also be intimated to concern

    Architect for rectification/correction if any.

    Step2: Finalization of structural Configuration. After receiving

    corrected working drawing from the architectural wing, the structural system is

    finalized. The structural arrangements of a building is so chosen as to make it

    efficient in resisting vertical as well as horizontal loads due to earthquake. The

    span of slabs co chosen that thickness of slab 100-150mm and slab panels,

    floor beams, and columns, are all marked and numbered on the architectural

    plans. Now the building is ready for structural design to start.

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 31

    ISOMETRIC VIEW OF FRAMED STRUCTURE

    Step3: Load Calculation and analysis. For each floor or roof, the

    loading intensity of slab is calculated taking into account the dead load of the

    slab, finish plaster, etc. including partitions and the live load expected on the

    floor, depending on the usage of the floor or roof. The linear loading of beams,

    columns, walls, parapets, etc. also calculated.

    Step3 (a): Preliminary Sizes of structural members. Before proceeding

    for load calculation preliminary sizes of slabs, beams,& columns decided. In

    manual load calculation preliminary sizes of structural members should be

    judicially fixed as once load calculation & analysis is done it is not easy to revise

    the same. But in computer aided analysis & design it can be revised easily.

    • Slab:- The thickness of the slab decided on the basis of span/d ratio

    assuming appropriate modification factor.

    • Beam : The width the beam generally taken as the width of wall

    i.e 230 or 300 mm. The width of beam is help full in placement of

    reinforcement in one layer & more width is help full in resisting

    shear due to torsion. The depth of beam is generally taken as 1/12

    th (for Heavy Loads) to 1/15 th (for Lighter Loads) of span.

    • Column:- Size of column depends upon the moments from the both

    the direction and the axial load. Preliminary Column size may be

    finalized by approximately calculation of axial load & moments.

    Procedure for vertical load calculation on Columns:

    Step(i): First, the load from slab (including Live load & Dead Load) is

    transferred on to the adjoining beams using formulas given below|:- For computation of shear force on beams & reactions on columns, an

    equivalent uniformly distributed load per linear meter of beam may be taken as : Equivalent u.d.l. on short beam of slab panel = w B/4.0 Equivalent u.d.l. on long beam of slab panel = w B/4 x [2-(B/L)] Where w is the total load on the slab panel in Kn/Sqm & L & B are long span & short spans of slab panel respectively.

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 32

    Step(ii): Over this load, the weight of wall (if any), self weight of beam etc. are added to get the load on beam (in running metre).

    Step(iii):The load (in running metre) on each beam is calculated as in Step 1 &

    Step 2.

    Step(iv):Then the loads from the beams are transferred to the columns. Step(v):Step (i) to Step (v) is repeated for each floor. Step(vi):These loads at various floors on each column are then added to get the

    total loads on each column, footing and the whole building.

    Step4: HORIZONTAL (SEISMIC) LOAD CALCULTAION:

    The Horizontal Load Calculation or the Load Calculations for Seismic case is

    carried out as per the Indian Standard Code IS:1893-2002.

    The loads calculated in Para-II above at various floor levels are modified as per

    the requirement of Para 7.3.1 of IS:1893-2002.

    The Seismic Shear at various floor levels is calculated for the whole Building

    using the values from IS 1893-2002.

    Calculation o f horizontal loads on buildings (As per is-1893-2002)

    Sample example for horizontal load calculation

    (I) BUILDING IS ON SEISMIC ZONE-IV (II) FOUNDATION TYPE ISOLATED FOOTINGS

    As per clause 7.5.3 o f IS-1893-2002 Design base shear vb V

    b = A h W (F)

    Where Ah = Design Horizontal acce lerat ion spectrum value as per

    6.4.2 of the code

    = (Z/2) (I/R) (Sa/g)

    Where Z = Zone factor as per table 2 o f IS Code (1893-2002) = 0.24 (in this case) I = Importance factor as per table 6 of IS-1893-2002)

    = 1.5 (Assuming tha t the b ldg. is T.E. Bldg.)

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 33

    R = Response reduction factor as per table 7 of IS code

    = 3.0 (for ordinary R.C. Moment res ist ing frame

    (OMRF)

    (Sa /g) = Average response accelerat ion coeffic ient for soil

    typ e & appropriate natural periods and lamping of the

    structure.

    For calcu lat ing of (Sa/g) value as above we have to calculate va lue

    of T i.e. Fundamental Nat ional Per iod (Seconds) (Clause 7.6 of IS

    Code)

    T = 0.075 h 0 .7 5 (For RC Frame build ing)

    = 0.0 85 h 0 . 7 5 (For Steel frame build ing)

    h = Height of building in Meter

    In case of building with brick in f ills walls.

