Date post: | 14-Apr-2018 |
Category: |
Documents |
Upload: | jose-luis-falcon-chavez |
View: | 236 times |
Download: | 0 times |
of 12
7/27/2019 Choosing Surge Arresters for LV Networks
1/1292506E.fm/2 Schneider ElectricUpdated: 21/02/02
surge arresterschoosing surge arresters for :LV networks
in function of the technicaldata for loads
#
the surge arresters level of protection (Up)depends on the installed equipment and therated voltage of the installation
#
Up must lie between:5
the full voltage of the permanent operatingconditions (Uc)5
the impulse withstand voltage (Uchoc) of
the equipment to be protected.
8/20 impulse withstand table for equipment to be protected#
general standard: IEC 60364-4
rated voltage equipment sensitivity withstand (Uchoc)of the installation
threephase reduced normal high very high
Uc < Up < Uchoc networks electronic circuit electrical household industrial industrial
devices: appliances: devices: devices:
televisions, alarms, HiFi, dishwashers, ovens motors, distribution electric
video recorders, computers refrigerators, protable cabinets, current meters,
telecommunication tools sockets, transfos. telemeters
400/690/1000 2.5 kV 4 kV 6 kV 8 kV
230/440 V 1.5 kV 2.5 kV 4 kV 6 kVshock wave shock wave shock wave shock wave
category I category II category III category IV
Uc value as in the French standard: NF C 15100 section 534
earthing systems TT TN-S TN-C ITUc value for common mode 1.5 Uo 1.5 Uo 1.5 Uo 1.732 Uo
(protection between live conductors and earth)
Uc value for differential mode 1.1 Uo 1.1 Uo 1.1 Uo
(protection between phase and neutral)
Uo: simple network voltage between phase and neutral
Uc: full voltage under permanent operating conditions
placing several surge arresters in a cascading configuration
The incoming protection device (P1) isdimensioned to run-off lightning currents at thesource of the installation, 2 cases are possible:#
if there is a level of protection (Up) too highfor the impulse withstand voltage (Uchoc) ofthe installations equipment:5
a secondary protection surge arrester (P2)placed near loads is sufficient, to lower thevoltage and make it compatible with theimpulse withstand voltage of the equipmentto be protected (see installation constraintspage 9).
Example figure 1
E: equipment to be protected with impulse
withstand of 1.5 kV
P1: incoming protection device dimensioned with Inand Imax that are sufficient enough to face lightning
currents that may appear and with a level of
protection of 2.5 kV
P2: surge arrester near equipment to be protected
with an adapted level of protection and which is
co-ordonated with P1
#
if sensitive equipment is too far from theincoming protection device(d 30 m figure 2):5
a secondary protection surge arrester (P2)placed near loads suffices, to lower the volta-ge and make it compatible with the impulsewithstand voltage of the equipment to be pro-tected (see installation constraints page 9).
Example figure 2
E: equipment to be protected with impulse
withstand of 1.5 kV
P1: incoming protection device dimensioned with In
and Imax that are sufficient enough to face lightningcurrents that may appear and with a level of
protection of 1.5 kV. This level of 1.5 kV is
acceptable in principle (even though there is no
margin), but the distance d is too great
P2: surge arrester near equipment to be protected
with an adapted level of protection and which is
co-ordonated with P1
Up surge arrester < Uchoc switchgearP1
P1 P2
E
E
Up:
1.2 kV
E57353
P1
P1 P2
d 30 m
E
E
E57354
servicespractical advice
Up:2 kV
Uchoc:1.5 kV
Up:
2 kVUchoc:
1.5 kV
France
7/27/2019 Choosing Surge Arresters for LV Networks
2/1292506E.fm/3Schneider Electric Updated: 21/02/02
surge arresterschoosing surge arresters for :LV networks
installation without a lighting conductor
(*) recommended
(1) since in the tertiary/industrial sector the cost of equipment to be protected is higher, damage
due to lightning is more significant
lightning flash density (Ng)
in function of the sitescharacteristics
installation with a lighting conductor#
if a lightning rod is planned or has already been installed on the building(or in a 50 m radius):5 choose an incoming protection device with an Imax 65 kA.
