Date post: | 10-Jul-2016 |
Category: |
Documents |
Upload: | prasana-balaji |
View: | 228 times |
Download: | 1 times |
ABHIJEET GABON POWER S.A.
TECHNICAL SPECIFICATION OF EPC CONTRACTFOR
218 MW COMBINED CYCLE POWER PROJECTAT LIBREVILLE, GABONVolume – III Part B
Electrical
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 1 of 88
TABLE OF CONTENT
1 DATA SHEET TO BE FILLED BY BIDDER......................................................2
1.1 GENERATOR.........................................................................................................2
1.2 GENERATOR CIRCUIT BREAKER..........................................................................16
1.3 ISOLATED PHASE BUS DUC................................................................................23
1.4 TRANSFORMERS.................................................................................................25
1.5 HIGH MEDIUM VOLTAGE SWITCHGEAR..............................................................29
1.6 LOW VOLTAGE SWITCHGEAR.............................................................................34
1.7 MOTOR...............................................................................................................37
1.8 DIESEL GENERATOR SET....................................................................................40
1.9 DC BATTERY AND BATTERY CHARGER...............................................................49
1.10 UPS..................................................................................................................... 53
1.11 ILLUMINATION....................................................................................................58
1.12 SWITCHYARD......................................................................................................61
1.13 CABLE................................................................................................................ 86
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 2 of 88
1 DATA SHEET TO BE FILLED BY BIDDER
1.1 Generator
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 3 of 88
Sr. No. Description Unit Parameter
1.0 GENERATOR MAIN PARAMETERS
1.1 Make, type and model & serial number
As per approved vendor list.
1.2 Maximum continuous rating MW MVA 70 MW/82.5 MVA for Gas turbine generator .
80 MW/95 MVA for Steam turbine generator
1.3 Rated terminal voltage kV 11 KV
1.4 Rated current Amps 4332 A for GTG
4987 A for STG
1.5 Rated frequency Hz 50
1.6 Rated power factor 0.85
1.7 Rotor current at Max. Continuous rating(MCR0
Amps To be furnished during detail engg.
1.8 Rotor voltage at MCR Volts To be furnished during detail engg
1.9 Maximum permissible variation range in :
a) Rated terminal voltage % +/- 5 % at rated power factor
b) Rated frequency % 47.5 Hz to 51.5 Hz.
c) Combined permissible variation of frequency and voltage (with characteristic- curves)without exceeding safe temperature rise.
% +/-10%
1.10 Synchronous speed rpm 3000
1.11 Number of poles Number 2
a) Line terminals brought out To be furnished during detailed engg.
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 4 of 88
Sr. No. Description Unit Parameter
b) Parallel paths per phase To be furnished during detailed engg.
b) Neutral terminals brought out To be furnished during detailed engg.
1.12 Type of stator winding connection 3-Phase,Star
1.13 Degree of protection of the enclosure for generator installed Indoor
IP54
1.14 Details of fire detection / protection provided for the generator with write-up,supplied
By CO2 injection internally
1.15 Generator efficiency at :
a) 100% load % To be furnished during detailed engg.
b) 75% load % To be furnished during detailed engg.
c) 50% load % To be furnished during detailed engg.
1.16 Minimum guaranteed short circuit ratio corresponding to maximum capability
1.1
1.17 Designation for method of cooling as per IS / IEC standards Air cooled
1.18 Rated Hydrogen pressure Kg / cm2
(g)NA
1.19 Basic impulse insulation withstand voltage of stator winding with respect to earth
kV (peak) To be furnished during detailed engg.
1.20 Permissible unbalanced loading subject to rated current not being exceeded in any phase
To be furnished during detailed engg.
a) Maximum continuous negative phase sequence current I2
% 10%
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 5 of 88
Sr. No. Description Unit Parameter
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 6 of 88
Sr. No. Description Unit Parameter
b) Maximum value of I22 t For transient
operation under system fault conditions (where t is in seconds)
To be furnished during detailed engg.
1.21 Maximum permissible capacitive loading at rated load & voltage
MVAR 63.2
1.22 Generator short time overload capability
% To be furnished during detailed engg.
1.23 Generator over speed capability % To be furnished during detailed engg.
2.0 GENERATOR PARAMETERS
2.1 Generator reactances in percent at rated kV and MVA, both saturated and unsaturated
To be furnished during detailed engg.
2.1.1 Direct axis synchronous reactance Xd
% To be furnished during detailed engg.
2.1.2 Quadrature axis synchronous reactance Xq
% To be furnished during detailed engg.
2.1.3 Direct axis transient reactance Xd’ % To be furnished during detailed engg.
2.1.4 Quadrature axis transient reactance X’q
% To be furnished during detailed engg.
2.1.5 Direct axis sub-transient reactance X”d
% To be furnished during detailed engg.
2.1.6 Quadrature axis sub-transient reactance X”q
% To be furnished during detailed engg.
2.1.7 Negative phase sequence reactance X2
% To be furnished during detailed engg.
2.1.8 Zero phase sequence reactance Xo % To be furnished during detailed engg.
2.1.9 Potier reactance % To be furnished during detailed engg.
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 7 of 88
Sr. No. Description Unit Parameter
2.1.10 Wave form factor To be furnished during detailed engg.
2.1.11 Telephone interference factor % To be furnished during detailed engg.
2.2 Permissible tolerance on all guaranteed reactance values
% (+) To be furnished during detailed engg.
2.3 Synchronous impedance Ohms To be furnished during detailed engg.
2.4 Transient open circuit time constant T’
msec. To be furnished during detailed engg.
2.5 Effective winding capacitance to earth
To be furnished during detailed engg.
a) Per phase F To be furnished during detailed engg.
b) All phase connected together F To be furnished during detailed engg.
3.0 GENERATOR TEMPERATURE RISES
3.1 Guaranteed temperature rise over max. inlet cooling air / Hydrogen temperature at rated load
To be furnished during detailed engg.
a) Stator windings oC To be furnished during detailed engg.
b) Stator core oC To be furnished during detailed engg.
i) In contact with insulated winding oC To be furnished during detailed engg.
ii) Not in contact with insulated winding oC To be furnished during detailed engg.
c) Rotor windings oC To be furnished during detailed engg.
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 8 of 88
Sr. No. Description Unit Parameter
3.2 Maximum cooling inlet air / hydrogen temperature corresponding to the highest cooling water temperature at rated load
Unit To be furnished during detailed engg.
3.3 Maximum temperature rise To be furnished during detailed engg.
a) Collector rings 0C To be furnished during detailed engg.
b) Generator Bearings To be furnished during detailed engg.
- Turbine end 0C To be furnished during detailed engg.
- Exciter end oC To be furnished during detailed engg.
c) Oil inlet temperature at highest bearing cooling water temperature
oC To be furnished during detailed engg.
4.0 GENERATOR LOSSES
4.1 Generator losses (curves for various losses vs load at different hydrogen pressure shall be enclosed)
a) Iron loss at no load kW To be finalized later
b) Iron loss at full load kW To be finalized later
c) Stray loss kW To be finalized later
d) Stator copper loss at full load kW To be finalized later
e) Rotor copper loss at No load kW To be finalized later
f) Rotor copper loss at full load kW To be finalized later
g) Friction and windage losses kW To be finalized later
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 9 of 88
Sr. No. Description Unit Parameter
h) Mechanical losses including bearing losses
kW To be finalized later
i) Total generator losses kW To be finalized later
5.0 GENERATOR STATOR CORE PARTICULARS
5.1 Stator core-outer diameter mm To be furnished during detailed engg.
5.2 Stator core-length mm To be furnished during detailed engg.
5.3 Air gap mm To be furnished during detailed engg.
5.4 Flux densities in various parts of the stator core under no-load and full load
NO LOAD / FULL LOAD
5.4.1 Air gap T To be furnished during detailed engg.
5.4.2 Stator core T To be furnished during detailed engg.
5.4.3 Stator teeth T To be furnished during detailed engg.
5.4.4 Rotor core T To be furnished during detailed engg.
5.4.5 Rotor teeth T To be furnished during detailed engg.
6.0 TYPE AND CONNECTION OF STATOR WINDINGS
6.1 Total No. of stator bars (top & bottom)
No. To be furnished during detailed engg.
a) @ 25 deg C ohms To be furnished during detailed engg.
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 10 of 88
Sr. No. Description Unit Parameter
b) @ 75 deg C ohms To be furnished during detailed engg.
7.0 ROTOR WINDING PARTICULARS
7.1 Class of field winding insulation CLASS F
7.2 Rotor winding resistance
a) @ 25 deg. C Ohms *
b) @ 75 deg. C Ohms *
8.0 GENERATOR MISCELLANEOUS
PARTICULARS
8.1 Noise level in free field / semi-reverberant conditions
a) No load (indicate distance also) dB (A) To be furnished during detailed engg.
b) On load (indicate distance also) dB (A) To be furnished during detailed engg.
8.2 Direction of rotation of generator as seen from turbine end
To be furnished during detailed engg.
8.3 Vibration amplitude (peak to peak) To be furnished during detailed engg.
a) Stator core vibration micro meter
To be furnished during detailed engg.
b) Stator core natural frequency c/s To be furnished during detailed engg.
c) Stator frame vibration micro meter
To be furnished during detailed engg.
d) Rotor vibration micro meter
To be furnished during detailed engg.
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 11 of 88
Sr. No. Description Unit Parameter
e) Bearing vibration micro meter
To be furnished during detailed engg.
8.4 No. and type of RTD’s / thermocouples provided
8.4.1 Stator winding No. As per system requirement
8.4.2 Stator core No. As per system requirement
8.4.3 Rotor winding No. As per system requirement
8.4.4 Bearings As per system requirement
a) Turbine end No. 1 No . for Gas turbine Generator
1 No . for Steam turbine Generator
b) Exciter end No. 1 No . for Gas turbine Generator
1 No . for Steam turbine Generator
9.0 EXCITATION SYSTEMS STATIC
9.1 Excitation System Parameter
9.1.1 Type of excitation system offered Brushless/Static
a) Nominal field voltage Volts 313.7 V for Gas turbine Generator 250.1 V. for Steam turbine
Generator
b) Maximum field voltage Volts To be furnished during detailed engg.*
c) Ceiling / Field forcing voltage Volts As indicated
d) Minimum and maximum field current with generator at i) No load ii) generator at 100% load
Amps To be furnished during detailed engg.*
9.1.2 Generator field characteristics
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 12 of 88
Sr. No. Description Unit Parameter
a) With generator at no-load and rated voltage
Volt Amps *
b) With generator at 125% of MCR Volt Amps *
c) With generator at rated load and rated Voltage at:
*
i) Rated p.f Volt Amps *
ii) Unity p.f. Volt Amps *
9.2 Make & type of online diode monitoring system
9.3 Brushless/Static Excitation System STATIC
9.3.1 Ratings :
(a) Continuous max. Output kW 212.2 KW for Gas turbine Generator .
