+ All Categories
Home > Documents > CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS...

CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS...

Date post: 07-Mar-2018
Category:
Upload: trinhhuong
View: 231 times
Download: 3 times
Share this document with a friend
33
29 CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS 3.1 INTRODUCTION The conventional three phase three wire inverters are suitable for supplying balanced three phase loads. But when the load is unbalanced, the four wire inverters become the best choice as they provide a neutral connection for a three phase unbalanced system using a fourth leg in the inverter topology. Four wire inverter is a method of providing a neutral connection for three phase four wire unbalanced systems using a four leg inverter topology by tying the neutral in high power UPS applications. Four leg inverter is able to provide a path for the neutral current, flexibility to control the neutral voltage and hence produces balanced voltage across each phase. In this section the four wire inverter for UPS system is simulated and results are verified with experimental researches. The analysis is based on power quality for linear and non linear loads particularly for rectifier loads. 3.2 BLOCK DIAGRAM OF THE PROPOSED UPS SYSTEM The block diagram of the four wire inverter UPS is depicted in Figure 3.1. When the main supply is ON, the rectifier provides power to the inverter as well as the battery. The load is always fed by the inverter. The main static switch is always OFF. Only when the UPS fails, the load will be connected directly to the supply mains through the static switch which will be
Transcript
Page 1: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

29

CHAPTER 3

FOUR WIRE INVERTER FOR UPS APPLICATIONS

3.1 INTRODUCTION

The conventional three phase three wire inverters are suitable for

supplying balanced three phase loads. But when the load is unbalanced, the

four wire inverters become the best choice as they provide a neutral

connection for a three phase unbalanced system using a fourth leg in the

inverter topology. Four wire inverter is a method of providing a neutral

connection for three phase four wire unbalanced systems using a four leg

inverter topology by tying the neutral in high power UPS applications. Four

leg inverter is able to provide a path for the neutral current, flexibility to

control the neutral voltage and hence produces balanced voltage across each

phase. In this section the four wire inverter for UPS system is simulated and

results are verified with experimental researches. The analysis is based on

power quality for linear and non linear loads particularly for rectifier loads.

3.2 BLOCK DIAGRAM OF THE PROPOSED UPS SYSTEM

The block diagram of the four wire inverter UPS is depicted in

Figure 3.1. When the main supply is ON, the rectifier provides power to the

inverter as well as the battery. The load is always fed by the inverter. The

main static switch is always OFF. Only when the UPS fails, the load will be

connected directly to the supply mains through the static switch which will be

Page 2: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

30

in ON state at that time. When the supply is off, then the inverter will be

supplied by the battery.

Figure 3.1 Block Diagram of the Conventional FWI based UPS System

If the mains static switch is not available, the load will be isolated

from supply at times of UPS failure. Thus an inverter is always on and it takes

power from the input ac supply or battery. The voltage feedback is given to

the controller which produces the necessary gating signals to the four wire

inverter switches. Under any unbalanced or nonlinear load circumstances, the

four wire inverter is used to provide the balanced and undistorted voltage to

the load (Eyyup et al 2007).

3.3 CIRCUIT DIAGRAM OF UPS SYSTEM

In four leg inverters the load neutral wire is connected to the fourth

leg as shown in Figure 3.2. This makes the control of neutral voltage more

flexible and hence produces balanced voltage Vdc across each phase. The two

additional power switches in four wire system, double the number of inverter

output states from 8(=23) to 16(=24).The UPS requires sinusoidal output with

minimum total harmonic distortion. It is achieved by using space vector pulse

width modulation technique. By this technique, the load voltage is compared

Page 3: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

31

with a reference voltage and the difference in amplitude is used to control the

modulating signal in the control circuit of the inverter. The circuit diagram

giving the load neutral point voltage for the three phase four wire inverter is

illustrated in Figures 3.2(a) and (b).

Figure 3.2 (a) Circuit Diagram of Three Phase Four Wire Inverter with Midpoint Capacitors

Figure 3.2 (b) Circuit Diagram of Three Phase Four Wire Inverter

Page 4: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

32

3.4 LITERATURE SURVEY

The paper proposed by Kumar et al (2005) a new software

implementation of SVPWM has given out a new way of implementing the

SVM technique in three phase inverter using MATLAB and PSIM software

packages. Space Vector PWM can be used to generate an averaged sinusoidal

voltage which utilizes DC bus voltage more efficiently and generates less

harmonic distortion. During voltage sag and power quality problems in UPS

the three phase inverters are not sufficient to provide quality power output.

