CORPORATE HEADQUARTERS 515 Broadway Albany, New York 12207-2964 T 518.257.3000 F 518.257.3100 NEW YORK OFFICE One Penn Plaza, 52nd Floor New York, New York 10119-0098 T 212.273.5000 F 212.273.5121 BUFFALO OFFICE 539 Franklin Street Buffalo, New York 14202-1109 T 716.884.9780 F 716.884.9787 www.dasny.org Alfonso L. Carney, Jr., Chair Paul T. Williams, Jr., President CODE PERMITTING PROGRAM ANNUAL REPORT Code Compliance Unit January 2015
Transcript
Page 1: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

CORPORATE HEADQUARTERS

515 Broadway Albany, New York 12207-2964

T 518.257.3000 F 518.257.3100

NEW YORK OFFICE

One Penn Plaza, 52nd Floor New York, New York 10119-0098

T 212.273.5000 F 212.273.5121

BUFFALO OFFICE

539 Franklin Street Buffalo, New York 14202-1109

T 716.884.9780 F 716.884.9787

www.dasny.org

Alfonso L. Carney, Jr., Chair

Paul T. Williams, Jr., President

CODE PERMITTING

PROGRAM

ANNUAL REPORT Code Compliance Unit

January 2015

Page 2: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

In accordance with Part 1204 of Title 19 of the Official Compilation of Codes, Rules and Regulations of the State of New York, DASNY has been designated as a construction permitting agency and, as such is responsible for the administration and enforcement of the Uniform Fire Prevention and Building Code (Uniform Code) as it pertains to activities the Authority undertakes within buildings in its custody. In accordance with section 1204-14 DASNY must prepare on or before February 1st of each year a report pertaining to the activities undertaken during the preceding calendar year. The following information is required to be included in the report for the year 2014: 1. DASNY

515 Broadway Albany, NY 12207

2. Code Coordinators;

a) James D. Godfrey b) John Adams

3. Code Compliance Managers;

a) James D. Godfrey b) Mark S. Moran c) Richard Theriault d) Jeanne Teale e) John Adams

4. Construction Permits issued - See Appendix A. 5. Code Compliance Certificates issued - See Appendix B. 6. Temporary Approvals for Occupancy issued - See Appendix C. 7. Open Construction Permits - See Appendix D. 8. Fire Safety Inspections - For the purposes of Section 1204.12, fire safety inspections were

conducted within DASNY owned buildings as follows:

a) DASNY’s Office Buildings (Albany, Delmar and Buffalo): Inspections are conducted by the DASNY’s Code Coordinator. Correction plans when necessary are maintained and made available through DASNY.

9. List of findings noted during fire safety inspections at the Authority’s office buildings:

See Appendix E, F and G.

Page 3: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

10. Outstanding Violations: All violations noted during the annual fire safety inspections have been completed or have been included on a correction plan in the Albany, Delmar and Buffalo offices.

11. Code related complaints - As of December 31, 2014, no complaints have been filed. This report is prepared in accordance with Part 1204 of Title 19 of the Official Compilation of Code, Rules and Regulations of the State of New York.

Page 4: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix A

Code Compliance Construction Permits Approved

JDE Number Project Title / JDE Description Project Description Permit # Status

2770309999 RPCI-Permit Only Projects BLSC 23kV Switchgear Replacement 14-165 View Details

Phase Description: N/A CP #14-165 Issued

2770309999 RPCI-Permit Only Projects Endoscopy Patient Holding Renovations 14-166 View Details

Phase Description: N/A CP #14-166 Issued

2770309999 RPCI-Permit Only Projects Endoscopy Renovations 14-14 View Details

Phase Description: N/A TAO Approved

2770309999 RPCI-Permit Only Projects Endoscopy Renovations-Frozen Section 14-162 View Details

Phase Description: N/A CP #14-162 Issued

2770309999 RPCI-Permit Only Projects Specialty Pharmacy 14-164 View Details

Phase Description: N/A CP #14-164 Issued

2809809999 VCDOH-DOH/WC-Security System Campus Wide Security System 14-05 View Details

Phase Description: N/A CP #14-05 Issued

2825409999 ROCKPC-Consolidate Support New Central Services Building 14-60 View Details

Phase Description: N/A CP #14-60 Issued

2940409999 FLDDSO-Rehab Entries/Walks B58 Vienna Bldg Rehab Entries-Walks & Asb Abatement 14-108 View Details

Phase Description: N/A CP #14-108 Issued

2958709999 VADDSO-Replace Sprinklers Replace existing sprinkler systems @ Hostel# 2357 14-20 View Details

Phase Description: N/A CP #14-20 Expired

2985009999 STBKSU-New Parking Garage Package B - Roundabout and Roadway Improvements 14-106 View Details

Phase Description: N/A CP #14-106 Issued

3031109999 CANTCT-Heritage & Rushton Exterior Rehab and Asbestos Abatement Mohawk Hall 14-31 View Details

Phase Description: N/A CP #14-31 Expired

3071109999 ONTAC-Flooring/Carpet Replace Hulbert & Huntington Halls Flooring Replacement 14-171 View Details

Phase Description: N/A CP #14-171 Issued

3081609999 BRNXPC-Provide Utility Provide Utility Connections to Existing Bldgs. 5, 12 & 13 14-98 View Details

Phase Description: N/A CP #14-98 Issued

3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details

Phase Description: N/A CCC Approved

3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP Fire Safety Initiative Rolland IRA 14-08 View Details

Phase Description: N/A CCC Approved

3127009999 PLATC-Mason/Moffit Halls Rehab Rehabilitation and Asbestos Abatement of Moffitt Hall 14-141 View Details

Phase Description: N/A CP #14-141 Issued

3129509999 BRNXPC-Recovery Ctr Bldg 5 Renovations and Asbestos Removal 14-73 View Details

Phase Description: Demo and Asbestos Abatement CP #14-73A Expired

3131909999 CDPC-Encapsulate Deteriorated Encapsulate Deteriorated Concrete Ideas 14-103 View Details

Phase Description: N/A CP #14-103 Issued

3132309999 CNDDSO-FS-BC 332 Hillside St. GAP Fire Safety Iniative Hillside IRA. 14-09 View Details

Phase Description: N/A CCC Approved

Page 5: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix A

3133709999 SUDDSO-New HVAC Cntrls CIT 1&2 Installation of a new DDC control system in CIT 1 and CIT 2. 14-104 View Details

Phase Description: N/A CP #14-104 Issued

3133809999 CDDDSO-Boiler and DHW Sys Upg Boiler and DHW System Upgrade 14-46 View Details

Phase Description: N/A CCC Approved

3134209999 WEDDSO-FS-BC 163 Hendricks Blv Fire Safety Improvements at Hendricks Blvd. Cheektowaga 14-111 View Details

Phase Description: N/A CP #14-111 Expired

3134309999 SIDDSO-New Boiler Controls Burner & Boiler Controls Upgrade 14-49 View Details

Phase Description: N/A CP #14-49 Issued

3134709999 WEDDSO-FS-BC 6520 Donlen Drive Fire Safety Improvements at Donlen Dr. Ellicottville 14-74 View Details

Phase Description: N/A CP #14-74 Expired

3134809999 SIDDSO-Replace Fire Alarm Syst SIDDSO Executive Way Fire Alarm System Upgrade 14-75 View Details

Phase Description: N/A CP #14-75 Issued

3135309999 WEDDSO-FS-HC 19 Pearl Street Fire Safety Improvements 14-41 View Details

Phase Description: N/A CP #14-41 Expired

3137209999 PURCHC-Bathrm Renov & Asbestos Bathroom Rehab Phase 2 14-51 View Details

Phase Description: N/A TAO Approved

3140409999 COBSAT-Fire Alarms Residence Halls Fire Alarm Replacement & Assoc. Abatement 14-21 View Details

Phase Description: Ten Eyck, Fake, Parsons, Davis and Dix Residence Halls TAO Expired

3141009999 FLDDSO-FS-BC 2380 Latta Rd Fire Safety Improvements at 2380 Latta Rd 14-63 View Details

Phase Description: N/A CP #14-63 Issued

3141109999 FLDDSO-FS-BC 4080 Circle Dr Fire Safety Improvements @ 4080 Circle Drive 14-64 View Details

Phase Description: N/A CP #14-64 Issued

3142609999 BUFFPC-Repl Dock Leveler B#62A Loading Dock Enclosure 14-29 View Details

Phase Description: N/A TAO Pending

3143109999 NEWPZC-Card Access Card Access Upgrade 14-18 View Details

Phase Description: Bliss, Bouton, Capen, Gage & Scudder Halls Card Access CP #14-18A Issued

3146809999 SUDDSO-FS-HC 225 Bayley Rd Hostel 1958, 225 Bayley Rd Massena NY Fire Safety Upgrade 14-67 View Details

Phase Description: N/A CP #14-67 Issued

3146909999 SUDDSO-FS-HC 227 Bayley Rd Fire Safety Upgrade 14-140 View Details

Phase Description: N/A CP #14-140 Issued

3147409999 FLDDSO-FS-BC 1310 Crittenden Fire Safety Improvements 14-65 View Details

Phase Description: N/A CP #14-65 Issued

3151009999 ALBSU-Livingston Facade Repair Window Replacement, Exterior Repairs, Haz Mat Abatement 14-135 View Details

Phase Description: Facade Restoration CP #14-135A Issued Phase Description: Window Replacement CP #14-135B Issued

3154009999 LIDDSO-FS-BC 26 East Moriches Fire Safety Upgrades 14-71 View Details

Phase Description: N/A CP #14-71 Issued

3155509999 GRILAB-Bldg 1 Chill Plant Chiller Plant Replacement 14-134 View Details

Phase Description: N/A CP #14-134 Issued

3157009999 LEDDSO-FS-BC 1 Skerry Court Fire Safety Upgrades at H# 10982, 7089, 10495, 10908, 14-127 View Details

Page 6: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix A 9833

Phase Description: N/A CP #14-127 Issued

3157809999 CDPC-Replace Data Ctr AC Unit Replace Data Center AC Unit 14-47 View Details

Phase Description: N/A CP #14-47 Expired

3157909999 FLDDSO-FS-BC 331 Whittier Rd Fire Safety Improvements at 331 Whittier Rd 14-66 View Details

Phase Description: N/A CP #14-66 Issued

3158009999 STUATC-Phase V Stutzman ATC Phase V 14-86 View Details

Phase Description: N/A CP #14-86 Issued

3158109999 STLATC-Phase V Building #67 Repairs - Phase V 14-61 View Details

Phase Description: N/A CP #14-61 Expired

3158209999 NORATC-Phase V Phase V Renovations Exterior Facade Repairs 14-52 View Details

Phase Description: N/A CP #14-52 Issued

3158309999 VANATC-Phase V Phase 5 Renovations 14-85 View Details

Phase Description: N/A CP #14-85 Issued

3158409999 CKPATC-Phase V Miscellaneous Rehab Phase V 14-105 View Details

Phase Description: N/A CP #14-105 Issued

3158509999 BRXATC-Phase V Bronx ATC Phase V Bldg 13 14-12 View Details

Phase Description: N/A CP #14-12 Expired

3160309999 CNDDSO-FS-BC 28 North Main St Hostel# 1353, 28 N. Main St Fire Safety Upgrades 14-99 View Details

Phase Description: N/A CP #14-99 Issued

3160409999 CNDDSO-FS-BC 2 Regina St Hostel #8562, 2 Regina St Fire Safety Upgrade 14-100 View Details

Phase Description: N/A CP #14-100 Issued

3160609999 ALFDCT-Boilers Phase II Boiler Decentraization - Schultz, Burdick, Braddon, Peet 14-04 View Details

Phase Description: N/A CCC Approved

3160909999 SAGCPC-Asbestos Abatement & Asbestos Abatement, minor HVAC duct and piping alterations 14-48 View Details

Phase Description: N/A CP #14-48 Expired

3161309999 VETOXF-Construct New Maint Bld New Maintenance Storage Building 14-16 View Details

Phase Description: N/A CCC Approved

3162209999 SIDDSO-Roof Replace & Re-point Roof Replacement & Asbestos 14-17 View Details

Phase Description: N/A CCC Approved

3162409999 IBR-Install New Roof Bldg #1 Installation of a new roof over the existing roof system 14-13 View Details

Phase Description: N/A CCC Approved

3164709999 ONTAC-Grant Hall Rehab Restoration of Grant Hall 14-07 View Details

Phase Description: N/A TAO Approved

3164809999 ONTAC-Telecomm Upgrade Hulbert Hall Telecommunications Upgrade 14-27 View Details

Phase Description: N/A CCC Approved

3166209999 CDDDSO-FS-BC 11 Bowen Hill Rd Fire Safety Upgrades at Hostel # 9683 and Hostel # 10135 14-15 View Details

Phase Description: N/A CP #14-15 Expired

3167609999 IBR-Provide Combustible Storag Flammable Materials Storage 14-11 View Details

Phase Description: N/A CP #14-11 Issued

3167709999 LIDDSO-Construct 2-Bed Additn Two-bedroom addition to existing IRA 14-32 View Details

Phase Description: N/A TAO Approved

Page 7: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix A 3168609999 WEDDSO-FS-HC 8746 Highland Ave Fire Safety Improvements @ 8746 Highland Ave 14-42 View Details

