Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.Rev 5058-CO900E
PUBLIC INFORMATION
Dynamix™ Integrated Vibration Protection System on EtherNet/IP
Roberto Fornez
Solution Architect Integrated Architecture
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
Dynamix and the Integrated Architecture
Questions?
2
Agenda
Functional Summary
Introducing the Dynamix 1444 Series
Applications
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
The XM architecture1 provides many modules2,
each designed to serve a specific application /
requirement.
XM is a Machinery Protection system that is also
capable of serving “some” condition monitoring
data3.
While XM can be integrated into a control
environment, because it is DeviceNet based, the
integration can be difficult and throughput
performance is limited. 1 And most competitive products
2 The XM-124, with the coming Version 7 firmware, will help address this problem
3 API-670 5th Edition will specifically allow for protection systems that also provide condition monitoring data
Existing architecture was designed
for another time…
Introducing the Dynamix 1444 SeriesWhy Build a Next Generation…
3
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
Introducing the Dynamix 1444 SeriesNext Generation Requirements…
4
Design Goals:
Simplify system design
Reduce costs for spares, training, support
Reduce costs for engineering, manufacturing and inventory
Focus investment on the functionality of the product rather than the quantity of part numbers
An architecture that offers a single
core module that:
Can be applied to any Machinery
Protection application
Can serve any Condition Monitoring
Application
Applies a native EtherNet/IP backplane
Is a component of Rockwell
Automation’s Integrated Architecture
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
Machine Protection
Machine Condition Monitoring
Introducing the Dynamix 1444 Series
5
Intelligent, Distributed, Rugged, Safe
High Performance Dual Processors, Ethernet, Integrated, Rated to +70 °C and Marine standards for Shock & Vibration, Hazardous Area Approved
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
Introducing the Dynamix 1444 Series(just) 6 Catalog Numbers
6
Three Optional Expansion Modules+ one common terminal base for all expansion modules.
A Single Main Module+ a single main module terminal base
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
Introducing the Dynamix 1444 SeriesIn a new, innovative package
7
Removable terminal connectors
Connectors are angled for improved access and visibilityEthernet connections located
for easy, uncluttered access
Both screw and spring version connectors available
Three Optional Expansion Modules+ one common terminal base for all expansion modules.
A Single Main Module+ a single main module terminal base
Integrated BNC connectors
Recessed frame designed for easy gripping
Innovative DIN mount design with tension and leveling control Soldered together card
stack construction
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
Dynamix 1444 Series1 Main Module
8
Dynamic Measurement Module(requires the 1444-TB-A terminal base)
4 Dynamic Inputs
2 Speed Inputs (TTL)
4 Buffered Outputs (BNC & Terminal Pins)
2 Digital Inputs
Function is user programmable
2 Digital Outputs
Function is user programmable
2 Ethernet ports
Single or Device Level Ring (DLR)
1 SPDT Relay
Many, perhaps most, applications will require only one or more Dynamic Measurement (Main) Modules
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
Dynamix 1444 Series1 Tachometer Expansion Module
9
Dynamic Measurement Module(requires the 1444-TB-A terminal base)
4 Dynamic Inputs
2 Speed Inputs (TTL)
4 Buffered Outputs (BNC & Terminal Pins)
2 Digital Inputs
Function is user programmable
2 Digital Outputs
Function is user programmable
2 Ethernet ports
Single or Device Level Ring (DLR)
1 SPDT Relay
Tachometer Signal Conditioner Expansion Module
(requires the 1444-TB-B terminal base)
2 Speed Inputs
any common speed sensors
2 Speed Outputs (TTL)
to Local Bus & Terminal Pins
2 Buffered Outputs (BNC)
6 Dynamic Measurement Modules
served per
Tachometer
Expansion
Module
1 per Dynamic
Measurement
Module
When (non TTL) speed signals must be monitored, a single Tachometer Signal Conditioner Expansion Module (TSCX) must be added. The TSCX is hosted by one
Main Module but can serve its TTL output signals 6 Main Modules.
