+ All Categories
Home > Documents > CHAPTER 3 STATIC SYNCHRONOUS SERIES...

CHAPTER 3 STATIC SYNCHRONOUS SERIES...

Date post: 13-Mar-2020
Category:
Upload: others
View: 0 times
Download: 0 times
Share this document with a friend
30
29 CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATOR 3.1 INTRODUCTION Series compensation is a means of controlling the power transmitted across transmission lines by altering or changing the characteristic impedance of the line. The power flow problem may be related to the length of the transmission line. The transmission line may be compensated by a fixed capacitor or inductor to meet the requirements of the transmission system. When the structure of the transmission network is considered, power flow imbalance problems arise. Inadvertent interchange occurs when the power system tie line becomes corrupted. This is because of unexpected change in load on a distribution feeder due to which the demand for power on that feeder increases or decreases. The generators are to be turned on or off to compensate for this change in load. If the generators are not activated very quickly, voltage sags or surges can occur. In such cases, controlled series compensation helps effectively. 3.2 SERIES COMPENSATOR Series compensation, if properly controlled, provides voltage stability and transient stability improvements significantly for post-fault systems. It is also very effective in damping out power oscillations and mitigation of sub-synchronous resonance (Hingorani 2000).
Transcript
Page 1: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

29

CHAPTER 3

STATIC SYNCHRONOUS SERIES COMPENSATOR

3.1 INTRODUCTION

Series compensation is a means of controlling the power

transmitted across transmission lines by altering or changing the characteristic

impedance of the line. The power flow problem may be related to the length

of the transmission line. The transmission line may be compensated by a

fixed capacitor or inductor to meet the requirements of the transmission

system. When the structure of the transmission network is considered, power

flow imbalance problems arise. Inadvertent interchange occurs when the

power system tie line becomes corrupted. This is because of unexpected

change in load on a distribution feeder due to which the demand for power on

that feeder increases or decreases. The generators are to be turned on or off to

compensate for this change in load. If the generators are not activated very

quickly, voltage sags or surges can occur. In such cases, controlled series

compensation helps effectively.

3.2 SERIES COMPENSATOR

Series compensation, if properly controlled, provides voltage

stability and transient stability improvements significantly for post-fault

systems. It is also very effective in damping out power oscillations and

mitigation of sub-synchronous resonance (Hingorani 2000).

Page 2: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

30

3.2.1 Voltage Stability

Series capacitive compensation reduces the series reactive

impedance to minimize the receiving end voltage variation and the possibility

of voltage collapse. Figure 3.1 (a) shows a simple radial system with feeder

line reactance X, series compensating reactance Xc and load impedance Z.

The corresponding normalized terminal voltage Vr versus power P plots, with

unity power factor load and 0, 50, and 75% series capacitive compensation,

are shown in Figure 3.1(b). The “nose point” at each plot for a specific

compensation level represents the corresponding voltage instability. So by

cancelling a portion of the line reactance, a “stiff” voltage source for the load

is given by the compensator.

(a) (b)

Figure 3.1 Transmittable power and voltage stability limit of a radial

transmission line as a function of series capacitive

compensation

3.2.2 Transient Stability Enhancement

The transient stability limit is increased with series compensation.

The equal area criterion is used to investigate the capability of the ideal series

compensator to improve the transient stability.

Page 3: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

31

Figure 3.2 Two machine system with series capacitive compensation

Figure 3.2 shows the simple system with the series compensated

line. Assumptions that are made here are as follows:

The pre-fault and post-fault systems remain the same for the

series compensated system.

The system, with and without series capacitive compensation,

transmits the same power Pm.

Both the uncompensated and the series compensated systems

are subjected to the same fault for the same period of time.

Figures 3.3 (a) and (b) show the equal area criterion for a simple

two machine system without and with series compensator for a three phase to

ground fault in the transmission line. From the figures, the dynamic

behaviour of these systems are discussed.

