Download: | 4 times |
Fire Protection Products
KBS Cable Coating 3
KBS Panel Seal 9
KBS Sealant 9
KBS Mortar Seal 15
KBS Sealbags 19
Flamro Caulking 24
Ruetgers Steel Coating 25
Fire Protection Product Range
Product Code Product Name Qty
KBS48679 KBS Cable Coating – 35kg Sprayable1 Drum
24 Drums96 Drums
KBS5001784 KBS Cable Coating – 7kg Brushable1 Drum
76 Drums304 Drums
KBS67387 KBS Mortar Seal 25kg1 Bag
40 Bags160 Bags
KBSSSCP KBS Single Sided Coated Panels 1 Panel
KBSDSCP KBS Double Sided Coated Panels 1 Panel
KBS48709 KBS Sealbags 250gm20 Bags
1200 Bags4800 Bags
KBS48711 KBS Sealbags 400gm35 Bags
1050 Bags4200 Bags
KBS48707 KBS Sealbags 720gm20 Bags
600 Bags2400 Bags
KBS48705 KBS Sealbags 1500gm 10 Bags
KBS48676 Sealant Cartidges120 Cartridges600 Cartridges
2400 Cartridges
FLR30004 Flamro BMK FR Caulking 20 Cartridges
PYRO-ST100 Pyroplast-ST100 Steel Coating 1 Drum
Fire protective coatingfor electrical cablesand penetration seals
KBS® Coating
General Information
KBS® Coating is a water-based, ablative fi re protective coating, especially developed for the fi re protection of grouped or bundled electrical cables and for penetration seals.
The main function of KBS® Coating is to prevent fl ame propa-gation along vertical and horizontal cable ways. KBS® Coating will also delay short circuit, whereby circuit integrity depends on the distance of the cables from fi re and the incurred temperature. KBS® Coating is easily applied by conventional methods such as spray and brush, as well as by hand (see application data). KBS® Coating is also available free of halogens – named KBS® Coating CLF.
KBS® Coating has been tested to all recognized international standards and is used worldwide, from the arctic circle to the tropics. Its effectiveness has been proven in several documented cases of actual fi res. KBS® Coating is produced only by BASF in Illertissen where a quality system fulfi lling the requirements of DIN EN ISO 9001 and DIN EN ISO 14001 has been in place for more than a decade.
KBS® Coating is also an integral part of the cable penetration seal KBS® Panel Seal ABL. Here it is used as a coating for the mineral wool panels, the sealing of the penetrating cables and other utilities. For use of KBS® Coating in the installation of KBS® Panel Seal ABL please refer to our separate brochure.
How does an ablative coating work?
KBS® Coating protects electrical cables through ablation as opposed to intumescence. Energy is consumed or generated to change any material from one condition or state to another.
Processes consuming energy are called “endothermic”. Some materials need large amounts of energy to decompose or “break down”. A good ablative composition requires a maximum of ener-gy to decompose. KBS® Coating when exposed to fi re starts to ablate by chemical and physical reactions, for instance evaporati-on, chemical cracking, melting - all this is consuming energy (heat) while keeping the cable relatively cool (for a certain space of time, as the process is self-sacrifi cial).
The gases and vapours generated during the ablative process push oxygen away from the surface, dilute fl ammable gases preventing them from burning and interrupt the ”chain reaction” of fi re chemically. After decomposition of all organic components, a solid structure of inorganic components remains offering further protection by insulation.
KBS® Coating...... lasts for the lifetime of cables... does not derate electrical cables... is totally weather and water resistant
KBS® Coatingprevents fl ame propagation along cable ways
Special FeaturesFire protection
KBS® Coating prevents flame propagation on cables, thus keeping a cable fire localized to its source, where, however, some minor damage to the most exposed cables must be accepted.
According to bibliographical references, a fire on vertical cable ways can spread 20 m per minute. Flame spread on KBS®-coa-ted vertical cables in the 40-minute IEC 60332-3 test has been restricted to less then 10 cm (see list of international test results).
