FLOOR TYPE AIR CONDITIONERS MFZ-KJ25VE MFZ-KJ35VE MFZ-KJ50VE MFZ-KJ60VE English INSTALLATION MANUAL For INSTALLER When installing multi units, refer to the installation manual of the multi unit for outdoor unit installation. Note: These models can be connected to the multi units, except for KJ60.
Transcript
Page 1: FLOOR TYPE AIR CONDITIONERS€¦ · FLOOR TYPE AIR CONDITIONERS MFZ-KJ25VE MFZ-KJ35VE MFZ-KJ50VE MFZ-KJ60VE English InstallatIon Manual For INSTALLER • When installing multi units,

FLOOR TYPE AIR CONDITIONERSMFZ-KJ25VE MFZ-KJ35VE MFZ-KJ50VE MFZ-KJ60VE

EnglishInstallatIon Manual For INSTALLER• When installingmulti units, refer to the installationmanual of themulti unit foroutdoorunitinstallation.

note:Thesemodelscanbeconnectedtothemultiunits,exceptforKJ60.

JG79A867H02_en.indd 1 2014/06/25 13:38:50

Page 2: FLOOR TYPE AIR CONDITIONERS€¦ · FLOOR TYPE AIR CONDITIONERS MFZ-KJ25VE MFZ-KJ35VE MFZ-KJ50VE MFZ-KJ60VE English InstallatIon Manual For INSTALLER • When installing multi units,

En-1

ContEnts1. BEFOREINSTALLATION....................................12. INDOORUNITINSTALLATION...........................33. OUTDOORUNITINSTALLATION.......................64. PURGINGPROCEDURES,LEAKTEST,AND

TESTRUN...........................................................75. PUMPINGDOWN................................................7

1. BEFoRE InstallatIon1-1. tHE FolloWInG sHoulD alWaYs BE oBsERVED FoR saFEtY• Besuretoread“THEFOLLOWINGSHOULDALWAYSBEOBSERVEDFORSAFETY”beforeinstallingtheairconditioner.• Besuretoobservethewarningsandcautionsspecifiedhereastheyincludeimportantitemsrelatedtosafety.• Afterreadingthismanual,besuretokeepittogetherwiththeOPERATINGINSTRUCTIONSforfuturereference.

1-2. sElECtInG tHE InstallatIon loCatIon

CAUTION (Couldleadtoseriousinjuryinparticularenvironmentswhenoperatedincorrectly.)

Required tools for InstallationPhillipsscrewdriverLevelScaleUtilityknifeorscissors25,35class65mm/50,60class75mmholesawTorquewrench

Wrench(orspanner)4mmhexagonalwrenchFlaretoolforR410AGaugemanifoldforR410AVacuumpumpforR410AChargehoseforR410APipecutterwithreamer

n Do not install the unit by yourself (user). Incomplete installation could cause fire, electric

shock, injury due to theunit falling, or leakageofwater.Consultthedealerfromwhomyoupurchasedtheunitoraqualifiedinstaller.

n Perform the installation securely referring to the installation manual.

Incomplete installation could cause fire, electricshock, injury due to theunit falling, or leakageofwater.

n When installing the unit, use appropriate protec-tive equipment and tools for safety.

Failuretodosocouldcauseinjury.n Install the unit securely in a place which can

bear the weight of the unit. Iftheinstallationlocationcannotbeartheweightof

theunit,theunitcouldfallcausinginjury.n Electrical work should be performed by a quali-

fied, experienced electrician, according to the installation manual. Be sure to use an exclusive circuit. Do not connect other electrical appli-ances to the circuit.

If thecapacityof thepowercircuit is insufficientorthereisincompleteelectricalwork,itcouldresultinafireoranelectricshock.

n Earth the unit correctly. Donotconnecttheearthtoagaspipe,waterpipe,

lightningrodor telephoneearth.Defectiveearthingcouldcauseelectricshock.

n Do not damage the wires by applying excessive pressure with parts or screws.

Damagedwirescouldcausefireorelectricshock.n Be sure to cut off the main power in case of set-

ting up the indoor P.C. board or wiring works. Failuretodosocouldcauseelectricshock.n Use the specified wires to connect the indoor

and outdoor units securely and attach the wires firmly to the terminal block connecting sections so the stress of the wires is not applied to the sections. Do not extend the wires, or use inter-mediate connection.

Incomplete connectingand securing could causefire.

n Do not install the unit in a place where inflam-mable gas may leak.

Ifgasleaksandaccumulatesintheareaaroundtheunit,itcouldcauseanexplosion.

n Do not use intermediate connection of the power cord or the extension cord and do not connect many devices to one aC outlet.

Itcouldcauseafireoranelectricshockduetode-fective contact, defective insulation, exceeding thepermissiblecurrent,etc.

n Be sure to use the parts provided or specified parts for the installation work.

Theuseofdefectivepartscouldcausean injuryorleakageofwaterduetoafire,anelectricshock,theunitfalling,etc.

n When plugging the power supply plug into the outlet, make sure that there is no dust, clogging, or loose parts in both the outlet and the plug. Make sure that the power supply plug is pushed com-pletely into the outlet.

Ifthereisdust,clogging,orloosepartsonthepowersupplyplugortheoutlet,itcouldcauseelectricshockorfire. If loosepartsare foundon thepowersupplyplug,replaceit.

n attach the electrical cover to the indoor unit and the service panel to the outdoor unit securely.

