Hilti, Inc., 5400 South 122nd East Avenue, Tulsa, OK 74121, (800) 879-8000
FIRESTOP SUBMITTAL PACKAGE
HVAC
Materials
FS-ONE Intumesent CaulkCP 606 Acrylic
Includes:Technical and Installation DataUL Certificate of Compliance
LEED informationMSDS
UL Details
Wood Floor AssembliesFC 7013c - Max. 4” (28 Ga) diameter sheet metal duct w/o damperFC 7025b - Max. 10” (28Ga) or 4” (30 Ga) diameter sheet metal duct w/o damperFC 7042a - Steel strut, steel cable, steel rod, steel angleFC 8014d - Single HVAC Line Set
Gypsum Wall AssembliesWL 7040g - Max. 48” x 24” sheet metal duct w/o damperWL 7042d - Max. 20” spiral wound duct w/o damper, or 12” sheet metal ductWL 7096a - Max. 13” x 12” sheet metal duct w/o damperWL 7059a - Max. 24” x 12”sheet metal duct with glass fiber duct insulationWL 7143b - Max. 24” x 24” sheet metal duct w/o damperWL 8047c - HVAC Line Set
Product Information
Chap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
s
Hilti, Inc. (U.S.) 1-800-879-8000 • www.us.hilti.com • en español 1-800-879-5000 • Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.
sodfm,ev iJdjfiwhriuh. NöoWE
Z8Z23awöp3i4eß0288u27 uze
4i5kirdwiloi4jtf-öx-.vbvbvh, ireiv
u9+ß12oeoo
tlke0´9^)&(/R 84tc )v 6453
FS-ONEHigh Performance Intumescent Firestop Sealant
FS-ONE Technical DataChemical basis Water-based intumescent acrylic
dispersionColor RedApplication temperature 40°F to 104°F (5°C to 40°C) Skin forming time Approx. 20-30 min.Curing time Approx. 2 mm / 3 daysMovement capability Approx. 5%Expansion rate Up to 3-5 times (unrestricted): original volumeTemperature resistance (cured) –40°F to 212°F (–40°C to 100°C)Surface burning characteristics Flame Spread: 0(ASTM E 84-96) Smoke Development: 5Sound transmission classification 56 (Relates to specific construction)(ASTM E 90-99) ApprovalsCalifornia State Fire Marshal Listing No. 4485-1200:108City of New York MEA 326-96-M Vol. IVTested in accordance with • UL 1479
• ASTM E 814• ASTM E 84
At 73°F (23°C) and 50% relative humidity
FILL, VOID OR CAVITY MATERIALFOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMSSEE UL FIRE RESISTANCE DIRECTORY
66Y7
FMAPPROVED
For Penetration Fire Stops.Consult the Factory Mutual Research Corporation Approval Guide.
R
C
LASSIFIED
FILL, VOID OR CAVITY MATERIALS CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.FOR USE IN TROUGH-PENETRATION
FIRESTOP SYSTEMS SEE UL FIRE RESISTANCE DIRECTORY
66Y7
Product description• Intumescent (expands when exposed to fire) firestop sealant that
helps protect combustible and non-combustible penetrations forup to 4 hours fire rating
Product features• Smoke, gas and water resistant after material has cured
• Contains no halogen, solvents or asbestos
• High fire rating properties
• Water based, easy to clean
• Protects most typical firestop penetration applications
• Can be painted
• Single component systems available
• Meets LEED™ requirements for indoor environmental quality credit4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paintsand Coatings
Areas of application• Steel, copper and EMT pipes
• Insulated steel and copper pipes
• Cable bundles
• Closed or vented plastic pipes
• HVAC penetrations
For use with• Concrete, masonry, drywall and wood floor assemblies
• Wall and floor assemblies rated up to 4 hours
Examples• Sealing around plastic pipe penetrations in fire rated construction
• Sealing around combustible and non-combustible penetrations infire rated construction
1. Clean opening. 2. Pack mineral wool.(If required)
3. Apply FS-ONE. 4. Smooth FS-ONE.
5. Leave completedseal undisturbed for 48hours.
6. Fasten identificationplate (if required).
1. Clean opening. 2. Pack mineral wool.(If required)
3. Apply FS-ONE. 4. Smooth FS-ONE.
5. Leave completedseal undisturbed for 48hours.
6. Fastenidentification plate (ifrequired).
FirestopSystem
Notice • Before handling, read Material Safety DataSheet and
product label for safe usage and health information.
• Instructions below are general guidelines — alwaysrefer to the applicable drawing in the UL FireResistance Directory or Hilti Firestop Systems Guidefor complete installation information
Opening 1. Clean the opening. Surfaces to which FS-ONE will be
applied should be cleaned of loose debris, dirt, oil,moisture, frost and wax. Structures supportingpenetrating items must be installed in compliancewith local building and electrical standards.
