ENGINE GOVERNING S YSTEM Governors America Corp., 720 Silver Street Agawam, MA 01001 phone: 413.786.5600 fax: 413.789.7736 www.governors-america.com [email protected] 1 LSM200 Series Load Sharing Module INTRODUCTION The LSM200 Series controls are multi-function load sharing and power control module accessories. They are intended to be used with Governors America Corp. speed control units on generator set applications requiring isochronous parallel- ing and for mains power control. Isochronous load sharing is its primary function. The LSM200 Series controls have the following capabilities: The LSM200 Series is presently available in two models, the LSM201 and the LSM201N. The LSM201 is the latest and current mode/ that meets all the specifications and functions described in this publication and is CE approved. The LS- M201N is functionally the same but lacks the extra filtering for CE approval. The LSM201 is supplied unless specified otherwise. DESCRIPTION Load Sharing Mode Engine generator sets with isochronous governors maintain the requested speed very precisely. If synchronous genera- tors are electrically paralleled to increase the total generated power capability, a system to apportion the load is required. Even the finest electric governors will have minor frequency differences among units to be paralleled, which would cause power variations. In this case, one generator set would con- tinuously increase the power it produces, while the other sets would decrease the power they produce. This condi- tion eventually leads to motorizing one or more generator/ engines. The load sharing system continuously adjusts the governor speed settings so that no average power difference exists. The generators are locked together through electrical synchronizing torques. They act as though they are tightly connected through a gear drive. The load sharing module measures the power that the gen- erator supplies to the main bus. Voltage inputs accept two ranges of three phase voltage. This covers most all appli- cations (see table in the specifications). In the design of polyphase generators, the presence of a third harmonic is possible. This odd order harmonic may cause errors in load sharing systems. To minimize this error and to improve the load sharing, a terminal is provided to connect to the neutral of a Wye configuration generator. The line current measurements are usually taken from cur- rent transformers existing in the equipment such as those used for ammeter circuits. Internal power measurement circuits develop a D.C. load signal across the parallel cable proportional to the AC power measured. The magnitude and sensitivity of the load sharing is adjustable through the LOAD SENSITIVITY control in the module. Test points TP1 (+) and TP2 (-) adjacent to this con- trol are used to measure the polarity and magnitude of the proportional power signal. This measurement is very impor- tant when initially installing a system and these test points may also be used in troubleshooting the system. • Isochronous Load Sharing (0% Droop) • Reverse Power Monitoring • Forward Power Monitoring • Load Anticipation • Automatic Power Ramping of its oncoming generator • Generator Power Ramping to the mains • Internal bar graph power measurement display • Power measurement with an external display OVERNORS MERICA ORP. C A G ISO 9001 CERTIFIED LSM201 LSM201N
Transcript
Page 1: E GA G LSM200 Series CORP. S Load Sharing Module€¦ · diagram 1 system wiring/outline s/n : model: gac overnors merica orp. made in agawam, ma u.s.a. caution engine speed control

ENGINE

GOVERNING

SYSTEM

Governors America Corp., 720 Silver Street Agawam, MA 01001phone: 413.786.5600 fax: 413.789.7736

[email protected]

1

LSM200 SeriesLoad Sharing Module

INTROduCTION

The LSM200 Series controls are multi-function load sharing and power control module accessories. They are intended to be used with Governors America Corp. speed control units on generator set applications requiring isochronous parallel-ing and for mains power control. Isochronous load sharing is its primary function. The LSM200 Series controls have the following capabilities:

The LSM200 Series is presently available in two models, the LSM201 and the LSM201N. The LSM201 is the latest and current mode/ that meets all the specifications and functions described in this publication and is CE approved. The LS-M201N is functionally the same but lacks the extra filtering for CE approval. The LSM201 is supplied unless specified otherwise.

dESCRIPTION

Load Sharing Mode

Engine generator sets with isochronous governors maintain the requested speed very precisely. If synchronous genera-tors are electrically paralleled to increase the total generated power capability, a system to apportion the load is required. Even the finest electric governors will have minor frequency differences among units to be paralleled, which would cause power variations. In this case, one generator set would con-tinuously increase the power it produces, while the other sets would decrease the power they produce. This condi-tion eventually leads to motorizing one or more generator/ engines. The load sharing system continuously adjusts the governor speed settings so that no average power difference exists. The generators are locked together through electrical synchronizing torques. They act as though they are tightly connected through a gear drive.