Phase Description: N/A CP #14-42 Expired

3168709999 WEDDSO-FS-HC 39 Maple Avenue Fire Safety Improvements @ 39 Maple Ave 14-28 View Details

Phase Description: N/A CP #14-28 Expired

3171309999 ROCKPC-Demolition of Bldg 11 Demolition of Bldg 11 14-102 View Details

Phase Description: N/A CP #14-102 Issued

3174509999 BUFC-Tower One Renovation Tower 1 Building Renovations and Asbestos Abatement 14-76 View Details

Phase Description: N/A CP #14-76 Issued

3183809999 SIDDSO-Single Bed Dwelling Bldg 47D Renovation and Addition 14-62 View Details

Phase Description: N/A CP #14-62 Issued

3186409999 BUFFPC-Repl Roof Sctns B 51 Roof Replace 14-59 View Details

Phase Description: N/A CP #14-59 Expired

3188409999 LIDDSO-Replace Deteriorated Window Replacement 14-82 View Details

Phase Description: N/A CP #14-82 Expired

3189809999 BKDDSO-Repl Windws & Ext Doors Replace Windows and Doors 14-160 View Details

Phase Description: N/A CP #14-160 Issued

3190009999 OSWGC-Compl Int Renov-Waterbur Waterbury Residence Hall Renovations 14-153 View Details

Phase Description: N/A CP #14-153 Issued

3190409999 BUFSU-Elevators Elevator Modernization & Asbestos Abatement 14-80 View Details

Phase Description: N/A CP #14-80 Issued

3190509999 BUFSU-Laundry Facilities Wilkeson & Fargo Quads Laundry Renovation 14-23 View Details

Phase Description: N/A CP #14-23 Issued

3190609999 BUFSU-Clement Hall Roofs Roof Replacement & Asbestos Abate @ Clement Hall S. Campus 14-19 View Details

Phase Description: N/A CP #14-19 Issued

3191409999 FLDDSO-AHU Sys Upgrade B#58 AHU System Upgrade 14-132 View Details

Phase Description: N/A CP #14-132 Issued

3191609999 FLDDSO-2013/14 CMM Hostel # 2477, Peterman Rd, Siding & Window Replacement 14-123 View Details

Phase Description: N/A CP #14-123 Issued

3191609999 FLDDSO-2013/14 CMM Hostel # 2494, 338 Gibson St. Siding Replacement 14-124 View Details

Phase Description: N/A CP #14-124 Issued

3191609999 FLDDSO-2013/14 CMM Hostel # 2550, 5700 Martz Rd, Siding Replacement 14-125 View Details

Phase Description: N/A CP #14-125 Issued

3191609999 FLDDSO-2013/14 CMM Hostel #10027 4519 St. Paul Blvd., Rochester, Kitchen Reno 14-113 View Details

Phase Description: N/A CP #14-113 Issued

3191609999 FLDDSO-2013/14 CMM Hostel #11140 77 Firestone Dr., Rochester, Kitchen Reno 14-114 View Details

Phase Description: N/A CP #14-114 Issued

3191609999 FLDDSO-2013/14 CMM Hostel #1220 671 Wyncoop Creek Rd, Chemung, Fence Replaceme 14-119 View Details

Phase Description: N/A CCC Approved

3191609999 FLDDSO-2013/14 CMM Hostel #1220 671 Wyncoop Creek Rd., Chemung, Basement Entran 14-118 View Details

Phase Description: N/A CP #14-118 Issued

Page 8: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix A 3191609999 FLDDSO-2013/14 CMM Hostel #1222 108 Keyel Dr Rochester NY 14625, Roof

Repair 14-72 View Details

Phase Description: N/A CP #14-72 Issued

3191609999 FLDDSO-2013/14 CMM Hostel #140 60 Elizabeth St., Dansville, Fire Escape Repairs 14-117 View Details

Phase Description: N/A CP #14-117 Issued

3191609999 FLDDSO-2013/14 CMM Hostel #209 2747 Route 96, Waterloo, NY Bedroom-Office Renov 14-112 View Details

Phase Description: N/A CP #14-112 Issued

3191609999 FLDDSO-2013/14 CMM Hostel #2178 44 Greenbriar Dr.,Gates, NY 14060 Replace Ramp 14-121 View Details

Phase Description: N/A CP #14-121 Issued

3191609999 FLDDSO-2013/14 CMM Hostel #2494 338 Gibson St., Canadaigua, NY Bathroom Reno 14-116 View Details

Phase Description: N/A CP #14-116 Expired

3191609999 FLDDSO-2013/14 CMM Hostel #340 30 Pierce St., Webster, NY Replace Back Patio 14-122 View Details

Phase Description: N/A CP #14-122 Issued

3191609999 FLDDSO-2013/14 CMM Hostel #354 255 Cuyler St., Palmyra, Bathroom Reno 14-115 View Details

Phase Description: N/A CP #14-115 Issued

3191609999 FLDDSO-2013/14 CMM Hostel #439,6807 Richmond Mills Rd. Roof Repairs 14-91 View Details

Phase Description: N/A CCC Approved

3191609999 FLDDSO-2013/14 CMM Hostel #638 1591 Wellington Ave, Savannah Replace Porch & Ra 14-120 View Details

Phase Description: N/A CP #14-120 Issued

3191609999 FLDDSO-2013/14 CMM Hostel #7043 545 Vienna St, Roof Repairs 14-92 View Details

Phase Description: N/A CCC Approved

3191609999 FLDDSO-2013/14 CMM Hostel 11155 49 South Ave, Repalce Windows & Siding 14-126 View Details

Phase Description: N/A CP #14-126 Issued

3191609999 FLDDSO-2013/14 CMM Hostel# 352, 4080 Circle Drive Williamson NY Roof Repair 14-93 View Details

Phase Description: N/A CP #14-93 Issued

3191609999 FLDDSO-2013/14 CMM Hostel# 430, Siing Sing Rd, Horseheads, NY Driveway Repiars 14-145 View Details

Phase Description: N/A CCC Pending

3191609999 FLDDSO-2013/14 CMM Install Generator at 108 Cobblestone Tr. 14-30 View Details

Phase Description: N/A CP #14-30 Expired

3191709999 WEDDSO-2013/14 CMM Hostel #10228 - Remington - Kitchen 14-57 View Details

Phase Description: N/A CP #14-57 Expired

3191709999 WEDDSO-2013/14 CMM Hostel #10228 979 Remington Dr. North Tonawanda Roof Repairs 14-43 View Details

Phase Description: N/A CP #14-43 Expired

3191709999 WEDDSO-2013/14 CMM Hostel #141 510 W. Main St.,Bathroom Renovs 14-34 View Details

Phase Description: N/A CP #14-34 Expired

3191709999 WEDDSO-2013/14 CMM Hostel #301 - South Park - Kitchen Renovation 14-56 View Details

Phase Description: N/A CP #14-56 Expired

3191709999 WEDDSO-2013/14 CMM Hostel #424 -Coolidge - Bathroom Renovation 14-54 View Details

Phase Description: N/A CP #14-54 Expired

Page 9: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix A

3191709999 WEDDSO-2013/14 CMM Hostel #7044 - Leydecker Rd - Kitchen-Bathroom 14-55 View Details

Phase Description: N/A CP #14-55 Expired

3191709999 WEDDSO-2013/14 CMM Hostel #8702, 710 McKinley Ave Dunkirk NY Roof Repairs 14-45 View Details

Phase Description: N/A CCC Approved

3191709999 WEDDSO-2013/14 CMM Hostel #9283 Roof Repairs 14-44 View Details

Phase Description: N/A CCC Pending

3191709999 WEDDSO-2013/14 CMM Hostel #9776 @ 6228 Dale Rd, Demo & New Construction Plan 14-36 View Details

Phase Description: N/A CP #14-36 Issued

3191709999 WEDDSO-2013/14 CMM Hostel 7293 @ 10380 Peck Hill Rd Bathroom Renovations 14-138 View Details

Phase Description: N/A CP #14-138 Issued

3191709999 WEDDSO-2013/14 CMM Hostel 9992 - 3965 Mapleton Wheatfield, Bathroom Renovs 14-110 View Details

Phase Description: N/A CP #14-110 Issued

3191709999 WEDDSO-2013/14 CMM Hostel# 10144 Bathroom Renovations 14-39 View Details

Phase Description: N/A CP #14-39 Issued

3191709999 WEDDSO-2013/14 CMM Hostel# 10436, 25 Haussauer Rd, Bathroom Renovs 14-35 View Details

Phase Description: N/A CP #14-35 Expired

3191709999 WEDDSO-2013/14 CMM Hostel# 10563 @ Bowen Road 14-58 View Details

Phase Description: N/A CP #14-58 Expired

3191709999 WEDDSO-2013/14 CMM Hostel# 11252, 8197 Schreiner, Roof Repairs 14-25 View Details

Phase Description: N/A CP #14-25 Expired

3191709999 WEDDSO-2013/14 CMM Hostel# 11469 - Upstairs Bathroom 14-139 View Details

Phase Description: N/A CP #14-139 Issued

3191709999 WEDDSO-2013/14 CMM Hostel# 1699, 6574 Dysinger Rd, Bathroom Renovs 14-40 View Details

Phase Description: N/A CCC Approved

3191709999 WEDDSO-2013/14 CMM Hostel# 447, 6187 Jefferson St., Bathroom Renovs 14-01 View Details

Phase Description: N/A CP #14-01 Expired

3191709999 WEDDSO-2013/14 CMM Hostel# 7303, 540 Leydecker Rd Bathroom Renovations 14-37 View Details

Phase Description: N/A CCC Approved

3191709999 WEDDSO-2013/14 CMM Hostel# 9140, 86 Seel St Bathroom Renovations 14-109 View Details

Phase Description: N/A CP #14-109 Issued

3191709999 WEDDSO-2013/14 CMM Hostel# 9522, 5866 Route 39 Bathroom Renovations 14-38 View Details

Phase Description: N/A CP #14-38 Issued

3191709999 WEDDSO-2013/14 CMM Hostel# 9818, 9523 Fuss Hill Rd Bathroom Renovations 14-02 View Details

Phase Description: N/A CP #14-02 Expired

3191709999 WEDDSO-2013/14 CMM Hostel#11463 - Bathroom Renovations 14-33 View Details

Phase Description: N/A CP #14-33 Expired

3191709999 WEDDSO-2013/14 CMM Replace Hot Water Tanks, Furances and Air Conditioning Units 14-03 View Details

Phase Description: N/A CCC Approved

3191909999 CDDDSO-2013/14 CMM Hosrel 984 2317 Broadway, Kitchen Renovations 14-142 View Details

Phase Description: N/A CP #14-142 Issued

3191909999 CDDDSO-2013/14 CMM Hostel # 9750, 954 Bennedict Rd Ballston Lake NY Roof 14-77 View Details

Page 10: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix A Repair

Phase Description: N/A CP #14-77 Expired

3191909999 CDDDSO-2013/14 CMM Hostel # 9843, 387 Gainsevoort Rd Fort Edward NY Roof Repair 14-78 View Details

Phase Description: N/A CP #14-78 Expired

3191909999 CDDDSO-2013/14 CMM Hostel #2451, 2243 Route 22A, Kitchen Renovation 14-147 View Details

Phase Description: N/A CP #14-147 Expired

3191909999 CDDDSO-2013/14 CMM Hostel 10409 160 Butler Pond Rd, Bathroom Renov 14-143 View Details

Phase Description: N/A CP #14-143 Issued

3191909999 CDDDSO-2013/14 CMM Hostel 11466, 17 Tripoli Rd Hudson Falls, Kitchen Renovation 14-148 View Details

Phase Description: N/A CP #14-148 Expired

3191909999 CDDDSO-2013/14 CMM Hostel 22, 2415 Albany St, Kitchen Renovation 14-146 View Details

Phase Description: N/A CP #14-146 Expired

3191909999 CDDDSO-2013/14 CMM Hostel 8953, 12 Fenway Circle, Kitchen Renov 14-150 View Details

Phase Description: N/A CP #14-150 Issued

3191909999 CDDDSO-2013/14 CMM Hostel 9734, 65 Worth Rd, Wilton NY, Kitchen Renovation 14-149 View Details

Phase Description: N/A CP #14-149 Issued

3191909999 CDDDSO-2013/14 CMM Hostel# 22, 2415 Albany Street Stair Replacement 14-128 View Details

Phase Description: N/A CP #14-128 Issued

3191909999 CDDDSO-2013/14 CMM Hostel# 2451, 2243 St. Rt 22A Hampton NY Roof Repair 14-79 View Details

Phase Description: N/A CP #14-79 Expired

3192009999 BRDDSO-2013/14 CMM Hostel #2724, 790 Ducth Valley Road, Ramp Replacement 14-81 View Details

Phase Description: N/A CP #14-81 Expired

3192009999 BRDDSO-2013/14 CMM Hostel 10707, Bathroom Renovations 14-70 View Details

Phase Description: N/A CP #14-70 Issued

3192009999 BRDDSO-2013/14 CMM Replace Ductwork & Asbestos Abatement 14-88 View Details

Phase Description: N/A CP #14-88 Issued

3192209999 LEDDSO-2013/14 CMM Generator Install @ Hostel's 2273, 7670, 1018, 121 & 2267 14-83 View Details

Phase Description: N/A CP #14-83 Issued

3192209999 LEDDSO-2013/14 CMM Generator installations @ Hostel's 7089, 8623 & 1176 14-84 View Details

Phase Description: N/A CP #14-84 Issued

3192309999 TADDSO-2013/14 CMM HVAC System Replacement 14-53 View Details

Phase Description: N/A CP #14-53 Expired

3192309999 TADDSO-2013/14 CMM Standby Generators at Hostels# 10320, 10571, 10367, 1995 14-90 View Details

Phase Description: N/A CP #14-90 Expired

3193009999 BKDDSO-2013/14 CMM H-2794 1364 Dean St. Bathroom Renovation 14-94 View Details

Phase Description: N/A CP #14-94 Expired

3193009999 BKDDSO-2013/14 CMM Hostel# 10273, 3024 Voorhies Ave Brooklyn, NY Roof Repair 14-95 View Details

Phase Description: N/A CP #14-95 Issued

3193209999 SIDDSO-2013/14 CMM Executive Way - Minor Maintenance 14-89 View Details

Phase Description: N/A CCC Approved

3193409999 LIDDSO-2013/14 CMM 102 DeBevoise Ave Kitchen,Dining and Hallway Rehab 14-156 View Details

Page 11: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix A Phase Description: N/A CP #14-156 Issued

