1 Suburban DynaPack H Series Owner's Manual 10/2017 Rev.4 WARNING! If the information in these instructions are not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance. Do not touch any electrical switch; do not use any phone in your building. Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. If you cannot reach a gas supplier, call the fire department. Installation and service must be performed by a qualified installer, service agency or the gas supplier. WARNING! Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Refer to the installation instructions and/or owners manual provided with this appliance. Installation and service must be performed by a qualified installer, service agency or the gas supplier. WARNING! Installation and servicing of air conditioning equipment can be hazardous due to internal refrigerant pressure and live electrical components. Only trained and qualified service personnel should install or service this equipment. Installation and service performed by unqualified persons can result in property damage, personal injury, or death. WARNING! For SAFE operation this must be installed using only the approved exterior grille and wall sleeve accessories. Failure to comply with this may result in property damage, personal injury, or death. CAUTION: The installation of this appliance must conform to the requirements of the National Fire Protection Association; the National Electrical Code, ANSI/ NFPA No. 70 (latest edition) in the United States; the Canadian Electrical Code part 1, CSA 22.1 (latest edition) in Canada; and any state or provincial laws or local ordinances. Local authorities having jurisdiction should be consulted before installation is made. Such applicable regulations or requirements take precedence over the general instructions in this manual. INSPECTING FOR FREIGHT DAMAGES Your unit was carefully packed in a container which complies with the National Safe Transit Test. This means that the packaged product, with normal handling, will withstand the load conditions encountered in normal transit and in handling. Your unit should be inspected immediately after unpacking to determine if any damage is present due to shipping or handling. If any damage is discovered, do not install the unit. Notify the transportation company immediately and file a damage claim. The manufacturer can bear no responsibility for damages which occur in transit or for improper operation of the unit as a result of shipping damages. AIRXCEL, INC. SUBURBAN APPLIED PRODUCTS 156 Seedling Drive Cordele, GA 31015 (229) 273-3636 www.SuburbanManufacturing.com DYNAPACK "H" SERIES MODELS DYPA12AC1A039H DYPA18AC1A039H, DYPA18AC1A052H DYPA24AC1A039H, DYPA24AC1A052H DYPA30AC1A039H, DYPA30AC1A052H DYPA36AC1A039H, DYPA36AC1A052H VERTICAL PACKAGED AIR CONDITIONER FEATURING GAS HEAT AND ELECTRIC COOLING INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS Installer: Leave this manual with the appliance Consumer: Retain this manual for future reference. This book contains instructions for installation and operation of your unit. Keep it in a safe place for ready reference. Should you require further information, contact your dealer. For future reference, you should record the following information from the units. MODEL NUMBER _________________________________________________ SERIAL NUMBER _________________________________________________ STOCK NUMBER _________________________________________________ DATE OF PURCHASE _____________________________________________ UNIT SPECIFICATIONS Do not operate this unit during construction as this may violate your warranty. HEATING MODEL DYPA 12AC1A039H DYPA 18AC1A039H DYPA 24AC1A052H DYPA 30AC1A052H DYPA 36AC1A052H BTU INPUT 39,000 39,000 52,000 52,000 52,000 VOLTS 208-230 208-230 208-230 208-230 208-230 AMPS 4.7 4.7 4.7 4.7 4.7 GAS CONNECTION 1 /2 Inch Pipe at Unit COOLING MODEL DYPA 12AC1A039H DYPA 18AC1A039H DYPA 24AC1A052H DYPA 30AC1A052H DYPA 36AC1A052H COOLING CAPACITY 12,000 17,000 23,600 28,400 34,800 VOLTS 208-230 208-230 208-230 208-230 208-230 WATTS 1175 1665 2380 2820 3480 MCA* 13.3 14.9 17.8 21.6 25.2 REFRIGERANT R410A REFRIGERANT CHARGE SEE INFORMATION STICKER ON UNIT *MCA= Minimun Circuit Ampacity Part Number 205096 10/2017 Rev. 4
Transcript

1 Suburban DynaPack H Series Owner's Manual 10/2017 Rev.4

WARNING! If the information in these instructions are not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS• Do not try to light any appliance.• Do not touch any electrical switch; do not use any phone in your

building.• Immediately call your gas supplier from a neighbor’s phone.

Follow the gas supplier’s instructions.• If you cannot reach a gas supplier, call the fire department.Installation and service must be performed by a qualified installer, service agency or the gas supplier.

WARNING! Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Refer to the installation instructions and/or owners manual provided with this appliance. Installation and service must be performed by a qualified installer, service agency or the gas supplier.

WARNING! Installation and servicing of air conditioning equipment can be hazardous due to internal refrigerant pressure and live electrical components. Only trained and qualified service personnel should install or service this equipment. Installation and service performed by unqualified persons can result in property damage, personal injury, or death.

WARNING! For SAFE operation this must be installed using only the approved exterior grille and wall sleeve accessories. Failure to comply with this may result in property damage, personal injury, or death.

CAUTION: The installation of this appliance must conform to the requirements of the National Fire Protection Association; the National Electrical Code, ANSI/NFPA No. 70 (latest edition) in the United States; the Canadian Electrical Code part 1, CSA 22.1 (latest edition) in Canada; and any state or provincial laws or local ordinances. Local authorities having jurisdiction should be consulted before installation is made. Such applicable regulations or requirements take precedence over the general instructions in this manual.

INSPECTING FOR FREIGHT DAMAGESYour unit was carefully packed in a container which complies with the National Safe Transit Test. This means that the packaged product, with normal handling, will withstand the load conditions encountered in normal transit and in handling. Your unit should be inspected immediately after unpacking to determine if any damage is present due to shipping or handling. If any damage is discovered, do not install the unit. Notify the transportation company immediately and file a damage claim.

The manufacturer can bear no responsibility for damages which occur in transit or for improper operation of the unit as a result of shipping damages.

AIRXCEL, INC.SUBURBAN APPLIED PRODUCTS

156 Seedling DriveCordele, GA 31015

(229) 273-3636www.SuburbanManufacturing.com

DYNAPACK "H" SERIESMODELS

DYPA12AC1A039HDYPA18AC1A039H, DYPA18AC1A052HDYPA24AC1A039H, DYPA24AC1A052HDYPA30AC1A039H, DYPA30AC1A052HDYPA36AC1A039H, DYPA36AC1A052H

VERTICAL PACKAGED AIR CONDITIONER FEATURING GAS HEAT AND ELECTRIC COOLINGINSTALLATION, OPERATING AND SERVICE INSTRUCTIONS

Installer: Leave this manual with the applianceConsumer: Retain this manual for future reference.

This book contains instructions for installation and operation of your unit. Keep it in a safe place for ready reference.Should you require further information, contact your dealer.

For future reference, you should record the following information from the units.

MODEL NUMBER _________________________________________________

SERIAL NUMBER _________________________________________________

STOCK NUMBER _________________________________________________

DATE OF PURCHASE _____________________________________________

UNIT SPECIFICATIONSDo not operate this unit during construction as this may violate your warranty.

HEATINGMODEL

DYPA12AC1A039H

DYPA18AC1A039H

DYPA24AC1A052H

DYPA30AC1A052H

DYPA36AC1A052H

BTU INPUT 39,000 39,000 52,000 52,000 52,000

VOLTS 208-230 208-230 208-230 208-230 208-230

AMPS 4.7 4.7 4.7 4.7 4.7

GAS CONNECTION

1/2 Inch Pipe at Unit

COOLINGMODEL

DYPA12AC1A039H

DYPA18AC1A039H

DYPA24AC1A052H

DYPA30AC1A052H

DYPA36AC1A052H

COOLINGCAPACITY 12,000 17,000 23,600 28,400 34,800

VOLTS 208-230 208-230 208-230 208-230 208-230

WATTS 1175 1665 2380 2820 3480

MCA* 13.3 14.9 17.8 21.6 25.2

REFRIGERANT R410A

REFRIGERANT CHARGE

SEE INFORMATIONSTICKER ON UNIT

*MCA= Minimun Circuit Ampacity

Part Number 20509610/2017 Rev. 4

Suburban DynaPack H Series Owner's Manual 10/2017 Rev.4 2

INSTALLING AND SECURING UNITTO WALL SLEEVE

Before installing and securing the unit to the wall sleeve, make sure that the proper grille kit is installed. Due to the temperatures of the combustion products released from the gas vent, DynaPack gas package units require the use of an aluminum grille kit (see ACCESSORIES on page 7).1. Double check the installation of the wall sleeve to make sure it is securely

attached to the wall opening. Inspect the wall sleeve drain for proper installation if an inside drain is being used.

2. Examine the gaskets on the wall sleeve to make sure there is a continuous seal between the wall sleeve and the unit.

3. Place DynaPack unit onto the wall sleeve. Lift the unit 3/4" and place over the wall sleeve base (see Figure 4). A PALLET JACK works well for this. Temporarily block the unit up and install front leveling bracket (see Figure 4). Adjust leveling legs to level.

4. Use the two retaining straps to secure the unit to the wall sleeve (see Figure 4). Verify that the gaskets of the wall sleeve make a complete seal to the unit paying particular attention to top and bottom corners of the unit to sleeve seal. Caulk if needed.

DUCT WORK The duct work for the dwelling should be designed for the lowest possible static pressure to reduce energy usage and noise. Table 3 lists the approximate cfm delivery of the units on each of the indoor blower speeds. Table 4 lists the recommended heating and cooling speeds with its approximate cfm delivery. Use both tables to properly design the duct system for both heating and cooling cfm.

AIR FILTERThe Dynapack unit is equipped with a permanent, cleanable air filter. This filter can be used if the unit is installed so that the filter is accessible to the homeowner. The permanent filter installed inside the unit must be removed and discarded if a disposable filter is installed in the return air duct. See Table 2 for the minimum filter area required for the Dynapack unit based on unit capacity. It is recommended that air filters be cleaned or replaced monthly to keep the cooling coil and interior duct surfaces clean and able to operate most efficiently. Optional MERV 13 filters are available.

MINIMUM REQUIRED SURFACE AREA FOR DISPOSABLE FILTERS

MODEL NUMBER FILTER AREADYPA12 288 square inchesDYPA18 288 square inchesDYPA24 480 square inches

DYPA30 & DYPA36 480 square inchesTABLE 2

CONDENSATE DRAIN - COOLINGThe Dynapack unit and wall sleeve each have their own drain. The unit drain is for the condensate developed by the evaporator coil. It needs to be trapped and routed to the building drain system. Use ¾” pvc pipe and fittings (field supplied).

The wall sleeve is equipped with a drain pan that collects rain water entering the wall sleeve and the unit condenser coil area. At the time of installation of the wall sleeve, this drain can be directed directly outside or turned inside and routed to the building drain system. If the wall sleeve drain is routed to the building sewer system, then it must be trapped to prevent sewer gasses from escaping. The top of the sewer trap must be no higher than 18 inches above the bottom of the furnace. See Figure 5.

INSTALLATIONWARNING! Installation of this appliance must be made in accordance with the written instructions provided in this manual. No agent, representative or employee of Suburban or other person has the authority to change, modify or waive any provision of the instructions contained in this manual.

The Dynapack units are vertical package units featuring gas fired heating with electrical air conditioning. The Dynapack unit has been safety certified by Intertek Testing Services to comply with the national safety codes of the USA and Canada. The Dynapack unit is certified to operate on natural gas.

The Dynapack unit is NOT certified for installation in a mobile home.Installations in the USA must be in accordance with city, county, or state codes and regulations. If local codes do not apply then the installation must be made in accordance with the National Fuel Gas Code and the National Electrical Code.

Installations made in Canada likewise must be in accordance with city, provincial, or national codes or the current version of CANI-B149 Installation Code.

WARNING! In the state of Massachusetts: This product must be installed by a licensed Plumber or Gas Fitter. When flexible connectors are used, the maximum length shall not exceed 36". When lever-type gas shutoffs are used, they shall be T-handle type.

The outdoor fan discharge or the condenser air intake cannot be connected to field fabricated ducting. This unit can only be installed using the factory supplied wall sleeves.

LOCATIONIMPORTANT: The Dynapack condensate drain system is designed to be installed in a conditioned space. To prevent freezing of the drain condensate in the P-Trap, the installation location should not be exposed to freezing conditions. In installations where the drain system is exposed to freezing conditions, we offer an optional heated P-Trap which is available for purchase. The part number for the heated P-Trap installation kit is K/10348 and the steps for installation are outlined in Appendix A.

The Dynapack unit is approved for indoor installation only and must be installed with one of the factory supplied wall sleeves. The unit is intended to be installed in a closet or equipment room. The unit is certified for 0” clearance to the cabinet sides, cabinet back and the first 3 feet of the supply duct. However for accessibility reasons it is recommended to maintain at least 1” clearance on the sides for proper installation and servicing. For closet installations allow 4” clearance from the unit door panels to the closet door. For equipment room installations allow 24”clearance from the unit door panels to a wall for servicing.

The wall sleeve and grille is intended to be installed flush with the exterior wall. The unit, wall sleeve, and grille are required to be installed certain distances from adjacent doors, operable windows and shrubbery. See Figure 9.

CAUTION: The unit must be installed level front to back and side to side. Adjust front leveling legs as necessary.

WALL SLEEVE AND GRILLE INSTALLATIONRefer to installation instructions included with the wall sleeve kit for guidance in assembling and installing the wall sleeve and grille.

TOP VIEW

4" MIN. TO DOOR

1" RECOMMENDED 1" RECOMMENDED

CONTROL WIRES ELECTRICAL POWER

Figure 1CAUTION: The sleeve will support the back of the unit.

VENTINGThe Dynapack unit uses outside air for combustion and vents the exhaust products directly outside. The Dynapack unit cannot be vented with other appliances. The venting system of the Dynapack unit cannot be modified or adjusted in any manner other than what is specified in these instructions.

The installation must be planned before hand so that the unit exhaust vent location complies with local or national codes in regards to distances between the unit vent and doors, operable windows, side walks, balconies, and patios. See the National Fuel Gas Code Z223.1 for the USA or Installation Code CANI-B149 for Canada. See Figure 9.

The venting system for the Dynapack 90% condensing furnace must be completed in the field using 1 1/2 inch PVC schedule 40 DWV pipe. The vent pipe will be straight for the full unit width wall sleeves. See Figure 2 for the typical full unit width vent pipe installation. The vent pipe must terminate approximately two inches outside the exterior grille.

INSERT STRAIGHT 1 1/2" SCHEDULE 40 PVC VENT1. PIPE THROUGH OPENING IN GRILLE. IN CANADA,

PIPE MUST BE SYSTEM 636 MATERIAL

APPLY PVC PIPE CEMENT TO PIPE AND INSERT2.INTO ELBOW.

3. SEE TABLE 1 FOR PIPE CUT LENGTH.

*CURTAIN WALL

WHEN INSTALLED, PIPE SHOULDEXTEND PAST GRILLE 2"±1/2"

Figure 2

3 Suburban DynaPack H Series Owner's Manual 10/2017 Rev.4

CONDENSATE DRAIN - FURNACEThe high efficiency furnace in this unit will produce condensate when operating. In addition, a trap is needed in order to overcome the negative pressure produced by the combustion inducer blower.

1. With the gas valve and outdoor section access panels removed, connect the drain trap to the internal drain hoses using the 90 degree barb fittings provided.

2. Install the ¾ x ¾ x 5/8 tee fitting in the air conditioner drain at the level of the combustion condensate trap.

3. Complete the furnace drain line by installing a barb fitting into the drain trap hose.

4. Install a 5/8 vinyl hose between the barb sitting and the tee fitting installed in the air conditioner drain line. See Figure 5. The furnace condensate line will self-prime on startup.

Note: The furnace drain and air conditioner condensate drain are open to the atmosphere which gives pressure equalization on the sewer trap preventing “double trapping.”

ELECTRICAL CONNECTIONSThe Dynapack unit is approved using copper conductors only. See the unit data plate for unit minimum circuit ampacity. Size the wire based on the unit circuit ampacity, type of wire used, and method of wiring, in conduit or open. If the electrical supply is 208 volt, then do not exceed 2% voltage drop based on the length of wire run. See the National Electrical Code or the Canadian Electrical Code for more information.

The typical electrical supply is two phase wires where voltage measured is 208-230 volts phase to phase. An additional wire for unit grounding is required. See the unit data plate for the maximum fuse or circuit breaker size. It is recommended that time delay fuses or a two pole HACR breaker be used in order to prevent nuisance trips.