The load sharing module measures the power that the gen-erator supplies to the main bus. Voltage inputs accept two ranges of three phase voltage. This covers most all appli-cations (see table in the specifications). In the design of polyphase generators, the presence of a third harmonic is possible. This odd order harmonic may cause errors in load sharing systems. To minimize this error and to improve the load sharing, a terminal is provided to connect to the neutral of a Wye configuration generator.

The line current measurements are usually taken from cur-rent transformers existing in the equipment such as those used for ammeter circuits.

Internal power measurement circuits develop a D.C. load signal across the parallel cable proportional to the AC power measured. The magnitude and sensitivity of the load sharing is adjustable through the LOAD SENSITIVITY control in the module. Test points TP1 (+) and TP2 (-) adjacent to this con-trol are used to measure the polarity and magnitude of the proportional power signal. This measurement is very impor-tant when initially installing a system and these test points may also be used in troubleshooting the system.

• Isochronous Load Sharing (0% Droop)• Reverse Power Monitoring• Forward Power Monitoring• Load Anticipation

• Automatic Power Ramping of its oncoming generator• Generator Power Ramping to the mains • Internal bar graph power measurement display• Power measurement with an external display

OVERNORS

MERICA

ORP.CAG

ISO 9001CERTIFIED

LSM201

LSM201N

Page 2: E GA G LSM200 Series CORP. S Load Sharing Module€¦ · diagram 1 system wiring/outline s/n : model: gac overnors merica orp. made in agawam, ma u.s.a. caution engine speed control

PTI4100 A2

This document is subject to change without notice. Caution: None of GAC products are flight certified controls including this item.

SPECIfICATIONS

PerforMance

Load Sharing..................................Adjustable to within ± 2% between setsOperating Modes... Isochronous and droop paralleling and main power controlReverse Power Monitor Trip Point...............................Adjustable from -2 to -20%Reverse Power Delay (Inverse Time Delay)......Adjustable from 0.5 to 15 secondsForward Power Monitor Trip Point....... “ON” trip point adjustable from 20-100%

.....“OFF” trip point adjustable from 0-80%Forward Power Delay.................................Adjustable from 0.4 to 30 SecondsPower Output Signal........................0 to -1 VDC represents reverse power

.............................0 to +6 VDC represents forward powerForward and Reverse Power Relay Contact Rating..... Form C, 10 Amp 290 VAParallel Cable Relay Contact Rating........................Gold Clad, 1.25 A 60 VA Max.All Performance specifications are based on 5 amps from the current trans-former secondary at full load on the generator.

environMentaLAmbient Temperature.........................................-40° to 185°F (-40 to +85°C)Relative Humidity……………………………………........…………up to 95%All Surface Finishes............................Fungus proof and corrosion resistance

reLiaBiLitYVibration…………….............................................................5G, 20-500 HzTesting....................................................................100% Functional Testing

PoWer inPUtS

3 phase AC Voltage signals..............Two selectable ranges accommodate 100-500 VAC Line to Line

Isolated from battery minus by 5000 VDCIsolated from case by 1000 VDC

3 phase AC Line Currents...........................0-5 Amps with 1.25 VA requirementIsolated from case by 1000 VDC

Common WYE connection to battery ground permitted. DC Supply..................17-32 VDC (Transient and Reverse voltage protected)Note: Battery (-) On All Sets Must Be Connected Together In Common

12 VDC units available on request.Polarity..........................................................Negative ground case isolated.Power Consumption-Battery Supply..................................................160 ma AC Phase Voltage Inputs 2.5 maExternal Power Meter (Voltage Output)............................10 ma max. current

PhYSicaLDimensions……………………………………… See Wiring Diagram (Fig. 1)Weight…………………………………………………........…1.2 lb (0.56 kg)Mounting................................……………………………………Any Position

