Page 1: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

System CPX-E

Description

Function

Parameterisation

8071027

2017-07

[8071029]

Page 2: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Festo – CPX-E-SYS-EN – 2017-07 –

Original instructions

CPX-E-SYS-EN

CoDeSys®, PI PROFIBUS PROFINET® are registered trademarks of the respective trademark owners in certain

countries.

Symbols used:

Recommendations, tips, references to other documentation

Page 3: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

Festo – CPX-E-SYS-EN – 2017-07 – English 3

Table of Contents

1 About this document 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.1 Further applicable documents 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.2 Target group 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.3 Product version 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.4 Product labelling 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5 Specified standards 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2 Function 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.1 Overview 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.1.1 Function example 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.1.2 Modules CPX-E 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.1.3 System CPX-E 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.1.4 Power supply concept 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.2 Influencing signal statuses 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.2.1 Influencing output signals 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.2.2 Influencing input signals 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.2.3 Forcen 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.2.4 Signal status when there is a fault (Fail safe) 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.2.5 Signal status in Idle status (Idle mode) 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3 Diagnostics options 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3.1 LED indicators 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3.2 Status bits 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3.3 I/O diagnostic interface 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3.4 Diagnostic memory 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3.5 Error classes 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3.6 Error numbers 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3 Parameterisation 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1 Parameterisation using Festo software 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.2 Parameterisation using the higher-order controller 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3 Types of parameters 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4 Parameters and data for the system CPX-E 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4.1 Overview 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4.2 Function numbers 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.5 System parameters 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.5.1 Monitoring 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.5.2 Fail safe 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.5.3 Force mode 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.5.4 Idle mode 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.5.5 System start 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.5.6 Analogue process value representation 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.6 Module parameters (module-specific) 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.6.1 Module monitoring 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.6.2 Behaviour after short circuit/overload 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.6.3 Input debounce time 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.6.4 Signal extension time 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.6.5 Data format for analogue value of inputs/outputs 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 4: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

4 Festo – CPX-E-SYS-EN – 2017-07 – English

3.7 Module parameters (channel-specific) 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.7.1 Signal extension channel x 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.7.2 Fail safe channel x 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.7.3 Idle mode channel x 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.7.4 Forcen channel x 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.8 Diagnostic memory parameters (Trace parameters) 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.8.1 Entries saved retentively with Power On 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.8.2 Run/Stop filter 1 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.8.3 Run/Stop filter 2 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.8.4 Error end filter 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.8.5 Error number filter 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.8.6 Module/channel filter 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.8.7 Module number 43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.8.8 Channel number 43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.8.9 Error number 43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.9 Diagnostic memory data 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.9.1 Number of entries in the diagnostic memory 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.9.2 Overflow 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.9.3 Status 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.9.4 Diagnostic memory 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.10 System diagnostic data 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.10.1 Status bits 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.10.2 Module number and diagnostic status 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.10.3 Error number 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.11 Module diagnostic data 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.11.1 Number of the first faulty channel 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.11.2 Error number 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.11.3 Info 2 and 3 (reserved) 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.12 System data 48. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.12.1 Expansion 48. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.12.2 Force mode 48. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.12.3 System start 48. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.12.4 Fail safe 48. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.12.5 Idle mode 49. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.12.6 System monitoring 49. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.13 Module data 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.13.1 Module code 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.13.2 Revision code 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.13.3 Serial number 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A Technical Data 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B Terminology 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Index 54. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 5: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

1 About this document

Festo – CPX-E-SYS-EN – 2017-07 – English 5

1 About this document

This document describes the function and parameterisation of the product series stated in the title.

Use of and further information on handling the products are described in other documents

� 1.1 Further applicable documents.

1.1 Further applicable documents

Document Contents

Instructions for use of system CPX-E (CPX-E-SYS) Instructions and important notes on mounting,

electrical installation and maintenance tasks in a system

CPX-E

Documentation for the components in a system CPX-E

and the connected peripherals

Information on use of the components

Special documentation on ATEX Information on the use of the product in explosive gas

atmospheres

Device description files Definition of the modules of a system CPX-E for

integration into the higher-order controller

Documentation of the higher-order controller and

additional participants in the network

Information on commissioning and parameterisation

of�the components

Tab. 1.1

For all available product documentation � www.festo.com/pk.

1.2 Target group

This document is intended for qualified specialised personnel. Experience with electrical control systems is required

in order to understand this documentation.

1.3 Product version

This document refers to the system consisting of modules CPX-E. The product version can be identified from the

product label or with the help of appropriate software from Festo.

Appropriate software for identifying the product version can be found in the Festo Support Portal

� www.festo.com/sp.

Information on using the software can be found in the integrated Help function.

1.4 Product labelling

The modules CPX-E are labelled on the side. The product labelling is described in the documentation supplied with

the product.

1.5 Specified standards

Version

DIN 46228-1:1992-08 EN 60529:2013-10

DIN 46228-4:1990-09 EN 60715:2001-09

EN 60068-2-27:2010-02 IEC 60204-1:2014-10

Tab. 1.2

Page 6: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Function

6 Festo – CPX-E-SYS-EN – 2017-07 – English

2 Function

2.1 Overview

The system CPX-E is a modular system for the connection of electrical periphery and designed for use in a protected

environment. A system CPX-E can be connected to a higher-order controller via a network using a bus module or

controller, or operated autonomously.

The behaviour of the system CPX-E can be adapted to the respective requirements through parameterisation.

By�accessing the internal parameters it is possible to influence the following, for example:

– Behaviour of the outputs in the event of communication errors (Fail-safe settings)

– Behaviour following fault clearance

– Debounce times and signal extension times for digital input signals

– Force settings (force signal status)

– Operating method of the diagnostic memory

Modules CPX-E are supplied with preset parameters. You can find the module-specific parameters in the

corresponding module documentation.

2.1.1 Function example

1

2

3

4

5

6

1 Higher-order controller2 Valve terminal VTUG3 Standards-based cylinder with proximity sensors

for�position sensing

4 Flow sensor5 Signal lamp6 System CPX-E with bus module and I/O modules

Fig. 2.1

Page 7: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Function

Festo – CPX-E-SYS-EN – 2017-07 – English 7

2.1.2 Modules CPX-E

This section presents an overview of the various modules CPX-E which can be used to construct a system CPX-E and

describes their functions.

You can find detailed information about the individual modules in the documentation supplied with

each�product.

Bus module

A bus module is the interface between a system CPX-E and the fieldbus/network, and performs the following

functions:

– Connection of the system CPX-E to the fieldbus/network

– Data transfer between the system CPX-E and the higher-order controller

– Transmission of control signals to the connected modules

– Monitoring the functionality of the connected modules

– Read and write access to system parameters, input and output signals and diagnostic data (dependent on the

bus module)

– Control of the system CPX-E

Examples of bus modules:

– CPX-E-PB (PROFIBUS DP)

– CPX-E-PN (PROFINET IO)

– CPX-E-EP (EtherNet/IP, Modbus TCP)

– CPX-E-EC (EtherCAT)

Overview (using CPX-E-EC as an example)

1 LED indicators2 DIL and/or rotary switches1)2)

3 Terminal block (coded, removable)4 Terminal block lock5 Module lock6 Network connection7 Linking element8 Functional earth contact FE

1) Dependent on the bus module

2) Not present on all bus modules

1

2

34

5

6

7

8

6

Fig. 2.2

Page 8: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Function

8 Festo – CPX-E-SYS-EN – 2017-07 – English

Controller

A controller is used to control a system CPX-E:

– Stand-alone system controller

– Incorporation into higher-order plant controllers via integrated communication interfaces (e.g. PROFINET) or

Ethernet.

Using a controller provides the option of implementing process visualisation via CODESYS in addition to

programming.

Examples of controllers:

– CPX-E-CEC-C1-PN

– CPX-E-CEC-M1-PN

Overview (using CPX-E-CEC-C1-PN as an example)

1 Cover (removable)2 Slot for SD memory card3 USB interface4 Ethernet interfaces5 Terminal block (coded, removable)6 Terminal block lock7 LED indicators8 Network connection9 Linking element

1

2

3

4

56

8

8

7

9

Fig. 2.3

Input/output modules

Input or output modules are used to process digital or analogue signals, depending on the module.

Examples of input and output modules:

– Digital input modules CPX-E-16DI-...

– Digital output modules CPX-E-8DO-...

– Analogue input modules CPX-E-4AI-U-I

– Analogue output modules CPX-E-4AO-U-I

– IO-Link master module CPX-E-4IOL-...

– Counter module CPX-E-1CI

Overview (using IO-Link master module CPX-E-4IOL as an example)

1 LED indicators2 Terminal blocks (coded, removable)3 Terminal block lock4 Module lock5 Linking element6 Functional earth contact FE7 DIL switch1)

1) Not present on all modules

1

2

3

2

4

5

6

7

Fig. 2.4

Page 9: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Function

Festo – CPX-E-SYS-EN – 2017-07 – English 9

2.1.3 System CPX-E

Rules for set-up

A system CPX-E essentially comprises a bus module or controller and a maximum of 10 further modules. The bus

module or controller is always positioned within a system CPX-E as the first module on the left. The other modules

can be added in any sequence.

Example set-up of system CPX-E

1 Bus module (here: CPX-E-PN)2 Input and output modules

– Digital input module CPX-E-16DI

– Digital output module CPX-E-8DO

– Analogue input module CPX-E-4AI-U-I

– Analogue output module CPX-E-4AO-U-I

– IO-Link master module CPX-E-4IOL

2

1

Fig. 2.5

H-rail mounting

The modules are mounted on an H-rail 35 × 7.5 mm to EN 60715.

When selecting screws for H-rail mounting, a distance between the H-rail and the linking elements of

3 mm must be observed.

The distance between the screws for mounting the H-rail may be a maximum of 50 mm.

Mounting distances

To guarantee sufficient dissipation of heat from the modules, the following minimum distances must be observed

when mounting the system CPX-E � Fig. 2.6.

Minimum distances for thesystem�CPX-E for vertical/horizontalmounting

1 System CPX-E2 End supports

Dimensions [mm]: a = 40

b = 20

c = 30

d = 106

e = 195

2

1

Fig. 2.6

Page 10: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Function

10 Festo – CPX-E-SYS-EN – 2017-07 – English

2.1.4 Power supply concept

The system CPX-E uses separate voltages to supply the electronics and sensors (UEL/SEN) and to supply outputs

(UOUT). The equivalent voltage potentials (+24 V DC and 0 V DC) are respectively connected to each other in the

terminal blocks. This enables the respective voltage to be transferred from one module to the next.

Operating voltage supply UEL/SEN

The operating voltage supply UEL/SEN to supply the electronics and sensors is fed in at the bus module or controller

and distributed internally to the entire system CPX-E by means of the linking.

Load voltage supply UOUT

The load voltage supply UOUT to supply the outputs is fed directly into the module, separately for each module

having outputs.