Prior to the fault, both of them transmit power Pm at angles 1 and

s1 respectively. During the fault, the transmitted electric power becomes

zero, while the mechanical input power to the generators remains constant

(Pm). Hence, the sending end generator accelerates from the steady-state

angles 1 and s1 to 2 and s2 respectively, when the fault clears. In the

figures, the accelerating energies are represented by areas A1 and As1. After

fault clearing, the transmitted electric power exceeds the mechanical input

Page 4: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

32

power and therefore the sending end machine decelerates. However, the

accumulated kinetic energy further increases until a balance between the

accelerating and decelerating energies, represented by the areas A1, As1 and

A2, As2, respectively, are reached at the maximum angular swings, 3 and s3

respectively. The areas between the P versus curve and the constant Pm line

over the intervals defined by angles 3 and crit, and s1 and scrit, respectively,

determine the margin of transient stability represented by areas Amargin and

Asmargin for the system without and with compensation.

(a) (b)

Figure 3.3 Equal area criterion to illustrate the transient stability

margin for a simple two-machine system (a) without

compensation and (b) with a series capacitor

Comparing figures 3.3(a) and (b), it is clear that there is an increase

in the transient stability margin with the series capacitive compensation by

partial cancellation of the series impedance of the transmission line. The

increase of transient stability margin is proportional to the degree of series

compensation.

Page 5: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

33

3.2.3 Power Oscillation Damping

Power oscillations are damped out effectively with controlled series

compensation. The degree of compensation is varied to counteract the

accelerating and decelerating swings of the disturbed machine(s) for damping

out power oscillations. When the rotationally oscillating generator accelerates

and angle increases (d /dt > 0), the electric power transmitted must be

increased to compensate for the excess mechanical input power and

conversely, when the generator decelerates and angle decreases (d /dt < 0),

the electric power must be decreased to balance the insufficient mechanical

input power.

Figure 3.4 Waveforms illustrating power oscillation damping by

controllable series compensation (a) generator angle (b)

transmitted power and (c) degree of series compensation

Figure 3.4 shows the waveforms describing the power oscillation

damping by controllable series compensation. Waveforms in figure 3.4(a)

show the undamped and damped oscillations of angle around the steady

Page 6: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

34

state value 0. The corresponding undamped and damped oscillations of the

electric power P around the steady state value P0, following an assumed fault

(sudden drop in P) that initiated the oscillation are shown by the waveforms in

figure 3.4(b). Waveform 3.4 (c) shows the applied variation of the degree of

series compensation, k applied. ‘k’ is maximum when d /dt > 0, and it is

zero when d /dt < 0.

3.2.4 Immunity to Sub-synchronous Resonance

The sub-synchronous resonance is known as an electric power

system condition where the electric network exchanges energy with a turbine

generator at one or more of the natural frequencies of the combined system

below the synchronous frequency of the system. With controlled series

compensation, the resonance zone is prohibited for operation and the control

system is designed in such a way that the compensator does not enter that

area. Also, an SSSC is an ac voltage source operating only at the fundamental

output frequency and its output impedance at any other frequency should be

zero. The SSSC is unable to form a series resonant circuit with the inductive

line impedance to initiate sub-synchronous system oscillations.

3.2.5 Types of Series Compensators

Series compensation is accomplished either using a variable

impedance type series compensators or a switching converter type series

compensator.

3.2.5.1 Variable impedance type series compensators

The thyristor controlled series compensators are the variable type of

compensators. The type of thyristor used for the variable type series

compensators has an impact on their performance. The types of thyristors

Page 7: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

35

used in FACTS devices are Silicon Controller Rectifier (SCR), Gate Turn-Off

Thyristor (GTO), MOS Turn-Off Thyristor (MTO), Integrated Gate

Commutated Thyristor (GCT or IGCT), MOS Controlled Thyristor (MCT)

and Emitter Turn-Off Thyristor (ETO). Each of these types of thyristors has

several important device parameters that are needed for the design of FACT

devices. These parameters are di/dt capability, dv/dt capability, turn-on time

and turn-off time, Safe Operating Area (SOA), forward drop voltage,

switching speed, switching losses, and gate drive power.

The variable impedance type series compensators are GTO

thyristor controlled series compensator (GCSC), Thyristor Switched Series

Capacitor (TSSC) and Thyristor Controlled Series Capacitor (TCSC).

GTO Thyristor Controlled Series Capacitor (GCSC)

A GCSC consists of a fixed capacitor in parallel with a GTO

Thyristor as in figure 3.5which has the ability to be turned on or off. The

GCSC controls the voltage across the capacitor (Vc) for a given line current.

