+ All Categories
Home > Documents > Final Presentation- Heat Exchange

Final Presentation- Heat Exchange

Date post: 22-Jan-2018
Category:
Upload: colin-hannahan
View: 132 times
Download: 6 times
Share this document with a friend
25
Heat Exchange “The Alphabet Boys” Group K1 Colin Hannahan, Nerses Haroutunian, Jon Gigas, Adam Haidari 1
Transcript
Page 1: Final Presentation- Heat Exchange

Heat Exchange“The Alphabet Boys” Group K1

Colin Hannahan, Nerses Haroutunian, Jon Gigas, Adam Haidari

1

Page 2: Final Presentation- Heat Exchange

Table of ContentsCalibration of flow rates with pneumatic valves………………………….……...3

Heat transfer coefficients compared with Reynolds # …………….……….….11

Heat Loss and Fouling Analysis ….………………………………………..……18

Conclusions and recommendations…………………………………..…………22

2

Page 3: Final Presentation- Heat Exchange

Calibrating Flow

3

Page 4: Final Presentation- Heat Exchange

Pneumatic valve setting corresponds to pressure (psig)

Measure flows by measuring mass of water over a given time (lbs/sec)

Calibrating Flowrates: Methods

4

Figure 1. A fully closed pneumatic valve. Figure 2. A partially opened pneumatic valve.

Page 5: Final Presentation- Heat Exchange

Calibrating Flowrates: Methods

5

Valves

Calibrating Operation Mode Steam Cooling Water

Process Water

Cooling Water Co-Current Closed Variable Constant

Cooling Water Counter-Current Closed Variable Constant

Process Water Counter-Current Closed Constant Variable

Figure 3. LabView dials for pneumatic valve of process and cooling waters.

Figure 4. View of apparatus outlining direction of flows.

Page 6: Final Presentation- Heat Exchange

Calibrating Flowrates: Calibration Curves

6Figure 5. Calibration curve for cooling water in co-current operation.

Page 7: Final Presentation- Heat Exchange

Calibrating Flowrates: Calibration Curves

7

Figure 6. Calibration curve for cooling water in counter-current operation.

Page 8: Final Presentation- Heat Exchange

Calibrating Flowrates: Calibration Curves

8Figure 7. Calibration curve for process water, independent of operation mode.

Page 9: Final Presentation- Heat Exchange

Flowmeter Error AnalysisFlowmeter readings were compared to values from valve correlation on all data logs.

Figure 8. Flowmeter error of process water at various flowrates. Figure 9. Flowmeter error of cooling water at various flowrates. 9

Page 10: Final Presentation- Heat Exchange

Calibrating Flowrates: Suggestions1. Cooling water flowrate undetermined under 6 psig.

2. First open each valve fully, then reduce to setpoint.

3. Redundancy moving between different operating method.

10

Page 11: Final Presentation- Heat Exchange

Calculating Heat Transfer Coefficients

11

ho and hi

Page 12: Final Presentation- Heat Exchange

12

ho and hi

Figure 10. Cooling-process water heat exchanger

Figure 11. Steam heat exchanger.

Page 13: Final Presentation- Heat Exchange

hi vs Reynolds Number

13

Figure 12. Comparing calculated Reynolds number to heat transfer coefficient for process water

Source: Bergman et al. (2007)

Page 14: Final Presentation- Heat Exchange

ho vs Reynolds Number

14Figure 13. Comparing calculated Reynolds number to heat transfer coefficient for cooling water in co-current operation mode.

Source: Bergman et al. (2007)

Page 15: Final Presentation- Heat Exchange

ho vs Reynolds Number

15Figure 14. Comparing calculated Reynolds number to heat transfer coefficient for cooling water in counter-current operation mode.

Source: Bergman et al. (2007)

ho,steam=11.7 kW/(m^2*s)

Page 16: Final Presentation- Heat Exchange

Reynolds Number Calculation

16

Figure 15. Kinematic viscosity of water decreases with increasing temperature.

Page 17: Final Presentation- Heat Exchange

Calculating hi, ho

17

Page 18: Final Presentation- Heat Exchange

Heat Loss and Fouling Analysis

18

Page 19: Final Presentation- Heat Exchange

Heat Loss: Methodology● Adjusted valve W2 to maintain constant liquid level in the sight glass

● Measured condensate flowrate and performed energy balance on the overall system

Balance:

19

Page 20: Final Presentation- Heat Exchange

Heat Loss: Results● Average total heat loss: 4.3 kW

● Average loss as a percentage of total heat transferred from steam: 9.9%

● Most loss likely due to radiation from steam piping.

20

Page 21: Final Presentation- Heat Exchange

Fouling Analysis● Observed rust in cooling water stream, but not in process water steam

● Significantly higher values of hi vs ho for cooling water at the same

Reynolds number

● Assumed differences due to fouling on outer surface of pipe

21

Page 22: Final Presentation- Heat Exchange

Conclusions● Flowrate valve correlations were developed based on pneumatic valve pressure

○ Flowrate range (0.2 - 1.35 lbs/sec)

● h vs Reynolds number consistent with correlation

● Fouling in cooling water heat exchanger

● Overall heat loss: 4 kW

○ ~ 10 % of total heat transferred

22

Page 23: Final Presentation- Heat Exchange

Recommendations● Valve C7 is very sticky

● Low cooling water valve settings are inaccurate

● Open valves fully (17 psig) to start before adjusting to desired flow

● Ensure that no steam flows out of apparatus

23

Page 24: Final Presentation- Heat Exchange

ReferencesDelta T Heat Exchangers. Fouling in Heat Exchangers. http://deltathx.com/uploadsdocs/foulingfactors.pdf (accessed October 4, 2015).

Engel, Y. A.; Boles, M. A. Thermodynamics: An Engineering Approach; Seventh.; McGraw-Hill: New York, NY, 2011; pp. 868–870.

Kestin, Joseph; Sokolov, Mordechai; Wakeham, William A. Viscosity of Liquid Water in the Range -8 °C to 150 °C. Journal of Physical and Chemical Reference Data. 1978, 7, 941-948.

Pipe and Hose. American National Pipe - NPT/NPS | Pipe and Hose. http://pipeandhouse.com/node/19 (accessed October 4, 2015).

24

Page 25: Final Presentation- Heat Exchange

Process Flow Diagram

25


Recommended