of 12
8/2/2019 Elec Calculation
1/12
= The load is running at iniatial power factor= Required to be corrected power factor
= kilovolt amperes reactant= Total connected load= After diversity maximum demand
= TCL x [tan (phi)1 - tan (phi)c]
= 50.00== 0= 0.80
(phi)1
(phi)c kVAr 2
kiloWattkVA
8/2/2019 Elec Calculation
2/12
Short Cicuirt Current Calculation
Formula:
k x S t
Where:
I = Short circuit current (Amps)
S = Copper area of conductor (mm) 90.0
t = Duration of short circuit current (seconds) 1
up to 5 seconds maximum
k = Constant to allow for an initial temperature
of 90 C & final conductor temperature of 250 C
= 143
I = 12,870.00 Amps
Notes:
1
2 It shound be ensured that the accessories associated with the cables are also
capable of operation at these values of fault current and temperature.
The formula given is based on the cables being fullly loaded at the start of a short
circuit (conductor temperature 90 C) and a final conductor temperature of 250 C.
=I
8/2/2019 Elec Calculation
3/12
Data:
total connected load: = 50.00 KiloWatt
Operating Voltage: = 440 Volts
Phase: = 3
Frequency: = 60 Hz
Total Distance: = 295 Feet cm
Power Factor: = 90% meter
I full load = (KW x 1,000)/^0.5xVxPF)
I full load = 72.90 Amps
Proposed Wire Size: = 90.0 mm
Where:
K = Resistance of conductor per foot
12 for circuits loaded more than 50% of conductor =
current carrying capacity
11 for circuit loaded not more than 50% of conductor =current carrying capacity
18 for aluminum conductors =
L = length of conductor,(feet)
I = Full Load current
d = cross-section of conductor in Circular - Mill =
0.0005067 mm per Cir-Mil
d = 177619.8934 CM
Vdrop = 2.31889387 volts
% Vdrop = 0.47%
Notes:1. Voltage Drop shall not exceed 3% of operating voltage
2. Increase of conductor as necessary to limit voltage drop to < 3%
90.00
Voltage Drop Calculation:
0.0005067
12
11
18
V drop = ((2xK) x L x Ifull load)/ d x 87%
8,997.70
8/2/2019 Elec Calculation
4/12
Table 4.9 Volt drops for mineral
p.v.c sheath p.v.c sheath p.v.c sheath bare sheath bare sheath Cross-sec Single-phase Single-phase
2xsingle/twin 3 core 3 x single 2xsingle/twin 2xsingle/twin area p.v.c sheath bare
(A) (A) (A) (A) (A) (mm) (mV/A/m) (mV/A/m)
1.0 (500V) 18.5 15.0 17.0 22.0 21.0 1.0 42.0 47.0
1.5 (500V) 23.0 19.0 21.0 28.0 27.0 1.5 28.0 31.0
2.5 (500V) 31.0 26.0 29.0 38.0 36.0 2.5 17.0 19.0
4.0 (500V) 40.0 35.0 38.0 51.0 47.0 4.0 10.0 12.0
1.0 (750V) 19.5 16.0 18.0 24.0 24.0 6.0 7.0 7.8
1.5 (750V) 25.0 21.0 23.0 31.0 30.0 10.0 4.2 4.7
2.5 (750V) 34.0 28.0 31.0 42.0 41.0 16.0 2.6 3.0
4.0 (750V) 45.0 37.0 41.0 55.0 53.0
6.0 (750V) 57.0 48.0 52.0 70.0 67.0 Formula:
10.0 (750V) 77.0 65.0 70.0 96.0 91.0
16.0 (750V) 102.0 86.0 92.0 127.0 119.0
Table 4.8 Current rating of mineral insulated cables clipped
directVolt drops for mineral insulated cables (from [Tables 4G1B &4G2B] o
(from [Tables 4G1B & 4G2A] of BS 7671:2008
Cross-sec
(mV/A/m(f
area
(mm)
VDrop =
8/2/2019 Elec Calculation
5/12
insulated cables
Three-phase Three-phase
p.v.c sheath bare
(mV/A/m) (mV/A/m)
36.0 40.0
24.0 27.0
14.0 16.0
9.1 10.0
6.0 6.8
3.6 4.1
2.3 2.6
BS 7671:2008)
or selected cable))(IF)(L)
1000
8/2/2019 Elec Calculation
6/12
Under Armour Armour wire Dia OverallCURRENT
RATING
mm mm mm mm kg / km Ohm / km Ohm / km Amp
1.5 * 9.1 0.9 13.5 380 8.8 12.1 25
2.5 * 10.6 0.9 14.5 445 7.7 7.41 33
4 * 11.4 0.9 17 550 6.8 4.61 44
6 * 13 1.25 18.5 770 4.3 3.08 56
10 * 15 1.25 20.5 1020 3.7 1.83 78
16 * 18 1.25 23.5 1320 3.1 1.15 99
25 20 1.6 26.1 1840 2.3 0.727 131
35 22.8 1.6 28.6 2310 2 0.524 162
50 25.5 1.6 32 2970 1.8 0.387 197
70 29.5 2 37.7 4240 1.2 0.268 251
95 33.5 2 41.7 5400 1.1 0.193 304
120 37.5 2.5 47.1 7000 0.76 0.153 353
150 41.5 2.5 51.4 8350 0.68 0.124 406