3193409999 LIDDSO-2013/14 CMM 2 Marshmallow Drive New Flooring 14-155 View Details

Phase Description: N/A CP #14-155 Issued

3196809999 BRDDSO-FS-BC 3 Jamie Ave FS-BC 14-152 View Details

Phase Description: N/A CP #14-152 Issued

3196909999 BRDDSO-FS-BC 386 Round Pond Rd FS-BC 14-154 View Details

Phase Description: all work except fire alarm CP #14-154A Expired

3197009999 BRDDSO-FS-BC 3601 Scribner Dr FS-BC 14-151 View Details

Phase Description: N/A CP #14-151 Issued

3197409999 BROCKC-Boiler Replacement Boiler Replacements at McLean, Harmon and Gordon Halls 14-50 View Details

Phase Description: N/A CP #14-50 Issued

3198309999 BUFC-Roof Replacement North Tower Roof Replacement & Assoc. Asbestos Abatement 14-22 View Details

Phase Description: N/A CP #14-22 Issued

3198609999 BUFC-Tower 3 Asbestos Abate Tower 3 Phase IV, Asbestos Abatement 14-26 View Details

Phase Description: N/A TAO Approved

3199209999 ALFDCT-Rehab of Public Spaces Entry and Building Renovations 14-137 View Details

Phase Description: N/A CP #14-137 Issued

3200609999 COBSAT-Roof Replacement Draper, Dix & Pearson Halls Re-Roofing & Asbestos Abatement 14-157 View Details

Phase Description: N/A CP #14-157 Issued

3200809999 BKDDSO-Replace Exterior Window Replace Exterior Windows 14-158 View Details

Phase Description: N/A CP #14-158 Issued

3200909999 BKDDSO-Remove Bilco Door Replace Basement Exterior Stairs 14-97 View Details

Phase Description: N/A CP #14-97 Issued

3203409999 BUFFPC-Strozzi 4S/Temp Ent Strozzi Bldg No. 62 Pharmacy Relocation 14-06 View Details

Phase Description: N/A CCC Approved

3203509999 BUFFPC-Secure Outdoor Rec Area Admissions entrance and North Drive Renovations 14-68 View Details

Phase Description: N/A CCC Pending

3204209999 ALBSU-Stuyvesant Tower Renov Window Replacement, Exterior Repairs, Haz Mat Abatement 14-136 View Details

Phase Description: N/A CP #14-136 Issued

3204509999 SIDDSO-Demo Existing Duplex Demo of existing duplex property 14-107 View Details

Phase Description: N/A CP #14-107 Issued

3204609999 MEDDSO-Repl/Repair Front Porch Porch Replacement 14-130 View Details

Phase Description: N/A CP #14-130 Issued

3205209999 BKDDSO-Repl Roofs and Asbestos Replace Roof and Asbestos Abatement 14-161 View Details

Phase Description: N/A CP #14-161 Issued

3206909999 PLATC-Mason Hall Ren Const Adm SUNY Plattsburgh Mason Hall Rehab and Asbestos Abatement 14-10 View Details

Phase Description: N/A CP #14-10 Issued

3208609999 PILGPC-Generator B#102 Install Generator and Remove UG Storage Tank 14-87 View Details

Phase Description: N/A CP #14-87 Issued

3209109999 BKDDSO-Bathroom/Shower Ceramic Bathroom Repairs 14-24 View Details

Page 12: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix A Phase Description: N/A CP #14-24 Expired

3213809999 BUFSU-Laundry Rm Renov Phase 2 Laundry Facilities Renovations 14-168 View Details

Phase Description: N/A CP #14-168 Issued

3213909999 BUFSU-Laundry Rm Renov Phase 1 Governors Complex Laundry Room Repairs 14-170 View Details

Phase Description: N/A CP #14-170 Issued

3216609999 BKDDSO-Repl Fire Stair H-716 Replace Fire Stair landing and Basement Stairs 14-159 View Details

Phase Description: N/A CP #14-159 Issued

3220909999 TADDSO-CMM 2014/15 Hostel# 10429-Central Air Conditioning Installation 14-167 View Details

Phase Description: N/A CP #14-167 Issued

3221009999 BRDDSO-CMM 2014/15 Hostel# 11667, Ramp Framing & Foundation-Basement Plan 14-129 View Details

Phase Description: general construction; electrical CP #14-129A Issued

3221009999 BRDDSO-CMM 2014/15 Hosttel# 10137-Roof Repairs 14-133 View Details

Phase Description: N/A CP #14-133 Issued

3221009999 BRDDSO-CMM 2014/15 Roof Repairs 14-144 View Details

Phase Description: N/A CCC Approved

3223609999 BUFC-Asbestos Removal 100% Phase V-Asbestos Abatement Floors 5-10 Stair B 14-169 View Details

Phase Description: N/A CP #14-169 Issued

3236609999 ELMRPC-Crisis Residence C&Y Crisis Residence 14-101 View Details

Phase Description: Asbestos Abatement & Demo CP #14-101A Issued Phase Description: Asbestos Abatement and Ward Renovations, Bldgs 2 and 4. CP #14-101B Issued Phase Description: Fire Alarm Work Only CP #14-101C Issued

3252009999 BINGPC-Masonry Wall Repairs Maonry Wall Repair 14-131 View Details

Phase Description: N/A CP #14-131 Issued

3263409999 HVDDSO-Improvements Respite Home Improvements Projects 14-163 View Details

Phase Description: N/A CP #14-163 Issued

Page 13: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix B

Code Compliance CCCs Approved

JDE Number Project Title / JDE Description Project Description Permit # Status

2604709999 PILGPC-A & I Tunnels A & I Tunnels 12-45 View Details

Phase Description: N/A CCC Approved

2758309999 BUFFPC-Replace Roof & Related Building# 4 Roof Replacement & Pointing 13-99 View Details

Phase Description: N/A CCC Approved

2770309999 RPCI-Permit Only Projects CCC Extramural Research Facility 11-124 View Details

Phase Description: N/A CCC Approved

2770309999 RPCI-Permit Only Projects Research Studies Bldg Fire Alarm Replacement 13-88 View Details

Phase Description: N/A CCC Approved

2835509999 BROCKC-MacVicar Renovation Macvicar Hall Asbestos Abatement 10-15 View Details

Phase Description: N/A CCC Approved

2836109999 ALBSU-New 500 Bed Facility New 500 Bed Dorm Phase II 10-94 View Details

Phase Description: N/A CCC Approved

2865209999 LIDDSO-SRU Bath Renovate III Bathroom Renovations & Asbestos Abatement 10-106 View Details

Phase Description: SRU 904 & 911 CCC Approved

2866309999 BKDDSO-Window Replacements & window replacement project Buildings 1&2 12-07 View Details

Phase Description: N/A CCC Approved

2897009999 BKDDSO-Correct Code Deficient Correction of Code Deficiencies 11-50 View Details

Phase Description: N/A CCC Approved

2898309999 POTSC-Lehman Hall Bath Rehab Lehman Roof Replacement 13-31 View Details

Phase Description: N/A CCC Approved

2910709999 BINGSU-ECH Collegiate Center Collegiate Center 09-71 View Details

Phase Description: N/A CCC Approved

2934209999 ROCKPC-Cook Chill BAC Replcmnt Replace BAC Equipment 12-81 View Details

Phase Description: N/A CCC Approved

2938509999 OSWGC-Shell Preservation Residence Hall Shell and Safety Improvements- Phase V 11-16 View Details

Phase Description: N/A CCC Approved

2964109999 BUFC-Tower 4 Renovations Domestic Water Heater Replacement-Towers 1-4 12-33 View Details

Phase Description: Tower #4 Renovation and Asbestos Abatement CCC Approved

2972909999 BKDDSO-Rehab Bathrooms, Bldgs. Bathroom rehab and structural slab replacement 12-65 View Details

Phase Description: N/A CCC Approved

2996609999 SIDDSO-Renov to Elec Dist Syst Renovations to Electrical Distribution System 13-85 View Details

Phase Description: N/A CCC Approved

3003109999 LIDDSO-Install Backup Generato LIDDSO Various Standby Generator Installations 13-71 View Details

Phase Description: N/A CCC Approved

3016009999 BUFSU-Ellicott Bathroom Bathroom Alterations and Asbestos Abatement 11-21 View Details

Phase Description: N/A CCC Approved

Page 14: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix B 3024409999 STUATC-Phase IV Misc Rehab Phase IV Miscellaneous Repairs, Building #37 12-58 View Details

Phase Description: N/A CCC Approved

3031109999 CANTCT-Heritage & Rushton Exterior Rehabilitation and Asbestos Abatement Smith Hall 13-52 View Details

Phase Description: N/A CCC Approved

3036209999 CORTC-New Residenc Hall New Residence Hall Project 12-61 View Details

Phase Description: Abatement, Demo, Foundations, Struct Steel, conc Plank CCC Approved Phase Description: Construction of New Residence Hall CCC Approved

3037309999 VETSAB-Interior Renovation PH2 Interior Renovations Phase II 12-36 View Details

Phase Description: N/A CCC Approved

3039909999 TADDSO-Renovation of IRA Renovation of 148 Hardenburgh Road 12-98 View Details

Phase Description: N/A CCC Approved

3051209999 CDPC-Parking Garage - Ph II Parking Garage Structure Repairs 12-49 View Details

Phase Description: N/A CCC Approved

3067109999 LIDDSO-Roof Replacement Roof Replacement and Chimney Enclosure 12-87 View Details

Phase Description: N/A CCC Approved

3067209999 MEDDSO-Replace Roof Roof Replacement and Associated Asbestos Abatement 12-90 View Details

Phase Description: N/A CCC Approved

3071009999 CNDDSO-Construct Fire Sprnklr Sprinkler Replacement @ 2 Tex Pultz Parkway 13-79 View Details

Phase Description: N/A CCC Approved

3071009999 CNDDSO-Construct Fire Sprnklr Sprinkler Replacement @ 4922 Snowhill Drive 13-77 View Details

Phase Description: N/A CCC Approved

3071009999 CNDDSO-Construct Fire Sprnklr Sprinkler replacement @ 53 Rowlee Rd 13-58 View Details

Phase Description: N/A CCC Approved

3071009999 CNDDSO-Construct Fire Sprnklr Sprinkler Replacement @ 6135 Dewey Rd 13-56 View Details

Phase Description: N/A CCC Approved

3071009999 CNDDSO-Construct Fire Sprnklr Sprinkler Replacement at 30 Elm Street 13-82 View Details

Phase Description: N/A CCC Approved

3073809999 SUDDSO-Main Entr & Rear Exit Building 2 Annex Walkway Coverings 13-17 View Details

Phase Description: N/A CCC Approved

3080409999 HH Richard-South Lawn Parking Lot Replacement & Site Landscaping 12-35 View Details

Phase Description: N/A CCC Approved

3083809999 PLATC-DeFredenburgh Hall Renov Rehab. & Associated Asb. Abatement at deFredenburg Hall 13-49 View Details

Phase Description: N/A CCC Approved

3084909999 BRDDSO-Owego Rt 17c HCO Mod Healthcare Res RT17C & Holiday Hill Rd 13-38 View Details

Phase Description: N/A CCC Approved

3085509999 BUFSU-Ellicott Complex, Good Fitness Upgrades @ Ellicott Complex Goodyear Hall & Govenors 13-65 View Details

Phase Description: N/A CCC Approved

3087709999 BUFSU-Exterior Renovation Ph 3 Wilkeson Stair Reconstruction 13-20 View Details

Phase Description: N/A CCC Approved

3089109999 FARMCT-Louver Replacement Attic louver replacement 12-62 View Details

Phase Description: N/A CCC Approved

3090609999 BINGPC-Install New Chiller Chiller Replacement 12-93 View Details

Phase Description: N/A CCC Approved

Page 15: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix B 3092309999 DELHCT-Rehab Bathrooms & Rehab Bathrooms & Upgrade Electrical Capacity 13-41 View Details

Phase Description: N/A CCC Approved

3096109999 NORATC-Install New Boilers Install Boilers, DWH, Generator & loading dock 13-28 View Details

Phase Description: N/A CCC Approved

3096609999 BRDDSO-Union 8 Bed HCO Modular Health Care Residence 1401 Middle Stella Ireland Road 13-70 View Details

Phase Description: N/A CCC Approved

3102309999 GENOC-Replace SoCampus Boilers Replace Boilers and Water Heaters - South Campus 12-119 View Details

Phase Description: N/A CCC Approved

3102909999 FLDDSO-Penfield 16 Bed HCO Health Care Residences (2) 12-89 View Details

Phase Description: N/A CCC Approved

3104109999 DASNY-Rehab Main Bathrooms Renovations & Rehabilation for Men's & Women's Toilet Rooms 12-69 View Details

Phase Description: N/A CCC Approved

3114109999 CNDDSO-Water Main,Sprklr,FA Phase II Sprinkler & FA Upgrades @ 46 W. River Drive 13-62 View Details

Phase Description: N/A CCC Approved

3115309999 VETBTV-Flooring Replacement Dining Room Flooring Replacement 13-87 View Details

Phase Description: N/A CCC Approved

3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP Fire Safety Initiative Rolland IRA 14-08 View Details

Phase Description: N/A CCC Approved

3127709999 WEDDSO-2012/13 Minor Maint Hostel #11252, 8197 Schreiner Rd Eden NY Bathroom Renovation 13-05 View Details

Phase Description: N/A CCC Approved

3127709999 WEDDSO-2012/13 Minor Maint Hostel# 587, 10693 Sisson Hwy North Collins NY Roof Replace 12-116 View Details

Phase Description: N/A CCC Approved

3130009999 NYSDOH-Demolition Controlled Demolition Asbestos containing material Bldg 14 13-64 View Details

Phase Description: N/A CCC Approved

3130209999 PURCHC-Coping & Roof Replace Roof Replacement 13-37 View Details

Phase Description: N/A CCC Approved

3130309999 ONTAC-Parking Lots Campus Wide Parking 13-12 View Details

Phase Description: N/A CCC Approved

3132309999 CNDDSO-FS-BC 332 Hillside St. GAP Fire Safety Iniative Hillside IRA. 14-09 View Details

Phase Description: N/A CCC Approved

3133809999 CDDDSO-Boiler and DHW Sys Upg Boiler and DHW System Upgrade 14-46 View Details

Phase Description: N/A CCC Approved

3135509999 DASNY-Delmar Justice Center Justice Center Kitchen-Bath Rehab 12-104 View Details

Phase Description: General Construction; Plumbing; HVAC; Electrical CCC Approved Phase Description: Demolition CCC Approved