In other words, when the GTO is closed the voltage across the capacitor is

zero and when the GTO is open the voltage across the capacitor is at its

maximum value. The magnitude of the capacitor voltage can be varied

continuously by the method of delayed angle control (max = 0, zero =

/2). For practical applications, the GCSC compensates either the voltage or

reactance.

Figure 3.5 GTO Controlled Series Capacitor

Page 8: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

36

Thyristor Switched Series Capacitor (TSSC)

Thyristor Switched Series Capacitor (TSSC) is another type of

variable impedance type series compensators shown in Figure 3.6. The TSSC

consists of several capacitors shunted by a reverse connected thyristor bypass

switch.

Figure 3.6 Thyristor Switched Series Capacitor

In TSSC, the amount of series compensation is controlled in a step-

like manner by increasing or decreasing the number of series capacitors

inserted into the line. The thyristor turns off when the line current crosses the

zero point. As a result, capacitors can only be inserted or deleted from the

string at the zero crossing. Due to this, a dc offset voltage arises which is

equal to the amplitude of the ac capacitor voltage. In order to keep the initial

surge current at a minimum, the thyristor is turned on when the capacitor

voltage is zero.

The TSSC controls the degree of compensating voltage by either

inserting or bypassing series capacitors. There are several limitations to the

TSSC. A high degree of TSSC compensation can cause sub-synchronous

resonance in the transmission line just like a traditional series capacitor. The

TSSC is most commonly used for power flow control and for damping power

Page 9: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

37

flow oscillations where the response time required is moderate. There are two

modes of operation for the TSSC-voltage compensating mode and impedance

compensating mode.

Thyristor Controlled Series Capacitor (TCSC)

Figure 3.7 shows the basic Thyristor Controlled Series Capacitor

(TCSC) scheme. The TCSC is composed of a series-compensating capacitor

in parallel with a thyristor-controlled reactor. The TCSC provides a

continuously variable capacitive or inductive reactance by means of thyristor

firing angle control. The parallel LC circuit determines the steady-state

impedance of the TCSC.

Figure 3.7 Thyristor Controlled Series Capacitor

The impedance of the controllable reactor is varied from its

maximum (infinity) to its minimum ( L). The TCSC has two operating

ranges; one is when Clim /2, where the TCSC is in capacitive mode.

The other range of operation is 0 Llim, where the TCSC is in inductive

mode. TCSC can be operated in impedance compensation mode or voltage

compensation mode.

Page 10: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

38

3.2.5.2 Switching converter type compensator

With the high power forced-commutated valves such as the GTO

and ETO, the converter-based FACTS controllers have become true. The

advantages of converter-based FACTS controllers are continuous and precise

power control, cost reduction of the associated relative components and a

reduction in size and weight of the overall system.

An SSSC is an example of a FACTS device that has its primary

function to change the characteristic impedance of the transmission line and

thus change the power flow. The impedance of the transmission line is

changed by injecting a voltage which leads or lags the transmission line

current by 90º.

Figure 3.8 Schematic diagram of SSSC

If the SSSC is equipped with an energy storage system, the SSSC

gets an added advantage of real and reactive power compensation in the

Page 11: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

39

power system. By controlling the angular position of the injected voltage

with respect to the line current, the real power is provided by the SSSC with

energy storage element. Figure 3.8 shows a schematic diagram of SSSC with

energy storage system for real and reactive power exchange.

The applications for an SSSC are the same as for traditional

controllable series capacitors. The SSSC is used for power flow control,

voltage stability and phase angle stability. The benefit of the SSSC over the

conventional controllable series capacitor is that the SSSC induces both

capacitive and inductive series compensating voltages on a line. Hence, the

SSSC has a wider range of operation compared with the traditional series

capacitors.

The primary objective of this thesis is to examine the possible uses

of the SSSC with energy storage system with state-of-the-art power

semiconductor devices in order to provide a more cost effective solution.

3.2.5.3 Comparison of Series Compensator Types

Figure 3.9 shows a comparison of VI and loss characteristics of

variable type series compensators and the converter based series compensator.

Figure 3.9 Comparison of Variable Type Series Compensators to

Converter Type Series Compensator

Page 12: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

40

From the figure the following conclusions can be made.