#
mount a secondary protection surge arrester Imax: 8 kA if:5
the distance between the incoming surge arrester and loads is 30 m5
the surge arresters voltage Up is too high in regards to the sensitivity of the loadto be protected (Uchoc), (see page 2).
residentiel
geographical location urban rural
lightning flash density (Ng)
Imax (kA) incoming protection 15* 15 15 15 30-40 65
Imax (kA) secondary protection if:Up too high and/or d 30 m
8 8
0.5 0.5
7/27/2019 Choosing Surge Arresters for LV Networks
3/1292506E.fm/4 Schneider ElectricUpdated: 21/02/02
surge arresterschoosing surge arresters for :LV networks
choice depending on the
earthing system
earthing systems TT TN-S TN-C ITdistributed IT non-
neutral distributed
neutral
class 2 test draw-out surge arrestersPRD MC 1P
Uc = 440 V 3P 3P
MC/MD 1P+N 1P+N 1P+N
Uc = 440/275 V 3P+N 3P+N 3P+N
class 2 test fixedsurge arresters
PF 30-65 kA MC 1P+N 1P+N 1P+N
Uc = 440 V 3P+N 3P+N 3P+n
PF 8-15 kA MC/MD 1P+N 1P+N 1P+N
Uc = 440/275 V 3P+N 3P+N 3P+N
PE MC 1P
Uc = 440 V 3x1P 3x1P
servicespractical advice France
7/27/2019 Choosing Surge Arresters for LV Networks
4/1292506E.fm/5Schneider Electric Updated: 21/02/02
surge arresterschoosing surge arresters for :LV networks
in function of the technicaldata for loads
#
the surge arresters level of protection (Up)depends on the installed equipment and therated voltage of the installation
#
Up must lie between:5
the full voltage of the permanent operatingconditions (Uc)5 the impulse withstand voltage (Uchoc) ofthe equipment to be protected.
8/20 impulse withstand table for equipment to be protected#
general standard: IEC 60364-4
rated voltage equipment sensitivity withstand (Uchoc)of the installation
threephase reduced normal high very high
Uc < Up < Uchoc networks electronic circuit electrical household industrial industrial
devices: appliances: devices: devices
televisions, alarms, HiFi, dishwashers, ovens motors, distribution electric
video recorders, computers refrigerators, protable cabinets, current meters,
telecommunication tools sockets, transfos. telemeters
400/690/1000 2.5 kV 4 kV 6 kV 8 kV
230/440 V 1.5 kV 2.5 kV 4 kV 6 kV
shock wave shock wave shock wave shock wavecategory I category II category III category IV
permanent operating full withstand voltage Uc as in the IEC 60364-5-534 standard
earthing systems TT TN-S TN-C IT
Uc value for common mode 1.5 Uo 1.1 Uo 1.1 Uo 1.732 Uo
(protection between live conductors and earth)
Uc value for differential mode 1.1 Uo 1.1 Uo 1.1 Uo
(protection between phase and neutral)
Uo: simple network voltage between phase and neutral
Uc: full voltage under permanent operating conditions
placing several surge arresters in a cascading configuration
The incoming protection device (P1) isdimensioned to run-off lightning currents at thesource of the installation, 2 cases are possible:#
if there is a level of protection (Up) too highfor the impulse withstand voltage (Uchoc) ofthe installations equipment:5
a secondary protection surge arrester (P2)placed near loads is sufficient, to lower thevoltage and make it compatible with theimpulse withstand voltage of the equipment tobe protected (see installation constraintspage 9-10).
Example figure 1
E: equipment to be protected with impulse
withstand of 1.5 kVP1: incoming protection device dimensioned with In
and Imax that are sufficient enough to face lightning
currents that may appear and with a level of
protection of 2.5 kV
P2: surge arrester near equipment to be protected
with an adapted level of protection and which is
co-ordonated with P1
# if sensitive equipment is too far from the in-coming protection device (d 30 m figure 2):5
a secondary protection surge arrester (P2)placed near loads suffices, to lower thevoltage and make it compatible with theimpulse withstand voltage of the equipmentto be protected (see installation constraintspage 9-10).
