*23558857_0717*Drive Technology \ Drive Automation \ System Integration \ Services
Revision
Drive System for Decentralized InstallationFieldbus Interfaces, Field Distributors
Edition 07/2017 23558857/EN
SEW-EURODRIVE—Driving the world
1Amendments/revisionsField distributor nameplate
Revision – Fieldbus Interfaces, Field Distributors 3
1 Amendments/revisionsThe following documentation is amended and revised.Observe the data specified in this revision. This document does not replace the de-tailed manual / compact manual.• "PROFIBUS Interfaces, Field Distributors" manual• "PROFINET IO Interfaces, Field Distributors" manual• "EtherNet/IP™ Interfaces, Field Distributors" manual• "EtherCAT® Interfaces, Field Distributors" manual• "INTERBUS Interfaces, Field Distributors" manual• "DeviceNet/CANopen Interfaces, Field Distributors" manual• "PROFIBUS Interfaces, Field Distributors" compact manual• "PROFINET IO Interfaces, Field Distributors" compact manual• "EtherNet/IP™ Interfaces, Field Distributors" compact manual• "EtherCAT® Interfaces, Field Distributors" compact manual• "INTERBUS Interfaces, Field Distributors" compact manual• "DeviceNet/CANopen Interfaces, Field Distributors" compact manual
1.1 Field distributor nameplateOrder-specific nameplate
The following figure shows an example of the order-specific nameplate of the MFE../MM../Z.8 field distributors:
P-Motor = 1,5kW95.7416041003.0001.17S0#:
0/ AGB1 IP65 ML 0001MFE52B/MM15D-503-00/Z28FType:
U= 3x380...500V I= 3,5A ACInput:
Made in GermanyFeldverteiler
Field Distributor
01UL®
LISTEDIND.CONT.EC
2D06
C US
General nameplate
The following figure shows an example of the general nameplate of the MFE../MM../Z.8 field distributors:
Input:
Input:
Output to next Field Distributor:
Output to drive:
3x200...500VU=30A ACImax= Imax=
3x200...500V
50...60Hz
U=
f=1,3...3,5A ACImax=
3x200...500VU=30A AC
3x0...Uinput
0,37...1,5kW
U=
P-Motor=1,6...4,0A ACImax=
The MF../Z.1 fieldbus interface does not have a general nameplate.
01
Only field distributors marked with the FS logo for functional safety may be installed insafety applications. For field distributors marked with the FS logo, the safety functionmust be described in the documentation.
2355
8857
/EN
– 0
7/20
17
1 Amendments/revisionsInstallation instructions for fieldbus interfaces, field distributors
Revision – Fieldbus Interfaces, Field Distributors4
1.2 Installation instructions for fieldbus interfaces, field distributors
1.2.1 Additional connection options with MFZ.6, MFZ.7 and MFZ.8 field distributors• The DC 24 V supply is connected with an X29 terminal block with two M4 x 12
studs and a pluggable X40 terminal.
1141387787
• The X29 terminal block can be used as an alternative to the X20 terminal (seechapter "Unit structure") for looping through the DC 24 V supply voltage. Bothstuds are connected internally to the 24 V connection at terminal X20.
Terminal assignmentNo. Name FunctionX29 1 24 V 0V24 reference potential for module electronics and sensors
(studs bridged with terminal X20/11)
2 GND 0V24 reference potential for module electronics and sensors (studs bridged with terminal X20/13)
• The plug-in terminal X40 ("Safety Power") is intended for the external DC 24 Vsupply of the MOVIMOT® inverter using a safety relay.This setup allows for operating a MOVIMOT® drive with FS marking in safety ap-plications. You find detailed information in the "MOVIMOT® MM..D – FunctionalSafety" manual.
Terminal assignmentNo. Name FunctionX40 1 24 V 24 V MOVIMOT® voltage supply for disconnection with safety
relay
2 GND 0V24 MOVIMOT® reference potential for disconnection withsafety relay
• Terminal X29/1 is factory-jumpered with X40/1 and terminal X29/2 with X40/2, sothat the MOVIMOT® inverter is supplied by the same DC 24 V voltage as the field-bus interface.
