Page 1: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

Consolidation and Upgrade of the SPS Electrical NetworksCurrent StatusJP. Sferruzza, on behalf of EN/EL

Page 2: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

JP. Sferruzza 2

Content of the Presentation

• Introduction on the SPS electrical networks;

• Problem statement;

• Current status of the project;

• Next steps;

• Collection of user requirements.

LIU-SPS 22/07/2015

Page 3: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

JP. Sferruzza 3

Content of the Presentation

• Introduction on the SPS electrical networks;

• Problem statement;

• Current status of the project;

• Next steps;

• Collection of user requirements.

LIU-SPS 22/07/2015

Page 4: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

JP. Sferruzza 4

The SPS Electrical Networks

Stable Network

• General services

• Lights• Ventilation• Racks,

etc…

Pulsed Network

• Power converters

Safety Network

• Lifts• Lights• Access• Fire

Detection• Ventilation

and smoke extraction

Different 400 kV transformersAssured by generators

LIU-SPS 22/07/2015

Page 5: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

JP. Sferruzza 5

18 kV and 400 V Pulsed Network

EMD1/BE

SMB

x6

SQF SQD

18 kV EMD2/BE

SMB

x8

BA3BB3

400 kV

18 kV

BA4BA2

BA1

BA7 BA6

BA5

BB3

Build. 861

LIU-SPS 22/07/2015

Page 6: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

JP. Sferruzza 6

18 kV and 400 V Stable Network

EMD1/E9

66 kV

18 kV

BA2

BA1

BA7

BA6

BA5

BB3

BA4

BA3

BB6

Build. 958

LIU-SPS 22/07/2015

Page 7: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

JP. Sferruzza 7

BK1

3.3 kVBE91

Generators

BK2 BK3

BK4BB4

BB5BK5

Nominal Supply from EMD2/E91

18 kVSEM11

Generators

BK7

BK6

Nominal Supply from EMD2/E91ME9 18 kV

18kV, 3.3 kV and 400 V Safety Network

BK1 to BB5 : 3.3 kV feeders from BE91 (Building 791)

BK6 et BK7 : 18 kV feeders from SEM11 (Building 2160)

BK1

3.3 kVBE91

Generators

BK2 BK3

BK4BB4

BB5BK5

Nominal Supply from EMD2/E91

18 kVSEM11

Generators

BK7

BK6

Nominal Supply from EMD2/E91ME9 18 kV

LIU-SPS 22/07/2015

Page 8: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

JP. Sferruzza 8

Content of the Presentation

• Introduction on the SPS electrical networks;

• Problem statement;

• Current status of the project;

• Next steps;

• Collection of user requirements.

LIU-SPS 22/07/2015

Page 9: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

JP. Sferruzza 9

BK1

3.3 kV

Generators

BK2 BK3

BK4BB4

BB5BK5

Nominal Supply from EMD2/E91

18 kVSEM11

Generators

BK7

BK6

Nominal Supply from EMD2/E91ME9 18 kV

Consolidation Done – Safety Network & UPSBK substations installed in 2000

LIU-SPS 22/07/2015

Page 10: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

JP. Sferruzza 10

Consolidation Done – High Voltage Cables

High voltage cables replaced during LS1

LIU-SPS 22/07/2015

Page 11: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

JP. Sferruzza 11

Status of the other Equipment

20351970 200020232024

SPS Installation

LS2 LS3

Foreseen run of HL-LHC

2015

Today

LIU-SPS 22/07/2015

Mid 20182019

Page 12: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

JP. Sferruzza 12

Status of the other Equipment

20351970 200020232024

Installationof the

electrical networks

LS2 LS3

Foreseen run of HL-LHC

2015

Today

Decreasing reliability

High voltage switchgears, transformers;Auxiliary power supply;Low voltage switchboards;Underground power distribution;

BK substations;Uninterrupted Power Supplies (UPS)

UPS lifetime

Recommended lifetime of the electrical equipment

LIU-SPS 22/07/2015

Mid 20182019

Page 13: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

JP. Sferruzza 13

Example of Failure

LIU-SPS 22/07/2015

• Blast in EMD5/B3 on 22/09/2013 (during LS1);

• The switchgear had to be replaced (>6 months);

• During a run, such a failure would stop the SPS for several

weeks in the best case (with a temporary solution).