The paper proposed by Pinheiro et al (2002), space vector modulation for

voltage-source inverters has given a brief description and implementation of

space vector modulation technique for various inverter configurations.

A generalized methodology is described in an understandable manner like

switching vectors, separation and boundary planes, as well as decomposition

matrices and also possible switching sequences are presented. However

attention has not been paid to predict the performance of inverter for

nonlinear loads.

The paper proposed by Mohd et al (2010) on four wire voltage

source inverters under unbalanced load conditions, the authors have

developed control functions and 3D SVM implementation for three-leg four

wire inverters. It is capable of providing good power quality to loads under

extreme unbalanced conditions. But it is inefficient during voltage sag

conditions. Broeck et al (1988) have analyzed the pulse width modulator

based on voltage space vectors concept to derive the switching instants for

voltage source inverters. It also gives a comparative study of space vector

concept and sinusoidal concept. Compared with SPWM the SVPWM can

work with higher modulation index. However the inverter is sensitive towards

nonlinearities, which is important especially at low modulation index.

Page 5: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

33

Lihua Li et al (2009) have discussed a new controller for three

phase four wire voltage generation inverters for generating high quality three

phase output voltages for all sorts of linear/nonlinear and balanced/unbalanced

loads. The proposed controller employs a circuit level decoupling method and

it is implemented by logic circuitry in combination with a control core and a

feedback signal processor. Almost all DC-DC control methods can be adapted

as the control core, while the feedback signal processor can be implemented

by either voltage compensator or current compensator. The implementation of

the controller is simple and flexible with only logic and analog circuitry

needed.

3.5 SPACE VECTOR MODULATION FOR THREE LEG FOUR

WIRE INVERTER

Space vector modulation is based on vector selection in the

(stationary) or in the dqo (rotating) reference frame. A set of three vectors Va,

Vb and Vc in the -frame can generate a normalized reference vector Vref in

the same plane using PWM averaged approximation. The average reference

vector can be obtained by sequentially applying these vectors in a modulation

period (Rajesh and Narayanan 2008).

T TT TS S1 21 1 1 1V dt= V dt+ V dt+ V dta cref bT T T TT T +T0 0S S S S1 1 2

(3.1)

where TS is the modulation period and T1 + T2 TS. Since Vref remains

constant during the modulation period, it can be approximated as

V =D .V +D .V +D .Va a c cref b b (3.2)

in which Da, Db and Dc are the duty cycles of vectors Va, Vb and Vc. In

3D-SVM algorithm, based on generating a zero-vector has been introduced.

Page 6: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

34

Still, the proposed algorithm has a drawback of stressing the Insulated Gate

Bipolar Transistors (IGBTs) unequally. In this work, another SVM algorithm

without using a zero-vector is launched. This algorithm based on vectors

compensation (compensated vectors approach) is more practical as it is not

only stressing the IGBTs equally but less as well. The proposed SVM

algorithm can be achieved through the following steps:

1. Determining the switching combinations and the corresponding

vectors.

2. Calculating the voltage drop related to each vector.

3. Identifying the position for each vector in the -space vector

diagram.

4. Identifying the reference vector position.

5. Calculating the duty cycles.

6. Building a vector sequence.

7. Computing pulse patterns.

3.5.1 Steps One, Two and Three

In a similar way to two level three phase inverters, there are eight

different switching combinations where the output terminals will be

connected to +1/2 or -1/2 of the input DC voltage. However, unlike two-level

three-leg inverters none of these switching combinations is generating zero

voltage at the output terminals, which make the implementation of SVM more

difficult. Table 3.1 presents the eight possible switching vectors and the

corresponding output voltages related to the DC-voltage as reference voltage.

The switching vectors can be represented in the -coordinates using

Clarke’s transformation. Table 3.1 also shows the normalized -values of

Page 7: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

35

each switching vector. Figure 3.3 depicts representation of these switching

vectors in space.