Alternately, the Dynapack unit may be wired with one phase wire where the voltage measured is 208-230 volts phase to neutral. In this case, the phase wire should be connected to L1 on the contactor. An additional wire for unit grounding is required.

On 208 volt systems the transformer wiring needs to be changed. Swap the red transformer wire for the orange wire for 208 volt operation.

A disconnect should be installed next to the unit so the electrical power can be turned off for servicing or maintenance.

GAS SUPPLYAll Dynapack units are built to operate on natural gas.Minimum gas supply pressure for purposes of input adjustment: Minimum MaximumNatural Gas 5" W.C. * 7" W.C.

*Water Column

GAS PIPINGThe Dynapack unit has a ½” pipe connection for the gas line. The size of the gas piping must be based on the length of the run and not the connection size. See table 5 for reference pipe sizing.

Consult with the local gas utility or code authority for gas piping installation.

If local codes allow the use of a flexible gas appliance connector, always use a new listed connector. Do not use a connector which has previously serviced another gas appliance.

The gas piping should contain a manual shut off valve with test port near the furnace in addition to a drip leg and a ground joint union for servicing. The test port needs to be upstream of the manual shut off valve for leak testing and adjusting the supply pressure regulator.

The manual shut off valve must be rated for the gas piping test pressure. If not, then the shut off valve must be removed from the piping system during testing. Once the gas piping up to the shut off valve has been tested, the remaining piping to the unit gas valve must be tested. Do not exceed ½ psig or 14” water column for this test or the gas valve may be damaged.

RETURN SUPPLY

ACCESS PANEL TO

CONTROLS

ACCESS PANEL TO GAS VALVE AND BURNERS

ACCESS PANEL TO COMPRESSOR

AND OUTDOOR FAN

DRIP LEG (FIELD SUPPLIED)

MANUAL SHUTOFF VALVE WITH 1

8"NPT PLUGGED TAPPING,ACCESSIBLE FOR TEST GAUGECONNECTION (FIELD SUPPLIED)

CONDENSATE DRAIN

GROUND JOINT UNION(FIELD SUPPLIED)

FILTER DOOR

TRAP

ROUTE TO BUILDING DRAIN

ELECTRICAL POWER ENTRANCE

FRONT VIEW

3/4" X 3/4" X 5/8" TEEDRAIN TRAP TUBE

18"

Figure 5

#10-24 X 1 12MACHINE SCREW

LEG LEVELER

38-16 HEX NUT

THE LEVELER BRACKET INSTALLSINTO UNIT BRACKET AND IS HELD

IN PLACE BY THE UNIT WEIGHT

#12 X .75" DRILL SCREWS(2 PLACES)

LOCATE BRACKET BY INSTALLINGTHE TAB UNDER THE UNIT BASEAND ABOVE THE BASE RAIL.

TINNERMAN CLIP

ATTACH BRACKET TO UNITWITH (2) #10 X 1/2" DRILL SCREWS(2 ON EACH BRACKET)

ENGAGE FLANGE ON WALL SLEEVEWITH FLANGE ON STRAP. TIGHTENMACHINE SCREWS UNTIL BRACKETCAN BE SECURED TO UNIT WITHDRILL SCREWS.

Figure 4

WALL SLEEVE (Nominal)

MAX WALL THICKNESS

PVC PIPE CUT LENGTH (Inches)

PIPE LENGTH EXTENSION FROM

UNIT

WALL SLEEVE STOCK NUMBERS

SHORT LONG

*CW 3 7/8" 27" 6" ---------- ----------4" 5 7/8" 29" 8" 1741 17366" 7 7/8" 31" 10" 1742 17378" 9 7/8" 33" 12" 1743 1738

10" 11 7/8" 35" 14" 1744 173912" 13 7/8" 37" 16" 1745 174014" 15 7/8" 39" 18" 1769 177016" 17 7/8" 41" 20" 1771 177217" 18 7/8" 42" 21" 1773 177418" 19 7/8" 43" 22" ---------- ----------20" 21 7/8" 45" 24" ---------- ----------22" 23 7/8" 47" 26" ---------- ----------

TABLE 1

Suburban DynaPack H Series Owner's Manual 10/2017 Rev.4 4

REQUIREMENTS FOR INSTALLATIONCommonwealth of Massachusetts

For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gas fitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.

a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.

3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one half (½) inch in size, “GAS VENT DIRECTLY BELOW, KEEP CLEAR OF ALL OBSTRUCTIONS”.

4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.

(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and

2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

VALVE ON/OFF SWITCH

INLET PRESSURE POST.TEST HOSE GOES OVER

OUTSIDE OF POST. USE 3

32 " HEX WRENCH TO OPEN ONE TURN.

OUTLET PRESSURE POST.TEST HOSE GOES OVEROUTSIDE OF POST. USE3

32 " HEX WRENCH TO OPENONE TURN.

INLET 12" NPT

REGULATOR ADJUSTMENTBENEATH THIS SCREW COVER

Figure 6

INDOOR CFM vs STATIC PRESSURE (Dry coil + no air filter)Model Number Blower

Speed 0.10" wc 0.15" wc 0.20" wc 0.25" wc 0.30" wc 0.40" wc 0.50" wc 0.60" wc 0.70" wc 0.80" wc

DYPA12AC1A***

LO 497 473 448 424 400 348 296 247 212 160MED LO 577 562 547 522 497 458 415 357 317 281

MED 757 748 739 716 692 670 635 586 558 521MED HI 937 920 905 888 872 852 827 790 728 677

HI 1060 1050 1042 1015 977 927 876 824 758 700

DYPA18AC1A***

LO 512 491 469 428 387 320 285 250 213 179MED LO 596 568 540 522 504 447 415 381 324 291

MED 773 761 748 730 711 675 640 622 586 550MED HI 972 955 938 927 915 874 850 825 796 766

HI 1108 1091 1074 1057 1039 1002 970 917 868 796

DYPA24AC1A***

LO 504 483 461 420 379 312 252 207 N/R N/RMED LO 588 560 532 514 496 439 377 320 262 202

MED 765 753 740 722 703 667 622 572 532 482MED HI 964 947 930 919 907 866 828 782 757 702

HI 1100 1083 1066 1049 1031 994 962 922 882 827

DYPA30AC1A***

LO 490 465 440 415 385 310 225 170 N/R N/RMED LO 570 540 520 500 476 415 365 310 250 205

MED 768 755 741 732 704 666 621 580 535 500MED HI 934 922 913 895 873 835 800 760 730 690

HI 1064 1046 1017 1009 995 965 935 900 875 828

DYPA36AC1A***

LO 490 465 440 415 385 310 225 170 N/R N/RMED LO 570 540 520 500 476 415 365 310 250 205

MED 768 755 741 732 704 666 621 580 535 500MED HI 934 922 913 895 873 835 800 760 730 690

HI 1064 1046 1017 1009 995 965 935 900 875 828

TABLE 3

CAUTION: Suburban does not recommend the use of flex tubing to make the gas connections to the unit unless the flex tubing is a high quality stainless certified by CSA and approved for use by local code.

WARNING! A pipe thread compound resistant to the action of natural gas must be used on all pipe joints.

WARNING! The gas valve supplied with this furnace is rated at 1/2 psig maximum. Any higher pressure may rupture the pressure regulator diaphragm and may cause over firing of the burners and improper burner operation. The over firing may result in the creation of carbon monoxide which could cause asphyxiation.

WARNING! FIRE OR EXPLOSION HAZARD! Failure to follow the safety warning exactly could result in serious injury, death, or property damage.

WARNING! Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury, or loss of life.

CONTROL WIRINGThe room thermostat should be installed on an interior wall and near the return air for the unit. It is recommended that a 5 conductor thermostat wire be used in case the room thermostat needs power from the unit transformer.

The low voltage pigtails for the thermostat wiring must be routed to the outside of the Dynapack unit for connection. The Dynapack unit contains a second knockout above the control box for this purpose. The National Electrical Code requires that low voltage wiring be kept separate from high voltage wiring and cannot be routed through the same knockout or conduit. Local codes may also require that an electrical box be installed on the low voltage knockout to contain the electrical connections.

Follow the thermostat manufacturers instructions for mounting and wiring. The low voltage is grounded inside the unit control box. See Figure 8.

5 Suburban DynaPack H Series Owner's Manual 10/2017 Rev.4

14. Compare the measured temperature rise to the nameplate range. If the measured rise is lower than the nameplate minimum, then select the next lower blower speed for the heating speed. If the measured temperature rise is above the nameplate maximum, then select the next higher blower speed for the heating speed.

15. If a new blower speed was selected then re-measure the temperature rise and repeat the adjustment if needed.

COOLING ADJUSTMENTSThe only cooling adjustment that can be made is in the blower speed. 1. Turn the unit on in the cooling mode and allow to operate until stable.2. Place a thermometer in the return air opening and another in the supply air

opening as close to the unit as possible. 3. The a/c unit must operate until condensate water is coming off of the

evaporator coil. Measure the return and supply air temperatures.4. Proper cooling operation is obtained if there is a 20 degree Fahrenheit drop

in air temperature through the a/c unit.5. If the air temperature drop is greater than 22 degrees then switch the cooling

speed to the next higher speed. If the air temperature drop is less than 18 degrees then switch the cooling speed to the next lower blower speed.

NOTE: If the cooling speed and the heating speed are the same, then the heating pigtail from the board and the cooling pigtail from the board can be attached to the same pigtail from the motor. Cap and secure with electrical tape all unused blower speed pigtails.

SYSTEM PERFORMANCEThe unit has been factory tested to insure proper air conditioning performance. If it is suspected that there is a refrigerant leak in the unit then the charge can be checked by placing a thermometer on the liquid line near the filter dryer and connecting a pressure gauge to the high side pressure fitting. Use a R410A saturated temperature chart to calculate the liquid subcooling. The unit is properly charged if it is operating between 8 and 14 degrees subcooling at any outdoor temperature above 65° F. See DYPA12 charging instructions below.

The system should be checked to see that none of the wiring worked loose during shipment.

ROOM AIR BLOWERThe Dynapack unit contains a 5 speed motor to allow a range of adjustments so the proper cooling and heating speeds can be obtained after installation. Table 4 lists the factory settings for the heating and cooling speeds based on capacity. The factory settings should work for most installations but the actual ductwork will dictate the best settings for your installation. The indoor motor is permanently lubricated and does not require periodic re lubricating.

The room air blower is controlled by the unit control board in addition to the wall thermostat. With the thermostat fan switched to ‘AUTO’, the room air blower will operate only when there is a call for heat or cooling. If the thermostat fan switch is switched over to ‘ON’, then the room air blower will run continuously. The control board will over ride the wall thermostat when switched to ‘AUTO’. There are various delay timings built into the board to delay starting and stopping of the room air blower to increase comfort and energy efficiency.

The furnace also contains safety limits that will operate when an abnormal condition is detected. These limits serve a particular purpose and should not be tampered with by relocating or wiring around. If the furnace does not operate, or the room air blower does not come on, or the a/c unit does not operate, then call a licensed service technician to diagnose and repair.

The Dynapack unit is designed certified to operate up to 4500 feet above sea level without modification for both the USA and Canada. Call Technical Service at 423-775-2131 for installations above 4500 feet.

OPERATION IN EXTREME COLD OR SNOWY AREASIn those areas where the ambient temperature is consistently below 0° F, indoor comfort can be improved by adjusting the heating blower speed to obtain the maximum temperature rise allowed per the unit data plate.

A Dynapack unit installed on the ground floor must have the furnace intake and exhaust above the anticipated snow fall for that area. Higher snowfall than anticipated will block the furnace intake and lead to the unit shutting off.

UNIT START - UP

WARNING! Failure to follow these instructions may lead to a fire, explosion, property damage, personal injury, or loss of life.

CAUTION: This furnace is equipped with a direct ignition control. Do not attempt to manually light the burners.

BEFORE OPERATING, smell all around the appliance area for gas. Be sure to smell next to the floor because gas is heavier than air and will settle on the floor. If you smell gas STOP. Open the windows and doors to clear out any gas. Recheck all gas piping and connections for leaks.

TO CHECK THE UNIT OPERATION:1. Make sure the gas valve is switched ON. Remove the gas

compartment door. Turn the gas valve knob or move the switch to the ON position. See figure 6. Do not use any tools to turn the knob. If you are unable to push in and turn the knob by hand then call a qualified service technician for assistance. Replace the gas compartment door.

2. Turn on electrical power to the unit.3. Switch the room thermostat to heat.4. Raise the set point to above the room temperature.5. The thermostat will call for heat and the combustion blower will

begin to operate.6. The combustion blower will operate for 15 to 20 seconds before

the ignition controls begins sparking, then the gas valve will open and the burners will light. The burners can be viewed through the sight glass in the door panel.

7. The room air blower starts 30 seconds after the burners light.8. Once the room reaches the set temperature, the burners turn off

and the room air blower turns off 90 seconds later.9. Switch the room thermostat over to cooling.10. Lower the set point to below the room temperature.11. After a slight delay the room air blower will begin to run and the

compressor will start. Note: There will be a 5 minute delay in the compressor starting if the thermostat set point was raised and then lowered again.

12. Once the room reaches the set temperature, the compressor will turn off and the room air blower will turn off 30 seconds later.

TO SHUT DOWN UNITTo turn off the unit switch the room thermostat to OFF. Turn the electrical power off and close the manual gas supply valve before performing any service to the unit.

HEATING ADJUSTMENTS1. Turn off the unit at the room thermostat and shut off the manual gas valve. 2. Connect a pressure gauge with suitable range (0 to 10” for natural gas) to

the inlet pressure port on the gas valve. See figure 6.3. Open the manual gas valve and turn the unit on.4. Once the furnace is operating, check the inlet gas pressure. Adjust the

pressure regulator to obtain an inlet pressure of 5” to 7” water column for natural gas.

5. Turn off the unit and shut off the manual gas valve.6. Move the pressure gauge to the manifold pressure port on the gas valve.

See figure 6.7. Once the furnace is operating, check the manifold pressure. Adjust the gas

valve pressure regulator to obtain a manifold pressure of 3.5” water column for natural gas.

8. On natural gas installations the input to the furnace must be checked to insure safe operation. Any other gas appliances that use the gas meter must be turned off including the pilot lights.

9. With the Dynapack furnace running, count the time it takes for the gas meter to make one revolution. Also record the gas meter rate of cubic feet per revolution. You will also need the average heating value of the natural gas for your location. Plug these factors into the equation below to calculate the gas input rate to the furnace in BTU per hour.

BTU/HR Input =

Cubic Feet Per Revolution

X 3600 X Heating ValveNumber of Seconds Per

Revolution

10. Your recorded value on input must be within + or- 2% of the rated input. If it is not then adjust the manifold pressure lower to reduce the input or higher to increase the input. Do not go outside of 3.2” to 3.8” water column.

11. Turn off the unit, close the manual gas valve, and remove the pressure gauge. Make sure the gas valve pressure port plug screws are tightened along with the gas valve regulator cap. Replace the burner compartment door.

12. Open the manual gas valve and turn on the furnace.13. Place a thermometer in the return air along with one in the supply air

as close to the furnace as possible. Once the supply air temperature is constant, record both temperatures. Subtract the return air temperature from the supply air temperature. This difference is the temperature rise of the furnace.

Suburban DynaPack H Series Owner's Manual 10/2017 Rev.4 6

MAINTENANCEWARNING! Disconnect all electrical power to the unit before conducting any maintenance procedures. Failure to disconnect the power could result in personal injury or death.

BURNERS:The burners can be removed for cleaning or changing orifices. PLEASE NOTE: This service must be performed by a qualified technician.

HEAT EXCHANGERThe heat exchanger should be inspected periodically by a qualified technician and cleaned if necessary. If cleaning is necessary, use a stiff brush with a wire handle to remove scale and soot. While cleaning the heat exchanger, the vent extension tube should also be cleaned. Remove the four screws on the combustion blower mounting plate and take out the blower. Use a brush to clean the vent extension tube.

COOLING SYSTEMThe refrigeration system normally requires no maintenance since it is a closed, self-contained system. Periodic maintenance is limited to:

• Cleaning the air filter. Follow directions noted on the filter and label attached to the access panel.

• Cleaning the condenser coil if covered with any foreign material, lint, leaves, or other obstructions.