Example figure 2
E: equipment to be protected with impulse
withstand of 1.5 kV
P1: incoming protection device dimensioned with In
and Imax that are sufficient enough to face lightningcurrents that may appear and with a level of
protection of 1.5 kV. This level of 1.5 kV is
acceptable in principle (even though there is no
margin), but the distance d is too great
P2: surge arrester near equipment to be protected
with an adapted level of protection and which is
co-ordonated with P1
Up surge arrester < Uchoc switchgear
P1
P1 P2
d 30 m
E
E
E57354
Up:1.2 kV
E
E
P1
P1 P2
E
E
Up:
1.2 kV
E57353
servicespractical advice
Up:
2 kV
Up:
2 kV
Uchoc:
1.5 kV
Uchoc:
1.5 kV
Export
7/27/2019 Choosing Surge Arresters for LV Networks
5/1292506E.fm/6 Schneider ElectricUpdated: 21/02/02
surge arresterschoosing surge arresters for :LV networks
in function of the sitescharacteristics
installation without lighting-rod#
the following table determines the maximum current of the surge arrester(s) to be installed
according to geographic situation and lightning stroke density of the site to be protected.#
mount a secondary protection surge arrester Imax: 8 kA if:5
the distance between the incoming surge arrester and loads is 30 m5
the surge arresters voltage Up is too high in regards to the sensitivity of the load to be protected(Uchoc) (see page 5).
residential
geographical location urban rural
lightning flash density (Ng)
Imax (kA) incoming protection 15* 15 15 15 30-40 65
Imax (kA) secondary protection if:Up too high and/or d 30 m
8 8
(*) recommended
tertiary/industrial (1)
continuity of supply of the not necessary partial mandatory
operation
consequence (financial) low high very high
of a lightning stroke on
equipment to be protected
lightning flash density (Ng)
Imax (kA) incoming protection 15 15 30-40 15 30-40 65 30-40 65 65
Imax (kA) secondary protection if: 8 8 8 8 8 8
Up too high and/or d 30 m
(1) since in the tertiary/industrial sector the cost of equipment to be protected is higher, damage due to
lightning is more significant
0.5 0.5
7/27/2019 Choosing Surge Arresters for LV Networks
6/1292506E.fm/7Schneider Electric Updated: 21/02/02
surge arresterschoosing surge arresters for :LV networks
in function of the sitescharacteristics
Installation with lightning rod#
presence of a lightning rod on the building or in a radius of 50 m can cause a direct lightningstroke generating a rise in potential of the frames and of the earth network. Part of thelightning current rises in the electrical installation through the earthing electrode then theearthing strip.#
to protect the loads, it is then necessary to install at the incoming side of the switchboard,a PRF1 class 1 test surge arrester with a very high drain-off capacity (limp 20 kA) and ableto arc and then conduct the lightning current to a remote earth referenced at O V, while alsoensuring a level of protection of 4 kV maximum between phase/neutral and earth.#
as this level of protection is too high, another surge arrester must be added in cascade, sothat residual voltage at the terminals of the second surge arrester lmax = 30-40 kA (PRD40,PF30, PE40 or STM) is compatible with the impact withstand voltage of the equipment to beprotected (impact U < 1.5kV)#
finally, if the loads to be protected are more than 30 m from the incoming protection, a fineprotection surge arrester lmax 8 kA will be installed (PRD8, PF8, PE8, STD) as close aspossible to the loads.
E91263
if d4
30 m
incomer end protection secondary protection
servicespractical advice
E91007
7/27/2019 Choosing Surge Arresters for LV Networks
7/1292506E.fm/8 Schneider ElectricUpdated: 21/02/02
surge arresterschoosing surge arresters for :LV networks
choice depending on the
earthing system(PRF1)
earthing systems TT TN-S TN-C ITdistributed IT non-
neutral distributed
neutral
class 1 test fixedsurge arresters
PRF1 2x1P 2x1P
4x1P 4x1P 3x1P
choice depending on the
earthing system
(PRD and ST offer)
earthing systems TT TN-S TN-C ITdistributed IT non-
neutral distributed
neutral
class 2 test draw-out surge arresters
PRD MC 1P
Uc = 275 V
MC 3P
Uc = 440 V 3P
MC/MD 1P+N 1P+N 1P+N
Uc = 440/275 V 3P+N 3P+N 3P+N
class 2 test fixedsurge arresters
STH-STM MC 1P+N 1P
FORBIDDEN
Uc = 275 V 3P+N 3P
STD MC 1P
Uc = 275 V 3P
MC/MD 1P+N 1P+N 1P+N
Uc = 440/275 V 3P+N 3P+N 3P+N
choice depending on the
earthing system(PRD, PF and PE offer)
earthing systems TT TN-S TN-C ITdistributed IT non-
neutral distributed
neutral
class 2 test draw-out surge arresters
PRD MC 1P
Uc = 275 V
MC 3P
Uc = 440 V 3P
MC/MD 1P+N 1P+N 1P+N
Uc = 440/275 V 3P+N 3P+N 3P+N
class 2 test fixedsurge arresters
PF 30-65 kA MC 1P+N 1P+N 1P+N
Uc = 440 V 3P+N 3P+N 3P+N
PF 8-15 kA MC/MD 1P+N 1P+N 1P+N
Uc = 440/275 V 3P+N 3P+N 3P+N
PE MC 1P
Uc = 440 V 3x1P 3x1P
servicespractical advice Export
7/27/2019 Choosing Surge Arresters for LV Networks
8/1292506E.fm/9Schneider Electric Updated: 21/02/02
surge arresterschoosing surge arresters for :LV networks
choosing a disconnectioncircuit-breaker
class 1 test surge arresters After having chosen the surge arrester(s)needed to protect the installation, theappropriate disconnection circuit-breaker is
to be chosen from the opposite table:#
its breaking capacity must be compatiblewith the installations breaking capacity#
each live conductor must be protectedexample: a 1P+n surge arrester must becombined with a 2P disconnectioncircuit-breaker (2 protected poles).