Iftheelectricalcoveroftheindoorunitand/ortheserv-icepaneloftheoutdoorunitarenotattachedsecurely,itcouldresultinafireoranelectricshockduetodust,water,etc.

n When installing, relocating, or servicing the unit, make sure that no substance other than the specified refrigerant (R410A) enters the refriger-ant circuit.

Anypresenceofforeignsubstancesuchasaircancauseabnormal pressure riseandmay result inexplosionorinjury.Theuseofanyrefrigerantotherthan that specified for the systemwill causeme-chanical failure, systemmalfunction,orunit break-down.Intheworstcase,thiscouldleadtoaseriousimpedimenttosecuringproductsafety.

n Do not discharge the refrigerant into the atmos-phere. If refrigerant leaks during installation, venti-late the room.

If refrigerant comes in contactwith a fire, harmfulgascouldbegenerated.

n Check that the refrigerant gas does not leak after installation has been completed.

If refrigerant gas leaks indoors, and comes intocontactwiththeflameofafanheater,spaceheater,stove,etc.,harmfulsubstanceswillbegenerated.

n use appropriate tools and piping materials for installation.

ThepressureofR410Ais1.6timesmorethanR22.Notusingappropriatetoolsormaterialsandincom-plete installation could cause thepipes to burst orinjury.

n When pumping down the refrigerant, stop the compressor before disconnecting the refriger-ant pipes.

If the refrigerant pipesaredisconnectedwhile thecompressor is runningand thestopvalve isopen,aircouldbedrawninandthepressureintherefrig-eration cycle couldbecomeabnormally high.Thiscouldcausethepipestoburstorinjury.

n When installing the unit, securely connect the refrigerant pipes before starting the compres-sor.

If the compressor is startedbefore the refrigerantpipesare connectedandwhen the stop valve isopen,aircouldbedrawninandthepressureintherefrigeration cycle couldbecomeabnormally high.Thiscouldcausethepipestoburstorinjury.

n Fasten a flare nut with a torque wrench as speci-fied in this manual.

If fastened too tight, a flarenutmaybreakafter alongperiodandcauserefrigerantleakage.

n the unit shall be installed in accordance with national wiring regulations.

n Install an earth leakage breaker depending on the installation place.

Ifanearthleakagebreakerisnotinstalled,itcouldcauseelectricshock.

n Perform the drainage/piping work securely ac-cording to the installation manual.

If thereisdefect inthedrainage/pipingwork,watercoulddrop from theunit, soakinganddamaginghouseholdgoods.

n Do not touch the air inlet or the aluminum fins of the outdoor unit.

Thiscouldcauseinjury.

n Do not install the outdoor unit where small ani-mals may live.

If small animals enter and touch theelectric partsinsidetheunit,itcouldcauseamalfunction,smokeemission,orfire.Also,adviseusertokeeptheareaaroundtheunitclean.

WARNING (Couldleadtodeath,seriousinjury,etc.)

EN

GLI

SH

InDooR unIt • Whereairflowisnotblocked.• Whereairspreadsovertheentireroom.• Rigidwallwithoutvibration.• Where it is not exposed to direct sunshine.Donot

exposetodirectsunshinealsoduringtheperiodfol-lowingunpackingtobeforeuse.

• Whereeasilydrained.• At adistance1mormoreaway fromyourTVand

radio.Operationof theair conditionermay interferewith radio orTV reception.Anamplifiermaybe re-quiredfortheaffecteddevice.

• Inaplaceas farawayaspossible fromfluorescentandincandescentlights.

Inordertomaketheinfraredremotecontroloperatetheair-conditionernormally.Theheat from the lightsmaycausedeformationortheultravioletmaycausedeterioration.

• Wheretheairfiltercanberemovedandreplacedeasily.REMotE ContRollER • Whereitiseasytooperateandeasilyvisible.• Wherechildrencannottouchit.• Select thepositionwhere the indoorunitcanreceive

thesignal fromtheremotecontrollerproperly.Checkthat signals from the remotecontrolleraresurely re-ceivedbytheindoorunitfromthatposition(‘beep’or‘beepbeep’receivingtonesounds).Afterthat,attachremotecontrollerholder toapillarorwall and installwirelessremotecontroller.

note: In roomswhere inverter type fluorescent lampsareused,thesignalfromthewirelessremotecontrollermaynotbereceived.outDooR unIt• Whereitisnotexposedtostrongwind.• Whereairflowisgoodanddustless.• Whererainordirectsunlightcanbeavoidedasmuch

aspossible.• Whereneighboursarenot annoyedbyoperation

soundorhotair.• Whererigidwallorsupportisavailabletopreventthe

increaseofoperationsoundorvibration.• Wherethereisnoriskofcombustiblegasleakage.• When installing theunit at a high level, be sure to

securetheunitlegs.• Where it isat least3maway from theantennaof

TVsetor radio.Operationof theairconditionermayinterferewithradioorTVreceptioninareaswherere-ceptionisweak.Anamplifiermayberequiredfortheaffecteddevice.