The SSSC is capable of internally generating a controllable

compensating voltage over any capacitive or inductive range

independent of the magnitude of the line current. The GCSC

and the TSSC generate a compensating voltage that is

proportional to the line current. The TCSC maintains the

maximum compensating voltage with decreasing line current

but the control range of the compensating voltage is

determined by the current boosting capability of the thyristor

controlled reactor.

The SSSC has the ability to be interfaced with an external dc

power supply. The external dc power supply is used to provide

compensation for the line resistance. This is accomplished by

the injection of real power as well as for the line reactance by

the injection of reactive power. The variable impedance type

series compensators cannot inject real power into the

transmission line. They can only provide reactive power

compensation.

The SSSC with energy storage can increase the effectiveness

of the power oscillation damping by modulating the amount of

series compensation in order to increase or decrease the

transmitted power. The SSSC increases or decreases the

amount of transmitted power by injecting positive and

negative real impedances into the transmission line. The

variable-type series compensators can damp the power

oscillations by modulating the reactive compensation.

3.3 STATIC SYNCHRONOUS SERIES COMPENSATOR (SSSC)

The Voltage Sourced Converter (VSC) based series compensators -

Static Synchronous Series Compensator (SSSC) was proposed by Gyugyi in

1989. The single line diagram of a two machine system with SSSC is shown

in Figure 3.10. The SSSC injects a compensating voltage in series with the

Page 13: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

41

line irrespective of the line current. From the phasor diagram, it can be stated

that at a given line current, the voltage injected by the SSSC forces the

opposite polarity voltage across the series line reactance. It works by

increasing the voltage across the transmission line and thus increases the

corresponding line current and transmitted power.

Figure 3.10 Simplified diagram of series compensation with the phasor

diagram.

The compensating reactance is defined to be negative when the

SSSC is operated in an inductive mode and positive when operated in

capacitive mode. The voltage source converter can be controlled in such a

way that the output voltage can either lead or lag the line current by 90o.

During normal capacitive compensation, the output voltage lags the line

current by 90o. The SSSC can increase or decrease the power flow to the

same degree in either direction simply by changing the polarity of the injected

ac voltage. The reversed (180o) phase shifted voltage adds directly to the

reactive voltage drop of the line. The reactive line impedance appears as if it

were increased. If the amplitude of the reversed polarity voltage is large

enough, the power flow will be reversed. The transmitted power verses

transmitted phase angle relationship is shown in Equation (3.1) and the

transmitted power verses transmitted angle as a function of the degree of

series compensation is shown in Figure 3.11.

P = sin + V cos (3.1)

Page 14: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

42

Figure 3.11 Transmitted power verses transmitted angle as a function of

series compensation

3.4 CONVERTERS

3.4.1 Basic Concept

The conventional thyristor device has only the turn on control and

its turn off depends on the natural current zero. Devices such as the Gate

Turn Off Thyristor (GTO), Integrated Gate Bipolar Transistor (IGBT), MOS

Turn Off Thyristor (MTO) and Integrated Gate Commutated Thyristor

(IGCT) and similar devices have turn on and turn off capability. These

devices are more expensive and have higher losses than the thyristors without

turn off capability; however, turn off devices enable converter concepts that

can have significant overall system cost and performance advantages. These

advantages in principle result from the converter, which are self commutating

as against the line commutating converters. The line commutating converter

consumes reactive power and suffers from occasional commutation failures in

the inverter mode of operation. Hence, the converters applicable for FACTS

controllers are of self commutating type (Hingorani and Gyugyi, 2000).

There are two basic categories of self commutating converters:

Page 15: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

43

Current sourced converters in which direct current always

has one polarity and the power reversal takes place through

reversal of dc voltage polarity.

Voltage sourced converters in which the dc voltage always

has one polarity and the power reversal takes place through

reversal of dc current polarity.

For reasons of economics and performance, voltage sourced

converters are often preferred over current sourced converters for FACTS

applications.

3.4.2 Voltage Source Inverters for SSSC

SSSC is a Voltage Sourced Converter based series compensator.