175.7 KW for Steam turbine Generator
(b) Rated voltage Volts 313.7 V for Gas turbine Generator 250.1 V. for Steam turbine
Generator
(c) Rated current Amps 676.1 A for Gas turbine Generator
702.3 A for Steam turbine Generator
(d) Rated full load speed rpm *
(e) Rated frequency Hz *
(f) Ceiling voltage Volts *
(g) Response ratio S *
(h) Expected peak current for terminal short circuit
Amps *
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 13 of 88
Sr. No. Description Unit Parameter
(i) Short time capacity kW/sec
9.3.1.2 Winding (Stator/Rotor):
(a) Type *
(b) Class of insulation *
9.3.1.3 Type of cooling provided *
9.3.1.4 Degree of protection for the exciter enclosure *
9.3.1.5 Type of drive *
9.3.2 Auxiliary exciter -permanent magnet generator(PMG) *
9.3.2.1 Ratings :
(a)
Continuous maximum
Continuous maximum output kW *
(b)
voltage
Rated voltage Volts *
(c)
current
Rated current Amps *
(d)
frequency
Rated frequency Hz *
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 14 of 88
Sr. No. Description Unit Parameter
(e)
time capacity
Short time capacity kVA/ sec *
9.3.2.2 Winding :
(a) *
(b) *
9.3.2.3 Type of cooling provided *
9.3.2.4 Degree of protection for the PMG enclosure *
9.3.3 Rotating Diodes & fuses
9.3.3.1 Make and type of diodes *
9.3.3.2 Total number of diodes No. *
9.3.3.3 Number of parallel paths per bridge arm
No. *
9.3.3.4 No. of parallel paths per bridge arm necessary for generator MCR
No. *
9.3.3.5 Method of cooling adopted for diodes *
9.3.3.6 Type of protection provided for rotating diodes *
9.3.3.7 Ceiling output voltage/current V/A *
9.3.4 Excitation system cooling
9.3.4.1 Air-to-Water Cooler
(a)
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 15 of 88
Sr. No. Description Unit Parameter
(b)capacity per cooler
9.4 Voltage Regulator and Accessories
9.4.1 a) Type Thyristor controlled dual channel
9.4.1 b) Quantity
9.4.2 No. of auto & manual channels
9.4.3 Guaranteed sensitivity *
9.4.4 Range of voltage level setting :
- auto
- manual
*
9.4.5 Whether following limiters and compensators provided
(a) Minimum excitation limiter *
(b) Maximum stator current limiter *
(c) Maximum excitation limiter *
(d) Maximum rotor current limiter *
(e) Volts/Hz. Limiter *
(f)Reactive drop compensator *
(g) Load angle limiter *
(h) Power system stabiliser *
(j) Power factor Regulator *
9.4.6 Whether following features/ monitors provided
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 16 of 88
Sr. No. Description Unit Parameter
(i) Auto synchroniser *
(ii) Field earth fault monitor – 2 Stage based on injection principle
*
(iii) On line shaft leakage
current/voltage monitoring
device, with same location
*
(iv) Details of any other
features/devices provided
*
9.4.7 Critical speed
( 1st, 2nd, 3rd values )
*
9.4.8 Type of cooling for field control cubicles
Natural / Forced
9.5 Main Exciter Field Breaker
9.5.1 Type *
9.5.2 Current rating Amps *
9.5.3 Voltage rating Volts *
9.5.4 Rupturing capacity kA
9.5.5 Making capacity kAp
9.5.6 i) Type of operating mechanism
ii) Operating Voltage
9.6 Miscellaneous Details Of Excitation System
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 17 of 88
Sr. No. Description Unit Parameter
9.6.1 Whether the following accessories/ schemes provided
(a) Field discharge resistor
(b) Field current measurement facility
(c) Field and exciter earth fault protection scheme
10.0 HYDROGEN COOLING SYSTEM
NA
10.1 Hydrogen NA
10.1.1 Type & total number of coolers provided
Nos. NA
10.1.2 Number of coolers required in simultaneous use at MCR
Nos. NA
10.1.3 Maximum Generator Loading with one cooler out of service
MVA NA
10.1.4 Cooling water maximum inlet temperature at highest ambient air temperature
oC NA
10.1.5 Inlet cooling air / hydrogen temperature at above cooling water temperature
oC NA
10.1.6 Type and material of tubes NA
10.1.7 Tube sheet material NA
10.1.8 Water box and shell material NA
10.2 Hydrogen gas / air system NA
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 18 of 88
Sr. No. Description Unit Parameter
10.2.1 Max. Inlet / outlet temp. of hydrogen / air
oC NA
11.0 SEAL OIL SYSTEM To be furnished during detail engineering
11.1 Seal Oil “H2” side
11.1.1 No. of pumps No. *
11.2 Seal oil “Air” side
11.2.1 No. of pumps
(a) No. *
(b) No. *
12.0 EXCITATION SYSTEM COOLING
12.1 Type of cooling Air/Water
12.1.1 If air, forced or natural
(a) Rectifier Transformer panel
(b) Thyristor panels
(c) AVR panels
(d) Other panels
*
12.1.2 If forced, No. of fans each 100% duty.
Nos. *
12.1.3 Whether automatic changeover of fans provided or not?
*
12.1.4 Whether standby fan provided to achieve 100% duty
Yes / No *
13.0 GENERATOR CAPABILITY
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 19 of 88
Sr. No. Description Unit Parameter
AND OTHER MISCELLANEOUS DATA/DIAGRAMS
13.1 Capability of generator with and without AVR (furnish capability diagram)
*
13.2 Open circuit and short circuit characteristic (calculated) curves enclosed
Yes/No *
13.3 Current and kVA rating of generator at voltage above 100%
Amps/ kVA
*
13.4 Overload capacity of generator for 1,2,3,4,5,6,10,15 and 60 sec.
MVA *
13.5 Value of voltage rise of generator with and without AVR in circuit at full load throw-off
p.u *
13.6 The maximum continuous voltage / frequency at which the generator could operate, particularly during run up or after a load throw-off with AVR on manual control
Volts/ Hz *
13.7 The maximum possible peak voltage which will appear across the two ends of the generator field winding after a full load throw-off
Volts *
13.8 Recommended mode of generator stator neutral earthing and particulars of surge capacitor for generator.
*
13.9 Tests
13.9.1 All type and routine tests will be carried out as per relevant National / International Standards.
Yes/No *
13.9.2 Running trials will be conducted in the shop with the generator, exciter and AVR connected up and combined as a unit on the test bed
Yes/No *
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 20 of 88
1.2 Generator Circuit breaker
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 21 of 88
Sr. No.
Description Unit Parameter
1 Manufacturer *
2 Standards *
3 Type *
4 Rated Voltage kV *
5 Rated frequency Hz *
6Rated short-time withstand current for
1 sec. with breaker as housed in the
panel
kA
*
7 Making current(peak) kA
8 Dynamic over current rating kA *
9 Basic Insulation Lvel
One minute power frequency withstand
voltage
kV rms*
Impulse withstand voltage kV peak *
10 Temperature rise
a) Maximum temp. rise over ambient
specified
b) Ambient temperature
11 Interchangeability of similar equipment *
12 Type & no. of phases *
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 22 of 88
Sr. No.
Description Unit Parameter
13 Arrangement for isolating breaker for
maintenance provided
14 Standard applicable *
15 Whether antipumping device provided *
16Whether control circuitry suitable for
monitoring of closing & tripping
circuits
17 Maximum design voltage *
a) Symmetrical breaking capacity(in kA at
rated voltage)
b) Asymmetrical breaking capacity for
various breakers at rated voltage
18a) Rated continuous current rating for
various breakers and corresponding
temperature.
b) Rated continuous current rating for
various breakers at the specified
ambient temperature.
19 No. of breaks/pole *
20 Type of material of contacts *
21 Whether contacts silver plated and
thickness of plating
22 Whether breaker designed to close and
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 23 of 88
Sr. No.
Description Unit Parameter
latch for making current release
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 24 of 88
Sr. No.
Description Unit Parameter
23 Weather trip free or fixed trip
24 Type of closing mechanism
25 Normal voltage of closing/tripping
mechanism/spring charging motor
26 Allowable vibration of voltage for
above
27 Power required for normal voltage for
a) Trip coil
b) Closing coil
c) Spring charging motor
28 Weight of circuit breaker with arc
extinguishing medium
29 Opening time in cycles
30 Making time in cycles
31 Opening time at
a) 10% Current
b) 50% Current
c) 100% Current
32 Duty cycle
33 Weather 6 Nos. adjustable (either in
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 25 of 88
Sr. No.
Description Unit Parameter
NO or NC) auxiliary contacts over and
above those required for breaker
operation/annunciation have been
provided or not.
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 26 of 88
Sr. No.
Description Unit Parameter
34 Current carrying capacity of auxiliary
switches.
35 No. of breaker operations necessary
before inspection & maintenance of
a) Switching rated load
b) Fault at 100% capacity
c) Faults at 50% capacity
d) Making under fault conditions
36 Accessibility of line connection
Whether terminals suitable with
isolated phase bus ducts
Heat dissipation at normal current
(KW)
Minimum value for pickup current for
i) Closing coil
ii) Tripping coil
37 Schematic control diagram of circuit
breaker enclosed
38 Are the following items supplied with
the breaker enclosure
39 Current transformers(CTs)
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 27 of 88
Sr. No.
Description Unit Parameter
a) No. of CTs provided with cores on
generator side of breaker
b) Technical particulars of C.Ts
40 Voltage transformers(VTs)
a) No. of VTs provided with cores on
generator side of breaker
b)No. of VTs provided with cores on L.V
side Gen-transformer(GT) side of
breaker
c) Technical particulars of V.Ts
41 Surge Capacitor
a) No. of Surge Capacitor provided on
generator side of breaker
b) No. of Surge Capacitor provided on
L.V side GT side of breaker
c) Technical particulars of Surge
Capacitor
42 Surge Arrestor
a) No. of Surge Arrestor
b) Technical particulars
42 Disconnector switch between breaker
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 28 of 88
Sr. No.
Description Unit Parameter
& LV side of GT
a) No.
b) Technical particulars
43 Earthing Switches(ES)
a) No.
b) Technical particulars
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 29 of 88
1.3 Isolated Phase Bus DuctSr. No.
Description Unit Parameter
1. Make *
2. Applicable standard *
3. Voltage rating of bus duct KV *
4. Rated current of main bus duct KA *
5. Three second short circuit current rating
a) Main KA
b) Tap-off KA
6. Momentary Overcurrent
a) Main KA *
b) Tap-off KA *
7. Degree of protection *
8. Thickness of the
a) Conductor mm *
b) Enclosure mm *
9. Losses in the
a) Conductor KW/m
b) Enclosure KW/m
10. Type of cooling *
11. Disconnecting links *
12. Material of conductor *
13. Material of enclosure *
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 30 of 88
Sr. No.
Description Unit Parameter
14.Temperature rise while operating at rated continuous current at ambient temp. of 500C
a) Conductor (hot spot) *
b) Enclosure (hot spot) *
15.Creepage distance for Insulators & bushing
16. Voltage transformer
a) Accuracy class *
b) Rated voltage factor *
17.Type of insulation for current transformer and neutral grounding transformer.
18. Duty rating
a) Neutral grounding transformer *
b) Neutral grounding resistor *
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 31 of 88
1.4 Gas Turbine Generator Transformers
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 32 of 88
Sr. No.
Description Unit Parameter
1 Transformer applications Step up
2 Type & make As per vendor list
3 Applicable standard As per IS/EDF std.
4 Quantity No(s). 2
5 Full load rating (ONAN/ONAF) MVA 90
6 Rating of each windings MVA 72/90
7 Rating no load voltage HV/LV kV 11/95
8 Rating of different cooling methods ONAN/ONAF
9 Impedance value % 12
10 Rated frequency Hz 50
11 Winding connection of different windings and vector group
Ynd11
12 System Earthing (HVLV) HV
13 Type of tap changer off circuit/on load OCTC
14 Full power tapping provided Yes/No Yes
15 Type of voltage variation (CFVV/VFVV/CBVV)
CFVV
16 Over fluxing capability For Over fluxing Factor 1.1 : Continuous1.25 : 60 Sec1.4 : 10 Sec.
17 Winding insulation type uniformly or non-uniformly insulated
Uniform on LV side & non Uniform on HV side
17.1 HV Non Uniform
17.2 LV Uniform
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 33 of 88
Sr. No.
