+ All Categories
Home > Documents > Elec Calculation

Elec Calculation

Date post: 05-Apr-2018
Category:
Upload: vs-pkd
View: 229 times
Download: 0 times
Share this document with a friend

of 12

Transcript
  • 8/2/2019 Elec Calculation

    1/12

    = The load is running at iniatial power factor= Required to be corrected power factor

    = kilovolt amperes reactant= Total connected load= After diversity maximum demand

    = TCL x [tan (phi)1 - tan (phi)c]

    = 50.00== 0= 0.80

    (phi)1

    (phi)c kVAr 2

    kiloWattkVA

  • 8/2/2019 Elec Calculation

    2/12

    Short Cicuirt Current Calculation

    Formula:

    k x S t

    Where:

    I = Short circuit current (Amps)

    S = Copper area of conductor (mm) 90.0

    t = Duration of short circuit current (seconds) 1

    up to 5 seconds maximum

    k = Constant to allow for an initial temperature

    of 90 C & final conductor temperature of 250 C

    = 143

    I = 12,870.00 Amps

    Notes:

    1

    2 It shound be ensured that the accessories associated with the cables are also

    capable of operation at these values of fault current and temperature.

    The formula given is based on the cables being fullly loaded at the start of a short

    circuit (conductor temperature 90 C) and a final conductor temperature of 250 C.

    =I

  • 8/2/2019 Elec Calculation

    3/12

    Data:

    total connected load: = 50.00 KiloWatt

    Operating Voltage: = 440 Volts

    Phase: = 3

    Frequency: = 60 Hz

    Total Distance: = 295 Feet cm

    Power Factor: = 90% meter

    I full load = (KW x 1,000)/^0.5xVxPF)

    I full load = 72.90 Amps

    Proposed Wire Size: = 90.0 mm

    Where:

    K = Resistance of conductor per foot

    12 for circuits loaded more than 50% of conductor =

    current carrying capacity

    11 for circuit loaded not more than 50% of conductor =current carrying capacity

    18 for aluminum conductors =

    L = length of conductor,(feet)

    I = Full Load current

    d = cross-section of conductor in Circular - Mill =

    0.0005067 mm per Cir-Mil

    d = 177619.8934 CM

    Vdrop = 2.31889387 volts

    % Vdrop = 0.47%

    Notes:1. Voltage Drop shall not exceed 3% of operating voltage

    2. Increase of conductor as necessary to limit voltage drop to < 3%

    90.00

    Voltage Drop Calculation:

    0.0005067

    12

    11

    18

    V drop = ((2xK) x L x Ifull load)/ d x 87%

    8,997.70

  • 8/2/2019 Elec Calculation

    4/12

    Table 4.9 Volt drops for mineral

    p.v.c sheath p.v.c sheath p.v.c sheath bare sheath bare sheath Cross-sec Single-phase Single-phase

    2xsingle/twin 3 core 3 x single 2xsingle/twin 2xsingle/twin area p.v.c sheath bare

    (A) (A) (A) (A) (A) (mm) (mV/A/m) (mV/A/m)

    1.0 (500V) 18.5 15.0 17.0 22.0 21.0 1.0 42.0 47.0

    1.5 (500V) 23.0 19.0 21.0 28.0 27.0 1.5 28.0 31.0

    2.5 (500V) 31.0 26.0 29.0 38.0 36.0 2.5 17.0 19.0

    4.0 (500V) 40.0 35.0 38.0 51.0 47.0 4.0 10.0 12.0

    1.0 (750V) 19.5 16.0 18.0 24.0 24.0 6.0 7.0 7.8

    1.5 (750V) 25.0 21.0 23.0 31.0 30.0 10.0 4.2 4.7

    2.5 (750V) 34.0 28.0 31.0 42.0 41.0 16.0 2.6 3.0

    4.0 (750V) 45.0 37.0 41.0 55.0 53.0

    6.0 (750V) 57.0 48.0 52.0 70.0 67.0 Formula:

    10.0 (750V) 77.0 65.0 70.0 96.0 91.0

    16.0 (750V) 102.0 86.0 92.0 127.0 119.0

    Table 4.8 Current rating of mineral insulated cables clipped

    directVolt drops for mineral insulated cables (from [Tables 4G1B &4G2B] o

    (from [Tables 4G1B & 4G2A] of BS 7671:2008

    Cross-sec

    (mV/A/m(f

    area

    (mm)

    VDrop =

  • 8/2/2019 Elec Calculation

    5/12

    insulated cables

    Three-phase Three-phase

    p.v.c sheath bare

    (mV/A/m) (mV/A/m)

    36.0 40.0

    24.0 27.0

    14.0 16.0

    9.1 10.0

    6.0 6.8

    3.6 4.1

    2.3 2.6

    BS 7671:2008)

    or selected cable))(IF)(L)