The compensation works by increasing the voltage across the impedance of

the given physical line, which in turn increases the corresponding line current

and the transmitted power. For normal capacitive compensation, the output

voltage lags the line current by 90o. With Voltage Source Inverters the output

voltage can be reversed by simple control action to make it lead or lag the line

current by 90o.

In the present work, 48-pulse VSI is designed and ideal switches

and zig-zag phase shifting transformers are used to build a GTO-type VSI.

Figure 3.12 shows the Matlab/Simulink model of 48 pulse VSI. This type of

converter is used in high-power Flexible AC Transmission Systems which are

used to control power flow on transmission grids.

The inverter described is harmonic neutralized. It consists of four 3-

phase, 3-level inverters and four phase-shifting transformers. The DC bus is

connected to the four 3-phase inverters. The four voltages generated by the

inverters are applied to secondary windings of four zig-zag phase-shifting

transformers connected in Wye (Y) or Delta (D). The four transformer

Page 16: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

44

primary windings are connected in series and the converter pulse patterns are

phase shifted so that the four voltage fundamental components sum in phase

on the primary side.

Figure 3.12 Matlab/Simulink model of 48 pulse Voltage Source Inverter

Each 3-level inverter generates three square-wave voltages which

can be +Vdc, 0, -Vdc. The duration of the +Vdc or -Vdc level (Sigma) can be

adjusted between 0 and 180 degrees from the sigma input of the firing pulse

generator block. Each inverter uses a 3-level bridge block where specified

power electronic devices are ideal switches. In this model, each leg of the

inverter uses 3 ideal switches to obtain the 3 voltage levels (+Vdc, 0, - Vdc).

The phase shifts produced by the secondary delta connections (-30

degrees) and by the primary zig-zag connections (+7.5 degrees for

9

-

8

N

7

+

6

C2

5

B2

4

A2

3

C1

2

B1

1

A1

A+

B+

C+

A-

B-

C-

a3

b3

c3

Zigzag

Phase-Shifting Transformer3

A+

B+

C+

A-

B-

C-

a3

b3

c3

n

Zigzag

Phase-Shifting Transformer2

A+

B+

C+

A-

B-

C-

a3

b3

c3

Zigzag

Phase-Shifting Transformer1

A+

B+

C+

A-

B-

C-

a3

b3

c3

n

Zigzag

Phase-Shifting Transformer

v+-

Voltage Measurement3

v+-

Voltage Measurement2

v+-

Voltage Measurement1

v+-

Voltage Measurement

A B C

a b c

Three-Phase Breaker

g

A

B

C

+

N

-

Three-Level Bridge3

g

A

B

C

+

N

-

Three-Level Bridge2

g

A

B

C

+

N

-

Three-Level Bridge1

g

A

B

C

+

N

-

Three-Level Bridge

A

B

C

A

B

C

Imes_SE

Vab_Tr2Dse

Goto3

Van_Tr2Yse

Goto2

Vab_Tr1Dse

Goto1

Van_Tr1Yse

Goto

emux 1

Pulses

Page 17: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

45

transformers 1Y and 1D, and -7.5 degrees for transformers 2Y and 2D) allow

to neutralize harmonics up to 45th

harmonic, as explained below:

The 30-degree phase-shift between the Y and D secondaries cancels

harmonics 5+12n (5, 17, 29, 41, ...) and 7+12n (7, 19, 31, 43, ...). In addition,

the 15-degree phase shift between the two groups of transformers (1Y and 1D

leading by 7.5 degrees, 2Y and 2D lagging by +7.5 degrees) allows

cancellation of harmonics 11+24n (11, 35, ...) and 13+24n (13, 37, ...).

Considering the fact that all 3n the harmonics are not transmitted by the Y and

D secondaries, the first harmonics which are not cancelled by the transformers

are 23rd, 25th, 47th and 49th. By choosing an appropriate conduction angle

for the 3-level inverters (sigma = 180 - 7.5 = 172.5 degrees), the 23rd and

25th can be minimized. The first significant harmonics are therefore the 47th

and 49th. This type of inverter generates an almost sinusoidal waveform

consisting of 48-steps. Also with 48 - pulse VSI, AC filters are not required.

The instantaneous values of the phase-to-phase voltage and the

phase to neutral voltage of the 48 pulse inverter are expressed as in equations

3.2 and 3.3.