KBS® Coating has an LOI (Limiting Oxygen Index) value of 100.
What is an LOI value of 100 ?The Limiting Oxygen Index value test, in accordance with ASTM D 2863, determines the percentage of oxygen in a nitrogen/oxygen mixture at which a material sustains burning on its own. In this test, which determines the burning characteristics of all plastic materials, the sample is secured in a glass cylinder – containing a definite gas flow of O2/N2 mixture – and ignited with a gas flame. Then the gas flame is removed and the sample is observed for continued burning. Soft PVC, as used for cable jackets, continu-es to burn at a low 25 – 30% oxygen content. Teflon, however, sustains burning only at a high 90 - 95% oxygen content.
KBS® Coating has an LOI of 100, which means, it does not even burn in a 100% oxygen environment.
AmpacityKBS® Coating does not affect the current carrying capacity of electrical cables. The FM test states “no derating required” (see list on page 5).
Why no derating when cables are coated with KBS® Coating?KBS® Coating protects electrical cables through ablation and not through insulation. It is dense and thermally conductive during normal cable operating temperatures. Its thermal conductivity is better than that of PVC. The coating increases the circumference (= surface) of the cable or cable bundle. The surficial area is further enlarged by the roughness of the coat (radiator effect). This exten-ded surface allows more heat to dissipate. The cable temperature, therefore, does not increase.
Prevention of poisonous and corrosive gases and smokeBy preventing the fire from spreading and eventually involving all cables, KBS® Coating also prevents the development of the dreaded HCl (hydrochloric acid) from PVC cables as well as the dense black smoke and poisonous gases developing from all types of cables.
Mechanical resistanceKBS® Coating is tough enough to sustain physical abuse such as walking on coated cable trays.
Human health compatibilityKBS® Coating is in no way affecting the human health system, it is non-toxic, solvent-free, phosphate-free and does not contain asbestos or any other substance identified as being cancerogenic. KBS® Coating is practically odourless and does not affect the human skin.
Weather and water resistanceKBS® Coating is permanent protection under all weather and climatic conditions. A 30 years outdoor test, documented by the Institute for Fire Protection of TU Brunswick/Germany, found KBS® Coating still performing the same as freshly produced material. Here cables had been exposed from highest summer heat to snow and ice in winter, part of their length being constantly immersed in water.
Chemical compatibilityKBS® Coating has been tested for compatibility with close to 90 chemicals and has been found to be unaffected by those most frequently found in industrial installations such as Diesel fuel, ethy-lene glycol, fuel oil, lubricating oil, turbine oil and many others.
FlexibilityKBS® Coating is highly flexible (see technical data).
Endurance / lifetimeKBS® Coating lasts for the lifetime of cables.
KBS® Coatinglasts for thelifetime of cables
Application on cables
Surface preparationExtensive cleaning of cables is not required. However, oil or grea-se should be taken up with dry rags (no solvent). Using a broom or vacuum cleaner to remove heavy layers of dust is sufficient.
Spray ApplicationThis is performed in the conventional way by spraying crosswise. On all exposed surfaces the wet thickness of the coating must be at least 2.5 mm. The use of an extension nozzle is recom-mended when full coating is required in areas with limited acces-sibility. If cables are situated close to a wall, the cavity between cables and wall is stuffed with mineral wool and then coated over. Usually the required thickness may be applied in one coat. However, if new vertically mounted cables are to be coated, it is recommended that a thin “fog-coat” should be applied first, let dry and the final coat be applied thereafter.
Application by HandSingle large diameter cables or bundles may be coated by hand. Again, a thin coat should be allowed to dry before the rest is applied, using both hands (wear rubber gloves) like an extruder. To achieve a smooth, even finish, use a wet brush.
Recommended coating thickness on cables:Wet approx. 2.5 mm – resulting in approx. 1.6 mm dry coating
Coverage at recommended thickness:Approx. 3.0 kg/m2 for level surface. For grouped cables or cables in trays allow 30% more material considering the curved surfaces.