• Installtheunithorizontally.• Pleaseinstallitinanareanotaffectedbysnowfallor

blowingsnow. Inareaswithheavysnow,please in-stallacanopy,apedestaland/orsomebaffleboards.

note:Itisadvisabletomakeapipingloopnearoutdoorunitsoastoreducevibrationtransmittedfromthere.

note: Whenoperatingtheairconditionerinlowoutsidetem-perature,besure to follow the instructionsdescribedbelow.• Never install theoutdoor unit in a placewhere

itsair inlet/outletsidemaybeexposeddirectly towind.

• Toprevent exposure towind, install theoutdoorunitwithitsairinletsidefacingthewall.

• Topreventexposure towind, it is recommendedtoinstallabaffleboardontheairoutletsideoftheoutdoorunit.

Avoid the followingplaces for installationwhereairconditionertroubleisliabletooccur.• Whereflammablegascouldleak.• Wherethereismuchmachineoil.• Whereoil is splashedorwhere thearea is filled

with oily smoke (suchas cookingareasand fac-tories, inwhich theproperties of plastic couldbechangedanddamaged).

• Saltyplacessuchastheseaside.• Where sulfidegas is generated suchasahot

spring.• Where there is high-frequencyorwirelessequip-

ment.• Where there is emissionof high levels ofVOCs,

includingphthalate compounds, formaldehyde,etc.,whichmaycausechemicalcracking.

Model names are indicated in 1-3.Wheninstallingmultiunits,refertotheinstallationmanualofthemultiunitforoutdoorunitinstallation.

JG79A867H02_en.indd 1 2014/06/25 13:38:50

Page 3: FLOOR TYPE AIR CONDITIONERS€¦ · FLOOR TYPE AIR CONDITIONERS MFZ-KJ25VE MFZ-KJ35VE MFZ-KJ50VE MFZ-KJ60VE English InstallatIon Manual For INSTALLER • When installing multi units,

En-2

Indoorunit

Wallholesleeve(C)

Cutofftheextralength. Pipefixingband

(E)

Wallholecover(D)

Sealthewallholegapwithputty(H).

Fixthepipetowallwithpipefixingband(E).

Fixingscrew(F)

1-3. sPECIFICatIons

1-4. INSTALLATION DIAGRAM

aCCEssoRIEsCheckthefollowingpartsbeforeinstallation.(1) Drainhose* 1(2) Remotecontrollerholder 1(3) Fixingscrewfor(2)3.5×16mm(Black) 2(4) Pipecover 1(5) Band 2(6) Battery(AAA)for(12) 2(7) Indoorunitmountingbracket 1(8) Fixingscrewfor(7)4×25mm 5(9) Woodscrewforindoorunitfixation 4(10) Washerof(9) 4(11) Felttape(Forleftorleft-rearpiping) 1(12) Wirelessremotecontroller 1(13) Aircleaningfilter 2

* note:TheDrainhoseisconnectedtotheunit.

<Outdoorunit>(14) Drainsocket(VEtypeonly) 1

Unitsshouldbeinstalledbylicensedcontractoraccordingtolocalcoderequirements.

Aftertheleaktest,applyinsulatingmaterialtightlysothatthereisnogap.

Besuretousewallholesleeve(C)topreventindoor/outdoorconnectingwire(A)fromcontactingmetalpartsinthewallandtopreventdamagebyrodentsincasethewallishollow.

PaRts to BE PRoVIDED at YouR sItE(A) Indoor/outdoorunitconnectingwire* 1(B) Extensionpipe 1(C) Wallholesleeve 1(D) Wallholecover 1(E) Pipefixingband 2to5(F) Fixingscrewfor(E)4×20mm 2to5(G) Pipingtape 1(H) Putty 1

(I)Drainhose(orsoftPVChose,15mminnerdia.orhardPVCpipeVP16)

1 or 2

(J) Refrigerationoil 1(K) Powersupplycord* 1

* note:Placeindoor/outdoorunitconnectingwire(A)andpowersupplycord(K)atleast1mawayfromtheTVantennawire.

150m

morbe

low

fromthe

floor

100mmormore

Noobstruction

100mmormore

*1 Connect to thepower switchwhichhasagapof 3mmormorewhenopen to interrupt thesourcepowerphase.(When thepower switch is shut off, itmust interrupt allphases.)

*2 Usewiresinconformitywithdesign60245IEC57.*3 Never usepipeswith thickness less than specified.The

pressureresistancewillbeinsufficient.*4 Useacopperpipeoracopper-alloyseamlesspipe.

*5 Becarefulnottocrushorbendthepipeduringpipebend-ing.

*6 Refrigerantpipebendingradiusmustbe100mmormore.*7 Ifpipelengthexceeds7m,additionalrefrigerant(R410A)

charge is required. (Noadditional charge is required forpipelengthlessthan7m.)

Additionalrefrigerant=A×(pipelength(m)–7)

*8 Insulationmaterial :Heat resisting foamplastic 0.045specificgravity

*9 Be sure to use the insulationof specified thickness.Ex-cessive thicknessmay cause incorrect installationof theindoorunitandinsufficientthicknessmaycausedewdrip-page.

*10Singleconnectiononly.