V (t) = 8 V sin(m t + 18.75 m + 11.25 t) (3.2)

V (t) = V sin(m t + 18.75 11.25 t) (3.3)

where,

V = V cos m (3.4)

V = V (1 + cos m) (3.5)

m=48r±i, i=0,1,2,…

+ for positive sequence harmonics and

- for negative sequence harmonics.

Page 18: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

46

The voltages Vbc48 and Vca48 exhibit a similar pattern except the

phase shifted by 120o and 240

o respectively. Similarly, the phase voltages

Vbn48 and Vcn48 are also phase shifted by 120o and 240

o respectively. For the

input voltage of 20kV at the dc side, the waveform at the ac side of the 48

pulse VSI is shown in Figure 3.13. The THD of the voltage is 1.31% and it is

shown in Figure 3.14.

Figure 3.13 Voltage at the ac side of the 48 pulse VSI

Figure 3.14 THD of the voltage at the ac side of the 48 pulse VSI

0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1

-0.1

-0.05

0

0.05

0.1

time (sec)

vo

lta

ge

(p

u)

Page 19: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

47

3.5 INTERNAL CONTROL SCHEME FOR SSSC

There are two ways in which the voltage source converter can be

internally controlled (Hingorani 2000). They are:

Indirect control scheme and

Direct control scheme

3.5.1 Indirect Control Scheme

In order to maintain a quadrature relationship between the converter

voltage and the line current, to provide series compensation, and to handle the

sub-synchronous resonance, the converter can be internally controlled. Figure

3.15 shows the block diagram of an indirect control scheme.

Figure 3.15 Block diagram of an indirect control scheme

The inputs to the internal control are the line current, the injected

compensating voltage, and the reference voltage. The control is synchronized

to the line current through the PLL which, after a + /2 or – /2 phase shift,

provides the basic synchronising signal . The output polarity detector

determines the positive capacitive or negative inductive reference voltage

Page 20: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

48

through which the + /2 or – /2 phase shift is determined. A simple closed

loop controller controls the compensating voltage. The absolute value of the

reference voltage is compared with the measured magnitude of the injected

voltage and the amplified difference is added as a correction angle to the

synchronizing signal . The gate signals will be changed accordingly and the

compensating voltage will be phase shifted with respect to the line current.

3.5.2 Direct Control Scheme

To maintain synchronism with the fundamental frequency, the

converter must be directly controlled. Control scheme for directly controlled

converter is shown in figure 3.16. The direct control scheme is for providing

both real and reactive power compensation if the converter is equipped with a

suitable dc power supply. The control is operated from three reference

signals - the desired magnitude of the series reactive compensating voltage,

the series and real compensating and the operating voltage of the dc capacitor.

The references are compared to the corresponding components of the

measured voltages. From these error signals, the magnitude of the injected

voltage and the phase angles are computed and the gate signals for the

converter are generated accordingly.

Figure 3.16 Block diagram of direct control scheme

Page 21: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

49

3.5.3 Control Scheme Proposed

The main function of the SSSC is to dynamically control the power

flow over the transmission line. The control scheme proposed by Anil.

Pradhan and Lehn (2006) is based on the line impedance control mode in

which the SSSC compensating voltage is derived by multiplying the current

amplitude with the desired compensating reactance Xqref. Since it is difficult

to predict Xqref under varying network contingencies, in the proposed scheme,

this controller is modified with power references instead of reactance

reference to operate the Static Synchronous Series Compensator in the

automatic power flow control mode (Geethalakshmi and Dhananjayan 2007).

The phase locked loop determines the frequency and t of the bus1

voltage. Bus2 voltage is converted to d-q components as Vd and Vq.

Similarly, current flowing from bus1 to bus2 is also converted to d-q

components as Id and Iq using d-q transformations as below. The abc to dq0

transformation computes the direct axis, quadrature axis and zero sequence

quantities in a two axis rotating reference frame for a three phase sinusoidal

signal. For the three phase voltage, the following equations are used to

compute the two axis rotating reference voltages.

V = (V sin( t) + V sin( 3) + V sin( t + 2 3)) (3.6)

V = (V cos( t) + V cos( 3) + V cos( t + 2 3)) (3.7)

V = (V + V + V ) (3.8)

For obtaining the dq currents from three phase currents, the voltage

is replaced with current.