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
Dynamix 1444 Series1 Relay Expansion Module…
10
Dynamic Measurement Module(requires the 1444-TB-A terminal base)
4 Dynamic Inputs
2 Speed Inputs (TTL)
4 Buffered Outputs (BNC & Terminal Pins)
2 Digital Inputs
Function is user programmable
2 Digital Outputs
Function is user programmable
2 Ethernet ports
Single or Device Level Ring (DLR)
1 SPDT Relay
Tachometer Signal Conditioner Expansion Module
(requires the 1444-TB-B terminal base)
2 Speed Inputs
any common speed sensors
2 Speed Outputs (TTL)
to Local Bus & Terminal Pins
2 Buffered Outputs (BNC)
6 Dynamic Measurement Modules
served per
Tachometer
Expansion
Module
1 per Dynamic
Measurement
Module
When more than one relay is needed, up to three Relay Expansion Modules may be added.Relay function is specific to the host Main
Module.
Relay Expansion Module(requires the 1444-TB-B terminal base)
4 Singe Pole Double
Throw (SPDT) Relays
5A, 250VAC/30VDC
3 per Dynamic Measurement Module
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
Dynamix 1444 Series1 Analog Output Expansion Module…
11
Dynamic Measurement Module(requires the 1444-TB-A terminal base)
4 Dynamic Inputs
2 Speed Inputs (TTL)
4 Buffered Outputs (BNC & Terminal Pins)
2 Digital Inputs
Function is user programmable
2 Digital Outputs
Function is user programmable
2 Ethernet ports
Single or Device Level Ring (DLR)
1 SPDT Relay
Tachometer Signal Conditioner Expansion Module
(requires the 1444-TB-B terminal base)
2 Speed Inputs
any common speed sensors
2 Speed Outputs (TTL)
to Local Bus & Terminal Pins
2 Buffered Outputs (BNC)
6 Dynamic Measurement Modules
served per
Tachometer
Expansion
Module
1 per Dynamic
Measurement
ModuleRelay Expansion Module
(requires the 1444-TB-B terminal base)
4 Singe Pole Double
Throw (SPDT) Relays
5A, 250VAC/30VDC
3 per Dynamic Measurement Module
When proportional analog outputs are required, one 4-20mA Output Expansion Module may be added.
4-20mA Output Expansion Module(requires the 1444-TB-B terminal base)
4 Channels
Proportional to any
measured value
1 per Dynamic Measurement Module
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
Dynamic Measurement Module(requires the 1444-TB-A terminal base)
4 Dynamic Inputs
2 Speed Inputs (TTL)
4 Buffered Outputs (BNC & Terminal Pins)
2 Digital Inputs
Function is user programmable
2 Digital Outputs
Function is user programmable
2 Ethernet ports
Single or Device Level Ring (DLR)
1 SPDT Relay
Tachometer Signal Conditioner Expansion Module
(requires the 1444-TB-B terminal base)
2 Speed Inputs
any common speed sensors
2 Speed Outputs (TTL)
to Local Bus & Terminal Pins
2 Buffered Outputs (BNC)
6 Dynamic Measurement Modules
served per
Tachometer
Expansion
Module
1 per Dynamic
Measurement
ModuleRelay Expansion Module
(requires the 1444-TB-B terminal base)
4 Singe Pole Double
Throw (SPDT) Relays
5A, 250VAC/30VDC
3 per Dynamic Measurement Module
4-20mA Output Expansion Module(requires the 1444-TB-B terminal base)
4 Channels
Proportional to any
measured value
1 per Dynamic Measurement Module
1444-TB-A Use with the 1444-DYN04-01RA Dynamic Measurement Module
Includes last octets Ethernet address selection
Precision module / base alignment guides
DIN mount tension / leveling screws
Local Bus ribbon connectors
1444-TB-B Use with:
1444-TSCX02-02RB Tachometer Signal Conditioner
Expansion Module
1444-RELX00-04RB Relay Expansion Module
1444-AOFX00-04RB 4-20mA Output Expansion Module
Includes address selection for Relay Modules
(addressing for other expansion modules is automatic)
Precision module / base alignment guides
DIN mount tension / leveling screws
Local Bus ribbon connectors
Dynamix 1444 Series2 Terminal Bases…
12
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
4-20mA Output Expansion Module
4 Channels
Dynamix 1444 Series(just) 6 Catalog Numbers!