Model Powersupply*1 Wirespecifications*2 Pipesize (thickness*3,*4)

Indoorunit Outdoorunit RatedVoltage Frequency Breaker

capacityPowersupply

(3-core)Indoor/outdoorconnectingwire Gas/Liquid

MFZ-KJ25VEMFZ-KJ35VE

MUFZ-KJ25VEMUFZ-KJ35VE

230V 50Hz10A 1.0mm2

4-core 2.0mm2

ø9.52/6.35mm(0.8mm)

MFZ-KJ50VE MUFZ-KJ50VE(HZ) 16A2.0mm2 ø12.7/6.35mm

(0.8mm)MFZ-KJ60VE*10 MUFZ-KJ60VE(HZ) 20A

(KJ25,35/KJ50,60)PipelengthandheightdifferenceMax.pipelength 20/30m

Max.heightdifference 12/15mMax.numberofbends*5,*6 10RefrigerantadjustmentA*7 30/20g/mInsulationthickness*8,*9 8mm

(KJ25,35/KJ50,60)100/500mmormore

100mmormore

(KJ25,35/KJ50,60)200/500mmormore

350mmormore

100mm

ormore

Appearanceoftheoutdoorunitmaydifferfromsomemodels.

Airinlet

Airoutlet

outdoor unit installation(KJ25,35/KJ50,60)

2/4-10mm×21mmslot

800/840mm150/175mm 500mm

344.5/390mm

285/330mm

304-325/349-371mm

40mm

Whenthepipingistobeattachedtoawallcontainingmetals(tinplated)ormetalnetting,useachemicallytreatedwoodenpiece20mmorthickerbetweenthewallandthepipingorwrap7to8turnsofinsulationvinyltapearoundthepiping.Touseexistingpiping,performCOOLoperationfor30minutesandpumpdownbeforeremovingtheoldairconditioner.Remakeflareaccordingtothedimensionfornewrefrigerant.

Drain piping for outdoor unit <VE type only>•Providedrainpipingbeforeindoorandoutdoorpipingconnection.

•Connectdrainhose(I)I.D.15mmasshownintheillustration.

•Makesuretoprovidedrainpipingwithadown-hillgradeforeasydrainflow.

(14) (I)

note:Installtheunithorizontally.Donot usedrain socket (14) in cold regions.Drainmayfreezeandmakethefanstop.Theoutdoor unit produces condensateduringtheheatingoperation.Select the installationplacetoensuretopreventtheoutdoorunitand/orthegroundsfrombeingwetbydrainwaterordamagedbyfrozendrainwater.

IMPoRtant notEs TocomplywiththerequirementsofAustralianstandardAS/NZS3000electricalinstallations(wir-ingrules),theelectricalwiringrequiredbetweentheindoorandoutdoorunitsmustbeinstalledbyalicencedelectricalcontractor.

JG79A867H02_en.indd 2 2014/06/25 13:38:52

Page 4: FLOOR TYPE AIR CONDITIONERS€¦ · FLOOR TYPE AIR CONDITIONERS MFZ-KJ25VE MFZ-KJ35VE MFZ-KJ50VE MFZ-KJ60VE English InstallatIon Manual For INSTALLER • When installing multi units,

En-3

Wall

Outdoorside

2-2. HolE DRIllInG1)Determinethewallholeposition.2)Drilladia.65mmhole(dia.75mmforKJ50/60).Theoutdoorside

shouldbe5to7mmlowerthantheindoorside.3)Insertwallholesleeve(C).

2-1. FIXInG oF InDooR unIt MountInG BRaCKEt• Findastructuralmaterial(suchasastud)inthewallandfixbracket(7)horizontallywithfixingscrews(8).• Topreventbracket(7)fromvibrating,besuretoinstallthefixingscrewsintheholesindicatedintheillustration.Foraddedsupport,fixingscrewsmay

alsobeinstalledinotherholes.

2. InDooR unIt InstallatIon

FORRIGHTDOWNWARDORLEFTDOWN-WARDPIPING(Thefollowingfigureisaviewofthebottomoftheindoorunitfromabove.)

FORREARORLEFT-REARPIPING(Thefollowingfigureisafrontview oftheindoorunitinstallationlocation.)

FORLEFTPIPING FORRIGHTPIPING

HolE PosItIons

ø65mm(KJ25/35)ø75mm(KJ50/60) 5-7mm

2-3. InDooR unIt PREPaRatIonRemovethefrontpaneloftheindoorunit.1)Pushdownthetabonthebothsidesoftheunittoopenthefrontpanel.2)Pullthefrontpaneltowardyoutoremoveit.3)Removethe2screws.4)Opentherearhorizontalvane.5)Pushthe2locationsonthetopofthepanel,andthenpulltheupperpartofthepaneltowardyou.6)Removethepanelwhileliftingitup(slightly).

Rearhorizontalvane

Panel

PanelPush

Indoorunit

6060

6030

6030

Frontpanel

Frontpanel

Indoorunit

Indoorside

Rearhorizontalvane

JG79A867H02_en.indd 3 2014/06/25 13:38:55

Page 5: FLOOR TYPE AIR CONDITIONERS€¦ · FLOOR TYPE AIR CONDITIONERS MFZ-KJ25VE MFZ-KJ35VE MFZ-KJ50VE MFZ-KJ60VE English InstallatIon Manual For INSTALLER • When installing multi units,

En-4

2-4-3. EMBEDDING THE INDOOR UNIT IN A WALL1.Makeaholeinthewall.2.Usingreinforcementmaterial,adjustthedepth.3.Remove6screwsthatfixthebasetotheunit.Removethebasefrom

theunit.4.Fixtheindoorunitat4pointswiththeincludedwoodscrews(9)and

washers(10).Tightenthescrewssecurely.

