+ All Categories
Home > Documents > Choosing Surge Arresters for LV Networks

Choosing Surge Arresters for LV Networks

Date post: 14-Apr-2018
Category:
Upload: jose-luis-falcon-chavez
View: 236 times
Download: 0 times
Share this document with a friend

of 12

Transcript
  • 7/27/2019 Choosing Surge Arresters for LV Networks

    1/1292506E.fm/2 Schneider ElectricUpdated: 21/02/02

    surge arresterschoosing surge arresters for :LV networks

    in function of the technicaldata for loads

    #

    the surge arresters level of protection (Up)depends on the installed equipment and therated voltage of the installation

    #

    Up must lie between:5

    the full voltage of the permanent operatingconditions (Uc)5

    the impulse withstand voltage (Uchoc) of

    the equipment to be protected.

    8/20 impulse withstand table for equipment to be protected#

    general standard: IEC 60364-4

    rated voltage equipment sensitivity withstand (Uchoc)of the installation

    threephase reduced normal high very high

    Uc < Up < Uchoc networks electronic circuit electrical household industrial industrial

    devices: appliances: devices: devices:

    televisions, alarms, HiFi, dishwashers, ovens motors, distribution electric

    video recorders, computers refrigerators, protable cabinets, current meters,

    telecommunication tools sockets, transfos. telemeters

    400/690/1000 2.5 kV 4 kV 6 kV 8 kV

    230/440 V 1.5 kV 2.5 kV 4 kV 6 kVshock wave shock wave shock wave shock wave

    category I category II category III category IV

    Uc value as in the French standard: NF C 15100 section 534

    earthing systems TT TN-S TN-C ITUc value for common mode 1.5 Uo 1.5 Uo 1.5 Uo 1.732 Uo

    (protection between live conductors and earth)

    Uc value for differential mode 1.1 Uo 1.1 Uo 1.1 Uo

    (protection between phase and neutral)

    Uo: simple network voltage between phase and neutral

    Uc: full voltage under permanent operating conditions

    placing several surge arresters in a cascading configuration

    The incoming protection device (P1) isdimensioned to run-off lightning currents at thesource of the installation, 2 cases are possible:#

    if there is a level of protection (Up) too highfor the impulse withstand voltage (Uchoc) ofthe installations equipment:5

    a secondary protection surge arrester (P2)placed near loads is sufficient, to lower thevoltage and make it compatible with theimpulse withstand voltage of the equipmentto be protected (see installation constraintspage 9).

    Example figure 1

    E: equipment to be protected with impulse

    withstand of 1.5 kV

    P1: incoming protection device dimensioned with Inand Imax that are sufficient enough to face lightning

    currents that may appear and with a level of

    protection of 2.5 kV

    P2: surge arrester near equipment to be protected

    with an adapted level of protection and which is

    co-ordonated with P1

    #

    if sensitive equipment is too far from theincoming protection device(d 30 m figure 2):5

    a secondary protection surge arrester (P2)placed near loads suffices, to lower the volta-ge and make it compatible with the impulsewithstand voltage of the equipment to be pro-tected (see installation constraints page 9).

    Example figure 2

    E: equipment to be protected with impulse

    withstand of 1.5 kV

    P1: incoming protection device dimensioned with In

    and Imax that are sufficient enough to face lightningcurrents that may appear and with a level of

    protection of 1.5 kV. This level of 1.5 kV is

    acceptable in principle (even though there is no

    margin), but the distance d is too great

    P2: surge arrester near equipment to be protected

    with an adapted level of protection and which is

    co-ordonated with P1

    Up surge arrester < Uchoc switchgearP1

    P1 P2

    E

    E

    Up:

    1.2 kV

    E57353

    P1

    P1 P2

    d 30 m

    E

    E

    E57354

    servicespractical advice

    Up:2 kV

    Uchoc:1.5 kV

    Up:

    2 kVUchoc:

    1.5 kV

    France

  • 7/27/2019 Choosing Surge Arresters for LV Networks

    2/1292506E.fm/3Schneider Electric Updated: 21/02/02

    surge arresterschoosing surge arresters for :LV networks

    installation without a lighting conductor

    (*) recommended

    (1) since in the tertiary/industrial sector the cost of equipment to be protected is higher, damage

    due to lightning is more significant

    lightning flash density (Ng)

    in function of the sitescharacteristics

    installation with a lighting conductor#

    if a lightning rod is planned or has already been installed on the building(or in a 50 m radius):5 choose an incoming protection device with an Imax 65 kA.