On DYPA12 models, place a thermometer on the compressor suction line above the accumulator. Connect a pressure gauge to the suction line pressure port. Use a R410A saturated temperature chart to calculate the suction super heat. Acceptable values are shown on the chart below.

ModelRecommendedHeating Speed

Approx.CFM

Approx.Temp Rise F

RecommendedCooling Speed

Approx.CFM

DYPA12AC1A039H high 1000 35 Low 400

DYPA18AC1A039H high 1000 35 medium low 550

DYPA18AC1A052H high 1000 45 medium low 550

DYPA24AC1A039H high 1000 35 medium 700

DYPA24AC1A052H high 1000 45 medium 700

DYPA30AC1A039H high 1000 35 medium high 900

DYPA30AC1A052H high 1000 45 medium high 900

DYPA36AC1A039H high 1000 35 high 1000

DYPA36AC1A052H high 1000 45 high 1000

Table 4

NominalIron Pipe

Size,Inches

InternalDiameter,

Inches

LENGTH OF PIPE (Feet)

10 20 30 40 50 60 70 80 90 100 125 150 175 200

1/4 .364 32 22 18 15 14 12 11 11 10 9 8 8 7 6

3/8 .493 72 49 40 34 30 27 25 23 22 21 18 17 15 14

1/2 .622 132 92 73 63 56 50 46 43 40 38 34 31 28 26

3/4 .824 278 190 152 130 115 105 96 90 84 79 72 64 59 55

1 1.049 520 350 285 245 215 195 180 170 160 150 130 120 110 100

1 - 1/4 1.380 1,050 730 590 500 440 400 370 350 320 305 275 250 225 210

1 - 1/2 1.610 1,600 1,100 890 760 670 610 560 530 490 460 410 380 350 320

2 2.067 3,050 2,100 1,650 1,450 1,270 1,150 1,050 990 930 870 780 710 650 610

2 - 1/2 2.469 4,800 3,300 2,700 2,300 2,000 1,850 1,700 1,600 1,500 1,400 1,250 1,130 1,050 980

3 3.068 8,500 5,900 4,700 4,100 3,600 3,250 3,000 2,800 2,600 2,500 2,200 2,000 1,850 1,700

4 4.025 17,500 12,000 9,700 8,300 7,400 6,800 6,200 5,800 5,400 5,100 4,500 4,100 3,800 3,500

TABLE 5Maximum Capacity of Pipe in Cubic Feet of Gas per Hour for Gas Pressures of 0.5 PSIG or Less and a Pressure Drop of 0.3 Inch Water Column

(Based on a 0.60 Specific Gravity Gas)

0

5

10

15

20

25

30

60 70 80 90 100 110 120

Com

pres

sor S

uctio

n Su

perh

eat

Outside Temperature F

DYPA12AC1A*** Charging Chart

7 Suburban DynaPack H Series Owner's Manual 10/2017 Rev.4

DYNAPACK ACCESSORIESPart No. Description Unit

1817 Architectural Grille, Aluminum Finish DYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

1818 Architectural Grille, Bronze Finish DYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

1819 Architectural Grille, Aluminum Finish DYPA30AC1A*** and DYPA36AC1A***

1820 Architectural Grille, Bronze Finish DYPA30AC1A*** and DYPA36AC1A***

1741 4" Wall Sleeve Kit DYPA12, DYPA18 and DYPA24

1736 4" Wall Sleeve Kit DYPA30 and DYPA36

1742 6" Wall Sleeve Kit DYPA12, DYPA18 and DYPA24

1737 6" Wall Sleeve Kit DYPA30 and DYPA36

1743 8" Wall Sleeve Kit DYPA12, DYPA18 and DYPA24

1738 8" Wall Sleeve Kit DYPA30 and DYPA36

1744 10" Wall Sleeve Kit DYPA12, DYPA18 and DYPA24

1739 10" Wall Sleeve Kit DYPA30 and DYPA36

1745 12" Wall Sleeve Kit DYPA12, DYPA18 and DYPA24

1740 12" Wall Sleeve Kit DYPA30 and DYPA36

1769 14" Wall Sleeve Kit DYPA 12, DYPA 18, and DYPA 24

1770 14" Wall Sleeve Kit DYPA 30 and DYPA 36

1771 16" Wall Sleeve Kit DYPA 12, DYPA 18, and DYPA 24

1772 16" Wall Sleeve Kit DYPA 30 and DYPA 36

1773 17" Wall Sleeve Kit DYPA 12, DYPA 18, and DYPA 24

1774 17" Wall Sleeve Kit DYPA 30 and DYPA 36

1821 18" Wall Sleeve Kit DYPA 12, DYPA 18, and DYPA 24

1822 18" Wall Sleeve Kit DYPA 30 and DYPA 36

1823 20" Wall Sleeve Kit DYPA 12, DYPA 18, and DYPA 24

1824 20" Wall Sleeve Kit DYPA 30 and DYPA 36

1825 22" Wall Sleeve Kit DYPA 12, DYPA 18, and DYPA 24

1826 22" Wall Sleeve Kit DYPA 30 and DYPA 36

WALL SLEEVE DIMENSIONS (Refer to Figure 7 on the following page)Part No. A B C D E Unit

1741 5 7/8 6 3/4 28 5/8 28 9/16 28 3/4 DYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

1742 7 7/8 8 3/4 28 5/8 28 9/16 28 3/4 DYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

1743 9 7/8 10 3/4 28 5/8 28 9/16 28 3/4 DYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

1744 11 7/8 12 3/4 28 5/8 28 9/16 28 3/4 DYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

1745 13 7/8 14 3/4 28 5/8 28 9/16 28 3/4 DYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

1769 15 7/8 16 3/4 28 5/8 28 9/16 28 3/4 DYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

1771 17 7/8 18 3/4 28 5/8 28 9/16 28 3/4 DYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

1773 18 7/8 19 3/4 28 5/8 28 9/16 28 3/4 DYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

1821 19 7/8 20 3/4 28 5/8 28 9/16 28 3/4 DYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

1823 21 7/8 22 3/4 28 5/8 28 9/16 28 3/4 DYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

1825 23 7/8 24 3/4 28 5/8 28 9/16 28 3/4 DYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

1736 5 7/8 6 3/4 32 5/8 28 9/16 32 3/4 DYPA30AC1A*** and DYPA36AC1A***

1737 7 7/8 8 3/4 32 5/8 28 9/16 32 3/4 DYPA30AC1A*** and DYPA36AC1A***

1738 9 7/8 10 3/4 32 5/8 28 9/16 32 3/4 DYPA30AC1A*** and DYPA36AC1A***

1739 11 7/8 12 3/4 32 5/8 28 9/16 32 3/4 DYPA30AC1A*** and DYPA36AC1A***

1740 13 7/8 14 3/4 32 5/8 28 9/16 32 3/4 DYPA30AC1A*** and DYPA36AC1A***

1770 15 7/8 16 3/4 32 5/8 28 9/16 32 3/4 DYPA30AC1A*** and DYPA36AC1A***

1772 17 7/8 18 3/4 32 5/8 28 9/16 32 3/4 DYPA30AC1A*** and DYPA36AC1A***

1774 18 7/8 19 3/4 32 5/8 28 9/16 32 3/4 DYPA30AC1A*** and DYPA36AC1A***

1822 19 7/8 20 3/4 32 5/8 28 9/16 32 3/4 DYPA30AC1A*** and DYPA36AC1A***

1824 21 7/8 22 3/4 32 5/8 28 9/16 32 3/4 DYPA30AC1A*** and DYPA36AC1A***

1826 23 7/8 24 3/4 32 5/8 28 9/16 32 3/4 DYPA30AC1A*** and DYPA36AC1A***

WARNING! The unit must be installed with approved wall sleeve and grille accessories for safe operation. Improper installations could result in property damage, personal injury, or death.

Suburban DynaPack H Series Owner's Manual 10/2017 Rev.4 8

Figure 7

T1 CC

L1COMP

C R L2CC

T2

1Ø POWER SUPPLY208/230V 60 Hz

G

CMB BLOWER

TRANSFORMER

HPSLPS

BR BR BK

RG

WHTY

BK

BK

BK

BK

HUM

L1

L1

R

YACB HEAT

ACB COOL

24V

24V

UNUSED

SPARKIGNITER

CCBK BK

BK

24 VAC

GROUND

Y WC RG

PK

HUM

FLAME

24V

FLAMESWITCH

BL

O 230V

INDUCER

BK

R

OFM

C

BKBR

WHT

GASVALVE

SWITCHHIGH LIMIT

ROLLOUTSWITCH

SWITCHPRESSURE

O

BL

PK

PK

R

O

G

BL

Y

BL

BL

BL

O

NOTE 1

Y

BK

PK

BL

BL

LIMITBLOWER

R

O

PUR BK

S

BK

Y

R

RC

BK

BL

BL

BL

BL

NG

L

C

43

2

1

5R

BL

G

1. INTERCHANGE ORANGE AND RED LEADS FOR 208V SUPPLY.2. OPTIONAL CAPACITOR ON SOME MODELS.

R

CNOTE 2

IBM

Figure 8

28 332

WALL SLEEVE

A

B

C

D

E

REQUIRED WALL OPENING

9 Suburban DynaPack H Series Owner's Manual 10/2017 Rev.4

Figure 9

VE

NT

TER

MIN

AL

AIR

SU

PP

LY IN

LET

XA

RE

A W

HE

RE

TE

RM

INA

L IS

NO

T P

ER

MIT

TED

A=

CLE

AR

AN

CE

AB

OV

E G

RA

DE

, V

ER

AN

DA

, PO

RC

H, D

EC

K, O

R

BA

LCO

NY

12 IN

CH

ES

(30c

m)

(SE

E N

OTE

a)

12 IN

CH

ES

(30c

m)

(SE

E N

OTE

a)

J=C

LEA

RA

NC

E T

O N

ON

ME

CH

AN

ICA

L A

IR S

UP

PLY

INLE

T TO

BU

ILD

ING

O

R T

HE

CO

MB

US

TIO

N A

IR IN

LET

TO A

NY

OTH

ER

AP

PLI

AN

CE

.

CA

NA

DIA

N IN

STA

LLAT

ION

SU

S IN

STA

LLAT

ION

S1

2

6 IN

CH

ES

(15c

m) F

OR

A

PP

LIA

NC

ES

£10

,000

Btu

h (3

kw),

12 IN

CH

ES

(30c

m) F

OR

A

PP

LIA

NC

ES

> 1

0,00

0 B

tuh

(3kw

) A

ND

£ 1

00,0

00 b

tuh

(30k

w)

6 IN

CH

ES

(15c

m) F

OR

AP

PLI

AN

CE

S

£10,

000

Btu

h (3

kw),

9 IN

CH

ES

(23c

m) F

OR

AP

PLI

AN

CE

S

> 10

,000

Btu

h (3

kw) A

ND

£

50,0

00

Btu

h (1

5kw

)12

INC

HE

S (3

0CM

) FO

R

AP

PLI

AN

CE

S >

50,

000

Btu

h (1

5kw

)

B=

CLE

AR

AN

CE

TO

WIN

DO

W O

R

DO

OR

TH

AT M

AY B

E O

PE

NE

D6

INC

HE

S (1

5cm

) FO

R

AP

PLI

AN

CE

S £

10,0

00 B

tuh

(3kw

), 12

INC

HE

S (3

0cm

) FO

R

AP

PLI

AN

CE

S >

10,

000

Btu

h (3

kw)

AN

D £

100

,000

btu

h (3

0kw

)

CA

NA

DIA

N IN

STA

LLAT

ION

SU

S IN

STA

LLAT

ION

S1

2

6 IN

CH

ES

(15c

m) F

OR

AP

PLI

AN

CE

S

£10,

000

Btu

h (3

kw),

9 IN

CH

ES

(23c

m) F

OR

AP

PLI

AN

CE

S

> 10

,000

Btu

h (3

kw) A

ND

£

50,0

00

btuh

(15k

w)

12 IN

CH

ES

(30C

M) F

OR

AP

PLI

AN

CE

S

> 50

,000

Btu

h (1

5kw

)

K=

CLE

AR

AN

CE

TO

A M

EC

HA

NIC

AL

AIR

SU

PP

LY IN

LET

6 FE

ET

(1.8

3m)

3 FE

ET

(91c

m) A

BO

VE

IF W

ITH

IN 1

0FE

ET

(3m

) HO

RIZ

ON

TALL

Y

C=

CLE

AR

AN

CE

TO

WIN

DO

W O

R

DO

OR

TH

AT M

AY B

E O

PE

NE

D*

a*

aL=

CLE

AR

AN

CE

AB

OV

E P

AVE

D

SID

EW

ALK

OR

PAV

ED

DR

IVE

WAY

LO

CAT

IED

ON

PU

BLI

C P

RO

PE

RTY

7 FE

ET

(2.1

3m)

* a

D=

VE

RTI

CA

L C

LEA

RA

NC

E T

O

VE

NTI

LATE

D S

OFF

IT L

OC

ATE

D

AB

OV

E T

HE

TE

RM

INA

L W

ITH

IN A

H

OR

IZO

NTA

L D

ISTA

NC

E O

F 2

FEE

T (6

1cm

) FR

OM

TH

E C

EN

TER

LIN

E

OF

THE

TE

RM

INA

L

* a

* a

M=

CLE

AR

AN

CE

UN

DE

R V

ER

AN

DA

, P

OR

CH

, DE

CK

, OR

BA

LCO

NY

12 IN

CH

ES

(30c

m)

* a

E=

CLE

AR

AN

CE

TO

UN

VE

NTI

LATE

D S

OFF

IT*

a*

a

F=C

LEA

RA

NC

E T

O O

UTS

IDE

CO

RN

ER

* a

* a

G=

CLE

AR

AN

CE

TO

INS

IDE

CO

RN

ER

* a

* a

H=

CLE

AR

AN

CE

TO

EA

CH

SID

E O

F C

EN

TER

LIN

E E

XTE

ND

ED

AB

OV

E

ME

TER

/ R

EG

ULA

TOR

AS

SE

MB

LY

3 FE

ET

(91c

m) W

ITH

IN A

HE

IGH

T 15

FE

ET

(4.5

m) A

BO

VE

TH

E M

ETE

R /

RE

GU

LATO

R

AS

SE

MB

LY*

a

I=C

LEA

RA

NC

E T

O S

ER

VIC

E

RE

GU

LATO

R V

EN

T O

UTL

ET

3 FE

ET

(91c

m)

* a

1IN

AC

CO

RD

AN

CE

WIT

H T

HE

CU

RR

EN

T C

SA

B14

9.1,

NAT

UR

AL

GA

S A

ND

PR

OPA

NE

INS

TALL

ATIO

N C

OD

E2

IN A

CC

OR

DA

NC

E W

ITH

TH

E C

UR

RE

NT

AN

SI Z

223.

1/N

FPA

54, N

ATIO

NA

L FU

EL

GA

S C

OD

EA

VE

NT

SH

ALL

NO

T TE

RM

INAT

E D

IRE

CTL

AB

OV

E A

SID

EW

ALK

OR

PAV

ED

DR

IVE

WAY

TH

T IS

LO

CAT

ED

BE

TWE

EN

TW

O S

ING

LE

FAM

ILY

DW

ELL

ING

S A

ND

SE

RV

ES

BO

TH D

WE

LLIN

GS

PE

RM

ITTE

D O

NLY

IF V

ER

AN

DA

, PO

RC

H, D

EC

K, O

R B

ALC

ON

Y IS

FU

LLY

OP

EN

ON

A M

INU

MU

M O

F TW

O S

IDE

S

BE

NE

ATH

TH

E F

LOO

R.

FOR

CLE

AR

AN

CE

S N

OT

SP

EC

IFIE

D IN

AN

SI Z

223.