4

575

740

70

4

33

3

33 3

705

2-4. INDOOR UNIT INSTALLATION2-4-1. INSTALLING THE INDOOR UNIT ON THE FLOOR1.Placetheindoorunitontheflatfloor.2.Fixtheindoorunitat4pointswiththeincludedwoodscrews(9)and

washers(10).Tightenthescrewssecurely.

2-4-2. MOUNTING THE INDOOR UNIT ON THE WALL1.Hookthetopoftheindoorunitontheindoorunitmountingbracket(7).2.Fixtheindoorunitat4pointswiththeincludedwoodscrews(9)and

washers(10).Tightenthescrewssecurely.

405

137

387

Indoorterminalblock

Indoor/outdoorunit connectingwire(A)

Outdoorterminalblock

Earthwire(green/yellow)

• Makeearthwirealittlelongerthanothers.(Morethan45mm)• Forfutureservicing,giveextralengthtotheconnectingwires.• Donot fold theexcesswire,orcram it intosmallspace.Takecautionnot to

damagethewires.• Besuretoattacheachscrewtoitscorrespondentterminalwhensecuringthe

cordand/orthewiretotheterminalblock.

2-5. ConnECtInG WIREs FoR InDooR unIt1)RemoveVAclamp.2)Passindoor/outdoorunitconnectingwire(A)fromthebackoftheindoorunit

andprocesstheendofthewire.3)Loosen terminal screw,and connect first theearthwire, then indoor/outdoor

unit connectingwire (A) to the terminal block.Be careful not tomakemis-wiring.Fixthewiretotheterminalblocksecurelysothatnopartofitscoreisappeared,andnoexternalforceisconveyedtotheconnectingsectionoftheterminalblock.

4)Firmlytightentheterminalscrewstopreventthemfromloosening.Aftertight-ening,pullthewireslightlytoconfirmthattheydonotmove.

5)Secureindoor/outdoorunitconnectingwire(A)andtheearthwirewiththeVAclamp.Neverfail tohooktheleftclawoftheVAclamp.AttachtheVAclampsecurely.

Terminalblock

Fixingscrew

Indoor/outdoorunitconnectingwire(A)

VAclamp

Leadwire

35mm15mm

2-6. PIPE FoRMInG anD InstallatIonPipe Forming• Routethedrainhosediagonallybelowtheconnectingpipes.• Makesurethatthedrainhoseisnotroutedupwardandthatthereareno

wavesinthehose.• Donotpullthehosewhenapplyingthetape.• Routethepipingsothatitdoesnotprojectpasttherearoftheindoorunit.(Refer

tothefiguretotheright.)Connecting Pipe Installation• Installtheconnectingpipessothatthepipingcanmoveslightlytothefront,

back,left,andright.

Pipingtape

Drainhose

Refrigerantpiping

Pipingbentout-ward

Push

• Besuretoinsulatetheconnectingpipessothattheydonotcontactthepanel.• Becarefulnottocrushtheconnectingpipeswhenbendingthem.

Removethecover.

RIGHTDOWNWARDPIPING OTHERPIPING

Band(5)

Pipecover(4)

Band(5)

Reinforcementmaterial

Unit

Base

JG79A867H02_en.indd 4 2014/06/25 13:38:58

Page 6: FLOOR TYPE AIR CONDITIONERS€¦ · FLOOR TYPE AIR CONDITIONERS MFZ-KJ25VE MFZ-KJ35VE MFZ-KJ50VE MFZ-KJ60VE English InstallatIon Manual For INSTALLER • When installing multi units,

En-5

Donotmakedrainpipingasshownbelow.

Accumulateddrainwater

Air

WavingWaterleakage

Donotraise

Waterleakage

Waterleakage

Tipofdrainhosedippedinwater

Ditch

Atleast50mmgap

Downwardslope

Drainhose

SofthoseI.D.15mm

DrainhoseHardvinylchloridepipeI.D.30mm

Insert securely

Differentdiameterjoint

70cmormore

Fig.1 Fig.2 Fig.3

2-7. DRaIn PIPInG• Iftheextensiondrainhosehastopassthrougharoom,besuretowrapitwithcommerciallysoldinsulation.• Thedrainhoseshouldpointdownwardforeasydrainflow.(Fig.1)• Ifthedrainhoseprovidedwiththeindoorunitistooshort,connectitwithdrainhose(I)thatshouldbeprovidedatyoursite.(Fig.2)• Whenconnectingthedrainhosetothehardvinylchloridepipe,besuretoinsertitsecurelyintothepipe.(Fig.3)

2-8. FRont PanEl InstallatIon1)Opentherearhorizontalvane.2)Attachthepanel.Makesurethatthecatchesareengaged.3)Fixthepanelwithscrews.4)Insertthebottompartofthefrontpanel.5)Push3placesontheupperpartofthefrontpaneltocloseit.

Wrap the felt tape (11) tightlyaround thepipesandhosestartingnearwherethepipesandhoseareroutedfromtheindoorunit.(Theoverlapwidthofthefelttape(11)shouldnotbemorethan1/2ofthetapewidth.)

Felttape(11)

Startwrappingthepipingtape(G)aroundthepipesandhose10mminsidetheindoorunit.

Fastentheendofthefelttape(11)withabandagestopper.