    1000

  • 8/2/2019 Elec Calculation

    6/12

    Under Armour Armour wire Dia OverallCURRENT

    RATING

    mm mm mm mm kg / km Ohm / km Ohm / km Amp

    1.5 * 9.1 0.9 13.5 380 8.8 12.1 25

    2.5 * 10.6 0.9 14.5 445 7.7 7.41 33

    4 * 11.4 0.9 17 550 6.8 4.61 44

    6 * 13 1.25 18.5 770 4.3 3.08 56

    10 * 15 1.25 20.5 1020 3.7 1.83 78

    16 * 18 1.25 23.5 1320 3.1 1.15 99

    25 20 1.6 26.1 1840 2.3 0.727 131

    35 22.8 1.6 28.6 2310 2 0.524 162

    50 25.5 1.6 32 2970 1.8 0.387 197

    70 29.5 2 37.7 4240 1.2 0.268 251

    95 33.5 2 41.7 5400 1.1 0.193 304

    120 37.5 2.5 47.1 7000 0.76 0.153 353

    150 41.5 2.5 51.4 8350 0.68 0.124 406

    185 46 2.5 56.6 10130 0.61 0.0991 463

    240 52.5 2.5 63 12840 0.54 0.0754 546

    300 57.5 2.5 68.8 15530 0.49 0.0601 628

    400 65 3.15 78.1 19950 0.35 0.047 728

    mm mm mm kg/km ohm/km amp mV/A/m amp

    1.5 0.7 3.4 22 12.1 22 31 19

    2.5 0.8 4.1 33 7.41 30 19 26

    4 0.8 4.7 49 4.61 40 12 35

    6 0.8 5.4 69 3.08 51 7.9 45

    10 1 7 116 1.83 71 4.7 63

    16 1 8 175 1.15 95 2.9 85

    25 1.2 10.1 274 0.727 126 1.9 111

    35 1.2 11.3 367 0.524 156 1.35 138

    50 1.4 13 495 0.387 189 1.05 168

    70 1.4 15 699 0.268 240 0.75 214

    95 1.6 17 968 0.193 290 0.58 259

    120 1.6 19 1164 0.153 336 0.48 299

    150 1.8 21 1413 0.124 375 0.43 328

    185 2 23.5 1828 0.0991 426 0.37 370

    240 2.2 26.5 2320 0.0754 500 0.33 433

    300 2.4 29.5 2988 0.0601 573 0.31 493

    400 2.6 34.3 3700 0.047 683 0.29 584

    500 2.8 38.2 4750 0.0366 783 0.28 666630 2.8 42.5 6000 0.0283 900 0.27 764

    Three or Fou

    Cables, Thre

    Phase a.c Cur

    Rating

    Maximum

    conductor

    Resistance at

    20C

    Nominal

    Conductor Area

    Radial Thickness

    of Insuation

    Mean Overall

    Diameter (upper

    limit)

    Approximate

    Cable WeightTwo cables,

    Single phase a.c.

    Current Rating

    Two cables,

    Single phase a.c.

    Volt Drop per

    Amp per Metre

    Conductor AreaApproximate

    Cable weight

    Maximum armour

    resistance at 20

    C

    Maximum

    conductor

    resistance at 20

    C

    Approximate Diameter

    600 / 1000 V Copper Power Cables

    Free A

    Thre

    Enclosed in conduit (method 30

  • 8/2/2019 Elec Calculation

    7/12

    Single - core PVC insulated, non armoured, stranded copper conductors

    ( BS 6004 & BS 6346 )

    Max. rating of'

    2 x 1C, 1 Phase 3/4 x 1C, 3 Phase MCB / MCCB

    mm mm (A)

    1.5 1.5 10

    2.5 2.5 154 4 20

    6 6 25

    6 10 30

    10 16 40

    16 25 50

    25 35 60

    35 50 80

    - 70 100

    - 95 125

    - 120 150

    Size of cables, in 'concealed' conduits

  • 8/2/2019 Elec Calculation

    8/12

    Max. Load

    current / demand

    (A)

    10

    1520

    25

    30

    40

    50

    60

    80

    100

    125

    150

  • 8/2/2019 Elec Calculation

    9/12

    Edition 16 IEE wiring regulation

    Current demand calculation

    where: P = 1500 kw

    V = 440 volt

    P.F = 90%

    I = amp

    Fault Current Calculation

    where: I = 2186.9 amp

    t = 0.2 sec

    k = 143

    S = 6.8 mm

    Applying diversity:

    1st unit 100 % = 02nd unit 100 % = 0

    3rd unit 25 % = 0

    4th unit 25 % = 0

    Total assumed Current demand = 0 amp

    Loop Impedance calculation (Zs)

    where: Zs = Loop impedance

    Ze = External loop Impedance for distributor &services cables

    R1 = Resistance of the phase conductor

    R2 = Circuit protective conductor (Earth)

    Zs = Ze + ( R1 + R2)

    a u ate va ue o 1+ 2) x rcu t engt x u t p er

    Correction Factors

    where:

    Ca = Factor for ambient temperature

    Cg = Factor for groups of cables

    Cf = Factor if BS 3036 rewirable fuse is used (factor is 0.725)

    Ci = Factor if cable is sorrounded by thermally insulating materialIb = Design current

    It = Tabulated conductor current carrying capacity

    In = Nominal rating or setting of protection

    Iz = Current carrying capacity of the conductors

    I2 = Current causing operation of the device

    2186.9

    ( R1 + R2) = 1000

  • 8/2/2019 Elec Calculation

    10/12

    Ca x Cg x Cf x CiIt

    In

  • 8/2/2019 Elec Calculation

    11/12

    Short Circuit Current Calculation

    Formula:

    k x S t

    Where:

    I = Short circuit current (Amps)

    S = Copper area of conductor (mm) 1.5

    t = Duration of short circuit current (seconds) 0.5

    up to 5 seconds maximum

    k = Constant to allow for an initial temperature

    of 90 C & final conductor temperature of 250 C

    = 143

    I = 303.35 Amps

    Notes:

    1

    2 It shound be ensured that the accessories associated with the cables are also capable of

    operation at these values of fault current and temperature.

    The formula given is based on the cables being fullly loaded at the start of a short circuit

    (conductor temperature 90 C) and a final conductor temperature of 250 C.

    =I

  • 8/2/2019 Elec Calculation

    12/12

    Power Factor improvement

    at 90% power

    factor

    at 60% power

    factor

    1273.5 kvar 1500 kvar

    1350 kvar

    76.5 kvar


Recommended