1/N

FPA

54 O

R C

SA

B14

9.1,

ON

E O

F TH

E F

OLL

OW

ING

SH

ALL

BE

IN

DIC

ATE

D:

*

A R

EFE

RE

NC

E T

O T

HE

FO

LLO

WIN

G F

OO

TNO

TE:

"CLE

AR

AN

CE

IN A

CC

OR

DA

NC

E W

ITH

LO

CA

L IN

STA

LLAT

ION

CO

DE

S A

ND

TH

E R

EQ

UIR

EM

EN

TS O

F TH

E G

AS

SU

PP

LIE

R A

ND

M

AN

UFA

CTU

RE

RS

INS

TALL

ATIO

N IN

STR

UC

TIO

NS

(SE

E M

AN

UA

L S

UP

PLI

ED

WIT

H A

PP

LIA

NC

E)

a)

OPE

RAB

LE

FIXE

D

CLO

SED

FIXE

D

CLO

SED

INSI

DE

CO

RN

ER D

ETAI

L

G

OPE

RAB

LE

A

C

FB

BBB

A

J

BI

H

MK

E

D

L

B

Suburban DynaPack H Series Owner's Manual 10/2017 Rev.4 10

Airxcel Commercial Group Limited Product WarrantyIf any part of your Airxcel Commercial Group Air Conditioner, Heat Pump or Unit Ventilator fails because of a manufacturing defect within the time frame in the table below, the Airxcel Commercial Group will furnish without charge, EXW Cordele, Georgia, the required replacement part. Any transportation, related service labor, diagnosis calls, filter, driers, and refrigerant are not included. The owner must provide proof of the date of the original start-up. The contractor’s invoice, the certificate of occupancy, or similar documents are examples of proof of the date of the original start-up.

Marvair, ICE, Eubank Suburban Applied Products90 Days DOA w/Flat Rate Labor 1 Year Parts/Labor – Flat Rate1 Year Parts 5 Years Heat Exchanger5 Years Compressor 5 Years Compressor

The following extra cost warranties are available from Airxcel Commercial Group:

Bronze Silver Gold DiamondAny Special Warranty Written for a Job 1 Year Parts/Labor 2 Years Parts/Labor 5 Years Parts/Labor

Any related service labor, diagnosis calls, filter, driers and refrigerant are not included. Airxcel Commercial Group will pay for non-priority shipping costs of the compressor during the first twelve months of the warranty period. After the first twelve months of the warranty period, all costs of shipment and risk of loss during the shipment of the compressor shall be the responsibility of the owner.

The owner of the product may ship the allegedly defective or malfunctioning product or part to Airxcel Commercial Group, at such owner’s expense, and Airxcel Commercial Group will diagnose the defect and, if the defect is covered under this warranty, Airxcel Commercial Group will honor its warranty and furnish the required replacement part. All costs for shipment and risk of loss during shipment of the product to Airxcel Commercial Group and back to the owner shall be the responsibility and liability of the owner. Upon written request by an owner, Airxcel Commercial Group may arrange for remote diagnosis of the allegedly defective or malfunctioning product or part but all costs for transportation, lodging and related expenses with regard to such diagnostic services shall be the responsibility and liability of the owner.

An owner requesting performance under this Warranty shall provide reasonable access to the allegedly defective or malfunctioning product or part to Airxcel Commercial Group and its authorized agents and employees.

This warranty applies only to products purchased and retained for use within the U.S.A., Canada, and Mexico. This warranty does not cover damage caused by improper installation, misuse of equipment or negligent servicing.

THIS WARRANTY CONSTITUTES THE EXCLUSIVE REMEDY OF ANY PURCHASER OF AN AIRXCEL COMMERCIAL GROUP HEAT PUMP OR AIR CONDITIONER AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING, WITHOUT LIMITATION, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR USE, TO THE FULLEST EXTENT PERMITTED BY LAW. IN NO EVENT SHALL ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR USE EXCEED THE TERMS OF THE APPLICABLE WARRANTY STATED ABOVE AND AIRXCEL COMMERCIAL GROUP SHALL HAVE NO OTHER OBLIGATION OR LIABILITY. IN NO EVENT SHALL MARVAIR BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OR MONETARY DAMAGES.

THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE-TO-STATE. Some states do not allow limitations or exclusions, so the above limitations and exclusions may not apply to you.

09/2017 Rev.5Supersedes 06/2004

IF YOU HAVE A PRODUCT PROBLEMFIRST: Contact the installer of the equipment or the selling dealer for warranty service. You may find his name on the product or with your homeowners manual.

If his name is not known, call your builder or general contractor if yours is a new structure.SECOND: Contact the Suburban distributor who supplied the product to the installer/dealer.THIRD: Contact: Suburban Applied Products Customer Service Department 156 Seedling Drive Cordele, GA 31015 (229) 273-3636 Fax: (229) 273-5154 www.SuburbanManufacturing.com

Please consult the Suburban Applied Products website at www.SuburbanManufacturing.com for the latest product literature. Detailed dimensional data is available upon request. A complete warranty statement can be found in each product’s Installation/Operation Manual, on our website. As part of the Suburban continuous improvement program, specifications are subject to change without notice.

P.O. Box 400 • Cordele, GA 31010156 Seedling Drive • Cordele, GA 31015 Ph: 229-273-3636 • Fax: 229-273-5154Email: [email protected]

Manufactured by:

11 Suburban DynaPack H Series Owner's Manual 10/2017 Rev.4

APPENDIX AThe Dynapack condensate drain system is designed to be installed in a conditioned space. To prevent freezing of the drain condensate in the P-Trap, the installation location should not be exposed to freezing conditions. In installations where the drain system is exposed to freezing conditions, we offer an optional heated P-Trap which is available for purchase. The part number for the heated P-Trap installation kit is K/10348.

Instructions for installing heated P-Trap kit:

1. Turn power off from main disconnect.2. Remove existing P-Trap drain.3. Remove middle & top doors and the control box cover.4. Slip extruded (black) rubber drain hose back into the unit.5. Route wires/heat cable on the supplied drain trap through the

bushing for the rubber drain hose.6. Route wires along existing wires up to Top/Line side of contactor.7. Wire as per drawing ES48000 sent with the kit to contactor &

ground lug.

8. Re-insert rubber drain hose through bushing with supplied Wires/Heat cable.

9. Insert barbed fitting on the P-Trap into rubber drain hose (soapy water can be used for easy installation).

10. Align P-Trap as needed for existing drain plumbing.11. Use wire ties to secure wires to existing wire/leads.12. Re-check connections. 13. Replace control box cover, middle & top doors.14. Unit is ready to be powered on.

APPROX. LOCATIONOF WIRES

B

DETAIL BSCALE 1 : 2

NOTE: ROUTE HEAT CABLE INHOLE/BUSHING WITH RUBBERDRAIN TUBE (MAY NEED TOPUSH DRAIN TUBE BACK OUTOF THE WAY TO RUN CABLETHROUGH HOLE) SEE STEP 4 & 8

(BLACK) RUBBER DRAIN HOSE

WIRES/HEAT CABLEHEATED P-TRAPWITH BARBED FITTINGMAY NEED TO SLIP ELBOW &BARBED FITTING OFF P-TRAPTO INSERT INTO RUBBER HOSE

CONNECT TO EXISTINGDRAIN PLUMBING

STEPS FOR INSTALLING HEATED P-TRAPTURN POWER OFF FROM MAIN DISCONNECT.1.REMOVE EXISTING P-TRAP DRAIN.2.REMOVE MIDDLE & TOP DOORS AND THE CONTROL BOX COVER.3.SLIP EXTRUDING (BLACK) RUBBER DRAIN HOSE BACK INTO THE UNIT.4.ROUTE WIRES/HEAT CABLE ON THE SUPPLIED DRAIN TRAP THROUGH 5.BUSHING FOR RUBBER DRAIN HOSE.ROUTE WIRE ALONG EXISTING WIRES UP TO TOP/LINE SIDE OF CONTACTOR.6.

7. WIRE AS PER DRAWING ES48000 TO CONTACTOR & GROUND LUG.8. RE-INSERT RUBBER DRAIN HOSE THROUGH BUSHING WITH SUPPLIED WIRES/HEAT CABLE.9. INSERT BARBED FITTING INTO RUBBER DRAIN HOSE. (SOAPY WATER CAN BE USED FOR EASY INSTALLATION)10. ALIGN P-TRAP AS NEEDED FOR EXISTING DRAIN PLUMBING.11. WIRE TIE WIRES TO EXISTING WIRE/LEADS.12. RE-CHECK CONNECTIONS. REPLACE CONTROL BOX COVER AND MIDDLE & TOP DOORS.UNIT IS READY TO BE POWERED ON.

REVISIONS

ECO# DATE REV. DESCRIPTION REV BY CHECKEDBY

10/3/2014 0 TM

SCALE DRAWN BY

APPROVED BY

TITLE

DATE DRAWING NUMBER

TOLERANCESEXCEPTAS NOTED

DECIMAL

±

FRACTIONAL

±

ANGULAR

±

REV.

Marvair Cordele, GA

This drawing contains confidential information of Marvair, a Division of AIRXCEL, Inc. This information is not to be disclosed or utilized without the expressed written permission of Marvair, a Division of AIRXCEL, Inc.

Division of AIRXCEL, Inc.

ID01580

TLC.03"

1

HEATER P-TRAP INSTALLATION INSTRUCTION

DYPA "H"

1/3/17

Suburban DynaPack H Series Owner's Manual 10/2017 Rev.4 12

ANNEXE ALe système Dynapack de drainage de condensats est conçu pour être installé dans un espace conditionné. Pour éviter que les condensats drainés dans ce siphon ne gèlent, l’emplacement de l’installation ne doit pas être exposé à une situation de gel possible. Dans des installations où le système de drainage est exposé à un possible gel, nous proposons en option à l’achat un siphon en P chauffé. La référence de pièce pour le kit d’installation de ce siphon chauffé est K/10348.

Instructions pour l’installation du siphon en P chauffé:

1. Coupez l’alimentation secteur en amont à l’interrupteur général.2. Enlevez le siphon en P de drainage existant.3. Ôtez les portes du milieu et du haut, ainsi que le couvercle du

boîtier de commande.4. Faites rentrer, en le glissant dans l’appareil, le tuyau (noir) de

drainage en caoutchouc extrudé.5. Faites passer les fils du câble de chauffage du siphon de

drainage chauffé au travers de l’œillet prévu pour le tuyau de drainage en caoutchouc.

6. Acheminez ces fils le long des fils existants jusqu’en haut de côté du contacteur.

7. Raccordez selon le schéma es48000 (inclus dans le kit) sur le contacteur et la cosse de terre.

8. Refaites passer le tuyau de drainage en caoutchouc par l’œillet où passent déjà les fils du câble de chauffage.

9. Insérez un raccord cannelé du siphon en T dans le tuyau de drainage en caoutchouc (L’utilisation d’eau savonneuse peut faciliter l’insertion).

10. Alignez le siphon en P selon le besoin par rapport à la plomberie de drainage existante.

11. Serrez des attaches sur les fils de raccordement existants.12. Vérifiez à nouveau les connexions. 13. Remettez en place le couvercle de boîtier de commande, et les

portes du milieu et du haut.14. L’appareil est prêt à être remis sous tension.

APPROX. LOCATIONOF WIRES

B

DETAIL BSCALE 1 : 2

NOTE: ROUTE HEAT CABLE INHOLE/BUSHING WITH RUBBERDRAIN TUBE (MAY NEED TOPUSH DRAIN TUBE BACK OUTOF THE WAY TO RUN CABLETHROUGH HOLE) SEE STEP 4 & 8

(BLACK) RUBBER DRAIN HOSE

WIRES/HEAT CABLEHEATED P-TRAPWITH BARBED FITTINGMAY NEED TO SLIP ELBOW &BARBED FITTING OFF P-TRAPTO INSERT INTO RUBBER HOSE

CONNECT TO EXISTINGDRAIN PLUMBING

STEPS FOR INSTALLING HEATED P-TRAPTURN POWER OFF FROM MAIN DISCONNECT. 1.REMOVE EXISTING P-TRAP DRAIN. 2.REMOVE MIDDLE & TOP DOORS AND THE CONTROL BOX COVER. 3.SLIP EXTRUDING (BLACK) RUBBER DRAIN HOSE BACK INTO THE UNIT. 4.ROUTE WIRES/HEAT CABLE ON THE SUPPLIED DRAIN TRAP THROUGH 5.BUSHING FOR RUBBER DRAIN HOSE.ROUTE WIRE ALONG EXISTING WIRES UP TO TOP/LINE SIDE OF CONTACTOR. 6.

7. WIRE AS PER DRAWING ES48000 TO CONTACTOR & GROUND LUG.8. RE-INSERT RUBBER DRAIN HOSE THROUGH BUSHING WITH SUPPLIED WIRES/HEAT CABLE.9. INSERT BARBED FITTING INTO RUBBER DRAIN HOSE. (SOAPY WATER CAN BE USED FOR EASY INSTALLATION)10. ALIGN P-TRAP AS NEEDED FOR EXISTING DRAIN PLUMBING.11. WIRE TIE WIRES TO EXISTING WIRE/LEADS.12. RE-CHECK CONNECTIONS. REPLACE CONTROL BOX COVER AND MIDDLE & TOP DOORS.UNIT IS READY TO BE POWERED ON.

REVISIONS

ECO#DATEREV.DESCRIPTIONREV BYCHECKEDBY

10/3/20140TM

SCALEDRAWN BY

APPROVED BY

TITLE

DATEDRAWING NUMBER

TOLERANCESEXCEPTAS NOTED

DECIMAL

±

FRACTIONAL

±

ANGULAR

±

REV.

MarvairCordele, GA

This drawing contains confidential information of Marvair, a Division of AIRXCEL, Inc. This information is not to be disclosed or utilized without the expressed written permission of Marvair, a Division of AIRXCEL, Inc.

Division of AIRXCEL, Inc.

ID01580

TLC.03"

1

HEATER P-TRAP INSTALLATION INSTRUCTION

DYPA "H"

1/3/17

REMARQUE : FAITES PASSER LE CÂBLE DU CHAUFFAGE DANS LE TROU AVEC ŒILLET AVEC LE TUBE DE DRAINAGE EN CAOUTCHOUC (IL PEUT ÊTRE NÉCESSAIRE DE FAIRE SORTIR LE TUBE DE DRAINAGE D’ABORD POUR FAIRE ENTRER LE CÂBLE DANS CE TROU). VOYEZ LES ÉTAPES 4 ET 8.

SIPHON EN T CHAUFFÉ AVEC RACCORD CANNELÉ. IL PEUT ÊTRE NÉCESSAIRE DE SORTIR LE COUDE ET LE RACCORD CANNELÉ DU SIPHON EN P POUR LEUR INSERTION DANS LE TUYAU EN CAOUTCHOUC.

TUYAU (NOIR) DE DRAINAGE EN CAOUTCHOUC.

EMPLACEMENT APPROXIMATIF DES FILS.

FILS DE CÂBLE DE CHAUFFAGE.

RÉALISEZ LA CONNEXION AVEC LA PLOMBERIE DE DRAINAGE EXISTANTE.

DÉTAIL B. ÉCHELLE 1:2

11

Garantie limitée des produits du groupe commercial AirxcelSi une partie quelconque d’un conditionneur d’air, d’une pompe à chaleur ou d’une unité de ventilation du groupe commercial Airxcel tombe en panne du fait d’un défaut dû à sa fabrication dans la plage de temps montrée dans le tableau qui suit, le constructeur fournira sans frais la pièce de remplacement voulue, départ usine (Cordele en Géorgie). Aucun des frais de transport, de main-d’œuvre de service, de demandes de diagnostic, de filtres, déshydrateurs ou réfrigérants, ne sont inclus. Le propriétaire du matériel doit fournir la preuve de la date de mise en service d’origine. La facture du maître d’œuvre ou le certificat d’occupation, par exemple, ou des documents similaires, peuvent servir de preuve de la mise en service d’origine.

Produits Marvair, ICE, EubankProduits SuburbanGarantie DOA de 90 jours avec allocation forfaitaire de main-d’œuvre 1 an de garantie pour pièces et main-d’œuvre (allocation forfaitaire)

1 an de garantie pour les pièces5 ans de garantie pour l’échangeur thermique

5 ans de garantie pour le compresseur5 ans de garantie pour le compresseur

Les garanties supplémentaires suivantes sont proposées pour les produits du groupe commercial Airxcel :

BronzeArgentOrDiamant Toute garantie spéciale écrite pour une tâche1 an de garantie pour les

pièces et la main-d’œuvre 2 ans de garantie pour les pièces et la main-d’œuvre

5 ans de garantie pour les pièces et la main-d’œuvre

Aucun des frais associés, de transport, de main-d’œuvre de service, de demandes de diagnostic, de filtres, déshydrateurs ou réfrigérants, ne sont inclus. Le groupe commercial Airxcel paiera les coûts de transport (en envoi non prioritaire) du compresseur pendant les douze premiers mois de la période de garantie. Après cette période des douze premiers mois, tous les coûts d’expédition et les risques de perte durant le transport du compresseur seront de la responsabilité du propriétaire.