Figure 3.3 3D Space Vectors

The vectors are taking place in layers according to the value of their

component. Three vectors (V2, V4 and V6) are located at the layer

V =1/6(VDC). The vectors (V1, V3 and V5) are lying at the layer

V = -1/6(VDC). The vectors V7 and V0 are located at the axis at

V =1/2(VDC) and V =-1/2(VDC), respectively. The projection of the vectors in

the frame is shown in Figure 3.3 which is divided into six prisms. The six

prisms in the space are shown in Figure 3.4. Each prism is divided into

two tetrahedrons, upper and lower tetrahedron. Each tetrahedron is

characterized by three vectors.

Page 8: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

36

Table 3.1 Switching States the Corresponding Output Voltages and Normalized Components of each Switching Vector

Switches

(ON)Vectors

Normalised output voltage Normalised -components

Va /VDC Vb /VDC Vc /VDC V /VDC V /VDC V /VDC

S4 S6 S2 V0 -1/2 -1/2 -1/2 0 0 -1/2

S1 S6 S2 V1 1/2 -1/2 -1/2 2/3 0 -1/6

S1 S3 S2 V2 1/2 1/2 -1/2 1/3 1/ 3 1/6

S4 S3 S2 V3 -1/2 1/2 -1/2 -1/3 1/ 3 -1/6

S4 S3 S5 V4 -1/2 -1/2 1/2 -2/3 0 1/6

S4 S6 S5 V5 -1/2 -1/2 1/2 -1/3 -1/ 3 -1/6

S1 S6 S5 V6 1/2 1/2 1/2 1/3 -1/ 3 1/6

S1 S3 S5 V7 1/2 1/2 1/2 0 0 ½

3.5.2 Step Four: Reference Vector Position Identification

Given that 12 tetrahedrons exist, there are 12 possibilities for the

reference vector position. The position of the reference vector can be

identified using the boundary planes limiting the tetrahedron. Each

tetrahedron is limited by three planes. The boundary planes can be determined

by means of the following linear equations.

1E : V = 0 7 1 3

(3.3)

E :V - 3 V + 4 V = 0 1 2 (3.4)

3 1E : V - V = 0 2 7 6 6

(3.5)

E :-2 V + 2 V = 0 2 3 (3.6)

Page 9: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

37

3 1E : V + V = 0 3 7 6 6

(3.7)

E :V + 3 V + 4 V = 03 4 (3.8)

Figure 3.4 3D Prisms for Three Leg Four Wire Inverter

The zero-vector is compensated by the vectors V0 and V7, both

lying against each other direction on the -axis. The reference vector can be

expressed as follows

V =D .V +D .V +D .Va a cref b b (3.9)

Page 10: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

38

where

V =Vc 7 and D =D -D7 0

V =Vc 0 and D =D -D70 (3.10)

3.5.3 Step Five: Duty Cycles Calculation

Once the target tetrahedron is defined the nearest three vectors are

chosen. By normalizing the standard vectors at the intermediate circuit

voltage, the duty cycles in matrix form can be written as follows

VD -refa -11D = V V V Va cb b -refVdcD Vc -ref

(3.11)

The duty cycles for the vectors V7 and/or V0 can be determined

according to the position of the reference vector. For the upper tetrahedron

and for the lower tetrahedron it is found using the equation

1-(D +D )+Da bD = D =D -D7 702 (3.12)

1-(D +D )+Da bD = D =D -D70 02 (3.13)

Table 3.2 Vector Sequence for the Upper and Lower Tetrahedrons in Each Prism

Prism Sequence 1 v0-v1-v2-v7-v7-v2-v1-v02 v0-v3-v2-v7-v7-v2-v3-v03 v0-v3-v4-v7-v7-v4-v3-v04 v0-v5-v4-v7-v7-v4-v5-v05 v0-v5-v6-v7-v7-v6-v5-v06 v0-v1-v6-v7-v7-v6-v1-v0

Page 11: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

39

3.5.4 Steps Six and Seven: Building Vector Sequence and Pulse

Pattern Computation

In order to reduce the current ripples, switching vectors adjacent to

the reference vector should be selected as they produce non conflicting

voltage pulses (same voltage polarity). Table 3.2 shows the vector sequence

for the upper and lower tetrahedrons in each prism. An example for

determining the switching sequence for the first prism is shown in Figure 3.5 (a).