3135809999 BUFC-Asbestos Abatement Asbestos Abatement Tower 1, Phase III 13-34 View Details

Phase Description: N/A CCC Approved

3137209999 PURCHC-Bathrm Renov & Asbestos Bldg 45 Farside Bathroom Rehab & Bldg Abatement 13-61 View Details

Phase Description: JOCs Work - 8 Bathroom Renovations CCC Approved

3140309999 FLDDSO-Upg Fire Spklr Sys Upgrade Fire Sprinkler System 13-44 View Details

Phase Description: N/A CCC Approved

3140509999 COBSAT-Masonry Masonry Restoration atVroman and Wieting Halls 13-43 View Details

Phase Description: N/A CCC Approved

Page 16: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix B 3142209999 BUFFPC-Imp Elec Svc Install AC Improve Electric Service and Install A-C 13-30 View Details

Phase Description: N/A CCC Approved

3142309999 CDDDSO-Replace Septic Sys CReplace Septic System 13-93 View Details

Phase Description: N/A CCC Approved

3143309999 ROCHPC-Smith Rd CR Renov Residental Rehab Roof Replacement and Asbestos Abatement 13-115 View Details

Phase Description: N/A CCC Approved

3158709999 SBEATC-Phase V Misc. Rehab & Assoc Asb. Abate Bldg 5 13-114 View Details

Phase Description: N/A CCC Approved

3159009999 BLAATC-Phase V Phase V OASAS ATC Remove & Replace Casework & Countertop 13-84 View Details

Phase Description: N/A CCC Approved

3160209999 ROCHPC-Replace Chiller-B#41 Replacement Chiller @ Bldg 41 13-35 View Details

Phase Description: N/A CCC Approved

3160609999 ALFDCT-Boilers Phase II Boiler Decentraization - Schultz, Burdick, Braddon, Peet 14-04 View Details

Phase Description: N/A CCC Approved

3161309999 VETOXF-Construct New Maint Bld New Maintenance Storage Building 14-16 View Details

Phase Description: N/A CCC Approved

3161409999 ALBSU-Fire Alarm & Boilers Boiler Replacement 13-83 View Details

Phase Description: N/A CCC Approved

3161509999 BUFSU-CO Detection Services Govenors Goodyear Clement 13-73 View Details

Phase Description: N/A CCC Approved

3161509999 BUFSU-CO Detection Services Renovations to Ellicot Dorms Life Safety System 13-50 View Details

Phase Description: N/A CCC Approved

3161509999 BUFSU-CO Detection Services Renovations to Richmond Dormitory 13-39 View Details

Phase Description: N/A CCC Approved

3162209999 SIDDSO-Roof Replace & Re-point Roof Replacement & Asbestos 14-17 View Details

Phase Description: N/A CCC Approved

3162409999 IBR-Install New Roof Bldg #1 Installation of a new roof over the existing roof system 14-13 View Details

Phase Description: N/A CCC Approved

3164809999 ONTAC-Telecomm Upgrade Hulbert Hall Telecommunications Upgrade 14-27 View Details

Phase Description: N/A CCC Approved

3167309999 BUFC-Hot Water Tank Replace Tower 3 DWH replacement & asbestos abatement at Tower 2 13-75 View Details

Phase Description: N/A CCC Approved

3170809999 BKDDSO-Repl Fire Sprinkler Sys 960 & 980 Elton St Replace Fire Sprinkler Systems 13-107 View Details

Phase Description: N/A CCC Approved

3191609999 FLDDSO-2013/14 CMM Hostel #1220 671 Wyncoop Creek Rd, Chemung, Fence Replaceme 14-119 View Details

Phase Description: N/A CCC Approved

3191609999 FLDDSO-2013/14 CMM Hostel #439,6807 Richmond Mills Rd. Roof Repairs 14-91 View Details

Phase Description: N/A CCC Approved

3191609999 FLDDSO-2013/14 CMM Hostel #7043 545 Vienna St, Roof Repairs 14-92 View Details

Phase Description: N/A CCC Approved

3191609999 FLDDSO-2013/14 CMM Hostel# 10027, 4519 St. Paul St Rochester, NY Roof Repairs 13-101 View Details

Phase Description: N/A CCC Approved

3191709999 WEDDSO-2013/14 CMM Hostel #447, 6187 Jefferson St Ellicottville NY Roof Repairs 13-122 View Details

Page 17: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix B Phase Description: N/A CCC Approved

3191709999 WEDDSO-2013/14 CMM Hostel #8702, 710 McKinley Ave Dunkirk NY Roof Repairs 14-45 View Details

Phase Description: N/A CCC Approved

3191709999 WEDDSO-2013/14 CMM Hostel# 1154, 2003 Orchard Parl Place Bathroom Renovs 13-112 View Details

Phase Description: N/A CCC Approved

3191709999 WEDDSO-2013/14 CMM Hostel# 1699, 6574 Dysinger Rd, Bathroom Renovs 14-40 View Details

Phase Description: N/A CCC Approved

3191709999 WEDDSO-2013/14 CMM Hostel# 7303, 540 Leydecker Rd Bathroom Renovations 14-37 View Details

Phase Description: N/A CCC Approved

3191709999 WEDDSO-2013/14 CMM Replace Hot Water Tanks, Furances and Air Conditioning Units 14-03 View Details

Phase Description: N/A CCC Approved

3192009999 BRDDSO-2013/14 CMM Hostel# 12006, 68 Governeurs Lane Endicott NY Roof Repairs 13-106 View Details

Phase Description: N/A CCC Approved

3192009999 BRDDSO-2013/14 CMM Hostel# 334, 415 Main St Johnson City NY Roof Repairs 13-103 View Details

Phase Description: N/A CCC Approved

3192109999 SUDDSO-2013/14 CMM Hostel #1985, 225 Bayley Ave Massena, NY Roof Repair 13-94 View Details

Phase Description: N/A CCC Approved

3192109999 SUDDSO-2013/14 CMM Hostel 11272, 22 Adams Lane Newcomb NY 12852 Roof Repair 13-98 View Details

Phase Description: N/A CCC Approved

3193209999 SIDDSO-2013/14 CMM Executive Way - Minor Maintenance 14-89 View Details

Phase Description: N/A CCC Approved

3193409999 LIDDSO-2013/14 CMM Hostel# 9402, 11 Sprague Drive Cnt Moriches NY Roof Repair 13-108 View Details

Phase Description: N/A CCC Approved

3193409999 LIDDSO-2013/14 CMM Hostel# 9453, 604 Woodbury Rd Plainview, NY Roof Repair 13-105 View Details

Phase Description: N/A CCC Approved

3203409999 BUFFPC-Strozzi 4S/Temp Ent Strozzi Bldg No. 62 Pharmacy Relocation 14-06 View Details

Phase Description: N/A CCC Approved

3221009999 BRDDSO-CMM 2014/15 Roof Repairs 14-144 View Details

Phase Description: N/A CCC Approved

Page 18: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix C Code Compliance Approved TAOS

JDE Number t Title / JDE Description Project Description Permit # Status

2770309999 RPCI-Permit Only Projects Endoscopy Renovations 14-14 View Details

Phase Description: N/A TAO Approved

2770309999 RPCI-Permit Only Projects Phlebotomy 13-67 View Details

Phase Description: N/A TAO Approved

2770309999 RPCI-Permit Only Projects Renov to Cancer Cell Center cGMP Therapeutic Cell Production 13-116 View Details

Phase Description: N/A TAO Approved

2964309999 FREDC-New Townhouse Des/Const New 240 bed Townhouse Residence Hall 12-105 View Details

Phase Description: N/A TAO Approved

2967209999 HUCHPC-Rehab of Building 8 Rehab of Bldgs 8 & 15 13-19 View Details

Phase Description: N/A TAO Approved

3086009999 NEWPZC-LeFevre Hall Renovations to Lefevre Hall 13-92 View Details

Phase Description: N/A TAO Approved

3137209999 PURCHC-Bathrm Renov & Asbestos Bathroom Rehab Phase 2 14-51 View Details

Phase Description: N/A TAO Approved

3164709999 ONTAC-Grant Hall Rehab Restoration of Grant Hall 14-07 View Details

Phase Description: N/A TAO Approved

3167709999 LIDDSO-Construct 2-Bed Additn Two-bedroom addition to existing IRA 14-32 View Details

Phase Description: N/A TAO Approved

3198609999 BUFC-Tower 3 Asbestos Abate Tower 3 Phase IV, Asbestos Abatement 14-26 View Details

Phase Description: N/A TAO Approved

Page 19: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix D Code Compliance