Le propriétaire du produit peut expédier à ses frais le produit ou la pièce supposée défectueux ou en panne au groupe commercial Airxcel, qui diagnostiquera le défaut, et, s’il est couvert par cette garantie, honorera ses clauses et livrera la pièce de remplacement. L’ensemble des coûts et des risques d’expédition de produit, vers le groupe commercial Airxcel et en retour vers le client, seront pris en charge par le client. Suite à une demande écrite du propriétaire, le groupe commercial Airxcel peut organiser un diagnostic sur site du défaut ou non-fonctionnement d’un produit ou d’une pièce, mais tous les coûts de transport, d’hébergement et les dépenses associées pour un tel service seront assumés par le demandeur.

Un propriétaire requérant une intervention à ce titre dans le cadre de la garantie devra permettre un accès raisonnable au produit ou à la pièce incriminée pour les agents et employés du groupe commercial Airxcel.

Cette garantie ne s’applique que pour des produits achetés et en utilisation aux USA, au Canada et au Mexique. Elle ne couvre pas des dommages causés par une installation incorrecte, un mésusage de l’équipement ou entretien négligent.

CETTE GARANTIE CONSTITUE LE REMÈDE EXCLUSIF POUR TOUT ACHETEUR D’UNE POMPE À CHALEUR OU D’UN CLIMATISEUR DU GROUPE COMMERCIAL AIRXCEL, ET TIENT LIEU DE TOUS AUTRES TYPES DE GARANTIES, EXPLICITES OU IMPLICITES, EN INCLUANT, SANS Y ÊTRE LIMITÉ, TOUTE GARANTIE IMPLICITE DE VALEUR MARCHANDE OU D’ADÉQUATION À UNE UTILISATION DONNÉE, DANS LA PLEINE MESURE PERMISE PAR LA LOI. EN AUCUN CAS UNE QUELCONQUE GARANTIE IMPLICITE DE VALEUR MARCHANDE OU D’ADÉQUATION À UNE UTILISATION DONNÉE NE POURRA DÉPASSER LES TERMES DE LA GARANTIE APPLICABLE PRÉSENTÉE ICI, ET LE GROUPE COMMERCIAL AIRXCEL N’AURA AUCUNE AUTRE OBLIGATION OU RESPONSABILITÉ. EN AUCUN CAS, MARVAIR NE SERA TENU POUR RESPONSABLE DE DOMMAGES ANNEXES OU CONSÉCUTIFS, OU DE PERTES FINANCIÈRES.

CETTE GARANTIE VOUS DONNE DES DROITS LÉGAUX SPÉCIFIQUES, ET VOUS POUVEZ AUSSI AVOIR D’AUTRES DROITS QUI VARI-ENT D’UNE PROVINCE À L’AUTRE. Certaines provinces ne permettent pas de limitations ou exclusions, de ce fait les limitations et exclusions mentionnées précédemment peuvent ne pas être applicables pour vous.

09/2017 Rév.5Remplace la version du 06/2004

SI VOUS AVEZ DES PROBLÈMES AVEC VOTRE PRODUITPREMIÈREMENT: Communiquez avec l’installateur de l’équipement ou le marchand qui vous a vendu l’appareil pour obtenir le service sous garantie. Son nom

pourrait se trouver sur l’appareil ou dans votre manuel du propriétaire. Si vous ne connaissez pas le nom, communiquez avec votre constructeur ou l’entrepreneur général s’il s’agit d’un nouveau bâtiment.

DEUXIÈMEMENT: Communiquez avec le distributeur de produits de Suburban qui a fourni le produit à l’installateur/marchand.TROISIÈMEMENT: Communiquez avec: Suburban Applied Products Service à la clientèle 156 Seedling Drive Cordele, GA 31015 (229) 273-3636 Télécopieur : (229) 273-5154 www.SuburbanManufacturing.com

Please consult the Suburban Applied Products website at www.SuburbanManufacturing.com for the latest product literature. Detailed dimensional data is available upon request. A complete warranty statement can be found in each product’s Installation/Operation Manual, on our website. As part of the Suburban continuous improvement program, specifications are subject to change without notice.

P.O. Box 400 • Cordele, GA 31010156 Seedling Drive • Cordele, GA 31015 Ph: 229-273-3636 • Fax: 229-273-5154Email: [email protected]

Manufactured by:

10

9

FIN D

E L'É

CH

AP

PE

ME

NT

BO

UC

HE

D'A

DM

ISS

ION

D'A

IR

XS

EC

TEU

R O

Ù LE

S S

OR

TIES

NE

SO

NT PA

S P

ER

MIS

ES

A=

ES

PAC

E LIB

RE

AU

-DE

SS

US

DU

SO

L, DE

S

RA

ND

AS

, DE

S P

OR

CH

ES

, DE

S PATIO

S O

U

DE

S B

AC

LCO

NS

12 PO

UC

ES

(30 cm)

(VO

IR LA N

OTE

A)

12 PO

UC

ES

(30 cm)

(VO

IR LA N

OTE

A)

J=E

SPA

CE

LIBR

E PA

R R

AP

PO

RT À

L'EN

TRÉ

E

NO

N M

ÉC

AN

IQU

E D

AN

S L'IM

ME

UB

LE O

U

L'EN

TRÉ

E D

'AIR

DE

CO

MB

US

TION

À

N'IM

PO

RTE

QU

EL A

UTR

E A

PPA

RE

IL É

LEC

TRO

NA

GE

R

INS

TALLATIO

NS

CA

NA

DIE

NN

ES

INS

TALLATIO

NS

AM

ÉR

ICA

INE

S1

2

6 PO

UC

ES

(15 cm) P

OU

R LE

S A

PPA

RE

ILS

ÉLE

CTR

OM

ÉN

AG

ER

S D

E <10

6 PO

UC

ES

(15 cm) P

OU

R LE

S A

PPA

RE

ILS

ÉLE

CTR

OM

ÉN

AG

ER

S D

E <10 000 B

tu/h (3kw))

9 PO

UC

ES

(23 cm) P

OU

R LE

S A

PPA

RE

ILS

ÉLE

CTR

OM

ÉN

AG

ER

S D

E >10 000 B

tu/h 93 kW)) E

T DE

<50 000 B

tu/h (15 kW))

12 PO

UC

ES

(30 cm) P

OU

R LE

S A

PPA

RE

ILS

ÉLE

CTR

OM

ÉN

AG

ER

S D

E >50 000 B

tu/h (15 kW))

B=

ES

PAC

E LIB

RE

PAR

RA

PP

OR

T AU

X

FEN

ÊTR

ES

OU

AU

X P

OR

TES

QU

I PE

UV

EN

T S

'OU

VR

IR

6 PO

UC

ES

(15 cm) P

OU

R LE

S A

PPA

RE

ILS

ÉLE

CTR

OM

ÉN

AG

ER

S

<10 000 Btu/h (3 kW

)12 P

OU

CE

S (30 cm

) PO

UR

LES

AP

PAR

EILS

É

LEC

TRO

NA

GE

RS

DE

>10 000 btu/h (3 kW

))E

T <100 000 Btu/h (30 kW

)

INS

TALLATIO

NS

CA

NA

DIE

NN

ES

INS

TALLATIO

NS

AM

ÉR

ICA

INE

S1

2

6 PO

UC

ES

(15 cm) P

OU

R LE

S A

PPA

RE

ILS

ÉLE

CTR

OM

ÉN

AG

ER

S D

E <10 000B

tU/h (3 kW

))9 P

OU

CE

S (32 cm

) PO

UR

LES

AP

PAR

EILS

É

LEC

TRO

NA

GE

RS

DE

K=

ES

PAC

E LIB

RE

PAR

RA

PP

OR

T À L'E

NTR

ÉE

M

ÉC

AN

IQU

E D

'ALIM

EN

TATION

EN

AIR

6 PIE

DS

(1,83 cm)

3 PIE

DS

(91 cm) A

U-D

ES

SU

S S

I LA DIS

TAN

CE

HO

RIZO

NTA

LE

ES

T DE

10 PIE

DS

(3 m)

C=

ES

PAC

E LIB

RE

PAR

RA

PP

OR

T AU

X

FEN

ÊTR

ES

OU

AU

X P

OR

TES

QU

I PE

UV

EN

T S

'OU

VR

IR* a

* aL=

ES

PAC

E LIB

RE

AU

-DE

SS

US

DE

S TR

OTTO

IRS

PAV

ÉS

OU

DE

S E

NTR

ÉE

S PAV

ÉE

S S

ITUÉ

ES

S

UR

DE

S P

RO

PR

IÉTÉ

S P

UB

LIQU

ES

7 PIE

DS

(2,13 cm)

* a

D=

ES

PAC

E LIB

RE

À LA V

ER

TICA

LE PA

R R

AP

PO

RT

AU

PAR

EM

EN

T VE

NTILÉ

SITU

É A

U-D

ES

SU

S

DE

LA SO

RTIE

À

* a* a

M=

ES

PAC

E LIB

RE

SO

US

LES

RA

ND

AS

, LES

P

RO

CH

ES

, LES

PATIOS

OU

LES

BA

LCO

NS

12 PO

UC

ES

(30 cm)

* a

E=

ES

PAC

E LIB

RE

PAR

RA

PP

OR

T AU

PAR

EM

EN

T NO

N

VE

NTILÉ

* a* a

F=E

SPA

CE

LIBR

E PA

R R

AP

PO

RT À

UN

CO

IN E

XTÉ

RIE

UR

* a* a

G=

ES

PAC

E LIB

RE

PAR

RA

PP

OR

T À U

N C

OIN

INTÉ

RIE

UR

* a* a

H=

ES

PAC

E LIB

RE

PAR

RA

PP

OR

T À C

HA

QU

E C

ÔTÉ

D

E LA LIG

NE

CE

NTR

ALE

SE

PR

OLO

NG

EA

NT

AU

-DE

SS

US

DE

CO

MP

TEU

R/D

ÉTE

ND

EU

R

3 PIE

DS

(91 cm) PA

R R

AP

PO

RT

* a

I=E

SPA

CE

LIBR

E PA

R R

AP

PO

RT À

LA SO

RTIE

D

'ÉC

HA

PP

EM

EN

T DU

GU

LATEU

R D

E

SE

RV

ICE

3 PIE

DS

(91 cm)

* a

1C

ON

FOR

ME

NT À

LA NO

RM

E C

SA

/AC

NO

R B

149.1 EN

VIG

UE

UR

PO

UR

LE G

AZ N

ATUR

EL E

T LE C

OD

E D

'INS

TALLATIO

N D

U P

RO

PAN

E.

2C

OR

FOR

ME

NT A

UX

NO

RM

ES

AN

SI Z2231.1/N

FPA 54 EN

VIG

UE

UR

, PO

UR

LE C

OD

E N

ATION

AL D

U G

AZ C

OM

BU

STIB

LE.

UN

ÉV

EN

T NE

DO

IT PAS

SE

SITU

ER

DIR

EC

TEM

EN

T AU

-DE

SS

US

D'U

N TR

OTTO

IR O

U D

'UN

E E

NTR

ÉE

PAVÉ

E S

ITUÉ

E E

NTR

E D

EU

X U

NITÉ

S D

E LO

GE

ME

NT U

NIFA

MILIA

LES

E

T DE

SS

ER

VIR

LES

DE

UX

UN

ITÉS

.P

ER

MIS

UN

IQU

EM

EN

T SI LA V

ÉR

AN

DA

, LE P

OR

CH

E, LE

PATIO O

U LE

BA

LCO

N E

ST E

NTIÈ

RE

ME

NT O

UV

ER

T SU

R A

U M

OIN

S D

EU

X C

ÔTÉ

S S

OU

S LE

NIV

EA

U D

E L'É

TAG

E.

PO

UR

AVO

IR LE

S E

SPA

CE

S LIB

RE

S N

ON

PR

ÉC

ISÉ

S D

AN

S LE

S N

OR

ME

S A

NS

I Z223.1/NFPA 54 O

U C

AS

/AC

NO

R B

149.1, L'UN

DE

S R

EN

SE

IGN

EM

EN

TS C

I-DE

SS

OU

S D

OIT

ÊTR

E IN

DIQ

:*

UN

E R

ÉFÉ

RE

NC

E À

LA NO

TE D

E B

AS

DE

PAG

E C

I-DE

SS

OU

S :

L'ES

PAC

E LIB

RE

CO

NFO

RM

ÉM

EN

T AU

X C

OD

ES

LOC

AU

X D

'INS

TALLATIO

N E

T LES

EX

IGE

NC

ES

CO

NTE

NU

ES

DA

NS

LES

INS

TRU

CTIO

NS

DU

FOU

RN

ISS

EU

R D

E G

AZ

ET D

ES

FAB

RIC

AN

TS (V

OIR

LE M

AN

UE

L FOU

RN

I AVE

C L'A

PPA

RE

IL).

a)

MO

BILE

FIXE

FERM

É

FIXE

FERM

É

DÉTAILS D

E

CO

IN IN

TÉRIEU

R

G

MO

BILE

A

C

FB

BB B

A

J

BI

H

MK

E

D

L

B

Figure 8

8

Figure 6

28 332

SUPPORT MURAL

A

B

C

D

E

OUVERTURE DANS LE MUR

Figure 7

T1 CC

L1

1Ø ALIMENTATION

COMPCRL2

CCT2

208/230V 60 Hz

G

CMB VENTILATEUR

TRANSFORMER

HPS LPSBRBRBK

RG

WHTY

BK

BK

BK

BK

HUM

L1

L1

R

YCHALEUR ACB

COOL ACB

24V

24V

INUTILISEE

L’ALLUMEUR

CC BKBKBK

24 VAC

GROUND

YW CR G

PK

HUM

FLAMME

24V

FLAMMEINTERRUPTEUR

BL

O230V

INDUCER

BK

R

OFMC

BKBR

WHT

VANNEGAZ

FIN DECOURSEHAUTE

PRESSOSTAT

INTERRUPTEURMISEEN

APPLICATION

O

BL

PK

PK

R

O

G

BL

Y

BL

BL

BL

O

NOTE 1

Y

BK

PK

BL

BL

LIMITEVENTILATEUR

R

O

PURBK

S

BK

Y

R

RC

BK

BL

BL

BL

BL

N

G

L

C

4

3

2

1

5

R

BL

G

R

C

NOTE 2

1. ECHANGE ORANGE ET ROUGE DES PISTES POUR 208V ALIMENTATION

2. CONDENSATEUR OPTION SUR CERTAINS MODELES

IBM

7

DYNAPACK ACCESSORIESNo de pièceDescriptionAppareil

1817Architectural Grille, Aluminum FinishDYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

1818Architectural Grille, Bronze FinishDYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

1819Architectural Grille, Aluminum FinishDYPA30AC1A*** and DYPA36AC1A***

1820Architectural Grille, Bronze FinishDYPA30AC1A*** and DYPA36AC1A***

17414" Wall Sleeve KitDYPA12, DYPA18 and DYPA24

17364" Wall Sleeve KitDYPA30 and DYPA36

17426" Wall Sleeve KitDYPA12, DYPA18 and DYPA24

17376" Wall Sleeve KitDYPA30 and DYPA36

17438" Wall Sleeve KitDYPA12, DYPA18 and DYPA24

17388" Wall Sleeve KitDYPA30 and DYPA36

174410" Wall Sleeve KitDYPA12, DYPA18 and DYPA24

173910" Wall Sleeve KitDYPA30 and DYPA36

174512" Wall Sleeve KitDYPA12, DYPA18 and DYPA24

174012" Wall Sleeve KitDYPA30 and DYPA36

176914" Wall Sleeve KitDYPA 12, DYPA 18, and DYPA 24

177014" Wall Sleeve KitDYPA 30 and DYPA 36

177116" Wall Sleeve KitDYPA 12, DYPA 18, and DYPA 24

177216" Wall Sleeve KitDYPA 30 and DYPA 36

177317" Wall Sleeve KitDYPA 12, DYPA 18, and DYPA 24

177417" Wall Sleeve KitDYPA 30 and DYPA 36

182118" Wall Sleeve KitDYPA 12, DYPA 18, and DYPA 24

182218" Wall Sleeve KitDYPA 30 and DYPA 36

182320" Wall Sleeve KitDYPA 12, DYPA 18, and DYPA 24

182420" Wall Sleeve KitDYPA 30 and DYPA 36

182522" Wall Sleeve KitDYPA 12, DYPA 18, and DYPA 24

182622" Wall Sleeve KitDYPA 30 and DYPA 36

DIMENSIONS du SUPPORT MURAL (Reportez-vous à la figure 7 à la page suivante)Part No.ABCDEUnit