SELECTION CHART

ModeL characteriSticS

LSM201 Extra Filtering/CE Approved

LSM201n Standard Filtering/Non-CE Approved

LSM201-12 12 Volt Version of LSM201

LSM201n-12 12 Volt Version of LSM201N

The parallel cable is the interconnection between each gen-erator set. Across this cable, each generator sends its load signal to a common point when the parallel cable’s circuit breaker contacts are closed. With all the parallel cables con-nected, a current flows in the cable that is proportional to any imbalance of load between the generators. The indi-vidual load sharing modules detect this imbalance, and a correction signal is sent to each governor to minimize the differences.

Automatic soft loading is a standard feature in the LSM200 Series modules. The oncoming generator set presets its load sharing to zero power until the parallel enable signal is given, then the unit ramps to equalize the loads of all com-mon generator sets. Soft unloading can be commanded via the ILC (Individual Load Control) terminals from service.

The load anticipation feature (Load Pulse) provides a signal that is a derivative function of the load. This load anticipation signal will make the governors more responsive to transient loads on the generator.

Forward and Reverse Power Monitors are provided for con-venience and protection in the load sharing module. When a

reverse power condition is sensed by the internal AC power measuring circuits, the internal relay contacts are closed.

The forward power monitor has both “ON” and “OFF” set points, which may be adjusted independently. The internal relay can be used to signal different load points.

Power control Mode

Automatic power ramping is a function provided in the LSM200 Series units. Each time the generator is put online or taken offline, the power can be ramped for a smooth tran-sition.

Mains Power control is also within the capability of this unit. With a slight reconnection, the unit can request its generator to supply a specific power level to the mains. This function can be controlled from local or remote locations. The power transitions are normally ramped up and down but may be made faster for rapid response.

The LSM200 Series of units additionally can be made part of a larger control system to manage a total power system.

Hence this unit can be commanded by other GAC accesso-ries to control the power from a group of engine generators.

Page 3: E GA G LSM200 Series CORP. S Load Sharing Module€¦ · diagram 1 system wiring/outline s/n : model: gac overnors merica orp. made in agawam, ma u.s.a. caution engine speed control

This document is subject to change without notice. Caution: None of GAC products are flight certified controls including this item.

3PTI4100 A

dIAGRAM 1 SYSTEM WIRING/OuTLINE

S/N :

MODEL:

GACOVERNORS

MERICA

ORP.

MADE IN AGAWAM, MA U.S.A.

CAUTIONENGINE SPEED CONTROL

COMPONENT. WHEN INSTALLINGOR SERVICING, REFER TO

PRODUCT PUBLICATION

(254)

(203)

(165

)

TOAMMETERCIRCUITS

GENERATOR

MAINS

L1

L2

L3

N

CT

CT

CT

.281

-+-+

SUPPLY

(7)

LOAD SHARINGMODULE

LSM201

(178

)

REVERSE POWERRELAY CONTACTS

FORWARD POWERRELAY CONTACTS

-

FORWARD POWERMONITOR PROGRAMMING

+ EXTERNALPOWER METEROUTPUT

INTERNAL+10 V DC SUPPLY

OPTIONALRAMP DEFEAT

17 - 32 V DC

OPTIONALGROUND

TP1TP2

CLOSE TO UNLOADOPEN TO LOAD GENERATOR

EXTERNAL POWER CONTROLINPUT 0 - 10V DCSEE PAGE 5

OPTIONAL EXTERNALMAINS POWER ADJUST

PARALLELCABLE

+-

CLOSE TO ENABLEPARALLEL RELAY

WD205C

OUTPUT TO GOVERNORSPEED CONTROL UNIT

CWTO TERMINAL 31 (+10V)

REVERSE POWERRELAY RESET(MOMENTARY-OPEN SWITCHOR JUMPER REQUIRED)

(40)

6.50

8.00

10.00

7.00

1.56

1 2

N 1 2 3 4 5 6 7 8 9NEUTRAL

CT1 CT2 CT3

LINE CURRENTINPUTS (0-5 AMPS)

AC VOLTAGEINPUTS (SET SW1)