    #

    mount a secondary protection surge arrester Imax: 8 kA if:5

    the distance between the incoming surge arrester and loads is 30 m5

    the surge arresters voltage Up is too high in regards to the sensitivity of the loadto be protected (Uchoc), (see page 2).

    residentiel

    geographical location urban rural

    lightning flash density (Ng)

    Imax (kA) incoming protection 15* 15 15 15 30-40 65

    Imax (kA) secondary protection if:Up too high and/or d 30 m

    8 8

    0.5 0.5

  • 7/27/2019 Choosing Surge Arresters for LV Networks

    3/1292506E.fm/4 Schneider ElectricUpdated: 21/02/02

    surge arresterschoosing surge arresters for :LV networks

    choice depending on the

    earthing system

    earthing systems TT TN-S TN-C ITdistributed IT non-

    neutral distributed

    neutral

    class 2 test draw-out surge arrestersPRD MC 1P

    Uc = 440 V 3P 3P

    MC/MD 1P+N 1P+N 1P+N

    Uc = 440/275 V 3P+N 3P+N 3P+N

    class 2 test fixedsurge arresters

    PF 30-65 kA MC 1P+N 1P+N 1P+N

    Uc = 440 V 3P+N 3P+N 3P+n

    PF 8-15 kA MC/MD 1P+N 1P+N 1P+N

    Uc = 440/275 V 3P+N 3P+N 3P+N

    PE MC 1P

    Uc = 440 V 3x1P 3x1P

    servicespractical advice France

  • 7/27/2019 Choosing Surge Arresters for LV Networks

    4/1292506E.fm/5Schneider Electric Updated: 21/02/02

    surge arresterschoosing surge arresters for :LV networks

    in function of the technicaldata for loads

    #

    the surge arresters level of protection (Up)depends on the installed equipment and therated voltage of the installation

    #

    Up must lie between:5

    the full voltage of the permanent operatingconditions (Uc)5 the impulse withstand voltage (Uchoc) ofthe equipment to be protected.

    8/20 impulse withstand table for equipment to be protected#

    general standard: IEC 60364-4

    rated voltage equipment sensitivity withstand (Uchoc)of the installation

    threephase reduced normal high very high

    Uc < Up < Uchoc networks electronic circuit electrical household industrial industrial

    devices: appliances: devices: devices

    televisions, alarms, HiFi, dishwashers, ovens motors, distribution electric

    video recorders, computers refrigerators, protable cabinets, current meters,

    telecommunication tools sockets, transfos. telemeters

    400/690/1000 2.5 kV 4 kV 6 kV 8 kV

    230/440 V 1.5 kV 2.5 kV 4 kV 6 kV

    shock wave shock wave shock wave shock wavecategory I category II category III category IV

    permanent operating full withstand voltage Uc as in the IEC 60364-5-534 standard

    earthing systems TT TN-S TN-C IT

    Uc value for common mode 1.5 Uo 1.1 Uo 1.1 Uo 1.732 Uo

    (protection between live conductors and earth)

    Uc value for differential mode 1.1 Uo 1.1 Uo 1.1 Uo

    (protection between phase and neutral)

    Uo: simple network voltage between phase and neutral

    Uc: full voltage under permanent operating conditions

    placing several surge arresters in a cascading configuration

    The incoming protection device (P1) isdimensioned to run-off lightning currents at thesource of the installation, 2 cases are possible:#

    if there is a level of protection (Up) too highfor the impulse withstand voltage (Uchoc) ofthe installations equipment:5

    a secondary protection surge arrester (P2)placed near loads is sufficient, to lower thevoltage and make it compatible with theimpulse withstand voltage of the equipment tobe protected (see installation constraintspage 9-10).