17415 7/86 3/428 5/828 9/1628 3/4DYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

17427 7/88 3/428 5/828 9/1628 3/4DYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

17439 7/810 3/428 5/828 9/1628 3/4DYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

174411 7/812 3/428 5/828 9/1628 3/4DYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

174513 7/814 3/428 5/828 9/1628 3/4DYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

176915 7/816 3/428 5/828 9/1628 3/4DYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

177117 7/818 3/428 5/828 9/1628 3/4DYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

177318 7/819 3/428 5/828 9/1628 3/4DYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

182119 7/820 3/428 5/828 9/1628 3/4DYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

182321 7/822 3/428 5/828 9/1628 3/4DYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

182523 7/824 3/428 5/828 9/1628 3/4DYPA12AC1A***, DYPA18AC1A*** and DYPA24AC1A***

17365 7/86 3/432 5/828 9/1632 3/4DYPA30AC1A*** and DYPA36AC1A***

17377 7/88 3/432 5/828 9/1632 3/4DYPA30AC1A*** and DYPA36AC1A***

17389 7/810 3/432 5/828 9/1632 3/4DYPA30AC1A*** and DYPA36AC1A***

173911 7/812 3/432 5/828 9/1632 3/4DYPA30AC1A*** and DYPA36AC1A***

174013 7/814 3/432 5/828 9/1632 3/4DYPA30AC1A*** and DYPA36AC1A***

177015 7/816 3/432 5/828 9/1632 3/4DYPA30AC1A*** and DYPA36AC1A***

177217 7/818 3/432 5/828 9/1632 3/4DYPA30AC1A*** and DYPA36AC1A***

177418 7/819 3/432 5/828 9/1632 3/4DYPA30AC1A*** and DYPA36AC1A***

182219 7/820 3/432 5/828 9/1632 3/4DYPA30AC1A*** and DYPA36AC1A***

182421 7/822 3/432 5/828 9/1632 3/4DYPA30AC1A*** and DYPA36AC1A***

182623 7/824 3/432 5/828 9/1632 3/4DYPA30AC1A*** and DYPA36AC1A***

AVERTISSEMENT! L’appareil doit être installé dans un support mural approuvé et des accessoires de grille pour fonctionner en toute sécurité. Les mauvaises installations pourraient causer des dommages à la propriété, des blessures ou un accident fatal.

RENDEMENT DU SYSTÈME L’appareil a été vérifié à l’usine pour assurer un bon rendement de la climatisation. Si on a des raisons de croire que l’appareil comporte une fuite de réfrigérant, la charge peut être vérifiée en plaçant un thermomètre sur la canalisation de liquide, près du déshydrateur-filtre et en branchant un manomètre sur le pressostat haute pression. Utilisez un tableau des températures saturées R410A pour calculer le sous-refroidissement du liquide. L’appareil a la charge requise si son sous-refroidissement se situe entre 8 et 14 degrés lorsque la température extérieure est supérieure à 65 º.

Le système devrait être vérifié pour s’assurer qu’aucun câblage ne s’est desserré pendant le transport.

VENTILATEUR DE L’AIR AMBIANTL’appareil Dynapack contient un moteur à quatre vitesses permettant de faire différents réglages afin que les vitesses appropriées de climatisation et de chauffage puissent être obtenues après l’installation. Le tableau 4 présente les réglages faits à l’usine des vitesses de climatisation et de chauffage. Les réglages faits à l’usine devraient convenir à la plupart des installations, mais le réseau de canalisations dictera le meilleur réglage pour votre installation. Le moteur intérieur est lubrifié à vie; il n’est pas nécessaire de le lubrifier de nouveau.

Le ventilateur de l’air ambiant est contrôlé par la plaquette de contrôle électronique de l’appareil en plus du thermostat mural. Quand le contrôle du ventilateur du thermostat est en position « AUTO », le ventilateur de l’air ambiant ne fonctionnera que lorsqu’il y a une demande de chauffage ou de climatisation. Si l’interrupteur du ventilateur au niveau du thermostat est en position « ON », le ventilateur de l’air ambiant fonctionnera sans arrêt. La plaquette de contrôle supplantera le thermostat mural lorsque le contrôle passe en position «AUTO». La plaquette de contrôle contient plusieurs délais temporels qui retarderont la mise en marche et l’arrêt du ventilateur de l’air ambiant pour augmenter le niveau de confort tout en améliorant l’efficacité énergétique.

La fournaise contient également des limites de sécurité qui entrent en fonction quand des conditions anormales sont décelées. Ces limites ont un but particulier et il ne faut pas les trafiquer en changeant leur emplacement ou par un câblage spécial. Si la fournaise ne fonctionne pas, si le ventilateur de l’air ambiant ne se met pas en marche ou si le climatiseur ne fonctionne pas, consultez un technicien de service qualifié pour faire le diagnostic et la réparation.

L’appareil Dynapack est conçu et certifié pour fonctionner jusqu’à 4500 pieds au-dessus du niveau de la mer sans modification tant aux États-Unis qu’au Canada. Consultez le service technique au 423-775-2131 lorsque l’installation doit être faite à plus de 4500 pieds d‘altitude.

Fonctionnement dans les régions extrêmement froides ou neigeuses Dans les régions où la température ambiante se situe très souvent à moins de 0 º F, le niveau de confort intérieur peut être amélioré en réglant le régime du ventilateur de chauffage de manière à obtenir une augmentation maximale de la température d’après la plaque signalétique de l’appareil.

L’appareil Dynapack installé au niveau du premier étage doit avoir une admission à la fournaise et un échappement qui sont situés au-dessus du niveau de neige prévu pour ce secteur. Les chutes de neige supérieures aux niveaux prévus bloqueront l’admission à la fournaise, au point où l’appareil s’arrêtera.

ENTRETIENAVERTISSEMENT! Débranchez toute l’alimentation électrique menant à l’appareil avant de faire des travaux d’entretien. Autrement, vous pourriez être blessé ou subir un accident fatal.

BRÛLEURS:Les brûleurs peuvent être retirés lors de leur nettoyage ou d’un changement d’orifices.Ces travaux de service doivent être faits par un technicien qualifié.ÉCHANGEUR DE CHALEURL’échangeur de chaleur devrait être inspecté périodiquement par un technicien qualifié et nettoyé au besoin. Si un nettoyage est nécessaire, utilisez une brosse à poils rigides à manche en métal pour retirer le tartre et la suie. Pendant le nettoyage de l’échangeur de chaleur, le tube de rallonge d’échappement devrait également être nettoyé. Retirez les quatre vis de la plaque de montage du ventilateur d’air de combustion et sortez le ventilateur. Utilisez une brosse pour nettoyer la rallonge de l’échappement.SYSTÈME DE CLIMATISATIONLe système de réfrigération n’a pas normalement besoin d’entretien parce qu’il s’agit d’un système autonome fermé. L’entretien périodique requis est le suivant :

• Nettoyage du filtre à air. Suivez les directives notées sur le filtre et l’étiquette apposée sur le panneau d’accès.

• Le nettoyage du serpentin du condenseur s’il est couvert de matières étrangères, de peluche, de feuilles ou d’autres obstructions.

Sur DYPA12 modèles, placer un thermomètre sur la conduite d'aspiration du compresseur au-dessus de l'accumulateur. Raccorder une jauge de pression à l'orifice de pression de la conduite d'aspiration. Utiliser un tableau de température saturée R410A pour calculer la chaleur super aspiration. Les valeurs acceptables sont présentés dans le tableau ci-dessous.

6

0

5

10

15

20

25

30

60708090100110120

Com

pressor Suction Superheat

Outside Temperature F

DYPA12AC1A*** Charging Chart

MODELEVitesse recommandée

pour le chauffageNbre approx. de pi cu/

minHausse approx. de

températureVitesse recommandée pour la climatisation

Nbre approx. de pi cu/min

DYPA12AC1A039Hhigh100035Low400

DYPA18AC1A039Hhigh100035medium low550

DYPA18AC1A052Hhigh100045medium low550

DYPA24AC1A039Hhigh100035medium700

DYPA24AC1A052Hhigh100045medium700

DYPA30AC1A039Hhigh100035medium high900

DYPA30AC1A052Hhigh100045medium high900

DYPA36AC1A039Hhigh100035high1000

DYPA36AC1A052Hhigh100045high1000

Table 4

Grosseur nominale du tuyau

(pouces)

Diamètre intérieur

(pouces)

LONGUEUR DU TUYAU (pieds)

102030405060708090100125150175200

1/4.36432221815141211111098876

3/8.4937249403430272523222118171514

1/2.62213292736356504643403834312826

3/4.8242781901521301151059690847972645955

11.049520350285245215195180170160150130120110100

1 - 1/41.3801,050730590500440400370350320305275250225210

1 - 1/21.6101,6001,100890760670610560530490460410380350320

22.0673,0502,1001,6501,4501,2701,1501,050990930870780710650610

2 - 1/22.4694,8003,3002,7002,3002,0001,8501,7001,6001,5001,4001,2501,1301,050980

33.0688,5005,9004,7004,1003,6003,2503,0002,8002,6002,5002,2002,0001,8501,700

44.02517,50012,0009,7008,3007,4006,8006,2005,8005,4005,1004,5004,1003,8003,500

TABLE 5Capacité maximale des tuyaux en pieds cubes de gaz/heure pour des pressions de gaz de 0,5 lb/po ca de pression manométrique et une chute de pression de 0,3 po CE

(Basé sur un gaz ayant une densité relative de 0,60)

Exigences pour l’installation dans leCommonwealth du Massachusetts

Pour tous les appareils à gaz comportant un échappement horizontal installé dans les murs latéraux des logements d’habitation, d’immeubles ou de structures utilisées en totalité ou en partie à des fins résidentielles, y compris celles qui sont utilisées ou exploitées par le Commonwealth et où la sortie d’échappement par le mur latéral se trouve à moins de sept (7) pieds au-dessus de la surface finale dans le secteur où se fait l’échappement, y compris, sans y être limité, les patios et les porches, les exigences ci-dessous doivent être respectées.1. INSTALLATION DE DÉTECTEURS DE MONOXYDE DE CARBONE. Au

moment de l’installation de l’équipement à gaz avec évent horizontal par le mur latéral, le plombier qui fait l’installation ou le monteur d’installations au gaz doit installer un détecteur de monoxyde de carbone à câblage électrique comportant une alarme et une pile de secours au niveau de l’étage où l’équipement est installé. En outre, le plombier ou le monteur qui fait l’installation doit veiller à ce qu’un détecteur à pile ou à câblage électrique comportant une alarme soit installé sur chaque étage additionnel de l’unité d’habitation, de l’immeuble ou de la structure desservie par l’équipement à gaz avec évent horizontal par le mur latéral. Il incombe au propriétaire de l’immeuble de retenir les services de professionnels qualifiés et titulaires de permis pour faire l’installation des détecteurs de monoxyde de carbone à câblage électrique.

a. Si l’équipement à gaz avec évent horizontal par le mur latéral est installé dans un vide sanitaire ou dans un grenier, le détecteur de monoxyde de carbone à câblage électrique comportant une alarme et une pile de secours peut être installé sur l’étage adjacent suivant.b.Si les dispositions de ces exigences ne peuvent pas être respectées, au moment de l’installation, le propriétaire aura trente (30) jours pour se conformer aux exigences ci-dessus, à condition qu’au cours de ces trente (30) jours, un détecteur à pile de monoxyde de carbone comportant une alarme soit installé.

2. DÉTECTEURS DE MONOXYDE DE CARBONE APPROUVÉS. Chaque détecteur de monoxyde de carbone requis en vertu de ce qui précède doit respecter la norme NFPA 720 et ANSI/UL 2034 en plus d’être certifié par AIS.

3. SIGNALISATION. Une plaque d’identification en métal ou en plastique doit être installée en permanence à l’extérieur du bâtiment à huit (8) pieds au moins au-dessus de la surface finie et directement en ligne avec l’évent d’échappement pour l’équipement ou l’appareil de chauffage à gaz avec évent horizontal. Le panneau doit se lire comme suit et l’inscription doit avoir au moins ½ po de hauteur : « ÉVENT DE GAZ IMMÉDIATEMENT CI-DESSOUS. NE PAS OBSTRUER ».

4. INSPECTION . L’état ou l’inspecteur local de l’équipement à gaz avec évent horizontal par le mur latéral ne doit pas approuver l’installation si, au moment de l’inspection, l’inspecteur constate que les détecteurs de monoxyde de carbone et la signalisation ne sont pas conformes aux dispositions de la norme 248 CMS 5.08(2)(a)1 à 4.

(b)EXEMPTIONS. L’équipement suivant est exempté des dispositions de la norme 248 CMS 5.08(2)(a) 1 à 4 :1. L’équipement indiqué au chapitre 10 intitulé « Equipement Not Required

To Be Vented » de la version la plus récente de la norme NFPA 54 tel qu’adoptée par le conseil.

2. L’équipement à gaz avec évent horizontal par le mur latéral est approuvé et installé dans une pièce ou dans une structure à part de l’unité de logement, de l’immeuble ou de la structure utilisée en totalité ou en partie à des fins résidentielles.

MISE EN MARCHE DE L’APPAREILAVERTISSEMENT! Si ces instructions ne sont pas respectées, cela pourrait mener à un incendie, à une explosion, à des dommages à la propriété, à des blessures, voire à un accident fatal.

MISE EN GARDE: Cette fournaise comporte un contrôle direct de l’allumage. Il ne faut pas essayer d’allumer manuellement les brûleurs.AVANT D’UTILISER L’ÉQUIPEMENT. Essayez de détecter une odeur de gaz autour de l’appareil. Essayez de détecter cette odeur au niveau du sol parce que le gaz est plus lourd que l’air et qu’il se trouvera au niveau du sol. Si vous sentez une odeur de gaz, ARRÊTEZ TOUT. Ouvrez les fenêtres et les portes pour que tout le gaz s’évapore. Refaites une vérification de tous les tuyaux de gaz et de tous les raccords pour voir s’ils sont étanches.Vérification du fonctionnement de l’appareil :1. Assurez-vous que la vanne à gaz est en position « ON ». Retirez la porte du

logement à gaz. Tournez le bouton de la vanne à gaz ou placez l’interrupteur en position « ON » (consultez la figure 5). N’utilisez pas d’outils pour tourner le bouton. Si vous ne pouvez pas enfoncer le bouton et le tourner à la main, communiquez avec un technicien de service qualifié pour avoir de l’aide. Remettez en place la porte du logement à gaz.

2. Mettez l’appareil sous tension.3. Placez le thermostat de la pièce en position de chauffage.4. Augmentez le réglage au-dessus de la température ambiante.5. Le thermostat demandera du chauffage et le ventilateur d’air de combustion

se mettra en marche.6. Le ventilateur d’air de combustion sera en marche pendant 15 à 20

secondes avant que les contrôles de l’allumage ne produisent une étincelle. La vanne de gaz s’ouvrira et les brûleurs s’allumeront. Vous pouvez voir les brûleurs par le hublot d’observation de la porte.

7. Le ventilateur d’air pour la pièce se met en marche 30 secondes après l’allumage des brûleurs.

8. Lorsque la température de la pièce parvient à la température demandée, les brûleurs s’éteignent et le ventilateur d’air de la pièce s’arrête 90 secondes plus tard.

9. Réglez le thermostat de la pièce en position de climatisation.10. Baissez le réglage du thermostat sous le niveau de la température ambiante.

11. Après un court délai, le ventilateur d’air de la pièce se met en marche ainsi que le compresseur. Note : il y aura un délai de 5 minutes avant que le compresseur ne se remette en marche si le réglage du thermostat a été augmenté puis réduit de nouveau.

12. Lorsque la pièce est parvenue à la température demandée, le compresseur s’arrête et le ventilateur d’air de la pièce s’arrête également 30 secondes plus tard.