Description Unit Parameter
18 Highest system voltage kV 95
19 Power frequency withstand voltage of winding
19.1 HV kV rms 200
19.2 LV kV rms 70
20 Standard rated lightning impulse withstand voltage
20.1 HV kV p 650
20.2 LV kV p 170
21 Maximum temperature rise at full load with 100% coolers :
21.1 Oil oC 40
21.2 Winding oC 45
22 Bushing particulars.
22.1 Applicable standard for bushing IS-2099
22.2 Clearance in air HV/LV/Neutral (between phases and phase to earth)
As per tech spec
22.2.1
HV (P-P) mm As per tech spec
22.2.2
HV (P-E) mm As per tech spec
22.2.3
LV (P-P) mm As per tech spec
22.2.4
HV - N mm As per tech spec
22.3 Quantity of oil in oil filled bushing litre To be furnished during detailed engineering
22.4 Creepage distance mm/kV 31
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 34 of 88
Sr. No.
Description Unit Parameter
23 No load loss at 100% rated voltage & frequency
kW
24 Load loss at rated current with 75 deg C
kW
25 Cooler loss at full load kW 5.6(all fans running)
26 Efficiency (0.85 Pf)
26.1 Full load 99.7
26.2 75% load
27 No load current A(approx)
28 Total estimated weight Kgs To be furnished during DE
29 OCTC/OLTC OCTC
29.1 Make As per approved vendor list provided
29.2 Rated Voltage Volts 110KV
29.3 Rated Current Amps 800
29.4 No. of steps 13
29.5 Step Voltage Volts +/- 2.5% at a step of 2.5%
29.6 Time of operation from one step to other for Auto / manual mode
Sec. 5-7
30 Type of axial and radial coil supports for HV/LV
31 No. of cooler banks and capacity of each cooler bank
As per 2X50% requirement
32 Guaranteed No load current *
31.1 When excited from LV side at 100% and 110% rated voltage
Amps *
33 Max. Flux density when rated and 110% rated voltage
Wb/m2 1.7
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 35 of 88
Sr. No.
Description Unit Parameter
34 Vacuum withstand capability main tank, radiators and accessories
mm of Hg
35 Weight
35.1 Core kg To be furnished during detailed engineering
35.2 Net copper wt. HV/LV kg ------do------
35.3 Oil kg ------do------
35.4 Tank, coolers & fittings kg ------do------
35.5 Total kg ------do------
35.6 Untanking weight kg ------do------
36 Cooling fans, oil pumps rating kW ------do------
37 Capability of transformer to remain in operation from hot conditions after failure of forced cooling with full load
minutes ------do------
38 On-line dissolved Gas Analyser Provided?
Yes/No no
39 Fibre optic based direct hot spot temperature measurement System Provided?
Yes/No no
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 36 of 88
1.5 Steam Turbine Generator Transformers
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 37 of 88
Sr. No.
Description Unit Parameter
1 Transformer applications Step up
2 Type & make As per vendor list
3 Applicable standard As per IS/EDF std.
4 Quantity No(s). 1
5 Full load rating (ONAN/ONAF) MVA 100
6 Rating of each windings MVA 80/100
7 Rating no load voltage HV/LV kV 11/95
8 Rating of different cooling methods ONAN/ONAF
9 Impedance value % 12
10 Rated frequency Hz 50
11 Winding connection of different windings and vector group
Ynd11
12 System Earthing (HVLV) HV
13 Type of tap changer off circuit/on load OCTC
14 Full power tapping provided Yes/No Yes
15 Type of voltage variation (CFVV/VFVV/CBVV)
CFVV
16 Over fluxing capability For Over fluxing Factor 1.1 : Continuous1.25 : 60 Sec1.4 : 10 Sec.
17 Winding insulation type uniformly or non-uniformly insulated
17.1 HV Non Uniform
17.2 LV Uniform
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 38 of 88
Sr. No.
Description Unit Parameter
18 Highest system voltage kV 95
19 Power frequency withstand voltage of winding
19.1 HV kV rms 200
19.2 LV kV rms 70
20 Standard rated lightning impulse withstand voltage
20.1 HV kV p 650
20.2 LV kV p 170
21 Maximum temperature rise at full load with 100% coolers :
21.1 Oil oC 40
21.2 Winding oC 45
22 Bushing particulars.
22.1 Applicable standard for bushing IS-2099
22.2 Clearance in air HV/LV/Neutral (between phases and phase to earth)
As per tech spec
22.2.1
HV (P-P) mm As per tech spec
22.2.2
HV (P-E) mm As per tech spec
22.2.3
LV (P-P) mm As per tech spec
22.2.4
HV - N mm As per tech spec
22.3 Quantity of oil in oil filled bushing litre To be furnished during detailed engineering
22.4 Creepage distance mm/kV 31
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 39 of 88
Sr. No.
Description Unit Parameter
23 No load loss at 100% rated voltage & frequency
kW
24 Load loss at rated current with 75 deg C
kW
25 Cooler loss at full load kW 5.6
26 Efficiency (0.85 Pf)
26.1 Full load 99.75
26.2 75% load
27 No load current A(approx)
28 Total estimated weight Kgs
29 OCTC/OLTC OCTC
29.1 Make As per approved vendor list provided
29.2 Rated Voltage Volts 110
29.3 Rated Current Amps 800
29.4 No. of steps 13
29.5 Step Voltage Volts +/- 2.5% at a step of 2.5%
29.6 Time of operation from one step to other for Auto / manual mode
Sec. 5-7
30 Type of axial and radial coil supports for HV/LV
*
31 No. of cooler banks and capacity of each cooler bank
2X50% as per requirement
32 Guaranteed No load current *
31.1 When excited from LV side at 100% and 110% rated voltage
Amps *
33 Max. Flux density when rated and 110% rated voltage
Wb/m2 1.71
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 40 of 88
Sr. No.
Description Unit Parameter
34 Vacuum withstand capability main tank, radiators and accessories
mm of Hg *
35 Weight
35.1 Core kg To be furnished during detailed engineering
35.2 Net copper wt. HV/LV kg ------do------
35.3 Oil kg ------do------
35.4 Tank, coolers & fittings kg ------do------
35.5 Total kg ------do------
35.6 Untanking weight kg ------do------
36 Cooling fans, oil pumps rating kW ------do------
37 Capability of transformer to remain in operation from hot conditions after failure of forced cooling with full load
minutes ------do------
38 On-line dissolved Gas Analyser Provided?
Yes/No no
39 Fibre optic based direct hot spot temperature measurement System Provided?
Yes/No no
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 41 of 88
1.6 Distribution Transformers
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 42 of 88
Sr. No.
Description Unit Parameter
1 Transformer applications Distribution
2 Type & make As per vendor list
3 Applicable standard *
4 Quantity No(s). 3
5 Full load rating (ONAN/ONAF) MVA 125
6 Rating of each windings MVA 104/125
7 Rating no load voltage HV/LV kV 90/33
8 Rating of different cooling methods ONAN/ONAF
9 Impedance value % 15
10 Rated frequency Hz 50
11 Winding connection of different windings and vector group
YNYnO
12 System Earthing (HVLV) Both
13 Type of tap changer off circuit/on load OLTC
14 Full power tapping provided Yes/No Yes
15 Type of voltage variation (CFVV/VFVV/CBVV)
CFVV
16 Over fluxing capability For Over fluxing Factor 1.1 : Continuous1.25 : 60 Sec1.4 : 10 Sec.
17 Winding insulation type uniformly or non-uniformly insulated
17.1 HV Non Uniform
17.2 LV Uniform
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 43 of 88
Sr. No.
Description Unit Parameter
18 Highest system voltage kV 90
19 Power frequency withstand voltage of winding
19.1 HV kV rms 185
19.2 LV kV rms 70
20 Standard rated lightning impulse withstand voltage
20.1 HV kV p 650
20.2 LV kV p 200
21 Maximum temperature rise at full load with 100% coolers :
21.1 Oil oC 40
21.2 Winding oC 45
22 Bushing particulars.
22.1 Applicable standard for bushing IS-2099
22.2 Clearance in air HV/LV/Neutral (between phases and phase to earth)
As per tech spec
22.2.1
HV (P-P) mm As per tech spec
22.2.2
HV (P-E) mm As per tech spec
22.2.3
LV (P-P) mm As per tech spec
22.2.4
HV - N mm As per tech spec
22.3 Quantity of oil in oil filled bushing litre To be furnished during detailed engineering
22.4 Creepage distance mm/kV 31
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 44 of 88
Sr. No.
Description Unit Parameter
23 No load loss at 100% rated voltage & frequency
kW
24 Load loss at rated current with 75 deg C
kW
25 Cooler loss at full load kW
26 Efficiency (0.85 Pf)
26.1 Full load
26.2 75% load
27 No load current A(approx)
28 Total estimated weight Kgs
29 OCTC/OLTC OCTC
29.1 Make As per approved vendor list provided
29.2 Rated Voltage Volts 110KV
29.3 Rated Current Amps 800
29.4 No. of steps 13
29.5 Step Voltage Volts +/- 2.5% at a step of 2.5%
29.6 Time of operation from one step to other for Auto / manual mode
Sec. 5-7
30 Type of axial and radial coil supports for HV/LV
*
31 No. of cooler banks and capacity of each cooler bank
2X50% as per requirement
32 Guaranteed No load current *
31.1 When excited from LV side at 100% and 110% rated voltage
Amps *
33 Max. Flux density when rated and 110% rated voltage
Wb/m2 1.71
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 45 of 88
Sr. No.