    Example figure 1

    E: equipment to be protected with impulse

    withstand of 1.5 kVP1: incoming protection device dimensioned with In

    and Imax that are sufficient enough to face lightning

    currents that may appear and with a level of

    protection of 2.5 kV

    P2: surge arrester near equipment to be protected

    with an adapted level of protection and which is

    co-ordonated with P1

    # if sensitive equipment is too far from the in-coming protection device (d 30 m figure 2):5

    a secondary protection surge arrester (P2)placed near loads suffices, to lower thevoltage and make it compatible with theimpulse withstand voltage of the equipmentto be protected (see installation constraintspage 9-10).

    Example figure 2

    E: equipment to be protected with impulse

    withstand of 1.5 kV

    P1: incoming protection device dimensioned with In

    and Imax that are sufficient enough to face lightningcurrents that may appear and with a level of

    protection of 1.5 kV. This level of 1.5 kV is

    acceptable in principle (even though there is no

    margin), but the distance d is too great

    P2: surge arrester near equipment to be protected

    with an adapted level of protection and which is

    co-ordonated with P1

    Up surge arrester < Uchoc switchgear

    P1

    P1 P2

    d 30 m

    E

    E

    E57354

    Up:1.2 kV

    E

    E

    P1

    P1 P2

    E

    E

    Up:

    1.2 kV

    E57353

    servicespractical advice

    Up:

    2 kV

    Up:

    2 kV

    Uchoc:

    1.5 kV

    Uchoc:

    1.5 kV

    Export

  • 7/27/2019 Choosing Surge Arresters for LV Networks

    5/1292506E.fm/6 Schneider ElectricUpdated: 21/02/02

    surge arresterschoosing surge arresters for :LV networks

    in function of the sitescharacteristics

    installation without lighting-rod#

    the following table determines the maximum current of the surge arrester(s) to be installed

    according to geographic situation and lightning stroke density of the site to be protected.#

    mount a secondary protection surge arrester Imax: 8 kA if:5

    the distance between the incoming surge arrester and loads is 30 m5

    the surge arresters voltage Up is too high in regards to the sensitivity of the load to be protected(Uchoc) (see page 5).

    residential

    geographical location urban rural

    lightning flash density (Ng)

    Imax (kA) incoming protection 15* 15 15 15 30-40 65

    Imax (kA) secondary protection if:Up too high and/or d 30 m

    8 8

    (*) recommended

    tertiary/industrial (1)

    continuity of supply of the not necessary partial mandatory

    operation

    consequence (financial) low high very high

    of a lightning stroke on

    equipment to be protected

    lightning flash density (Ng)

    Imax (kA) incoming protection 15 15 30-40 15 30-40 65 30-40 65 65

    Imax (kA) secondary protection if: 8 8 8 8 8 8

    Up too high and/or d 30 m

    (1) since in the tertiary/industrial sector the cost of equipment to be protected is higher, damage due to

    lightning is more significant

    0.5 0.5

  • 7/27/2019 Choosing Surge Arresters for LV Networks

    6/1292506E.fm/7Schneider Electric Updated: 21/02/02

    surge arresterschoosing surge arresters for :LV networks

    in function of the sitescharacteristics

    Installation with lightning rod#

    presence of a lightning rod on the building or in a radius of 50 m can cause a direct lightningstroke generating a rise in potential of the frames and of the earth network. Part of thelightning current rises in the electrical installation through the earthing electrode then theearthing strip.#

    to protect the loads, it is then necessary to install at the incoming side of the switchboard,a PRF1 class 1 test surge arrester with a very high drain-off capacity (limp 20 kA) and ableto arc and then conduct the lightning current to a remote earth referenced at O V, while alsoensuring a level of protection of 4 kV maximum between phase/neutral and earth.#

    as this level of protection is too high, another surge arrester must be added in cascade, sothat residual voltage at the terminals of the second surge arrester lmax = 30-40 kA (PRD40,PF30, PE40 or STM) is compatible with the impact withstand voltage of the equipment to beprotected (impact U < 1.5kV)#

    finally, if the loads to be protected are more than 30 m from the incoming protection, a fineprotection surge arrester lmax 8 kA will be installed (PRD8, PF8, PE8, STD) as close aspossible to the loads.