13
Dynamic Measurement Module
4 Dynamic Inputs
2 TTL Speed Inputs
Terminal Bases
1 Main Module Base
1 Expansion Module
Base
Tachometer Signal Conditioner Expansion Module
2 Speed Inputs
2 TTL Speed Outputs
Relay Expansion Module
4 SPDT Relays
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION 14
Dynamix 1444 SeriesEthernet
Ethernet Connector (2): RJ45, shielded 1
Speed: 10MB / 100MB
Modes: Half/full duplex
Operation: Auto-switching
Auto negotiation
Auto mitigation
Protocol ODVA Conformance Tested
EtherNet/IP Industrial Protocol
Connectivity Single Ethernet (IEEE 802.3)
Device Level Ring (ODVA)
IP Address Set by hardware switch on the terminal base,
Set in configuration 2
Concurrent Access Controller (owner)
Up to 3 additional sessions
Time Synchronization IEEE-1588 Standard Ver. 2
CIP Sync (ODVA)1 Allen-Bradley 1585 Ethernet Media recommend
2 IP address retained in nonvolatile memory
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
XM®
54.7 mm 2.15 in
103.5 mm4.1 in
Dynamix 1444 SeriesA Compact, Distributed I/O Architecture
116
mm
/ 4.
.5 in
155
mm
/ 6.
1 in
90.2
mm
3.
55 in
93.8
mm
/ 3.
69 in
94.0 mm3.7 in
2 Channels + 1 Tach Input
4 Channels + 2 TTL Speed Inputs
100.
7 m
m /
3..9
6 in
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
Dynamix 1444 SeriesA Compact, Distributed I/O Architecture (still)
Includes 1 Tachometer Signal
Conditioner Expansion
module per 6 Main modules
Includes only Main modules
4 Channels + 2 TTL Speed Inputs
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
Dynamix 1444 SeriesPower, Environment, Certifications & Approvals
17
PowerRedundant Supplies Integral redundant power supply inputs with supply fault detection and status available on I/O
Supply Voltage +24VDC (18V to 32V wide range input) – designed to accommodate battery backed systems
Electrical SafetyCE, CSA & UL
Hazardous AreaIECex-Zone 2 & ATEX – Zone 2, cUL – Class 1 Div 2 Groups A,B,C,D
Region & Country MarksCE, C-Tick, Russia*, Brazil*, Korean*
Marine Certifications*DNV, BV, ABS, Lloyds, RINA, GL, KRS
Functional Safety**TUV certified to SIL 2***
* May not be available at initial release
** Will not be available at initial release
*** When used with local, expansion module, relays
EnvironmentOperating temperature -25°C to +70°C
Conformal coating All circuit cards are conformal coated
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
ArchitectureNetwork Connections on Main Module
Insert / Remove Under Power
Interconnect via included ribbon cable between terminal bases
Dynamix 1444 SeriesArchitecture & Local Bus
Power
Host / Expansion Module Network
TTL Signal & TX OK
Power
TTL Signal & TX OK
TTL Signal & TX OK
TTL Signal & TX OK
Host / Expansion Module Network
Local BusHost / Expansion Module Communications
Speed Signal Distribution
Power Distribution
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
Configuration from any Logix controller
Support included in
Studio 5000 V20+
Standard assemblies for
Configuration
Input
Output
1444 Series & the Integrated ArchitectureFully Supported by Logix
19
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
Dynamix and the Integrated Architecture
Further Detail…
Questions?