L1 L2 L3 K L K L K LS1 S2 S1 S2 S1 S2

10 11 12 13 14 15 16 17 18 19 20 21+ _ PUT

OUTCABLEPARALLEL

UNLOADILC LOAD

22 23 24 25 26 27 28 29 30 31 32 33+ _

REV FOR

+_

POWER MONITORCONTACTS

LOAD UNLOAD

RAMPING

LOADSENSITIVITY

LOADANTIC

FORWARD POWERMONITOR ADJUST

ONOFF

REVERSE POWERMONITOR DELAY

FORWARD POWERMONITOR DELAY

REVERSE POWERMONITOR ADJUST

24V DCSUPPLY

POWERMETER

ADJUSTRAMPSW1

FORPWR

REVPWR

REVERSE POWERRESET

PARALLEL ENABLE

ILC LOAD/UNLOAD RAMP

EXTERNAL POWERMETER CAL

GENERATOR POWERDISPLAY CAL

GENERATOR POWERCONTROL

LSM201

Page 4: E GA G LSM200 Series CORP. S Load Sharing Module€¦ · diagram 1 system wiring/outline s/n : model: gac overnors merica orp. made in agawam, ma u.s.a. caution engine speed control

This document is subject to change without notice. Caution: None of GAC products are flight certified controls including this item.

4PTI4100 A

dIAGRAM 2 SYSTEM WIRING/OuTLINE

N 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

22 23 24 25 26 27 28 29 30 31 32 33

+ _UNLOAD

PARALLEL

+ _

REV FOR

POWERMONITOR

CONTACTS

NEUTRAL

CT1 CT2 CT3REVERSE POWERRESET

POWERMETER

+_

LOAD UNLOAD

ADJUSTRAMP

LOADADJUST DELAY ON

ADJUST

OFF DELAY

24V DCSUPPLY

LINE CURRENTINPUTS (0-5 AMPS)

PUTOUTCABLE

PARALLEL

ENABLE

ILC LOAD

ILC LOAD/UNLOAD RAMP

POWERFOR

REVPOWER

POWER DISPLAYGENERATOR

CAL

GENERATOR POWERCONTROL

FORWARDREVERSE

POWER MONITORS

AC VOLTAGEINPUTS (SET SW1)

RAMPING

ANTIC

OFF= 240-500 VSW1 AC VOLTAGE

LOADSENSITIVITY

POWER METEREXTERNAL

CAL

L1 L2 L3 K L K L K LS1 S2 S1 S2 S1 S2

S/N :

MODEL:

GACOVERNORS

MERICA

ORP.

MADE IN AGAWAM, MA U.S.A.

CAUTIONENGINE SPEED CONTROL

COMPONENT. WHEN INSTALLINGOR SERVICING REFER TOPRODUCT PUBLICATION.

-+

(254)

(203)

(165

)

TP1

TP2

TOAMMETERCIRCUITS

GENERATOR

MAINS

4 PLACES

LOAD SHARINGMODULE

L1L2

L3

N

CT

CT

CT

(40)

.281

LSM201N

(7)

REVERSE POWERRELAY CONTACTS

FORWARD POWERMONITOR PROGRAMMING

-+

-+

SUPPLY

FORWARD POWERRELAY CONTACTS

INTERNAL+10V DC SUPPLY

EXTERNALPOWER METEROUTPUT

1 2ON

FFO

17 - 32 V DC

OPEN TO LOAD GENERATORCLOSE TO UNLOAD

OPTIONALRAMP DEFEAT

EXTERNAL POWERCONTROL INPUT0 - 10V DC

OPTIONAL EXTERNALMAINS POWER ADJUST

(178

)

ON= 100-280 V

OPTIONALGROUND

PARALLELCABLE

+-

CLOSE TO ENABLEPARALLEL RELAY

WD202D

OUTPUT TO GOVERNORSPEED CONTROL UNIT

CWTO TERMINAL 31 (+10V)

REVERSE POWERRELAY RESET(MOMENTARY OPEN SWITCHOR JUMPER REQUIRED)

6.50

1.56

8.00

10.00

7.00

LSM201N