    E91263

    if d4

    30 m

    incomer end protection secondary protection

    servicespractical advice

    E91007

  • 7/27/2019 Choosing Surge Arresters for LV Networks

    7/1292506E.fm/8 Schneider ElectricUpdated: 21/02/02

    surge arresterschoosing surge arresters for :LV networks

    choice depending on the

    earthing system(PRF1)

    earthing systems TT TN-S TN-C ITdistributed IT non-

    neutral distributed

    neutral

    class 1 test fixedsurge arresters

    PRF1 2x1P 2x1P

    4x1P 4x1P 3x1P

    choice depending on the

    earthing system

    (PRD and ST offer)

    earthing systems TT TN-S TN-C ITdistributed IT non-

    neutral distributed

    neutral

    class 2 test draw-out surge arresters

    PRD MC 1P

    Uc = 275 V

    MC 3P

    Uc = 440 V 3P

    MC/MD 1P+N 1P+N 1P+N

    Uc = 440/275 V 3P+N 3P+N 3P+N

    class 2 test fixedsurge arresters

    STH-STM MC 1P+N 1P

    FORBIDDEN

    Uc = 275 V 3P+N 3P

    STD MC 1P

    Uc = 275 V 3P

    MC/MD 1P+N 1P+N 1P+N

    Uc = 440/275 V 3P+N 3P+N 3P+N

    choice depending on the

    earthing system(PRD, PF and PE offer)

    earthing systems TT TN-S TN-C ITdistributed IT non-

    neutral distributed

    neutral

    class 2 test draw-out surge arresters

    PRD MC 1P

    Uc = 275 V

    MC 3P

    Uc = 440 V 3P

    MC/MD 1P+N 1P+N 1P+N

    Uc = 440/275 V 3P+N 3P+N 3P+N

    class 2 test fixedsurge arresters

    PF 30-65 kA MC 1P+N 1P+N 1P+N

    Uc = 440 V 3P+N 3P+N 3P+N

    PF 8-15 kA MC/MD 1P+N 1P+N 1P+N

    Uc = 440/275 V 3P+N 3P+N 3P+N

    PE MC 1P

    Uc = 440 V 3x1P 3x1P

    servicespractical advice Export

  • 7/27/2019 Choosing Surge Arresters for LV Networks

    8/1292506E.fm/9Schneider Electric Updated: 21/02/02

    surge arresterschoosing surge arresters for :LV networks

    choosing a disconnectioncircuit-breaker

    class 1 test surge arresters After having chosen the surge arrester(s)needed to protect the installation, theappropriate disconnection circuit-breaker is

    to be chosen from the opposite table:#

    its breaking capacity must be compatiblewith the installations breaking capacity#

    each live conductor must be protectedexample: a 1P+n surge arrester must becombined with a 2P disconnectioncircuit-breaker (2 protected poles).

    disconnectionPRF1 fuse circuit-breaker

    Iimp: 60 kA 125 A Max. compact NS160HgL (22 x 58) TM125D Max.

    class 2 test surge arrestersmax. lightning disconnection circuit-breakerdischarge current rating curve

    8-15-30-40 kA 20 A C

    65 kA 50 A C

    installation constraintsclass 2 test surge arrester

    the 50 cm rule in the switchboardConnections must be as short as possible.

    Do not exceed a distance of 50 cm, toefficiently protect electrical loads.

    co-ordinating 2 surge arresters (the 10 m rule)#

    In the case of an exposed site and thepresance of sensitive loads, it is recommended to co-ordinate upstream and downstream protection in a cas-cading configuration.