disconnectionPRF1 fuse circuit-breaker
Iimp: 60 kA 125 A Max. compact NS160HgL (22 x 58) TM125D Max.
class 2 test surge arrestersmax. lightning disconnection circuit-breakerdischarge current rating curve
8-15-30-40 kA 20 A C
65 kA 50 A C
installation constraintsclass 2 test surge arrester
the 50 cm rule in the switchboardConnections must be as short as possible.
Do not exceed a distance of 50 cm, toefficiently protect electrical loads.
co-ordinating 2 surge arresters (the 10 m rule)#
In the case of an exposed site and thepresance of sensitive loads, it is recommended to co-ordinate upstream and downstream protection in a cas-cading configuration.
O-OFF
O-OFF
T
OFF
O-OFF
O-OFF
O-OFF
O-OFF
NL
MERLIN G
ERIN
C40r-275
Imax:40kA(8/20
)
In:15kA(8/20)
Up:1,2kV
Uc:275V
multi 9
PRDMER
LINGERIN
C Neutra
lr
multi 9
PRD
d1
d2
d3
PRD
d1+d2+d3
50cm
2
type
or delayed
O-OFF
O-OFF
NL
MERLINGE
RIN
multi9
PRDMER
LINGERIN
CNeutral r
multi9
PRD
O-OFF
O-OFF
NL
MERLINGE
RIN
multi9
PRDMER
LINGERIN
C Neutral r
multi9
PRD
O-OFF
O-OFF
incomerend
protection
secondaryp
rotection
servicespractical advice
E57321
E57322
7/27/2019 Choosing Surge Arresters for LV Networks
9/1292506E.fm/10 Schneider ElectricUpdated: 21/02/02
surge arresterschoosing surge arresters for :LV networks
installation constraints PRF1class 1 test surge arresterPRF1 surge arrester with reactor#
if the distance between the two incoming protectionsurge arresters is < 15 m, mount an L40A decouplingcoil cat. n. 16640 in series.
PRF1 surge arrester without reactor#
if the two incoming protection surge arresters are installed in separate switch-boards, more than 15 m apart, the decoupling coil is not required.
E57662
E57662
E57603
E57626
#
The 50 cm rule also applies to connection of the PRF1 surge arrester
E57602
STM STM
O-OFF
O-OFF
NL
MERLINGER
IN
multi 9
PRDMERL
INGERIN
C Neutr
al r
multi 9
PRD
O-OFF
O-OFF
limp=60k
A
Up 4kV
Uc=255V
50HzAC
Q=30As
1 6 6 2
0
MERLING
ERIN
PRF1
MERLIN GE
RIN
limp= 60
kA
Up 4kV
Uc=255V
50HzAC
Q= 30As
1 6 6 2 0
PRF1
Un 500V
50/60Hz
In40A
Ln=15H
1 6 6 4 0
MERLING
ERIN
L40A
Un 500V5
0/60Hz
In 40A
Ln= 15
H
1 6 6 4 0
MERLINGE
RIN
L40A
PF, PE
PRD, STM
NL
multi 9
PRD
C Neutra
lr
multi 9
PRD
limp= 60
kA
Up 4kV
Uc=255V
50HzAC
Q= 30As
1 6 6
2 0
PRF1
limp =60kA
Up 4kV
Uc= 255
V50HzAC
Q=30As
1 6 6
2 0
PRF1
O-OFF
O-OFF
O-OFF
O-OFF
PF, PE
PRD, STM
limp=60kA
Up4kV
Uc= 255V50
HzAC
Q=30As
1 6 6 2
0
MERLIN
GERIN
PRF1
limp =60kA
Up 4kV
Uc=255V5
0HzAC
Q=30As
MERLING
ERIN
1 6 6 2 0
PRF1
T
OFF
O-OFF
O-OFF
O-OFF
O-OFF
d1
d2
d3
d1+d2
+d350
cm
125 A Max.gL (22x58)
Compact NS 160HTM125D Max.