    T = 0.09 h /d 1 /2

    Where h = height of bu ild ing in Meter

    and d = Base d imension of the bu ilding at the plinth leve l in

    Meter along the considered direction o f the latera l

    fo rce.

    Value of (Sa/g) is to be read from f ig 2 on page 16 of IS

    Code depending upon Soil condit ion & Fundamenta l Natural period

    T.

    Or the va lue of (Sa/g) may be calcu lated on the basis o f

    Following.

    Formulas:- (i) For rocky, or hard soil sites

    (Sa/g) = 1+15 T if 0 .00≤T≤ 0 .10

    = 2.50 if 0 .10≤T≤ 0 .40

    =1.00/T if 0 .40≤T≤ 4 .00

    (ii) For medium soil sites (Sa/g) = 1+15 T if 0.00≤T≤ 0 .10

    = 2.5 0 if 0 .10≤T≤0.55

    = 1.36/T if 0 .55≤T≤ 4 .00

    ( iii) For soft so il sites (Sa/g) = 1+15 T if 0.00≤T≤

  • E4-E5 Civil (Technica l) Rev date : 20-04-11

    BSNL India For Interna l Circulat ion Only Page: 34

    = 2.50 if 0 .10≤T≤0.67

    =1.67/T if 0 .67≤T≤ 4 .00

    W= Seismic weight of the building as per clause 7.4.2 of the code.

    A

    B

    C

    2 b

    ays @

    7.5

    m C

    /C

    TYPICAL FLOOR PLAN

    Bldg. is three storey with Each

    storey of 5.0m height

    4 bays @ 4.0 m C/C

    164.9

    157.99

    47.01

    Frame with EQ Loads

  • BSNL India For Interna l Circulat ion Only Page: 35

    Calculating Seismic weight of building per frame for frame (B)

    Length bldg = 16.00 M

    C/C distance of frames = 7.50 M

    Densit y of R.C.C = 25 KN/m3

    Floor slab = 0.15×16.00×7 .50×25 = 450 KN (A)

    Co lumn below slab = 0.300×(0.70-0.15)×16.00×25

    = 0.30×0 .55×16 .00×25=66 KN (B)

    Co lumns = 0.30×0 .60×(5.00+5.00)/2 ×25× 5 = 112.5 KN (C) Live load = 600 kg/m2 = 6.00 kn/m2

    As per table 8 of code when live load is above 3.00 kn/m2 50%

    of live load to be considered for lamp mass ca lcu lat ion.

    Lump mass at First Floor = 0.50×6.00×16×7.50 = 360 KN (D) To tal lamp mass f irst f loor & second floor (Assuming same L.L. on S.F.)

    (A)+(B)+(C)+(D) = 450+66+112.50+360

    = 988.50 KN

    (ii) Wight lamped at terrace Floor slab:-

    = 0.13×16.00×7.50×25 = 390 KN (E)

    Beam below slab = 0.23×(0.60-0.15)×16.00×25

    = 0.23×0.45×16.00×25

    = 41 .4.KN (F)

    Co lumns = 0.30×0.600×5.00 /2×25×5 = 56.25 KN (G) L.L. = Nil During Earthquake = 0. ( As per the clause 7.3.2 o f the

    code the imposed load on roof need not to be considered )

    To tal lamped mass at terrace level = (E)+(F)+(G)

    = 390+41.40+56.25=487.65 KN

    Total weight o f building per framed per inner frame F.F = 988.50 KN S.F. = 988.50 KN Terrace = 487.65 KN 2464.65 KN

  • BSNL India For Interna l Circulat ion Only Page: 36

    Putting a ll values in Formulas (F) Vb = Design base shear = (z/z)(I/R(Sa/g) w Value of T = 0.09 h/Vd

    H = Height of bldg. = 15.00 m (3x5.0=15.00m )

    d = 16.00 m

    T = 0.09×15.00/V 16.00 = 0.3375 = 0.34

    For med ium soils For T = 0.34 Sa/g = 2.50 Vb = 0.24 /2×1.50 /3.00×2 .50×2465.65 = 369.85 KN Distribution base shear is done using formula (clause 7.7)

    F i = w i h i 2 / ∑ w j h j

    2 x Vb

    Where Fi = Design lateral force at f loor i

    W i = Seismic weight of floor i

    hi = he ight of f loor in m from base.

    n = number of story’s in the build ing is equal to number of levels at

    which masses are located.