The pulse sequence can be achieved by comparing the duty cycles with a

carrier signal. The pulse sequence for phase a, b and c are shown in Figure 3.5 (b)

for the same mentioned case.

(a) (b)

Figure 3.5 Building Vector Sequence and Pulse Pattern Computation (a) Steps for the Modulation in the First Prism and (b) Symmetric Modulation in the First Prism

Page 12: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

40

3.6 OPERATING MODES OF FOUR WIRE SYSTEM

Three phase four wire VSI is commonly used for three phase

voltage generation. It consists of eight switches Tap Txn and filters comprising of

inductors LA LX and capacitors CA CC, interfacing a dc source with three

phase ac loads. The switches operate at switching frequency to chop the dc

bus voltage E into high frequency chunks; the LC network filter out the

switching harmonics and pass the fundamental to output terminals. The VSI is

very well controlled and it is able to generate balanced high quality AC output

voltage irrespective of the loading conditions.

Figure 3.6 Three Phase Output Voltage

Figure 3.7 Vector Diagram of Three Phase Output Voltage

Page 13: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

41

Figure 3.8 Active Voltage Vectors for Region (a) 0°-60°, (b) 120°-180° and (c) 180°-240°

The expected three phase output voltage vectors are depicted in Figure 3.6. It is equivalent to an equilateral triangle in the vector plane as

illustrated in Figure 3.7, where the three outer lines represent line voltages VAB, VBC and VCA, the three inner lines correspond to phase voltages VAO,

VBO and VCO. It is observed that there are only three independent lines within the triangle, i.e., if the position and length of three independent lines are

determined then the rest of the lines in the triangle are automatically settled. For example, if lines that correspond to VAB, VBC and VBO are drawn, lines

that represent VAO, VCO and VAC will be determined by the nature of this vector triangle. This indicates that the active control of any two line voltages

and one phase voltage can lead to the full control of a three phase four wire system. The circuit level decoupling method proposed for three phase three

wire system can therefore be extended to three phase four wire domain based on the earlier analysis.

As shown in Figure 3.7, one line cycle is divided into six regions.

In region 0°-60°, 120°–180°and 240°-300°, the voltage waveforms as

depicted in Figure 3.8 follow the same pattern, i.e., one phase voltage is

always lower than the other two. The selection of actively controlled voltage

vectors is as follows. The lowest phase voltage is selected as the active phase

voltage under control (in 0°-60°, it is –VBO) and the line voltages between the

lowest phase voltage and the other two phases are selected as the active line

voltages under control (in 0 –60 , it is VAB and VCB).

Page 14: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

42

The switching logics of the proposed controller are sustained in the

following method. Table 3.3 shows the switching parameters (in 0º - 60º, it is

VAB and VCB). The switching sequence in Table3.3 minimizes the switching

stress and harmonics and thus improves the four wire inverter operation.

Figure 3.9 illustrates the equivalent circuit for the proposed three phase, four

wire voltage source inverter during (0-60o) internal mode.

Table 3.3 Switching Logics for Proposed System

Switches

Intervals S1 S2 S3 S4 S5 S6 N1 N2

-60 ON OFF OFF OFF OFF ON ON OFF 60 -120 ON ON OFF OFF OFF OFF OFF ON120 -180 OFF ON ON OFF OFF OFF ON OFF 180 -240 OFF OFF ON ON OFF OFF OFF ON240 -300 OFF OFF OFF ON ON OFF ON OFF 300 -360 OFF OFF OFF OFF ON ON OFF ON

Figure 3.9 Equivalent Circuit for Four Wire System during (a) 00-600

and (b) 60°-120°

Page 15: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

43

Figure 3.10 Active Voltage Vectors during (a) 60°-120°, (b) 180°- 240° and (c) 300°-360°

1. The switch Tin (a, b, c) for the phase with the lowest voltage is

always turned ONand the corresponding Tip for this phase is

always turned OFF.