Construction Permit Status

JDE Number Project Title / JDE Description Project Description Permit # Status

3160309999 CNDDSO-FS-BC 28 North Main St Hostel# 1353, 28 N. Main St Fire Safety Upgrades 14-99 View Details

Phase Description: N/A CP #14-99 Issued

3081609999 BRNXPC-Provide Utility Provide Utility Connections to Existing Bldgs. 5, 12 & 13 14-98 View Details

Phase Description: N/A CP #14-98 Issued

3200909999 BKDDSO-Remove Bilco Door Replace Basement Exterior Stairs 14-97 View Details

Phase Description: N/A CP #14-97 Issued

3193009999 BKDDSO-2013/14 CMM Hostel# 10273, 3024 Voorhies Ave Brooklyn, NY Roof Repair 14-95 View Details

Phase Description: N/A CP #14-95 Issued

3193009999 BKDDSO-2013/14 CMM H-2794 1364 Dean St. Bathroom Renovation 14-94 View Details

Phase Description: N/A CP #14-94 Expired

3191609999 FLDDSO-2013/14 CMM Hostel# 352, 4080 Circle Drive Williamson NY Roof Repair 14-93 View Details

Phase Description: N/A CP #14-93 Issued

3192309999 TADDSO-2013/14 CMM Standby Generators at Hostels# 10320, 10571, 10367, 1995 14-90 View Details

Phase Description: N/A CP #14-90 Expired

3192009999 BRDDSO-2013/14 CMM Replace Ductwork & Asbestos Abatement 14-88 View Details

Phase Description: N/A CP #14-88 Issued

3208609999 PILGPC-Generator B#102 Install Generator and Remove UG Storage Tank 14-87 View Details

Phase Description: N/A CP #14-87 Issued

3158009999 STUATC-Phase V Stutzman ATC Phase V 14-86 View Details

Phase Description: N/A CP #14-86 Issued

3158309999 VANATC-Phase V Phase 5 Renovations 14-85 View Details

Phase Description: N/A CP #14-85 Issued

3192209999 LEDDSO-2013/14 CMM Generator installations @ Hostel's 7089, 8623 & 1176 14-84 View Details

Phase Description: N/A CP #14-84 Issued

3192209999 LEDDSO-2013/14 CMM Generator Install @ Hostel's 2273, 7670, 1018, 121 & 2267 14-83 View Details

Phase Description: N/A CP #14-83 Issued

3190409999 BUFSU-Elevators Elevator Modernization & Asbestos Abatement 14-80 View Details

Phase Description: N/A CP #14-80 Issued

3174509999 BUFC-Tower One Renovation Tower 1 Building Renovations and Asbestos Abatement 14-76 View Details

Phase Description: N/A CP #14-76 Issued

3134809999 SIDDSO-Replace Fire Alarm Syst SIDDSO Executive Way Fire Alarm System Upgrade 14-75 View Details

Phase Description: N/A CP #14-75 Issued

3134709999 WEDDSO-FS-BC 6520 Donlen Drive Fire Safety Improvements at Donlen Dr. Ellicottville 14-74 View Details

Phase Description: N/A CP #14-74 Expired

3191609999 FLDDSO-2013/14 CMM Hostel #1222 108 Keyel Dr Rochester NY 14625, Roof Repair 14-72 View Details

Phase Description: N/A CP #14-72 Issued

3154009999 LIDDSO-FS-BC 26 East Moriches Fire Safety Upgrades 14-71 View Details

Phase Description: N/A CP #14-71 Issued

Page 20: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix D

3192009999 BRDDSO-2013/14 CMM Hostel 10707, Bathroom Renovations 14-70 View Details

Phase Description: N/A CP #14-70 Issued

3164709999 ONTAC-Grant Hall Rehab Restoration of Grant Hall 14-07 View Details

Phase Description: N/A TAO Approved

3146809999 SUDDSO-FS-HC 225 Bayley Rd Hostel 1958, 225 Bayley Rd Massena NY Fire Safety Upgrade 14-67 View Details

Phase Description: N/A CP #14-67 Issued

3157909999 FLDDSO-FS-BC 331 Whittier Rd Fire Safety Improvements at 331 Whittier Rd 14-66 View Details

Phase Description: N/A CP #14-66 Issued

3147409999 FLDDSO-FS-BC 1310 Crittenden Fire Safety Improvements 14-65 View Details

Phase Description: N/A CP #14-65 Issued

3141109999 FLDDSO-FS-BC 4080 Circle Dr Fire Safety Improvements @ 4080 Circle Drive 14-64 View Details

Phase Description: N/A CP #14-64 Issued

3141009999 FLDDSO-FS-BC 2380 Latta Rd Fire Safety Improvements at 2380 Latta Rd 14-63 View Details

Phase Description: N/A CP #14-63 Issued

3183809999 SIDDSO-Single Bed Dwelling Bldg 47D Renovation and Addition 14-62 View Details

Phase Description: N/A CP #14-62 Issued

2825409999 ROCKPC-Consolidate Support New Central Services Building 14-60 View Details

Phase Description: N/A CP #14-60 Issued

3186409999 BUFFPC-Repl Roof Sctns B 51 Roof Replace 14-59 View Details

Phase Description: N/A CP #14-59 Expired

3191709999 WEDDSO-2013/14 CMM Hostel# 10563 @ Bowen Road 14-58 View Details

Phase Description: N/A CP #14-58 Expired

3191709999 WEDDSO-2013/14 CMM Hostel #10228 - Remington - Kitchen 14-57 View Details

Phase Description: N/A CP #14-57 Expired

3191709999 WEDDSO-2013/14 CMM Hostel #301 - South Park - Kitchen Renovation 14-56 View Details

Phase Description: N/A CP #14-56 Expired

3191709999 WEDDSO-2013/14 CMM Hostel #7044 - Leydecker Rd - Kitchen-Bathroom 14-55 View Details

Phase Description: N/A CP #14-55 Expired

3191709999 WEDDSO-2013/14 CMM Hostel #424 -Coolidge - Bathroom Renovation 14-54 View Details

Phase Description: N/A CP #14-54 Expired

3158209999 NORATC-Phase V Phase V Renovations Exterior Facade Repairs 14-52 View Details

Phase Description: N/A CP #14-52 Issued

3197409999 BROCKC-Boiler Replacement Boiler Replacements at McLean, Harmon and Gordon Halls 14-50 View Details

Phase Description: N/A CP #14-50 Issued

2809809999 VCDOH-DOH/WC-Security System Campus Wide Security System 14-05 View Details

Phase Description: N/A CP #14-05 Issued

3134309999 SIDDSO-New Boiler Controls Burner & Boiler Controls Upgrade 14-49 View Details

Phase Description: N/A CP #14-49 Issued

3160909999 SAGCPC-Asbestos Abatement & Asbestos Abatement, minor HVAC duct and piping alterations 14-48 View Details

Phase Description: N/A CP #14-48 Expired

3191709999 WEDDSO-2013/14 CMM Hostel #10228 979 Remington Dr. North Tonawanda Roof Repairs 14-43 View Details

Phase Description: N/A CP #14-43 Expired

Page 21: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix D 3168609999 WEDDSO-FS-HC 8746 Highland Ave Fire Safety Improvements @ 8746 Highland Ave 14-42 View Details

Phase Description: N/A CP #14-42 Expired

3135309999 WEDDSO-FS-HC 19 Pearl Street Fire Safety Improvements 14-41 View Details

Phase Description: N/A CP #14-41 Expired

3191709999 WEDDSO-2013/14 CMM Hostel# 10144 Bathroom Renovations 14-39 View Details

Phase Description: N/A CP #14-39 Issued

3191709999 WEDDSO-2013/14 CMM Hostel# 9522, 5866 Route 39 Bathroom Renovations 14-38 View Details

Phase Description: N/A CP #14-38 Issued

3191709999 WEDDSO-2013/14 CMM Hostel #9776 @ 6228 Dale Rd, Demo & New Construction Plan 14-36 View Details

Phase Description: N/A CP #14-36 Issued

3191709999 WEDDSO-2013/14 CMM Hostel# 10436, 25 Haussauer Rd, Bathroom Renovs 14-35 View Details

Phase Description: N/A CP #14-35 Expired

3191709999 WEDDSO-2013/14 CMM Hostel #141 510 W. Main St.,Bathroom Renovs 14-34 View Details

Phase Description: N/A CP #14-34 Expired

3191709999 WEDDSO-2013/14 CMM Hostel#11463 - Bathroom Renovations 14-33 View Details

Phase Description: N/A CP #14-33 Expired

3167709999 LIDDSO-Construct 2-Bed Additn Two-bedroom addition to existing IRA 14-32 View Details

Phase Description: N/A TAO Approved

3031109999 CANTCT-Heritage & Rushton Exterior Rehab and Asbestos Abatement Mohawk Hall 14-31 View Details

Phase Description: N/A CP #14-31 Expired

3191609999 FLDDSO-2013/14 CMM Install Generator at 108 Cobblestone Tr. 14-30 View Details

Phase Description: N/A CP #14-30 Expired

3142609999 BUFFPC-Repl Dock Leveler B#62A Loading Dock Enclosure 14-29 View Details

Phase Description: N/A TAO Pending

3168709999 WEDDSO-FS-HC 39 Maple Avenue Fire Safety Improvements @ 39 Maple Ave 14-28 View Details

Phase Description: N/A CP #14-28 Expired

3191709999 WEDDSO-2013/14 CMM Hostel# 11252, 8197 Schreiner, Roof Repairs 14-25 View Details

Phase Description: N/A CP #14-25 Expired

3190509999 BUFSU-Laundry Facilities Wilkeson & Fargo Quads Laundry Renovation 14-23 View Details

Phase Description: N/A CP #14-23 Issued

3198309999 BUFC-Roof Replacement North Tower Roof Replacement & Assoc. Asbestos Abatement 14-22 View Details

Phase Description: N/A CP #14-22 Issued

3140409999 COBSAT-Fire Alarms Residence Halls Fire Alarm Replacement & Assoc. Abatement 14-21 View Details

Phase Description: Ten Eyck, Fake, Parsons, Davis and Dix Residence Halls TAO Expired

3191709999 WEDDSO-2013/14 CMM Hostel# 9818, 9523 Fuss Hill Rd Bathroom Renovations 14-02 View Details

Phase Description: N/A CP #14-02 Expired

3190609999 BUFSU-Clement Hall Roofs Roof Replacement & Asbestos Abate @ Clement Hall S. Campus 14-19 View Details

Phase Description: N/A CP #14-19 Issued

3143109999 NEWPZC-Card Access Card Access Upgrade 14-18 View Details

Phase Description: Bliss, Bouton, Capen, Gage & Scudder Halls Card Access CP #14-18A Issued Phase Description: Esopus, Lenape, Crispell, Bevier, Deyo, Dubois & College/Shango Halls Card CP Pending

3071109999 ONTAC-Flooring/Carpet Replace Hulbert & Huntington Halls Flooring Replacement 14-171 View Details

Phase Description: N/A CP #14-171 Issued

Page 22: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix D 3213909999 BUFSU-Laundry Rm Renov Phase 1 Governors Complex Laundry Room Repairs 14-170 View Details

Phase Description: N/A CP #14-170 Issued

3223609999 BUFC-Asbestos Removal 100% Phase V-Asbestos Abatement Floors 5-10 Stair B 14-169 View Details

Phase Description: N/A CP #14-169 Issued

3213809999 BUFSU-Laundry Rm Renov Phase 2 Laundry Facilities Renovations 14-168 View Details

Phase Description: N/A CP #14-168 Issued

3220909999 TADDSO-CMM 2014/15 Hostel# 10429-Central Air Conditioning Installation 14-167 View Details

Phase Description: N/A CP #14-167 Issued

2770309999 RPCI-Permit Only Projects Endoscopy Patient Holding Renovations 14-166 View Details

Phase Description: N/A CP #14-166 Issued

2770309999 RPCI-Permit Only Projects BLSC 23kV Switchgear Replacement 14-165 View Details

Phase Description: N/A CP #14-165 Issued

2770309999 RPCI-Permit Only Projects Specialty Pharmacy 14-164 View Details

Phase Description: N/A CP #14-164 Issued

3263409999 HVDDSO-Improvements Respite Home Improvements Projects 14-163 View Details

Phase Description: N/A CP #14-163 Issued

2770309999 RPCI-Permit Only Projects Endoscopy Renovations-Frozen Section 14-162 View Details

Phase Description: N/A CP #14-162 Issued

3205209999 BKDDSO-Repl Roofs and Asbestos Replace Roof and Asbestos Abatement 14-161 View Details

Phase Description: N/A CP #14-161 Issued

3189809999 BKDDSO-Repl Windws & Ext Doors Replace Windows and Doors 14-160 View Details

Phase Description: N/A CP #14-160 Issued

3216609999 BKDDSO-Repl Fire Stair H-716 Replace Fire Stair landing and Basement Stairs 14-159 View Details

Phase Description: N/A CP #14-159 Issued

3200809999 BKDDSO-Replace Exterior Window Replace Exterior Windows 14-158 View Details

Phase Description: N/A CP #14-158 Issued

3200609999 COBSAT-Roof Replacement Draper, Dix & Pearson Halls Re-Roofing & Asbestos Abatement 14-157 View Details

Phase Description: N/A CP #14-157 Issued

3193409999 LIDDSO-2013/14 CMM 102 DeBevoise Ave Kitchen,Dining and Hallway Rehab 14-156 View Details

Phase Description: N/A CP #14-156 Issued

3193409999 LIDDSO-2013/14 CMM 2 Marshmallow Drive New Flooring 14-155 View Details

Phase Description: N/A CP #14-155 Issued

3190009999 OSWGC-Compl Int Renov-Waterbur Waterbury Residence Hall Renovations 14-153 View Details

Phase Description: N/A CP #14-153 Issued

3196809999 BRDDSO-FS-BC 3 Jamie Ave FS-BC 14-152 View Details

Phase Description: N/A CP #14-152 Issued

3197009999 BRDDSO-FS-BC 3601 Scribner Dr FS-BC 14-151 View Details

Phase Description: N/A CP #14-151 Issued

3191909999 CDDDSO-2013/14 CMM Hostel 8953, 12 Fenway Circle, Kitchen Renov 14-150 View Details

Phase Description: N/A CP #14-150 Issued

3191909999 CDDDSO-2013/14 CMM Hostel 9734, 65 Worth Rd, Wilton NY, Kitchen Renovation 14-149 View Details

Phase Description: N/A CP #14-149 Issued

3191909999 CDDDSO-2013/14 CMM Hostel 10409 160 Butler Pond Rd, Bathroom Renov 14-143 View Details

Page 23: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix D Phase Description: N/A CP #14-143 Issued

3191909999 CDDDSO-2013/14 CMM Hosrel 984 2317 Broadway, Kitchen Renovations 14-142 View Details

Phase Description: N/A CP #14-142 Issued

3127009999 PLATC-Mason/Moffit Halls Rehab Rehabilitation and Asbestos Abatement of Moffitt Hall 14-141 View Details

Phase Description: N/A CP #14-141 Issued

3146909999 SUDDSO-FS-HC 227 Bayley Rd Fire Safety Upgrade 14-140 View Details

Phase Description: N/A CP #14-140 Issued

2770309999 RPCI-Permit Only Projects Endoscopy Renovations 14-14 View Details

Phase Description: N/A TAO Approved

3191709999 WEDDSO-2013/14 CMM Hostel# 11469 - Upstairs Bathroom 14-139 View Details

Phase Description: N/A CP #14-139 Issued

3191709999 WEDDSO-2013/14 CMM Hostel 7293 @ 10380 Peck Hill Rd Bathroom Renovations 14-138 View Details

Phase Description: N/A CP #14-138 Issued

3199209999 ALFDCT-Rehab of Public Spaces Entry and Building Renovations 14-137 View Details

Phase Description: N/A CP #14-137 Issued

3204209999 ALBSU-Stuyvesant Tower Renov Window Replacement, Exterior Repairs, Haz Mat Abatement 14-136 View Details

Phase Description: N/A CP #14-136 Issued

3151009999 ALBSU-Livingston Facade Repair Window Replacement, Exterior Repairs, Haz Mat Abatement 14-135 View Details

Phase Description: Facade Restoration CP #14-135A Issued Phase Description: Window Replacement CP #14-135B Issued

3155509999 GRILAB-Bldg 1 Chill Plant Chiller Plant Replacement 14-134 View Details

Phase Description: N/A CP #14-134 Issued

3221009999 BRDDSO-CMM 2014/15 Hosttel# 10137-Roof Repairs 14-133 View Details

Phase Description: N/A CP #14-133 Issued

3191409999 FLDDSO-AHU Sys Upgrade B#58 AHU System Upgrade 14-132 View Details

Phase Description: N/A CP #14-132 Issued

3252009999 BINGPC-Masonry Wall Repairs Maonry Wall Repair 14-131 View Details

Phase Description: N/A CP #14-131 Issued

3204609999 MEDDSO-Repl/Repair Front Porch Porch Replacement 14-130 View Details

Phase Description: N/A CP #14-130 Issued

3221009999 BRDDSO-CMM 2014/15 Hostel# 11667, Ramp Framing & Foundation-Basement Plan 14-129 View Details

Phase Description: general construction; electrical CP #14-129A Issued

3191909999 CDDDSO-2013/14 CMM Hostel# 22, 2415 Albany Street Stair Replacement 14-128 View Details

Phase Description: N/A CP #14-128 Issued

3157009999 LEDDSO-FS-BC 1 Skerry Court Fire Safety Upgrades at H# 10982, 7089, 10495, 10908, 9833 14-127 View Details

Phase Description: N/A CP #14-127 Issued

3191609999 FLDDSO-2013/14 CMM Hostel 11155 49 South Ave, Repalce Windows & Siding 14-126 View Details

Phase Description: N/A CP #14-126 Issued

3191609999 FLDDSO-2013/14 CMM Hostel # 2550, 5700 Martz Rd, Siding Replacement 14-125 View Details

Phase Description: N/A CP #14-125 Issued

3191609999 FLDDSO-2013/14 CMM Hostel # 2494, 338 Gibson St. Siding Replacement 14-124 View Details

Phase Description: N/A CP #14-124 Issued

3191609999 FLDDSO-2013/14 CMM Hostel # 2477, Peterman Rd, Siding & Window Replacement 14-123 View Details

Page 24: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix D Phase Description: N/A CP #14-123 Issued