185 46 2.5 56.6 10130 0.61 0.0991 463
240 52.5 2.5 63 12840 0.54 0.0754 546
300 57.5 2.5 68.8 15530 0.49 0.0601 628
400 65 3.15 78.1 19950 0.35 0.047 728
mm mm mm kg/km ohm/km amp mV/A/m amp
1.5 0.7 3.4 22 12.1 22 31 19
2.5 0.8 4.1 33 7.41 30 19 26
4 0.8 4.7 49 4.61 40 12 35
6 0.8 5.4 69 3.08 51 7.9 45
10 1 7 116 1.83 71 4.7 63
16 1 8 175 1.15 95 2.9 85
25 1.2 10.1 274 0.727 126 1.9 111
35 1.2 11.3 367 0.524 156 1.35 138
50 1.4 13 495 0.387 189 1.05 168
70 1.4 15 699 0.268 240 0.75 214
95 1.6 17 968 0.193 290 0.58 259
120 1.6 19 1164 0.153 336 0.48 299
150 1.8 21 1413 0.124 375 0.43 328
185 2 23.5 1828 0.0991 426 0.37 370
240 2.2 26.5 2320 0.0754 500 0.33 433
300 2.4 29.5 2988 0.0601 573 0.31 493
400 2.6 34.3 3700 0.047 683 0.29 584
500 2.8 38.2 4750 0.0366 783 0.28 666630 2.8 42.5 6000 0.0283 900 0.27 764
Three or Fou
Cables, Thre
Phase a.c Cur
Rating
Maximum
conductor
Resistance at
20C
Nominal
Conductor Area
Radial Thickness
of Insuation
Mean Overall
Diameter (upper
limit)
Approximate
Cable WeightTwo cables,
Single phase a.c.
Current Rating
Two cables,
Single phase a.c.
Volt Drop per
Amp per Metre
Conductor AreaApproximate
Cable weight
Maximum armour
resistance at 20
C
Maximum
conductor
resistance at 20
C
Approximate Diameter
600 / 1000 V Copper Power Cables
Free A
Thre
Enclosed in conduit (method 30
8/2/2019 Elec Calculation
7/12
Single - core PVC insulated, non armoured, stranded copper conductors
( BS 6004 & BS 6346 )
Max. rating of'
2 x 1C, 1 Phase 3/4 x 1C, 3 Phase MCB / MCCB
mm mm (A)
1.5 1.5 10
2.5 2.5 154 4 20
6 6 25
6 10 30
10 16 40
16 25 50
25 35 60
35 50 80
- 70 100
- 95 125
- 120 150
Size of cables, in 'concealed' conduits
8/2/2019 Elec Calculation
8/12
Max. Load
current / demand
(A)
10
1520
25
30
40
50
60
80
100
125
150
8/2/2019 Elec Calculation
9/12
Edition 16 IEE wiring regulation
Current demand calculation
where: P = 1500 kw
V = 440 volt
P.F = 90%
I = amp
Fault Current Calculation
where: I = 2186.9 amp
t = 0.2 sec
k = 143
S = 6.8 mm
Applying diversity:
1st unit 100 % = 02nd unit 100 % = 0
3rd unit 25 % = 0
4th unit 25 % = 0
Total assumed Current demand = 0 amp
Loop Impedance calculation (Zs)
where: Zs = Loop impedance
Ze = External loop Impedance for distributor &services cables
R1 = Resistance of the phase conductor
R2 = Circuit protective conductor (Earth)
Zs = Ze + ( R1 + R2)
a u ate va ue o 1+ 2) x rcu t engt x u t p er
Correction Factors
where:
Ca = Factor for ambient temperature
Cg = Factor for groups of cables
Cf = Factor if BS 3036 rewirable fuse is used (factor is 0.725)
Ci = Factor if cable is sorrounded by thermally insulating materialIb = Design current
It = Tabulated conductor current carrying capacity
In = Nominal rating or setting of protection
Iz = Current carrying capacity of the conductors
I2 = Current causing operation of the device
2186.9
( R1 + R2) = 1000
8/2/2019 Elec Calculation
10/12
Ca x Cg x Cf x CiIt
In
8/2/2019 Elec Calculation
11/12
Short Circuit Current Calculation
Formula:
k x S t
Where:
I = Short circuit current (Amps)
S = Copper area of conductor (mm) 1.5
t = Duration of short circuit current (seconds) 0.5
up to 5 seconds maximum
k = Constant to allow for an initial temperature
of 90 C & final conductor temperature of 250 C
= 143
I = 303.35 Amps
Notes:
1
2 It shound be ensured that the accessories associated with the cables are also capable of
operation at these values of fault current and temperature.
The formula given is based on the cables being fullly loaded at the start of a short circuit
(conductor temperature 90 C) and a final conductor temperature of 250 C.
=I
8/2/2019 Elec Calculation
12/12
Power Factor improvement
at 90% power
factor
at 60% power
factor
1273.5 kvar 1500 kvar
1350 kvar
76.5 kvar