5
High accuracy of Class 0.2S Monitors power quality parameters NAVIGATOR PRO NP 8710 www.elmeasure.com Demand update every second 1s capturing of Sag & Swell with waveforms Comprehensive monitoring of essential power,energy demand and power quality.
Transcript
  • High accuracy ofClass 0.2S

    Monitors powerquality parameters

    NAVIGATOR PRONP 8710

    www.elmeasure.com

    Demand updateevery second

    1s capturing of Sag &Swell with waveforms

    Comprehensive monitoring

    of essential power,energy

    demand and power quality. “

  • Ÿ True RMS measurements.

    Ÿ High accuracy metering with class 0.5/Class 0.2S

    (optional) as per standard IEC 62053-22.

    Ÿ Measures THD and harmonics up to 63 rd order with a

    sampling rate of 512 samples/cycle

    Ÿ Captures and measures power quality events: flicker, K

    factor, crest factor,sag/ swell, interruption & unbalance in

    accordance with EN50160

    Ÿ Display basic, power, energy,demand for both import and

    export parameters.

    Ÿ Representation of waveforms for instantaneous V,I,

    harmonics,Sag/Swell.

    Ÿ Records events such as Sag/Swell for voltage with the

    time stamp in 1s duration.

    Ÿ Simultaneous sampling of voltage and current.

    Ÿ Programmable PT & CT ratio.

    Ÿ Demand update every second to forecast VA,KW& KVAR

    accurately

    Ÿ Energy resetting at 999999kVAh *transformer ratio.

    Ÿ Available RS485 communication and optional ethernet or

    GPRS interface communication (factory configurable).

    Ÿ Password protection for security against mishandling.

    NP 8710NAVIGATOR PRO“The Navigator Pro 8710 multifunction power meter offers

    all the basic/power/ energy measurement and power quality

    monitoring capabilities”.

    FeaturesApplications

    Monitoring critical load,incomers, and

    HT panels

    Building Management system

    Utility billing in Apartments and commercial

    complexes

    Study load pattern

    Energy auditing

    Measuring power & energy variants in

    Gensets, Test benches, and the laboratories

  • DatasheetElectrical Services:

    Microprocessor Multi-tasking ,Multi user ,Real Time control

    Operating Temperature -10°C to + 55°C (14°F - 131°F)

    Storage Temperature -25°C to +70°C (-13°F - 158°F)

    Accuracy Class 0.5 (Default) IEC 62053-22.

    Class 0.2S as per IEC 62053-22 (Optional).

    Update Rate 1s for all parameters

    Measured Voltage Inputs

    Sensing / Measurement True RMS, 1s update time. 4 Quadrant Power & Energy.

    Input voltage (Measurement) 4 Voltage inputs (V1, V2, V3, N) Programmable 110 or 415V LL Nominal

    Primary Programmable up to 999 kV.

    Burden 0.2VA Max. per phase

    External Fuse Rating 2 Amps

    Frequency 45 Hz - 65Hz

    Measured Current Inputs

    Input Current (Measurement) Current inputs (AR, AY, AB) 10mA - 6A (Field configurable 1A or 5A)

    Primary Programmable up to 99 kA

    Overload 10A max continuous, 50A max for 3s

    Burden 0.2VA Max. per phase

    Auxiliary Supply (Control Power) 80 to 300V AC, 40-70Hz

    Burden 5VA Max

    External Fuse Rating 200mA

    CT PT Ratio Max 2000 MVA Programmable

    Protection Class 3

    Measurement Category CAT lll ( As per IEC 61010)

    Display Resolution LCD display

    Graphics LCM unit consists of 128 × 64 dot-matrix LCD panel

    Number of dots/characters 120x64 (W×H)

    Humidity 5% to 95% non-condensing

    Pollution Degree 2 (As per IEC 61010)

    Altitude Below 2000mts

    Insulation Double Insulation ( As per IEC 61010-1)

    Ingress Protection IP 51 ( IP 54 front facia optional )

    Wire Gauge (Connecting wires) 26 - 10AWG (4.0m㎡). Network Communication:

    Communication RS 485 serial channel connection Industry standard Modbus. RTU

    protocol. 4800 bps to 38400 bps (preferred 9600 bps) 2000 volts AC

    isolation for 1 minute between communication and other circuits.

    Baud rate 9600 bps to 115200 bps (preferred 9600 bps)

    Isolation 2000 volts AC isolation for 1 minute between communication and other

    circuits.

  • Dimension Bezel 90 X 90 mm

    Mounting Panel mount

    30

    96

    90

    9096

    41

    +290-0

    +290-0

    Mechanical Specification

    Dimension 96mm X 96mm

    Weight Without Packing 300g, With Packing 375g

  • BENGALURU

    PLOT NO.: 47-P, HARDWARE PARK, KIADB,

    HUVINAYAKANAHALLI, JALA HOBLI, YELAHANKA TALUK,

    BENGALURU - 562 149. KARNATAKA INDIA

    Registered Office

    UNIT III

    #764, 4TH PHASE, 707, YELAHANKA NEW TOWN,

    BENGALURU - 560 064. KARNATAKA, INDIA

    UNIT II

    GOWTHAM GARDEN NO. 4, VEERAPANDICOIMBATORE - 641 019. TAMIL NADU, INDIA

    Manufacturing Units UNIT I

    PLOT NO.: 47-P, HARDWARE PARK, KIADB,

    HUVINAYAKANAHALLI, JALA HOBLI, YELAHANKA TALUK,

    BENGALURU - 562 149. KARNATAKA, INDIA

    Service Hotline:

    [email protected]

    +91 639-1010-320Monday to Friday 8:00 am. to 5:00 pm. IST

    Sale Offices

    COIMBATORE

    # 150, RA J ILLAM, NVM LAYOUT NEW SIDDHAPUDHURCOIMBATORE - 641 019. TAMIL NADU, INDIA

    SECUNDERABAD

    # 51, 1ST FLOOR, CHANDRAGIRI COLONY, NEAR RTA, THRIMUGHERRY,SECUNDERABAD - 500 015. TELANGANA, INDIA

    MUMBAI

    # 101, MILLENIUM PLAZA BEHIND SAKINAKA TELEPHONE EXCHANGE, ANDHERI - KURLA ROAD SAKINAKA, ANDHERI (EAST)MUMBAI - 400 072. MAHARASTRA, INDIA

    DELHI

    # G-10, G-11, GROUND FLOOR, BAISOYA COMPLEX,NAYABANS, SECTOR-15,NOIDA – 201301. INDIA.

    CHENNAI

    # 945, GROUND FLOOR, MIG, FIRST MAIN ROAD, TNHB

    COLONY, VELACHERY,

    CHENNAI – 600 042. TAMIL NADU, INDIA

    BENGALURU

    #57, EBENEZER ENCLAVE, NORRIS ROAD, NEAR

    NANJAPPA CIRCLE LANGFORD TOWN,

    BENGALURU - 560 025. KARANATAKA, INDIA

    PC/NP/V0.1/1018

    Page 1Page 2Page 3Page 4Page 5


Recommended