3191609999 FLDDSO-2013/14 CMM Hostel #340 30 Pierce St., Webster, NY Replace Back Patio 14-122 View Details

Phase Description: N/A CP #14-122 Issued

3191609999 FLDDSO-2013/14 CMM Hostel #2178 44 Greenbriar Dr.,Gates, NY 14060 Replace Ramp 14-121 View Details

Phase Description: N/A CP #14-121 Issued

3191609999 FLDDSO-2013/14 CMM Hostel #638 1591 Wellington Ave, Savannah Replace Porch & Ra 14-120 View Details

Phase Description: N/A CP #14-120 Issued

3191609999 FLDDSO-2013/14 CMM Hostel #1220 671 Wyncoop Creek Rd., Chemung, Basement Entran 14-118 View Details

Phase Description: N/A CP #14-118 Issued

3191609999 FLDDSO-2013/14 CMM Hostel #140 60 Elizabeth St., Dansville, Fire Escape Repairs 14-117 View Details

Phase Description: N/A CP #14-117 Issued

3191609999 FLDDSO-2013/14 CMM Hostel #2494 338 Gibson St., Canadaigua, NY Bathroom Reno 14-116 View Details

Phase Description: N/A CP #14-116 Expired

3191609999 FLDDSO-2013/14 CMM Hostel #354 255 Cuyler St., Palmyra, Bathroom Reno 14-115 View Details

Phase Description: N/A CP #14-115 Issued

3191609999 FLDDSO-2013/14 CMM Hostel #11140 77 Firestone Dr., Rochester, Kitchen Reno 14-114 View Details

Phase Description: N/A CP #14-114 Issued

3191609999 FLDDSO-2013/14 CMM Hostel #10027 4519 St. Paul Blvd., Rochester, Kitchen Reno 14-113 View Details

Phase Description: N/A CP #14-113 Issued

3191609999 FLDDSO-2013/14 CMM Hostel #209 2747 Route 96, Waterloo, NY Bedroom-Office Renov 14-112 View Details

Phase Description: N/A CP #14-112 Issued

3134209999 WEDDSO-FS-BC 163 Hendricks Blv Fire Safety Improvements at Hendricks Blvd. Cheektowaga 14-111 View Details

Phase Description: N/A CP #14-111 Expired

3191709999 WEDDSO-2013/14 CMM Hostel 9992 - 3965 Mapleton Wheatfield, Bathroom Renovs 14-110 View Details

Phase Description: N/A CP #14-110 Issued

3167609999 IBR-Provide Combustible Storag Flammable Materials Storage 14-11 View Details

Phase Description: N/A CP #14-11 Issued

3191709999 WEDDSO-2013/14 CMM Hostel# 9140, 86 Seel St Bathroom Renovations 14-109 View Details

Phase Description: N/A CP #14-109 Issued

2940409999 FLDDSO-Rehab Entries/Walks B58 Vienna Bldg Rehab Entries-Walks & Asb Abatement 14-108 View Details

Phase Description: N/A CP #14-108 Issued

3204509999 SIDDSO-Demo Existing Duplex Demo of existing duplex property 14-107 View Details

Phase Description: N/A CP #14-107 Issued

2985009999 STBKSU-New Parking Garage Package B - Roundabout and Roadway Improvements 14-106 View Details

Phase Description: N/A CP #14-106 Issued

3158409999 CKPATC-Phase V Miscellaneous Rehab Phase V 14-105 View Details

Phase Description: N/A CP #14-105 Issued

3133709999 SUDDSO-New HVAC Cntrls CIT 1&2 Installation of a new DDC control system in CIT 1 and CIT 2. 14-104 View Details

Phase Description: N/A CP #14-104 Issued

3131909999 CDPC-Encapsulate Deteriorated Encapsulate Deteriorated Concrete Ideas 14-103 View Details

Phase Description: N/A CP #14-103 Issued

3171309999 ROCKPC-Demolition of Bldg 11 Demolition of Bldg 11 14-102 View Details

Page 25: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix D Phase Description: N/A CP #14-102 Issued

3236609999 ELMRPC-Crisis Residence C&Y Crisis Residence 14-101 View Details

Phase Description: Asbestos Abatement & Demo CP #14-101A Issued Phase Description: Asbestos Abatement and Ward Renovations, Bldgs 2 and 4. CP #14-101B Issued Phase Description: Fire Alarm Work Only CP #14-101C Issued

3160409999 CNDDSO-FS-BC 2 Regina St Hostel #8562, 2 Regina St Fire Safety Upgrade 14-100 View Details

Phase Description: N/A CP #14-100 Issued

3206909999 PLATC-Mason Hall Ren Const Adm SUNY Plattsburgh Mason Hall Rehab and Asbestos Abatement 14-10 View Details

Phase Description: N/A CP #14-10 Issued

3191709999 WEDDSO-2013/14 CMM Hostel# 447, 6187 Jefferson St., Bathroom Renovs 14-01 View Details

Phase Description: N/A CP #14-01 Expired

3183909999 CNDDSO-2013/14 CMM Hostel# 1353 roof Repairs, 28 North Madison Cortland NY 13-97 View Details

Phase Description: N/A CP #13-97 Expired

3100509999 SUDDSO-New NFPA 13 Sprklr Sys Bldg 2 Sprinkler System Feasibility Report 13-96 View Details

Phase Description: N/A CP #13-96 Expired

2530009999 BFDDSO-Repl Fac@Hillside Campu Replacement Facility at Hillside Campus 13-95 View Details

Phase Description: N/A CP #13-95 Issued

3086009999 NEWPZC-LeFevre Hall Renovations to Lefevre Hall 13-92 View Details

Phase Description: N/A TAO Approved

3047909999 NEWPZC-New 200 Bed Dorm New 223 Bed Residence Hall 13-90 View Details

Phase Description: N/A CP #13-90 Issued

2830209999 BRNXPC-New SRO Residence New 48 Bed Studio Res 13-09 View Details

Phase Description: N/A CP #13-09 Expired

3071009999 CNDDSO-Construct Fire Sprnklr Sprinkler Replacement @ 6165 Dewey Road 13-81 View Details

Phase Description: N/A CP #13-81 Issued

3071009999 CNDDSO-Construct Fire Sprnklr Sprinkler Replacement @ 6175 Dewey Road 13-80 View Details

Phase Description: N/A CP #13-80 Issued

2737409999 BRNXPC-Transitional Living Res New Transitional Living Residence 13-08 View Details

Phase Description: N/A CP #13-08 Expired

3071009999 CNDDSO-Construct Fire Sprnklr Sprinkler Replacement @ 6155 Dewey Road 13-78 View Details

Phase Description: N/A CP #13-78 Issued

3071009999 CNDDSO-Construct Fire Sprnklr Sprinkler Replacement @ 6145 Dewey Road 13-76 View Details

Phase Description: N/A CP #13-76 Issued

3131809999 CDDDSO-Exterior Facade Clean, Repoint & Waterproof the Exterior Facade Bldgs 1-12 13-74 View Details

Phase Description: N/A CP #13-74 Issued

2985009999 STBKSU-New Parking Garage Phase 1 - East Campus Parking 13-72 View Details

Phase Description: N/A TAO Pending

3173409999 BROCKC-Abate Flooring and Haz Materials Removal @ Perry, Briggs, & Bramley Halls 13-68 View Details

Phase Description: N/A CP #13-68 Expired

3143009999 NEWPZC-Roof Replacement Roof Replace with Asbestos Abate @ Bliss and Scudder Halls 13-63 View Details

Phase Description: N/A CP #13-63 Issued

3127709999 WEDDSO-2012/13 Minor Maint Hostel#1628, 8370 RT 38 South Dayton, NY Bathroom Renovs 13-06 View Details

Phase Description: N/A CP #13-06 Expired

Page 26: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix D 3071009999 CNDDSO-Construct Fire Sprnklr Sprinkler Replacement @ 105 Catherine Street 13-57 View Details

Phase Description: N/A CP #13-57 Expired

2770309999 RPCI-Permit Only Projects Clinical Science Center 13-54 View Details

Phase Description: N/A CP #13-54 Issued

3052709999 BRNXPC-Telecommunications Telecommunications Package 13-04 View Details

Phase Description: N/A CP #13-04 Issued

2740009999 SLAWPC-Replace 7 HVAC Units Rehab of existing mechanical HVAC equipment 13-36 View Details

Phase Description: N/A CP #13-36 Issued

3001709999 BRNXPC-BMS Package Building Management System 13-03 View Details

Phase Description: N/A CP #13-03 Issued

2770309999 RPCI-Permit Only Projects Existing Fire Exit Stair Modification 13-26 View Details

Phase Description: N/A CP #13-26 Expired

3039809999 HHHSP-Masonry Rehab Ph I & II Exterior Restoration Bldg 38 13-23 View Details

Phase Description: N/A CP #13-23 Issued

3126609999 BUFSU-Goodyear Hall Roof Repl Good year Hall Roof Replacemement and Asbestos Abatement 13-22 View Details

Phase Description: N/A CP #13-22 Expired

3191709999 WEDDSO-2013/14 CMM Hostel# 11242, 6566 Milestrip Rd Bathroom Renovs 13-121 View Details

Phase Description: N/A CP #13-121 Expired

3191709999 WEDDSO-2013/14 CMM Hostel# 11494, 4250 Loran Ave Hamburg, NY Bathroom Renovs 13-120 View Details

Phase Description: N/A CP #13-120 Expired

3134109999 WEDDSO-FS-BC 3 Victoria Blvd Fire Safety Improvements at 3 Victoria Cheektowaga 13-119 View Details

Phase Description: N/A CP #13-119 Expired

2821209999 BFDDSO-New Seven Bed IRA New 7 Bed IRA 13-118 View Details

Phase Description: N/A CP #13-118 Issued

3028809999 BFDDSO-Rehab to 153-10 79th St 8 Bed IRA Existing Home Renovations R4 Residence 13-117 View Details

Phase Description: N/A CP #13-117 Expired

2770309999 RPCI-Permit Only Projects Renov to Cancer Cell Center cGMP Therapeutic Cell Production 13-116 View Details

Phase Description: N/A TAO Approved

3191709999 WEDDSO-2013/14 CMM Hostel# 147, 1238 Olean Rd, Chaffee, NY Bathroom Renovs 13-113 View Details

Phase Description: N/A CP #13-113 Expired

3193409999 LIDDSO-2013/14 CMM H XXXX, 11 Sprague Dr. Ctr Morich Deck & Stair Replacement 13-110 View Details

Phase Description: N/A CP #13-110 Issued

3191609999 FLDDSO-2013/14 CMM Hostel# 11332, 2900 Penfield Rd Macedon Rd NY Roof Repairs 13-102 View Details

Phase Description: N/A CP #13-102 Expired

3191609999 FLDDSO-2013/14 CMM Hostel # 637 11894 W. Main St Wolcott NY 14590 Roof Repairs 13-100 View Details

Phase Description: N/A CP #13-100 Expired

2830009999 BRNXPC-Safe Horizon Haven Hse 44 Bed Crisis Building 13-10 View Details

Phase Description: N/A CP #13-10 Expired

3052609999 BRNXPC-Security Package BMHR Security Package 12-97 View Details

Phase Description: N/A CP #12-97 Issued

3062809999 ALBSU-Mohawk Tower Renovation Phase I - Hazardous Material 12-83 View Details

Phase Description: PH 1 Hazardous Materials Abatement & Demo TAO Expired Phase Description: Phase III - Interior Rehab TAO Expired Phase Description: Phase II - Windows, Exterior Repairs and Hazardous Abatement TAO Expired

Page 27: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix D

3066009999 SUDDSO-Sprinkler Initiative Replace Fire Sprinkler Systems 12-82 View Details

Phase Description: N/A CP #12-82 Expired

2737309999 BRNXPC-New Children's Bldg. Bronx MH Redevlopment Project Childrens Center 12-79 View Details

Phase Description: N/A CP #12-79 Issued

3096109999 NORATC-Install New Boilers Exterior Facade Repairs 12-77 View Details

Phase Description: N/A CP #12-77 Expired

3052809999 BRNXPC-Fire Alarm Fire Alarm Package Submission 12-76 View Details

Phase Description: N/A CP #12-76 Issued

3096109999 NORATC-Install New Boilers Replace 8 exterior doors 12-73 View Details

Phase Description: N/A CP #12-73 Expired

3047909999 NEWPZC-New 200 Bed Dorm Phase I - Sitework 12-60 View Details

Phase Description: N/A CP #12-60 Issued

3067809999 FLDDSO-Sprinklers at 13 Homes Replace Fire Sprinkler Systems Sites 25-37 12-42 View Details

Phase Description: N/A CP #12-42 Issued

2737509999 BRNXPC-New Adult Residence New Adult Building 12-21 View Details

Phase Description: N/A CP #12-21 Expired

3103109999 CDDDSO-Roof Repl Bldg 9 Roof Replacement and Asbestos Abatement 12-118 View Details

Phase Description: N/A CP #12-118 Issued

3127709999 WEDDSO-2012/13 Minor Maint Hostel #9639, 47 Gail Dr, Cattaraugus NY Bathroom Renovs 12-117 View Details

Phase Description: N/A CP #12-117 Expired

3127709999 WEDDSO-2012/13 Minor Maint Hostel# 10430, 125 Cheshire Lane Amherst NY Bathroom Renovs 12-114 View Details

Phase Description: N/A CP #12-114 Expired

3127709999 WEDDSO-2012/13 Minor Maint Hostel# 398, 90 Lemans Cheektowaga, NY Kitchen Renovs 12-113 View Details

Phase Description: N/A CP #12-113 Expired

3127709999 WEDDSO-2012/13 Minor Maint Hostel# 9818, 9523 Fuss Hill Rd Little Valley NY Roof Replac 12-112 View Details

Phase Description: N/A CP #12-112 Expired

3126409999 FLDDSO-B-66 Replace Chiller Chiller Replacement at Tymeson Hall 12-106 View Details

Phase Description: N/A CP #12-106 Expired

3013309999 OASAS-Odyssey House Bldg 13 Rehab of an existing 50,000 sq ft. treatment facility. 12-103 View Details

Phase Description: N/A CP #12-103 Issued

2958709999 VADDSO-Replace Sprinklers Fire Protection & Fire Alarm, Upgrade at South Bristol IRA 11-08 View Details

Phase Description: N/A CP #11-08 Issued

2958709999 VADDSO-Replace Sprinklers Sprinkler System Community Residence ICF 35 South State St 11-44 View Details

Phase Description: N/A CP #11-44 Expired

2958709999 VADDSO-Replace Sprinklers Replace existing sprinkler systems 11-43 View Details

Phase Description: N/A CP #11-43 Issued

2770309999 RPCI-Permit Only Projects GCDC Air Handling Unit Replacement 11-40 View Details

Phase Description: N/A CP #11-40 Expired

2958709999 VADDSO-Replace Sprinklers H#1291 4846 Stoner Hill Rd Dansville- H#1753 344 S. M. Perry 11-129 View Details

Phase Description: N/A CP #11-129 Expired

2958709999 VADDSO-Replace Sprinklers Replace Sprinkler System in Hostel #1200 & #1386 11-128 View Details

Phase Description: N/A CP #11-128 Expired

Page 28: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix D 2982609999 BRNXPC-Elevator Package Campus Elevator Project 10-116 View Details