1 Bus module CPX-E-PN2 Digital input module CPX-E-16DI3 Digital output module CPX-E-8DO4 Analogue input module CPX-E-4AI-U-I5 Analogue output module CPX-E-4AO-U-I6 IO-Link master module CPX-E-4IOL7 Load voltage supply UOUT

8 Operating voltage supply UEL/SEN

9 Linking

78

9

1 2 3 4 5 6

Fig. 2.7

The operating voltage supply UEL/SEN and load voltage supply UOUT are routed separately from each

other within a system CPX-E. If this separation is not required for the respective use case, both voltages

can also be supplied from a common voltage source. In this case, it must be possible to disconnect the

load voltage supply separately.

Page 11: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Function

Festo – CPX-E-SYS-EN – 2017-07 – English 11

2.2 Influencing signal statuses

Functions for influencing signal statuses

Function Priority1) Brief description Signals that can be

influenced

Forcen2) 1 Influences signal statuses independently of actual

signal statuses � 2.2.3.

Input and output signals

Fail safe 2 Specifies signal statuses that take effect in the event

of�communication errors in the network � 2.2.4.

Output signals

Idle mode3) 3 Specifies signal statuses that take effect when

switching to Idle status � 2.2.5.

Output signals

1) If several functions are active at the same time

2) Primarily for test purposes during commissioning

3) Only relevant for certain network protocols

Tab. 2.1

2.2.1 Influencing output signals

The basic settings for the respective function are preset using system parameters. By setting the system parameter

appropriately, you can specify the desired signal status for each channel individually, using channel-specific module

parameters.

Force

Memory

Fail safe

Idle mode

Module parameterIdle mode channel x

Reset outputs

01

0System parametersIdle mode

Yes No

Assume idle mode Ho

ld la

st s

tate

Idle mode status

Memory

Module parameterFail safe channel x

Reset outputs

01

0System parameterFail safe

Yes No

Assume fault mode Ho

ld la

st s

tate

Network communication faults

0 1

Module parameterForce channel x

System parameterForce mode

Enable Disable

Output

1

Output signal (e.g. via network)

Disable

Idle mode is only relevant for certain

network protocols.

1 Status LED for the respective output

Fig. 2.8

Page 12: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Function

12 Festo – CPX-E-SYS-EN – 2017-07 – English

2.2.2 Influencing input signals

1Force 0 1

Module parameterForce channel x

System parameterForce mode

Enable Disable

Input signal

Input

Disable

1 Status LED for the respective input

Fig. 2.9

Forcen an input does not modify the input signal itself and cannot be observed at the relevant status LED.

The�logical status of the input only changes internally and may be effective in a program.

2.2.3 Forcen

Fundamentals

The Forcen function permits the manipulation of signal statuses independently of the actual operating conditions.

Forcen enables input and output signals to be overwritten. Input signals actually present or changes in status by

program will be ignored. The input signals actually present and the output signals generated by the user program

only become valid again when the Forcen function is deactivated.

The Forcen function is used mainly in the commissioning phase in order to set certain signals to the desired status

for test purposes even if the wiring is not complete.

Parameterisation

In the system CPX-E, Force parameterisation is possible for:

– Digital inputs and outputs

– Solenoid coils (only in combination with CPX-E-4IOL)

– Inputs and outputs of the I/O diagnostic interface and status bits

– Analogue inputs and outputs

Forcen is enabled or disabled globally for the system CPX-E using the “Force mode” system parameter.

System parameters Settings Description

Force mode Disabled (presetting) Forcen disabled1)

Enabled Forcen enabled1)

1) Applies to the entire system CPX-E

Tab. 2.2

The signal status can be specified according to the channel (input/output) for each module.

Module parameter Settings Description

Force mode Disabled (presetting) Forcen is disabled for the channel

Force state Adopt the signal status defined

by Force state

Force state

Digital signal Reset signal (presetting) Reset input/output signal

Set signal Set input/output signal

Analogue signal Analogue value (0 = presetting) Value of the analogue signal

Tab. 2.3

Page 13: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Function

Festo – CPX-E-SYS-EN – 2017-07 – English 13

Mode of operation

Input information actually present will be replaced by the values entered in the Force table in the process image for

the inputs.

Information actually present in the process image for the outputs will be replaced by the values entered in the Force

table and transmitted to the physical outputs.

Force parameterisation – example for binary signals

1 1 0 0 1 0 0 0

0 1 0 1 0 1 1 0

1 1 1 0 1 0 1 0

Force mode

0 = Force disabled

1 = Force state

Force state

0 = Reset signal

1 = Set signal

0 1 1 0 0 0 1 0

1

2

3

1 Signal status previously2 Module parameter (according to channel)

3 Signal status afterwards

Fig. 2.10

Force parameterisation – example for analogue signals

1 1 0 0 1 0 0 0

100 505 100 321 202 110 80 50

321 288 333 432 400 505 11 500

Force mode

0 = Force disabled

1 = Force value

Force state

100 505 333 432 202 505 11 500

1

2

3

1 Analogue signal previously2 Module parameter (according to channel)

3 Analogue signal afterwards

Fig. 2.11

Page 14: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Function

14 Festo – CPX-E-SYS-EN – 2017-07 – English

2.2.4 Signal status when there is a fault (Fail safe)

Fundamentals

The Fail-safe parameterisation is used to help specify the signal status which the outputs are to assume in the event

of communication errors in the network (Fail-safe status). This should establish a defined machine/system status in

the event of communication errors in the network (e.g. failure of the higher-order controller).

Parameterisation

In the system CPX-E, Fail-safe parameterisation is possible for:

– Digital outputs

– Analogue outputs

– Solenoid coils (only in combination with CPX-E-4IOL or digital outputs)

The “Fail safe” system parameter can be used to globally specify the signal status which the outputs are to assume

in the event of communication errors in the network, e.g. in the event of:

– Communication failure (network interruption, PLC failure)

– Communication stop

System parameter Settings Description

Fail safe Reset outputs (presetting) Reset all outputs

Hold last state Retain current signal status for all outputs

Assume Fault-mode value Adopt the signal status defined for the

relevant channel

Tab. 2.4

“Reset outputs” means the following:

– Monostable valves move to the initial position.

– Bistable valves remain in the current position.

– Mid-position valves go into mid-position (pressurised, exhausted or closed, depending on

valve�type).

If “Assume Fault mode value” is activated, the signal statuses defined by module parameter for the relevant channel

will take effect � Tab. 2.5.

Module parameter Settings Description

Fault mode Hold last state Retain current signal status

Fault state (presetting) Adopt the signal status defined

by Fault state

Fault state

Digital signal Reset output (presetting) Reset output signal

Set output Set output signal

Analogue signal Analogue value Value of the analogue signal

Tab. 2.5

Page 15: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Function

Festo – CPX-E-SYS-EN – 2017-07 – English 15

Mode of operation

The Fault mode parameter is used to determine whether the current signal status is to be retained or whether the

signal status defined by the Fault state parameter is to be assumed.

Fail-safe parameterisation – example for binary signals

0 1 0 1 1 1 0 0

0 0 0 1 0 1 0 0

1 1 0 0 1 1 1 0

Fault mode

0 = Hold last state

1 = Fault state

Fault state

0 = Reset output

1 = Set output

1 0 0 1 0 1 1 0

1

2

3

1 Signal status before the fault2 Module parameter (according to channel)

3 Signal status after the fault

Fig. 2.12

Fail-safe parameterisation – example for analogue signals

0 1 0 1 1 1 0 0

222 500 500 500 333 321 100 200

100 321 444 230 700 604 0 333

Fault mode

0 = Hold last state

1 = Fault state

Fault state

100 500 444 500 333 321 0 333

1

2

3

1 Signal status before the fault2 Module parameter (according to channel)

3 Signal status after the fault

Fig. 2.13

Page 16: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Function

16 Festo – CPX-E-SYS-EN – 2017-07 – English

2.2.5 Signal status in Idle status (Idle mode)

This function is only relevant for certain network protocols � Description for the respective bus module.

Fundamentals

The Idle-mode parameterisation is used to help specify the signal status which the outputs are to assume when

switching to Idle status. This should establish a defined machine/system status.

Parameterisation

In the system CPX-E, Idle-mode parameterisation is possible for:

– Digital outputs

– Analogue outputs

– Solenoid coils (only in combination with CPX-E-4IOL or digital outputs)

The Idle mode system parameter can be used to globally specify the signal status which the outputs are to assume

when switching to Idle status.

System parameters Settings Description

System Idle mode Reset outputs (presetting) Reset all outputs

Hold last state Retain current signal status for all outputs

Assume Idle-mode value Adopt the signal status defined for the

relevant channel

Tab. 2.6

If “Assume Idle mode value” is activated, the signal statuses defined by module parameter for the relevant channel

will take effect � Tab. 2.7.

Module parameter Settings Description

Idle mode Hold last state Retain current signal status

Idle state (presetting) Adopt the signal status defined

by Idle state

Idle state

Digital signal Reset output (presetting) Reset output signal

Set output Set output signal

Analogue signal Analogue value Value of the analogue signal

Tab. 2.7

Mode of operation

The mode of operation is identical to Fail-safe parameterisation � Fig. 2.12 and Fig. 2.13.

Page 17: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Function

Festo – CPX-E-SYS-EN – 2017-07 – English 17

2.3 Diagnostics options

For the diagnostics of errors, various possibilities are available depending on the parameterisation and network

protocol used.

Diagnostics option Description Detailed information

LED display components

System-specific System status and errors are displayed directly on the

module via LED indicators.

� 2.3.1

Module- or

network-specific

Module or network status and errors are displayed directly

on the module via LED indicators.

� Documentation for

respective module

Internal system diagnostics

Status bits Common diagnostic messages (global error messages) are

displayed by means of 8 internal inputs (8 status bits).

� 2.3.2

I/O diagnostic interface Diagnostic information for the system CPX-E is made

available via the I/O diagnostic interface. The I/O

diagnostic interface enables bus-independent read access

to diagnostic information, data and parameters via

16�internal inputs and 16 internal outputs.

� 2.3.3

Network-specific

diagnostic functions

Special diagnostic functions or communication services

may be available, such as DPV1 for PROFIBUS, depending

on the network used.

� Description for the

respective bus module

Tab. 2.8

2.3.1 LED indicators

Various LED indicators are available on every module for the visualisation of the statuses and errors. A distinction is

made here between system-specific LED indicators and those specific to the module or network.

The system-specific LED indicators of the controllers and bus modules are described in this document.

LED indicators specific to the module or network are described in the documentation for the respective

module.

Power System [PS] – Operating voltage supply UEL/SEN

LED (green) Meaning Remedy

lights up

ON

OFFVoltage supply present. No error. –

flashes

ON

OFFVoltage supply present, but outside of the

tolerance range.