20
Agenda
Functional Summary
Introducing the Dynamix 1444 Series
Applications
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
The only architecture
capable of serving the
Machinery Protection &
Condition Monitoring
requirements of
any application in
any industry!
21
Dynamix 1444 SeriesDesigned to Serve Industry
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION 22
Machinery Protection
General Protection Applications
Provide alarm indication / annunciation via local relays
and/or RA Visualization solutions
API-670 (5th Edition) Compliant Applications
Can satisfy all the requirements of the standard
While the controller is required for (initial) configuration, it
is not required for a 1444 Series system to perform its
function
1444 Series modules include nonvolatile memory.
At power up the system will load its saved configuration, if or until its controller serves it another one
Safety (SIL-2) Applications
Requires use of local relays (expansion module)
All safety related attributes in the configuration assembly
are hidden
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION 23
Machinery Condition MonitoringLogix™ Integrated Solutions
Apply simple rule based logic for Fault Diagnostic
Trend fault indicators in Process Historian
Implement advanced Monitoring Solutions for any
class of machine or for any complexity of
application…
Implement least cost per channel multiplexed* solutions
Monitor machine tools and other cyclic applications with
Profiles to detect deviant behavior relative to position or time
Apply alarm limits based on process considerations (fluid
type, material, speed, etc.)
* Multiplexed systems are available as an SSB Solutions offering
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION 24
Machinery Condition MonitoringPart of an Integrated Predictive Maintenance System
Connect the 1444 Series to
Rockwell Automation’s
Emonitor™ Software
Emonitor is scalable software that
provides the industry’s most
comprehensive suite of tools for
establishing and executing a
condition-based predictive
maintenance program.
Connect* any number of 1444 Series
systems to Emonitor servers
Consolidate all of your machinery
condition information into a single
plant or enterprise wide database
* Data is harvested by the controller where it is read either on schedule or trigger by Emonitor
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
Dynamix and the Integrated Architecture
Further Detail…
Questions?
25
Agenda
Functional Summary
Introducing the Dynamix 1444 Series
Applications
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
Dynamix 1444 SeriesCapabilities
26
Machine Protection
Machine Condition Monitoring
Real Time, Continuous, Surveillance
Real Time Processing of Critical Parameters, Continuous Processing of Diagnostic Data, Demand Processing of Infrequent Measures
Relays
4-20mA Outputs
Event Capture
Event Log
Trend / Alarm
Startup /
Coastdown
Vibration
Acceleration
Velocity
Displacement
Absolute Shaft Vibration
Spike Energy (gSE)
Speed
Pressure
Thrust
Case Expansion
Differential Expansion
Rod Drop
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
1444 Series Functional SpecificationsMeasurements Summary
Dynamic (AC) Measurements
Discrete Measurementso Per Channel Pair
• SMAX Magnitude
• Shaft Absolute Vibration
o Per Channel
• Overall (2)
• Order Magnitude & Phase (4)
• FFT Band (8)
• Not 1x (1)
• Bias / Gap (1)
• gSE Overall (1)
Complex Measurementso TWF and FFT (to 1600 lines)
o Asynchronous or Synchronous
Demand Measurements
Synchronous, Asynchronous
TWF and FFT (to 12,800 lines)
Simultaneous Cross Module
Measurements
Static (DC) Measurements
Single DC Channelso Axial Position
• Thrust
• Valve Position
o Eccentricity
o Rod Drop
o Proportional Voltage
Paired DC Channelso Differential Expansion
Speed Measurements
SpeedRetains maximum speed measured
Rate of change of speed
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
1444 Series Functional SpecificationsAlarms & Relays Summary
Alarms & Relays
Measurement Alarms
Apply limits to measured parameter
24 measurement alarms may be defined
Voted Alarms Apply voting logic to Measurement Alarms
13 voted alarms may be defined
Relays
Associate with any voted alarm, or…
Leave unassigned to actuate only on fault.
