+ All Categories
Home > Documents > DATA SHEET: TEMBREAK 2 S400-NE MCCB - Terasaki · 2017. 1. 26. · TB2 E/S 630 Page 1 of 4 MCCB...

DATA SHEET: TEMBREAK 2 S400-NE MCCB - Terasaki · 2017. 1. 26. · TB2 E/S 630 Page 1 of 4 MCCB...

Date post: 01-Mar-2021
Category:
Upload: others
View: 3 times
Download: 0 times
Share this document with a friend
4
4,500 15,000 630 Max In (A) of Frame Model S400 Number of Poles 3, 4 Typ NE e Nominal current ratings I n (A) 50°C 250 400 Electrical characteristics Rated operational voltage U e (V) AC 50/60 Hz 690 - 800 8 DC Rated insulation voltage U i (V) Rated impulse withstand voltage U imp (kV) Ultimate breaking capacity I cu (kA) 690V AC 20 30 45 50 85 - 15 30 45 50 85 - (IEC, JIS, AS/NZS) 525V AC 440V AC 400/415V AC 220/240V AC 250V DC Service breaking capacity I cs (kA) 690V AC (IEC, JIS, AS/NZS) 525V AC 440V AC 400/415V AC 220/240V AC 250V DC Rated breaking capacity (NEMA) (kA) 480V AC 25 85 240V AC Rated short-time withstand current I cw (kA) 0.3 Seconds 5 Protection Adjustable thermal, adjustable magnetic Fixed thermal, fixed magnetic Microprocessor Utilisation category B Installation Front connection (FC) Extension bar (FB) Cable clamp (FW) Rear connection (RC) Plug-in (PM) DIN rail mounting (DA) - Dimensions height (mm) 260 140 185 103 4.2 5.6 width (mm) 3 pole (mm) 4 pole depth (mm) Weight weight (kg) 3 pole 4 pole Operation Direct Opening Action Toggle operation Door mounted (HS) / Breaker mounted handle (HB) Motor operation (MC) Endurance Electrical cycles 415V AC Mechanical cycles DATA SHEET: TEMBREAK 2 S400-NE MCCB Standard Optional - Not Available TB2 E/S 630 Page 1 of 4 MCCB Electrical Characteristics to IEC 60947-2, EN 60947-2, JIS C 8201-2-1 ANN.1, AS/NZS 3947-2, NEMA AB-1
Transcript
Page 1: DATA SHEET: TEMBREAK 2 S400-NE MCCB - Terasaki · 2017. 1. 26. · TB2 E/S 630 Page 1 of 4 MCCB Electrical Characteristics to IEC 60947-2, EN 60947-2, JIS C 8201-2-1 ANN.1, AS/NZS

4,50015,000

630Max In (A) of FrameModel S400Number of Poles 3, 4Typ NEe

Nominal current ratingsIn (A) 50°C 250

400

Electrical characteristicsRated operational voltage Ue (V) AC 50/60 Hz 690

-8008

DCRated insulation voltage Ui (V)Rated impulse withstand voltage Uimp (kV)

Ultimate breaking capacity Icu (kA) 690V AC 2030455085-

1530455085-

(IEC, JIS, AS/NZS) 525V AC440V AC400/415V AC220/240V AC250V DC

Service breaking capacity Ics (kA) 690V AC (IEC, JIS, AS/NZS) 525V AC

440V AC400/415V AC220/240V AC250V DC

Rated breaking capacity (NEMA) (kA) 480V AC 25 85240V AC

Rated short-time withstand current Icw (kA) 0.3 Seconds 5

Protection Adjustable thermal, adjustable magneticFixed thermal, fixed magneticMicroprocessorUtilisation category B

InstallationFront connection (FC)Extension bar (FB) •Cable clamp (FW) •Rear connection (RC) •

•Plug-in (PM)DIN rail mounting (DA) -Dimensions height (mm) 260

1401851034.25.6

width (mm) 3 pole (mm) 4 pole

depth (mm)Weight weight (kg) 3 pole

4 pole

Operation Direct Opening ActionToggle operationDoor mounted (HS) / Breaker mounted handle (HB) •Motor operation (MC) •Endurance Electrical cycles 415V AC