Phase Description: N/A CP #10-116 Issued

2919809999 BROCKC-Maintenance & Repairs Dorm Maintenance & Repair High Rise Phase 2 10-101 View Details

Phase Description: N/A CP #10-101 Expired

Page 29: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix E

Fire Safety Inspection Form 12/10 Page 1

FIRE SAFETY INSPECTION FORM

Fire Code of New York State Date: 12/23/14 Inspected By: John Adams NYS-CEO #: 0994-7271B

Campus/Facility: Dormitory Authority - State of New York Client: N/A

(Address) 515 Broadway, Albany, NY 12207

Building Name(s): DASNY Headquarters Building Numbers: 515

Code Enforcement Jurisdiction: DASNY Other:

Occupancy Classification(s):B Construction Classification: II-A

Comments: Inspection conducted on 12-19-14

No Topic Fire Code Section

In Compliance

Needs Correction

Not Applicable Comment

1 GENERAL: Various Evacuation Drills

conducted 405.1

Evacuation Drill Reports 405.5 Emergency Evacuation

Plan 404.3

Employee Training Program

406.3

Hazard Communication (MSDS available)

407.2

Fire alarm testing reports 901.6 Sprinkler System

inspection/testing reports 901.6

Fire Pump Inspection/test reports

901.6

Fire Extinguisher inspection records

901.6

Special Suppression System inspection records (Kitchen, clean agent, etc)

901.6

Elevator inspection Records

PM 606.1.1

Emergency Power/Lighting inspection reports

604.4

2 EGRESS Chapter 10

Two means of egress 1015.1

Exit width (44”) 1017.2 .

No Obstructions/Storage 1003.6

Exits not block by furnishing or decorations

1011.4

Exits and Exit Discharge properly Illuminated

1028.8

Emergency Lighting 1012.9

Walking surface secure and slip free

PM-305.4

Page 30: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

No Topic Code Section

In Compliance

Needs Correction

Not Applicable Comment

Fire Safety Inspection Form 12/10 Page 2

Exit signage 1011

Exit signs illuminated 1011.2

Door swing in direction of egress

1008.1.2

No dead bolts or Locks 1008.1.8.3

Doors operate properly (self closing & latch)

1008

No Door Wedges

Hold-open devices maintained

703.2.2

Interior Stairway maintained

PM 305.4

Handrails/Guards PM 305.5 Exterior Exit discharge

clear/maintained PM 302.3

Exterior Stairway maintained

PM 302.5

3 FIRE PROTECTION SYSTEMS:

Chapter 9 FM 200 system inspection OK.

Fire Alarm System 907 Indicate Type of System: Addressable Zoned

Operable (No Troubles) 901.6

Pull stations 907.4

Smoke detection 907

Carbon Monoxide Alarms 610.3

Sounding devices 907

Visual appliances 907

Annual Inspection/Tests Performed

907.20

Sprinkler System 903 Indicate Type of Sprinkler System NFPA 13 NFPA 13R NFPA 13D

Sprinkler Valves

supervised or locked in open position

903.4.3

Sprinkler Obstructions (storage 18”)

315.2.1

FDC Obstructions/capped 901.8

Sprinkler Annual Inspection/Testing performed

903.5 Dry Valve not tested (per documentation)

Sprinkler system monitored by Fire Alarm system

903.4

Kitchen Hood suppression system

904.11

Kitchen extinguisher type K for hood system

906.4

Hood Suppression Annual inspection/tests performed

904.11

Standpipe System 905

Occupant Hoses Stations 905.5

Fire Hydrants operational 508.5

Hydrants obstructed 508.5.4

Page 31: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

No Topic Code Section

In Compliance

Needs Correction

Not Applicable Comment

Fire Safety Inspection Form 12/10 Page 3

Fire Extinguishers 906

Proper type 906.3

Proper location/visible 906.5

Hung-up or in cabinet 906.7

Properly tagged/inspected 906.2

Properly sealed 906.2

4 FIRE DOORS: Chapter 7/ NFPA 80

No holes or breaks exist in surfaces of door or frame

NFPA 80

The door, frame, hinges, hardware, are in working order

NFPA 80

Door clearances are compliant

NFPA 80

No parts are missing or broken

NFPA 80

Self-closing devices are operational

NFPA 80

Coordinator operational NFPA 80

Latching hardware secures doors properly

NFPA 80

No field modifications NFPA 80

Smoke door gaskets installed with no voids

NFPA 80

5 ELECTRICAL: Chapter 6

Electrical devices not damaged & free from shock hazard

605.1

Extension Cord not used for permanent wiring

605.5

Extension Cord used properly (no splices or multiple cords)

605.5.3

Extension Cords not properly grounded

605.5.4

No open junction boxes or open wiring splices

605.6

Minimum two receptacles per habitable space

PM 605.2

GFCI Receptacles in Bathrooms

PM 605.2

Electrical Panel Covers in place

605.1

Electrical Panel working clearance (36”)

605.3

Not accessible to Children PM303.15

No Storage in Electrical Rooms

315.2

6 PLUMBING: PM

Chapter 5

Page 32: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

No Topic Code Section

In Compliance

Needs Correction

Not Applicable Comment

Fire Safety Inspection Form 12/10 Page 4

Fixtures properly installed and maintained

PM 504.1

Potable water provided PM 505.2 Hot water provided PM 505.4 Drinking Fountain

provided PM 502.4.1

No Sewer fumes 504.3

7 MECHANICAL/HEATING/COOLING:

PM Chapter 6

Minimum bldg temperature 68 degrees

PM 602.3

Mechanical equipment operational (Boiler/Furnace)

PM 603.1

Chimney/Vent operating properly

PM 603.2

Proper Clearances maintained

PM 603.3

Safety controls maintained PM 603.4 Combustion Air provided PM 603.5 No gas/oil fumes FG 304.2 Equipment rooms not

accessible to Children PM303.15

Fire/smoke dampers maintained

PM 607.1

Air Conditioning Equipment maintained

PM 601.2

Laundry Dry exhaust vent PM 403.5

8 HAZARDOUS MATERIALS:

Chapters 27 - 44

Not accessible to Children PM303.15

Proper Storage (cabinets or designated rooms)

2703.1

Storage within allowable quantities

3405.3.5.2

Gas Cylinders stored properly (upright/secured/capped)

3004.1

9 STORAGE/WASTE: Chapter 3 Not accessible to Children PM303.15

Combustible storage orderly

315.2

Unnecessary storage removed

2nd Floor Southeast Offices (2 cubes): Filled with drawings to capacity.

Combustibles not storage near ignition sources

315.2

Ceiling Clearances (18” sprinklers)

315.2.1

No fueled equipment (lawn care or snow removal) stored in bldg.

313.1

Page 33: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

No Topic Code Section

In Compliance

Needs Correction

Not Applicable Comment

Fire Safety Inspection Form 12/10 Page 5

10 EXTERIOR: Various Fire Lanes maintained

clear 503.4

Fire Hydrants maintained 508.5 Exterior vegetation

properly maintained 304.1.2

Exterior waste materials properly containerized

304.3

Sidewalks in good condition

PM 302.3

Exterior Stairway, handrails and guards maintained

PM 304.10

All exterior exit discharge areas are not obstructed by snow, storage, etc.

PM 302.3

11 SIGNAGE: Various

Occupant Load Posted 1028.4 Elevator signage provided

(use stair in fire emergency)

607.2

No Smoking Signs provided

310.3

Fire Extinguisher location signs

906.5

Hazardous Materials spaces identified

2703.5

ADDITIONAL COMMENTS: 1. Archive Room on 1st Floor – N/East Exit: Keep exit clear of debris (shelf parts etc.) that could fall and

become and obstruction during emergency egress.

Page 34: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

No Topic Code Section

In Compliance

Needs Correction

Not Applicable Comment

Fire Safety Inspection Form 12/10 Page 6

2. Stairwell Fire Rated doors were reviewed for compliance with NFPA 80 as it pertains to Property

Maintenance: 1.) 4th Floor East Stair door top gap >3/16” maximum allowed for steel doors by NFPA 80. 2.) 1st Floor door by 1st Floor store: Gaps exceed maximum 1/8” allowed by NFPA 80.

NYS Fire Code, Section 703.2 Opening protectives. Opening protectives shall be maintained in an operative condition in accordance with NFPA 80. Fire doors and smoke barrier doors shall not be blocked or obstructed or otherwise made inoperable. Fusible links shall be replaced promptly whenever fused or damaged. Fire door assemblies shall not be modified. NYS Fire Code, Section 6.3.1.7* Clearances. 6.3.1.7.1 The clearances between the top and vertical edges of the door and the frame, and the meeting edges of doors swinging in pairs, shall be 1⁄8 in. ± 1⁄16 in. (3.18 mm ± 1.59 mm) for steel doors and shall not exceed 1⁄8 in. (3.18 mm) for wood doors. 6.3.1.7.2 Clearances shall be measured from the pull face of the door(s).

3. Provide up to date test reports for dry sprinkler system. Reports provided did not indicate required annual “trip test” per NFPA 25.

Page 35: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix F

FIRE SAFETY INSPECTION FORM

Fire Code of New York State

Fire Safety Inspection Form 12/10 Page 1

Date: 12/18/14 Inspected By: John Adams NYS-CEO #: 0994-7271B

Campus/Facility: DASNY Client: DASNY

(Address) Buffalo Office @ 539 Franklin Steet

Building Name(s): DASNY Buffalo Headquarters Building Numbers: 539

Code Enforcement Jurisdiction: DASNY Other:

Occupancy Classification(s):B Construction Classification: Type IV

Comments: Date of test was December 16th, 2014

No Topic Fire Code Section

In Compliance

Needs Correction

Not Applicable Comment

1 GENERAL: Various Evacuation Drills

conducted 405.1

Evacuation Drill Reports 405.5 Emergency Evacuation

Plan 404.3

Employee Training Program

406.3

Hazard Communication (MSDS available)

407.2

Fire alarm testing reports 901.6 Battery operated CO/SD Units. Batteries replaced semi-annualy

Sprinkler System inspection/testing reports

901.6

Fire Pump Inspection/test reports

901.6

Fire Extinguisher inspection records

901.6 Two outdated extinguishers. (1. Kitchen, 2. 2nd Floor center)

Special Suppression System inspection records (Kitchen, clean agent, etc)

901.6

Elevator inspection Records

PM 606.1.1

Emergency Power/Lighting inspection reports

604.4

2 EGRESS Chapter 10

Two means of egress 1015.1

Exit width (44”) 1017.2 See “Additional Comments”

No Obstructions/Storage 1003.6

Exits not block by furnishing or decorations

1011.4

Exits and Exit Discharge properly Illuminated

1028.8

Page 36: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

No Topic Code Section

In Compliance

Needs Correction

Not Applicable Comment

Fire Safety Inspection Form 12/10 Page 2

Emergency Lighting 1012.9

Walking surface secure and slip free

PM-305.4

Exit signage 1011

Exit signs illuminated 1011.2

Door swing in direction of egress

1008.1.2

No dead bolts or Locks 1008.1.8.3

Doors operate properly (self closing & latch)

1008

No Door Wedges

Hold-open devices maintained

703.2.2

Interior Stairway maintained

PM 305.4

Handrails/Guards PM 305.5 Exterior Exit discharge

clear/maintained PM 302.3

Exterior Stairway maintained

PM 302.5

3 FIRE PROTECTION SYSTEMS:

Chapter 9

Fire Alarm System 907 Indicate Type of System: Addressable Zoned

Operable (No Troubles) 901.6 N/A

Pull stations 907.4 N/A

Smoke detection 907 Battery Operated

Carbon Monoxide Alarms 610.3 Battery Operated

Sounding devices 907 N/A

Visual appliances 907 N/A

Annual Inspection/Tests Performed

907.20 N/A

Sprinkler System 903 Indicate Type of Sprinkler System NFPA 13 NFPA 13R NFPA 13D

Sprinkler Valves

supervised or locked in open position

903.4.3

Sprinkler Obstructions (storage 18”)

315.2.1

FDC Obstructions/capped 901.8

Sprinkler Annual Inspection/Testing performed

903.5

Sprinkler system monitored by Fire Alarm system

903.4

Kitchen Hood suppression system

904.11

Kitchen extinguisher type K for hood system

906.4

Hood Suppression Annual inspection/tests performed

904.11

Page 37: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

No Topic Code Section

In Compliance

Needs Correction

Not Applicable Comment

Fire Safety Inspection Form 12/10 Page 3

Standpipe System 905

Occupant Hoses Stations 905.5

Fire Hydrants operational 508.5

Hydrants obstructed 508.5.4

Fire Extinguishers 906 See “Additional Comments”

Proper type 906.3

Proper location/visible 906.5

Hung-up or in cabinet 906.7 Hung on wall

Properly tagged/inspected 906.2 See “Additional Comments”

