+ All Categories
Home > Documents > FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED...

FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED...

Date post: 19-Mar-2020
Category:
Upload: others
View: 0 times
Download: 0 times
Share this document with a friend
28
Glenn E. Schmitt, P.E. Environmental Director Fleet and Industrial Supply Center Puget Sound Ready. Resourceful. Responsive! FISC Puget Sound Manchester Fuel Department Maintenance, Leak Detection in Large Underground Storage Tanks
Transcript
Page 1: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

1

Glenn E. Schmitt, P.E.Environmental Director

Fleet and Industrial Supply CenterPuget Sound

Ready. Resourceful. Responsive!

FISC Puget SoundManchester Fuel Department

Maintenance,Leak Detection in LargeUnderground Storage

Tanks

Page 2: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

Report Documentation Page Form ApprovedOMB No. 0704-0188

Public reporting burden for the collection of information is estimated to average 1 hour per response, including the time for reviewing instructions, searching existing data sources, gathering andmaintaining the data needed, and completing and reviewing the collection of information. Send comments regarding this burden estimate or any other aspect of this collection of information,including suggestions for reducing this burden, to Washington Headquarters Services, Directorate for Information Operations and Reports, 1215 Jefferson Davis Highway, Suite 1204, ArlingtonVA 22202-4302. Respondents should be aware that notwithstanding any other provision of law, no person shall be subject to a penalty for failing to comply with a collection of information if itdoes not display a currently valid OMB control number.

1. REPORT DATE MAY 2009 2. REPORT TYPE

3. DATES COVERED 00-00-2009 to 00-00-2009

4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large Underground Storage Tanks

5a. CONTRACT NUMBER

5b. GRANT NUMBER

5c. PROGRAM ELEMENT NUMBER

6. AUTHOR(S) 5d. PROJECT NUMBER

5e. TASK NUMBER

5f. WORK UNIT NUMBER

7. PERFORMING ORGANIZATION NAME(S) AND ADDRESS(ES) Naval Supply Systems Command,Fleet Logistics Center Puget Sound ,467W Street ,Bremerton,WA,98314-5100

8. PERFORMING ORGANIZATIONREPORT NUMBER

9. SPONSORING/MONITORING AGENCY NAME(S) AND ADDRESS(ES) 10. SPONSOR/MONITOR’S ACRONYM(S)

11. SPONSOR/MONITOR’S REPORT NUMBER(S)

12. DISTRIBUTION/AVAILABILITY STATEMENT Approved for public release; distribution unlimited

13. SUPPLEMENTARY NOTES Presented at the NDIA Environment, Energy Security & Sustainability (E2S2) Symposium & Exhibitionheld 4-7 May 2009 in Denver, CO.

14. ABSTRACT

15. SUBJECT TERMS

16. SECURITY CLASSIFICATION OF: 17. LIMITATION OF ABSTRACT Same as

Report (SAR)

18. NUMBEROF PAGES

27

19a. NAME OFRESPONSIBLE PERSON

a. REPORT unclassified

b. ABSTRACT unclassified

c. THIS PAGE unclassified

Standard Form 298 (Rev. 8-98) Prescribed by ANSI Std Z39-18

Page 3: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

2

BRIEF OVERVIEW

Introduction

Scope of Military Large USTs

Issues at Military Storage Tanks

Types of USTs

Page 4: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

3

BRIEF OVERVIEW

Typical ConstructionRegulatory DriversManchester Experience

Manchester TerminalMaintenance Methods and HistoryLeak Detection History at MFD

Conclusions

Page 5: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

4

Definitions

AFHE – Automated Fuel Handling EquipmentAtmospheric tanks – vented to Atmosphere –not pressurizedATG – Automatic Tank GagingBarrel – 42 US gallonsDESC – Defense Energy Support CenterFloating Roof Tanks – Roof floats on product StoredLarge USTs – USTs larger than 50,000 gallons or 1200 barrelsPrecision Leak Detection – quantitative leak detection at less than 1 gallon/hr.

Page 6: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

5

Large Military USTs

Army – 4 Large USTS (non active)

Air Force – 136 Active Large USTSBiggest is 280,000 Barrels

Navy 325 Active Large USTs Biggest is 300,000 Barrels

Page 7: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

6

Military Storage Tank Issues

Old InfrastructureTanks Built in 1940’s/1950’s

Storage RequirementsMaintenance of Minimum Volumes for Mission Requirements

Lack of GuidanceNo good standards for MaintenanceNo Industry Standard for large USTS

Page 8: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

7

Military Storage Tank Issues

Technological LimitationsInstalled Inventory Management limitationsPrecision leak Detection Limitations