ARRÊT DE L’APPAREILPour arrêter l’appareil, placez le thermostat de la pièce en position « OFF ». Coupez l’alimentation électrique et fermez la vanne manuelle d’alimentation en gaz avant de faire des travaux de service sur l’appareil.Réglage pour le chauffage1. Éteignez l’appareil au niveau du thermostat de la pièce et fermez la vanne

de gaz.2. Branchez le manomètre avec la gamme appropriée (0 à 10 º pour le gaz

naturel) au point de pression d’entrée pour la vanne de gaz (voir la figure 6).3. Ouvrez la vanne manuelle de gaz et mettez l’appareil en marche.4. Lorsque la fournaise est en marche, vérifiez la pression du gaz à l’entrée.

Ajustez le régulateur de pression de manière à obtenir une pression d’entrée de 5 po à 7 po CE pour le gaz naturel.

5. Arrêtez l’appareil et fermez la vanne manuelle de gaz.6. Placez le manomètre sur le point de pression du collecteur de la vanne de

gaz (voir la figure 6).7. Lorsque la fournaise est en marche, vérifiez la pression au niveau du

collecteur. Réglez le régulateur de pression de la vanne de gaz de manière à obtenir une pression au collecteur de 3,5 po CE pour le gaz naturel.

8. Sur les installations au gaz naturel, l’entrée à la fournaise doit être vérifiée pour s’assurer de son bon fonctionnement. Tous les autres appareils à gaz qui utilisent le même compteur de gaz doivent être arrêtés, y compris les veilleuses.

9. Lorsque la fournaise Dynapack est en marche, mesurez le temps requis pour que le compteur de gaz fasse un tour. Consignez également le nombre de pieds cubes de gaz par révolution du compteur de gaz. Il vous faudra également la valeur moyenne de chauffage du gaz naturel pour votre emplacement. Insérez ces valeurs dans l’équation ci-dessous pour calculer le taux d’entrée de gaz en BTU/h.

BTU/h=

Pieds cubes par révolution

X3600Xvanne de chauffage

Nombre en secondes par révolution

10. La valeur que vous consignez pour l’entrée doit se situer à ± 2 % de la valeur nominale de l’entrée. Autrement, abaissez le réglage de la pression au collecteur de manière à réduire ou à augmenter l’entrée selon le cas. Ne dépassez pas 3,2 po à 3,8 po CE.

11. Arrêtez l’appareil; coupez l’alimentation en gaz au niveau de la vanne manuelle et retirez le manomètre. Assurez-vous que le bouchon sur le point de pression de la vanne à gaz est bien vissé de même que le capuchon installé sur le régulateur de la vanne de gaz. Refermez la porte du logement du brûleur.

12. Ouvrez la vanne manuelle de gaz et mettez la fournaise en marche.13. Placez un thermomètre dans le retour d’air et un autre dans l’alimentation en

air soufflé aussi près de la fournaise que possible. Lorsque la température de l’air soufflé est constante, consignez les deux températures. Soustrayez la température de l’air du retour de la température de l’air soufflé. Cette différence est l’augmentation de la température par la fournaise.

14. Comparez l’augmentation de la température mesurée par rapport à la gamme apparaissant sur la plaque signalétique. Si l’augmentation mesurée est inférieure au minimum apparaissant sur la plaque signalétique, choisissez la vitesse inférieure suivante du ventilateur comme vitesse pour le chauffage. Si l’augmentation de la température mesurée se situe au-dessus du maximum affiché sur la plaque signalétique, choisissez la vitesse supérieure suivante du ventilateur pour le chauffage.

15. Si la nouvelle vitesse du ventilateur a été choisie, refaites les mesures de l’augmentation de la température et refaites l’ajustement au besoin.

AJUSTEMENT POUR LA CLIMATISATIONPour la climatisation, le seul réglage qui peut être fait est la vitesse de rotation du ventilateur.1. Mettez l’appareil en mode de climatisation et laissez l’appareil fonctionner

jusqu’à ce qu’il soit parvenu à un état stable.2. Placez un thermomètre dans l’ouverture de l’air de retour et un autre dans

l’ouverture de l’air soufflé aussi près de l’appareil que possible.3. L’appareil de climatisation doit fonctionner jusqu’à ce que le serpentin

d’évaporation produise de l’eau de condensation. Mesurez les températures de l’air au retour et à l’alimentation soufflée.

4. La climatisation fonctionne correctement s’il y a une chute de 20 degrés Fahrenheit de la température de l’air par l’appareil de climatisation.

5. Si la chute de température de l’air dépasse 22 degrés, faites passer la vitesse de climatisation à la prochaine vitesse supérieure. Si la diminution de la température de l’air est inférieure à 18 degrés, faites passer la vitesse de climatisation à la prochaine vitesse inférieure du ventilateur.

NOTE: Si la vitesse de climatisation et la vitesse de chauffage sont identiques, la queue de cochon de chauffage en provenance de la carte électronique et la queue de cochon de climatisation en provenance de la carte électronique peuvent être raccordées à la même queue de cochon en provenance du moteur. À l’aide de ruban électrique, amarrez toutes les queues de cochon inutilisées de la vitesse du ventilateur.

5

CÂBLAGE DE CONTRÔLELe thermostat de la pièce devrait être installé sur un mur intérieur et près du retour d’air à l’appareil. Un thermostat à 5 conducteurs devrait être utilisé au cas où le thermostat de la pièce doit recevoir son alimentation électrique en provenance du transformateur de l’appareil.

La queue de cochon basse tension du câblage du thermostat doit aller à l’exté-rieur de l’appareil Dynapack pour le raccordement. L’appareil Dynapack contient une deuxième débouchure située au-dessus de la boîte de contrôle à cette fin. Le National Electrical Code exige que le câblage basse tension soit tenu à part du câblage haute tension; il ne peut pas passer par la même débouchure ou la même canalisation. Les codes locaux peuvent également exiger qu’une boîte électrique soit installée sur la débouchure basse tension pour y faire les raccor-dements électriques.

Suivez les instructions du fabricant du thermostat pour faire l’installation et le câ-blage. La basse tension est mise à la terre à l’intérieur de la boîte de contrôle de l’appareil. Consultez le schéma de câblage ci-joint (voir la page 8).

INTERRUPTEUR DE LA VANNE

POINT DE PRESSION À L'ENTRÉE. LE TUYAU DE VÉRIFICATION S'INSTALLE

PAR-DESSUS L'EXTÉRIEUR DU POINT DE VÉRIFICATION.

UTILISEZ UNE CLÉ HEXAGONALE DE 3/32 PO POUR OUVRIR

LE POINT D'UN TOUR.

POINT DE PRESSION DE SORTIE. LE TUYAU DE VÉRIFICATION S'INSTALLE PAR-DESSUS L'EXTÉRIEUR DU POINT DE VÉRIFICATION. UTILISEZ UNE CLÉ HEXAGONALE DE 3/32 PO POUR OUVRIR LE POINT D'UN TOUR.

ENTRÉE DE ½ PO NPT

AJUSTEMENT DU RÉGULATEUR SOUS LE COUVERCLE DE CETTE VIS

Figure 6

MISE EN GARDE: Suburban ne recommande pas d’utiliser un tuyau flexible pour faire le raccordement de gaz à l’appareil, sauf si le tuyau flexible est de haute qualité, fait d’acier inoxydable, si le tuyau est certifié par CSA/ACNOR et s’il est approuvé par le code local.

AVERTISSEMENT! Un composé pour filetage résistant au gaz naturel doit être utilisé sur tous les raccordements de tuyaux.

AVERTISSEMENT! La vanne à gaz fournie avec cette fournaise est conçue pour un maximum de ½ lb/po ca de pression manométrique. Toute pression plus élevée peut endommager le diaphragme du régulateur de pression en plus de causer une combustion excessive au niveau des brûleurs et un mauvais fonctionnement de ces derniers. Cela peut créer du monoxyde de carbone, ce qui peut entraîner une asphyxie.

AVERTISSEMENT! DANGER D’INCENDIE OU D’EXPLOSION! Si les avertissements de sécurité ne sont pas respectés à la lettre, cela pourrait entraîner des blessures graves, des accidents mortels ou des dommages à la propriété.

AVERTISSEMENT! Ne vérifiez jamais l’étanchéité d’une installation à l’aide d’une flamme vive. Utilisez une solution d’eau et de savon disponible sur le marché et conçue spécialement pour la détection des fuites au niveau de tous les raccords. Un incendie ou une explosion pourrait entraîner des dommages à la propriété, des blessures, voire un accident fatal.

4

PI CU/MIN A L'INTERIEUR P/R A LA PRESSION STATIQUE (serpentin humide + filtre a l'air)MODELEVitesse du

ventilateur0.10" po CE0.15" po CE0.20" po CE0.25" po CE0.30" po CE0.40" po CE0.50" po CE0.60" po CE0.70" po CE0.80" po CE

DYPA12AC1A***

BASSE497473448424400348296247212160MOYEN BASSE577562547522497458415357317281

MOYEN757748739716692670635586558521MOYEN ÉLEVÉ937920905888872852827790728677

ÉLEVÉ1060105010421015977927876824758700

DYPA18AC1A***

BASSE512491469428387320285250213179MOYEN BASSE596568540522504447415381324291

MOYEN773761748730711675640622586550MOYEN ÉLEVÉ972955938927915874850825796766

ÉLEVÉ110810911074105710391002970917868796

DYPA24AC1A***

BASSE504483461420379312252207N/RN/RMOYEN BASSE588560532514496439377320262202

MOYEN765753740722703667622572532482MOYEN ÉLEVÉ964947930919907866828782757702

ÉLEVÉ11001083106610491031994962922882827

DYPA30AC1A***

BASSE490465440415385310225170N/RN/RMOYEN BASSE570540520500476415365310250205

MOYEN768755741732704666621580535500MOYEN ÉLEVÉ934922913895873835800760730690

ÉLEVÉ1064104610171009995965935900875828

DYPA36AC1A***

BASSE490465440415385310225170N/RN/RMOYEN BASSE570540520500476415365310250205

MOYEN768755741732704666621580535500MOYEN ÉLEVÉ934922913895873835800760730690

ÉLEVÉ1064104610171009995965935900875828

TABLEAU 3

CONDENSATION DE VIDANGE - CHAUFFAGELe four à haute efficacité dans cette unité produira condensats lors de l'utilisation. De plus, une interruption est nécessaire pour surmonter la pression négative produite par le ventilateur de l'évacuateur de combustion.1. Avec le panneau d'accès de la vanne de gaz retiré, branchez le siphon au

tuyau de drainage interne en utilisant le raccord cannelé droites prévu.2. Placer le raccord dans le tuyau de vidange du climatiseur juste en dessous où

il sort de l'unité Dynapack le tee 3/4 x 3/4 x 5/8.3. Remplissez le tuyau d'évacuation du four en installant le "coude cannelé 5/8

à 90 degrés dans le tuyau de vidange du piège.4. Installer un tuyau de vinyle 5/8 entre le 90 degré approprié et raccord en T

installé dans la conduite de vidange du climatiseur. Voir Figure 5. L'ligne four de condensat s'auto premier au démarrage.

RACCORDEMENTS ÉLECTRIQUESL’appareil Dynapack est approuvé pour les conducteurs en cuivre seulement. Consultez les données sur l’appareil pour connaître l’intensité minimale du circuit électrique. Déterminer la grosseur du câble en fonction de l’intensité du circuit de l’appareil, le type de câblage utilisé et la méthode de câblage, soit avec ou sans canalisation. Si l’alimentation électrique est de 208 volts, ne dépassez pas la chute de tension de plus de 2 % en fonction de la longueur de câblage utilisée. Consultez le National Electrical Code ou le Code canadien de l’électricité pour avoir plus de renseignements.

L’alimentation électrique typique fait appel à un câblage à deux phases où la tension mesurée est de 208-230 volts entre phases. Un câble additionnel de mise à la terre de l’appareil est requis. Consultez la plaque signalétique de l’appareil pour avoir le calibre minimum du fusible ou du coupe-circuit. Un fusible à circuit temporisé ou à coupe-circuit bipolaire HACR peut être utilisé pour prévenir les déclenchements de nuisance.

D’un autre côté, l’appareil Dynapack peut être câblé pour une alimentation monophasée lorsque la tension mesurée est de 208-230 volts entre la phase et le neutre. Dans ce cas, le câble de phase devrait être branché à L1 du contacteur. Un câble additionnel de mise à la terre de l’appareil est requis.

Sur les systèmes à 208 volts, le câblage du transformateur doit être changé. Changez le câble rouge du transformateur pour un conducteur orangé qui peut être utilisé pour un circuit de 208 V.

Un coupe-circuit doit être installé près de l’appareil pour couper l’alimentation électrique pendant les travaux de service ou d’entretien.

ALIMENTATION EN GAZTous les appareils Dynapack sont conçus pour utiliser du gaz naturel.Pression minimale de l’alimentation en gaz pour faire l’ajustement de l’admission: Minimum MaximumGAZ NATUREL 5 po CE 7 po CE

CE = Colonne d'Eau

CANALISATION DE GAZL’appareil Dynapack a un raccord pour un tuyau de ½ po pour l'alimentation en gaz. La grosseur du tuyau doit être basée sur la longueur du tuyau et non sur la grosseur du raccord. Consultez le tableau 5 pour avoir la grosseur du tuyau.

Consultez le service public d’alimentation en gaz ou l’autorité régissant le code concernant l’installation du tuyau de gaz.

Si le code local permet d’utiliser un raccord flexible pour l’appareil à gaz, utilisez toujours les connecteurs les plus récents de la liste. N’utilisez pas de connecteur qui a déjà été utilisé sur un autre appareil à gaz.

Le tuyau à gaz devrait contenir une vanne d’arrêt manuelle dont la prise d’essai se trouve près de la fournaise en plus d’un point de purge et d’un raccord de joint rodé pour les travaux de service. La prise d’essai doit se situer en amont de la vanne d’arrêt manuelle de l’épreuve d’étanchéité et de l’ajustement du régulateur de la pression d’alimentation.

La vanne d’arrêt manuelle doit avoir des valeurs nominales conformes à la pression d’essai du tuyau de gaz. Autrement, la vanne d’arrêt doit être retirée du réseau de canalisations pendant la vérification. Lorsque le tuyau à gaz menant à la vanne d’arrêt a été vérifié, le reste de la tuyauterie menant à la vanne à gaz de l’appareil doit être vérifié. Ne dépassez pas ½ lb/po ca de pression manométrique ou 14 po CE pour ce test; autrement, la vanne à gaz pourrait être endommagée.3

Figure 5

RETOURENTRÉE

PANNEAU D'ACCÈ AUX CONTRÔLES

PANNEAU D'ACCÈS À LA VANNE DE GAZ ET

AUX BRULEURS

PANNEAU D'ACCÈS AU COMPRESSEUR

ET AU VENTILATEUR EXTÉRIEUR

POINT DE PURGE (NON FOURNI)

VANNE D'ARRÊT MANUEL ET TROU TARAUDÉ DE DÉBOUCHAGE DE 1

8 PO NPT ACCESSIBLE POUR LE RACCORDEMENT DU MANOMÈTRE D'ESSA (NON FOURNI)

DRAIN D'ÉVACUATION DE L'EAU DE CONDENSATION

RACCORD À JOINT RODÉ(NON FOURNI)

PORTE MENANT AU FILTRE

SIPHON

ACHEMINEMENT VERS LE DRAIN DE L'IMMEUBLE

ENTRÉE DE L'ALIMENTATION ÉLECTRIQUE

VUE AVANT

PINCE TINNERMAN

VIS #10-24 X 1 1/2"

PIED DE MISE A NIVEAU

BOULON 3/8-16

LE SUPPORT DE MISE ANIVEAU S'INSTALLE DANS LESUPPORT DE L'UNITE ET ESTMAINTENUE EN PLACE GRACE

AU POIDS DE L'UNITE

VIS AUTOPERFORANTE #12 X .75"(2 VIS)

METTRE EN PLACE LE SUPPORTEN INSTALLANT LA PATTE SOUSLA BASE DE L'UNITE ETAU DESSUS DU RAIL.

ATTACHER LE SUPPORT A L'UNITEAVEC (2) VIS AUTOPERFORANTES #10 X 1/2"(2 SUR CHAQUE SUPPORT)

METTRE EN CONTACT LE COTE DU SUPPORTMURAL AVEC LA COURROIE LATERALE.SERRER LES VIS JUSQU'A CE QUE LE SUPPORT PUISSE ETRE SECURISE A L'UNITEAVEC LES VIS AUTOPERFORANTES.