Properly sealed 906.2

4 ELECTRICAL: Chapter 6

Electrical devices not damaged & free from shock hazard

605.1

Extension Cord not used for permanent wiring

605.5

Extension Cord used properly (no splices or multiple cords)

605.5.3

Extension Cords not properly grounded

605.5.4

No open junction boxes or open wiring splices

605.6

Minimum two receptacles per habitable space

PM 605.2

GFCI Receptacles in Bathrooms

PM 605.2

Electrical Panel Covers in place

605.1

Electrical Panel working clearance (36”)

605.3

Not accessible to Children PM303.15

No Storage in Electrical Rooms

315.2

5 PLUMBING: PM

Chapter 5

Fixtures properly installed and maintained

PM 504.1

Potable water provided PM 505.2 Hot water provided PM 505.4 Drinking Fountain

provided PM 502.4.1

No Sewer fumes 504.3

6 MECHANICAL/HEATING/COOLING:

PM Chapter 6

Minimum bldg temperature 68 degrees

PM 602.3

Mechanical equipment operational (Boiler/Furnace)

PM 603.1

Chimney/Vent operating PM 603.2

Page 38: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

No Topic Code Section

In Compliance

Needs Correction

Not Applicable Comment

Fire Safety Inspection Form 12/10 Page 4

properly Proper Clearances

maintained PM 603.3

Safety controls maintained PM 603.4 Combustion Air provided PM 603.5 No gas/oil fumes FG 304.2 Equipment rooms not

accessible to Children PM303.15

Fire/smoke dampers maintained

PM 607.1

Air Conditioning Equipment maintained

PM 601.2

Laundry Dry exhaust vent PM 403.5

7 HAZARDOUS MATERIALS:

Chapters 27 - 44

Not accessible to Children PM303.15

Proper Storage (cabinets or designated rooms)

2703.1

Storage within allowable quantities

3405.3.5.2

Gas Cylinders stored properly (upright/secured/capped)

3004.1

8 STORAGE/WASTE: Chapter 3 Not accessible to Children PM303.15

Combustible storage orderly

315.2

Unnecessary storage removed

Combustibles not storage near ignition sources

315.2

Ceiling Clearances maintained (18” sprinklers)

315.2.1

No fueled equipment (lawn care or snow removal) stored in bldg.

313.1

9 EXTERIOR: Various Fire Lanes maintained

clear 503.4

Fire Hydrants maintained 508.5 Exterior vegetation

properly maintained 304.1.2

Exterior waste materials properly containerized

304.3

Sidewalks in good condition

PM 302.3 Weather cloudy and cool during inspection.

Exterior Stairway, handrails and guards maintained

PM 304.10

All exterior exit discharge PM 302.3

Page 39: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

No Topic Code Section

In Compliance

Needs Correction

Not Applicable Comment

Fire Safety Inspection Form 12/10 Page 5

areas are not obstructed by snow, storage, etc.

10 SIGNAGE: Various

Occupant Load Posted 1028.4 Elevator signage provided

(use stair in fire emergency)

607.2

No Smoking Signs provided

310.3

Fire Extinguisher location signs

906.5

Hazardous Materials spaces identified

2703.5

ADDITIONAL COMMENTS:

1.) 2nd Floor by Transient Office: clear space between copy machine and office wall. 36” clear space required on 2nd level with <50 occupants.

The Following are additional “Property Maintenance Issues” to be addressed by Building Management. (Please Note: Comments below do not depict all issues on the exterior as it would be suggested to have a Condition Assessment done of the Property by an A/E to provide an official report of Capital Improvements for the Property)

1.) Exterior: Shingles blowing off of roof. Building Management indicated that a roof replacement was out to bid.

Page 40: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

No Topic Code Section

In Compliance

Needs Correction

Not Applicable Comment

Fire Safety Inspection Form 12/10 Page 6

2.) Exterior: Clean wood and debris noted around A/C Condensing unit and window..

3.) Exterior: Clean leaves/debris and re-caulk where piping and electric conduit enters the building to keep moisture and rodents out.

4.) Exterior: Caulk gaps at window and block.

Page 41: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

No Topic Code Section

In Compliance

Needs Correction

Not Applicable Comment

Fire Safety Inspection Form 12/10 Page 7

5.) Exterior by Gas Line: Properly locate gutter to splash block to help keep moisture away from the building. It appears that the gutter is in the ground.

Page 42: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

Appendix G

Fire Safety Inspection Form 12/10 Page 1

FIRE SAFETY INSPECTION FORM Fire Code of New York State

Date: 12/30/2014 Inspected By: John Adams NYS-CEO #: 0994-7271B

Campus/Facility: DASNY Delmar Properly/Office Client: DASNY

(Address) 161 Delaware Avenue, Delmar NY

Building Name(s): NYS Justice Center Building Numbers: 161

Code Enforcement Jurisdiction: DASNY Other:

Occupancy Classification(s):B Construction Classification: IIB

Comments:

No Topic Fire Code Section

In Compliance

Needs Correction

Not Applicable Comment

1 GENERAL: Various Evacuation Drills

conducted 405.1

Evacuation Drill Reports 405.5 Emergency Evacuation

Plan 404.3 Currently in Progress/design

Employee Training Program

406.3

Hazard Communication (MSDS available)

407.2

Fire alarm testing reports 901.6 Tested prior to occupancy 2013 Sprinkler System

inspection/testing reports 901.6 Tested by Professional Fire Protection on 10/14/14

(tested quarterly)

Fire Pump Inspection/test reports

901.6

Fire Extinguisher inspection records

901.6 2nd Floor Server 208 (Fire extinguisher not inspected monthly)

Special Suppression System inspection records (Kitchen, clean agent, etc)

901.6

Elevator inspection Records

PM 606.1.1 Monthly

Emergency Power/Lighting inspection reports

604.4 New Generator installed on 12/6/13 / Light Packs in various locations (Montly Testing on file/Annual test done by Allstate Power)

2 EGRESS Chapter 10

Two means of egress 1015.1

Exit width (44”) 1017.2

No Obstructions/Storage 1003.6

Exits not block by furnishing or decorations

1011.4

Exits and Exit Discharge properly Illuminated

1028.8

Emergency Lighting 1012.9

Walking surface secure and slip free

PM-305.4

Page 43: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

No Topic Code Section

In Compliance

Needs Correction

Not Applicable Comment

Fire Safety Inspection Form 12/10 Page 2

Exit signage 1011

Exit signs illuminated 1011.2

Door swing in direction of egress

1008.1.2

No dead bolts or Locks 1008.1.8.3

Doors operate properly (self closing & latch)

1008

No Door Wedges

Hold-open devices maintained

703.2.2

Interior Stairway maintained

PM 305.4

Handrails/Guards PM 305.5 Exterior Exit discharge

clear/maintained PM 302.3

Exterior Stairway maintained

PM 302.5

3 FIRE PROTECTION SYSTEMS:

Chapter 9

Fire Alarm System 907 Indicate Type of System: Addressable Zoned

Operable (No Troubles) 901.6

Pull stations 907.4

Smoke detection 907

Carbon Monoxide Alarms 610.3

Sounding devices 907

Visual appliances 907

Annual Inspection/Tests Performed

907.20 Tested on 5-7-14 by Fire Security and Sound Systems

Sprinkler System 903 Indicate Type of Sprinkler System NFPA 13 NFPA 13R NFPA 13D

See Comments Sprinkler Valves

supervised or locked in open position

903.4.3 See Comments.

Sprinkler Obstructions (storage 18”)

315.2.1

FDC Obstructions/capped 901.8

Sprinkler Annual Inspection/Testing performed

903.5

Sprinkler system monitored by Fire Alarm system

903.4

Kitchen Hood suppression system

904.11

Kitchen extinguisher type K for hood system

906.4

Hood Suppression Annual inspection/tests performed

904.11

Standpipe System 905

Occupant Hoses Stations 905.5

Fire Hydrants operational 508.5

Page 44: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

No Topic Code Section

In Compliance

Needs Correction

Not Applicable Comment

Fire Safety Inspection Form 12/10 Page 3

Hydrants obstructed 508.5.4

Fire Extinguishers 906

Proper type 906.3

Proper location/visible 906.5

Hung-up or in cabinet 906.7

Properly tagged/inspected 906.2

Properly sealed 906.2

4 FIRE DOORS: Chapter 7/ NFPA 80

No holes or breaks exist in surfaces of door or frame

NFPA 80

The door, frame, hinges, hardware, are in working order

NFPA 80

Door clearances are compliant

NFPA 80

No parts are missing or broken

NFPA 80

Self-closing devices are operational

NFPA 80

Coordinator operational NFPA 80

Latching hardware secures doors properly

NFPA 80

No field modifications NFPA 80

Smoke door gaskets installed with no voids

NFPA 80

5 ELECTRICAL: Chapter 6

Electrical devices not damaged & free from shock hazard

605.1

Extension Cord not used for permanent wiring

605.5

Extension Cord used properly (no splices or multiple cords)

605.5.3

Extension Cords not properly grounded

605.5.4

No open junction boxes or open wiring splices

605.6

Minimum two receptacles per habitable space

PM 605.2

GFCI Receptacles in Bathrooms

PM 605.2

Electrical Panel Covers in place

605.1

Electrical Panel working clearance (36”)

605.3 See Comments

Not accessible to Children PM303.15

No Storage in Electrical Rooms

315.2 See Comments

Page 45: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

No Topic Code Section

In Compliance

Needs Correction

Not Applicable Comment

Fire Safety Inspection Form 12/10 Page 4

6 PLUMBING: PM Chapter 5

Fixtures properly installed and maintained

PM 504.1

Potable water provided PM 505.2 Hot water provided PM 505.4 Drinking Fountain

provided PM 502.4.1

No Sewer fumes 504.3

7 MECHANICAL/HEATING/COOLING:

PM Chapter 6

Minimum bldg temperature 68 degrees

PM 602.3

Mechanical equipment operational (Boiler/Furnace)

PM 603.1 Inspection due 1/1/15

Chimney/Vent operating properly

PM 603.2

Proper Clearances maintained

PM 603.3

Safety controls maintained PM 603.4 Combustion Air provided PM 603.5 No gas/oil fumes FG 304.2 Equipment rooms not

accessible to Children PM303.15

Fire/smoke dampers maintained

PM 607.1

Air Conditioning Equipment maintained

PM 601.2

Laundry Dry exhaust vent PM 403.5

8 HAZARDOUS MATERIALS:

Chapters 27 - 44

Not accessible to Children PM303.15

Proper Storage (cabinets or designated rooms)

2703.1

Storage within allowable quantities

3405.3.5.2

Gas Cylinders stored properly (upright/secured/capped)

3004.1

9 STORAGE/WASTE: Chapter 3 Not accessible to Children PM303.15

Combustible storage orderly

315.2

Unnecessary storage removed

Combustibles not storage near ignition sources

315.2

Ceiling Clearances (18” sprinklers)

315.2.1

No fueled equipment (lawn care or snow

313.1

Page 46: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

No Topic Code Section

In Compliance

Needs Correction

Not Applicable Comment

Fire Safety Inspection Form 12/10 Page 5

removal) stored in bldg.

10 EXTERIOR: Various Fire Lanes maintained

clear 503.4

Fire Hydrants maintained 508.5 Exterior vegetation

properly maintained 304.1.2

Exterior waste materials properly containerized

304.3

Sidewalks in good condition

PM 302.3

Exterior Stairway, handrails and guards maintained

PM 304.10

All exterior exit discharge areas are not obstructed by snow, storage, etc.

PM 302.3

11 SIGNAGE: Various

Occupant Load Posted 1028.4 See Comments Elevator signage provided

(use stair in fire emergency)

607.2

No Smoking Signs provided

310.3

Fire Extinguisher location signs

906.5

Hazardous Materials spaces identified

2703.5

ADDITIONAL COMMENTS: 1.) Fire Evacuation Drill Repots shall include the following as required by the Fire Code of NYS. Building Manager (Barry Jones) to provide forms used at 515 Broadway to be used at 161 Delaware Avenue for required fire drills. A. Staff members on duty and participating. (Note, Building Management has this information, but it is not included on the actual form filed) B. Number of occupants evacuated. 2.) Rear Stair / Storage Room / Old Server/AC Room: Provide sprinkler coverage as required by NFPA 13 Sprinkler Code. (Noted 2013 as well. This must be completed asap.)

Page 47: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

No Topic Code Section

In Compliance

Needs Correction

Not Applicable Comment

Fire Safety Inspection Form 12/10 Page 6

3.) 1st Floor Admin - Electric Panel L1: Relocate table that is that has been placed in front of the electric panel to allow for required 36" clear space as required by the National Electrical Code. 4.) Sprinkler Valve Room 117A: Valve leaking at time of inspection. Contact Professional Fire Protection Inc. to repair.

Page 48: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

No Topic Code Section

In Compliance

Needs Correction

Not Applicable Comment

Fire Safety Inspection Form 12/10 Page 7

5.) 1st Floor Conference Room (Video 122) / Training Room 116: Complete installation of Maximum Occupancy Signs within assembly space as required. NOTE: Signs installed without number designation.

6.) Storage 123: Locate storage away from front of electric panel to provide a minimum 36” clear working space as required by the National Electric Code.

Page 49: CODE PERMITTING PROGRAM · 3118009999 MEDDSO-Bathroom Redesign Bathroom Redesign 14-69 View Details Phase Description: N/A CCC Approved 3126909999 CNDDSO-FS-BC: 101 Rolland Terr GAP

No Topic Code Section

In Compliance

Needs Correction

Not Applicable Comment

Fire Safety Inspection Form 12/10 Page 8

7. Storage 131/JC Closet: Restore ceiling and install cover on above ceiling electrical panel

8.) Main Computer Room: Provide sprinkler coverage as required for this room. The “Ansul System” was removed during construction. A sprinkler system should’ve been provided to comply with the requirements of NFPA 13.


Recommended