2. The switches Tin and Tip for the other two phases are driven

complementarily, where the duty ratio of one Tip is defined by

Dp; the duty ratio of the other Tip is defined by dn.

3. The switches Txn and Txp for the neutral phase are driven

complementarily, where the duty ratio of Txp is defined by Dx.

With this treatment, Figure 3.2 becomes equivalent to Figure 3.9 (a)

in 0°–60° region, which can be further rearranged into Figure 3.9 (b).

The same equivalent circuit is also applicable to 120°-180° and 240°-300°

regions, where the selection of active phase/line voltages follows Figure 3.8.

Page 16: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

44

Figure 3.11 Equivalent Circuit for Four Wire System during (a) 00-600

and (b) 60°-120°

While in region 60°-120°,180°-240and 300°-360°, the voltage

waveforms in Figure.3.6.have another pattern, i.e., one phase is always higher

than the other two. The selection of actively controlled voltage vectors is as

follows: the highest phase voltage is selected as the active phase voltage

under control (in 60°-120°, it is VAO); the line voltages between the highest

phase voltage and the other two phases are selected as the active line voltages

under control (in 60°-120°, it is VAB and VAC). Figure 3.10 shows the selected

active voltage vectors for region 60°-120°, 180°-240°and 300°-360°.

Correspondingly following modulation method is used.

For further analysis, following assumptions are made.

1) LA=LB=LC=LX=L

2) CA=CB=CC=C

Page 17: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

45

3) Switching frequency is much higher than fundamental

frequency

4) dp>dn>dx

Equivalent circuit for four wire system during (a) 00-600 and

(b) 600-1200 is shown in Figure 3.11. The first three assumptions usually

become true in three phase voltage generation application, while the last one

is made for the ease of analysis. Detailed analysis is performed in region 0°-

60° as illustrated in Figure 3.9 (b), while similar derivation can be extended to

all other regions. With output voltages VAB, VCB and VBO following their

respective reference voltages, Figure 3.9 (b) is redepicted with outputs

replaced by three voltage sources for the ease of analysis. Assuming

d >d >dp n x , the equivalent circuit in one switching cycle is depicted. The

voltage applied on each inductor in one switching cycle is derived through the

application of superposition, i.e., combining the voltage drop from individual

voltage.

3.7 STABILITY ANALYSIS OF THREE PHASE FOUR WIRE

INVERTER

The physical elements of the UPS system are replaced with

equivalent control blocks and the system depicted in Figure 3.12 can be

represented with a continuous time system block diagram illustrated in

Figure 3.13. In the diagram, each component of the UPS system is modeled

with an appropriate continuous time transfer function block which will be

detailed in the following discussion. Employing this model, the system

stability can be investigated via tools such as Routh-Hurwitz stability

criterion. The controller gain limits for stability can be established based on

the control bandwidth requirements and the controller parameters can then be

optimized based on the control bandwidth requirements.

Page 18: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

46

CanV

ci

Figure 3.12 Design of the UPS Control System

ˆ ( )CV S

*( )CV S

* ( )invV S

Figure 3.13 Simplified S-Domain Mathematical Model

Figure 3.13 depicts the block diagram of the UPS control system

which includes the control elements with their simplified S-domain

mathematical model. The UPS system control block diagram includes

measurement delay block, sampling delay block and PWM delay blocks.

Page 19: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

47

ˆ ( )CV S

( )CV S

*( )CV S

( )cI Sˆ ( )cI S

( )LI S

0( )I S

11 samps

11 PWMs

1

s LL I1cs

11 s measure

11 s measure

Figure 3.14 First Order Delay Transfer Function

In the implemented system, the output voltages are measured by

isolated voltage transducers with considerable delay and are applied to the

digital control unit as the feedback signals of the closed loop system. These

output voltages are the main control variables of the four leg inverter based

UPS system. This results in a measurement delay ( measure). Thus, the

measurement delay depicted in Figure 3.14 can be modeled with a first order

delay transfer function with unity gain.

The current transducer is used to measure the capacitor current.

Similar to the modeling of the voltage measurement delay, current

measurement delay can be modeled with a first order delay transfer function.

