GENERAL DESCRIPTION
ColorOdorPack/UnitFluid Wt. per Gal.
Florescent PinkNot OffensiveBulk/Drums9.35 - 9.45 lbs./gal.
SUITABLE APPLICATIONS
• Water Based HVAC• Process Heating and Cooling• Thermal Energy Storage
• Hydronic Heating Systems• Fire Sprinkler Systems• Solar Heating
PROPERTIES
Reserve Alkalinity
Specific Gravity @ 60˚F
Boiling Point, Reflux
pH 50/50 Solution
Total Water & Inhibitors
Total Glycols
TYPICAL VALUES
11.0 mL min.
1.125 - 1.135
317˚F
9.0 - 9.6
4%
96%
ASTM TEST METHOD
D-1121
D-1122
D-1120
D-1287
D-1123
E-202
Technical Data Sheet
Ethylene Glycol
Inhibited Ethylene Glycol-based Heat Transfer FluidThermal Charge EG heat transfer �uid is formulated of 96% weight percent ethylene glycol and has a specially designed package of industrial corrosion inhibitors. The �uid is dyed �uorescent pink to aid in leak detection.Thermal Charge EG provides freeze protection to -60˚F (-50˚C) and burst protection to -100˚F (-73˚C).
Recommended use temperature range: -60˚F (-50˚C) to 250˚F (120˚C)
11110
THERMAL CHARGE EG FLUID % VOLUME REQUIRED
For Freeze Protection
17%26%35%41%46%50%55%59%63%
For Burst Protection
12%18%23%27%
31.4%31.4%31.4%31.4%31.4%
-7-12-18-23-29-34-40-46-51
20100
-10-20-30-40-50-60
Temperature(F°) (C°)
To order, please call Old World Industries, Inc.Customer Service at 1-800-323-8755.Thermal Charge™ is a trademark of
Old World Industries, Inc. ©2010 All Rights ReservedOld World Industries, Inc. 4065
Commercial Ave. Northbrook, IL 60062-1851
CORROSION TEST RESULTS
MaterialTested
CopperStandard SolderBrassSteelCast IronCast Aluminum
ASTM D-1384Maximum Weight
Allowed
10 mg30 mg10 mg10 mg10 mg30 mg
Heat Transfer
Fluid Results
2 mg 1 mg 2 mg3 mg 0 mg2 mg