Application of firestop sealant 2. Install the prescribed backfilling material type and
depth to obtain the desired rating (if required). Leavesufficient depth for applying FS-ONE.
3. Application of firestop sealant: Apply FS-ONE to therequired depth in order to obtain the desired fire rating.Make sure FS-ONE contacts all surfaces to providemaximum adhesion. For application of FS-ONE use astandard caulking gun, foil pack gun, bulk loader andbulk gun. With FS-ONE buckets, Graco type sealantpumps may be used. (Contact pump manufacturer forproper selection).
4. Smoothing of firestop sealant: To complete the seal,tool immediately to give a smooth appearance.Excess sealant, prior to curing, can be cleanedaway from adjacent surfaces and tools with water.
5. Leave completed seal undisturbed for 48 hours.
6. For maintenance reasons, a penetration seal couldbe permanently marked with an identification plate.In such a case, mark the identification plate andfasten it in a visible position next to the seal.
Not for use • High movement expansion joints
• Underwater
• On materials where oil, plasticizers or solvents maybleed i.e. impregnated wood, oil based seals, greenor partially vulcanized rubber
• In any penetration other than those specificallydescribed in this manual or the test reports
Storage • Store only in the original packaging in a location
protected from moisture at temperatures between 40°F (5°C) and 86°F (30°C)
• Observe expiration date on the packaging
Installation instructions for FS-ONE
FirestopSystem
FirestopSystem
CA
BLE
PIP
E
Hilti, Inc. 5400 South 122nd East Avenue
Tulsa, OK 74146
1-800-879-8000 www.hilti.com
February 24, 2009 To Whom It May Concern: Re: Hilti FS-ONE Intumescent Firestop – LEED Info. The Hilti FS-ONE Intumescent Firestop is manufactured in Kaufering, Germany. The FS-ONE pail is made of polyethylene and can be completely recycled. There is no post-consumer or post-industrial content in FS-ONE and it cannot be recycled. The VOC content for FS-ONE is 75 grams/liter. FS-ONE is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for the disposal of non-regulated industrial waste can vary from state to state and even city to city. For this reason, you should consult your local and state regulatory agencies for direction on disposal. Please feel free to contact me at (918) 872-3704 if you have questions. Sincerely, Jerry Metcalf MPH, CHMM Safety/Environmental Manager Hilti Inc (918) 872 3704 [email protected] Rev. Date: 2/24/09
Product Information
Chap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
sC
hap
ter
Tab
s
Hilti, Inc. (U.S.) 1-800-879-8000 • www.us.hilti.com • en español 1-800-879-5000 • Hilti Firestop Systems Guide 2007
Hilti. Outperform. Outlast.
Hilti FirestopSaving Livesthrough innovationand education
CP 606Flexible Firestop Sealant
CP 606 Technical DataChemical basis Acrylic based firestop sealantColor Available in red or whiteApplication temperature 40°F to 104°F (5°C to 40°C)Skin-forming time Approx. 15 minCuring time Approx. 3 mm / 3 daysVolume shrinkage Less than 20%Movement capability Approx. 10%Temperature resistance –22°F to 176°F (–30°C to 80°C)Surface burning characteristics Flame Spread: 0(ASTM E 84-96) Smoke Development: 5Sound transmission classification 56 (Relates to specific construction)(ASTM E 90-99) ApprovalsCalifornia State Fire Marshal Listing No. 1452-1200:112
Listing No. 1451-1200:121Listing No. 4485-1200:132
City of New York MEA 100-99-M, Vol. IVTested in accordance with • UL 2079 • ASTM E 814
• ASTM E 1966 • ASTM E 84• UL 1479
At 73°F (23°C) and 50% relative humidity
FMAPPROVED
For Penetration Fire Stops.Consult the Factory Mutual Research Corporation Approval Guide.
R
C
LASSIFIED
FILL, VOID OR CAVITY MATERIALS CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.FOR USE IN TROUGH-PENETRATION
FIRESTOP SYSTEMS SEE UL FIRE RESISTANCE DIRECTORY
66Y7
FILL, VOID OR CAVITY MATERIALFOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMS AND JOINT SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY 66Y7
Product description• An acrylic based firestop sealant that provides movement
capability in fire rated joints and seals through penetrationsapplications
Product features• Silicone free
• Halogen, asbestos and solvent free
• UV-resistant
• Paintable
• Meets 500 cycle requirements (ASTM E 1966 & UL 2079)
• Smoke, fume and water resistant
• Easy clean up with water
• Single component systems available
• Meets LEED™ requirements for indoor environmental quality credit4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paintsand Coatings
Areas of application• Sealing construction/expansion joints
• Top-of-wall joints
• Metal pipes
• Cable bundles
• HVAC penetrations
For use with• Various base materials such as masonry, concrete, metal, etc.