• The guide values for both studs are:– Current carrying capacity: 16 A– Permitted tightening torque for hex nuts: 1.2 Nm ± 20%.
• The guide values for the X40 screw terminal are:– Current carrying capacity: 10 A– Connection cross section: 0.25 mm2 – 2.5 mm2
– Permitted tightening torque: 0.6 Nm
2355
8857
/EN
– 0
7/20
17
2FunctionOperating notes
Revision – Fieldbus Interfaces, Field Distributors 5
2 Function2.1 Operating notes
WARNINGElectric shock caused by dangerous voltages at the connections, cables and motorterminals.When the device is switched on, dangerous voltages are present at the connectionsas well as at any connected cables and motor terminals. This also applies evenwhen the device is inhibited and the motor is at standstill.Severe or fatal injuries.• Do not switch under load.• Before performing any work on the device, disconnect it from the voltage supply.
Note that dangerous voltages can occur at the terminals and connections for upto 1 minute after the controller is switched off.
• Block the output stage of the inverter before switching at the output of the device.
WARNINGElectric shock from capacitors that have not been fully discharged.Severe or fatal injuries.• Disconnect the inverter from the power. Observe the minimum switch-off time
after disconnection from the supply system:– 1 minute
WARNINGRisk of crushing if the motor starts up unintentionally.Severe or fatal injuries• Observe the startup instructions.• Deactivate all control signals.
WARNINGDanger of burns due to hot surfaces of the device (e.g. the heat sink).Serious injuries.• Do not touch the device until it has cooled down sufficiently.
INFORMATION• The maximum output frequency in any operating mode is 120 Hz.• If the maximum output frequency is exceeded, the status LED of the MOVIMOT®
inverter flashes slowly red (error 08 "speed monitoring").
2355
8857
/EN
– 0
7/20
17
3 ServiceInspection and maintenance
Revision – Fieldbus Interfaces, Field Distributors6
3 Service
3.1 Inspection and maintenance3.1.1 MOVIMOT® inverter
The MOVIMOT® inverter is maintenance-free. SEW‑EURODRIVE does not prescribeany inspection or maintenance work for the MOVIMOT® inverter.Exception: For extended storage, refer to the instructions in the "Service" > "Extendedstorage" chapter.
3.1.2 MotorThe motor requires regular inspection and maintenance work.Observe the notes and instructions in chapter "Inspection/Maintenance" of the motoroperating instructions.
3.1.3 Gear units (only for MOVIMOT® gearmotors)The gear unit requires regular inspection and maintenance work.Observe the notes and instructions in chapter "Inspection/Maintenance" of the gearunit operating instructions.
3.1.4 RepairsOnly SEW-EURODRIVE is authorized to carry out repairs.
3.2 MOVIMOT® device replacementMOVIMOT®devicereplacement
INFORMATIONFor information on the device replacement of the MOVIMOT® inverter, refer to the"MOVIMOT® MM..D" operating instructions.
2355
8857
/EN
– 0
7/20
17
4Technical dataTechnical data of the fieldbus interface
Revision – Fieldbus Interfaces, Field Distributors 7
4 Technical data4.1 Technical data of the fieldbus interface4.1.1 MF../Z.1. connection module with fieldbus interface
MF../Z.1.Max. permitted total cur-rent
16 A
Ambient temperature -25 °C – 60 °C
Storage temperature -25 °C – 85 °C
Degree of protection IP65 (fieldbus interface and motor connection cable attached andfastened, all plug connections sealed)
Interface PROFIBUS, PROFINET IO, EtherNet/IP™, EtherCAT®, DeviceNet™
Permitted cable length between connection moduleand MOVIMOT®
max. 30 m
Mass Approx. 1.0 kg
4.2 Technical data for field distributors4.2.1 MF../Z.3. field distributors
MF../Z.3.Supply voltages Vline AC 3 x 380 V -10% – AC 500 V +10%
AC 3 x 200 V -10% – AC 240 V +10%
Line frequency fline 50 – 60 Hz
Max. permitted total cur-rent X1 (X1 terminal)
Imax 32 A (according to UL max. 30 A)
Max. permitted total currentX21 (X21 terminals)
32 A
Max. permitted total cur-rent X20 (X20 terminals)
12 A
Ambient temperature -25 °C – 60 °C
Storage temperature -25 °C – 85 °C
Degree of protection IP65 (fieldbus interface and motor connection cable attached andfastened, all plug connections sealed)
Interface PROFIBUS, PROFINET IO, EtherNet/IP™, EtherCAT®, DeviceNet™
Permitted motor cablelength
max. 30 m (with SEW‑EURODRIVE hybrid cable, type B) for cross section reduction compared to the supply system cable Note the line fusing.