� Eliminate undervoltage.

Linking on the bus module is missing or

incomplete.

� Check linking.

flashes

ON

OFFThe internal fuse of the voltage supply has

tripped.

� Eliminate short circuit/overload.

Depending on the parameterisation,

the voltage supply is then switched on

again automatically (factory setting)

or it must be switched off and then on

again.

off

ON

OFFVoltage supply not present. � Check connection of the power supply.

Tab. 2.9

Page 18: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Function

18 Festo – CPX-E-SYS-EN – 2017-07 – English

Power Load [PL] – Load voltage supply UOUT

LED (green) Meaning Remedy

lights up

ON

OFFVoltage supply present. No error. –

flashes

ON

OFFVoltage supply present, but outside of the

tolerance range.

� Eliminate undervoltage.

off

ON

OFFVoltage supply not present. � Check connection of the power supply.

Tab. 2.10

System Failure [SF] – System fault

LED (red)1) Meaning Remedy

flashes

ON

OFFSimple error/information

(error class 1)

� 2.3.5 Error classes

ON

OFFError

(Error class 2)ON

OFFSerious error

(Error class 3)

off

ON

OFFNo error –

1) The system error LED flashes as a function of the error class in question.

Tab. 2.11

Modify [M] – Parameterisation modified or Force active

LED (yellow) Meaning

lights up

ON

OFFSystem start with saved parameterisation and saved expansion set; parameters and

expansion are saved to retentive memory; external parameterisation is blocked.1)

Caution when replacing systems with saved parameterisation.

In the case of these systems, parameterisation is not carried out automatically by the

higher-order controller on replacement.

� Before replacement, note required settings and restore them after replacement,

if�required.

flashes

ON

OFFThe Forcen function is enabled.1)

off

ON

OFFSystem start with default parameterisation (factory setting) and current expansion set;

external parameterisation is possible (presetting).

1) The indication of the Forcen function (LED flashing) has priority over indication of the setting for the system start with the saved

parameterisation and saved extension (LED lights up).

Tab. 2.12

Page 19: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Function

Festo – CPX-E-SYS-EN – 2017-07 – English 19

2.3.2 Status bits

Irrespective of the bus module used, the system CPX-E provides 8 status bits for displaying common diagnostic

messages (global error messages).

Status bits are configured like inputs. The input addresses which are to be assigned to status bits depend on the

network protocol used � Description for the respective bus module.

The status bits supply coded diagnostic information in form of 0 or 1 signals. If all bits supply a logic 0, no error is

reported.

– Bits 0 to 3 specify the module type in which errors have occurred.

– Bits 4 to 7 specify the type of error.

Bit Diagnostic information with logic 1 Description

0 Error at valve Module type in which an error has occurred

1 Error at output

2 Error at input

3 Error in analogue, function or technology module

4 Undervoltage Error type

5 Short circuit/overload

6 Wire break

7 Other error

Tab. 2.13

Examples of typical status information

No error signalled

Error type Module type

Other

error

Wire break Short

circuit

Under­

voltage

Analogue,

function

Input Output Valve

Bit 7 6 5 4 3 2 1 0

Status 0 0 0 0 0 0 0 0

Tab. 2.14

Short circuit at the output

Error type Module type

Other

error

Wire break Short

circuit

Under­

voltage

Analogue,

function

Input Output Valve

Bit 7 6 5 4 3 2 1 0

Status 0 0 1 0 0 0 1 0

Tab. 2.15

Undervoltage of sensor supply

Error type Module type

Other

error

Wire break Short

circuit

Under­

voltage

Analogue,

function

Input Output Valve

Bit 7 6 5 4 3 2 1 0

Status 0 0 0 1 0 1 0 0

Tab. 2.16

If different errors occur simultaneously on different module types, errors cannot be assigned.

The I/O diagnostic interface can be used to distinguish errors clearly � 2.3.3 I/O diagnostic interface.

Page 20: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Function

20 Festo – CPX-E-SYS-EN – 2017-07 – English

2.3.3 I/O diagnostic interface

For networks that do not have extensive diagnostic functions, the diagnostic information for the system CPX-E is

available via the I/O diagnostic interface. The I/O diagnostic interface enables network-independent read access to

diagnostic information, data and parameters via internal inputs and outputs (16 I/16 O).

Organisation of internal data and parameters

Internal data and parameters of the modules and of the system CPX-E are stored in a common memory area. The I/O

diagnostic interface can provide read access to individual bytes of this memory area with the aid of the function

number.

Parameters can be modified with the aid of network-specific functions, depending on the network used

� 3 Parameterisation.

Mode of operation of the I/O diagnostic interface

Detailed diagnostic information can be accessed via the I/O diagnostic interface. For example, it is possible to

ascertain on exactly which module and which channel an error has occurred. 16 input bits and 16 output bits,

through which all diagnostic data can be retrieved, are available for accessing the system diagnostics.

The addresses of the input and output bits of the I/O diagnostic interface depend on the network used

� Description for the respective bus module.

Output bits

The function number of the desired data is specified in binary coded form using the output bits O0 ... O12 of the I/O

diagnostic interface. The function number is applied when control bit O15 supplies a logic 1.

2

189101112131415 01234567

Function number

Control bitReserved

1 Bit number 2 Outputs

Fig. 2.14

Input bits

The reply data are output by the system CPX-E via the input bits I0 ... I7 when the acknowledgement bit I15 supplies

a logic 1.

189101112131415 01234567

Diagnostic data

Acknowledgement bit

Reserved

2

1 Bit number 2 Inputs

Fig. 2.15

If control bit O15 supplies a logic 0, acknowledgement bit I15 will be reset automatically and the status

byte will be shown with the diagnostic data bits.

Page 21: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Function

Festo – CPX-E-SYS-EN – 2017-07 – English 21

Reading out diagnostic data

The function number is applied if there is a rising edge at control bit O15. The input bits I0 ... I7 supply the diagnostic

data when the acknowledgement bit supplies a logic 1.

Reading out the diagnostic data flow diagram

NoAcknow­ledgementbit =1?

Yes

Start the read process

Set function number

Set control bit (O15)

Apply data

No

Yes

Reset control bit O15

Acknow­ledgementbit =0?

Start timeout

Timer

expired?

Reset control bit

Timer

expired?

No

Yes

TimeoutYes

No

Fig. 2.16

Page 22: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Function

22 Festo – CPX-E-SYS-EN – 2017-07 – English

Example 1: Check whether diagnostic data is available

Function number 1937 specifies whether there are diagnostic data and contains, where applicable, the number of

the first module on which an error has occurred � Tab. 3.38.

– Function number = 1937

– 1937 dec. = 11110010001 bin

Reading out function number 1937

2

189101112131415 01234567

Function number

Control bit

1 0 0 1 0 0 0 11 0 0 0 0 1 1 1

Reserved

1 Bit number of the outputs 2 Signal status of the outputs

Fig. 2.17

Diagnostic data are available if bit 6 supplies a logic 1. Bits 0 ... 5 then contain the module number of the first faulty

module � Tab. 3.38.

If, for example, there were a fault on module 5 (5 dec. = 101 bin), the following input data would be available:

Reply data (example – error on module 5)

189101112131415 01234567

Diagnostic data

Acknowledgement bit

Reserved

10 0 100 0 11

2

1 Bit number of the inputs 2 Signal status of the inputs

Fig. 2.18

Detailed information on the module diagnostic data � 3.11 Module diagnostic data.

Page 23: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Function

Festo – CPX-E-SYS-EN – 2017-07 – English 23

Example 2: Reading out current error numbers of module 5

Using the module number of the faulty module, it is possible to ascertain the function numbers of the relevant

module diagnostic data � 3.11 Module diagnostic data.

Module diagnostic data can be e.g.:

– The number of the faulty channel

– The module error number.

The following function number can be used to ascertain e.g. the module error number of module 5:

– Function number = 2008 + 4 * 5 + 1 = 2029

– 2029 dec. = 11111101101 bin

Reading out the module error number of module 5

2

189101112131415 01234567

Function numberControl bit

1 1 1 0 1 1 0 11 0 0 0 0 1 1 1

1 Bit number 2 Signal status of the outputs

Fig. 2.19

Fig. 2.20 shows by way of example the reply data in the case of error number 4 (4 dec. = 100 bin).

Reply data with error number 4

189101112131415 01234567

Diagnostic data

Acknowledgement bit

Reserved

00 0 100 0 01

2

1 Bit number of the inputs 2 Signal status of the inputs

Fig. 2.20

Page 24: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Function

24 Festo – CPX-E-SYS-EN – 2017-07 – English

2.3.4 Diagnostic memory

Fundamentals

The diagnostic memory is used for logging error statuses. Recording the time when errors occur and error

sequences makes it easier to find the cause of errors which are otherwise difficult to locate. Errors which occur

during operation are entered in the diagnostic memory. Depending on parameterisation, the first or the last

40�entries are saved, as well as the respective time measured from the moment the power supply was switched on.

Parameterisation

Various diagnostic memory filters can be parameterised by means of diagnostic memory parameters

(��3.8 Diagnostic memory parameters (Trace parameters)). These filters can be used to suppress the recording of

certain system statuses, and to control both starting and stopping. The mode of operation of the diagnostic memory

filters is shown in the following figure � Fig. 2.21.

The mode of operation of the diagnostic memory filters

Error end filter

Start: Error

Run/

stop

Filter 2

Error number filter

Module/channel filter

0 = Always record

1 = Record up to the defined FN

2 = Record up to the defined FN + MN

3 = Record up to the defined FN + MN + CN

4 = Record as from the defined FN

5 = Record as from the defined FN + MN

6 = Record as from the defined FN + MN + CN

Run/stop filter 1 The first 40 errors or the last 40 errors

Register end of fault or not

Record defined FN or not

Record FN of a module/channel only

Dia

gn

ost

ic

me

mo

ry

MN = Module number

CN = Channel number

FN = Error number

Fig. 2.21

Page 25: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Function

Festo – CPX-E-SYS-EN – 2017-07 – English 25

Mode of operation

A maximum of 40 diagnostic messages can be saved in the diagnostic memory. Using appropriate software from

Festo or using a controller CPX-E-CEC... via CoDeSys, it is possible to parameterise which messages are saved and

how these are saved, among other things. This includes how long they are stored for or the diagnostic memory

mode (“Entries remanent at Power ON”) and the memory procedure (“Run/Stop” setting). An explanation of the

major settings can be found in the following sections.

Suitable software for parameterisation can be found on the Festo Support Portal � www.festo.com/sp.

Detailed information on using the software can be found in the integrated Help function.

Memory duration or diagnostic memory mode

(“Trace parameters” > “Entries remanent at Power ON” or “Diag.Buffer – Mode”):

– “Active” or “remanent”:

The diagnostic messages remain saved when the operating voltage UEL/SEN is switched off or after a power

failure.

