Installation Instructions 5200 Series Electric Strike HES, Inc. Phoenix, AZ 800-626-7590 www.hesinnovations.com 1 Electrical Specifications Minimum Wire Gauge Requirements (Based on Round Trip) Solenoid Voltage 12 VDC 24 VDC 200 feet or less 200 – 300 feet 300 – 400 feet 18 gauge 16 gauge 14 gauge 20 gauge 18 gauge 16 gauge 3 ASSA ABLOY, the global leader in door opening solutions Product Components 1 2 5200 Electric Strike Body Trim Enhancer 12-Volt and 24-Volt Pigtails Electrical Ratings for Solenoid Continuous Duty 12 VDC 50 .24 24 VDC 200 .12 Resistance in Ohms Amps Solenoids are rated at +/- 10% indicated value. *10% maximum duty cycle (2 minutes maximum on time) Indoor use only 4 Cutout Templates for Frame Preparation © 2015, Hanchett Entry Systems, Inc., an ASSA ABLOY Group company. 3059006.002 rev C 1 2 3 Diagram 1: Product Components Intermittent Duty* 12–16 VAC 50 .24 – .32 24 VAC 200 .12 Resistance in Ohms Amps 501 Faceplate Option (4-7/8” x 1-1/4”), Square Corners and Flat Faceplate Used with cylindrical locksets in ANSI metal jambs 501A Faceplate Option (4-7/8” x 1-1/4”), Radius Corners and Flat Faceplate Used with cylindrical locksets or spring latches in aluminum frames [mm] Inches 1 -1/4" [31.8] 4 -7/8" [124] 3 -3/8" [85.7] 13/16" [20.6] 3/32" [2.3] 4 -7/8" [124] 4 -1/8" [104.8] 1 -7/16" [36.6] 1 -1/4" [31.8] R 1/8" [3] 3 -3/8" [85.7] 1 -1/4" [31.8] 4 -7/8" [124] 13/16" [20.6] [2.3] 3/32" [mm] Inches 1 -1/4" [31.8] 4 -7/8" [124] 4 -1/8" [104.8] 1 -7/16" [36.6] [mm] Inches 3-3/8" [85.7] 13/16" [20.6] 3/32" [2.3] 1 -7/16" [36.5] 7-15/16" [201.6] 1 -7/16" [36.6] 7 -15/16" [201.6] 7 -7/16" [189] 1 -7/16" [36.6] R 3/16" [4.1] 502 Faceplate Option (7-5/16” x 1-7/16”), Radius Corners and Flat Faceplate Used with cylindrical locksets or spring latches in aluminum frames [mm] Inches 1 -1/4" [36.5] 3 -3/8" [85.7] 6 -7/8" [174.3] 13/16" [20.6] 3/32" [2.3] 6 -7/8" [174.3] 6 -1/8" [155.6] 1 -1/4" [31.8] 1 -7/16" [36.6] R 3/16" [4.1] 503 Faceplate Option (6-7/8” x 1-1/4”), Radius Corners and Flat Faceplate Used with cylindrical locksets or spring latches in aluminum frames [mm] Inches 10" [254] 1 -3/8" [34.9] 3 -3/8" [85.7] 13/16" [20.6] 3/32" [2.3] 1 -3/8" [34.9] 10" [254] 8 -1/2" [215.6] 8 -1/2" [215.6] 1 -7/16" [36.6] 1 -3/8" [34.9] R 1/8" [4] 504 Faceplate Option (10” x 1-3/8”), Radius Corners and Flat Faceplate Used with cylindrical locksets; four-point mounting for wood installations NOTE: The 5200 has an in-frame horizontal adjustment range of about 1/4” (6.4 mm) to allow adjustment of the electric strike in the frame opening to accomodate for the horizontal position of the latchbolt after the strike has been installed. The “Adjusting the Horizontal” section provides steps for this adjustment.
Transcript
Page 1: Cutout Templates for Frame Preparation HES, Inc. 5200 ....pdf · Installation Instructions 5200 Series Electric Strike HES, Inc. Phoenix, AZ 800-626-7590 1 Electrical Specifications