Description Unit Parameter
34 Vacuum withstand capability main tank, radiators and accessories
mm of Hg *
35 Weight
35.1 Core kg To be furnished during detailed engineering
35.2 Net copper wt. HV/LV kg ------do------
35.3 Oil kg ------do------
35.4 Tank, coolers & fittings kg ------do------
35.5 Total kg ------do------
35.6 Untanking weight kg ------do------
36 Cooling fans, oil pumps rating kW ------do------
37 Capability of transformer to remain in operation from hot conditions after failure of forced cooling with full load
minutes ------do------
38 On-line dissolved Gas Analyser Provided?
Yes/No no
39 Fibre optic based direct hot spot temperature measurement System Provided?
Yes/No no
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 46 of 88
1.7 Unit Auxiliary Transformer
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 47 of 88
Sr. No. Description Unit Parameter
1 Transformer applications Auxiliary
2 Type & make As per vendor list
3 Applicable standard As per IS/EDF standards
4 Quantity No(s). 2
5 Full load rating (ONAN/ONAF) MVA 10
6 Rating of each windings MVA 10
7 Rating no load voltage HV/LV kV 11/6.9
8 Rating of different cooling methods ONAN/ONAF
9 Impedance value % 8
10 Rated frequency Hz 50
11 Winding connection of different windings and vector group
Dyn1
12 System Earthing (HVLV) LV
13 Type of tap changer off circuit/on load OLTC
14 Full power tapping provided Yes/No Yes
15 Type of voltage variation (CFVV/VFVV/CBVV)
CFVV
16 Over fluxing capability For Over fluxing Factor 1.1 : Continuous1.25 : 60 Sec1.4 : 10 Sec.
17 Winding insulation type uniformly or non-uniformly insulated
17.1 HV Non Uniform
17.2 LV Uniform
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 48 of 88
Sr. No. Description Unit Parameter
18 Highest system voltage kV 12
19 Power frequency withstand voltage of winding
19.1 HV kV rms 20
19.2 LV kV rms 2
20 Standard rated lightning impulse withstand voltage
20.1 HV kV p 50
20.2 LV kV p 24
21 Maximum temperature rise at full load with 100% coolers :
21.1 Oil oC 55
21.2 Winding oC 45
22 Bushing particulars.
22.1 Applicable standard for bushing IS-2099
22.2 Clearance in air HV/LV/Neutral (between phases and phase to earth)
As per IEC/EDF spec
22.2.1 HV (P-P) mm As per IEC/EDF spec
22.2.2 HV (P-E) mm As per IEC/EDF spec
22.2.3 LV (P-P) mm As per IEC/EDF spec
22.2.4 HV - N mm As per tech spec
22.3 Quantity of oil in oil filled bushing litre To be furnished during detailed engineering
22.4 Creepage distance mm/kV 31
23 No load loss at 100% rated voltage & frequency
kW 12 KW
24 Load loss at rated current with 75 deg C
kW
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 49 of 88
Sr. No. Description Unit Parameter
25 Cooler loss at full load kW 2 KW
26 Efficiency (0.85 Pf)
26.1 Full load 99.47
26.2 75% load 99.57
27 No load current A(approx)
28 Total estimated weight Kgs To be decided during DE
29 OCTC/OLTC OLTC
29.1 Make As per approved vendor list provided
29.2 Rated Voltage Volts
29.3 Rated Current Amps
29.4 No. of steps
29.5 Step Voltage Volts
29.6 Time of operation from one step to other for Auto / manual mode
Sec. *
30 Type of axial and radial coil supports for HV/LV
*
31 No. of cooler banks and capacity of each cooler bank
32 Guaranteed No load current *
31.1 When excited from LV side at 100% and 110% rated voltage
Amps *
33 Max. Flux density when rated and 110% rated voltage
Wb/m2 *
34 Vacuum withstand capability main tank, radiators and accessories
mm of Hg *
35 Weight
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 50 of 88
Sr. No. Description Unit Parameter
35.1 Core kg To be furnished during detailed engineering
35.2 Net copper wt. HV/LV kg ------do------
35.3 Oil kg ------do------
35.4 Tank, coolers & fittings kg ------do------
35.5 Total kg ------do------
35.6 Untanking weight kg ------do------
36 Cooling fans, oil pumps rating kW ------do------
37 Capability of transformer to remain in operation from hot conditions after failure of forced cooling with full load
minutes ------do------
38 On-line dissolved Gas Analyser Provided?
Yes/No no
39 Fibre optic based direct hot spot temperature measurement System Provided?
Yes/No no
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 51 of 88
1.8 Unit Station Transformer/Station Service Transformer
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 52 of 88
Sr. No. Description Unit Parameter
1 Transformer applications Auxiliary
2 Type & make As per vendor list
3 Applicable standard As per IS/EDF std.
4 Quantity No(s). 4
5 Full load rating (ONAN/ONAF) MVA 2.5
6 Rating of each windings MVA 2.5
7 Rating no load voltage HV/LV kV 6.6/0.433
8 Rating of different cooling methods ONAN
9 Impedance value % 7.2
10 Rated frequency Hz 50
11 Winding connection of different windings and vector group
Dyn11
12 System Earthing (HVLV) LV
13 Type of tap changer off circuit/on load OLTC
14 Full power tapping provided Yes/No Yes
15 Type of voltage variation (CFVV/VFVV/CBVV)
CFVV
16 Over fluxing capability For Over fluxing Factor 1.1 : Continuous1.25 : 60 Sec1.4 : 10 Sec.
17 Winding insulation type uniformly or non-uniformly insulated
17.1 HV Non Uniform
17.2 LV Uniform
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 53 of 88
Sr. No. Description Unit Parameter
18 Highest system voltage kV 12
19 Power frequency withstand voltage of winding
19.1 HV kV rms 20
19.2 LV kV rms 2
20 Standard rated lightning impulse withstand voltage
20.1 HV kV p 50
20.2 LV kV p 24
21 Maximum temperature rise at full load with 100% coolers :
21.1 Oil oC 55
21.2 Winding oC 45
22 Bushing particulars.
22.1 Applicable standard for bushing IS-2099
22.2 Clearance in air HV/LV/Neutral (between phases and phase to earth)
As per IEC/EDF spec
22.2.1 HV (P-P) mm As per IEC/EDF spec
22.2.2 HV (P-E) mm As per IEC/EDF spec
22.2.3 LV (P-P) mm As per IEC/EDF spec
22.2.4 HV - N mm As per tech spec
22.3 Quantity of oil in oil filled bushing litre To be furnished during detailed engineering
22.4 Creepage distance mm/kV 31
23 No load loss at 100% rated voltage & frequency
kW 2.5
24 Load loss at rated current with 75 deg kW 23
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 54 of 88
Sr. No. Description Unit Parameter
C
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 55 of 88
Sr. No. Description Unit Parameter
25 Cooler loss at full load kW
26 Efficiency (0.85 Pf)
26.1 Full load 98.75
26.2 75% load 98.99
27 No load current A(approx)
28 Total estimated weight Kgs 7150
29 OCTC/OLTC OLTC
29.1 Make As per approved vendor list provided
29.2 Rated Voltage Volts
29.3 Rated Current Amps
29.4 No. of steps
29.5 Step Voltage Volts
29.6 Time of operation from one step to other for Auto / manual mode
Sec. *
30 Type of axial and radial coil supports for HV/LV
*
31 No. of cooler banks and capacity of each cooler bank
32 Guaranteed No load current *
31.1 When excited from LV side at 100% and 110% rated voltage
Amps *
33 Max. Flux density when rated and 110% rated voltage
Wb/m2 *
34 Vacuum withstand capability main tank, radiators and accessories
mm of Hg *
35 Weight
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 56 of 88
Sr. No. Description Unit Parameter
35.1 Core kg To be furnished during detailed engineering
35.2 Net copper wt. HV/LV kg ------do------
35.3 Oil kg ------do------
35.4 Tank, coolers & fittings kg ------do------
35.5 Total kg ------do------
35.6 Untanking weight kg ------do------
36 Cooling fans, oil pumps rating kW ------do------
37 Capability of transformer to remain in operation from hot conditions after failure of forced cooling with full load
minutes ------do------
38 On-line dissolved Gas Analyser Provided?
Yes/No no
39 Fibre optic based direct hot spot temperature measurement System Provided?
Yes/No no
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 57 of 88
1.6 High Medium Voltage Switchgear
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 58 of 88
Sr. No.
Description Unit Parameter
1 Manufacturer’s name As per approved vendor list provided
2 Applicable Standard As per IS/EDF
3 Nominal system voltage, phase & frequency
33 ± 10%, Three, 50 Hz ± 5%
4 System neutral earthing considered earthed
5 Max. system voltage V 36
6 One minute power frequency withstand voltage
1.2/50 uS impulse withstand voltage
kV rms
k V peak
70
170
7 Switching over voltages generated and time to crest
kV p / microsec
a) Switching off motor with its rotor locked
To be furnished during detailed engineering
b) Switching off unloaded transformer *
8 Ref. ambient temperature Deg. C 50°C
9 S. C. Current withstand capability (current / duration)
a) Short time for 1 sec kA rms 31.5
b) Dynamic rating kA peak 2.5 x rated short time current
10 Cable entry From bottom
11 Bus bar As per Sld
a) Material As per Sld
b) Continuous current rating A As per Sld
c) Max. temp. of bus bars, dropper, Deg. C To be furnished during detailed engineering
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 59 of 88
Sr. No.
Description Unit Parameter
connectors & contacts at continuous current rating under site reference ambient temperature.
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 60 of 88
Sr. No.
Description Unit Parameter
12 Thickness of sheet steel enclosures/doors.
mm 2/2.5 CRCA
a) Cold rolled 2
b) Hot rolled 2.5
13 Degree of protection
a) Bus Bar IPH4
b) For others IPH6
c) For complete switchgear IP4X
14 Paint shade RAL7032
15 Earthing bus bar size & material considered
50X6mm,Copper
16 Clearance in air of live faults
a) Phase to phase Mm As per IEC/EDF Standards
b) Phase to earth mm As per IEC/EDF Standards
17 Circuit breakers
a) Manufacturer As per approved vendor list provided
b) Type of circuit breaker Vacuum
c) Rated operating duty Continuous(O -3m -CO -3m – CO)
d) Rated currents under site ambient temp.(for each type of breaker)
To be furnished during detailed engineering
e) Rated symmetrical breaking current kA rms As per IEC/EDF Standards
f) Making current kA peak As per IEC/EDF Standards
g) S.C current withstand & duration
Short time for 1 sec kA rms 31.5
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 61 of 88
Sr. No.
Description Unit Parameter
Dynamic rating kA peak 2.5 x rated short time current
h) Asymmetrical breaking current
AC component As per IEC/EDF Standards
DC component As per IEC/EDF Standards
t) Operating time
Opening time Cycles Not more than 60
Closing time Cycles Not more than 100
j) Closing & Opening coil particulars Two trip coils
k) Switching over voltage As per IEC/EDF Standards
l) Trip free operating mechanism type Spring charged motor
m) Aux. control voltage for trip, close, annunciation & spring charging
Close- 220V DC, 2W (+10% to –15%)
Trip-220V DC, 2W (+10% to –30%)
Spring-220V DC, 2W (+10% to –15%)
n) Aux. control voltage for space heater, DC failure annunciation, motor winding/ space heaters, lighting etc
240V ± 10%, 1 Ph, 2W
p) Breakers application
Transformer control YES
Motor control NO
q) Type of external switching over-voltage limiting device provided
19 CTs To be furnished during detailed engineering
a) Type *
b) Ratio
c) Burden *
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 62 of 88
Sr. No.
Description Unit Parameter
d) Accuracy class *
e) Knee point Voltage
f) Magnetising current @ Vk/2
g) Secondary resistance
h) Class of Insulation
i) Short time & Dynamic current rating
j) Applicable Standard
k) No. of Cores
20 Details of CBCTs To be furnished during detailed engineering
21 VTs
a) Type *
b) Ratio
c) Burden
d) Acuracy class
e) Magnetising Characterstics
f) Method of connection
g) Class of Insulation
h) Rated Voltage factor (Continuous & 08 hours)
i) Applicable Standard
j) No. of Cores
22 Earthing arrangement for
a) Bus bar side *
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 63 of 88
Sr. No.
Description Unit Parameter
b) Cable side *
24 Details of LA/SA
25 Particulars of Breaker handling Tools
27 Particulars of meters
28 Particulars of Relays
29 Particulars of Spring charging motor
30 Panel construction details
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 64 of 88
1.7 Low Voltage switchgear
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 65 of 88
Sr. No.
Description Unit Parameter
1 Manufacturer's name As per approved vendor list
2 Applicable Standard As per IEC/French standards
3 Nominal system voltage, phase &
frequency
V 6600± 10%
4 System neutral earthing considered Three5 Maximum system voltage V 6900
5.1 One minute power frequency
withstand voltage
kV rms 20 kV ( r.m.s)
5.2 1.2/50 µSec impulse withstand voltage kV peak 60 kV ( peak)6 Short Circuit withstand capability
6.1 Short time for 1 sec kA rms 40 kA6.2 Dynamic rating kA peak 100 kA7 Reference ambient temperature Deg. C 50°C
8 Continuous current rating under site
reference ambient condition
A As per SLD
9 Maximum temperature of Bus Bars,
dropper, connectors & contacts at
continuous current rating under site
reference ambient temperature
Deg. C 40ºC for plain joints
50ºC for Silver plated joints
10 Material of bus bars considered Copper
11 Cable entry a) Power Cables-Bottom
b) Control Cables- Bottom12 Degree of protection
13 Thickness of sheet steel
enclosures/doors
13.1 Cold Rolled mm 2
13.2 Hot Rolled mm 2.5
14 Shape of paints
15 Earthing bus bar size & material
considered
mm 150X12mm2 copper
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 66 of 88
Sr. No.