– “Inactive” or “not remanent”:

The diagnostic messages are lost after the operating voltage UEL/SEN is switched off or after a power failure.

Memory procedure

(“Trace parameters” > “Run/Stop 1” or “Diag.Buffer – Mode”):

– “Save first 40 entries” or “Stop after 40 records...”: (Stop after 40 entries...):

The bus module saves the first forty diagnostic messages. Additional, subsequent messages are not saved.

– “Save last 40 entries” or “Record continually...”:

Continuous saving of the diagnostic messages. After the fortieth message, the oldest message will be

overwritten.

Error end filter

(“Trace parameters” > “Fault end filter” or “Diag.Buffer – Error end”):

– “Record outgoing faults” or “Record coming/going” (record incoming/outgoing errors):

When an error occurs and is eliminated, the error number and the time of the event are recorded.

– “Do not record outgoing faults” or “Record coming only” (record incoming errors only):

The error number and the time of the event are recorded only when an error occurs. If the error is eliminated, the

time of the event will not be recorded.

2.3.5 Error classes

Possible errors of the system CPX-E are divided into three error classes (1 ... 3) with different priority, depending on

the seriousness of the error. If an error occurs, the system error LED (SF) flashes as a function of the error class in

question.

Error class Flashing sequence of the system error LED (SF) Error weighting Priority

1 1x flash, pause Minor Low

2 2x flash, pause Medium Medium

3 3x flash, pause High High

Tab. 2.17

If several errors occur together, the error with the highest priority will have precedence, in other words:

– The system error LED flashes according to the higher priority.

– The number of the error with the higher priority will be entered in the system diagnostic data under function

number 1938 (error number).

Within an error class, errors of modules with a lower module number have higher priority. That means that, within an

error class, errors on

– Module number 0 have the highest priority

– Module number 1 have the second highest priority

– etc.

Page 26: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Function

26 Festo – CPX-E-SYS-EN – 2017-07 – English

2.3.6 Error numbers

Error numbers (error class 2)

Error

number

Meaning Remedy

0 No error –

1 General diagnostics (module-specific errors) � Description for the respective module

2 Short circuit/overload in sensor supply (SCS) or at

output (SCO)

Eliminate short circuit/overload � Description

for the respective module.

3 Wire break/idling at current input/output � Check cables and sensors/actuators and

replace where required.

4 Failure of load voltage supply UOUT due to short

circuit/overload (on output side)

� Check actuators and their connections.

5 Undervoltage in the operating voltage supply

UEL/SEN (on input side)

� Eliminate undervoltage.

6 … 8 Reserved –

9 Value falling below nominal range � Check signal range and parameterised limit

value.10 Value exceeding nominal range

11 Short circuit at valve � Check valve and pneumatic interface.

12 Reserved –

13 Wire break at valve (open load) � Check valve and pneumatic interface.

14 Limit value of the condition counter exceeded � Set or delete the limit value of the condition

counter by parameterising.

15 Module/channel failed � Check module/peripherals and replace if

necessary.

16 Saved configuration is different to the actual

expansion of the system.

For the system:

� Check expansion and save again if necessary

� Tab. 3.13.

For the bus module:

� Modify the System Start parameter to

“System start with default parameterisation

and current CPX-E expansion”.

For the controller:

� Save the actual configuration as the set

configuration using the CoDeSys software.

17 Saved I/O length of the module is different to the

actual system expansion.

� Error number 16

18 Number of I/O points exceeded � Check DIL switch position and system

expansion � Description for the respective

bus module/controller.

19 Nominal service life/life cycle exceeded � Replace module or spare part � Description

for the respective module.

20 Error in

parameterisation

Signal range � Check the parameterisation and if necessary

repeat using the correct parameters.21 Data format

22 Linear scaling

23 Measured value

smoothing

24 Lower limit value

25 Upper limit value

26 Error on actuator supply � Eliminate short circuit and check actuators

and actuator supply.

27 Missing or incorrect spare part � Replace module or spare part � Description

for the respective module.

Page 27: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Function

Festo – CPX-E-SYS-EN – 2017-07 – English 27

Error numbers (error class 2)

Error

number

RemedyMeaning

28 Alarm value reached � Check operating conditions � Description

for the respective module.

29 Error in parameterisation � Check the parameterisation and if necessary

repeat using the correct parameters.

30 Error in internal communication

(no new output data)

� Replace module if switching on and off does

not remedy problem.

31 Bus connection interrupted � Make bus connection or check configuration.

32 STI read access defective � Repeat STI read access.

33 Read access parameter defective � Repeat read access parameter.

34 … 36 Reserved –

37 Defect in the controller function

(e. g. setpoint value cannot be reached)

� Check pressure and actuator supply.

38 No valve recognised � Check valve (function/installation), replace if

necessary.

39 Maintenance required � Description for the respective module

40 … 47 Reserved –

48 Calibration error (factory adjustment missing) � Replace module.

49 Current loop is in the lower drop-out range � Check the installation/parameterisation of

the actuator � Description for the respective

module.50 Current loop is in the upper drop-out range

51 Physical limit value for a sensor exceeded:

– Process value invalid

– Possible hardware damage

� Check structure (compliance with module

specification), check module for damage and

replace if necessary.

52 Short circuit at cold junction compensation � Eliminate short circuit and check connected

CJC sensors if necessary.

53 Wire break at cold junction compensation � Check cables and connected CJC sensors and

replace where required.

54 Calibration data is faulty � Replace module.

55 Formation of the process value is invalid due to

faulty structure

� Check structure (compliance with module

specification).

56 … 63 Reserved –

64 The number of modules in the current system

expansion does not match the saved expansion

� Correct expansion or save new expansion.

65 … 69 Reserved –

70 System expansion is greater than the number of

stations set

� Check DIL switch position (increase number

of stations).

71 Bus connection interrupted � Check wiring.

72 … 79 Reserved –

80 Module-specific malfunction � Description for the respective module

81 … 99 Reserved –

100 Error in configuration/parameterisation � Check configuration/parameterisation,

correct if necessary or repeat commissioning.

101 Error executing a positioning job � Check the positioning task and correct if

necessary.102 Error executing a positioning record

103 Error in control or in the parameters of a

positioning job

104 Error in the process control or the system

configuration

� Check system configuration, positioning job,

I/O signals or system status and correct as

necessary.

Page 28: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Function

28 Festo – CPX-E-SYS-EN – 2017-07 – English

Error numbers (error class 2)

Error

number

RemedyMeaning

105 Error in the peripherals (power supply, operating

pressure, etc.)

� Check peripherals, power supply and

operating pressure.

106 Error in valve or on axis string � Check valves and cables and replace where

required.

107 Error in the controller or drive regulator � Check controller or drive regulator and

replace if necessary.

108 Error in measuring system or on axis string � Check measuring system and cables and

replace where required.

109 Error in the motor or power section � Check motor or power section and replace if

necessary.

110 … 114 Reserved –

115 Module/channel in a subordinate system has

failed

� Check subordinate module

(function/installation) and replace if

necessary � Description for the respective

module.

Tab. 2.18

Error numbers (error class 3)

Error

number

Meaning Remedy

128 Hardware defective � Check hardware and replace if necessary.

129 Bus module faulty � Replace bus module.

130 System error on bus module � Replace module if switching on and off does

not remedy problem.

131 Error in internal communication during start-up � Check system and replace if necessary.

132 System error � Replace module if switching on and off does

not remedy problem.

133 … 134 Module faulty � Replace module.

135 Error in internal configuration, module out of order � Check system and replace if necessary.

136 System error � Replace module if switching on and off does

not remedy problem.

137 Error in internal configuration, module out of order � Check system and replace if necessary.

138 Error in internal configuration, e.g.:

– Module not correctly mounted, plugged in

– Module faulty

� Check module mounting/arrangement

(no�gaps in system expansion), check module

and replace if necessary.

139 Error when processing cyclical services

(e.g.�parameters)

� Check control program, check system and

replace if necessary.

140 Hardware defective � Identify and replace faulty module.

141 Malfunction in internal communication;

system�was not yet operational

� Check application environment, check system

and replace if necessary.142

143 System error � Replace module if switching on and off does

not remedy problem.

144 Module does not have a valid licence � Procure licence or replace module.

145 … 149 Reserved –

150 System error � Replace module if switching on and off does

not remedy problem.

151 … 199 Reserved –

Tab. 2.19

Page 29: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

2 Function

Festo – CPX-E-SYS-EN – 2017-07 – English 29

Error numbers (error class 1)

Error

number

Meaning Remedy

200 Error in parameterisation (parameter transfer

failed)

� Replace module if switching on and off does

not remedy problem.

201 Address incorrect � Check DIL switch position and correct if

necessary.

202 Initialisation of the protocol chip defective � Replace module if switching on and off does

not remedy problem.

203 Reserved –

204 Invalid switch position � Check DIL switch position and correct if

necessary.

205 … 253 Reserved –

254 Undervoltage of electronics and sensors � Eliminate undervoltage.

255 Unknown error –

Tab. 2.20

Page 30: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

3 Parameterisation

30 Festo – CPX-E-SYS-EN – 2017-07 – English

3 Parameterisation

With the aid of parameterisation, the behaviour of the system CPX-E or the behaviour of individual modules and

channels can be adapted to the particular application. Parameterisation can be performed using suitable software

from Festo or using the higher-order controller. The parameters are preset at the factory.

The parameterisation options depend on the bus module or controller used � Description of the

respective bus module/controller.

3.1 Parameterisation using Festo software

Suitable software for parameterisation can be found on the Festo Support Portal � www.festo.com/sp.

Information on using the software can be found in the integrated Help function.

3.2 Parameterisation using the higher-order controller

There are various options for parameterisation of the system CPX-E using the higher-order controller � Tab. 3.1.

Parameterisation options Description/benefits

Interface module or

scanner/master

Parameterisation can be ensured e.g. in the start-up phase or after network

interruptions.

User program in the higher-order

controller

The parameters can be modified during run-time.

Network-specific configurators Parameters can be modified during the commissioning phase or during the

troubleshooting.

Tab. 3.1

3.3 Types of parameters

A distinction is made between the following types of parameters:

Parameter type Description Overview of

parameters

System parameters Influence the behaviour of the complete system CPX-E. � Tab. 3.3

Module parameters

Module-specific Influence the behaviour of a particular module. � Tab. 3.4

Channel-specific Influence the behaviour of a particular channel.

Diagnostic memory parameters Influence the mode of operation of the internal diagnostic

memory.

� Tab. 3.5

Tab. 3.2

Page 31: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

3 Parameterisation

Festo – CPX-E-SYS-EN – 2017-07 – English 31

System parameters Brief description

Diagnostics and monitoring for:

– Short circuit/overload

– Undervoltage at outputs

Switches monitoring of short circuit/ overload and undervoltage for the entire

system CPX-E on or off.