Technical Data
Composition:KBS® Coating consists of water-based thermoplastic resins, inorganic incombus-tible fibres, fillers, pigments and various flame retardant chemicals. KBS® Coating is free of asbestos and solvents.
Colour: Off-white
Viscosity: Approx. 40,000 mPas
Density: Approx. 1.43 g/cm3
pH-value: Approx. 8.0
Application on mineral wool panels
This substrate can be coated either by spraying or by hand, using a trowel. When preferring the latter application techni-que, use a large steel trowel, such as employed for leveling out concrete surfaces. For the KBS® Panel Seal ABL an applica-tion rate of approximately 3.0 kg/m2 will result in the required dry thickness of approx. 1.6 mm.
KBS® Coating is available in two kinds of make-up.KBS® Coating sprayable and KBS® Coating Brushable.
ThinningKBS® Coating is water-based. However, both types mentio-ned before, usually do not require thinning.
Spray equipmentKBS® Coating may be applied with a large variety of spray equipment designed for application of high viscosity materials. Good results have been obtained with the following:
Airless spray equipmentGraco Smart Mark VPressure at gun: 0 – 200 barSpray gun orifice: 0.9 – 1.0 mm(preferably reversible tip)
Please noteAir supply, air pressure, diameter of material hose as well as minimum orifice opening must be adhered to as recommen-ded. All filters with the equipment must be removed prior to operating with KBS® Coating.
Solids: Approx. 70%
Limiting Oxygen Index (LOI): ≥ 95(minimum requirement acc.to German approval)
Toxicity: Non-toxic
Storage temperature: 5 – 30°C, Must be protected from frost !
Shelf-life:In closed original containers at room temperature at least 18 months
Packaging:Plastic drums of 35, pails of 25 and 7 kg
Thinning i.e. cleaning of equipment: Water
Drying time:Depending on temperature and humidityTo the touch: within 24 hours (20°C/65% RH)Cured: approx. 3 days (20°C/65% RH)
Flexibility:PVC cables of 12 mm diameter coated with KBS® Coating may be bent to a 3 cm radius without cracking.
Thermal conductivity:λ = 0.69 W m-1 · K-1 at 25°C
Specific resistance:ρp = 1.06 ·109 (Ohm · cm) at 23°C / 50% RHρp = 4.10 · 105 (Ohm · cm) at 23°C / 83% RH
CountryGermany
Great Britain
Norway
USA
Type of TestQualifying test concerning reduction of fire risks
Current carrying capacity
Dermatology test
Flame propagation on coated cables
Flame propagation on coated cables
Flame propagation on coated cables
Flame propagation TÜV Nord
Circuit Integrity
Ship Approval Germanischer Lloyd
Ageing and weathering
LOI-determination
Flame spread
Fire spread
Ampacity
Current carrying capacity
Salt water exposure
Dielectric strength
Flammability test
FM approval
Standard-
-
-
DIN 4102, p. 1 (B1)
IEC 60332-3
IEC 60332-3-22
category A/F
IMO FTPC, p. 5
IEC 60331-11
IMO Res. MSC. 61 (67)
-
ASTM D2863
BS 476, p. 7
NT Fire 004
FM 3971
FM 3971
FM 3971
FM 3971
FM 3971
FM 3971
Resultignition prevented
no derating
no effect
passed
non-propagating
passed
non-propagating
52 minutes
passed
no damage after 30 years
100
class 1
Class IN 1
-
no derating
-
-
passed
-
Ref.No.008
106B
110A / 110B
169
148
053
047
052
060
180
111 / 180
916 A
710
2001
2001
2001
2001 / 2023
2001 / 2023
2001 / 2023
Selection of International Test Results and Approvals
BASF Personal Care and Nutrition GmbHRobert-Hansen-Straße 189257 Illertissen (Germany)Tel.: +49 (73 03) 13 - 297Fax: +49 (73 03) 13 - 209
[All products in the text marked with an ® are trademarks of the BASF Group.]