• Wall and floor assemblies rated up to 3 hours
Examples• Where a gypsum wall assembly meets the underside of
a metal or concrete deck
• Sealing expansion joints to impede the passage of fire, smoke andtoxic fumes
• Sealing around HVAC penetrations through fire-rated assemblies
Notice • Before handling, read Material Safety DataSheet and
product label for safe usage and health information.
• Instructions below are general guidelines — alwaysrefer to the applicable drawing in the UL FireResistance Directory or Hilti Firestop Systems Guidefor complete installation information
Opening1. Clean the opening. Surfaces to which CP 606 will
be applied should be cleaned of loose debris, dirt,oil, wax and grease. The surface should bemoisture and frost free.
Application of firestop2. Insert fill of mineral wool or backer (as required).
3. Apply firestop over backer.
4. Smooth firestop sealant with a trowel before theskin forms. Once cured, CP 606 can only beremoved mechanically.
5. For maintenance reasons, a penetration seal can bepermanently marked with an identification plate andfastened in a visible position next to the seal.
Not for use• On areas immersed in water
Storage• Store only in the original packaging in a location
protected from moisture at a temperature of 40°F to77°F (5°C to 25°C)
• Observe expiration date on package
Installation instructions for CP 606
1. Clean opening 2. Insert backingmaterial compressedper UL System
3. Apply CP 606 4. Smooth CP 606 5. Fasten identificationplate (if required)
1. Clean opening 2. Insert backingmaterial
3. Apply CP 606 4. Smooth CP 606 5. Fasten identificationplate (if required)
FirestopSystem
FirestopSystem
JO
INT
DU
CT
Hilti, Inc. 5400 South 122nd East Avenue
Tulsa, OK 74146
1-800-879-8000 www.hilti.com
February 24, 2009 To Whom It May Concern: Re: Hilti CP 606 Flexible Firestop – LEEDs Info. The Hilti CP 606 Flexible Firestop Sealant is manufactured in Kaufering, Germany. The CP 606 pail is made of polyethylene and can be completely recycled. There is no post-consumer or post-industrial content in CP 606 and it cannot be recycled. The CP 606 does not contain any Rapidly Renewable Materials. The VOC content for CP 606 is 71.0 grams/liter. CP 606 is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for the disposal of non-regulated industrial waste can vary from state to state and even city to city. For this reason, you should consult your local and state regulatory agencies for direction on disposal. Please feel free to contact me at (918) 872-3704 if you have questions. Sincerely, Jerry Metcalf MPH, CHMM Safety/Environmental Manager Hilti Inc. 918 872 3704 [email protected] Rev. Date: 2/24/09
Sheet Drawing No.HILTI, Inc.
Tulsa, Oklahoma USA (918) 252-6000Date
Scale
FRONT VIEW
A
A
SECTION A-A
NOTES : 1. MAXIMUM AREA OF OPENING = 1300 SQ. IN. WITH A MAXIMUM DIMENSION OF 50 IN. 2. ANNULAR SPACE = MINIMUM 0", MAXIMUM 2". 3. AFTER SEALING SPACE BETWEEN DUCT AND GYPSUM WALL ASSEMBLY WITH HILTI
FIRESTOP SEALANT, FASTEN STEEL ANGLE (MIN. 18 GA.) TO DUCT WITH MINIMUM NO. 8 x 3/4" LONG SHEET METAL SCREWS. STEEL ANGLE TO OVERLAP DUCT BY MINIMUM 2" AND GYPSUM WALL ASSEMBLY BY MINIMUM 1". ANGLE DOES NOT HAVE TO BE FASTENED TO GYPSUM WALL ASSEMBLY.
1. GYPSUM WALL ASSEMBLY (UL/ULC CLASSIFIED U300 OR U400 SERIES WALL) (1-HR. OR 2-HR. FIRE-RATING) (2-HR. SHOWN).
2. (NOT SHOWN). WOOD STUDS TO CONSIST OF NOMINAL 2" x 4" LUMBER. STEEL STUDS TO BE MINIMUM 2-1/2" WIDE.
3. RECTANGULAR SHEET METAL DUCT (MAXIMUM SIZE : 24" x 48", MINIMUM 24 GA. THICKNESS). (NOTE : NOT FOR USE IN DUCT SYSTEMS CONTAINING A FIRE DAMPER).
4. OPENING TO BE "FRAMED OUT" WITH LIGHTGAGE METAL FRAMING STUDS. 5. MINIMUM 5/8" DEPTH HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT, HILTI CP 601S ELASTO- MERIC
FIRESTOP SEALANT, OR HILTI CP 606 FLEXIBLE FIRESTOP SEALANT. 6. (NOT SHOWN). APPLY MINIMUM 1/2" BEAD HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT, HILTI CP
601S ELASTOMERIC FIRESTOP SEALANT, OR HILTI CP 606 FLEXIBLE FIRESTOP SEALANT AT POINT OF CONTACT PRIOR TO ATTACHING STEEL ANGLE.