The sampled feedback signals are utilized in the control algorithm

to generate the voltage reference signals (VC*), these voltage reference signals

are applied to the PWM blocks at the end of the sampling period (Ts). For the

sake of simplicity, the delays, which are discussed above and illustrated in

Figure 3.14 can be considered as total system delay and can be modeled with

Page 20: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

48

an equivalent single delay block as shown in Figure 3.15. The system in

Figure 3.15 can be represented with simplified control block diagrams as

shown in Figure 3.16. In the diagram, Gv(s) is the transfer function of the

inverter reference voltage to output voltage.

ˆ ( )CV S

( )CV S

*( )CV S

( )cI S

( )LI S

0( )I S

11 Ts

1

s LL I1cs

( )cG s

Figure 3.15 Equivalent Single Delay Block

ˆ ( )CV S

*( )CV S

( )cI S

( )cG s

( )iG s

( )vG s

Figure 3.16 Simplified Control Block Diagram

The output voltage controlled transfer function of Figure 3.16 is

given in Equation (3.14). For simplification, single resonant frequency

controller rather than a resonant filter bank is taken for stability analysis

1G (s)=v 3 2L C s +C (L + r )s +[C (K +r )+ ]s+1T T L L Tf f f f f ad

(3.14)

Page 21: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

49

where,

Kad- is gain appears to play a significant role in determining the

Characteristic equation and the stability behavior of the system.

T measure samp PWM (3.15)

In order to investigate the stability of the given linear system, the

Routh-Hurwitz stability criterion is employed. For this purpose the output

voltage is expressed in Equation (3.16) in terms of numerator and

denominator terms C(s), D(s) and R(s) as given in Equations (3.17) to (3.19).

R(s) is the characteristic equation of the control system.

C(s) D(s)*V (s)= V (s)+ I (s)oC CR(s) R(s) (3.16)

2 2C(s)=K s +2K s+K (m )p p eim (3.17)

2 2D(s)=-(L s+r )(1+s )(s +(m ) )eL Tf (3.18)

5 4 3 2 5R(s)=a s +a s +a s +a s +a s +a50 1 2 3 0 (3.19)

In the above denominator term R(s), the coefficients are given in

terms of the circuit parameters and controller parameters in Equations (3.20)

to (3.24).

1 f T L fa =C ( r +L ) (3.20)

2 f L T f e ad T2a =C (r + L (m ) +K )+ (3.21)

3 f e T L f p2a =C (m ) ( r +L )+K +1 (3.22)

Page 22: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

50

2 24 f e L ad im T ea =C (m ) (r +K )+K + (m ) (3.23)

25 e pa =(m ) (K +1) (3.24)

The Routh-Hurwitz stability criterion states that the necessary (but not

sufficient) condition for stability is that all the coefficients of the

characteristic equation R(s) must be positive. Since for the system stability

negative feedback is employed, all the controller coefficients Kad, Kimand Kp

must be positive by definition. With this assumption, reviewing the above

coefficient equations, it can be clearly seen that all the coefficients are

positive for positive controller gains. Thus, the necessary condition for

stability is satisfied. The sufficient condition involves ordering the

coefficients according to the Routh-Hurwitz criterion ordering table shown in

Table 3.4 and then obtaining the additional coefficients b1, b2, c1, c2, d1, e1

defined in Equations (3.25) to (3.30). Using the values of coefficients from

the Table 3.4, stability analysis is done and shown in Figure3.17

Table 3.4 Routh Hurwitz Criterion

S5 a0 a2 a4

S4 a1 a3 a5

S3 b1 b2 0

S2 c1 c2

S d1 0

e1

Page 23: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

51

2T L T p f1 2 0 3

1 f ad L1 T L f

r - K La a -a ab = =C (K +r )+

a r +L (3.25)

2p e f T21 4 0 5

2 im ad L f e1 T L f

K (m ) La a -a ab = =K +(K +r )C (m ) -

a r +L (3.26)

2f T L f f e L

1 3 2 1 im1 p

1 f ad T p

C ( r +L )C (m ) r Kb a -b a

c = =K +1-b C K - K

(3.27)

21 5 3 12 e p

1

b a -b ac = =(m ) K +1

b (3.28)

1 2 1 11

1

c b b cd

c

-= (3.29)

21 2 1 11 e p

1

d c -c de = =(m ) (K +1)d

(3.30)

Assuming that f T LL >> r and ad LK r>> the above coefficients can be

approximated in the following equations.

