Modeling Energy Consumption in Religious Establishments Franco Morelli Hyoungsub Kim
Transcript
Page 1: E plus presentation

Modeling Energy

Consumption in Religious

Establishments

Franco Morelli

Hyoungsub Kim

Page 2: E plus presentation

The church is located amongst a community

of residential homes

• College Station, TX

• ASHRAE Climate Zone 2A – Hot

&Humid

• Between 6,000 and 9,000 CDD

Page 3: E plus presentation

The building has a 24,864 ft2 footprint. Community

meeting areas in center. Classrooms and ,offices on

outside.

Page 4: E plus presentation

The buildings have several architectural

features that make modeling challenging, yet

interesting

• Cultural Hall

• Basketball Court

• Stage

• Divider

• Approx. 53’ x 79’ x 20’

• Chapel

• Approx. 53’ x 53’ x 20’

• 2 Tinted glass

doorways lead to

vestibule

Page 5: E plus presentation

A couple more interesting architectural

features

• Transformed Rooms

with Dividers

• Several Self

Contained Rooms

• 2 Vestibules

• 3 Foyers

Page 6: E plus presentation

A couple of energy consuming features of the

building

• Tankless Water

Heating

• Bathrooms

• Baptismal Font

• T8 and T12 Lighting

Page 7: E plus presentation

The buildings use several traditional, vapor

compression split systems for cooling

Page 8: E plus presentation

There are 10 air handles supplying

conditioned air to 10 zones.

Page 9: E plus presentation

Building Layout

Floor Plan Section Plan

Two Parts : 1. Cultural Hall & Chapel

2. Office & Hallway

Page 10: E plus presentation

Zone

EnergyPlus Model

1. HVAC Template_1 Zone

2. HVAC Template_9 Zone

3. Chiller_1 Zone

4. Chiller_9 Zone

1 Zone 9 Zone

HVAC Duct

Page 11: E plus presentation

SketchUp Model

Axonometric Drawing

Page 12: E plus presentation

Schedule

Occupancy

1. Chapel & Cultural hall

(Weekly & Daily)

2. Office

(Weekly & Daily)

Lighting & Equipment

1. Weekly

2. Daily

60% 90%

Page 13: E plus presentation

Results

Page 14: E plus presentation

0.00

5000.00

10000.00

15000.00

20000.00

25000.00

30000.00

35000.00

1 2 3 4 5 6 7 8 9 10 11 12

with attic [kWh]

without attic [kWh]

Measured data(kWh)

Baseline_Template_1 Zone

VS

Attic Without Attic

100% 150%

100% 230%

Total

December

Page 15: E plus presentation

Baseline_Template_9 Zone

(initial result)

Initial result > Measured data : 1.7 times

Internal Gains

People : 0.05 person/m^2 (office)

0.75 person/m^2 (chapel)

Lighting : 10 W/m^2

Equipment : 8.9 W/m^2

0.00

5000.00

10000.00

15000.00

20000.00

25000.00

30000.00

35000.00

40000.00

1 2 3 4 5 6 7 8 9 10 11 12

Initial [kWh]

Measured data [kWh]

Page 16: E plus presentation

Baseline_Template_9 Zone

(Calibration)Schedules

Chapel : weekly, daily

Office : weekly, dailyFinal result < Measured data : 10%

0.00

5000.00

10000.00

15000.00

20000.00

25000.00

1 2 3 4 5 6 7 8 9 10 11 12

calibration [kWh]

Measured data [kWh]

Page 17: E plus presentation

0.00

5000.00

10000.00

15000.00

20000.00

25000.00

1 2 3 4 5 6 7 8 9 10 11 12

1zone [kWh]

9zone [kWh]

Bill(kWh)

Baseline_Template_9 Zone

Final result (9 zone) < Measured data : 10%

Final result (1 zone) < Measured data : 8.4%

; except March, July : 12%

; except March, July : 12%

Page 18: E plus presentation

The energy efficiency improvements

Page 19: E plus presentation

The energy efficiency improvements

0.00

5000.00

10000.00

15000.00

20000.00

25000.00

1 2 3 4 5 6 7 8 9 10 11 12

baseline[kWh]

Insulation [kWh]

Improve Insulation : exterior wall ( 50mm 76mm )

roof insulation ( X 50mm ) 4 % improvement

Page 20: E plus presentation

0.00

5000.00

10000.00

15000.00

20000.00

25000.00

1 2 3 4 5 6 7 8 9 10 11 12

baseline [kWh]

Window [kWh]

Improve window : clear 3mm / Air 13mm / clear 3mm

Triple LoE glass 2% improvement

The energy efficiency improvements

Page 21: E plus presentation

0.00

5000.00

10000.00

15000.00

20000.00

25000.00

1 2 3 4 5 6 7 8 9 10 11 12

baseline [kWh]

Insul+Win [kWh]

6% improvement

The energy efficiency improvements

Improve insulation : 76 mm insulation

Improve window : Triple LoE glass

Page 22: E plus presentation

0.00

5000.00

10000.00

15000.00

20000.00

25000.00

1 2 3 4 5 6 7 8 9 10 11 12

baseline [kWh]

Insul+Win+Orient

The energy efficiency improvements (orientation)

1% improvement

Total : 7 %

Southeast South

Page 23: E plus presentation

Chiller System Simulation Comparison

Page 24: E plus presentation

Comparison of billed energy usage with

chilled water HVAC energy usage for single

zone simulation

Page 25: E plus presentation
Page 26: E plus presentation

Comparison of split HVAC with chilled water

HVAC energy usage for single zone

simulation

Page 27: E plus presentation

Comparison of billed energy usage with chilled water HVAC energy usage for 9 zone simulation

Page 28: E plus presentation
Page 29: E plus presentation

Comparison of split HVAC with chilled water HVAC energy usage for 9 zone simulation

Page 30: E plus presentation

Questions?