PRF1
16 35 mm2
16 50 mm2
servicespractical advice
7/27/2019 Choosing Surge Arresters for LV Networks
10/1292506E.fm/11Schneider Electric Updated: 21/02/02
surge arresterschoosing surge arresters for :LV networks (continued)communication networks
case of earth leakage
devices
The best way to guarantee the continuity ofsupply of priority circuits, while ensuring
safety in the case of atmosphericdisturbances is to combine:#
a surge arrester that can protect sensitiveloads against atmospheric overvoltages#
a circuit-breaker with an upstream earthleakage protection device of 300/500 mAselective, to ensure total earth leakagediscrimination#
a residual current device of 30 mA and "si"type placed downstream is insensitive to thistype of disturbance.
Another solution can be foreseen: use acircuit-breaker (not earth leakage) at the
incoming end of the installation followed bya residual current circuit-breaker. The surgearrester is to be connected between the twodevices (see below).Careful, the link L must be class II.
In installations fitted out with a general earthleakage protection, it is preferable to placethe surge arrester upstream from thisprotection.However, certain power distributors do notallow intervention at this distribution level(this is for instance the case for LVsubscribers in France).It is therefore necessary to plan a selectivedevice of the
P
type, or with delayedtripping, so that when the current runs off tothe earth through the surge arrester, it doesnot produce nuisance tripping of theincoming circuit-breaker.
ID "si"30 mA
ID
30 mA
residual current
device of the2
type or delayed
disconnection
circuit-
breaker
surge
arrester
other circuits prioritycircuits
L: class II link
circuit-
breaker
combined
with RCCB
uses
residual
current
circuit-
breaker
surge arrester
disconnection
circuit-
breaker
surge
arrester
uses
high
sensitivity
selective
RCD
with the earth
leakage
protection
device of the
2
type
residual current
device of the2
type or delayed
choice depending on thecommunication network
type of network series PRC PRI 1248 V PRI 6 V
telecommunication
digital 300 Hz RTC
numeris access T0
specialised 24 V line
specialised modem line base
band 64 kbit/s
MIC line and access T2
computer
current loop 200 V
current loop 1248 V
RS 232 (12 V)
RS 485 (12 V)
current loop 6 V
RS 422 (6 V)
RS 423 (6 V)
supply 12/48 V
fire safety centralising equipment,
ELV load, intrusion centralising
servicespractical advice
E57324
E57325
E573256
7/27/2019 Choosing Surge Arresters for LV Networks
11/1292506E.fm/12 Schneider ElectricUpdated: 21/02/02
end of life surge arresters for LV networksAt the end of its life the surge arrester or itscartridge is destroyed, this can be one of 2
types:#
internal end of life disconnection:5
the accumulation of electrical shockscauses the varistors to age, which translatesinto a rise in the leakage current, above 1mA there is thermal runaway anddisconnection of the surge arrester#
external end of life disconnection:5
is produced when an overvoltage is tooenergetic (lightning stroke directly on theline), above the surge arresters flowcapacity there where the varistors areplaced in solid short-circuit with the earth (or
possible between the phase and neutral)5
this short-circuit is eliminated by themandatory disconnection circuit-breaker.
surge arresters for communicationnetworksThe surge arrestor is only at the end of life inshort-circuit, following the accumulation ofelectrical shocks which causes it to age orfollowing an overvoltage that is tooenergetic.
indication PRD65r and PRD40r surge arrestersThese surge arresters include:#
a built-in NO/NC remote indication contact# a mechanical indicator on the front panelwith a power reserve:5
white: normal operation (1)5
white/red: cartridge to be replaced in thenear future (2)5
red: cartridge to be immediatelyreplaced (3).
series PRD65, PRD40, PRD15, PRD8,PE40, PE15, PE8, ST, PRC and PRI surgearrestersThese surge arresters include:#
a mechanical indicator on front panel:5
white: normal operation
5
red: surge arrester to be immediatelyreplaced.