Page 22: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

50

The reference inputs to the controller are Pref and Qref, which are to

be maintained in the transmission line. The instantaneous power is obtained in

terms of d-q quantities of voltages and currents as below:

P = V I + V I (3.9)

Q = V I + V I (3.10)

From equations 3.9 and 3.10, the required current references are

calculated as follows:

I = P V + Q V / V + V (3.11)

I = P V + Q V / V + V (3.12)

Figure 3.17 Matlab / Simulink model for the generation of firing pulses

for the 48 pulse VSI

Figure 3.17 shows the Matlab / Simulink model for the generation

of firing pulses for the 48 pulse VSI. The desired current references namely

Idref and Iqref are compared with actual current components Id and Iq

respectively and the error signals are processed in the PI controller. The PI

Series Controller

1

Pulses1/z

1/z

1/z

1/z

Terminator

Idqref

Idq

Vdq

Subsystem

Scope2

Scope1Scope

PQref

Vdq

Idqref

Reference Computation

Vabc( pu )

Freq

wt

Sin_Cos

PLL

Vdq

Vdc

Sigma

angle

Mag and angle

Idqref

PQ

PQref

Sigma

D_Alpha

Alpha

wt

Pulses

Firing Pulses

Generator

0

f requency

wt

Vabc

Iabc

PQ

Vdq

Idq

--

4

VdcPM_SE

3

Iabc

2

Vabc_B2

1

Vb1

Page 23: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

51

controller parameters are designed by Ziegler Nichols’s PI tuning method.

The PI controller parameters set for this process are 0.045 and 16.5 for the

proportional and integral gains respectively. Based on these controller

parameters set, the required small displacement angle has been derived to

control the angle of the injected voltage with respect to the line current. A

Phase Locked Loop (PLL) is used to determine the instantaneous angle of

the three-phase line voltage V1abc. The current components Id and Iq of the

three phase line currents are used to determine the angle r relative to the

voltage V1abc. Depending upon the instantaneous reactive power with respect

to the desired value either /2 is added (inductive) or subtracted (capacitive)

with Thus, the required phase angle is derived as in the equation 3.13.

ref = r ±( /2) (3.13)

3.6 SIMULATION RESULTS

The details of the test system are given in appendix-1. It is a three

area four bus system. Two parallel lines are connected between the two areas

with 200 and 280km in length. The SSSC is connected in the second line of

280km in length. The line is divided into two parts of 100km and 180km.

SSSC is connected between bus 1 and bus 2 in the 100 km length line.

The simulation carried out is as follows: Initially, power flow

control of the line is tested. Hence, the real power reference is varied and the

results are discussed. Qref is kept constant. SSSC is connected at 0.01sec.

Before the insertion of SSSC, the real power flow through the line is 8.85 pu.

In case (a) the Pref is set to 8.5 pu and at 0.25 sec, Pref is increased to 10 pu.

Figure 3.18 shows the corresponding waveforms for power flow through

transmission line 2. It is clear from the figure that the commanded power

references are achieved. In case (b) the Pref is increased to a higher value of

Page 24: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

52

0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.58

9

10

11

12

Time (sec)

Lin

e p

ow

er

flow

(pu)

13 pu. But the final power flow achieved is 12.8 pu which is shown in

Figure 3.19.

Figure 3.18 Real power flow through line 2 for case (a)

Figure 3.19 Real power flow through line 2 for case (b)

The next command is given to Qref. Pref is fixed to a value of

11pu. Before the insertion of SSSC, the reactive power flow is -0.62 pu.

Qref is initially commanded to -0.5 pu and at 0.25 sec it is changed to -0.8 pu.

Figure 3.20 shows the corresponding waveform. Both the set values are

obtained finally.

0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.58

9

10

11

12

13

Time (sec)

Lin

e p

ow

er

flow

(pu)

Page 25: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

53

Figure 3.20 Reactive power flow through line 2

Figure 3.21 shows the quadrature relationship between the line

current and the injected voltage. To have a clear waveform, the magnitude of

the line current is reduced to 0.25 of the original value.