    O-OFF

    O-OFF

    T

    OFF

    O-OFF

    O-OFF

    O-OFF

    O-OFF

    NL

    MERLIN G

    ERIN

    C40r-275

    Imax:40kA(8/20

    )

    In:15kA(8/20)

    Up:1,2kV

    Uc:275V

    multi 9

    PRDMER

    LINGERIN

    C Neutra

    lr

    multi 9

    PRD

    d1

    d2

    d3

    PRD

    d1+d2+d3

    50cm

    2

    type

    or delayed

    O-OFF

    O-OFF

    NL

    MERLINGE

    RIN

    multi9

    PRDMER

    LINGERIN

    CNeutral r

    multi9

    PRD

    O-OFF

    O-OFF

    NL

    MERLINGE

    RIN

    multi9

    PRDMER

    LINGERIN

    C Neutral r

    multi9

    PRD

    O-OFF

    O-OFF

    incomerend

    protection

    secondaryp

    rotection

    servicespractical advice

    E57321

    E57322

  • 7/27/2019 Choosing Surge Arresters for LV Networks

    9/1292506E.fm/10 Schneider ElectricUpdated: 21/02/02

    surge arresterschoosing surge arresters for :LV networks

    installation constraints PRF1class 1 test surge arresterPRF1 surge arrester with reactor#

    if the distance between the two incoming protectionsurge arresters is < 15 m, mount an L40A decouplingcoil cat. n. 16640 in series.

    PRF1 surge arrester without reactor#

    if the two incoming protection surge arresters are installed in separate switch-boards, more than 15 m apart, the decoupling coil is not required.

    E57662

    E57662

    E57603

    E57626

    #

    The 50 cm rule also applies to connection of the PRF1 surge arrester

    E57602

    STM STM

    O-OFF

    O-OFF

    NL

    MERLINGER

    IN

    multi 9

    PRDMERL

    INGERIN

    C Neutr

    al r

    multi 9

    PRD

    O-OFF

    O-OFF

    limp=60k

    A

    Up 4kV

    Uc=255V

    50HzAC

    Q=30As

    1 6 6 2

    0

    MERLING

    ERIN

    PRF1

    MERLIN GE

    RIN

    limp= 60

    kA

    Up 4kV

    Uc=255V

    50HzAC

    Q= 30As

    1 6 6 2 0

    PRF1

    Un 500V

    50/60Hz

    In40A

    Ln=15H

    1 6 6 4 0

    MERLING

    ERIN

    L40A

    Un 500V5

    0/60Hz

    In 40A

    Ln= 15

    H

    1 6 6 4 0

    MERLINGE

    RIN

    L40A

    PF, PE

    PRD, STM

    NL

    multi 9

    PRD

    C Neutra

    lr

    multi 9

    PRD

    limp= 60

    kA

    Up 4kV

    Uc=255V

    50HzAC

    Q= 30As

    1 6 6

    2 0

    PRF1

    limp =60kA

    Up 4kV

    Uc= 255

    V50HzAC

    Q=30As

    1 6 6

    2 0

    PRF1

    O-OFF

    O-OFF

    O-OFF

    O-OFF

    PF, PE

    PRD, STM

    limp=60kA

    Up4kV

    Uc= 255V50

    HzAC

    Q=30As

    1 6 6 2

    0

    MERLIN

    GERIN

    PRF1

    limp =60kA

    Up 4kV

    Uc=255V5

    0HzAC

    Q=30As

    MERLING

    ERIN

    1 6 6 2 0

    PRF1

    T

    OFF

    O-OFF

    O-OFF

    O-OFF

    O-OFF

    d1

    d2

    d3

    d1+d2

    +d350

    cm

    125 A Max.gL (22x58)

    Compact NS 160HTM125D Max.

    PRF1

    16 35 mm2

    16 50 mm2

    servicespractical advice

  • 7/27/2019 Choosing Surge Arresters for LV Networks

    10/1292506E.fm/11Schneider Electric Updated: 21/02/02

    surge arresterschoosing surge arresters for :LV networks (continued)communication networks

    case of earth leakage

    devices

    The best way to guarantee the continuity ofsupply of priority circuits, while ensuring

    safety in the case of atmosphericdisturbances is to combine:#

    a surge arrester that can protect sensitiveloads against atmospheric overvoltages#

    a circuit-breaker with an upstream earthleakage protection device of 300/500 mAselective, to ensure total earth leakagediscrimination#

    a residual current device of 30 mA and "si"type placed downstream is insensitive to thistype of disturbance.