PE65 surge arrestersThese surge arresters include:#
a mechanical indicator on the front panelwith a power reserve:5
white: normal operation
5
white/red: cartridge is to be replaced in thenear future5
red: surge arrester is to be immediatelyreplaced.
PF surge arresters
These surge arresters include:#
a built-in remote indication NC contact forthe PF65r and PF30r models#
an orange light indicator on the front panel:5
not lit: normal operation5
flashing: surge arrester to be immediatelyreplaced.
14 11 12
E57214
(1)
14 11 12
E57217
(2)
14 11 12
E57215
(3)
indication by the circuit-breaker#
end of life is indicated by the opendisconnection circuit-breaker#
the best indication consists in indication ofthe continuity of protection, which is linked tothe closing of the upstream circuit-breakerthat is combined with an SD contact and
surge arrester operation indication using:
5
the transfer contact that is built-into thePF65r, PF30r, PRD65r and PRD40r surgearresters (diagram 1)5
or an EM/RM indication auxiliary(diagram 2)
diagram 1 (example PRD) diagram 2
11 12
NL
MERLING
ERIN
Imax. :65
kA
Un : 230 V
~
Uc :440
V~
In :20kA
Up:1,8k
V
multi 9
PRDMER
LINGERIN
Imax. : 6
5 kA
Un :230 V
~
Uc:4 40
V~
In:20 k
A
Up:1,8
kV
multi 9
PRD
O-OFF
O-OFF
SD
O-OFF
O-OFF
14 11
12
indicator
disconnect
ion
circuit-
breaker
surge
arrester
0.5mm
2 1.5m
m2
12VDC-
10mA
250VAC-
1A
2A
1 51 5
2 4
6O-O
FF
O-OFF
O-OFF
O-OFF
EMUn:
230Va
NL
MERLINGE
RIN
C40r-275
Imax:40kA
(8/20)
In:15kA(8/2
0)
Up:1,2kV
Uc:275V
multi 9
PRDMERL
INGERIN
CNeutral
r
multi 9
16562
RMUn : 2
30Va
250VAC-
50Hz
6VDC-
10mA
250VAC-
50Hz-5
A
servicespractical advice
surge arrestersend of life and indication
E57243
E57320
7/27/2019 Choosing Surge Arresters for LV Networks
12/12
installation#
adaptable on PRD, PE, ST, PRI and PRCsurge arresters#
the EM/RM modules allow for up to 15surge arrester modules of 18 mm with a limitof 270 mm to be monitored using an opticallink#
the EM emitter is mounted to the left, theRM receiver to the right#
the RM receiver includes an NO/NCremote transfer contact for the combinedsurge arrester(s)#
supply of the EM/RM modules must beprotected by a breaking device(2 A).
technical data#
power:5
min.: 6 V DC and 10 mA5
max.: 250 V AC and 5 A#
isolation:5 between contacts: 1 kV AC5
between the contacts and the coil:2.5 kV AC.
indication#
the 2 green indicators are lit up and thered indicator is not:5
EM/RM modules: OK5
surge arrester(s): OK#
the green EM indicator is lit up,the red indicator is lit up:5
EM/RM modules: OK5
verify the status of the surge arrester(s)#
all indicators are extinguished:5
verify the supply of modules.
1 5
1 5
2 46
O-OFF
O-OFF
EMUn:
230Va
O-OFF
O-OFF
NL
MERLINGE
RIN
C40r-275
Imax:40kA
(8/20)
In:15kA(8/2
0)
Up:1,2kV
Uc:275V
multi 9
PRDMERL
INGERIN
CNeutral r
multi 9
PRD
16562
RMUn: 2
30 Va
2A
250VAC-
50Hz
6VDC-
10mA
250VAC-
50Hz-5
A
NL
EMUn:2
30Va
RMUn:2
30Va
16592
16592
opticallink
EMemitter
RMreceive
r
redfault
indicator
NO/NCcon
tactgreeni
ndicator
forcorrectoperat
ion
greenindic
ator
forcorrect
operation
PRD / PE / ST / PRC / PRI
EM RMPRD...
2 4 6
OK
PRD / PE / ST / PRC / PRIEM RM
PRD...
2 4 6
servicespractical advice
surge arrestersEM/RM remote indication modules
additionalinformation
dimensions : page 90148/2conseils pratiques : page 92506/2
E57318
E57319
E57337