This document, or any answers or information provided herein by BASF, does not constitute a legally binding obligation of BASF. While the descripti-ons, designs, data and information contained herein are presented in good faith and believed to be accurate, it is provided for your guidance only. Because many factors may affect processing or application/use, we recom-mend that you make tests to determine the suitability of a product for your particular purpose prior to use. It does not relieve our customers from the obligation to perform a full inspection of the products upon delivery or any other obligation. The claims and supporting data provided in this publica-tion have not been evaluated for compliance with any jurisdiction’s regula-tory requirements and the results reported may not be generally true under other conditions or in other matrices. Users must evaluate what claims and information are appropriate and comply with a jurisdiction’s regulatory requirements. NO WARRANTIES OF ANY KIND, EITHER EXPRESS OR IMP-LIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, ARE MADE REGARDING PRODUCTS DESCRIBED OR DESIGNS, DATA OR INFORMATION SET FORTH, OR THAT THE PRODUCTS, DESIGNS, DATA OR INFORMATION MAY BE USED WITHOUT INFRINGING THE INTELLECTUAL PROPERTY RIGHTS OF OTHERS. IN NO CASE SHALL THE DESCRIPTIONS, INFORMATION, DATA OR DESIGNS PROVIDED BE CONSIDE-RED A PART OF OUR TERMS AND CONDITIONS OF SALE.
Antec Engineering Pty Limited
9 Chicago AvenueBLACKTOWN NSW 2148Australia
Ph: +61 2 9622 9622Fax: +61 2 9622 9199Email: [email protected]
www.antec.com.au
Distributed in Australia by
Solutions for the Mining, Minerals Processing& Infrastructure Industries
Single and doublepanel penetration sealsfor cables
KBS® Panel Seal ABL
General Information
The KBS® Panel Seal ABL consists of mineral wool panels coated with KBS® Coating, KBS® Sealant to fill gaps and KBS® Coating to coat the penetrating cables and support systems.
Only the visible sides of the panels and penetrating items have to be coated with KBS® Coating.
KBS® Panel Seal ABL can be installed as a single or double panel seal, depending on the required fire resistance time.
KBS® Coating is a water-based ablative fire protective coating, KBS® Sealant is a water-based ablative fire protective putty. KBS® Coating is suitable for penetration seals and fire protection of cables or other utilities.
Both products last for the lifetime of cables. KBS® Coating is highly flexible, totally weather- and water-resistant, and compatible with various chemicals.
Any mineral wool panels with a minimum density of 150 kg/m3
and a melting point above 1000°C can be used for KBS® Panel Seal ABL. If not available on the local market, they can be sup-plied by our distributor.
KBS® Coating and KBS® Sealant are produced only by BASF in Illertissen maintaining a quality system which fulfils the require-ments of DIN EN ISO 9001 and DIN EN ISO 14001.
KBS® Panel Seal ABL is used to seal any size of opening in walls and floors
Technical Information
The KBS® Panel Seal ABL is used to seal any size of opening in walls and floors, providing a fire- and smoke- tight seal around all penetrating utilities such as cables, cable supports, pipes and ducts.KBS® Panel Seals ABL have been tested and approved world-wide and have received various ratings depending on type and national standard. (Please see list of international test reports/ap-provals on back page). Please note the following results:
Single Panel Seal (panel thickness 50-60 mm): Rated up to 120 min.
Double Panel Seal:Rated up to 180 min.
Panels are usually coated with KBS® Coating at a coverage of approx. 2.0 kg/m2 on the exposed (visible) side only, resulting in approx. 1.3 mm dry thickness. This means the same amount of coating is used per opening, independent whether it is a single or double panel seal. Panels may be precoated or coated on site by spray or brush. Precoated panels are also available from our distributor.The double panel seal usually is constructed with an air space between the two panels. Preferably the panels are installed flush with the outside of the wall. Cables and other penetrating items are coated with KBS® Coa-ting at a coverage rate of approx. 3.0 kg/m2, corresponding to approx. 1.6 mm dry thickness.