WL7040g
1 of 1
5/64" = 1"
Sept. 11, 2001
UL/cUL SYSTEM NO. W-L-7040
F-RATING = 1-HR. OR 2-HR.T-RATING = 0-HR.
WL7
040g
.0911
01
12
3
4 5
6
MAXIMUM 6" C/C SPACING(SEE NOTE NO. 3 BELOW)
Sheet Drawing No.
HILTI, Inc.Tulsa, Oklahoma USA (918) 252-6000
Date
Scale
FRONT VIEW
A
A
SECTION A-A
NOTES : 1. MAXIMUM DIAMETER OF OPENING FOR STEEL STUD WALLS = 21-3/4" 2. MAXIMUM DIAMETER OF OPENING FOR WOOD STUD WALLS = 14-1/2". 3. ANNULAR SPACE = MINIMUM 0", MAXIMUM 1-1/2".
1. GYPSUM WALL ASSEMBLY (UL/ULC U300 OR U400 SERIES WALL SERIES) (1-HR. OR 2-HR. FIRE-RATING) (2-HR. SHOWN).
2. (NOT SHOWN). WOOD STUDS TO CONSIST OF NOMINAL 2" x 4" LUMBER. STEEL STUDS TO BE MINIMUM 2-1/2" WIDE.
3. PENETRATING ITEM TO BE ONE OF THE FOLLOWING : A. MAXIMUM 20" NOMINAL DIAMETER SPIRAL WOUND SHEET METAL DUCT (MIN. 24 GA.). B. MAXIMUM 12" NOMINAL DIAMETER SHEET METAL DUCT (MIN. 28 GAUGE).
4. HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT, HILTI CP 601S ELASTOMERIC FIRESTOP SEALANT, OR HILTI CP 606 FLEXIBLE FIRESTOP SEALANT :
A. MINIMUM 5/8" DEPTH, FOR A 1-HR. FIRE RATING. B. MINIMUM 1-1/4" DEPTH, FOR A 2-HR. FIRE RATING.
5. MINIMUM 1/2" BEAD HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT OR CP 601S ELASTOMERIC FIRESTOP SEALANT, OR HILTI CP 606 FLEXIBLE FIRESTOP SEALANT AT POINT OF CONTACT.
WL7042d
1 of 1
3/32" = 1"
Jan. 15, 2001
UL/cUL SYSTEM NO. W-L-7042
F-RATING = 1-HR. OR 2-HR.T-RATING = 0-HR.
WL7
042d
.0115
01
12
3
4
5
Sheet Drawing No.HILTI, Inc.
Tulsa, Oklahoma USA (918) 252-6000Date
Scale
FRONT VIEW
A
A
SECTION A-A
NOTES : 1. MAX. AREA OF OPENING = 395 SQ. IN. WITH A MAX. DIM. OF 26-3/4". 2. INSULATION SHOULD BE COMPRESSED 50% SUCH THAT THE
ANNULAR SPACE = MIN. 1/4", MAX. 1".
1. GYPSUM WALL ASSEMBLY (UL/ULC CLASSIFIED U400 SERIES WALL) (1-HR. OR 2-HR. FIRE-RATING) (2-HR. SHOWN).
2. (NOT SHOWN). STEEL STUDS TO BE MINIMUM 2-1/2" WIDE. OPENING TO BE "FRAMED OUT" ON ALL SIDES OF OPENING WITH LIGHTGAGE METAL STUD MATERIAL.
3. MAXIMUM 24" x 12" RECTANGULAR SHEET METAL DUCT (MINIMUM 24 GA.). (NOTE : NOT FOR USE IN DUCT SYSTEMS CONTAINING A FIRE DAMPER).
4. MAXIMUM 1-1/2" THICKNESS GLASS FIBER DUCT INSULATION (MIN. 3/4 PCF DENSITY) WITH FOIL-SCRIM-KRAFT FACING. (SEE NOTE NO. 2 BELOW).
5. HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT : A. MINIMUM 5/8" DEPTH OF SEALANT FOR A 1-HR. FIRE-RATING. B. MINIMUM 1-1/4" DEPTH OF SEALANT FOR A 2-HR. FIRE-RATING.
WL7059a
1 of 1
3/32" = 1"
Feb. 1, 2001
UL/cUL SYSTEM NO. W-L-7059
F-RATING = 1-HR. OR 2-HR.T-RATING = 1/2-HR. OR 3/4-HR.
WJ7
059a
.0201
01
12
3
4 5