    Vb = 369.85 KN

    Floor W i KN h i (m) W i h i 2 F i

    F.F. S.F.

    Terrace level

    988.50 988.50 487.65

    6.00 11.00 16.00

    35586 119608.5 124800

    47.01 KN 157.99 164.85

    ∑w i hi 2 = 279994.5 ∑ = 369.85 KN

    Step5. VERTICAL LOAD ANALYSIS:

    a) GENERAL:

    The skeleto n frame work of a mult i sto ried R.C.C. framed

    structu re is made up of a system of columns, beams and slabs. It is

    presumed that the re inforcements are a lwa ys so arranged that all joints

    of the frame are mono lithic.

    In view of the uncertain property of materia l creep, shr inkage

    and a number of approximate s implifying assumptions made in the

    detailed analysis of multi storied framed structures (such as condit ions

  • BSNL India For Interna l Circulat ion Only Page: 37

    of end restraints etc.) it is co nsidered suffic ient to obtain reasonable

    accurac y of analysis fo r the design of structu re. If the normal moment

    distr ibution is applied to all joints, the work invo lved is enormous.

    However with certain assumptions, it is possib le to analyze the frames

    and get resu lts which will be adequate for design purposes.

    To simplify ana lysis the three dimensional mult isto ried R.C.C.

    framed structure are considered as combinat ions of p laner framed in

    two d irections. It is assumed that each of these p laner frames act

    independent ly o f the frames.

    Procedure for Frame analysis for ca lculation of moments in

    Columns & beams:

    Step(i) : Fir st, the load from slab (including Live load & Dead Load) is

    transferred on to the adjo ining beams using formulas given

    below|:-

    For computation of Bend ing Moments in beams , an equ ivalent

    uniformly d istr ibuted load per linear meter of beam may be taken as :

    Equiva lent u.d.l. on short beam of slab panel = w B/3.0

    Equiva lent u.d.l. on long beam of slab panel = w B/6 x [ 3-(B/L)2 ]

    where w is the to tal load on the slab panel in Kn/Sqm & L & B are

    long span & short spans of s lab panel respect ive ly.

    Step(ii) : Over this load, the weight of wall ( if any), self weight of

    beam etc. are added to get the load on beam (in running Meter).

    Step(iii) :The load (in running Meter) on each beam is ca lculated as in

    Step 1 & Step 2.

    Step(iv):Step (i) to Step (iii) is repeated for each floor Step(v):Then these loads are used as u.d.l on a part icular frame for

    ana lysis by moment distr ibution method as described in the next

    sect ion.

    b) METHOD OF ANALYSIS:

  • BSNL India For Interna l Circulat ion Only Page: 38

    Analysis of large framed structures beams too Cumbersome with

    the class ical method of structure ana lysis such a Clape yron’s theorem

    of three moments, Cast ingiliano’s therefore o f least work, Poison’s

    method of vir tual work etc. Therefore, it become necessar y to evolve

    simpler methods.

    Some of these are :-

    a.) Hardy cross method of moment distr ibution.

    b.) Kani’s method of iteration.

    c) HARDY CROSS METHOD OF MOMENT DISTRIBUTION:

    In this method, the ‘balancing’ and ‘carry-over’ const itu te one c ycle

    and it has been found the ‘carry-over’ values converge fast enough to

    become quite insignificant a fter four c ycle of operation. it is,

    therefore, o ften adequate to stop the computation after four cyc les.

    The frame is analyzed by this method either:

    i. Floor-wise assuming the co lumns to be fixed for ends.

    or i i. Taking the frame as a whole. The whole frame analysis can be

    carried out for several a lternat ive loading arrangements for

    obtaining maximum posit ive and negat ive bending moment.

    Generally frames are analyzed floor-wise for the worst

    condit ions of loading.

    The method is described in the fo llowing steps. Step1: Calculate the st iffness of a ll members. Enter them in the

    calculat ion scheme.

    Step2: Calculated the d istr ibution factor at a ll joints from the

    st iffness. Enter them in the calculat ion scheme.

    Step3: Look the jo ints and calculate the f ixed-end moments. Enter

    them in the calcu lat ion scheme.

    Step4: Unlock the joint one by one by applying imaginary external moments

    at each joint which nullifier the unbalanced moment at the joint.

    Distribute the imaginary external moment among all members

  • BSNL India For Interna l Circulat ion Only Page: 39

    Meeting at the joint in proportion to the ir re lat ive

    st iffness and enter these va lue in the scheme. This

    operation is called balancing.

    Step5: Enter the carry-over moments at the far in the scheme.