In all KBS® Panel Seals ABL, it is required that only the exposed (visible) penetrating items (cables, support systems, pipes, etc.) must be coated with KBS® Coating for a distance away from the seal. This distance is specified in national tests and differs from country to country according to respective requirements.
Retrofitting of additional utilities is achieved with ease in a KBS® Panel Seal ABL. The opening for the penetrating item is cut as accurately as possible with a pointed saw or a saw-tooth knife and sealed after installation of the utilities with KBS® Sealant. Where the opening has been cut larger than the penetrating item, loose mineral wool should be stuffed tightly in the remaining space before applying KBS® Sealant.
1. 5.2. 6.3. 7.4. 8.
Measure exact location on cables and cable supports, using a meter stick, a mason’s compass or a piece of string with which you can locate cables by measuring from the corners.
Transfer measurements onto mineral wool panel, but add about 3 mm on height and width of panel cut (this will result in a tighter fit). Now cut panel into as many pieces as necessary to fit in the opening.
Check cut by placing the panel pieces into the opening and make necessary correc-tions.
Apply KBS® Coating to the edges of the panels as well as to the insides of the opening where panels will be fitted. Prior to coating application all areas to be coated have to be cleared of dust, additionally the surface of the building section should be wetted with water.
After panel is in place, check carefully for possible openings, stuffing them with loose mineral wool. Apply KBS® Coating or KBS® Sealant covering carefully spots stuffed with loose wool, also use KBS® Coating or KBS® Sealant liberally between cables and other spots which may allow leakage of fumes and smoke.
Use masking tape to keep cables and surrounding area on wall or ceiling clean.
Now apply KBS® Coating by spray or brush, first to panels, then to cables and support systems to distance required by national tests. Coat wall about 2 cm over edge of opening.
Attention: If walking on a floor penetration is not possible to prevent this, use any suitable cover.
Place one edge of panel first in the opening completely and push it slowly into opening. Since the panel has been cut oversize, a piece of wood and a hammer will be necessary to get panel in place. If panel is loose in the opening, it should be discarded and replaced by a new one.
Installation Instructions
Country
Austria
Belgium
France
Germany
Great Britain
Italy
Netherlands
Singapore
South Africa
Sweden
Switzerland
USA
KBS Penetration Method*
single panel
double panel
single panel
double panel
double panel
double panel
double panel
single panel
double panel
double panel
double panel
double panel
double panel
single panel
double panel
single panel
single panel
double panel
double panel
single panel
single panel
double panel
double panel
double panel
single panel
double panel
single panel
single panel
double panel
double panel
double panel
Ceiling or Wall Test
ceiling
wall
wall
wall
wall
ceiling
steel bulkhead
wall
wall
ceiling
wall
wall
ceiling
wall / ceiling
wall / ceiling
wall
wall
wall
ceiling
wall
wall
wall
wall / ceiling
wall
wall / ceiling
wall / ceiling
wall
ceiling
wall
ceiling
wall / ceiling
Thickness of penetration[mm]
Official Fire ResistanceF/T Rating[minutes]
Standard
ÖNORM B 3800
ÖNORM B 3800
NBN 713.020
NBN 713.020
Arrêté du 21.4.83
Arrêté du 5.1.59
SOLAS 197/IMO A 517
DIN 4102
DIN 4102
DIN 4102
DIN 4102
DIN 4102
DIN 4102
BS 476, p. 8
BS 476, p. 8
BS 476, p. 20
Circolare M No. 91
Circolare M No. 91
Circolare n. 91
NBN 713.020 /
prEN 1366-3
NBN 713.020 /
prEN 1366-3
NBN 713.020 /
prEN 1366-3
BS 476, p. 20
SABS 0177
NT-FIRE 005
NT-FIRE 005
VKF, AEAI
VKF, AEAI
VKF, AEAI
VKF, AEAI
ASTM E 814
Ref. No.