Makesurethatthedrainhoseisnotroutedupward.

FORLEFTORLEFT-REARPIPINGBundletheconnectingpipesanddrainhosetogether,andthenwraptheminfelttape(11).

Cutandusethelowersidepanelsontheleftandrightsidesoftheindoorunitasshownbelow.Smooththecutedgesofthesidepanelssothattheywillnotdamagetheinsulationcoating.• Forleftorrightpiping • Installingflushagainstawallwithmolding

Molding

Cutthelowersidepanelstomatchtheheightofthemolding.

Fig.5

Projection

Makesuretohookthecatch.

Drainhose

Pullthehosetoconfirmitiscon-nectedsecurely.

Fig.4

the Drain hose is removed at installation.• When routing thedrain piping,make sure that thedrain

hose(1)isroutedasshown.(Fig.4)• Insertthedrainhoseallthewaytothebaseofthedrain

pan(endconnection).(Fig.5) Makesurethatthecatchofthedrainhoseissecurelyhookedontotheprojectiononthehosefittingofthedrainpan.

• Afterconnectingthedrainhose,besuretopullthehosetoconfirmthatitisconnectedsecurely.

Frontpanel

Indoorunit

Indoorunit

Panel

Panel

2-9. ConnECtInG an IntERFaCE (option)/ConnECtoR CaBlE (option) to tHE aIR ConDItIonER

Thinpartoftheconnectingcable.Placethispartwherecustomerscannottouchit.Roomair

conditioner Mainbodyofaninterface

ThickpartoftheconnectingcableIndoorcontrolP.C.board

CN105forinterfaceCN104forconnectorcable

• Connectaninterface/connectorcabletotheindoorcontrolP.C.boardofanairconditionerwithaconnectingcable.

• Cuttingorextendingtheconnectingcableoftheinterface/connectorcableresultsindefectsinconnecting.Donotbundletheconnectingcabletogetherwithpowersupplycord,indoor/outdoorconnectingwire,and/orearthwire.Keepasmuchdistanceaspossiblebetweentheconnectingcableandthosewires.

• Thethinpartoftheconnectingcableshouldbestoredandplacedwherecustomerscannottouchit.

Rearhorizontalvane

JG79A867H02_en.indd 5 2014/06/25 13:39:01

Page 7: FLOOR TYPE AIR CONDITIONERS€¦ · FLOOR TYPE AIR CONDITIONERS MFZ-KJ25VE MFZ-KJ35VE MFZ-KJ50VE MFZ-KJ60VE English InstallatIon Manual For INSTALLER • When installing multi units,

En-6

1)Removethepanel.2)OpenthecoveroftheindoorcontrolP.C.board.3)JointheconnectingcabletoCN105and/orCN104ontheindoorcontrolP.C.board.4)Routetheconnectingcablethroughthispointinthefigure.5)Attachthecableclampprovidedwithinterface/connectorcabletothethickpartofthe

connectingcablewithascrew4×16asshowninthefigure.6)ClosethecoveroftheindoorcontrolP.C.board.Becarefulnottocatchthethinpart

oftheconnectingcableinthecover.Reinstallthepanel.

5)

4)

3)CN105 WARNINGFix the connecting cable at the prescribed position securely.Incorrect installation may cause electric shock, fire, and/ or malfunction.

3. outDooR unIt InstallatIon

3-2. FlaRInG WoRK1)Cutthecopperpipecorrectlywithpipecutter.(Fig.1,2)2)Completelyremoveallburrsfromthecutcrosssectionofpipe.(Fig.3)

• Puttheendofthecopperpipetodownwarddirectionasyouremoveburrsinordertoavoidtoletburrsdropinthepiping.

3)Removeflarenutsattachedtoindoorandoutdoorunits,thenputthemonpipehavingcompletedburrremoval.(Notpossibletoputthemonafterflaringwork.)

4)Flaringwork(Fig.4,5).Firmlyholdcopperpipeinthedimensionshowninthetable.SelectAmmfromthetableaccordingtothetoolyouuse.

5)Check• ComparetheflaredworkwithFig.6.• Ifflareisnotedtobedefective,cutofftheflaredsectionanddoflaringworkagain.

3-3. PIPE ConnECtIon• Fastenflarenutwithatorquewrenchasspecifiedinthetable.• Whenfastenedtootight,flarenutmaybreakafteralongperiodandcauserefrigerantleakage.• Besure towrap insulationaround thepiping.Directcontactwith thebarepipingmay result inburnsor

frostbite.Indoor unit connectionConnectbothliquidandgaspipingstoindoorunit.• Applya thincoatof refrigerationoil (J)on theflaredendsof thepipes.Donotapply refrigerationoilon

screwthreads.Excessivetighteningtorquewillresultindamageonthescrew.• Forconnection,firstalignthecenter,thentightenthefirst3to4turnsofflarenut.• Usetighteningtorquetableaboveasaguidelineforindoorunitsideunionjointsection,andtightenusing

twowrenches.Excessivetighteningdamagestheflaresection.outdoor unit connectionConnectpipestostopvalvepipejointoftheoutdoorunitinthesamemannerappliedforindoorunit.• Fortightening,useatorquewrenchorspannerandusethesametighteningtorqueappliedforindoorunit.