    Step6: Repeat steps 4 & 5, t ill the carry-over moments become

    insignificant.

    Step7: Balance the unbalanced moment obtained from the last

    carry-over operation.

    Step8: Add the init ial f ixed-end moments, balancing moments and

    carry-over moments to get the f inal end moments in beam

    & co lumns.

    A sample of moment distr ibu tion method is shown on next two pages.

    CALCUL ATION OF DISTRIBUTION F ACTOR FOR FRAME ANALYSIS

    SNO.

    JOIN T MEMBER Size in

    Cm

    Moment o f Ine rt ia Cm4 ( I)

    Le ng th of me

    mber

    Cm

    K=I/L

    Sum K D.F.

    1

    B D

    A- II I R igh t beam 30 45 227812. 50 600

    379.69

    1030. 58

    0. 37

    Lower Col. 30 45 227812. 50 350 650.

    89 0. 63

    2

    B-II I

    Lef t beam 30 45 227812. 50 600 379.

    69

    1802. 01

    0. 21

    Righ t beam 30 60 540000. 00 700 771.

    43 0. 43

    Lower Col. 30 45 227812. 50 350 650.

    89 0. 36

    3 C-II I

    Lef t beam 30 60 540000. 00 700 771.

    43

    1422. 32

    0. 54

    Lower Col. 30 45 227812. 50 350 650.

    89 0. 46

    4

    A- II

    Upper co l. 30 45 227812. 50 350 650.

    89

    1681. 47

    0. 39

    Righ t beam 30 45 227812. 50 600 379.

    69 0. 23

    Lower Col. 30 45 227812. 50 350 650.

    89 0. 39

    5

    B-II

    Lef t beam 30 60 540000. 00 600 900.

    00

    2973. 21

    0. 30

    Upper co l. 30 45 227812. 50 350 650.

    89 0. 22

    Righ t beam 30 60 540000. 00 700 771.

    43 0. 26

  • BSNL India For Interna l Circulat ion Only Page: 40

    Lower Col. 30 45 227812. 50 350 650.

    89 0. 22

    6

    C-II

    Lef t beam 30 60 540000. 00 700 771.

    43

    2073. 21

    0. 37

    Upper co l. 30 45 227812. 50 350 650.

    89 0. 31

    Lower Col. 30 45 227812. 50 350 650.

    89 0. 31

    7

    A- I

    Upper co l. 30 45 227812. 50 350 650.

    89

    1572. 99

    0. 41

    Righ t beam 30 45 227812. 50 600 379.

    69 0. 24

    Lower Col. 30 45 227812. 50 420 542.

    41 0. 34

    8

    B-I

    Lef t beam 30 45 227812. 50 600 379.

    69

    2344. 42

    0. 16

    Upper co l. 30 45 227812. 50 350 650.

    89 0. 28

    Righ t beam 30 60 540000. 00 700 771.

    43 0. 33

    Lower Col. 30 45 227812. 50 420 542.

    41 0. 23

    9

    C-I

    Lef t beam 30 60 540000. 00 700 771.

    43

    1964. 73

    0. 39

    Upper co l. 30 45 227812. 50 350 650.

    89 0. 33

    Lower Col. 30 45 227812. 50 420 542.

    41 0. 28

    FRME ANALYSIS BY MOMENT DISTRIBUTION METHOD

    III

    U.d . l .