213
210
314 A
313
610
602
620/621
183
049
049
112
112
112
904
904
943
1011
1011
1012
411
411
411
3206
4005
817
817
531
531
510
510
2020
Selection of International Test Results and Approvals
60
150
50
150
200
200
2 x 75
60
120
150
150
200
150
50
150
60
60
250
200
50
50
140
150
100
60
140
60
60
120
150
150
60
90
90
120
120
120
60
30
90
90
90
90
90
90
180
90
120
180
180
60
90
90
180
120
60
120
60
60
90
90
120
BASF Personal Care and Nutrition GmbHRobert-Hansen-Straße 189257 Illertissen (Germany)Tel.: +49 (73 03) 13 - 297Fax: +49 (73 03) 13 - 209
[All products in the text marked with an ® are trademarks of the BASF Group.]
This document, or any answers or information provided herein by BASF, does not constitute a legally binding obligation of BASF. While the descripti-ons, designs, data and information contained herein are presented in good faith and believed to be accurate, it is provided for your guidance only. Because many factors may affect processing or application/use, we recom-mend that you make tests to determine the suitability of a product for your particular purpose prior to use. It does not relieve our customers from the obligation to perform a full inspection of the products upon delivery or any other obligation. The claims and supporting data provided in this publica-tion have not been evaluated for compliance with any jurisdiction’s regula-tory requirements and the results reported may not be generally true under other conditions or in other matrices. Users must evaluate what claims and information are appropriate and comply with a jurisdiction’s regulatory requirements. NO WARRANTIES OF ANY KIND, EITHER EXPRESS OR IMP-LIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, ARE MADE REGARDING PRODUCTS DESCRIBED OR DESIGNS, DATA OR INFORMATION SET FORTH, OR THAT THE PRODUCTS, DESIGNS, DATA OR INFORMATION MAY BE USED WITHOUT INFRINGING THE INTELLECTUAL PROPERTY RIGHTS OF OTHERS. IN NO CASE SHALL THE DESCRIPTIONS, INFORMATION, DATA OR DESIGNS PROVIDED BE CONSIDE-RED A PART OF OUR TERMS AND CONDITIONS OF SALE.
Antec Engineering Pty Limited
9 Chicago AvenueBLACKTOWN NSW 2148Australia
Ph: +61 2 9622 9622Fax: +61 2 9622 9199Email: [email protected]
www.antec.com.au
Distributed in Australia by
Solutions for the Mining, Minerals Processing& Infrastructure Industries
BMK FR Caulking
FLAMRO BMK is specially designed to seal smallholes in walls and floors against fire.
FLAMRO BMK consists of non-toxic pigments, fireand energy absorbing fillers, inorganic and organicfibres and flame retardant radical binders that have aflame retardant effect.
Code: FLR30004
Object Description
Binding agent Special dispersion – solvent less
Pigments / fillers Not combustible and flame retardant pigments and fillers
pH-value Approx. 8
Viscosity Paste like
Flash point: None
Shelf-life Sealed in original containers at room temperature at least 1 year
Thinner Clean water, maximum 5 weight percent
Tool cleaning Clean with water immediately after use
Consumption Approx. 2.05kg / m2 for a dry film thickness of 1mm
Drying time Through-drying – depending on room temperature, air humidity and on coating thickness: 1-3 days
Surface Surfaces must be stable, clean and free of grease and dust; steel and iron parts should be protected against corrosion in case of outdoor applications or in areas where condensed water may be developed
Moisture-sensitivity FLAMRO BMK coatings are no susceptible to moisture and can also be used for outdoor applications
Temperature-sensitivity
The applied coating compound withstands temperatures from -40oC to +80oC, there is neither chemical breakdown, discolouration nor a deterioration in it efficacy
ST100 Water Based Intumescent Steel Coating
The new Pyroplast ST100 is a waterborne intumescent coating for fire protection of internal structural steelwork (columns, beams, framework) designed to protect life & assets.
Offers F30 to F90 fire protection provisions with a single system.