    Another solution can be foreseen: use acircuit-breaker (not earth leakage) at the

    incoming end of the installation followed bya residual current circuit-breaker. The surgearrester is to be connected between the twodevices (see below).Careful, the link L must be class II.

    In installations fitted out with a general earthleakage protection, it is preferable to placethe surge arrester upstream from thisprotection.However, certain power distributors do notallow intervention at this distribution level(this is for instance the case for LVsubscribers in France).It is therefore necessary to plan a selectivedevice of the

    P

    type, or with delayedtripping, so that when the current runs off tothe earth through the surge arrester, it doesnot produce nuisance tripping of theincoming circuit-breaker.

    ID "si"30 mA

    ID

    30 mA

    residual current

    device of the2

    type or delayed

    disconnection

    circuit-

    breaker

    surge

    arrester

    other circuits prioritycircuits

    L: class II link

    circuit-

    breaker

    combined

    with RCCB

    uses

    residual

    current

    circuit-

    breaker

    surge arrester

    disconnection

    circuit-

    breaker

    surge

    arrester

    uses

    high

    sensitivity

    selective

    RCD

    with the earth

    leakage

    protection

    device of the

    2

    type

    residual current

    device of the2

    type or delayed

    choice depending on thecommunication network

    type of network series PRC PRI 1248 V PRI 6 V

    telecommunication

    digital 300 Hz RTC

    numeris access T0

    specialised 24 V line

    specialised modem line base

    band 64 kbit/s

    MIC line and access T2

    computer

    current loop 200 V

    current loop 1248 V

    RS 232 (12 V)

    RS 485 (12 V)

    current loop 6 V

    RS 422 (6 V)

    RS 423 (6 V)

    supply 12/48 V

    fire safety centralising equipment,

    ELV load, intrusion centralising

    servicespractical advice

    E57324

    E57325

    E573256

  • 7/27/2019 Choosing Surge Arresters for LV Networks

    11/1292506E.fm/12 Schneider ElectricUpdated: 21/02/02

    end of life surge arresters for LV networksAt the end of its life the surge arrester or itscartridge is destroyed, this can be one of 2

    types:#

    internal end of life disconnection:5

    the accumulation of electrical shockscauses the varistors to age, which translatesinto a rise in the leakage current, above 1mA there is thermal runaway anddisconnection of the surge arrester#

    external end of life disconnection:5

    is produced when an overvoltage is tooenergetic (lightning stroke directly on theline), above the surge arresters flowcapacity there where the varistors areplaced in solid short-circuit with the earth (or

    possible between the phase and neutral)5

    this short-circuit is eliminated by themandatory disconnection circuit-breaker.

    surge arresters for communicationnetworksThe surge arrestor is only at the end of life inshort-circuit, following the accumulation ofelectrical shocks which causes it to age orfollowing an overvoltage that is tooenergetic.

    indication PRD65r and PRD40r surge arrestersThese surge arresters include:#

    a built-in NO/NC remote indication contact# a mechanical indicator on the front panelwith a power reserve:5

    white: normal operation (1)5

    white/red: cartridge to be replaced in thenear future (2)5

    red: cartridge to be immediatelyreplaced (3).

    series PRD65, PRD40, PRD15, PRD8,PE40, PE15, PE8, ST, PRC and PRI surgearrestersThese surge arresters include:#

    a mechanical indicator on front panel:5

    white: normal operation

    5

    red: surge arrester to be immediatelyreplaced.

    PE65 surge arrestersThese surge arresters include:#

    a mechanical indicator on the front panelwith a power reserve:5

    white: normal operation

    5

    white/red: cartridge is to be replaced in thenear future5

    red: surge arrester is to be immediatelyreplaced.

    PF surge arresters

    These surge arresters include:#

    a built-in remote indication NC contact forthe PF65r and PF30r models#

    an orange light indicator on the front panel:5

    not lit: normal operation5

    flashing: surge arrester to be immediatelyreplaced.