    28

    6 .00

    U.D.L 24

    7.00

    0 .63 0.37 30X45 0 .21 0.43 0 .36 30X60 0.54

    0 .46

    0

    -84 .0

    0 In t .FEM 84.00 0 -98.00 In t .FEM 98.00 0

    bal . 52 .92

    31 .08 2 .94 6.02 5 .04

    -52.92

    -45.08

    C. O. 14 .63 1.47 15 .54 0.74 -26.46 2.52

    -12.66

    BAL -10.14 -5.96 2 .14 11.06 3 .66 5.48

    4 .66

    Tot al 57 .41

    -57 .4

    1 104.62 17.82 -115.76 53.08

    -53.08

  • BSNL India For Interna l Circulat ion Only Page: 41

    Tot al 38 .28 4.06

    -34.87

    BAL -17.43

    BAL -0.42

    BAL 12.99

    C. O. 26 .46

    C.O. 3.01

    C.O. -

    22.54

    29 .25 1.47

    -25.32

    0 0 0

    0 .39 0.22

    0 .31

    II

    25

    6 .00

    20

    7.00

    0 .39 0.23 0.3 0.22 0 .26 0.37

    0 .31

    0

    -75 .0

    0 In t .FEM 75.00 0 -81.67 In t .FEM 81.67 0

    29 .25

    17 .25 2 1.47 1 .73

    -30.22

    -25.32

    C. O. 17 .22 1 8 .63 5.39 -15.11 0.87

    -20.22

    BAL -17.43

    -10 .2

    8 -0 .58 -0.42 -0 .5 15 .5 12.99

    29 .04

    -67 .0

    3 85 .05 6.44 -95.55 67.82

    -32.55

    Tot al 41 .81 15.18

    -51.01

    BAL -7 .26 3.66

    2 .08

    C. O. 14 .63 0.74

    -12.66

    34 .44 10.78

    -40.43

    0 0 0

    0 .41 0.28

    0 .33

    I

    28

    6 .00

    30

    7.00

  • BSNL India For Interna l Circulat ion Only Page: 42

    0 .34 0.24 0 .16 0.23 0 .33 0.39 0 .2

    8

    0

    -84 .0

    0 In t .FEM 84.00 0 -122.50 In t .FEM

    122.50 0

    28 .56 20 .1

    6 6 .16 8.86 12 .71 -

    47.78

    -34.

    3

    C.O. 0 3.08 10 .08 0 -23.89 6.36 0

    BAL -6 .02 -4.25 2 .09 3.01 4 .31 2.46 1 .7

    6

    22 .54

    -65 .0

    1 102.33 11.87 -129.37 83.54

    -32.54

    A B C

    Step6. HORIZONTAL LOAD ANALYSIS:-

    Frame analysis for horizonta l loads calculated in step 4 is carr ied ou t by using :- (a)Approximate Method:-

    i) Cant ilever method.

    ii) Portal method .

    Approximate methods are used for preliminar y designs only. For f ina l

    design we may use exact method i.e ( i) Slope deflect ion or matrix

    methods (ii) Factor method.

    We will no t d iscuss these methods in detail as now modern computer package as STAAD PRO is ava ilable fo r analysis. Step7: DESIGN OF COULMN,FOUNDATIONS, BEAMS & SLABS:

    After load calcu lat ion & analysis for vert ica l & horizonta l

    loads, design o f Columns ,Foundations, Beams, Slabs and are to be

    carried out as per the var ious clauses of IS codes, IS 456-2000,

    IS:1893-2002, IS:13920-1993 etc.

    The Design of Co lumn, Foundation, Beams and Slabs are discussed in

    details in following sect ion.

  • BSNL India For Interna l Circulat ion Only Page: 43

    A. Design o f columns: - With the knowledge of ( i) Vertical load

    (ii) Moments due to horizontal loads on either axis;( iii) Moments due

    to vertical loads on either axis, act ing on each co lumn, at a ll floor

    leve ls of the building, columns are designed by charts of SP-16(Design

    Aids) with a load factor of 1.5 for vertical load effect and with a load

    factor of 1.2 for the combined effects of the vertical and the horizonta l

    loads. The step confirms the s ize of columns assumed in the

    architectural drawings. The design o f each column is carr ied out from

    the top of foundation to the roof, varying the amount of stee l

    reinforcement fo r suitable groups for ease in design. Further,

    slenderness effects in each sto rey are considered for each column

    group.

    Important Considerations in design o f Columns:-

    (i)Effective height of column:- The effective height of a column is

    defined as the height between the po ints o f contra f lexure of the

    buckled co lumn. For effect ive column height refer table 28 (Annexure

    E) of IS: 456-2000.

    For framed structure effect ive height of column depends

    upon re lat ive st iffness of the column & various beams framing into the

    column at its two ends. (Refer Annexure E of IS: 456-2000.)

    (ii)Unsupported Length: - The unsupported length l, o f a compression

    member sha ll be taken as the c lear dis tance between end restraints

    except that :-

    In beam & slab co nstruct ion, it sha ll be the clear d istance between

    the f loor & under side of the shallower beam framing into the columns

    in each direct ion at the next higher f loor leve l.

    (iii) Slenderness limits for columns: - The unsupported length

    between end restraints shall no t exceed 60 times the least latera l

    dimensio n of a column.

    (iv) Minimum Eccentricity: - All columns sha ll be designed for

    minimum eccentric it y equal to unsupported length of column/500 plus

    least latera l dimensio n/30, subject to a minimum of 20 mm.

    Or emi n ≥ l/500+ D/30 ≥ 20 mm

  • BSNL India For Interna l Circulat ion Only Page: 44

    Where l= unsupported length of column in mm.

    D=Lateral dimension o f column in the d irect ion under

    considerat ion in mm.