Mass Approx. 1.3 kg2355
8857
/EN
– 0
7/20
17
4 Technical dataTechnical data for field distributors
Revision – Fieldbus Interfaces, Field Distributors8
4.2.2 MF../Z.6. field distributors
MF../Z.6.Connection voltages Vline AC 3 x 380 V -10% – AC 500 V +10%
AC 3 x 200 V -10% – AC 240 V +10%
Line frequency fline 50 – 60 Hz
Max. permitted total cur-rent X1 (X1 terminal)
Imax 32 A (according to UL max. 30 A)
Max. permitted total cur-rent X21 (X21 terminals)
32 A
Max. permitted total cur-rent X20 (X20 terminals)
12 A
Maintenance switch Load disconnector and line protectionType: ABB MS 325 – 9 + HK20Switching: black/red, triple lock
Ambient temperature -25 °C – 55 °C
Storage temperature -25 °C – 85 °C
Degree of protection IP65 (fieldbus interface, power supply connection cover and motor con-nection cable attached and fastened, all plug connections sealed)
Interface PROFIBUS, PROFINET IO, EtherNet/IP™, EtherCAT®, DeviceNet™
Permitted motor cablelength
max. 30 m (with SEW‑EURODRIVE hybrid cable, type B)
Mass Approx. 3.6 kg
2355
8857
/EN
– 0
7/20
17
4Technical dataTechnical data for field distributors
Revision – Fieldbus Interfaces, Field Distributors 9
4.2.3 MF../MM../Z.7. field distributors
MF../MM..-..3-00/Z.7.MOVIMOT® inverter MM
03DMM05D
MM07D
MM11D
MM15D
Connection voltages Vline AC 3 x 380 V -10% – AC 500 V +10%AC 3 x 200 V -10% – AC 240 V +10%
Line frequency fline 50 – 60 Hz
Max. permitted total cur-rent X1 (X1 terminal)
Imax 32 A (according to UL max. 30 A)
Motor power S1 PMot 0.37 kW0.5 HP
0.55 kW0.75 HP
0.75 kW1.0 HP
1.1 kW1.5 HP
1.5 kW2.0 HP
Nominal line current Iline
with Vline = AC 400 V AC 1.3 A AC 1.6 A AC 1.9 A AC 2.4 A AC 3.5 A
with Vline = AC 230 V AC 1.9 A AC 2.4 A AC 3.5 A - -
Nominal output current IN
with Vline = AC 400 V AC 1.6 A AC 2.0 A AC 2.5 A AC 3.2 A AC 4.0 A
with Vline = AC 230 V AC 2.5 A AC 3.2 A AC 4.0 A - -
Output voltage VO 0 – Vline
Max. permitted total cur-rent X21(X21 terminals)
32 A
Max. permitted total cur-rent X20(X20 terminals)
12 A
Ambient temperature -25 °C – 40 ˚C (PN reduction: 3% IN per K to max. 60 °C)
Storage temperature -25 °C – 85 °C
Degree of protection IP65 (fieldbus interface, power supply connection cover, MOVIMOT® in-verter and motor connection cable attached and fastened, all plug con-nections sealed)
Interface PROFIBUS, PROFINET IO, EtherNet/IP™, EtherCAT®, DeviceNet™
Permitted motor cablelength
15 m (with SEW‑EURODRIVE hybrid cable, type A)