Signal status when there is a

malfunction (Fail-safe parameter)

Defines the status which digital output signals are to assume in the event of

communication errors on the network.

Signal status in Idle mode1) Defines the status which digital output signals are to assume when switching

to Idle status.

Force signal status

(Force parameter)

Manipulation of signal statuses separate from actual operating conditions

and independent of the higher-order controller.

System start Specifies the start-up behaviour of the system CPX-E.

Analogue process value

representation (data format)2)

Switches the data format for displaying analogue process values (I/O signals).

1) This function is only relevant for certain network protocols � Description for the respective bus module.

2) Special parameter, only available on certain bus modules

Tab. 3.3

Module parameters Brief description

Module-specific

Diagnostics and monitoring for:

– Short circuit/overload

– Undervoltage

– Wire break

Switches monitoring of short circuit/overload and undervoltage on the

module on or off.

Behaviour after:

– Short circuit/overload

– Wire break

Specifies, after a short circuit/overload or wire break, whether the power is to

remain switched off or whether it is to be switched on again automatically.

Input debounce time Serves for trouble-free recognition of digital input signals.

Signal extension time Serves for recognising short signals.

Data format of analogue values � Description for the respective analogue module

Channel-specific

Signal extension Serves for recognising short signals.

Monitoring of wire break Serves for recognising connection errors.

Fault mode Defines the status that the relevant channel is to assume in the event of

communication errors on the network.Fault state

Idle mode1) Defines the status which digital output signals are to assume when the Idle

function is accessed.Idle state1)

Force mode Actual signals are replaced in the process image by the Force settings.

Force state

1) This function is only relevant for certain network protocols � Description for the respective bus module.

Tab. 3.4

Diagnostic memory parameters Brief description

Entries, saved retentively Specifies whether the contents of the diagnostic memory are to be retained

after the power supply is switched on again or whether they are to be deleted.

Diagnostic memory filters:

– Run/stop filter 1 + 2

– Error end filter

– Error number filter

– Module/channel filter

The diagnostic memory filters can be used to suppress the recording of certain

error messages, and to control both the start and stop of the error recording.

Tab. 3.5

Page 32: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

3 Parameterisation

32 Festo – CPX-E-SYS-EN – 2017-07 – English

3.4 Parameters and data for the system CPX-E

3.4.1 Overview

Parameters Description

System parameters Specify global system functions for the entire system, e.g.:

– Diagnostic monitoring

– System start

Module parameters Specify module-specific and channel-specific functions for the respective

module, e.g.:

– Input debounce time

– Signal extension time

Diagnostic memory parameters Specify the mode of operation of the diagnostic memory

Tab. 3.6

Data Description

System diagnostic data Global information about the system status

(e.g. error number, common diagnostic message)

Module diagnostic data Information on locating errors (e.g. error number, number of the first faulty

channel etc.)

Diagnostic memory data Entries in the diagnostic memory (maximum 40)

System data Information on global system settings

Module data Serial number, revision code and module code of the modules used

Tab. 3.7

3.4.2 Function numbers

Function number1) Description Data/parameters Detailed

information

0 Expansion System data � Tab. 3.44

Force mode � Tab. 3.45

System start � Tab. 3.46

1 Fail safe � Tab. 3.47

Idle mode � Tab. 3.48

2 System monitoring � Tab. 3.49

16 + 16 m + 0 Module code Module data � Tab. 3.50

16 + 16 m + 13 Revision code � Tab. 3.51

784 + 4m + 0 … 3 Serial number � Tab. 3.52

1936 Status bits System diagnostic data � Tab. 3.37

1937 Module number and diagnostic status � Tab. 3.38

1938 Error number � Tab. 3.39

2008 + 4 m + 0 Number of the first faulty channel Module diagnostic data � Tab. 3.40

2008 + 4 m + 1 Module error number � Tab. 3.41

2008 + 4 m + 2 Info 2 (reserved) � Tab. 3.42

2008 + 4 m + 3 Info 3 (reserved) � Tab. 3.43

3480 Entries saved retentively with Power On Diagnostic memory parameters � Tab. 3.24

Run/stop filter 1 � Tab. 3.25

1) m = module number (counting from left to right, beginning with 0)

2) d = Diagnostic event

3) Access is protocol-specific � Description of bus module

4) Only relevant for certain network protocols � Description of bus module

Page 33: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

3 Parameterisation

Festo – CPX-E-SYS-EN – 2017-07 – English 33

Function number1) Detailed

information

Data/parametersDescription

3482 Number of entries in the diagnostic

memory

Diagnostic memory data � Tab. 3.33

3483 Overflow � Tab. 3.34

Status � Tab. 3.35

3484 Run/stop filter 2 Diagnostic memory parameters � Tab. 3.26

Error end filter � Tab. 3.27

Error number filter � Tab. 3.28

Module/channel filter � Tab. 3.29

3485 Module number � Tab. 3.30

3486 Channel number � Tab. 3.31

3487 Error number � Tab. 3.32

3488 + 10d + 0 … 9 Diagnostic memory Diagnostic memory data � Tab. 3.36

4401 Monitoring System parameters � Tab. 3.9

4402 Fail safe � Tab. 3.10

Force mode � Tab. 3.11

Idle mode � Tab. 3.12

System start � Tab. 3.13

Analogue process value representation � Tab. 3.14

4828 + 64 m + 0 Module monitoring Module parameters

(module-specific)

� Tab. 3.15

4828 + 64 m + 1 Behaviour after short circuit/overload � Tab. 3.16

Input debounce time � Tab. 3.17

Signal extension time � Tab. 3.18

4828 + 64 m + 3 Data format for analogue value of

inputs

� Tab. 3.19

Data format for analogue value of

outputs

4828 + 64 m + 6 Signal extension channel x Module parameters

(channel-specific)

� Tab. 3.203) Fail safe channel x � Tab. 3.21

Idle mode channel x � Tab. 3.22

Forcen channel x � Tab. 3.234) Number of input bytes (Rx size) System data

(network-specific)

Number of output bytes (Tx size) –

1) m = module number (counting from left to right, beginning with 0)

2) d = Diagnostic event

3) Access is protocol-specific � Description of bus module

4) Only relevant for certain network protocols � Description of bus module

Tab. 3.8

Page 34: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

3 Parameterisation

34 Festo – CPX-E-SYS-EN – 2017-07 – English

3.5 System parameters

3.5.1 Monitoring

System parameter – Monitoring

Activates or deactivates (suppresses) monitoring of short

circuit/overload and undervoltage for the entire system.1)

If monitoring is active, an error reported by the module will be:

– Sent to the higher-order master

– Entered in the diagnostic memory3)

– Entered in the module diagnostic data and, if applicable, in the

status bits

– Indicated by the red common error LED on the module

Selection via parameters

F no.2) Bit

4401 7 6 5 4 3 2 1 0

Short circuit/overload in sensor supply (SCS) 01

Short circuit/overload at the outputs (SCO) 01

Undervoltage at outputs (UOUT) 01

1) Values: 1 = active (presetting); 0 = inactive

2) Function number

3) Dependent on filter settings

Tab. 3.9

Monitoring can also be set separately for each module using the module parameter “Module monitoring”

� Tab. 3.15. The mode of operation of the channel error LED remains unaltered.

3.5.2 Fail safe

System parameter – Fail safe

Specifies which signal status the outputs are to assume in the event of

communication errors in the network, e.g. in the event of network

interruption, failure of the higher-order controller, communication stop.

Selection via parameters

F no.1) Bit

4402 7 6 5 4 3 2 1 0

Reset all outputs (presetting) 0 0

Hold last state (retain signal status) 0 1

Assume Fault mode 1 0

1) Function number

Tab. 3.10

When changing from “Assume Fault mode” to “Reset all outputs” or to “Hold last state”, the

channel-orientated Fail-safe settings (module parameters “Fault mode” and “Fault state”) are reset

automatically for safety reasons in order to avoid undesired signal statuses.

The Fault-mode status is set using the channel-specific module parameters � Tab. 3.21.

3.5.3 Force mode

System parameter – Force mode

Specifies for the entire system whether the Forcen function is disabled

or enabled.

Selection via parameters

F no.1) Bit

4402 7 6 5 4 3 2 1 0

Force mode disabled (presetting) 0 0

Force mode enabled (retain signal status) 0 1

1) Function number

Tab. 3.11

Page 35: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

3 Parameterisation

Festo – CPX-E-SYS-EN – 2017-07 – English 35

By changing this parameter, the channel-orientated Force settings (module parameters “Force mode” and

“Force state”) are reset automatically for safety reasons in the following cases in order to avoid undesired

signal statuses:

– Change using Festo software: when switching from “enabled” to “disabled”

– Change via the network: When changed from “disabled” to “enabled”

Force signals have priority over Fail-safe signals.

3.5.4 Idle mode

System parameter – Idle mode1)

Establishes which signal status outputs are to assume when the system

switches to Idle status.

Selection via parameters

F no.2) Bit

4402 7 6 5 4 3 2 1 0

Reset all outputs (presetting) 0 0

Hold last state (retain signal status) 0 1

Assume Idle mode 1 0

1) This parameter is only relevant for certain network protocols � Description for the respective bus module.

2) Function number

Tab. 3.12

When changing from “Assume Idle mode” to “Reset all outputs” or to “Hold last state”, the

channel-orientated Idle-mode settings (module parameters “Idle mode” and “Idle state”) are reset

automatically for safety reasons in order to avoid undesired signal statuses.

3.5.5 System start

System parameter – system start

Specifies the starting behaviour of the system and saves all current

parameter settings and the current expansion.

Selection via parameters

F no.1) Bit

4402 7 6 5 4 3 2 1 0

System start with default parameterisation (factory setting) and current CPX

expansion; external parameterisation is possible (presetting)

0

System start with saved parameterisation and saved CPX expansion; parameters

and expansion are saved to retentive memory; external parameterisation is

blocked; the Modify LED (M) on the bus module lights up

1

1) Function number

Tab. 3.13

If bit 6 is set to 1, the current parameter settings will be write-protected and the current expansion will be

saved, except for bit 6 itself and the module parameters “Forcen channel X”.

Recommendation: “System start with default parameterisation and current CPX expansion”. The desired

parameterisation can then be created in the start-up phase or after a network interruption, e.g. by the

interface module or the scanner/master (depending on the network used). If “System start with default

parameterisation and current CPX expansion” is active, the factory settings for all module and system

parameters will be applied after switching on and off.

Page 36: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

3 Parameterisation

36 Festo – CPX-E-SYS-EN – 2017-07 – English

3.5.6 Analogue process value representation

System parameter – Analogue process value recommendation1)

Switches the data format or byte sequence for displaying analogue

process values.

Selection via parameters

F no.2) Bit

4402 7 6 5 4 3 2 1 0

INTEL byte sequence (presetting):

Least significant bit on the left, most significant bit on the right (LSB-MSB)3)

0

MOTOROLA byte sequence:

Most significant bit on the left, least significant bit on the right (MSB-LSB)3)

1

1) This parameter is only relevant for certain bus modules � Description for the respective bus module.