    (v)Design Approach: - The design o f column is complex s ince it is

    sub jected to axia l loads & moments which may very independently.

    Co lumn design requ ired:-

    I. Determinat ion o f the cross sect iona l dimension.

    II. The area of longitud inal steel & it s distr ibution.

    III. Transverse stee l.

    The maximum axial load & moments act ing a long the length of

    the column are considered for the design of the column sect ion either

    by the working stress method or limit state method.

    The transverse reinfo rcement is provided to impart effect ive

    lateral support aga inst buckling to ever y longitudina l bar. It is either in

    the form of circular r ings of polygonal links (lateral t ies) .

  • BSNL India For Interna l Circulat ion Only Page: 45

  • BSNL India For Interna l Circulat ion Only Page: 46

    B. Design o f foundations: - With the knowledge o f the column loads

    and moments at base and the soil data, foundations for columns are

    designed

    The following is a lis t o f different t ypes of foundations in o rder

    to preference with a view to economy: (i) Ind ividual footings ( ii)

    Combinat ion of individual and combined footings ( iii) Strip footings

    with reta ining wall act ing as str ip beam wherever applicable; ( iv) Raft

    foundations of the t ypes (a) Slab (b) beam-slab.

    The brick wall footings are also designed at this stage. Often,

    plinth beams are provided to support brick walls and also to act as

    earthquake t ies in each p rincipal d irect ion. Plinth beams, retaining wal l

    if any, are a lso designed at this stage, being considered as part of

    foundations.

    Important Considerations in design o f Foundations:-

    a) Introduction: - Foundations are structural elements that transfer loads from the bu ilding or ind ividual column to the earth. If these loads are to be properly transmitted, foundations must be designed to prevent excessive sett lement or rotation, to minimize differentia l sett lement and to provide adequate safety aga inst slid ing and over turning.

    b) Depth of foundation:-

    Depth of foundation below ground level may be obtained by using Rankine's

    formula

    2 p 1 – Sin Ø h = - - - - - - - - - - - - - - - γ 1 + Sin Ø Where h = Minimum dep th of foundation

    p = Gross bearing capacit y

    γ = Densit y of soil

    Ø = Angle of Repose of soil

  • BSNL India For Interna l Circulat ion Only Page: 47

    c) Recommendations o f IS 456 -2000, limit state design, bending,

    shear, cracking & development

    i) To determine the area required for proper transfer of total load on the soil, the

    total load (the combination of dead, live and any other load without multiplying it

    with any load factor) need be considered.

    To tal Load including Self Weight Plan Area o f foo ting = ------------------------------------- Allowable bearing capacit y of soil

    i i) IS 1904 – 1978, Code o f Practice for Structura l Safety of Buildings: shallow foundation, sha ll govern the genera l deta ils.

    i i i) Thickness of the edge of footing:-(Reference c lause 34.1 .2) The thickness at the edge shall not be less than 15 cm for footing on soils. iv) Dimension of pedestal:-

    In the case of plain Cement Concrete pedestals, the angle between the plane passing through the bottom edge of the pedestal and the corresponding junction edge of the column with pedestal and the horizontal plane shall be governed by the expression.

    100 qo Tan α (should not be less than) 0.9 x ----------- + 1 Fck

    Where qo = Calculated maximum bearing pressure at the base of the

    pedestal/ footing in N/mm2 fck = Character ist ic strength of concrete at 28 days in N/mm2

  • BSNL India For Interna l Circulat ion Only Page: 48

    (v) Bending Moment

    (Reference Clauses- 34.2.3 .1 & 34 .2.3.2)

    FAC E OF PEDESTA

    PLAIN CONCRETE PEDES TAL

    α

    Co lumn

    X Y

    X Y

    COLUMN

    PEDESTAL BASE

    FACE OF CO LUMN

  • BSNL India For Interna l Circulat ion Only Page: 49

    ISOLATED COLUMN FOOTING

    The bending Moment will be considered at the face of column, Pedestal or wall

    and shall be determined by passing through the section a vertical place which

    extends completely across the footing, and over the entire area of the footing or,

    one side of the said plane.

    (vi)Shear

    (Reference Clause 33.2.4.1)

    The shear strength of footing is governed by the following two factors:-

    a) The footing acting essentially as a wide beam, with a potential diagonal

    crack intending in a plane across the entire width, the critical section for

    this condition shall be assumed as a vertical section located from the face

    of the column, pedestal or wall at a distance equal to the effective depth of

    the footing in case of footings on soils.