Mass Approx. 3.6 kg
2355
8857
/EN
– 0
7/20
17
4 Technical dataTechnical data for field distributors
Revision – Fieldbus Interfaces, Field Distributors10
4.2.4 MF../MM../Z.8. field distributors with operating point 400 V/50 Hz
MF../MM..-503-00/Z.8.MOVIMOT® inverter MM
03DMM05D
MM07D
MM11D
MM15D
MM22D
MM30D
MM40D
Size 1 2 2LConnection voltages Vline AC 3 x 380 V -10% – AC 500 V +10%
Line frequency fline 50 – 60 Hz
Max. permitted total cur-rent X1 (X1 terminal)
Imax 32 A (according to UL max. 30 A)
Motor power S1 PMot 0.37 kW0.5 HP
0.55 kW0.75 HP
0.75 kW1.0 HP
1.1 kW1.5 HP
1.5 kW2.0 HP
2.2 kW3.0 HP
3.0 kW4.0 HP
4.0 kW5.4 HP
Nominal line current Iline AC1.3 A
AC1.6 A
AC1.9 A
AC2.4 A
AC3.5 A
AC5.0 A
AC6.7 A
AC7.3 A
Nominal output current IN AC1.6 A
AC2.0 A
AC2.5 A
AC3.2 A
AC4.0 A
AC5.5 A
AC7.3 A
AC8.7 A
Output voltage VO 0 – Vline
Max. permitted total cur-rent X21 (X21 terminals)
32 A
Max. permitted total cur-rent X20 (X20 terminals)
12 A
Maintenance switch Load disconnectorType: ABB OT16ET3HS3ST1Switching: black/red, triple lock
Ambient temperature -25 °C – 40 ˚C (PN reduction: 3% IN per K to max. 55 °C)
Storage temperature -25 °C – 85 °C
Degree of protection IP65 (fieldbus interface, power supply connection cover, MOVIMOT® in-verter and motor connection cable attached and fastened, all plug con-nections sealed)
Interface PROFIBUS, PROFINET IO, EtherNet/IP™, EtherCAT®, DeviceNet™
Permitted motor cablelength
15 m (with SEW‑EURODRIVE hybrid cable, type A)
Mass Approx. 5.2 kg Approx. 6.7 kg
2355
8857
/EN
– 0
7/20
17
4Technical dataTechnical data for field distributors
Revision – Fieldbus Interfaces, Field Distributors 11
4.2.5 MF../MM../Z.8. field distributors with operating point 230 V/60 Hz
MF../MM..-233-00/Z.8.MOVIMOT® inverter MM
03DMM05D
MM07D
MM11D
MM15D
MM22D
Size 1 2Connection voltages Vline AC 3 x 200 V -10% – AC 240 V +10%
Line frequency fline 50 – 60 Hz
Max. permitted total cur-rent X1 (X1 terminal)
Imax 32 A (according to UL max. 30 A)
Motor power S1 PMot 0.37 kW0.5 HP
0.55 kW0.75 HP
0.75 kW1.0 HP
1.1 kW1.5 HP
1.5 kW2.0 HP
2.2 kW3.0 HP
Nominal line current Iline AC 1.9 A AC 2.4 A AC 3.5 A AC 5.0 A AC 6.7 A AC 7.3 A
Nominal output current IN AC 2.5 A AC 3.2 A AC 4.0 A AC 5.5 A AC 7.3 A AC 8.7 A
Output voltage VO 0 – Vline
Max. permitted total cur-rent X21 (X21 terminals)
32 A
Max. permitted total cur-rent X20 (X20 terminals)
12 A
Maintenance switch Load disconnectorType: ABB OT16ET3HS3ST1Switching: black/red, triple lock