2) Function number

3) LSB = Least Significant Bit; MSB = Most Significant Bit

Tab. 3.14

Page 37: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

3 Parameterisation

Festo – CPX-E-SYS-EN – 2017-07 – English 37

3.6 Module parameters (module-specific)

Module parameters refer to module-specific or channel-specific functions. 64 bytes are available for parameters in

each module.

You can find detailed information on the module parameters supported by the module used, as well as

parameter values and their presettings, in the description for the relevant module.

3.6.1 Module monitoring

Module parameter – Module monitoring

Monitoring of the possible errors can be activated or deactivated

(suppressed) independently for each module.1)

If monitoring is active, an error will be:

– Sent to the bus module

– Indicated by the common error LED on the module

Selection via parameters

F no.2) Bit

4828 7 6 5 4 3 2 1 0

+ 64m

Short circuit/overload in sensor supply (SCS) + 0 01

Short circuit/overload at the outputs (SCO) 01

Undervoltage at outputs (UOUT) 01

Monitoring of parameterisation errors 01

1) Values: 1 = active (presetting); 0 = inactive

2) Function number; m = module number (counting from left to right, beginning with 0)

Tab. 3.15

Monitoring can also be set for the entire system via the “Monitoring" system parameter � Tab. 3.9.

3.6.2 Behaviour after short circuit/overload

Module parameter – Behaviour after short circuit/overload

Specifies, after a short circuit/overload in the sensor supply or the

outputs, whether the relevant voltage is to remain switched off or

whether it is to be switched on again automatically.1)

Selection via parameters

F no.2) Bit

4828 7 6 5 4 3 2 1 0

+ 64m

Short circuit/overload in sensor supply (SCS) + 1 01

Short circuit/overload at the outputs (SCO) 01

Short circuit/overload at the analogue signal 01

1) Values: 1 = Switch voltage back on; 0 = Voltage remains switched off

2) Function number; m = module number (counting from left to right, beginning with 0)

Tab. 3.16

With the setting “Voltage remains switched off ”, you must switch the power off and back on or set/reset

the relevant signals to recover the voltage.

Page 38: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

3 Parameterisation

38 Festo – CPX-E-SYS-EN – 2017-07 – English

3.6.3 Input debounce time

Module parameter – Input debounce time

Specifies when a change of edge of the sensor signal on the relevant

module is to be accepted as a logical input signal.

Selection via parameters

F no.1) Bit

4828 7 6 5 4 3 2 1 0

+ 64m

Input debounce time 0.1 ms + 1 0 0

3 ms (typical presetting) 0 1

10 ms 1 0

20 ms 1 1

1) Function number; m = module number (counting from left to right, beginning with 0)

Tab. 3.17

You can find more information on this parameter in the description for the respective module.

3.6.4 Signal extension time

Module parameter – Signal extension time

Specifies the signal extension time for the respective module.

Signal statuses accepted as logical input signals usually remain valid at

least until the specified signal extension time (minimum signal duration)

has expired. Changes of edge within the extension time are ignored.

Selection via parameters

F no.1) Bit

4828 7 6 5 4 3 2 1 0

+ 64m

Signal extension time 0.5 ms + 1 0 0

15 ms (typical presetting) 0 1

50 ms 1 0

100 ms 1 1

1) Function number; m = module number (counting from left to right, beginning with 0)

Tab. 3.18

The signal extension time can be activated channel-by-channel � Tab. 3.20. You can find more

information on this parameter in the description for the respective module.

3.6.5 Data format for analogue value of inputs/outputs

Module parameter – Data format for analogue value of inputs/outputs

Specifies the data format for internal processing of the relevant

analogue values.1)

The choice of data format depends on the network or master used and

simplifies evaluation of the analogue values.

Selection via parameters

F no.2) Bit

4828 7 6 5 4 3 2 1 0

+ 64m

Data format for analogue value of inputs + 3 01

01

Data format for analogue value of outputs 01

01

1) Values � Description for the respective module

2) Function number; m = module number (counting from left to right, beginning with 0)

Tab. 3.19

Page 39: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

3 Parameterisation

Festo – CPX-E-SYS-EN – 2017-07 – English 39

3.7 Module parameters (channel-specific)

3.7.1 Signal extension channel x

Module parameter (channel-specific) – Signal extension channel x

Specifies whether the signal extension for the relevant channel is to be

enabled or disabled.1)

The signal extension time can be specified separately for each module

� Tab. 3.18.

Selection via parameters

F no.2) Bit

4828 7 6 5 4 3 2 1 0

+ 64m

Signal extension Channel 0 + 6 01

Channel 1 01

Channel 2 01

Channel 3 01

Channel 4 01

Channel 5 01

Channel 6 01

Channel 7 01

1) Values: 1 = enabled; 0 = disabled

2) Function number; m = module number (counting from left to right, beginning with 0)

Tab. 3.20

3.7.2 Fail safe channel x

Module parameters (channel-specific) – Fail safechannel x

The Fail-safe parameterisation can be used to specify the signal status

which the outputs are to assume in the event of communication errors

� 2.2.4 Signal status when there is a fault (Fail safe).

Selection via parameters

Fault mode channel x Hold last state Access is via protocol-specific functions

� Description for the bus module.Fault state (presetting)

Fault state channel x Reset output (presetting)

Set output

Tab. 3.21

3.7.3 Idle mode channel x

Module parameters (channel-specific) – Idle modechannel x1)

The Idle-mode parameterisation can be used to specify the signal status

which the outputs are to assume when switching to Idle status

(� 2.2.5 Signal status in Idle status (Idle mode)).

Selection via parameters

Idle mode channel x Hold last state Access is via protocol-specific functions

� Description for the bus module.Idle state (presetting)

Idle state channel x Reset output (presetting)

Set output

1) Not supported by all bus modules

Tab. 3.22

Page 40: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

3 Parameterisation

40 Festo – CPX-E-SYS-EN – 2017-07 – English

3.7.4 Forcen channel x

Module parameters (channel-specific) – Forcenchannel x

The Forcen function permits the manipulation of signal statuses

independently of the actual operating conditions � 2.2.3 Forcen.

Selection via parameters

Force mode inputs, channel x Disabled (presetting) Access is via protocol-specific functions

� Description for the bus module.Force state

Force state inputs, channel x Set signal

Reset signal (presetting)

Force mode outputs, channel x Disabled (presetting)

Force state

Force state outputs, channel x Set signal

Reset signal (presetting)

Tab. 3.23

Page 41: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

3 Parameterisation

Festo – CPX-E-SYS-EN – 2017-07 – English 41

3.8 Diagnostic memory parameters (Trace parameters)

The mode of operation of the diagnostic memory can be adapted to individual requirements using the diagnostic

memory parameters. The diagnostic memory parameters retain their last setting after the power supply has been

switched off and on again and are saved so as to be protected against mains failure.

You can find more information about the mode of operation of the diagnostic memory in the Function

chapter � 2.3.4 Diagnostic memory.

3.8.1 Entries saved retentively with Power On

Diagnostic memory parameter – Entries saved retentively with Power On

Specifies whether the contents of the diagnostic memory are to be

retained after the power supply is switched on again or whether they are

to be deleted.1)

The diagnostic memory will be deleted if the mode is changed.

Selection via parameters

F no.2) Bit

3480 7 6 5 4 3 2 1 0

Entries saved retentively with renewed switch-on 01

1) Values: 1 = active (presetting); 0 = inactive

2) Function number

Tab. 3.24

3.8.2 Run/Stop filter 1

Diagnostic memory parameter – Run/Stop filter 1

Diagnostic memory filter which is used to specify whether the first

40 errors or the last 40 errors are to be saved.

The diagnostic memory will be deleted if the mode is changed.

Selection via parameters

F no.1) Bit

3480 7 6 5 4 3 2 1 0

Save the first 40 entries; stop after 40 entries 0

Save the last 40 entries; overwrite old entries (presetting) 1

1) Function number

Tab. 3.25

3.8.3 Run/Stop filter 2

Diagnostic memory parameter – Run/Stop filter 2

Diagnostic memory filter which is used to determine when the recording

of errors is to be started or stopped.

MN = module number, CN = channel number, FN = error number1)

Selection via parameters

F no.2) Bit

3484 7 6 5 4 3 2 1 0

Run/Stop filter 2 inactive (presetting) 0 0 0

Record up to the defined FN 0 0 1

Record up to the defined FN + MN 0 1 0

Record up to the defined FN + MN + CN 0 1 1

Record from the defined FN 1 0 0

Record from the defined FN + MN 1 0 1

Record from the defined FN + MN + CN 1 1 0

Reserved 1 1 1

1) The appropriate numbers are specified by means of the diagnostic memory parameters “Module number” (� Tab. 3.30), “Channel number”

(� Tab. 3.31) and “Error number” (� Tab. 3.32).

2) Function number

Tab. 3.26

Page 42: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

3 Parameterisation

42 Festo – CPX-E-SYS-EN – 2017-07 – English

3.8.4 Error end filter

Diagnostic memory parameters – Error end filter

Diagnostic memory filter which is used to specify whether outgoing

errors are to be recorded or not.

Selection via parameters

F no.1) Bit

3484 7 6 5 4 3 2 1 0

Record outgoing errors (end of error); filter inactive (presetting) 0

Do not record outgoing errors (end of error); filter active 1

1) Function number

Tab. 3.27

By recording the outgoing errors it can be determined how long an error has existed. Incoming and

outgoing errors each represent one entry. With outgoing errors, the error number “0” is entered.

A�maximum of 40 entries are saved in total.

3.8.5 Error number filter

Diagnostic memory parameter – Error number filter

This diagnostic memory filter can be used to suppress recording of

a�desired error message or to record a desired error message only.1)

Selection via parameters

F no.2) Bit

3484 7 6 5 4 3 2 1 0

Error number filter inactive (presetting) 0 0

Record only defined error number 0 1

Do not record defined error number 1 0

Reserved 1 1

1) The relevant numbers are specified by means of the diagnostic memory parameter “Error number” (� Tab. 3.32).

2) Function number

Tab. 3.28

3.8.6 Module/channel filter

Diagnostic memory parameter – Module/channel filter

This diagnostic memory filter can be used to suppress the recording of

errors of other modules or channels so that errors in a particular module

or channel can be analysed.1)

Selection via parameters

F no.2) Bit

3484 7 6 5 4 3 2 1 0

Module/channel filter inactive (presetting) 0 0

Record the error number of a given module only 0 1

Record the error number of a given channel only 1 0

Reserved 1 1

1) The relevant numbers are specified by means of the diagnostic memory parameters “Module number” (� Tab. 3.30) and “Channel number”

(� Tab. 3.31).