Description Unit Parameter
16 Clearance in air of live parts As per IEC/French Standards
16.1 phase to phase mm As per IEC/French Standards
16.2 phase to earth mm As per IEC/French Standards
17 Circuit Breaker
a) type Vaccum / SF6b) rated operating duty 0-3-CO-3-COc) rated current at site reference ambient
temp.
Amps 1600
d) rated breaking current kA rms As per IEC/French Standards
e) rated making current kA rms As per IEC/French Standards
f) short time current withstand capacity
for 1 sec duration
kA peak As per IEC/French Standards
g) asymmetrical breaking current
1) ac component kA rms As per IEC/French Standards
2) dc component kA rms As per IEC/French Standards
h) operating time
1) opening time sec Not more than 60 2) closing time sec Not more than 100i) closing and opening coil particulars cycle
j) switching over voltage factor As per IEC/French Standards
18 Trip free operating mechanism type Motor wound spring charged
stored energy
19 Auxilary control voltage for trip,
close, annunciation & spring charging
220 V DC (85%-110%)
20 Auxilary control voltage for space
heater, DC failure annunciation, motor
winding/space heaters, lighting etc
220 V DC (85%-110%)
21 Breaker application
a) incomers & ties As per requirement
b) outgoing As per requirement
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 67 of 88
Sr. No.
Description Unit Parameter
22 Details of contractors/switches/fuses
a) type Cast resin bar primary
b) rated operating duty
c) rated current at site reference
ambient temp.
d) rated breaking current As per IEC/French Standards
e) rated making current As per IEC/French Standards
f) short time current withstand
capacity for 1 sec duration
As per IEC/French Standards
g) asymmetrical breaking current As per IEC/French Standards
1) ac component
2) dc component
h) operating time
1) opening time
2) closing time
23 Details of CTs To be furnished during detailed
engineering
a) type
b) ratio
c) burden
d) accuracy class
e) knee point voltage
f) magnetizing current at Vk/2
g) secondary resistance
h) class of insulation
i) short time & dynamic current rating
j) applicable standard
k) no. of cores 3
24 Details of VTs To be furnished during detailed
engineering
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 68 of 88
Sr. No.
Description Unit Parameter
a) type
b) ratio
c) burden
d) accuracy class
e) magnetizing characteristic
f) method of connection
g) class of insulation
h) rated voltage factor (continuous & 8
hours)
i) applicable standard
j) no of cores
25 Particulars of meters
26 Particulars of relays
27 Panel construction details
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 69 of 88
1.8 Motor
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 70 of 88
Sr. No.
Description Unit Parameter
AC Motor
1.0 Application/Designation
2.0 Name of the Manufacturer As per approved vendor list
provided
3.0 Type of motors/ frame size Squirrel cage three/single phase
induction
4.0 Rated
4.1 Output kW 0.22,160-4000
4.2 Speed rpm 3000
4.3 Voltage V 230/400,6.6
4.4 No.of Phases / Frequency 3/1,50Hz
4.5 System neutral As per requirement
5.0 Type of Duty As per IEC/French Standards
5.1 Type of Duty (IS-325 or equivalent) As per IEC/French Standards
5.2 Duty designation (IS-325 or
equivalent)
As per IEC/French Standards
6.0 Supply Conditions
6.1 (a) Allowable variations in
6.2 Voltage % ± 10%
6.3 Frequency % ± 5%
6.4 Combined % 10% (absolute sum) + frequency
6.5 Permissible unbalance in supply
voltage
% 80
7.0 Current To be furnished during DE
7.1 Full load Amps To be furnished during DE
7.2 Starting % FL To be furnished during DE
8.0 Method of starting To be furnished during DE
8.1 Starting time Sec To be furnished during DE
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 71 of 88
Sr. No.
Description Unit Parameter
8.1.1 With rated Voltage To be furnished during DE
8.1.2 With min. Voltage To be furnished during DE
8.1.3 With Max. Voltage To be furnished during DE
8.2 Safe stall time under hot/cold
condition
Sec To be furnished during DE
8.2.1 With rated Voltage To be furnished during DE
8.2.2 With min. Voltage To be furnished during DE
8.2.3 With Max. Voltage To be furnished during DE
9.0 Insulation To be furnished during DE
9.1 Class of insulation To be furnished during DE
9.2 Temperature rise by winding
resistance method
Deg. C To be furnished during DE
10.0 Type of cooling (IS : 6362) Deg. C To be furnished during DE
11.0 Degree of protection (IS:4691 or
equivalent)
To be furnished during DE
12.0 Suitable for outdoor operation Yes / No To be furnished during DE
13.0 Normal winding connection Star /
Delta
To be furnished during DE
14.0 Permissible No. of equally spread
starts per hour under normal service
conditions
To be furnished during DE
15.0 Efficiency (%) % To be furnished during DE
15.1 Full load To be furnished during DE
15.2 75 % Load To be furnished during DE
15.3 50 % Load To be furnished during DE
15.4 25 % Load To be furnished during DE
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 72 of 88
Sr. No.
Description Unit Parameter
16.0 Power Factor
16.1 Full Load
16.2 75 % Load
16.3 50 % Load
16.4 25 % Load
17.0 Torque To be furnished during DE
17.1 Starting To be furnished during DE
17.2 Maximum (Pullout) To be furnished during DE
17.3 Pull up To be furnished during DE
18.0 Motor reactance (pu) To be furnished during DE
18.1 Subtransient To be furnished during DE
18.2 Transient To be furnished during DE
18.3 Steady state To be furnished during DE
19.0 Fault level kA/sec
DC MOTORS
1.0 Rated Voltage V 125
2.0 Class of Insulation As per IEC/EDF
3.0 Temperature rise *
4.0 Method of starting *
Items under AC motors which are applicable for DC motors shall also be listed
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 73 of 88
1.9 Diesel Generator Set
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 74 of 88
Sr. No.
Description Unit Parameter
1.0 Diesel Engine – General Data
1.1 Manufacturer’s name, make, model number
As per approved vendor list provided
1.2 Standard rating at ISO conditions KW 1.6
1.3 De-rating factors due to:
1.3.1 Harmonics %
1.3.2 Altitude %
1.3.3 Inlet air temperature %
1.3.4 Humidity %
1.3.5 Cooling water temperature %
1.3.6 Overall de-rating factor (max. 10%) %
1.4 Conditions output at site conditions KW
1.5 Maximum engine rating at site conditions with 10% overload
KW
1.6 Number of cylinders
1.7 Arrangement of cylinders
1.8 Direction of rotation as viewed from free end
1.9 Operating speed RPM Not more than 750
1.10 Number of strokes 4
1.11 Piston speed M/sec
1.12 Minimum acceptable lube oil temperature at start-up
0C
1.13 Maximum period for which the engine can operate without cooling water supply
Min
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 75 of 88
Sr. No.
Description Unit Parameter
1.14 Foundation bolts and anti vibration pads to be provided
Yes
2.0 Turbo charger / Super charged
2.1 Manufacturer
2.2 Speed RPM
3.0 Fuel oil system
3.1 Day tank *
3.2 Number of days tanks *
3.3 Capacity-Each Litres *
3.4 Material of construction
3.5 Thickness of shell
3.6 Hand operated fuel oil pump provided *
3.7 Filters
3.8 Type
3.9 Number
4.0 Lube oil system
4.1 Filters *
4.1.1 Type *
4.1.2 Number
4.1.3 Grade of lube oil to be used
4.2 AC/DC motor driven standby pump, if any, to be included
4.3 AC motor driven primary oil pump with Clock timer
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 76 of 88
Sr. No.
Description Unit Parameter
5.0 Engine cooling system
5.1 Cooling water/make-up water quality acceptable
*
5.1.1 If no, indicate requirement
5.2 Cooling water flow rate
5.2.1 Engine cooling circuit LPM
5.2.2 Lube oil cooler LPM
5.2.3 Turbocharger cooler LPM
5.2.4 Total 5.2.1 to 5.2.3 LPM
5.3 Expansion tank
5.3.1 Capacity Litres
5.3.2 Material of construction
5.3.3 Thickness Mm
5.4 By-pass control valves to be included *
5.5 Temperature of cooling water
5.5.1 At engine inlet 0C
5.5.2 At engine outlet 0C
6.0 Air intake and exhaust
6.1 Intake filter type *
6.2 Exhaust silencer type *
6.3 Maximum back pressure mmWc
7.0 Stack
7.1 Flow rate of flue gases leaving DG M3/Hr
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 77 of 88
Sr. No.
Description Unit Parameter
7.2 Temperature of flue gas leaving DG set/entering stack
0C
7.3 Density of flue gases at stack inlet Kg/ M3
7.4 Stack diameter x height M
7.5 Number of flue gas openings
7.6 Flue gas connection size M
7.7 Height of flue gas connection centre-line above the foundation level
M
8.0 Heat exchangers
8.1 Type of construction
8.2 Shell side
8.2.1 Flow rate of fluid circulated
8.2.2 Inlet/Outlet temperature 0C
8.3 Type side
8.3.1 Fluid circulated Cooling water
8.3.2 Flow rate of fluid circulated Kg/Hr
8.3.3 Inlet/Outlet temperature 0C
8.4 Material specification
8.4.1 Shell/frame (for plate type)
8.4.2 Tubes/plates (for plate type)
8.4.3 Tube sheets/end plate (for plate type)
8.5 Bolts/Nuts
8.6 Gaskets
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 78 of 88
Sr. No.
Description Unit Parameter
8.7 Radiator
8.7.1 Material of construction
8.7.2 Fan motor rating KW
9.0 Generator and accessories
9.1 Manufacturer’s Name
9.2 Design rating KW
9.3 Continuous output rating KW
9.3.1 Nominal ISO rating KW
8.3.2 Maximum rating at site KW
9.3.3 De-rated output under harmonic loading
KW
9.4 Power factor
9.5 Rated voltage V
9.6 Rated current / Phase Amps
9.7 Speed RPM
9.8 Frequency Hz
9.9 Field current at rated output and voltage Amps
9.10 Insulation class
9.10.1 Stator
9.10.2 Rotor
9.11 Temperature rise above ambient of 500
(By thermometer)
9.11.1 Stator 0C
9.11.2 Rotor 0C
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 79 of 88
Sr. No.
Description Unit Parameter
9.11.3 Cores 0C
9.12 Moment of inertia of rotating mass in diesel engine, generator, exciter etc.,
Kg/M2
9.13 Efficiency
9.13.1 50% load / 75% load / Full load % / /
9.14 Largest motor allowed to start within 15% maximum allowable starting voltage DIP
KW
9.14.1 With DOL starter/Star delta starter
9.15 KW rating of space heaters KW
9.16 Transient reactances
9.16.1 X’d %
9.16.2 X” d %
9.17 Degree of protection
10.0 Main exciter
10.1 Rated voltage
10.2 Rated current
10.3 Ceiling voltage at zero load and rated speed
V
10.4 Ceiling voltage at rated current and rated speed
V
10.5 Excitation system response ratio
10.6 Insulation class
10.6.1 Stator
10.6.2 Rotor
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 80 of 88
Sr. No.