3-4. INSULATION AND TAPING1)Coverpipingjointswithpipecover.2)Foroutdoorunitside,surelyinsulateeverypipingincludingvalves.3)Usingpipingtape(G),applytapingstartingfromtheentryofoutdoorunit.

• Stoptheendofpipingtape(G)withtape(withadhesiveagentattached).•Whenpipinghavetobearrangedthroughaboveceiling,closetorwherethetemperatureandhumidityarehigh,windadditionalcommerciallysoldinsulationtopreventcondensation.

Pipediameter(mm)

Nut(mm)

A(mm) TighteningtorqueClutchtype

tool forR410A

Clutchtypetool

forR22

Wingnuttypetool forR22

N•m kgf•cm

ø6.35(1/4”) 17

0to0.5 1.0to1.51.5to2.0

13.7to17.7 140to180ø9.52(3/8”) 22 34.3to41.2 350to420ø12.7(1/2”) 26

2.0to2.549.0to56.4 500to575

- - - -

Copperpipe

Good

TiltedUnevenBurred

Nogood

Fig.1 Fig.2

BurrCopperpipeSparereamer

Pipecutter

Clutchtype

Flaringtool

Fig.4

Fig.3

Smoothallaround

Evenlengthallaround

Insideisshiningwithoutanyscratches.

Flarenut

Die

Fig.5 Fig.6

Copperpipe

Wingnuttype

WARNING

When installing the unit, securely connect the refrigerant pipes before starting the compressor.

3-1. ConnECtInG WIREs FoR outDooR unIt1)Opentheservicepanel.2)Loosenterminalscrew,andconnectindoor/outdoorunitconnectingwire(A)fromthe

indoorunitcorrectlyontheterminalblock.Becarefulnottomakemis-wiring.Fixthewiretotheterminalblocksecurelysothatnopartofitscoreisappeared,andnoex-ternalforceisconveyedtotheconnectingsectionoftheterminalblock.

3)Firmly tighten the terminalscrews toprevent them from loosening.After tightening,pullthewireslightlytoconfirmthattheydonotmove.

4)Connectpowersupplycord(K).5)Fix indoor/outdoorunitconnectingwire(A)andpowersupplycord(K)withthecord

clamp.6)Closetheservicepanelsecurely.

• Makeearthwirealittlelongerthanothers.(Morethan100mm)• Forfutureservicing,giveextralengthtotheconnectingwires.• Besuretoattacheachscrewtoitscorrespondentterminalwhensecuringthecordand/or

thewiretotheterminalblock.

Terminalblock

Cordclamp

Terminalblock

Powersupplycord(K)

15mm35mm

Leadwire

<KJ25,35> <KJ50,60>Indoor/outdoorunitconnectingwire(A)

Power supply cord (K)

Whenmountingtheinterfaceandtheconnectorcable,usethisscrewtofixtheconnectingcable.

3)CN104

JG79A867H02_en.indd 6 2014/06/25 13:39:04

Page 8: FLOOR TYPE AIR CONDITIONERS€¦ · FLOOR TYPE AIR CONDITIONERS MFZ-KJ25VE MFZ-KJ35VE MFZ-KJ50VE MFZ-KJ60VE English InstallatIon Manual For INSTALLER • When installing multi units,

En-7

Whenrelocatingordisposingoftheairconditioner,pumpdownthesystemfollowingtheprocedurebelowsothatnorefrigerantisreleasedintotheatmos-phere.1)Connectthegaugemanifoldvalvetotheserviceportofthestopvalveonthegaspipesideoftheoutdoorunit.2)Fullyclosethestopvalveontheliquidpipesideoftheoutdoorunit.3)Closethestopvalveonthegaspipesideoftheoutdoorunitalmostcompletelysothatitcanbeeasilyclosedfullywhenthepressuregaugeshows0

MPa[Gauge](0kgf/cm2).4)StarttheemergencyCOOLoperation.

TostarttheemergencyoperationinCOOLmode,disconnectthepowersupplyplugand/orturnoffthebreaker.After15seconds,connectthepowersupplyplugand/orturnonthebreaker,andthenpresstheE.O.SWonce.(TheemergencyCOOLoperationcanbeperformedcontinuouslyforupto30minutes.)

5)Fullyclosethestopvalveonthegaspipesideoftheoutdoorunitwhenthepressuregaugeshows0.05to0MPa[Gauge](approx.0.5to0kgf/cm2).6)StoptheemergencyCOOLoperation.

PresstheE.O.SWtwicetostoptheoperation.

5. PuMPInG DoWn

4-4. EXPLANATION TO THE USER• UsingtheOPERATINGINSTRUCTIONS,explaintotheuserhowtousetheairconditioner(howtousetheremotecontroller,howtoremovetheairfil-

ters,howtoremoveorputtheremotecontrollerintheremotecontrollerholder,howtoclean,precautionsforoperation,etc.)• RecommendtheusertoreadtheOPERATINGINSTRUCTIONScarefully.

Caution:• Aftertestrunorremotesignalreceptioncheck,turnofftheunitwiththeE.O.SWortheremotecontrollerbeforeturningoffthepowersupply.Notdo-

ingsowillcausetheunittostartoperationautomaticallywhenpowersupplyisresumed.to the user• Afterinstallingtheunit,makesuretoexplaintheuseraboutautorestartfunction.• Ifautorestartfunctionisunnecessary,itcanbedeactivated.Consulttheservicerepresentativetodeactivatethefunction.Refertotheservicemanual

fordetails.