2) Function number

Tab. 3.29

Page 43: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

3 Parameterisation

Festo – CPX-E-SYS-EN – 2017-07 – English 43

3.8.7 Module number

Diagnostic memory parameter – Module number

Module number for the diagnostic memory filter

Only effective if an appropriate diagnostic memory filter is active.

Selection via parameters

F no.1) Bit

3485 7 6 5 4 3 2 1 0

Module number 0 ... 47 (0 = presetting) 01

01

01

01

01

01

1) Function number

Tab. 3.30

3.8.8 Channel number

Diagnostic memory parameter – Channel number

Channel number for the diagnostic memory filter

Only effective if an appropriate diagnostic memory filter is active.

Selection via parameters

F no.1) Bit

3486 7 6 5 4 3 2 1 0

Channel number 0 ... 63 (0 = presetting) 01

01

01

01

01

01

1) Function number

Tab. 3.31

3.8.9 Error number

Diagnostic memory parameter – Error number

Error number for the diagnostic memory filter

Only effective if an appropriate diagnostic memory filter is active.

Selection via parameters

F no.1) Bit

3487 7 6 5 4 3 2 1 0

Error number 0 ... 255 (0 = presetting) 01

01

01

01

01

01

01

01

1) Function number

Tab. 3.32

Page 44: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

3 Parameterisation

44 Festo – CPX-E-SYS-EN – 2017-07 – English

3.9 Diagnostic memory data

3.9.1 Number of entries in the diagnostic memory

Diagnostic memory data – Number of entries in the diagnostic memory

Specifies the number of entries in the diagnostic memory.

Can be used as a loop counter if the complete diagnostic memory is to

be read out by PLC program.

Selection via parameters

F no. Bit

34821) 7 6 5 4 3 2 1 0

Number of entries in the diagnostic memory (0 ... 40) 01

01

01

01

01

01

1) Function number

Tab. 3.33

3.9.2 Overflow

Diagnostic memory data – Overflow

Indicates whether the diagnostic memory has overflowed. Overflow

means that more than 40 errors have occurred.

The overflow is displayed when the first 40 errors are recorded as well as

when the last 40 errors are recorded.

Selection via parameters

F no.1) Bit

3483 7 6 5 4 3 2 1 0

No overflow 0

Overflow 1

1) Function number

Tab. 3.34

3.9.3 Status

Diagnostic memory data – Status

Indicates whether error recording is active or inactive.

Error recording can be stopped and started with the Run/Stop filters.

Selection via parameters

F no.1) Bit

3483 7 6 5 4 3 2 1 0

Recording active 0

Recording inactive 1

1) Function number

Tab. 3.35

Page 45: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

3 Parameterisation

Festo – CPX-E-SYS-EN – 2017-07 – English 45

3.9.4 Diagnostic memory

Diagnostic memory data – Diagnostic memory (10 bytes per entry, 40 entries)

The diagnostic memory contains a maximum of 40 diagnostic entries,

with each diagnostic entry consisting of 10 bytes.

The first 5 bytes contain information on the time of the error and the

last 5 byes contain information about the error.

Selection via parameters

F no.1) Bit

3488 7 6 5 4 3 2 1 0

Byte Description Value + 10d

1 Days

Number of days2)

0 … 255 + 0 01

01

01

01

01

01

01

01

2 Hours

Number of hours2)

0 … 23 + 1 01

01

01

01

01

3 Minutes

Number of minutes2)

0 … 59 + 2 01

01

01

01

01

01

4 Seconds

Number of seconds2)

0 … 59 + 3 01

01

01

01

01

01

5 Milliseconds

Number of 10 milliseconds2)

Bit 7 is additionally set if it is the first entry

after a switch-on.

0 … 99

or

128 … 227

+ 4 01

01

01

01

01

01

01

01

6 Module code3)

Module code of the module which reported

the error

0 … 255 + 5 01

01

01

01

01

01

01

01

7 Module position

Module number of the module which

reported the error; 63 = error not

module-related

0 … 47;

63

+ 6 01

01

01

01

01

01

8 Channel number3)

Number of first faulty output channel

(bits�0 ... 5; values: 0 ... 63)

0 … 255 + 7 0 0 01

01

01

01

01

01

Number of first faulty input channel

(bits�0 ... 5; values: 0 ... 63)

1 0 01

01

01

01

01

01

Module error (bits 0 ... 5; values: 0 ... 63) 0 1 01

01

01

01

01

01

Reserved 1 1 01

01

01

01

01

01

9 Error number

(possible error messages � 2.3.5)

0 … 255 + 8 01

01

01

01

01

01

01

01

10 Subsequent channels

Number of subsequent channels with the

same error

0 … 63 + 9 01

01

01

01

01

01

1) Function number; d = Diagnostic event = 0 … 39; current diagnostic event = 0

2) Measured from the moment the power supply is switched on

3) If the error number = 0, the content of these bytes is also 0. If the error number lies between 128 ... 199 (error class 3), the content of these

bytes is not relevant (servicing required).

Tab. 3.36

Page 46: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

3 Parameterisation

46 Festo – CPX-E-SYS-EN – 2017-07 – English

3.10 System diagnostic data

3.10.1 Status bits

System diagnostic data – Status bits

The 8 status bits display common diagnostic messages.1)

– Bit 0 … 3: source of error

– Bit 4 … 7: type of error

Selection via parameters

F no.2) Bit

1936 7 6 5 4 3 2 1 0

Source of error Valve 01

Outlet 01

Input 01

Analogue/technology module 01

Type of error Undervoltage 01

Short circuit/overload 01

Wire break 01

Other error 01

1) Values: 1 = error present; 0 = no error

2) Function number

Tab. 3.37

3.10.2 Module number and diagnostic status

System diagnostic data – Module number and diagnostic status

Indicates whether there are diagnostic data and contains, where

applicable, the number of the first module on which an error has

occurred.1)

With the aid of the module number of the faulty module, you can

ascertain the function number of the relevant diagnostic data.

Selection via parameters

F no. Bit

1937 7 6 5 4 3 2 1 0

Module number of the first faulty module (0 ... 47) 01

01

01

01

01

01

Diagnostic status 01

1) Values: 1 = Diagnostic data available; 0 = no diagnostic data

Tab. 3.38

3.10.3 Error number

System diagnostic data – Error number

Current error number (possible error messages � 2.3.5)

Function number 1937 indicates whether diagnostic data are available

� Tab. 3.38.

Selection via parameters

F no.1) Bit

1938 7 6 5 4 3 2 1 0

Error number (0 … 255) 01

01

01

01

01

01

01

01

1) Function number

Tab. 3.39

Page 47: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

3 Parameterisation

Festo – CPX-E-SYS-EN – 2017-07 – English 47

3.11 Module diagnostic data

The module diagnostic data are attributed to the function numbers 2008 … 2199. A total of 4 items of diagnostic

information are available in 4 consecutive bytes for each module.

The function number of the diagnostic data for the faulty module is therefore calculated as follows:

– Function number = 2008 + (4 x module number) + information number

The module number of the first faulty module can be determined with the aid of the system diagnostic

data (function number 1937) � Tab. 3.38.

3.11.1 Number of the first faulty channel

Module diagnostic data – Number of the first faulty channel

Indicates the number of the first faulty channel. Selection via parameters

F no.1) Bit

2008 7 6 5 4 3 2 1 0

+ 4m

Channel number (0 … 63) + 0 01

01

01

01

01

01

Number of first faulty output channel 0 0

Number of first faulty input channel 1 0

Module error 0 1

Reserved 1 1

1) Function number; m = module number (counting from left to right, beginning with 0)

Tab. 3.40

3.11.2 Error number

Module diagnostic data – Error number

Error number (possible error messages � 2.3.5) Selection via parameters

F no.1) Bit

2008 7 6 5 4 3 2 1 0

+ 4m

Error number (0 … 255) + 1 01

01

01

01

01

01

01

01

1) Function number; m = module number (counting from left to right, beginning with 0)

Tab. 3.41

3.11.3 Info 2 and 3 (reserved)

Module diagnostic data – Info 2 (reserved)

Info 2 (reserved) Selection via parameters

F no.1) Bit

2008 7 6 5 4 3 2 1 0

+ 4m

Reserved + 2 01

01

01

01

01

01

01

01

1) Function number; m = module number (counting from left to right, beginning with 0)

Tab. 3.42

Module diagnostic data – Info 3 (reserved)

Info 3 (reserved) Selection via parameters

F no.1) Bit

2008 7 6 5 4 3 2 1 0

+ 4m

Reserved + 3 01

01

01

01

01

01

01

01

1) Function number; m = module number (counting from left to right, beginning with 0)

Tab. 3.43

Page 48: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

3 Parameterisation

48 Festo – CPX-E-SYS-EN – 2017-07 – English

3.12 System data

System data provide information about global system settings and the system status. The system data are not

saved to retentive memory and are lost on switching off.

3.12.1 Expansion

System data – Expansion

Indicates whether the current expansion of the system corresponds to

the saved expansion.

See also system parameter “System start” � Tab. 3.13.

Selection via parameters

F no.1) Bit

0 7 6 5 4 3 2 1 0

Uniform expansion 0

Non-uniform expansion 1

1) Function number

Tab. 3.44

3.12.2 Force mode

System data – Force mode

Indicates whether Forcen is disabled or enabled.

See also system parameter “Force mode” � Tab. 3.11.

Selection via parameters

F no.1) Bit

0 7 6 5 4 3 2 1 0

Forcen disabled 0

Forcen enabled 1

1) Function number

Tab. 3.45

3.12.3 System start

System data – System start

Indicates how the system start is to be carried out.

See also system parameter “System start” � Tab. 3.13.

Selection via parameters

F no.1) Bit

0 7 6 5 4 3 2 1 0

System start with default parameterisation (factory setting) and current expansion 0

System start with saved parameterisation and saved equipment status 1

1) Function number

Tab. 3.46

3.12.4 Fail safe

System data – Fail safe

Indicates whether Fail safe is active or inactive. Selection via parameters

F no.1) Bit

1 7 6 5 4 3 2 1 0

Reset all outputs 0 0

Hold last state (retain signal status) 0 1

Assume Fault mode 1 1

1) Function number

Tab. 3.47

Page 49: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

3 Parameterisation

Festo – CPX-E-SYS-EN – 2017-07 – English 49

3.12.5 Idle mode

System data – Idle mode

Indicates whether Idle mode is active or inactive. Selection via parameters

F no.1) Bit

1 7 6 5 4 3 2 1 0

Reset all outputs 0 0

Hold last state (retain signal status) 0 1

Assume Idle mode 1 1

1) Function number

Tab. 3.48

3.12.6 System monitoring

System data – System monitoring

Indicates whether monitoring of short-circuit/overload and

undervoltage is active or inactive.1)

See also system parameter “Monitoring” � Tab. 3.9.