1 f ad T pb C K - K (3.31)

22 im e f ad T pb K +(m ) (C K - K ) (3.32)

f f im1 p

f ad T p

C L Kc K +1-C K - K

(3.33)

Figure 3.17 shows the bode plot of open loop controller for three

phase four wire inverter. From the Figure it is observed that the system is

stable for the input voltages of 180V to 270V.

Page 24: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

52

-150

-100

-50

0

10-4 10-3 10-2 10-1 100 101 102 103-225

-180

-135

-90

-45

Bode DiagramGm = 246 dB (at 5.77e+005 rad/sec) , Pm = -180 deg (at 0 rad/sec)

Frequency (rad/sec)

Figure 3.17 Magnitude and Phase Plots of Output Voltage Control of Four Wire Inverter

3.8 SIMULATION RESULTS

The proposed three phase four wire inverter with controller is tested

with online UPS system and it is simulated on Matlab/Simulink. The AC

output voltage is generated by the four wire inverter with filter and without

filter condition. To validate the simulation results 3kVA, 1200V, 10A, 50HZ

prototype four wire inverter is fabricated in the laboratory.

From the simulation analysis it is evident that the neutral leg

provides a lower impedance loop for unbalanced current and triplen

harmonics, so the imbalance of output is drastically reduced. The neutral

inductance LX can reduce the current that flows through the switching

components of neutral leg. Figure 3.18 shows the simulated line and phase

Page 25: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

53

voltages of four wire inverter. It shows the neutral voltage during balanced

condition. Figure 3.19 shows the line and phase voltages during unbalanced

conditions. Figure 3.20 shows the simulated line current waveforms with filter

circuit. Figure 3.21 shows the simulated waveform of four wire inverter with

controller. The controller provides constant terminal voltage during sag conditions.

Figure 3.18 Simulation Result for Output Line Voltage after Filter

Figure 3.19 Simulation Result for Output Line Voltage before Filter

Page 26: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

54

Figure 3.20 Simulation Result for Output Current

Figure 3.21 Closed Loop Output Voltage for Controller

To predict the performance of the proposed UPS system, the load

test is conducted and the corresponding input current and output voltage THD

are measured and tabulated as shown in Table 3.5.The input THD is almost

same for different loading conditions but the output voltage THD is varying

with respect to load variations as shown in Figure 3.22. The input current

Page 27: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

55

THD is varying with respect to switching frequency as shown in Figure 3.23.

The higher the value of the switching frequency, more is the harmonics

injected into the input side of the converter and hence greater is the value of

THD.

0 2 4 6 8 10 12 14 16 18 200

0.5

1

1.5

Harmonic order

Fundamental (50Hz) = 190.1 , THD= 4.86%

Figure 3.22 THD for the Terminal Voltage of Four Wire Inverter With Filter

0 2 4 6 8 10 12 14 16 18 200

5

10

15

20

Harmonic order

Fundamental (50Hz) = 190 , THD= 30.99%

Figure 3.23 THD for the Terminal Voltage of Four Wire Inverter Without Filter

Page 28: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

56

3.9 EXPERIMENTAL RESULTS AND DISCUSSION

To validate the simulation results, an experimental setup of 1kVA,

440v, 50Hz 3phase four wire inverter is fabricated in the laboratory. The

simulation results very well coincide with experimental results. The PIC

microcontroller is used to generate the gating pulses to the four wire inverter.

The power IGBT is used as power switch. The line voltages across the phases

without filter at switching frequency of 1200 HZ are measured and shown in

Figures 3.24 to 3.28. From the Figures it is observed that the magnitudes of

line voltages of all the phases are equal with desired phase displacement

because of the neutral voltage control in FWI where as it is not so in

traditional three wire inverter.