Installation Instructions5200 Series Electric Strike

HES, Inc.Phoenix, AZ800-626-7590www.hesinnovations.com

1

Electrical Specifications

Minimum Wire Gauge Requirements(Based on Round Trip)

Solenoid Voltage12 VDC 24 VDC

200 feet or less

200 – 300 feet

300 – 400 feet

18 gauge

16 gauge

14 gauge

20 gauge

18 gauge

16 gauge

3

ASSA ABLOY, the global leaderin door opening solutions

Product Components1 2 5200 Electric Strike Body Trim Enhancer 12-Volt and 24-Volt Pigtails

Electrical Ratings for SolenoidContinuous Duty 12 VDC

50

.24

24 VDC200.12

Resistance in OhmsAmps

Solenoids are rated at +/- 10% indicated value.*10% maximum duty cycle (2 minutes maximum on time)Indoor use only

4Cutout Templates for Frame Preparation

© 2015, Hanchett Entry Systems, Inc., an ASSA ABLOY Group company.

3059006.002 rev C

1

2

3

Diagram 1: Product Components

Intermittent Duty* 12–16 VAC 50

.24 – .32

24 VAC200.12

Resistance in OhmsAmps

501 Faceplate Option (4-7/8” x 1-1/4”), Square Corners and Flat FaceplateUsed with cylindrical locksets in ANSI metal jambs

501A Faceplate Option (4-7/8” x 1-1/4”), Radius Corners and Flat FaceplateUsed with cylindrical locksets or spring latches in aluminum frames

[mm]Inches

1 -1/4"[31.8]

4 -7/8"[124]3 -3/8"

[85.7]

13/16"[20.6]

3/32"[2.3]

4 -7/8"[124]

4 -1/8"[104.8] 1 -7/16"

[36.6]

1 -1/4"[31.8]

R 1/8"[3]

3 -3/8"[85.7]

1 -1/4"[31.8]

4 -7/8"[124]

13/16"[20.6]

[2.3]3/32"

[mm]Inches

1 -1/4"[31.8]

4 -7/8"[124]

4 -1/8"[104.8] 1 -7/16"

[36.6]

[mm]Inches

3-3/8"[85.7]

13/16"[20.6]

3/32"[2.3]

1 -7/16"[36.5]

7-15/16"[201.6] 1 -7/16"

[36.6]7 -15/16"[201.6]

7 -7/16"[189]

1 -7/16"[36.6]R 3/16"

[4.1]

502 Faceplate Option (7-5/16” x 1-7/16”), Radius Corners and Flat FaceplateUsed with cylindrical locksets or spring latches in aluminum frames

[mm]Inches

1 -1/4"[36.5]

3 -3/8"[85.7] 6 -7/8"

[174.3]

13/16"[20.6]

3/32"[2.3]

6 -7/8"[174.3]

6 -1/8"[155.6]

1 -1/4"[31.8]

1 -7/16"[36.6]

R 3/16"[4.1]

503 Faceplate Option (6-7/8” x 1-1/4”), Radius Corners and Flat FaceplateUsed with cylindrical locksets or spring latches in aluminum frames

[mm]Inches

10"[254]

1 -3/8"[34.9]

3 -3/8"[85.7]

13/16"[20.6]

3/32"[2.3]

1 -3/8"[34.9]

10"[254]

8 -1/2"[215.6]

8 -1/2"[215.6]

1 -7/16"[36.6]

1 -3/8"[34.9]R 1/8"

[4]

504 Faceplate Option (10” x 1-3/8”), Radius Corners and Flat FaceplateUsed with cylindrical locksets; four-point mounting for wood installations

NOTE: The 5200 has an in-frame horizontal adjustment range of about 1/4” (6.4 mm) to allow adjustment of the electric strike in the frame opening to accomodate for the horizontal position of the latchbolt after the strike has been installed. The “Adjusting the Horizontal” section provides steps for this adjustment.