STANDARD FEATURES
• Small layer thicknesses (applies to F30-F90)
• Only 3-4 operations for coating F90 = lower costs for application
• Water based system enables parallel work and less protection measures
• Significant cost advantages for handling, transport and storage
• Primer and top coats also available
THE INTUMESCENT ADVANTAGE
• Lightweight, small layer thicknesses
• Easy and Fast application
• Does not affect other trades on site
• Dust free, smooth finish is ideal for visible sections – intumescent paints keep the original structure & appearance
• Easy to maintain
• Can be applied offsite and transported to site
• Technical support and training
ST100 Water Based Intumescent Steel Coating
ABOUT RUETGERS ORGANICS
• Strong history – since 1877
• Owned by International Chemical Investors GmbH, Germany
• Over 25 years experience in the manufacture of fire protection systems
• Ruetgers product range:
• Wood preservation systems
• Fire protection systems:
• Wood
• Structural steel
• Textiles
HOW INTUMESCENTS WORK
• Intumescent coatings swell to form a layer of char foam in case of fire or heat (250-300oC)
• The foam layer protects the substrate from heat transfer for a period of time (eg. 30, 60, 90 or 120 minutes)
• Package usually consists of anti-corrosive primer, intumescent paint and top coat
DETERMINING THE FIRE RATING
• Australia has a performance based system which means that the fire risk needs to be calculated for each of the structures
• This risk determines the fire rating
• Example: a warehouse may only require a 30 minute fire rating whilst a hospital may require 120 minute fire rating
• There can be different ratings in different areas of the building
• The building designer determines the fire risk of the structure
ST100 Technical Information
Fields of Application
For the protection of internal and semi-exposed structural steel (I-sections and hollow sections). Not suitable for fully exposed structural steelwork or exposure to highly aggressive gas.
Standards AS1530.4 / DIN4102 / BS476
Pack Size 25kg buckets
Colour & Finish
Off-white with a rough surface and texture depending on the application process
Surface Preparation
Untreated Surfaces Steel or iron surfaces should be degreased and blast cleaned to preparation grade SA 2 ½ according to ISO 8501/ 1+2. If only hand cleaning is possible then degrease surface, wire brush to grade ST3 according to ISO 8501/1+2 and apply a suitable approved anti-rust primer with recommended dry film thickness.
Primed Surfaces Remove poorly adhering coats, check good-adhering coats for compatibility. If necessary run down slightly, remove dust and touch up with a suitable primer.
Galvanised surfaces Remove dust and grease and apply a suitable primer
Application Method
Brushing, rolling, airless spraying
Application Quantities
Loadings for the different applications and for different countries are available and depend on local approvals.
Application Guidelines
Stir well before use. Do not dilute. Do not apply at temperatures below +5oC (product, surface and air) and a relative air humidity over 80%. Brushing: Apply at least 2 coats to obtain an even film thickness. Airless spraying: If necessary dilute with up to 5% water.
ST100 Technical Information cont.
Cleaning Tools Rinse with water immediately after use to avoid drying out.
Drying Time At 20oC, 60% relative air humidity and an application rate of 1000g/m2: • Dry to touch after approximately 4 hours • Can be recoated after approximately 24 hours
Application of Topcoat
Application of a topcoat can protect the intumescent coat against effects of atmospheric humidity and other environmental influences. If a topcoat is not applied, surfaces treated with pyroplast® ST100 should not be exposed to high humidity or rain.
Density Approximately 1.27 g/cm3 at 20oC
Flash Point Not inflammable
Regulation on Hazardous material
The product is not hazardous according to 91/155/EWG
VOC Max. limit value of product according to EU (cat. 1.1i/WB): 140g/l (2007)/140g/l (2010). This product contains max. 75g/l VOC.
Precautions Always observe usual precautions when working with paints
Storage / Transport
Protected from frost and humidity pyroplast® ST100 can be stored for at least 36 months in sealed containers.
Environmental Protection
Do not allow pyroplast® ST100 to seep into the soil, water or drainage channels.
This technical leaflet has been compiled to the best of our knowledge and experience. In view of the large number of applications, we are unable to give a guarantee for every case.