EDMS 1314867

Page 14: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

JP. Sferruzza 14

Content of the Presentation

• Introduction on the SPS electrical networks;

• Problem statement;

• Current status of the project;

• Next steps;

• Collection of user requirements.

LIU-SPS 22/07/2015

Page 15: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

JP. Sferruzza 15

Current Status

• Preliminary study started in February 2015;

• Overview of the current status of the SPS electrical networks;

• Identification of the risks on the project;

• Project roadmap, priorities.

LIU-SPS 22/07/2015

Page 16: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

JP. Sferruzza 16

Work Packages Definition and Priority

Network Equipment Quantity to be replacedObsolescence

degreeImpact of a failure Priority

Work

Package

Stable and pulsed

networks

-

Primary distribution

HV transformers 22

High

Shutdown of the

SPS

Possible impact on other sites

High WP1

HV cubicles 84

HV cables 1-2 km

LV primary switchboards 34

Auxiliary power supply systems 18

Stable and pulsed

networks

-

Secondary distribution

LV secondary switchboards 71

HighComplete or partial

shutdown of the

SPS, depending on

the circuit

Mediu

m

WP2

UPS 17

Underground power

distribution and lights

Underground power distribution 370 boxes, 70 km cablesHigh

WP3Normal lights 1100 lights, 14 km cables LowLow

Safety network

Backup lights 350 lights, 14 km cables High Safety - low impact

Emergency lights 310 lights, 14 km cables Very High Safety - high impact

Very

High

WP4

HV transformers 4

HighAccess, safety of

personnelWP5HV cubicles 2

LV secondary switchboards 3

LIU-SPS 22/07/2015

Page 17: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

JP. Sferruzza 17

Risks - Interaction with other Projects

Electrical Networks

Consolidation

Identification & De-cabling of Obsolete

Equipment in the Injectors

LIU Project

LIU-SPS 22/07/2015

Upgrade

It is also a chance!

Page 18: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

JP. Sferruzza 18

Risks - Interaction with non-EL Users

Electrical Network Consolidation Project

Non-EL Users

Some works planned by non-EL users will require the availability of some parts of the networks concerned by the EL consolidation

Some new needs will have to be taken into account by an “upgrade” part of the project

LIU-SPS 22/07/2015

COORDINATION MEETINGS

Page 19: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

JP. Sferruzza 19

Content of the Presentation

• Introduction on the SPS electrical networks;

• Problem statement;

• Current status of the project;

• Next steps;

• Collection of user requirements.

LIU-SPS 22/07/2015

Page 20: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

JP. Sferruzza 20

Next Steps

• Beginning of the study phase in June;

• The study phase will require the collection of user needs for upgrade;

• Objective of the study phase: define a general strategy for all SPS sites, end 2015.

LIU-SPS 22/07/2015

Page 21: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

JP. Sferruzza 21

Project Costing

• A detailed cost breakdown for the consolidation works will be provided after completion of the study phase;

• Funding for the consolidation will be covered by EL-SPS & ACC-CONS;

• The cost of dedicated upgrades for projects such as LIU shall be covered by the project concerned.

LIU-SPS 22/07/2015

Page 22: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

JP. Sferruzza 22

Content of the Presentation

• Introduction on the SPS electrical networks;

• Problem statement;

• Current status of the project;

• Next steps;

• Collection of user requirements.

LIU-SPS 22/07/2015

Page 23: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

JP. Sferruzza 23

Collection of User Requirements - Timeline

LIU-SPS 22/07/2015

June Dec.July Aug. Sept. Oct. Nov.

Memo

Identification of concerned projects and

project leaders

For each project, electrical load schedule to be studied with the

help of EN/ELValidation

End Study Phase Beginning Design Phase Objective: first installation

works during EYETS 2016

2016

Page 24: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

JP. Sferruzza 24

Collection of User Requirement - Parameters

• List of electrical loads, location;

• Rated power;

• Absorbed power;

• Power factor;

• Nominal voltage;

• Load profile;

• Load criticality;

• Space required;

• Planning of installation and commissioning.LIU-SPS 22/07/2015

Page 25: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.

JP. Sferruzza 25

Conclusion

• A wide project for EN/EL, able to ensure the reliability of the SPS electrical supply for the next 30 years;

• Good opportunity to coordinate upgrade and consolidation works in a single project;

• The Study Phase requires the collection of user needs for upgrade (for end of October 2015);

• General strategy for all SPS site to be determined by the end of the year.

LIU-SPS 22/07/2015

Page 26: Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.