Inconsistent Operator Training Standards

Page 9: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

8

Results

April 26, 2007 FISC Pearl Harbor Reports a loss of 366,000 gallons from tank 1403 (AST) (later revised to 359,000 gallons)

Page 10: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

9

Results

Results – a 1inch by 3 inch hole in sump

Operator Error detecting loss

Page 11: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

10

Types of USTs

ConcreteCut and coveredUnderground Construction

SteelCut and coveredRiveted TanksWelded tanks

Page 12: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

11

Typical construction

® aa0a

saaaaa aaaaaa assaaa aaaaaa

aaaa

--o

Page 13: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

12

Typical construction

Valve PitATG

Tanks

Sump

Foundation

Drain

Stilling Well

Skin

Valve

Page 14: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

13

Regulatory Drivers

40 CFR 280/281Derives Basic Regulation of Underground Storage TanksThese tanks are Field Constructed –therefore “deferred” (40CFR 280.10)

State/Local RequirementsDOD Reguirements

Page 15: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

14

MFD GENERAL INFO

•Size: Facility encompasses 234 acres and has 1.5 miles of shoreline on Puget Sound and Rich Passage

•Personnel: 39 civilian and 2 military operate the facility

Page 16: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

15

TERMINAL LAYOUT

MAIN GATEDFM PIPELINE

JP-5 PIPELINE JP-5 PIPELINE

JP-8 PIPELINE

0 • JP-8(AS'l) JP-5 (UST) Oll..YWASTE

0 • STORAGE 0

JP-8(UST) FUELOll.. OFF-SPEC

0 RECLAIMED PRODUCT 0 Q

F-76(US'l) WATER CONGLOMERATE on..

0 LUBEOll..

• F.S.ll ..

MOGASPUMPS

CLAM BAY

LITTLE CLAM BAY

A

A JP-8 TRUCK RACK

• SPARE TANK

................... . ................ .

RICH PASSAGE

ORCHARD POINT

PUGETSOUND

Page 17: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

16

Terminal Tankage

Underground Storage Tanks34 Bulk Fuel 5 metal 27/50 MBBL tanks9 concrete coated 27MBBL tanks20 concrete coated 47/50Mbbl Tanks

Aboveground Tanks• 5 80Mbbls Bulk tanks• 4 Lube oil tanks• 5 Waste Oil/Waste water tanks• 2 Additive Tanks

Pipelines• F76 1.9 miles• JP8 3.8 miles• JP5 3.0 miles

38 Bulk Storage Tanks (33 UST / 5 AST)1,834 Mbbls (77,009,730 Gallons)

Page 18: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

17

Maintenance Methods/History

Definitive Need to Clean and Inspect Bulk TanksNo definitive guidance (API 653 etc.)Coating installation challenges

Page 19: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

18

Coating Issues

Failure at the Tank wall joint (cove Failure

Failure of floor coating

Page 20: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

19

Further Challenges

Leaking Skin Valves/Pipe nipples

Leaking older Tank Penetrations

Page 21: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

20

DESC CMPs

Tank Inspection Repair

Pipelines

Leak Detection

Cathodic Protection

Page 22: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

21

Manchester Methods

Detailed InspectionVisualDye PenetrantHigh Voltage Holiday DetectionUltrasonic

RepairsCoatingPenetrationsValves

Page 23: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

22

Maintenance Validations

Final Inspections

Leak Detection

Page 24: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

23

Leak Detection

Arizona InstrumentsVapor Detection Technology Failed due to complexity, and preexisiting vapors in soil matrix

Tracer Technology• Requires Injection of Trace Elements• Tanks are Atmospheric, vented• Soil Matrix is not homogenous

AFHE XLD 2000• Technology relied on software for temperature/atmospheric pressure correction• Complicated analysis of plots required• Lack of SPAWAR support

VISTA Precision Leak DetectionApplied to Tanks 29 and 16Required Isolating the Tanks – long turnaroundAccurate to California Standard

Page 25: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

24

Leak Detection Challenges

Technical Capability of Leak Detection

Tank construction challenges

Ullage requirements

Timing

Page 26: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

25

Manchester Results

Contractor Partners (Shaw E& I, Michael Baker Corp, Vista)

Necessity of Ullage

Water Intrusion

Page 27: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

26

Conclusions

Aggressive Maintenance Allows continued use of this assetManaged Maintenance will minimize ultimate replacement costsEnvironmentally and Economically viable method of fuels storage

Page 28: FISC Puget Sound Manchester Fuel Department Maintenance ...MAY 2009 2. REPORT TYPE 3. DATES COVERED 00-00-2009 to 00-00-2009 4. TITLE AND SUBTITLE Maintenance, Leak Detection in Large

FISC Puget Sound - Manchester

27

QUESTIONS???


Recommended