Description Unit Parameter
11.0 Automatic voltage regulator
11.1 Type
11.2 Burden of AVR on CTs and PTs
11.2.1 CT’s VA
11.2.2 PT’s VA
11.3 Dead band, if any
11.4 Field discharge resistor Ohms
11.5 Type and rating of field breaker
12.0 Performance guarantees
12.1 Continuous output at site conditions KW *
12.2 10% overload for one(1) hour out of a total of 12 consecutive hours of operation without over heating
KW *
12.3 Fuel oil consumption at 50%, 75% and full load
Gms/KWHr *
12.4 Lube oil consumption Gms/KWHr
12.5 Cooling water temperature at
Engine
Outlet 0C
*
12.6 Cooling water pressure drop Kg/cm2
12.7 Noise level dB(A)
13.0 Weight schedu1e
13.1 Weight of engine and standard accessories excluding the weight of flywheel
Kg
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 81 of 88
Sr. No.
Description Unit Parameter
13.2 Weight of flywheel Kg
13.3 Total shipping weight Kg
13.3.1 Weight of generator Kg
13.3.2 Weight of control panel Kg
13.4 Weight of single heaviest piece to be handled during :
13.4.1 Erection Kg
13.4.2 Maintenance Kg
14.0 Dimensions
14.1 Shipping dimensions *
14.1.1 Engine L x B x H M
14.1.2 Generator L x B x H M
15.0 Miscellaneous
15.1 General arrangement drawing to be enclosed
*
15.2 P&I diagram to be enclosed *
15.3 Total heat dissipation from DG set Kcal/Her
15.4 Ventilation requirements to be enclosed *
15.5 Synchronising scheme as per requirement
*
15.6 Protection scheme to be enclosed *
15.7 Suitability of operation for the load
Pattern assumed
*
16.0 CODES & STANDARDS
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 82 of 88
Sr. No.
Description Unit Parameter
16.1 BS-5514/ISO-3046 Specification for reciprocating internal combustion engine (Part (I-VI)
*
*
16.2 BS-5000 : Part 99 – Machines for miscellaneous application
*
16.3 IS-4722 – Rotary electrical machinery *
16.4 VDI – 2063 : Measurement and evaluation of mechanical vibrations of reciprocating piston engines and piston compressors
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 83 of 88
1.10 DC Battery and Battery ChargerSr. No.
Description Unit Parameter
1.0 Name of the Manufacturer (Ni-Cd
battery)
As per approved vendor list
provided
1.1 Application DC load requirements
1.2 No. of battery Bank required . Nos To be furnished during DE
1.3 Reference ambient temperature for
design of electrical devices
0C 50
1.4 DC system voltage V 220
1.5 Ampere hour capacity of battery at27
deg. C temperature for 5 HOURS rate
Ah 1350 AH
1.6 Discharge duty considered for battery
sizing
1.7 a) Required area of battery and
charger room
b) Battery orientation/ mounting
arrangement
a)To be furnished during DE
b)Steel Rack
1.8 Charging method proposed Float-cum-boost charger
1.9 Battery charger rating required to
charge the battery in 10 hrs from
fully discharged conditions (both
Voltage and current range to be
specified).
2.15 to 2.25 Volts per cell
1.10 No. of cells per set To be furnished during DE
1.11 Open circuit voltage of each cell
1.12 Capacity factor considered for
battery sizing
*
1.13 The details of de-rating factor
considered for temperature correction,
*
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 84 of 88
Sr. No.
Description Unit Parameter
ageing, future margin considered
( min. 10 %) and any
other required as per relevant
standard
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 85 of 88
Sr. No.
Description Unit Parameter
1.14 Type of enclosure *
1.15 Type of battery cell *
1.16 Life of the battery Hour *
1.17 No. of full charge-discharge cycles in
a life
Nos. *
1.18 Recommended charging and
discharging rate
Normal operation
Quick charging
First charging
*
2.0 BATTERY CHARGER
2.1 Number of charger required Nos. To be furnished during DE
2.2 Type Solid-state (thyristor based), full wave, fully
controlled (6 pulse), three phase bridge for
continuous application
2.3 DC system voltage (nominal) Volts 230-240 Volt
2.4 DC system earthing ungrounded
2.5 Ambient design temperature Deg.C 50ºC
2.6 DC bus load considered with break up
a) Short time loadb) Continuous loadc) Starting current of largest
connected DC motor
Amp
For sec
2.7 Battery charger current and voltage rating
Float
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 86 of 88
Sr. No.
Description Unit Parameter
Boost
2.8 Float/Trickle charging current of battery
*
2.9 Maximum Boost charging current of battery
Max. Boost charging voltage battery
Amp
Volt
*
2.10 Max. time for Boost charging of battery
Hours *
2.11 AC system data
Supply 415V, 3phase, 50Hz, 4wire
Variation in supply % Voltage variation-10%
Frequency variation-5%
Short circuit level kA 50 kA(rms) symmetrical
Type of earthing Solidly earthed
2.12 Performance
DC voltage setting adjustment for float charger
% 1
Maximum permissible variation in DC voltage (No load to full load)
% Within 1% of the set value
DC voltage setting adjustment for boost charging at constant voltage
1
DC volt adjustment for boost charging
*
Minimum permissible power factor at rated continuous load
*
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 87 of 88
Sr. No.
Description Unit Parameter
2.13 Voltage stabilisation for constant voltage regulator
% *
2.14 Cable entry *
2.15 Permissible ripple content at rated continuous load
Without battery % 1
with battery % 1
2.16 Peak inverse voltage of power devices
v *
2.17 Thyristor bridge cooling *
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 88 of 88
1.11 UPS
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 89 of 88
Sr. No.
Description Unit Parameter
1.0 Name of the Manufacturer As per approved vendor list
provided
1.1 Type Ni-Cd
1.2 Power Rating at load PF 0.8 lagging As per tech specs
1.3 Application Critical Power supply
1.4 Quantity (Nos.) 1
1.5 Method of energy storage Static
1.6 Designation *
1.7 Whether transfer switch required for
secondary back up
Yes
1.8 Installation
1.9 Temperature
1.9.1 Ambient
For Operation 0C 50
For Storage 0C 50
1.9.2 Ref. Design Temp. 0C *
2.0 Enclosure Sheet steel, IP42
2.1 Material
2.2 Sheet thickness mm *
2.3 Degree of Protection as per IS-247 IP32
2.4 Painting
Exterior To be decided during DE
Interior To be decided during DE
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 90 of 88
Sr. No.
Description Unit Parameter
2.5 Cable entry From bottom
2.6 Acoustic noise level As per IEC/EDF standards
3.0 UPS system
3.1 Input 190-302
3.1.1 Supply voltage with 230
Isolation transformer.
3.1.2 Allowable variation
Voltage % 10%
Frequency % 5%
Combined voltage + Frequency %
3.2 Output
3.2.1 Output voltage 230
3.2.2 AC voltage accuracy (Steady state)
over entire load, load PF & DC
voltage range
% 2%
3.2.3 Transient voltage regulation +/-2
3.2.4 Transient Recovery 50msec
3.2.5 Voltage wave form
3.2.6 Range of adjustment of AC output
voltage
50+_ 0.5 Hz to 50+_ 2 Hz
3.2.7 AC harmonic content 3% maximum
3.2.8 Nominal frequency 50 Hz
3.2.9 Frequency regulation 5%
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 91 of 88
Sr. No.
Description Unit Parameter
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 92 of 88
Sr. No.
Description Unit Parameter
4.0 DC Link (Battery)
4.1 No. of 100% capacity batteries 2X100
4.2 Type of battery cell Lead Acid Plante/ stationary Nickel Cadmium type
4.3 DC link voltage *
4.4 DC voltage variation range *
4.5 Battery support time 1 hour
4.6 Mounting arrangement Steel racks
5.0 Battery Charger
(Rectifier Unit)
5.1 No. of chargers 2X100%
5.2 Rectifier Unit Full wave
5.3 Type Solid-state, full wave fully controlled. 3Phase Bridge.
5.4 Parallel operation
5.5 Recharge time on boost charge 5hrs
5.6 In rush current
5.7 Battery parallel operation
6.0 Inverter
6.1 No. of inverters in system To be decided during DE
6.2 Type of power switching device Static, Parallel Dual Redundant
6.3 Current capacity
6.3.1 Over load 125% of rated KVA & p.f for 10 minutes
6.3.2 Short time withstand 500% for 5 msec
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 93 of 88
Sr. No.
Description Unit Parameter
6.3.3 Over current setting range
6.3.4 Synchronising
- Between inverters yes
- Between inverters and standby
supply
yes
6.4 Synchronising range To be decided during DE
7.0 Static Switch
7.1 Type Solid-state, SCR
7.2 No. of switches To be decided during DE
7.3 Rating To be decided during DE
7.4 Nominal Frequency 50Hz
7.5 Maximum transfer time 1/4th cycle maximum.7.6 Short time rating 50KA
7.7 Whether make before break Yes
8.0 Static voltage stabilizer with step-
down transformers.
8.1 Input.
8.1.1 Input voltage
8.1.2 Allowable variation
Voltage *
Frequency *
8.2 Output
8.2.1 Out put voltage *
8.2.2 Out put voltage accuracy % *
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 94 of 88
Sr. No.
Description Unit Parameter
8.3 Over load *
9.0 Redundant A.C. Distribution board
with required No. of feeders along
with 20% spare feeders, adequate
protection & meeting.
10.0 Ground detector system *
11.0 Manual Bypass switch & isolators. *
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 95 of 88
1.12 Illumination
Sr. No.
Description Unit Parameter
1.0 Make of light fittingsAs per approved vendor list
provided
2.0 Make of main DBAs per approved vendor list
provided
3.0 Make of sub-lighting DBAs per approved vendor list
provided
4.0Type of fitting for periphery lighting and control for same
5.0 Cable laying method As per IEC/EDF standards
6.0 Control operations: Continuous
7.0 Escape lighting
8.0 Type of cable proposed As per IEC/EDF standards
9.0 Make of light fittings As per approved vendor list provided
10.0 Make of cables As per approved vendor list provided
11.0 Type of fittings at various locations As per IEC/EDF standards
12.0DC emergency lighting control board with necessary contactor.
Yes
13.0Type of incomer for main and sub-DBs.
As per IEC/EDF standards
14.0 Type of outgoing for main and sub- As per IEC/EDF standards
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 96 of 88
Sr. No.
Description Unit Parameter
DBs
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 97 of 88
Sr. No.
Description Unit Parameter
15.0Second source of supply considered for all the areas
a)Degree of protection for main and sub-DB enclosure:
As per IEC/EDF standards
b)Mounting details for DBs: As per IEC/EDF standards
16.0Phase to phase and phase to earth clearances in main and sub-DBs:
As per IEC/EDF standards
17.0 Busbar arrangement in Sub-DBs:
18.0 Make of ballastAs per approved vendor list
provided
19 Make of cables …………….do………….
20 Make of switches …………….do………….
21Erection accessories such as junction boxes, clamps, saddles
…………….do………….
22 Make of ceiling fans …………….do………….
23 Make of exhaust fans …………….do………….
24Make of flame-proof fittings and catalogue numbers
…………….do………….
25 Rating of exhaust fans To be decided during DE
26Deviations, if any, on technical design data:
*
27 Make of switchesAs per approved vendor list
provided
28Erection accessories such as junction boxes, clamps, saddles
As per approved vendor list provided
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 98 of 88
For Outdoor Lighting
Sr. No.
