Commissioning ground coupled heat pumpoffice building Bayer Diegem
VCB – Hernieuwbare energie voor gebouwen, 2012-09-13 ir. Pedro Pattijn
Agenda
1. Bayer office building project
2. Evaluation� Energyconsumption
� Heat pumps
� Free-cooling
� Bore hole system
� Comfort
3. Primary energysaving & CO2-reduction
4. Conclusions & Proposals
Agenda
1. Bayer office building project
2. Evaluation� Energyconsumption
� Heat pumps
� Free-cooling
� Bore hole system
� Comfort
3. Primary energysaving & CO2-reduction
4. Conclusions & Proposals
Building
Demo-project innovative energytechnologies – VEA
Green Building – European Commission
Belgian Energy Award non-residential buildings 2009
Architect : Reginald SchellenBuilding type: Office buildingDesign : 2007Construction: 2008 – 2009In use : feb 2009Net floor area (NFA): 11.249 m²Conditioned floor area: 7.050 m²
Building
Building
Installation
Geothermal system: borehole heat exchanger(60 probes, length 100m)used for heating and cooling purposes
Backup heating system: gas condensation boilerBackup cooling system: compression chillerDistribution system: TABS, floor ventiloconvectors, ventilationOther systems: Earth-air heat exchanger (EAHX)
(12 tubes, diam. 315 mm, length 55 m)thermal heat recovery wheel
System
System
Source : Geotabs Tetra project
Scheme
Source : Geotabs Tetra project
Metering
Borehole heat exchanger
• 60 bore holes (5 x 12, rectangular)• 100m depth• 4m distance• 50 m³/h
Heat Pump
• HP3 : Lennox HWW 055CS,51 kWth,16 kWel, (COP=3,2)
• Ground : in 6°C out 3°C• Condensor : in 40°C / out 45°C
• HP1&HP2 : Lennox HWW 070CS,70 kWth, 16 kWel, (COP=4,5)
• Ground : in 6°C / out 3°C• Condensor : in 23°C / out 28°C
• Plate heat exchanger free cooling, 170 kW
• Boiler: Viessmann Vitocrossal 300 CT3, 2x383 kW, regime 70/50°C, eff. 109%
• Chiller : Lennox NAC 420D NM1M, 430 kWth, (EER 3,11), R410A,• chilled water 12/7°C• outside air temperature 35°C
Backup
Standard
Agenda
1. Bayer office building project
2. Evaluation / Commissioning� Energyconsumption
� Heat pumps
� Free-cooling
� Bore hole system
� Comfort
3. Primary energysaving & CO2-reduction
4. Conclusions & Proposals
Senter Novem 2007Energy Consumption
BenchmarksIngenium
500 – 10.000m² officesAir conditioned - standard
offices average offices
Specific Gas consumption (kWh/m².year)
70 151 178 100
Specific Electrical consumption (kWh/m².year)
120 85 226 60
Bayer
Year Consumption
Considerations :
� No submetering (gas, heat, cold, electrical)
� High comfort requirements summer & winter
� High occupancy rate
<>
Gas consumption
Considerations : • Considerable high consumption
at summer : kitchen (sanitary hot water)
• Humidification : steam for AHU
• May / june 2010 :
problem with humidification
Electrical consumption
Considerations : • High consumption : AHU, office equipment, lights, kitchen equipment
• Small consumption: 3 heat pumps, chiller
• Small reduction in monthly electricity consumption (i.e. water pump fountain)
Electrical consumption
Considerations : • Total low electricity consumption HPs
• HP3 : almost no elec. consumption
• HP1 & HP2 : similar profile
• Summer : (almost) no consumption
• More heating power available
Proposals : • Connect HP3 to central heat system
• Change climate control strategy
Temperatures HP
Temp.set point ↓
Energyperformance HP
Ptherm,deliv
(MWh/year)
Ptherm,extract
(MWh/year)
Pelectrical
(MWh/year)
COPyear COPstd.ref.
HP 1+HP2 78 65 17 4,6 4,5
HP3 29 3 26 1,3 3,2
HP 1+ HP2 HP3
Pth,deliv Pth,extract Pel COP Pth,deliv Pth,extract Pel COP
MWh MWh MWh MWh MWh MWh
nov '10 (*) 12,16 10,00 2,16 5,63 2,51 0,44 2,07 1,21
dec '10 25,08 19,03 6,06 4,14 10,69 0,53 10,16 1,05
jan '11 15,65 12,21 3,45 4,54 5,21 0,55 4,67 1,12
febr '11 (*) 15,57 12,12 3,45 4,51 5,67 0,51 5,17 1,10
mrt '11 (*) 8,65 6,79 1,85 4,66 4,16 0,53 3,63 1,14
april '11 0,00 0,99 0,00 0,26
mei '11 0,00 0,00 0,00 0,04
juni '11 0,00 0,00 0,00 0,01
juli '11 0,00 0,00 0,04 0,03 0,01 0,03 1,25
aug '11 0,00 0,00 0,04 0,07 0,04 0,03 2,59
sept '11 0,00 0,00 0,04 0,03 0,00 0,03 1,17
okt '11 0,72 0,54 0,17 4,13 0,19 0,17 0,02
nov '11 1,30 1,04 0,27 4,88 0,44 0,44 0,00
dec '11 5,62 4,12 1,50 3,74 0,39 0,38 0,01
Considerations :• COP HP3 very low!