    FOR ONE WAY BENDING ACTION

    For one way shear action, the nominal shear stress is calculated as follows:-

    Vu

    τv = -------

    b.d

    Where

    τv = Shear stress

    Vu = Factored vertical shear force

    b = Breadth of critical section

    d = Effective depth

    τv < τc ( τc = Design Shear Strength of Concrete Based on % of longitudinal tensile reinforcement refer Table 61 of SP-16)

  • BSNL India For Interna l Circulat ion Only Page: 50

    CRITICAL SECTION FOR ONE -WAY SHEAR

    (FOR TWO WAY BENDING ACTION)

    For two may bending action, the following should be checked in punching shear. Punching shear shall be around the perimeter 0.5 time the effective depth away from the face of column or pedestal. For two way shear action, the nominal shear stress is calculated in accordance with lause 31.6.2 of the code as follows:-

    Vu

    τv = ----------

    b0.d

    Where

    τv = Shear stress

    b0 = Periphery of the critical section

    d = Effective depth

    Vu = Factored vertical shear force

    B

    A

    C R IT IC AL SE C T ION

    d

    d

  • BSNL India For Interna l Circulat ion Only Page: 51

    When shear reinforcement is not provided, the nominal shear stress at the critical section should not exceed [Ks. τc]

    Where

    Ks = 0.5 + Bc (But not greater than 1)

    Short dimension of column or pedestal

    Bc = ----------------------------------------------------

    Long dimension of column or pedestal

    τc = 0.25 fek N/mm2

    Note:-It is general practice to make the base deep enough so that shear reinforcement is not required.

    (vii)Development Length

    (Reference Clause 34.2.4.3)

    The critical section for checking the development length in a footing shall be assumed at the same planes as those described for bending moment in clause 34.2.3 of code (as discussed 4.5 of the handout) and also at all other vertical planes where abrupt changes of section occur.

    (viii) Reinforcement:- The Min % of steel in footing slab should be 0.12% & max spacing should not be more than 3 times effective depth or 450 mm whichever is less. (Reference Clause 34.3) Only tensile reinforcement is normally provided. The total

    reinforcement shall be laid down uniformly in case of square footings. For rectangular footings, there shall be a central band, equal to the width of the footings. The reinforcement in the central band shall be provided in accordance with the following equation.

    Reinforcement in central Band width 2

    -------------------------------------------------- = ------

    Total reinforcement in short direction B + 1

    Where Long side of footing

    B = --------------------------- Short side of footing

  • BSNL India For Interna l Circulat ion Only Page: 52

    (ix)Transfer of Load at the Base of Column

    (Reference Clause 34.4)

    The compressive stress in concrete at the base of column or pedestal shall be

    transferred by bearing to the top of supporting pedestal or footing.

    The bearing pressure on the loaded area shall not exceed the permissible

    bearing stress in direct

    A1

    Compression multiplied by a value equal to ------

    A2

    but not greater than 2

    Where

    A1 = Supporting area for bearing of footing, which is sloped or

    stepped footing may be taken as the area of the lower base of

    the largest frustum of a pyramid or cone contained wholly with

    in the footing and having for its upper base, the area actually

    loaded and having side slope of one vertical to two horizontal.

    A2 = Loaded area at the column base.

    For limit state method of design, the permissible bearing stress shall be = 45 fek

    4.91 If the permissible bearing stress is exceeded either in column concrete or in

    footing concrete, reinforcement must be provided for developing the excess force.

    The reinforcement may be provided either by extending the longitudinal bars into

    the footing or by providing dowels in accordance with the code as give in the

    following:-

    1) Minimum area of extended longitudinal bars or dowels must be 0.5% of

    cross sectional area of the supported column or pedestal.

    2) A minimum of four bars must be provided.

    3) If dowels are used their diameter should not exceed the diameter of the

    column bars by more than 3 mm.

    4) Enough development length should be provided to transfer the

    compression or tension to the supporting member.

    5) Column bars of diameter larger than 36 mm, in compression only can be

    dowelled at the footing with bars of smaller diameters. Te dowel must

    extend into the column a distance equal to the development length of the

    column bar. At the same time, the dowel must extend vertically into the

    footing a distance equal to the development length of the dowel.

  • BSNL India For Interna l Circulat ion Only Page: 53

    C. Design of Floor slabs:- . Design o f f loor s labs and beams is taken up

    with the First Floor & upwards .The s labs are designed as one-wa y or

    two-way panels, taking the edge condit ions o f the supporting edges in

    to account, with the loading alread y dec ided as per functional use of

    slab panel.