Main modules include a single onboard physical relay. With
expansion modules this can be expanded to 5, 9 or 13 relays
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
1444 Series Functional SpecificationsEvent Capture
Startup
Running
Coastdown
no load
high load
Startup / Coastdown buffers
o 4 buffers, each containing 640 discrete
data records & 64 dynamic data records
• Allows for a potential “single buffer” of
up to 2560 discrete and 256
dynamic records
o Trigger on ΔRPM and Δtime
• Include a post startup sample period
Alarm / Trend buffers
o Trend: 640 discrete data records & 64
dynamic data records
o Alarm: Trend buffer (copy) + 260 discrete
data records @ 100 ms sample rate
Trigger on:
• Any alarm, or
• Controller I/O
control bit
Event log
Records occurrences of:
• Configuration Change
• Alarm Set / Clear
• Startup / Coastdown Begin /
End
• more….
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
Dynamix and the Integrated Architecture
Further Detail…
Questions?
30
Agenda
Functional Summary
Introducing the Dynamix 1444 Series
Applications
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
Configuration Assembly
Large Configuration Assembly
Requires Logix V20+
Basic application, channel input
types, I/O, and compliance
requirement defined in Module
Definition…
…allows Guided Configuration
of low level parameters
Assembly is fully exposed and
programmatically accessible…
…unless a SIL-2 application, in
which case all Safety related
assembly attributes are hidden
Dynamix 1444 SeriesController I/O: The Usual 3 Assemblies
31
I/O is provided and managed the same way as for any IA product. It’s just bigger!
Controller Output
Controller Input
Input Assembly parameters selected
in Module Definition.
Control Bits Data
Trip Inhibit
Set Point Multiply (2)
Gate Controls (2)
Alarm Reset
Alarm Buffer Trigger
Alarm Buffer Reset
Transient Buffer Resets (4)
Speeds (2)
Alarm Limits (16)
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION 32
Rockwell Automation’s Network StrategySeamless, Secure Communications Everywhere
Rockwell Automation follows a
strategy of using open network
technology for seamless, top-
floor to plant level
integration. These open
networks speak a common
language and share a universal set
of communication services. As a
result, information can be
communicated seamlessly,
safely and securely throughout
the plant, from shop floor to top
floor, even if the top floor is a
world away.
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION 33
Rockwell Automation’s Network StrategyWith Dynamix Integrated into the Architecture
Dynamix™
Condition
Monitoring
Dynamix™
Protection
CBM Applications,
Asset Management
ApplicationsCBM,
From the beginning the Dynamix
1444 Series was designed and
developed to execute this core Rockwell Automation
strategy.
Native dual port Ethernet, the
EtherNet/IP protocol, Device
Level Ring, an integrated Logix solution, and all of the products
and capabilities of Rockwell
Automation’s Integrated
Architecture…
These are what makes the
Dynamix 1444 Series the
industries most open yet
secure, integrated and
capable solution for
machinery monitoring and
protection available today.
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
1444 Series System ArchitecturesDedicated Condition Monitoring System
34
A single controller might manage
an entire condition monitoring
architecture for an entire plant...
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION 35
1444 Series System ArchitecturesCondition Monitoring within an Integrated Architecture
Or a plants monitoring
solutions might be split
based on criticality into sub
networks, each managed by
its own controller.
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved.PUBLIC INFORMATION
The Dynamix 1444 Seriesand the Integrated Architecture…
36
An architecture with a
single core module that:
Can be applied to any
Machinery Protection
application
Can serve any Condition
Monitoring Application
Applies a native EtherNet/IP
backplane
Is a component of Rockwell
Automation’s Integrated
Architecture