Page 2: Cutout Templates for Frame Preparation HES, Inc. 5200 ....pdf · Installation Instructions 5200 Series Electric Strike HES, Inc. Phoenix, AZ 800-626-7590 1 Electrical Specifications

2Installation

3Installation (continued)LBM Wiring

White

Orange Normally Open

Green Normally Closed

Common

Normally Open

Yellow Normally Closed

DIAGRAM 5: CYLINDRICAL LOCKSETS

LBSM Wiring

Brown

Blue Normally Open

Yellow Normally Closed

Common

Note 1: The 5200 series Electric Strikes are pre-set for FAIL SECURE OPERATION.

Note 2: There are two #2-56 screws located on the back of the strike for coverting the operation mode.

10. To convert from FAIL SECURE OPERATION to FAIL SAFE OPERATION, LOOSEN the two #2-56 screws located on the back of the strike, but DO NOT REMOVE them.

11. MOVE the Selector Stop Pins to the FAIL SAFE OPERATION position as pictured in Diagram 5.

12. TIGHTEN the two #2-56 screws to secure the strike in FAIL SAFE OPERATION.

13. VERIFY the 5200 is now in FAIL SAFE OPERATION.

14. IF the 5200 still operates as FAIL SECURE, THEN ENSURE the #2-56 screws are fully seated and tightened.

Diagram 5: FAIL SAFE OPERATION Mode Setting

BrownBlueYellow

White Orange Green

Converting the Operation Mode

Diagram 3: Latchbolt Monitor Diagram 4: Latchbolt Strike Monitor

Verifying the Operation Mode

15. TURN the horizontal adjustment screws slowly to adjust the strike in-frame, as shown in Diagram 6.

16. DO NOT REMOVE the screws or ROTATE them more than 3 full turns.

17. TIGHTEN the screws securely once the strike has been adjusted to allow the K-Nut teeth to dig into the strike housing and prevent slippage during use.

Adjusting the Horizontal

Diagram 6: Horizontal Adjustment

K-NUT

b

HorizontalAdjustmentScrews

Note: For 12 VDC, the Plug In Connector (pigtail) marked “12 VDC” should be used; for 24 VDC, the pigtail marked “24 VDC should be used.

1. SELECT the appropriate pigtail that matches system power and electrically CONNECT as illustrated in Diagram 2.

2. If no connector is present, CONFIGURE the wires as illustrated in Diagram 2.

3. If using the Latchbolt Monitor (LBM) or Latchbolt Strike Monitor (LBSM), REFER to Diagrams 3 and 4 on Page 3 to complete wiring.

Note: The 5200 ships in FAIL SECURE OPERATION mode.

4. USE Diagrams 5 and 6 on Page 3 as a guide to convert 5200 to FAIL SAFE OPERATION, if needed.

5. ATTACH the appropriate faceplate.

CAUTION!Before connecting any device at the installation site, verify input voltage using a multimeter.Many power supplies and low voltage transformers operate at higher levels than listed. Any input voltage exceeding10% of the solenoid rating may cause severe damage to the unit and will void the warranty.

6. PREPARE the frame using the appropriate template for the faceplate (see Page 4).

RED

RED/GREEN

BLACK

VIOLET

RED

BLACK

VIOLET

RED/GREEN

IF CONNECTOR IS MISSING

(+ 12 VDC)

(-NEG)

(+ 24 VDC)

(-NEG)

or

Elec

tric

Stri

ke

Elec

tric

Stri

ke

CONNECT TOGETHER

CONNECT TOGETHER

CONNECT TOGETHER

7. Electrically CONNECT the wires from the power source to the 5200.

8. INSTALL the 5200 in the jamb cutout.

9. IF horizontal adjustment is needed, THEN GO TO the “Adjusting the Horizontal” section (see Page 3).

Preparing the Strike

Finishing the Installation

Preparing the Frame

Diagram 2: 12V to 24V Conversion


Recommended