Figure 4

MUR MANCHES (Nominale)MAX EPAISSEUR

TUYAU EN PVC LONGUEUR DE

COUPE (po)

LONGUEUR DU TUYAU EXTENSION

DE L'UNITE

NUMEROS MUR CHEMISE STOCK

COURTLONG

*CW3 7/8"27"6"--------------------4"5 7/8"29"8"174117366"7 7/8"31"10"174217378"9 7/8"33"12"17431738

10"11 7/8"35"14"1744173912"13 7/8"37"16"1745174014"15 7/8"39"18"1769177016"17 7/8"41"20"1771177217"18 7/8"42"21"1773177418"19 7/8"43"22"--------------------20"21 7/8"45"24"--------------------22"23 7/8"47"26"--------------------

TABLE 1

INSTALLATION ET AMARRAGE DE L’APPAREIL SUR LE SUPPORT MURAL

Avant d’installer et d’amarrer l’appareil sur le support mural, installez la grille correctement. Compte tenu de la température des gaz de combustion qui s’échappent par la sortie d’échappement, l’appareil Dynapack au gaz exige une grille en aluminium (voir la rubrique ACCESSOIRES à la page 9).1. Vérifiez l’installation du support mural pour vous assurer qu’il est bien

amarré à l’ouverture pratiquée dans le mur. Inspectez le drain du support mural pour vous assurer qu’il est bien installé si vous utilisez un drainage à l’intérieur de l’immeuble.

2. Vérifiez les joints étanches du support mural pour vous assurer qu’il y a un scellement continu entre le support mural et l’appareil.

3. Placez l’appareil Dynapack sur le support mural. Soulevez l’arrière de l’appareil et placez-le sur la base du support mural (voir la figure 3). Un chariot de transport des réfrigérateurs pourrait donner de bons résultats ici. Bloquez temporairement l’appareil en position levée et installez le support avant de mise au niveau (voir la figure 3). Réglez la mise au niveau jusqu’à ce que l’appareil soit au niveau ou incliné vers l’arrière sur le support mural jusqu’à ¼ de la bulle du niveau.

4. Utilisez les supports d’installation et deux courroies pour retenir l’appareil sur le support mural (voir la figure 3). Assurez-vous que les joints étanches font un scellement complet de l’appareil; apportez une attention spéciale aux coins supérieurs et inférieurs de la jonction entre l’appareil et le support mural. Au besoin, ajoutez un matériau d’étanchéité.

CANALISATIONSLes canalisations prévues pour l’unité de logement doivent être conçues en fonction de la pression statique la plus faible possible afin de réduire la consommation d’énergie et le bruit. Le tableau 2 présente la liste de volumes approximatifs d’air de l’appareil pour chaque vitesse du ventilateur intérieur. Le tableau 4 présente la liste des vitesses recommandées pour le chauffage et la climatisation avec les capacités approximatives exprimées en pieds cubes/minute. Utilisez les deux tableaux pour concevoir correctement le réseau de canalisations en fonction du volume d’air utilisé pour le chauffage et la climatisation.

FILTRE À AIRL'unité DynaPack est équipé d'un filtre à air permanente, nettoyable. Ce filtre peut être utilisé si l'appareil est installé de façon à ce que le filtre est accessible pour le propriétaire. Le filtre permanent installé à l'intérieur de l'appareil doit être retiré et jeté si un filtre jetable est installé dans le conduit de retour d'air. Voir le tableau 2 pour la zone de filtration minimale requise pour l'unité Dynapack basé sur la capacité de l'unité. Il est recommandé que les filtres à air sont nettoyés ou remplacés par mois pour garder le serpentin de refroidissement et les surfaces conduit intérieur propre et capable de fonctionner plus efficacement. Option MERV 13 filtres sont disponibles.

SURFACE MINIMAL

NUMERO DE MODELESUPERFICIE DU FILTRE

DYPA12288 po ca

DYPA18288 po ca

DYPA24480 po ca

DYPA30 & DYPA36480 po ca

TABLEAU 2

CONDENSATION DE VIDANGE - CLIMATISEURL'unité Dynapack et manchon de mur ont chacun leur propre fuite. Le drain de l'unité pour l'eau de condensation est développé par la bobine d'évaporateur. Il doit être pris au piège et acheminé vers le système de drainage de bâtiment. Utilisez ¾ pipe "et raccords en PVC (fourni). Le manchon de paroi est équipé d'un bac de récupération qui recueille l'eau de pluie entrant dans le manchon de la paroi et la surface de bobine du condenseur. Au moment de l'installation du manchon de paroi, ce drain peut être dirigée directement à l'extérieur ou à l'intérieur et tourné routé vers le système de drainage de bâtiment. Si le drain du manchon mural est acheminé vers le système d'égout bâtiment, il doit être pris au piège à éviter les gaz d'égout de s'échapper.

INSTALLATIONAVERTISSEMENT! L’installation de cet appareil doit être faite conformément aux instructions écrites contenues dans ce manuel. Aucun agent, représentant ou employé de Suburban ou d’autres personnes n’a l’autorité nécessaire pour changer, modifier ou annuler les dispositions contenues dans les instructions présentées dans ce manuel.

Les appareils Dynapack sont des ensembles verticaux contenant un chauffage au gaz et une climatisation à l’électricité. Les appareils Dynapack sont certifiés au plan de la sécurité par Intertek Testing Services et ils sont conformes aux codes nationaux de sécurité des États-Unis et du Canada. L’appareil Dynapack est certifié pour être utilisé avec le gaz.L’appareil Dynapack N’EST PAS certifié pour être installé dans les maisons mobiles.Les installations faites aux États-Unis doivent être conformes aux codes et aux règlements des villes, des comtés ou des états. Si les codes locaux ne s’appliquent pas, l’installation doit être conforme au National Fuel Gas Code et au National Electrical Code.Les installations faites au Canada doivent également être faites conformément aux codes des villes, des provinces ou du pays ou conformément à la version la plus récente du Code d’installation CANI-B149.

AVERTISSEMENT! Au Massachusetts, ce produit peut être installé par un plombier ou un monteur d’installations au gaz détenant une licence. Lorsque des raccords flexibles sont utilisés, la longueur maximale ne doit pas dépasser 36 po. Lorsque des dispositifs de coupure à levier du gaz sont utilisés, le levier doit avoir la forme d’un T.

La décharge du ventilateur extérieur ou l’admission d’air au condensateur ne peuvent pas être raccordées à des canalisations fabriquées sur place. L’appareil ne peut être installé qu’en utilisant les supports muraux fournis par l’usine.

EMPLACEMENTIMPORTANT: Le système Dynapack de drainage de condensats est conçu pour être installé dans un espace conditionné. Pour éviter que les condensats drainés dans ce siphon ne gèlent, l’emplacement de l’installation ne doit pas être exposé à une situation de gel possible. Dans des installations où le système de drainage est exposé à un possible gel, nous proposons en option à l’achat un siphon en P chauffé. La référence de pièce pour le kit d’installation de ce siphon chauffé est K/10348, et les étapes de son installation sont décrites dans l’Annexe A.

L’appareil Dynapack est approuvé par les installations à l’intérieur uniquement et ils doivent être installés à l’aide d’un des supports muraux fournis par l’usine. L’appareil est conçu pour être installé dans une garde-robe ou dans le local de mécanique. L’appareil est certifié pour un écartement de 0 po de chaque côté de l’armoire, à l’arrière de cette dernière et sur les trois premiers pieds de la canalisation d’alimentation. Mais pour des raisons d’accessibilité, il est préférable de conserver un espace d’au moins 1 po sur les côtés pour avoir une bonne installation et pour faciliter le service. Pour les installations dans les garde-robes, laissez un espace libre de 4 po entre les panneaux de la porte de l’appareil et la porte de la garde-robe. Lorsque l’installation est faite dans un local de mécanique, prévoyez un espace libre de 24 po entre les panneaux de la porte de l’appareil et le mur pour faire les travaux de service.

Le manchon mur et la grille est destiné à être installé au ras du mur extérieur. L'unité, manchon mural, et la grille doivent être installés certaines distances de portes adjacentes, des fenêtres ouvrantes et des arbustes. Voir figure 8.

ATTENTION: L'appareil doit être installé avant de niveau vers l'arrière et sur les

côtés. Réglez les pieds de mise à niveau avant que nécessaire.

INSTALLATION DU SUPPORT MURAL ET DE LA GRILLEConsultez les instructions d’installation fournies avec le support mural pour savoir comment assembler et installer le support mural et la grille.MISE EN GARDE: Le support sert d’appui pour l’arrière de l’appareil.

VENTILATIONL’appareil Dynapack utilise l’air extérieur pour la combustion et il évacue les gaz d’échappement directement à l’extérieur. L’appareil Dynapack ne peut pas partager l’évacuation de ses gaz avec d’autres appareils. Le système d’échappement de l’appareil Dynapack ne peut pas être modifié ou réglé autrement qu’en respectant les instructions présentées dans les présentes.L’installation doit être planifiée d’avance afin que l’emplacement de la sortie des gaz d’échappement respecte les codes locaux ou nationaux en ce qui a trait aux distances à conserver entre l’emplacement pour l’évacuation de l’appareil et les portes, les fenêtres mobiles, les trottoirs, les balcons et les patios. Consultez la National Fuel Gas Code Z223-1 pour les États-Unis ou le Code d’installation CANI-B149 pour le Canada (voir la figure 9).Le système de ventilation pour le Dynapack 90% à condensation et doit être complétée dans le domaine de l'aide 1 1/2 inch schedule PVC 40 du tuyau d'évacuation et de ventilation. Le tuyau de ventilation sera droite pour les manches complètes de mur de largeur d'unité. Voir la figure 2 pour l'installation typique pleine unité de tuyau largeur de ventilation. Le tuyau de ventilation doit se terminer environ deux pouces en dehors de la grille extérieure.

VUE DU DESSUS

AU MOINS 4 PO JUSQU'À LA PORTE

RECOMMANDATION: 1 PORECOMMANDATION: 1 PO

CÂBLAGE DE CONTRÔLEALIMENTATION ÉLECTRIQUE

Figure 1

2

*MUR RIDEAU1. INSÉREZ-LE DIRECTEMENT 1 1/2 "PVC SCHEDULE 40

CONDUITES PAR OUVERTURE EN GRILLE. AU CANADA, TUYAU DOIT ÊTRE SYSTÈME 636 MATÉRIEL

2. APPLIQUER PVC PIPE CIMENT PIPE ET INSERT INTO COUDE.

3. LE TABLEAU 1 PIPE CUT LONGUEUR.

UNE FOIS INSTALLÉ, PIPE ETENDE GRILLE PASSÉ 2 ± 1/2 po.

Figure 2

DYNAPACKMODÈLES

DYPA12AC1A039HDYPA18AC1A039H, DYPA18AC1A052HDYPA24AC1A039H, DYPA24AC1A052HDYPA30AC1A039H, DYPA30AC1A052HDYPA36AC1A039H, DYPA36AC1A052H

CONDITIONNEUR MONOBLOC VERTICAL AVEC CHAUFFAGE AU GAZ ET CLIMATISATION À L’ÉLECTRICITÉ

INSTRUCTIONS D’INSTALLATION, D’UTILISATION ET DE SERVICEINSTALLATEUR: Laisser ce manuel avec l’appareil

CONSOMMATEUR: Conserver ce manuel à titre de référenceCe livre contient les instructions d’installation et d’utilisation de votre appareil. Conservez-le à un endroit sûr comme référence

immédiate. Si vous avez besoin de renseignements additionnels, communiquez avec votre marchand.

AVERTISSEMENT! Si l’information présentée dans ces instructions n’est pas suivie à la lettre, un incendie ou une explosion pourraient survenir et causer des dommages à la propriété, des blessures, voire un accident fatal.

Ne remisez pas ou n’utilisez pas d’essence ou d’autres vapeurs ou des liquides inflammables à proximité de cet appareil ou de n’importe quel autre appareil.

QUE FAUT-IL FAIRE LORSQU’ON SENT UNE ODEUR DE GAZ ?• N’essayez pas d’allumer l’appareil.• Ne touchez pas aux interrupteurs électriques. N’utilisez pas les

téléphones de votre immeuble.• Communiquez immédiatement avec votre fournisseur de gaz à partir du

téléphone d’un voisin. Suivez les instructions du fournisseur de gaz.• Si vous ne pouvez pas rejoindre un fournisseur de gaz, communiquez

avec le service des incendies de votre localité.L’installation et le service doivent être exécutés par un installateur qualifié, une agence de service ou le fournisseur de gaz.

AVERTISSEMENT! Si l’installation, les réglages, les modifications, le service et l’entretien ne sont pas faits correctement, la propriété pourrait être endommagée ou quelqu’un pourrait être blessé, voire subir un accident fatal. Consultez les instructions d’installation ou le manuel de l’utilisateur fournis avec cet appareil. L’installation et les travaux de service doivent être accomplis par un installateur, une agence de service ou un fournisseur de gaz qualifié.

AVERTISSEMENT! L’installation et les travaux de service exécutés sur un appareil de climatisation peuvent présenter des dangers en raison de la pression interne du réfrigérant et des composants sous tension électrique. Seul un personnel de service formé et qualifié devrait installer ou assurer le service de cet équipement. L’installation et les travaux de services accomplis par des gens non qualifiés peuvent causer des dommages à la propriété, des blessures, voire un accident fatal.

AVERTISSEMENT! Pour un fonctionnement SÉCURITAIRE, ceci doit être installé uniquement à l’aide des accessoires approuvés (grille d’extérieur et manchons muraux). Le non-respect de ces instructions peut entraîner des dommages matériels, des blessures et même la mort.

MISE EN GARDE: L’installation de cet appareil doit respecter les exigences de la National Fire Protection Association; du Code américain de l’électricité, des normes ANSI/NFPA No. 70 (édition la plus récente) des États-Unis; du Code canadien de l’électricité, partie 1, de la norme CSA/ACNOR 22.1 (édition la plus récente) au Canada; et les lois des états ou des provinces ou les ordonnances locales. Les autorités locales qui ont juridiction devraient être consultées avant que l’installation ne soit faite. Les règlements ou les exigences pertinentes ont préséance sur les instructions générales contenues dans ce manuel.

INSPECTION DES DOMMAGES DE FRETVotre appareil a été emballé avec soin dans un contenant qui respecte les dispositions du National Safe Transit Test. Cela signifie que les produits emballés, s’ils sont manutentionnés normalement, résisteront aux conditions rencontrées lors d’un transport et d’une manutention normale. Votre appareil devrait être inspecté immédiatement après son déballage pour déterminer s’il a été endommagé pendant son transport ou sa manutention. Si des dommages sont découverts, n’installez pas l’appareil; avisez l’entreprise de transport immédiatement et présentez une demande d’indemnisation.

Le fabricant n’a aucune responsabilité pour les dommages subis par l’appareil pendant son transport ou pour un mauvais fonctionnement en raison des dommages subis pendant le transport.

À titre de référence, consignez l’information ci-dessous.

NUMÉRO DE MODÈLE ___________________________________________NUMÉRO DE SÉRIE ______________________________________________NUMÉRO D’ARTICLE _____________________________________________DATE D’ACHAT __________________________________________________

FICHE TECHNIQUE DE L’APPAREILN’utilisez pas cet appareil pendant les travaux de construction pour ne pas annuler votre garantie.

CHAUFFAGEMODÈLE

DYPA12AC1A039H

DYPA18AC1A039H

DYPA24AC1A052H

DYPA30AC1A052H

DYPA36AC1A052H

BTU (ENTRÉE)39,00039,00052,00052,00052,000

VOLTS208-230208-230208-230208-230208-230

AMPÈRES4.74.74.74.74.7

RACCORDEMENT DE GAZ

1/2 Inch Pipe at Unit

CLIMATISATIONMODÈLE

DYPA12AC1A039H

DYPA18AC1A039H

DYPA24AC1A052H

DYPA30AC1A052H

DYPA36AC1A052H

CAPACITÉ DE CLIMATISATION12,00017,00023,60028,40034,800

VOLTS208-230208-230208-230208-230208-230

WATTS11751665238028203480

MCA*13.314.917.821.625.2

RÉFRIGÉRANTR410A

CHARGE DE RÉFRIGÉRANT

SEE INFORMATIONSTICKER ON UNIT

*MCA= Minimum Circuit Ampacity N˚ De Pièce: 20509410/2017 Rev. 4

AIRXCEL, INC.SUBURBAN APPLIED PRODUCTS

156 Seedling DriveCordele, GA 31015

(229) 273-3636www.SuburbanManufacturing.com