The disturbances if any is due to the approximation in the time

calculation as explained below. The first step was to determine the values for

all parameters used to obtain the time variables. These parameters affect the

values of time variables and also the pulse width of the output pattern. The

fundamental frequency was set to the desired value of 50 Hz. The

implementation process of the project was initially conducted for low

switching frequency of 300Hz. Next the sampling frequency was increased to

1200 Hz and results were obtained.

Figure 3.24 Line-Line Voltage (A-B) of FWI at Switching Frequency of 1200Hz

Page 29: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

57

Figure 3.25 Line-Line Voltage (B-C) of FWI at Switching Frequency of 1200Hz

Figure 3.26 Line-Line Voltage (C-A)of FWI at Switching Frequency of 1200Hz

Figure 3.27 shows the line to line voltages of FWI with filter. From the Figure it is

observed that the voltage spikes are present in some of the lines where the

magnitude of voltage is around 270 V. This may damage the switches during the

active mode of operation.

Page 30: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

58

Figure 3.27 Line-Line Voltage of FWI at Switching Frequency of 1200Hz with Filter

Figures 3.28 to 3.30 show the gating pulses for the three legs of the inverter.

Each figure shows two pulses that are complementary in operation .i.e.

whenever upper switch is on, lower switch is off. Table 3.5 shows the line

voltages of four wire inverter across the phases with filter at switching

frequency of 300 Hz.

Figure 3.28 Gating Pulses for Upper and Lower Switches of A Phase

Page 31: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

59

Figure 3.29 Gating Pulses for Upper and Lower Switches of B Phase

Figure 3.30 Gating Pulses for Upper and Lower Switches of C Phase

Table 3.5 gives the variation of output voltage THD for two

different value of switching frequency in FWI. From the table it is observed

that the % of THD of output voltage is around 80% higher than the % THD

with filter. The lower value of switching frequency introduced more

Page 32: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

60

harmonics in its output voltage. The percentage of THD in 300Hz switching

frequency is around 60% higher than THD in 1200Hz switching frequency.

Table 3.5 Voltage and THD at Two Switching Frequencies of FWI

SwitchingFrequency

(HZ) Phases

DC LinkVoltage

(V)

Vrms

(V)Vpeak

(V)

%THD Before Filter

After Filter

300A-B 190 115 192 81 12.4B-C 190.1 116 198 85 8.4C-A 190 115 191 89.5 8.2

1200A-B 190 100 120 32.34 6B-C 189.7 102 117 31.12 5.7C-A 190.2 100 115 30.99 4.86

Results taken are for two different switching frequencies i.e. 300Hz

and 1200Hz. First the experiment was performed for 300Hz. Later the number

of samples was increased to 24. PIC has following advantages like low cost,

wide availability, extensive collection of application notes, availability of low

cost or free development tools etc. PIC 16f877A is a low end processor and

hence it has limitations in terms of processing speed where a lot of online

mathematical calculation is involved. Probably it won’t be a problem with

high level processors like DSPIC, DSP, FPGA etc. Considering the accuracy

of time calculation, one should use float numbers in order to obtain accurate

time variables. All embedded C program is converted to assembly level

before compiling and time consumption for processing float variables is more

in assembly language. Rounding up the time values to nearest integer by

means of some offline calculations, it was possible to get the fundamental

frequency of 50Hz.Results were taken for two sets of sampling frequency i.e.

300Hz and 1200Hz .As the Sampling frequency increases, THD decreases.

Page 33: CHAPTER 3 FOUR WIRE INVERTER FOR UPS APPLICATIONS …shodhganga.inflibnet.ac.in/bitstream/10603/16548/8/08_chapter3.pdf · FOUR WIRE INVERTER FOR UPS APPLICATIONS ... But when the

61

3.10 SUMMARY

The basic operation and drawbacks of conventional four wire

system are briefly explained in this chapter. In order to overcome these

drawbacks, a solid state four wire inverter has been implemented for the UPS

systems. The four wire inverter based UPS system is simulated and analyzed

for various input and output conditions. The stability of the system is

analyzed using transfer function model. The Space Vector PWM scheme is

used to control the FWI. Two switching frequencies are used to predict the

performance of FWI. At higher switching frequency the FWI provides lower

value of THD whereas switching losses are higher. The dead time in the

PWM inverter the output and input side THD is around 31 % and 42 %

respectively. The limitations in the conventional FWI are overcome by

introduction of FWZSI and ZSMLI for UPS systems and to be discussed in

chapter 4 and 5.


Recommended