Figure 3.21 Wave forms for 0.25 of line current and injected voltage

For analysing transient stability, a three phase to ground fault is

simulated at 0.2 sec in line 2. The fault is cleared at 0.3 sec. The reference

real and reactive power values set are 11 pu and -0.67 pu respectively and the

results are analysed. Figure 3.22 and 3.23 show the real and reactive power

flow through transmission line 2.

0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5-1.4

-1.2

-1

-0.8

-0.6

-0.4

-0.2

0

Time (sec)

Reactive p

ow

er flow

(pu)

0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5-3

-2

-1

0

1

2

3

Time (sec)

0.2

5 o

f lin

e c

urr

ent

(pu)

Inje

cte

d v

oltage (

pu)

i

v

Page 26: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

54

Figure 3.22 Real power flow through line 2

Figure 3.23 Reactive power flow through line 2

Figure 3.24 Current flowing through line 2

0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.50

5

10

15

20

25

Time (sec)

Lin

e p

ow

er

flow

(pu)

0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5-5

0

5

10

15

20

25

Time (sec)

Reactive p

ow

er flow

(pu)

0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5-150

-100

-50

0

50

100

150

Time (s)

Lin

e C

urr

ent (p

u)

Page 27: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

55

Figure 3.24 represents the current flow through line 2 and the value

is 10 pu during normal operating condition and the peak value goes to 147 pu

during fault. Figure 3.25 shows the injected voltage from SSSC and it is 0.06

pu during steady state condition and the oscillations are more during fault

period.

Figure 3.25 Injected voltage from SSSC

Figure 3.26 Voltage across the dc capacitor

0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5-0.8

-0.6

-0.4

-0.2

0

0.2

0.4

0.6

0.8

Time (sec)

Inje

cte

d v

oltage (pu)

0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5-1

0

1

2

3

4

5

6x 10

4

Time (sec)

Voltage a

cro

ss t

he c

apacitor

(Volts)

Page 28: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

56

Figure 3.26 shows the waveform of voltage across the capacitor.

During faulted period, the value overshoots to 53kV and settles to 21.5 kV in

the post fault period.

Figure 3.27 and 3.28 show the waveforms of the electrical power

output from generator 1 for the cases without and with SSSC respectively.

Figures 3.29 and 3.30 show the waveforms of the load angle for the machine

and from the figures it is clear that the oscillations are reduced for the system

with SSSC. The overshoot and settling time are also less for the system with

SSSC.

Figure 3.27 Electrical power output from generator 1 for the case

without SSSC

Figure 3.28 Electrical power output from generator 1 for the case with

SSSC

0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5-1

-0.5

0

0.5

1

1.5

2

2.5

3

Time (sec)

Outp

ut active p

ower (p

u)

0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5-1

-0.5

0

0.5

1

1.5

2

2.5

Time (sec)

Outp

ut active p

ower

Page 29: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

57

Figure 3.29 Load angle of machine 1 for the case without SSSC

Figure 3.30 Load angle of machine 1 for the case with SSSC

Table 3.1 Comparative results for the system without and with SSSC

Without SSSC With SSSC

Electrical power

output from

generator 1

Peak value (pu) 2.54 2.14

Load angle Peak value (degrees) 52.5 51

0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5-20

-10

0

10

20

30

40

50

60

Time (sec)

Load a

ngle

(degre

es)

0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5-20

-10

0

10

20

30

40

50

Time (sec)

Load a

ngle

(degre

es)

Page 30: CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATORshodhganga.inflibnet.ac.in/bitstream/10603/10308/8/08... · 2015-12-04 · x The system, with and without series capacitive compensation,

58

3.7 CONCLUSION

The objectives of series compensators have been discussed.

Variable impedance type series compensators and a switching converter type

series compensator have been discussed. A comparative study has been made.

The modelling of SSSC has been discussed. The harmonic neutralised 48

pulse voltage source inverter has been realised. The output waveform and the

THD of the 48 pulse voltage source inverter have been analysed. The various

control schemes used for the control of SSSC have been discussed in detail

and the proposed control scheme with PI controller is given. Simulation

results have been carried out for real and reactive power commands and three

phase fault in line 2 of the proposed system. From the results, the comparison

is tabulated for the system without and with SSSC and the results show a

good improvement in the transient stability of the system with SSSC.


Recommended