Description Unit Parameter
1.0 Type of fittings envisaged:As per approved vendor list
provided
2.0 Make of fittings: …………….do………….
3.0 Lux level to be obtained: *
4.0 Provision of escape lighting:
5.0 Location of main and sub-DBs *
6.0 Control of lighting: *
7.0 Automatic / Manual:
8.0 Cable laying above ground:
9.0 Type of fittings envisaged: *
10.0 Make of fittings: *
11.0 Lux level to be obtained: *
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 99 of 88
1.13 Switchyard
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 100 of 88
Sr. No. Description Unit Parameter
1.0 RATING
1.0 Switchyard Design & layout
1.1 Rated Voltage kV 90
1.2 1.2/50 Micro sec impulse withstand voltage
kV *
1.3 One minute power frequency withstand voltage
kV *
1.4 Current ratings *
a) Continuous for Main buses Amp 2000 Amps
b) Phase to phase Amp -
c) Short time withstand current and duration
kA &sec 40kA for 1 sec
1.5 Minimum air clearance
a) Phase to phase mm 900 mm
b) Phase to ground mm 900 mm
c) Live point to ground mm 4600 mm
d) Section clearance mm 4600 mm
1.6 Bay width M 10
1.7 Phase to phase spacing M 2.5
1.8 Size of the i) switchyard L x B 136x90
ii) switchyard building L x B x H 136x90x15
1.9 Design tensions
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 101 of 88
a) Main bus Kg To be furnished during detail engineering
b) Bay bus Kg To be furnished during detail engineering
a) Overhead conductors for GT connection
Kg To be furnished during detail engineering
1.10 Total creepage distance for all equipment
Indoor
Out door
mm
Ref-31mm/KV
1.11 Protected creepage distance mm Ref-31mm/KV
1.12 Factor of safety adopted for the structural design
a) Normal condition To be furnished during detail engineering
b) Short circuit condition To be furnished during detail engineering
c) Seismic condition To be furnished during detail engineering
1.13 Type of design for Main & bay buses
a) Strung bus or tubular bus To be furnished during detail engineering
b) Material To be furnished during detail engineering
2.0 Circuit Breakers
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 102 of 88
2.1 Make, type, country of manufacture
As per approved vendor list provided
2.2 Applicable standard As per IEC/EDF Standards
2.3 Rated voltage kV As per IEC/EDF Standards
2.4 Type of circuit breaker (SF6) SF6
2.5 Reference ambient temperature 500C
2.6 Rated continuous current Amp 1600Amps
2.7 Rated short circuit breaking current and rated making current
kA 40 KA for 1 sec
100 KA(peak)
2.8 Temperature rise of contacts over an ambient of 450C while carrying rated current
0C As per IEC/EDF Standards
2.9 Rated operating duty 0-0.3 sec-C0-3mins-CO
2.10 Total break time msec To be furnished during detail engineering
2.11 Total make time msec To be furnished during detail engineering
2.12 Rated transient recovery voltage for terminal fault
kV To be furnished during detail engineering
2.13 Rated transient recovery voltage for short line faults
kV To be furnished during detail engineering
2.14 No. of breaks in series To be furnished during detail engineering
2.15 Insulation level
a) One minute P.F. withstand voltage
kV 185
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 103 of 88
b) Impulse withstand voltage kVp 450
c) Switching surge withstand voltage
kVp To be furnished during detail engineering
2.16 Minimum clearance in air
a) Between live parts mm Ref-SLD
b) Between live part & earth mm Ref-SLD
c) Centre to centre distance between phases
mm Ref-SLD
2.17 Fixed trip or trip free To be finalised during detail engineering
2.18 Type of operating mechanism Spring-spring
2.19 Normal method of tripping To be furnished during detail engineering
2.20 Emergency method of tripping To be furnished during detail engineering
2.21 No. of trip coils per phase 125 V DC
2.22 Range of voltage for
(a) Trip coils To be furnished during detail engineering
(b) Closing coils To be furnished during detail engineering
2.23 Rated line charging current To be furnished during detail engineering
2.24 Rated cable charging current To be furnished during detail engineering
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 104 of 88
2.25 Maximum over voltage when switching off
(a) Unloaded transformer To be furnished during detail engineering
(b) Unloaded lines To be furnished during detail engineering
(c) Cable charging To be furnished during detail engineering
(d) Capacitor banks To be furnished during detail engineering
2.26 When switching off a synchronous system
(a) Maximum current kA To be furnished during detail engineering
(b) Maximum recovery voltage between contacts
kA To be furnished during detail engineering
2.27 No. of operating circuit breaker can perform without inspection, replacement of contacts
(a) At rated breaking current To be furnished during detail engineering
(b) At rated continuous current To be furnished during detail engineering
2.28 Creepage distance for the interrupter insulator
mm 31 mm / KV
2.29 Creepage distance for the interrupter insulator
mm 31 mm / KV
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 105 of 88
2.30 Cantilever strength of circuit breaker at the terminal pad
kg To be furnished during detail engineering
2.31 Whether pressure switches for SF6 pressure low alarm, trip, lockout closing, lock out, opening are provided
YES
2.32 Compressed air system details
(a) Type (unit / centralised) To be furnished during detail engineering
(b) Rated pressure To be furnished during detail engineering
(c) Time for the compressor to charge to reservoir from atmospheric pressure
To be furnished during detail engineering
(d)
Time for the compressor to replenish the reservoir from starting pressure to rated pressure
To be furnished during detail engineering
(e)
Number of stored close open operation before lockout pressure is reached
To be furnished during detail engineering
(f) Whether pressure, switches for start, stop of compressor, high, low alarm, close lockout, open lockout, auto reclose lockout provided
To be furnished during detail engineering
3.0 90kV Isolators
3.1 Make, type, and country of manufacture
As per approved vendor list
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 106 of 88
3.2 Reference standard As per IEC/EDF Standards
3.3 Rated voltage & frequency Volts, Hz 90 KV/50Hz
3.4 Rated current Amp Ref-SLD
3.5 Reference ambient temperature 0C 50
3.6 Short time withstand current & duration
kA. sec 40 KA for 1 sec
3.7 Dynamic withstand current kAp To be furnished during detail engineering
3.8 Maximum temperature rise of current carrying parts
50 0C
3.9 Insulation Test values
(a) One minute P.F. wet withstand voltage
(i) Between poles & earth
kV To be furnished during detail engineering
(ii) Across isolating distance
kV To be furnished during detail engineering
(b) Impulse withstand voltage
(i) Between poles & earth
kVp To be furnished during detail engineering
(ii) Across isolating distance kVp To be furnished during detail engineering
3.10 Material
(a) Main contact To be furnished during detail engineering
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 107 of 88
(b) Arcing contact To be furnished during detail engineering
(c) Current carrying parts To be furnished during detail engineering
3.11 Whether contacts are silver faced YES
3.12 Clearance
(a) Between poles mm To be furnished during detail engineering
(b) Between live parts and earth
mm To be furnished during detail engineering
(c) Between live parts when switch is open
To be furnished during detail engineering
(i) Between same pole mm To be furnished during detail engineering
(ii) Between adjacent pole mm To be furnished during detail engineering
3.13 Phase spacing mm To be furnished during detail engineering
3.14 Type of interlock Both interlock electrically operated
(a) External *
(b) Earth switch *
3.15 Insulators Solid core
(a) Type of insulator (solid core) Horizontal,centre break
(b) Cantilever strength 800 Kg
(c) Total creepage distance 31 mm / KV
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 108 of 88
(d) Applicable standards As per IEC/EDF Standards
3.16 Operating mechanism(motor/manual)
(a) Main blade Motorized & Manual
(b) Earth blade Motorized & Manual
4.0 90kV Current Transformer
4.1 Make & country of Manufacture As per IEC/EDF Standards
4.2 Applicable standards As per IEC/EDF Standards
4.3 Rated voltage class 90 Kv
4.4 Insulation withstand level 450 KV (peak)
(a) Impulse withstand voltage 1.2/50 microsec wave
kV peak To be furnished during detail engineering
(b) One minute power frequency withstand voltage
kV rms To be furnished during detail engineering
4.5 Number of cores per CT
4.6 Rated secondary current for each core
1.1Core 1 A To be furnished during detail engineering
2.1Core 2 A To be furnished during detail engineering
3.1Core 3 A To be furnished during detail engineering
4.1Core 4 A To be furnished during detail engineering
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 109 of 88
5.1Core 5 A To be furnished during detail engineering
6.1Core 6 A To be furnished during detail engineering
4.7 Ratio taps for each core
Core 1 To be furnished during detail engineering
Core 2 To be furnished during detail engineering
Core 3 To be furnished during detail engineering
Core 4 To be furnished during detail engineering
Core 5 To be furnished during detail engineering
Core 6 To be furnished during detail engineering
4.8 Whether it is possible to adjust tap setting of any core independent of other cores
YES/ NO Yes
4.9 Relaying cores To be furnished during detail engineering
(a) Accuracy class (for 5P20) Shall be 0.2 sec for metering cores
(b) Rated burden (for 5P20) VA To be furnished during detail engineering
(c) Accuracy limit factor (5P20) To be furnished during detail engineering
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 110 of 88
(d) Minimum knee point voltage VK for PS class
Volts To be furnished during detail engineering
(e) Maximum excitation current at VK, VK/2 Volts (for PS class
mA To be furnished during detail engineering
(f) Maximum secondary resistance (for PS class)
To be furnished during detail engineering
4.10 For metering cores :
a) Accuracy class To be furnished during detail engineering
b) Rated burden To be furnished during detail engineering
c) Rated power factor VA To be furnished during detail engineering
d) Instrument security factor To be furnished during detail engineering
Short time thermal current rating 40 KA for 1 sec.
a) Current kA To be furnished during detail engineering
b) Rated time sec
4.12 Dynamic current rating kA peak 100 KAp
4.13 Maximum temperature rise of windings at rated primary current and rated burden, when referred to specified ambient temperature