    14 11 12

    E57214

    (1)

    14 11 12

    E57217

    (2)

    14 11 12

    E57215

    (3)

    indication by the circuit-breaker#

    end of life is indicated by the opendisconnection circuit-breaker#

    the best indication consists in indication ofthe continuity of protection, which is linked tothe closing of the upstream circuit-breakerthat is combined with an SD contact and

    surge arrester operation indication using:

    5

    the transfer contact that is built-into thePF65r, PF30r, PRD65r and PRD40r surgearresters (diagram 1)5

    or an EM/RM indication auxiliary(diagram 2)

    diagram 1 (example PRD) diagram 2

    11 12

    NL

    MERLING

    ERIN

    Imax. :65

    kA

    Un : 230 V

    ~

    Uc :440

    V~

    In :20kA

    Up:1,8k

    V

    multi 9

    PRDMER

    LINGERIN

    Imax. : 6

    5 kA

    Un :230 V

    ~

    Uc:4 40

    V~

    In:20 k

    A

    Up:1,8

    kV

    multi 9

    PRD

    O-OFF

    O-OFF

    SD

    O-OFF

    O-OFF

    14 11

    12

    indicator

    disconnect

    ion

    circuit-

    breaker

    surge

    arrester

    0.5mm

    2 1.5m

    m2

    12VDC-

    10mA

    250VAC-

    1A

    2A

    1 51 5

    2 4

    6O-O

    FF

    O-OFF

    O-OFF

    O-OFF

    EMUn:

    230Va

    NL

    MERLINGE

    RIN

    C40r-275

    Imax:40kA

    (8/20)

    In:15kA(8/2

    0)

    Up:1,2kV

    Uc:275V

    multi 9

    PRDMERL

    INGERIN

    CNeutral

    r

    multi 9

    16562

    RMUn : 2

    30Va

    250VAC-

    50Hz

    6VDC-

    10mA

    250VAC-

    50Hz-5

    A

    servicespractical advice

    surge arrestersend of life and indication

    E57243

    E57320

  • 7/27/2019 Choosing Surge Arresters for LV Networks

    12/12

    installation#

    adaptable on PRD, PE, ST, PRI and PRCsurge arresters#

    the EM/RM modules allow for up to 15surge arrester modules of 18 mm with a limitof 270 mm to be monitored using an opticallink#

    the EM emitter is mounted to the left, theRM receiver to the right#

    the RM receiver includes an NO/NCremote transfer contact for the combinedsurge arrester(s)#

    supply of the EM/RM modules must beprotected by a breaking device(2 A).

    technical data#

    power:5

    min.: 6 V DC and 10 mA5

    max.: 250 V AC and 5 A#

    isolation:5 between contacts: 1 kV AC5

    between the contacts and the coil:2.5 kV AC.

    indication#

    the 2 green indicators are lit up and thered indicator is not:5

    EM/RM modules: OK5

    surge arrester(s): OK#

    the green EM indicator is lit up,the red indicator is lit up:5

    EM/RM modules: OK5

    verify the status of the surge arrester(s)#

    all indicators are extinguished:5

    verify the supply of modules.

    1 5

    1 5

    2 46

    O-OFF

    O-OFF

    EMUn:

    230Va

    O-OFF

    O-OFF

    NL

    MERLINGE

    RIN

    C40r-275

    Imax:40kA

    (8/20)

    In:15kA(8/2

    0)

    Up:1,2kV

    Uc:275V

    multi 9

    PRDMERL

    INGERIN

    CNeutral r

    multi 9

    PRD

    16562

    RMUn: 2

    30 Va

    2A

    250VAC-

    50Hz

    6VDC-

    10mA

    250VAC-

    50Hz-5

    A

    NL

    EMUn:2

    30Va

    RMUn:2

    30Va

    16592

    16592

    opticallink

    EMemitter

    RMreceive

    r

    redfault

    indicator

    NO/NCcon

    tactgreeni

    ndicator

    forcorrectoperat

    ion

    greenindic

    ator

    forcorrect

    operation

    PRD / PE / ST / PRC / PRI

    EM RMPRD...

    2 4 6

    OK

    PRD / PE / ST / PRC / PRIEM RM

    PRD...

    2 4 6

    servicespractical advice

    surge arrestersEM/RM remote indication modules

    additionalinformation

    dimensions : page 90148/2conseils pratiques : page 92506/2

    E57318

    E57319

    E57337


Recommended