4-3. AUTO RESTART FUNCTIONThisproductisequippedwithanautorestartfunction.Whenthepowersupplyisstoppedduringoperation,suchasduringblackouts,thefunctionautomati-callystartsoperationintheprevioussettingoncethepowersupplyisresumed.(Refertotheoperatinginstructionsfordetails.)

4-2. TEST RUNMake sure the following is done.•Panelisinstalledcorrectly.•Indoorandoutdoorunitsareinstalledcorrectly,andpowerissupplied.1)PresstheE.O.SWonceforCOOL,andtwiceforHEAToperation.Testrunwillbeperformedfor30minutes.Iftheleftlamp

oftheoperationindicatorblinksevery0.5seconds,inspecttheindoor/outdoorunitconnectingwire(A)formis-wiring.Afterthetestrun,emergencymode(settemperature24ºC)willstart.

2)Tostopoperation,presstheE.O.SWseveraltimesuntilallLEDlampsturnoff.Refertooperatinginstructionsfordetails.Checking the remote (infrared) signal receptionPresstheON/OFFbuttonontheremotecontroller(12)andcheckthatanelectronicsoundisheardfromtheindoorunit.PresstheON/OFFbuttonagaintoturntheairconditioneroff.• Oncethecompressorstops,therestartpreventivedeviceoperatessothecompressorwillnotoperatefor3minutestopro-

tecttheairconditioner.

4. PURGING PROCEDURES, LEAK TEST, AND TEST RUN

Emergencyoperationswitch(E.O.SW)

When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes. the compressor may burst if air etc. get into it.

WARNING

4-1. PURGING PROCEDURES AND LEAK TEST

StopvalveforGAS

Stopvalvecap(Torque19.6to29.4N•m,200 to300kgf•cm)

Vacuumpump(orthevacuumpumpwiththefunctiontopreventthebackflow)

Gaugemanifoldvalve(forR410A)

Compoundpressuregauge(forR410A)–0.101MPa

(–760mmHg)

HandleLow HandleHigh

Adapterforpre-ventingthebackflow

Chargehose(forR410A)

*Close*Open

Hexagonalwrench

Precautionswhenusingthecontrolvalve Whenattachingthecontrolvalvetotheserviceport,valvecoremayde-formorloosenifexcesspressureisapplied.Thismaycausegasleak.

Serviceport

BodyClose

OpenControlvalve

A

Whenattachingthecontrolvalvetotheserviceport,makesurethatthevalvecoreisinclosedposition,andthen tightenpartA.Donot tightenpartAor turnthebodywhenvalvecoreisinopenposition.

Serviceportcap(Torque13.7to17.7N•m,140to180kgf•cm)

*4to5turns

1)Removeserviceportcapofstopvalveon thesideof theoutdoorunitgaspipe.(Thestopvalvesarefullyclosedandcoveredincapsininitialstate.)

2)Connectgaugemanifoldvalveandvacuumpumptoserv-iceportofstopvalveonthegaspipesideof theoutdoorunit.

3)Runthevacuumpump.(Vacuumizeformorethan15min-utes.)

4)Check thevacuumwithgaugemanifoldvalve, thenclosegaugemanifoldvalve,andstopthevacuumpump.

5)Leaveas it is for oneor twominutes.Make surepointergaugemanifoldvalveremainsinthesameposition.Confirmthat pressuregauge shows–0.101MPa [Gauge] (–760mmHg).

6)Removegaugemanifoldvalvequicklyfromserviceportofstopvalve.

7)Afterrefrigerantpipesareconnectedandevacuated, fullyopenall stopvalvesonbothsidesofgaspipeand liquidpipe.Operatingwithout fully opening lowers theperform-anceandthiscausestrouble.

8)Refer to 1-3., and charge theprescribedamount of re-frigerant if needed.Be sure to charge slowlywith liquidrefrigerant.Otherwise,compositionoftherefrigerantinthesystemmaybechangedandaffectperformanceoftheairconditioner.

9)Tightencapofserviceporttoobtaintheinitialstatus.10)Leaktest

StopvalveforLIQUID

Pressuregauge(forR410A)

Chargehose

JG79A867H02_en.indd 7 2014/06/25 13:39:05

Page 9: FLOOR TYPE AIR CONDITIONERS€¦ · FLOOR TYPE AIR CONDITIONERS MFZ-KJ25VE MFZ-KJ35VE MFZ-KJ50VE MFZ-KJ60VE English InstallatIon Manual For INSTALLER • When installing multi units,

JG79A867H02_en.indd 8 2014/06/25 13:39:05

Page 10: FLOOR TYPE AIR CONDITIONERS€¦ · FLOOR TYPE AIR CONDITIONERS MFZ-KJ25VE MFZ-KJ35VE MFZ-KJ50VE MFZ-KJ60VE English InstallatIon Manual For INSTALLER • When installing multi units,

JG79A867H02_en.indd 9 2014/06/25 13:39:05

Page 11: FLOOR TYPE AIR CONDITIONERS€¦ · FLOOR TYPE AIR CONDITIONERS MFZ-KJ25VE MFZ-KJ35VE MFZ-KJ50VE MFZ-KJ60VE English InstallatIon Manual For INSTALLER • When installing multi units,