Ambient temperature -25 °C – 40 ˚C (PN reduction: 3% IN per K to max. 55 °C)
Storage temperature -25 °C – 85 °C
Degree of protection IP65 (fieldbus interface, power supply connection cover, MOVIMOT® in-verter and motor connection cable attached and fastened, all plug con-nections sealed)
Interface PROFIBUS, PROFINET IO, EtherNet/IP™, EtherCAT®, DeviceNet™
Permitted motor cablelength
15 m (with SEW‑EURODRIVE hybrid cable, type A)
Mass Approx. 5.2 kg Approx. 6.7 kg
2355
8857
/EN
– 0
7/20
17
4 Technical dataTechnical data for field distributors
Revision – Fieldbus Interfaces, Field Distributors12
4.2.6 MF../MM../Z.9. field distributors
MF../MM..-..3-00/Z.9.MOVIMOT® inverter MM
03DMM05D
MM07D
MM11D
MM15D
Connection voltages Vline AC 3 x 380 V -10% – AC 500 V +10%AC 3 x 200 V -10% – AC 240 V +10%
Line frequency fline 50 – 60 Hz
Max. permitted total cur-rent X1 (X1 terminal)
Imax 25 A (with derating 1.3% per K to max. 55 °C)
Motor power S11) PMot 0.37 kW0.5 HP
0.55 kW0.75 HP
0.75 kW1.0 HP
1.1 kW1.5 HP
1.5 kW2.0 HP
Nominal line current1) Iline
with Vline = AC 400 V AC 1.3 A AC 1.6 A AC 1.9 A AC 2.4 A AC 3.5 A
with Vline = AC 230 V AC 1.9 A AC 2.4 A AC 3.5 A - -
Nominal output current1) IN
with Vline = AC 400 V AC 1.6 A AC 2.0 A AC 2.5 A AC 3.2 A AC 4.0 A
with Vline = AC 230 V AC 2.5 A AC 3.2 A AC 4.0 A - -
Output voltage1) VO 0 – Vline
Max. permitted totalpower of all connected drives
3.3 kW with S1 operation4.5 kW with S3 operation (cyclic duration factor max. 75%)
Max. permitted total cur-rent X21 (X21 terminals)
8 A
Max. permitted terminalcurrent X20 (X20 termin-als)
1.5 A
Maintenance switch (op-tion)
Load disconnectorType: ABB OT16ET3HS3ST1Switching: black/red, triple lock
Ambient temperature -25 °C – 40 ˚C (PN reduction: 3% IN per K to max. 55 °C)
Storage temperature -25 °C – 85 °C
Degree of protection IP65 (fieldbus interface, cover plate, MOVIMOT® inverter and motorconnection cable attached and fastened, all plug connections sealed)
Interface PROFINET IO
Permitted motor cablelength
3 × 10 m (with SEW‑EURODRIVE hybrid cable, type A)
Mass Approx. 10 kg1) Technical data per drive
2355
8857
/EN
– 0
7/20
17
4Technical dataDimension drawings
Revision – Fieldbus Interfaces, Field Distributors 13
4.3 Dimension drawings
4.3.1 Dimension drawing of MF ..Z.1./MQ ../Z.1. fieldbus interfaceThe following figure shows the dimensions of the fieldbus interface MF ..Z.1./MQ ../Z.1.