Selection via parameters

F no.2) Bit

2 7 6 5 4 3 2 1 0

Short circuit/overload in sensor supply (SCS) 01

Short circuit/overload at the outputs (SCO) 01

Undervoltage at outputs (UOUT) 01

1) Values: 1 = active; 0 = inactive

2) Function number

Tab. 3.49

Page 50: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

3 Parameterisation

50 Festo – CPX-E-SYS-EN – 2017-07 – English

3.13 Module data

Module data contain information appropriate to the respective modules and are thus used to identify modules.

3.13.1 Module code

Module data – Module code

Indicates the module code of the module. You can find the module codes

in the corresponding module documentation.

Selection via parameters

F no.1) Bit

16 7 6 5 4 3 2 1 0

+ 16m

Reserved (0)

Module code (1 … 245)

Reserved (246 … 255)

+ 0 01

01

01

01

01

01

01

01

1) Function number; m = module number (counting from left to right, beginning with 0)

Tab. 3.50

3.13.2 Revision code

Module data – Revision code

Indicates the module version (� Product labelling). Selection via parameters

F no.1) Bit

16 7 6 5 4 3 2 1 0

+ 16m

Revision code (0 … 255) + 13 01

01

01

01

01

01

01

01

1) Function number; m = module number (counting from left to right, beginning with 0)

Tab. 3.51

3.13.3 Serial number

Module data – Serial number

Indicates the serial number of the module (in hexadecimal). Selection via parameters

F no.1) Bit

784 7 6 5 4 3 2 1 0

+ 4m

8th figure + 0 01

01

01

01

7th figure 01

01

01

01

6th figure + 1 01

01

01

01

5th figure 01

01

01

01

4th figure + 2 01

01

01

01

3rd figure 01

01

01

01

2nd figure + 3 01

01

01

01

1st figure 01

01

01

01

1) Function number; m = module number (counting from left to right, beginning with 0)

Tab. 3.52

Page 51: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

A Technical Data

Festo – CPX-E-SYS-EN – 2017-07 – English 51

A Technical Data

General

Feature Specification/value

Mounting position Vertical/horizontal

Ambient temperature [°C] –5 … +60 (–5 … +50)1)

Storage temperature [°C] –20 … +70

Air humidity (non-condensing) [%] 0 … 95

Max. permissible setup altitude above sea level [m] 2000

Max. number of modules per system CPX-E,

including the bus module or controller

11

Address volume of the inputs/outputs [byte] 64/64 (maximum)

Degree of protection in accordance with EN 60529 IP20

Protection against electric shock (protection against

direct and indirect contact to IEC 60204-1)

Through the use of PELV circuits

(protected�extra-low voltage)

CE marking (see declaration of conformity)

� www.festo.com

To EU EMC Directive

Explosion prevention and protection (IECEx/ATEX) � Special documentation on ATEX

Certification RCM compliance mark

Contamination level 2

Vibration and shock resistance in accordance with EN 600682)

Vibration (part 2-6) H-rail SL1

Shock (part 2 - 27) H-rail SL1

Continuous shock (part 2-27) H-rail SL1

1) For horizontal mounting position

2) Explanation of the severity levels � Tab. A.2 … Tab. A.4

Tab. A.1

Vibration load

Frequency range [Hz] Acceleration [m/s2] Deflection [mm]

SL1 SL2 SL1 SL2 SL1 SL2

2 … 8 2 … 8 – – ±3.5 ±3.5

8 … 27 8 … 27 10 10 – –

27 … 58 27 … 60 – – ±0.15 ±0.35

58 … 160 60 … 160 20 50 – –

160 … 200 160 … 200 10 10 – –

Tab. A.2

Shock load

Acceleration [m/s2] Duration [ms] Shocks per direction

SL1 SL2 SL1 SL2 SL1 SL2

±150 ±300 11 11 5 5

Tab. A.3

Continuous shock load

Acceleration [m/s2] Duration [ms] Shocks per direction

±150 6 1000

Tab. A.4

Page 52: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

A Technical Data

52 Festo – CPX-E-SYS-EN – 2017-07 – English

Power supply

Feature Specification/value

Operating voltage supply UEL/SEN

Nominal operating voltage [V DC] 24 ± 25 %

Trigger level, undervoltage identification [V DC] 17.5

Max. current load of terminal strip [A] 8

Mains buffering time Module-dependent1)

Load voltage supply UOUT

Nominal operating voltage [V DC] 24 ± 25 %2)

Trigger level, undervoltage identification Module-dependent1)

Max. current load of terminal strip [A] 8

1) � Documentation of the modules

2) The indication of tolerance deviates in case of some modules.

Tab. A.5

Connection data of the terminal strips

Feature Specification/value

4-pin 6-pin

Conductor cross section

Solid [mm²] 0.14 … 1.5

Flexible [mm²] 0.14 … 2.5 0.14 … 1.5

Flexible with wire end sleeve

Without plastic sleeve [mm²] 0.14 … 1.5

With plastic sleeve [mm²] 0.14 … 1.5 0.14 … 1.5

Length of the wire end sleeve without plastic sleeve1)

Conductor cross section 0.14 … 1.0 mm2 [mm] 8 … 10

Conductor cross section 1.5 mm2 [mm] 8 … 10 10

Length of the wire end sleeve with plastic sleeve2)

Conductor cross section 0.14 … 0.34 mm2 [mm] 8 … 10

Conductor cross section 0.5 … 1.0 mm2 [mm] 8 … 10 10

1) In accordance with DIN 46228-1

2) In accordance with DIN 46228-4

Tab. A.6

Page 53: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

B Terminology

Festo – CPX-E-SYS-EN – 2017-07 – English 53

B Terminology

Term/abbreviation Description

Bus module Connects a system CPX-E to the network; transmits control signals to the

connected modules CPX-E and monitors their functionality.

Device description file Protocol-specific file for configuring the bus module in the control software for

the higher-order controller. This contains all the information required to

parameterise the system CPX-E via control software.

DIL switch Switch consisting of several switch elements with which settings can be made

(dual in-line).

I/O Input and output

I/O diagnostic interface Network-independent diagnostic interface at I/O level, which enables access to

the internal data of the system CPX-E.

I/O module Collective term for modules that provide analogue or digital inputs and/or

outputs.

Modules CPX-E Collective term for the various modules which can be incorporated in a

system�CPX-E.

PLC Programmable logic controller

Status bits Internal status information (common diagnostic messages) of the system CPX-E,

provided as input signals via the network.

System CPX-E Complete system consisting of modules CPX-E.

Tab. B.1 Terms and abbreviations

Page 54: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

54 Festo – CPX-E-SYS-EN – 2017-07 – English

Index

A

Abbreviations, 53

Analogue process value representation, 36

B

Behaviour after short circuit/overload, 37

Bus module, 7

C

Channel number, 43

Controller, 8

D

Data, 32

– Diagnostic memory data, 32

– Module data, 32

– Module diagnostic data, 32

– System data, 32

– System diagnostic data, 32

Data format for analogue value of inputs/outputs, 38

Diagnostic memory, 24, 45

Diagnostic memory data, 32, 44

– Diagnostic memory, 45

– Number of entries in the diagnostic memory, 44

– Overflow, 44

– Status, 44

Diagnostic memory parameters, 31, 32, 41

– Channel number, 43

– Entries saved retentively with Power On, 41

– Error end filter, 42

– Error number, 43

– Error number filter, 42

– Module number, 43

– Module/channel filter, 42

– Run/stop filter 1, 41

– Run/stop filter 2, 41

Diagnostics options, 17

– I/O diagnostic interface, 20

– LED indicators, 17

– Status bits, 19

E

Entries saved retentively with Power On, 41

Error classes, 25

Error end filter, 42

Error number, 43, 46, 47

Error number filter, 42

Error numbers, 26

Expansion, 48

F

Fail safe, 34, 48

Fail safe channel x, 39

Force, 12

Force channel x, 40

Force mode, 34, 48

Function example, 6

Function numbers, 32

Further applicable documents, 5

H

H-rail mounting, 9

I

I/O diagnostic interface, 20

Idle mode, 35, 49

Idle mode channel x, 39

Influencing signal statuses

– Fail safe, 11

– Force, 11

– Idle mode, 11

Input debounce time, 38

Input module, 8

L

LED indicators, 17

– Modify [M], 18

– Power load [PL], 18

– Power system [PS], 17

– System failure [SF], 18

Load voltage supply, 10

M

Module code, 50

Module data, 32, 50

– Module code, 50

– Revision code, 50

– Serial number, 50

Module diagnostic data, 32, 47

– Error number, 47

– Number of the first faulty channel, 47

Module monitoring, 37

Module number, 43

Module number and diagnostic status, 46

Module parameters, 31, 32

Module parameters (channel-specific), 39

– Fail safe channel x, 39

– Force channel x, 40

– Idle mode channel x, 39

– Signal extension channel x, 39

Page 55: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the

Festo – CPX-E-SYS-EN – 2017-07 – English 55

Module parameters (module-specific), 37

– Behaviour after short circuit/overload, 37

– Data format for analogue value of inputs/outputs, 38

– Input debounce time, 38

– Module monitoring, 37

– Signal extension time, 38

Module/channel filter, 42

Modules CPX-E, 7

– Bus module, 7

– Controller, 8

– Input module, 8

– Output module, 8

Monitoring, 34

Mounting distances, 9

N

Number of entries in the diagnostic memory, 44

Number of the first faulty channel, 47

O

Operating voltage supply, 10

Output module, 8

Overflow, 44

P

Parameters, 32

– Diagnostic memory parameters, 31, 32

– Module parameters, 31, 32

– System parameters, 31, 32

Power supply, 10

– Load voltage, 10

– Operating voltage, 10

Power supply concept, 10

R

Revision code, 50

Rules for set-up, 9

Run/stop filter 1, 41

Run/stop filter 2, 41

S

Serial number, 50

Signal extension channel x, 39

Signal extension time, 38

Status, 44

Status bits, 19, 46

System CPX-E, 9

– H-rail mounting, 9

– Mounting distances, 9

– Rules for set-up, 9

System data, 32, 48

– Expansion, 48

– Fail safe, 48

– Force mode, 48

– Idle mode, 49

– System monitoring, 49

– System start, 48

System diagnostic data, 32, 46

– Error number, 46

– Module number and diagnostic status, 46

– Status bits, 46

System monitoring, 49

System parameters, 31, 32, 34

– Analogue process value representation, 36

– Fail safe, 34

– Force mode, 34

– Idle mode, 35

– Monitoring, 34

– System start, 35

System start, 35, 48

T

Target group, 5

Technical data, 51

Terminology, 53

Trace parameter, 41

Types of parameters, 30

Page 56: CPX-E-SYS DESC C 2017-07 8071029g1 - Festo€¦ · 2 Function 6 Festo – CPX-E-SYS-EN – 2017-07 – English 2 Function 2.1 Overview The system CPX-E is a modular system for the