ºC To be furnished during detail engineering
4.14 Class of insulation of windings Oil immersed,Class-A
4.15 Radio influence voltage V To be furnished during detail engineering
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 111 of 88
4.16 Cantilever strength at terminal Kg To be furnished during detail engineering
4.17 Creepage distance of insulator housing
M 31mm/KV
5.0 Voltage Transformer
5.1 Manufacturer and country of manufacture
As per IEC/EDF Standards
5.2 Applicable standards As per IEC/EDF Standards
5.3 Type of VT As per IEC/EDF Standards
5.4 Insulation withstand level To be furnished during detail engineering
5.4.1 Impulse withstand voltage 1.20/50 micro sec.
kV peak 450 KV (peak)
5.4.2 One minute power frequency withstand voltage
kV rms 185
5.5 Number of secondary windings for each VT
3
5.6 Rated primary voltage kV 90/√3
5.7 Rated secondary voltage V 110/√3
5.8 Rated VA burden for each secondary windings
VA To be furnished during detail engineering
5.9 Rated power factor To be furnished during detail engineering
5.10 Accuracy class for each secondary winding
5.10.1 Winding – 1 To be furnished during detail engineering
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 112 of 88
5.10.2 Winding – 2 To be furnished during detail engineering
5.10.3 Winding – 3 To be furnished during detail engineering
5.11 Method of connection To be furnished during detail engineering
5.11.1 Primary winding
5.11.2 Each
(a)
(b)
(c)
secondary winding
Winding – 1
Winding – 2
Winding – 3
NA
5.12 Rated voltage factor 1.2 continuous & 1.5 for 30 sec
5.13 Maximum temperature rise of windings at 110% excitation and rated burden, when referred to specified ambient temperature
ºC As per IEC/EDF Standards
5.14 Class of insulation of windings Oil immersed,Class-A
5.15 Capacitor data To be furnished during detail engineering
5.15.1 High voltage capacitance pF To be furnished during detail engineering
5.15.2 Intermediate voltage capacitance pF To be furnished during detail engineering
5.15.3 Nominal intermediate voltage kV 90/110
5.15.4 Equivalent capacitance for carrier coupling
pF To be furnished during detail engineering
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 113 of 88
5.15.5 Maximum permissible impedance at power frequency
Ohms To be furnished during detail engineering
5.16 Total creepage distance mm 31mm/KV
5.17 Radio influence voltage Volts To be furnished during detail engineering
5.18 Details of high speed switch(es) on secondary winding (alternative to fuses)
To be furnished during detail engineering
5.18.1 Make, type, rating , coil rating, other technical details
Amp As per IEC/EDF Standards
5.19 Cantilever strength Kg As per IEC/EDF Standards
6.0 Lightning Arresters
6.1 Maker’s Name and Type and country of manufacture
As per IEC/EDF Standard
6.2 Arrester type As per IEC/EDF Standards
6.3 Applicable standards As per IEC/EDF Standards
6.4 Arrester class kV As per IEC/EDF Standards
6.6 Rated frequency Hz 50
6.7 Nominal discharge current (8/20 micro seconds wave)
kA 20
6.8 Minimum discharge capability KJ/kV As per IEC/EDF Standards
6.9 Residual voltage corresponding to
kV (peak)
6.9.1 Steep current impulse As per IEC/EDF Standards
6.9.2 Lighting impulse As per IEC/EDF Standards
6.9.3 Switching impulse As per IEC/EDF Standards
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 114 of 88
6.10 Reference voltage (TEC TC37-WG-4 1985)
A To be furnished during detail engineering
6.11 Reference voltage (TEC TC37-WG-4 1985)
kV(rms) To be furnished during detail engineering
6.12 Overvoltage withstand capability for :
a) 10 cycles kV(rms) To be furnished during detail engineering
b) 1 second kV(rms) To be furnished during detail engineering
c) Continuous kV(rms) To be furnished during detail engineering
6.13 Energy discharge capacity KJ/kV To be furnished during detail engineering
6.14 Maximum residual voltage at nominal discharge current
kV(rms) To be furnished during detail engineering
6.15 Discharge voltage at 5kA discharge current
kV(peak) To be furnished during detail engineering
6.16 Discharge voltage at 10 kA discharge current
kV(peak) To be furnished during detail engineering
6.17 Discharge voltage at 20 kA discharge current
KV(peak) To be furnished during detail engineering
6.18 Impulse current withstand
(a) High current short duration (4/10 micro second wave)
kV(peak) To be furnished during detail engineering
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 115 of 88
(b) Low current long duration
A(peak) To be furnished during detail engineering
(c) Virtual duration of rectangular wave
Micro-second
To be furnished during detail engineering
6.19 One minute power frequency (dry) withstand voltage of arrester housing
kV(rms) To be furnished during detail engineering
6.20 Impulse withstand test voltage of arrester housing with 1.2/50 micro-second wave
kV(peak) 450KVp (peak)
6.21 Total creepage distance of whole arrester housing
mm 31mm/kv
6.22 Cantilever strength of complete arrester
kg 800 ( minimum)
6.23 Pressure relief class (as per IEC 60099)
To be furnished during detail engineering
6.24 Routine Tests
a) Measurement of reference voltage test
Yes/No Yes
b) Residual voltage test
Yes/No Yes
c) Leakage check for arrester units with sealed housings
Yes/No Yes
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 116 of 88
d) Current distribution test for multi-column arrester
Yes/No Yes
6.25 Acceptance Tests
(a) Measurement of power frequency voltage on the complete arrester at the reference current measured at the bottom of the arrester
Yes/No Yes
(b) Lighting impulse residual voltage on the complete arrester or arrester unit at nominal discharge current
Yes/No Yes
(c) Partial discharge test at 1.05 times continuous operating voltage
Yes/No Yes
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 117 of 88
7.0 Insulator and hardware (Fill in for bus post ‘Insulator as well as insulator string)
7.1 Insulator / Insulator string
(a) Manufacturer and country of manufacture
As per IEC/EDF Standards
(b) Applicable standard
As per IEC/EDF Standards
(c) Type of insulator (Antifog / normal)
Solid core
(d) Insulating material
To be furnished during detail engineering
(e) No. of units per string
(f) Creepage distance
(i) disc unit
(ii) string assembly
mm
mm
To be furnished during detail engineering
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 118 of 88
(g) One minute power frequency withstand dry
(i) single disk
(ii) string assembly / bus post
kV
kV
To be furnished during detail engineering
(h) One minute power frequency withstand (wet)
i) disk unit
ii) string assembly / bus post
kV
kV
To be furnished during detail engineering
(i) Impulse withstand voltage (dry)
ii)disk unit
ii) string assembly / bus post
kVp
kVp
To be furnished during detail engineering
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 119 of 88
(j) Impulse withstand voltage (wet)
i) disk unit
ii) string assembly / bus post
kVp
kVp
To be furnished during detail engineering
(k) Electro mechanical strength of each disk
kg To be furnished during detail engineering
(l) Live parts to earth clearance (spark over distance)
mm To be furnished during detail engineering
(m) Cantilever strength (for bus post insulator only)
kg To be furnished during detail engineering
(n) Tensile strength (for bus post insulator only)
kg To be furnished during detail engineering
(o) Compression strength (for bus post insulator only)
kg To be furnished during detail engineering
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 120 of 88
(p) Visual discharge voltage for falling power frequency voltage (string and bus post insulator)
kg To be furnished during detail engineering
7.2 Insulator Hardware
(a) Manufacturer As per IEC/EDF Standards
(b) Applicable standard
As per IEC/EDF Standards
(c) All ferrous parts are hot dip galvanised
Yes/No Yes
8.0 Bus Conductors, Clamps and Connectors
8.1 Flexible Conductor AAC/ACSR Aster
(a) Size of conductor for main bus and bus coupler bay buses
To be furnished during detail engineering
(b) Size of conductor for other bay buses, transfer bus
To be furnished during detail engineering
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 121 of 88
(c) The temperature rise of the conductor while carrying the rated current
To be furnished during detail engineering
(d) Purity of Aluminium / copper
To be furnished during detail engineering
8.2 Tubular Conductor Aluminium tube
*
(a) Size of the tabular conductor for bus
To be furnished during detail engineering
(b) The temperature rise of the tabular conductor while carrying the rated current
To be furnished during detail engineering
(c) Purity of Aluminium/copper
To be furnished during detail engineering
8.3 Shield wire
a) Material of the shield wire
To be furnished during detail engineering
b) Size of the shield wire
To be furnished during detail engineering
8.4 Clamps and connectors
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 122 of 88
(a) Whether material specification of the clamps and connectors are as per specification
Yes/No Yes
(b) Temperature rise of the clamp while carrying the rated current
ºC To be furnished during detail engineering
(c) Minimum thickness at any part of the clamps
mm To be furnished during detail engineering
(d) Corona extinction voltage for falling power frequency voltage.
V To be furnished during detail engineering
(e) Wedge type connectors Yes Yes
9.0 SWITCHYARD CONTROL PANEL (SCP)
9.1 Make and country of manufacture
As per IEC/EDF Standards
9.2 Degree of protection for enclosure
As per IEC/EDF Standards
9.3 Applicable standards As per IEC/EDF Standards
9.4 Indicating Meters yes
9.4.1 Meter size mm 48x48 or 96x96
9.4.2 Accuracy As per EDF Std.
9.4.3 Type Analog/Digital
9.5 MWHr / MVARHr Energy meters Yse
9.5.1 Accuracy (Required 0.2S) Yes
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 123 of 88
9.5.2 Whether retransmission contact provided (Required)
Yes
9.6 Transducers Yes
9.6.1 Accuracy yes
9.6.2 Output current To be furnished during detail engineering
9.6.3 No. of channels To be furnished during detail engineering
9.6.4 Type No. & Make As per approved vendor list
9.7 Whether annunciators scheme, features, sequence and size are same as the one offered for plant control system
yes
9.8 Mimic material and width in mm To be furnished during detail engineering
10.0 Switchyard Relay Panel
10.1 Panel make and country of manufacture
As per approved vendor list
10.2 Degree of protection for enclosure of panel
IP-43
10.3 Mounting of relays Front-Top
10.3.1 On conventional panels Front mounting
10.3.2 On pre-engineered panel Front mounting
10.4 Relay Particulars To be furnished during detail enginering
10.4.1 Control voltage 127 V
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 124 of 88
10.4.2 Current rating 50 KA for 1 sec
10.4.3 Voltage rating AC supply 415V/240 V,3 Ph,4 wire
10.4.4 Operating temperature range Ambient Temp.
10.4.5 Applicable standards As per IEC/EDF Standards
10.4.6 Aux. supply operating range
10.4.7 On line automatic testing facility provided
Yes
10.4.8 On line manual testing facility provided
Yes
10.5 Relay types offered (list each relay and furnish the data)
As per approved vendor list
10.6 All the relays offered are type tested
Yes / No yes
10.7 If no which are all not type tested NA
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 125 of 88
1.14 CableSr. No.
Description Unit Parameter
1.0 Name of the Manufacturer As per approved vendor list
2.0 Conductor Stranded and compacted copper or Aluminium
3.0 No. Core X Size As per system requirement
4.0 Form- circular/segmented circular
5.0 Effective cross sectional area sq. mm Min-2.5
Max-6
6.0 Single core power cables armouring Galvanised single round
steel wire
7.0 Multi core power cable armouring Galvanised single round
steel wire
8.0 Whether cores identification numbers
for cables with 5 cores and above to be
provided
Yes
9.0 Whether incremental running lengths
are marked on cable
*
10.0 Finished Cable As per IEC/EDF standards
10.1 Diameter under armour mm
10.2 Diameter over armour mm
10.3 Overall diameter mm
11.0 Cable drums
11.1 Wheter cable drums confirm to IS:
10417
11.2 Length of cables in drum & tolerance km To be decided during DE
11.3 Weight of cable drum without cables kg …………..do…………..
11.4 Weight of cable drum with cables kg …………..do…………..
11.5 Type of end sealing
12.0 FRLS Cables
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 126 of 88
Sr. No.
Description Unit Parameter
12.1 Critical oxygen index value at room
temp. when tested as per ASTM-D-
2863
29
12.2 Temp. index value at 21 Oxygen index
when tested as per ASTM-D-2863 /
NES-715-1
2500°C
12.3 Total acid gas generation by weight
when tested as per IEC-754-1 in %
Less than 20%
12.4 c) Smoke generation under fire when
tested as per ASTM-D-2843 in smoke
density rating
60%
12.5 d) Will the cables offered against this
specification pass the flammability
tests as per
*
1. Class - F3 - Swedish standard SS-
424-1475
Yes
2. IEC 332-1 Yes
3. IEC 331-1 Yes
13.0 Whether Cable pass the hydraulic
stability and ultraviolet tests as per
DIN 53377
Yes
14.0 Whether Finished Cable pass the
flammability test as per IEC-60322
Yes
15.0 Maximum dielectric loss of cable as
per km at normal voltage and
frequency
Watt/km
16.0 Short circuit capability for 1 Sec kA rms
17.0 Maximum dielectric stress at core
screen
kV/cm
18.0 Maximum overall diameter of cables mm
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 127 of 88
NOTE :
‘*’ Information shall be filled furnished by CONTRACTOR along with offer
Rev. 0 – 06.03.12 Document No: P.003080 E49 0457 Page 128 of 88