40
6xM20x1.5
2xM12x1.5
25
76
102
115
Ø 4.4
66
.5
81
.5
10
6
82
.5
95
30
22
.5
25
10
MFE52, MFE62
MF.22/32, MQ.22/32, MFE72
MF.21, MQ.21
27021599179888907
2355
8857
/EN
– 0
7/20
17
4 Technical dataDimension drawings
Revision – Fieldbus Interfaces, Field Distributors14
4.3.2 MF../Z.3., MQ../Z.3. field distributors – dimension drawingThe following figure shows the dimensions of the field distributors MF../Z.3. and MQ../Z.3.:
121
58
10
0
12
4
83
5.5
6.5
17
5
100
5.5
19
0
13
7
93
.5
59
43.5
33.5
M16 x1.5
M25 x 1.5
M20 x1.5
40.5
MFE52, MFE62
MF.22/32, MQ.22/32, MFE72
MF.21, MQ.21
27021599245579275
2355
8857
/EN
– 0
7/20
17
4Technical dataDimension drawings
Revision – Fieldbus Interfaces, Field Distributors 15
4.3.3 MF../Z.6., MQ../Z.6. field distributors – dimension drawingThe following figure shows the dimensions of the field distributors MF../Z.6. and MQ../Z.6.:
78
14
3
15
0
28
44
44
44
50
44
16
9
20
6
M2
5 x
1.5
M2
0 x
1.5
55
29
36
5
36
5
39
8
7 7
33
49
180
194
MFE52, MFE62
MF.22/32, MQ.22/32, MFE72
MF.21, MQ.21
27021599246139275
2355
8857
/EN
– 0
7/20
17
4 Technical dataDimension drawings
Revision – Fieldbus Interfaces, Field Distributors16
4.3.4 Dimension drawing of field distributors MF../MM03 – MM15/Z.7., MQ../MM03 – MM15/Z.7.The following figure shows the dimensions of MF../MM03-MM15/Z.7., MQ../MM03-MM15/Z.7. field distributors:
253.7
326
6.5 6.5
63
.5
59
.5
81
12
2
48 35
35
35
171
200
35
14
6
10
5
MFE52, MFE62
MF.22/32, MQ.22/32, MFE72
MF.21, MQ.21 M25x1,5
M20x1,5
141
12
8
66
65
40
69
27021599304777355
2355
8857
/EN
– 0
7/20
17
4Technical dataDimension drawings
Revision – Fieldbus Interfaces, Field Distributors 17
4.3.5 Dimension drawing of field distributors MF../MM03 – MM15/Z.8., MQ../MM03 – MM15/Z.8.The following figure shows the dimensions of the field distributors MF../MM03 – MM15/Z.8., MQ../MM03 – MM15/Z.8.:
M25 x 1.5
29
66
97
119
223
2006.5
123
126
150
270
293
109
44
44
44
44
M20 x 1.5
50
34
30
56
30
8
29
0
MF
E5
2, M
FE
62
MF.2
2/3
2, M
Q.2
2/3
2, M
FE
72
MF.2
1, M
Q.2
1
27021599307058827
2355
8857
/EN
– 0
7/20
17
4 Technical dataDimension drawings
Revision – Fieldbus Interfaces, Field Distributors18
4.3.6 Dimension drawing of field distributors MF../MM22 – MM30/Z.8., MQ../MM22 – MM30/Z.8.The following figure shows the dimensions of the field distributors MF../MM22 – MM30/Z.8., MQ../MM22 – MM30/Z.8.:
36
73
126
443
9
M20x1.5M25x1.5
290
321
35
0
36
5
205
239
6.5
6.5
126
154
113
130
MF
.22
/32
, M
Q.2
2/3
2, M
FE
72
MF
E5
2, M
FE
52
MF
.21
, M
Q.2
1
35
61
56
104
44 44
44
27021599307060747
2355
8857
/EN
– 0
7/20
17
4Technical dataDimension drawings
Revision – Fieldbus Interfaces, Field Distributors 19
4.3.7 MF../MM40/Z.8., MQ../MM40/Z.8. field distributors – dimension drawingThe following figure shows the dimensions of the field distributors MF../MM40/Z.8.,MQ../MM40/Z.8.:
36
73
126
44
39
M20x1.5M25x1.5
290
321
35
0
36
5
205
239
6.5
6.5
126
154
113
130
MF
.22
/32
, M
Q.2
2/3
2, M
FE
72
MF
E5
2, M
FE
62
MF
.21
, M
Q.2
1
35
61
56
104
44 44
44
342
27021599449977355
2355
8857
/EN
– 0
7/20
17
4 Technical dataDimension drawings
Revision – Fieldbus Interfaces, Field Distributors20
4.3.8 Dimension drawing MF../MM03 – MM15/Z.9. field distributorsThe following figure shows the dimensions of the field distributors MF../MM03 –MM15/Z.9.:
X2
X13
X11 X12
X3
X14
X41 X42 X43
DI0
DI1
RUN
BUS-F
SYS-F
link/act1
link/act2MF
E52B
Eth
ern
et
DI2
DI3
DI4
DI5
DO0
DO1
X5
0
1 m
in
MO
VIM
OT
®
X5
0
1 m
in
MO
VIM
OT
®
X5
0
1 m
in
MO
VIM
OT
®
DI0
DI1
RUN
BUS-FS
SYS-F
link/act1
link/act2MF
E52 E
thern
et
DI2
DI3
DI4
DI5
DO0
DO1
121110987654321 121110987654321 121110987654321
15
2
59
10
7
23
541
140209 140
572
20
13
0
60282
6.5
8.2
14
5
11
507
102
66
31
88
18226804747 2355
8857
/EN
– 0
7/20
17
5Declaration of conformity
Revision – Fieldbus Interfaces, Field Distributors 21
5 Declaration of conformity
EU Declaration of ConformityTranslation of the original text 900030410/EN
SEW-EURODRIVE GmbH & Co. KGErnst-Blickle-Straße 42, D-76646 Bruchsaldeclares under sole responsibility that the following products
Bruchsal
a) Authorized representative for issuing this declaration on behalf of the manufacturerb) Authorized representative for compiling the technical documents
Place Date
20.07.2017
Managing Director TechnologyJohann Soder
a) b)
Frequency inverters of the product family MOVIMOT® MM..D-..3-..MOVIMOT® .../MM../...
in accordance with
Machinery Directive 2006/42/EC(L 157, 09.06.2006, 24-86)
This includes the fulfillment of the protection targets for "electrical power supply" in accordance with annex I No. 1.5.1according to the Low Voltage Directive 73/23/EEC -- Note: 2014/35/EU is currently valid.
EMC Directive 2014/30/EU 4)(L 96, March 29, 2014, 79-106)
RoHS Directive 2011/65/EU(L 174, July 1, 2011, 88-110)
Applied harmonized standards: EN ISO 13849-1:2008/AC:2009EN 61800-5-2:2007EN 61800-5-1:2007EN 61800-3:2004/A1:2012EN 50581:2012
4) According to the EMC Directive, the listed products are not independently operable products. EMC assessment is only possibleafter these products have been integrated in an overall system. For the assessment, the product was installed in a typical plantconfiguration.
2355
8857
/EN
– 0
7/20
17
5 Declaration of conformity
Revision – Fieldbus Interfaces, Field Distributors22
EU Declaration of ConformityTranslation of the original text 900040410/EN
SEW-EURODRIVE GmbH & Co. KGErnst-Blickle-Straße 42, D-76646 Bruchsaldeclares under sole responsibility that the following products
Bruchsal
a) Authorized representative for issuing this declaration on behalf of the manufacturerb) Authorized representative for compiling the technical documents
Place Date
19.06.2017
Managing Director TechnologyJohann Soder
a) b)
Field distributors of the series MF../Z.3.MQ../Z.3.MF../Z.6.MQ../Z.6.MF../Z.7.MQ../Z.7.MF../Z.8.MQ../Z.8.MF../Z.9.
in accordance with
Low Voltage Directive 2014/35/EU(L 96, March 29, 2014, 357-374)
EMC Directive 2014/30/EU 4)(L 96, March 29, 2014, 79-106)
RoHS Directive 2011/65/EU(L 174, July 1, 2011, 88-110)
Applied harmonized standards: EN 50178:1997EN 61800-3:2004/A1:2012EN 50581:2012
4) According to the EMC Directive, the listed products are not independently operable products. EMC assessment is only possibleafter these products have been integrated in an overall system. For the assessment, the product was installed in a typical plantconfiguration.
2355
8857
/EN
– 0
7/20
17
SEW-EURODRIVE—Driving the world
SEW-EURODRIVE GmbH & Co KGP.O. Box 302376642 BRUCHSALGERMANYPhone +49 7251 75-0Fax +49 7251 [email protected]