    The design of floor slab is carried out as per clause 24.4 &

    37.1.2 & Annexure D o f IS: 456-2000. The Bending moment

    coefficients are to be taken from table- 26 of the code depending upon

    the support condit ion & bending moment calcu lated & reinforcement

    steel may be calculated from the charts of SP-16. The slab design for

    particular floor may be done in tabular form as shown below.

  • BSNL India For Interna l Circulat ion Only Page: 54

    SLAB DESIGN

    Name of

    project:-

    Level of s lab

    Slab ID

    Edge condit io n

    Tota l load in

    KN/Sq.m w

    Short

    spa n lx m

    long spa n ly m

    ly/lx

    1.5 *w* lx *lx

    sl

    ab

    th

    ic

    kne

    s

    s

    in

    mm

    Shor t span Mome nt KN-M

    Steel in short span

    Long spa n moment KN-

    M

    St ee l in

    long span

    α

    x

    (

    +

    )

    Α

    x

    (

    -

    ) mux+

    m

    u

    x

    -

    S

    t

    e

    e

    l

    Α

    y

    (

    +

    )

    α

    y

    (-

    )

    m

    u

    y

    +

    m

    u

    y

    -

    Stee

    l

    1 2 3 4 5 6 7 8 9 1

    0 11= 7 x 9

    1

    2

    =

    7

    x1

    0

    1

    3 1

    4

    1

    5

    1

    6

    =

    7

    x1

    4

    1

    7

    =

    7

    x1

    5

    1 8

    S1

    Two Adj . Edge. Discont . (Case No.4)

    8.50

    3.50

    5.25 1.5

    156.80

    120

    0.056

    0.075

    8.78

    11.76

    0.035

    0.047

    5.49

    7.37

    S2

  • BSNL India For Interna l Circulat ion Only Page: 55

    Method of calculation of steel from Tables of SP-16 for slab design

    Determine the main reinforcement required for a slab with the following data:

    Factored moment Mu 9.60 kN.mper Metre width

    Depth of slab 10 cm

    Concrete mix M 20

    Characteristic strength a) 415 N/mm2

    METHOD OF REFERRING TO TABLES FOR SLABS Referring to table 35 (for fck=20 & fy = 415 N/mm

    2), directly we get the following

    reinforcement for a moment of resistance of 9.60 kN.m per Metre width:

    8 mm dia at 13 cm spacing or 10 mm dia at 210 cm spacing Reinforcement given in the table is based on a cover of 15 mm or bar diameter which-

    ever is greater.

    Check for Deflection:-Slab is also checked for control of Deflection as per clause

    23.2.1, 24.1 & Fig 4. of the IS:456-2000.

    D. Design of floor Beams:-. The beams are designed as continuous beams,

    monolithic with reinforced concrete columns with their far ends assumed fixed. The

    variation in the live load position is taken into account by following the two-cycle

    moment distribution. the moments are applied a face correction to reduce them to the

    face of the members. The moments due to horizontal loads are added to the above

    moments. Each section of the beam is designed for load factor of 1.5 for vertical load

    effect and with a load factor of 1.2 for the combined effects of the vertical and the

    horizontal loads.

    The effect of the shear due to vertical and horizontal loads is also similarly

    taken care of. It may be noted that the shear component due to wind or earthquake

    may be significant and it may affect the size and the range of shear stirrups. Bent- up

    bars are not effective for earthquake shear due to its alternating nature. The beam

    design can be easily done by a computer program which will give reinforcement at

    various critical sections along the length of the beam and also shear stirrups required

    it saves considerable time and labour of a designer.

    In manual method span of a beam is generally designed at three sections i.e

    at two supports & at Mid span. The each section is designed for factored Moment,

    Shear & equivalent shear for Torsion if any at a section.

  • BSNL India For Interna l Circulat ion Only Page: 56

    Two examples of beam design are given below illustrating calculation of

    steel reinforcement with help of SP-16.

    Example1.Singly Reinforced Beam

    Determine the main tension reinforcement required for a

    rectangular beam sect ion with the following data:

    Size o f beam 30 X 60 cm

    Concrete mix M 20

    Character ist ic strength 415 N/mm2 o f reinfo rcement

    Facto red moment 170 kN.m

    Assuming 20 mm dia bars with 25 mm clear cover, Effect ive depth= 600 – 25 – 20 /2 = 565 mm From Tab le D for fy = 415 N/ mm

    2 and f c k = 20 N/mm

    2

    Mu, l im/bd2 = 2.76 N/ mm2

    = 2.76/1000 X (1000)2

    = 2.76 X 103 kN/m2

    Mu, l im = 2.76 X 103 bd 2

    = 2.76 X 103 X 0.300 X0.565


Recommended