Mechanical cycles

DATA SHEET: TEMBREAK 2 S400-NE MCCB

Standard • Optional - Not Available

TB2 E/S 630

Page 1 of 4

MCCB Electrical Characteristics to IEC 60947-2, EN 60947-2, JIS C 8201-2-1 ANN.1, AS/NZS 3947-2, NEMA AB-1

Page 2: DATA SHEET: TEMBREAK 2 S400-NE MCCB - Terasaki · 2017. 1. 26. · TB2 E/S 630 Page 1 of 4 MCCB Electrical Characteristics to IEC 60947-2, EN 60947-2, JIS C 8201-2-1 ANN.1, AS/NZS

With extension bars (optional)

With extension bars (optional)

30

30

Front connected

Rear connected

Front connected with Motor Operator

Rear connected with Motor Operator

DATA SHEET: TEMBREAK 2 S400-NE MCCB

Outline Dimensions S400-NE

ASL: Arrangement Standard Line HL: Handle Frame Centre Line

Page 2 of 4

Page 3: DATA SHEET: TEMBREAK 2 S400-NE MCCB - Terasaki · 2017. 1. 26. · TB2 E/S 630 Page 1 of 4 MCCB Electrical Characteristics to IEC 60947-2, EN 60947-2, JIS C 8201-2-1 ANN.1, AS/NZS

11

8 (max.)

20 (max.)

Preperation of conductor

30 (max.)

Support or rail

Support or rail

Mounting screwM10x30 max.

Mounting screw M5 x 20

Mounting plate

90102

260

97

4

102113

48

138142

180

6t6t

198

258

65

276

90102

260

971

4

32

6t32

204208

246

12

1

Insulating plate

Mounting plate

Mounting M6 NUT

Insulating plate

Mounting screw M6x70

Mounting on a support or rails (shown with optional connection bars oriented for rear access)

Mounting through the backplate (shown with optional connection bars oriented for rear access)

Mounting on the backplate (optional connection bars must be oriented for front access)

Outline Dimensions Termination of Busbar

ASL: Arrangement Standard Line HL: Handle Frame Centre Line

DATA SHEET: TEMBREAK 2 S400-NE MCCB

Outline Dimensions S400-NE Plug-in Version

Page 3 of 4

Page 4: DATA SHEET: TEMBREAK 2 S400-NE MCCB - Terasaki · 2017. 1. 26. · TB2 E/S 630 Page 1 of 4 MCCB Electrical Characteristics to IEC 60947-2, EN 60947-2, JIS C 8201-2-1 ANN.1, AS/NZS

Percent Rated Current IRPercent Rated Current In

LT

ST

PTA

NP

Option

Standard

IR (A)LTD Pick-up current IR xIn 0.4 0.5 0.63 0.8 0.9 0.95 1.0

1Characteristics

Note(1) gF is not available when In is 250A. (2) Ii max. = 13 x In. (3) 1.0 x IR or 0.5 x IR can be selected. Characteristic of neutral protection (tN vs. IN) isidentical to characteristic of phase protection (tR vs. IR). (4) When you specify gF on MCCBs with 3 poles the terminal block is automatically fitted toconnect with the external neutral CT for 3 phases 4 wires system. See terminal blocks in section 4.

No. 2 3 4 5 6 711

2.5 5 100.20.1

14(Max: 13 x In) Note (2)0.840

1.0/0.5 Note (3)

tN=tRtN

IN

tpIpIi

tsd

Isd xIR

xIRxIR

xIR

(s)

(s)

gFNote(4)

0.20.2tg

Ig xIn(s)

(s)

tR (s)at 200% x IR at 600% x IR

21 21 5 10 19 29

INST

In = 400A; 250A Note (1)

Time/Current Characteristic Curves

S400-NE

Page 4 of 4

DATA SHEET: TEMBREAK 2 S400-NE MCCB


Recommended