Proposals :� Check HP3� Connect HP3 on central
heating system
Energyperformance HP
Considerations :• HP1 & HP2 = alternating regime• Pel HP 1 ≈ Pel HP 2• Pth HP 1 > Pth HP 2• COP HP1 = 5 • COP HP2 = 3,5
Proposal : � Check HP2
Free-cooling
Considerations :• Good operation free-cooling• Small or no operation chiller• Temperature diff. (depart/retour)
is rather small• More cooling power available
Proposals :• Change climate control strategy
Energy Balance
Considerations :• +/- good balance• good regeneration• Year over year temperatures / Long term balance
= not enough info yet = to be followed up
Extracted heat : 64,4 MWh
Extracted cold : 63 MWh
Temperature bore holes
Thermal Comfort
Considerations:• Design comfort criteria : 20°C – 25°C = OK
• Optimal comfort zone : 20,5°C – 23,5°C = +/- OK
23,5
20,5
Thermal comfort
Considerations:• Good thermal summer comfort
Proposal :• Increase temp. set.point / dead band temp. control in summer > energy saving
Thermal comfort
Considerations :
• Winter comfort = OK
• Large spread oper.int.temp.(Tmin – Tmax) at similar Tref.ext. (range 0°C-10°C)
• Mid season = risk of overheating
• Control sunshades!
Agenda
1. Bayer office building project
2. Evaluation� Energyconsumption
� Heat pumps
� Free-cooling
� Bore hole system
� Comfort
3. Primary energysaving & CO2-reduction
4. Conclusions & Proposals
Energy/CO2 saving
HPs + bore holes + backup boiler +
backup chiller (Bayer)
std. boilers + std. chillers (Reference)
Electrical consumption MWh e 73 84
Primary electrical consumption GJ p 656 756
Gas consumption GJ p 0 302
Total Primary energy consumption GJ p 656 1.058
Reduction Primary energy GJp
% Saving -
402
38%
Primary Energy Saving
HPs + bore holes + backup boiler +
backup chiller (Bayer)
std. boilers + std. chillers (Reference)
CO2 due to electrical consumption ton 73 84
CO2 due to gas consumption ton 0 17
Total CO2-emission ton 73 101
Reduction CO 2-emission ton% Saving -
CO2-Saving
28
28%
Agenda
1. Bayer office building project
2. Evaluation� Energyconsumption
� Heat pumps
� Free-cooling
� Bore hole system
� Comfort
3. Primary energysaving & CO2-reduction
4. Conclusions & Proposals
Conclusions
Evaluation1. Energyconsumption:
• Gas: medium/low, no submetering
• Electricity: medium/high, heat pumps/chiller ↓
2. Heat pumps• COP HP1 > COP HP2
• COP HP3 very low
3. Free-cooling: • good performance
4. Bore holes : • temperatures depart/retour = OK,
• good energy balance/regeneration
5. Thermal comfort :• Good summer / winter comfort
• Risk of overheating in mid season (sunshades !)
Proposals
• HP 3: • Check performance
• Connect to central heat system
• HP 1 / HP 2:• HP1 = standard / HP 2 = backup
• Check performance HP2
• Indoor climate control :• Increase set.point / dead band zone indoor temperature
within adaptive comfort limits
• Check controlstrategy individual roomcontrol of indoor temperature
(TABS, ventilation, ventiloconvectors)
Towards optimal design and control of geothermal heat pumps
combined with thermally activated building systems in offices
WP1: Project coordination and management
WP2: State-of-the-art review of design methods �design tree
WP3: Inventory of cases � online database
WP4: Monitoring of real GEO-HP-TABS cases
WP5: Model simulations
WP6: System operation and controller development
�MPC implementation
WP7: Comfort survey tool development �www.comfortmeter.eu
WP8: Guidelines for improved design and control �REHVA guidebook
WP9: Dissemination and valorisation
www.geotabs.eu
GeoTabs
� Ingenium nv
� ir. Pedro Pattijn
� Business Unit Manager Energy & Sustainability
� Nieuwe Sint Annadreef 23
� 8200 Brugge
� Tel. 050/40.45.30
� Fax 050/40.45.34
� E-mail: [email protected]
� Web: www.ingenium.be
Questions?